LB2003_83
VENTILATION SCHEDULEVENTILATION SCHEDULE TERMINAL UNIT SCHEDULE , , , AHU-1 AHU-2 INLET COOLING HEATING COIL ASHRAE STANDARD 62-1999 MULTIPLE SPACE OSA CALCULATION ASHRAE STANDARD 62-1999 MULTIPLE SPACE OSA CALCULATION TAG LOCATION SERVICE 'E NUMBER DIA MAX MIN LAT NOTES(in.) CFM CFM CFM GPM (F) LOCATION FLOOR COOLING UBC 1002 UBC 1202 OUTSIDE AIR MINIMUM OSA LOCATION FLOOR COOLING UBC 1002 UBC 1202 OUTSIDE AIR MINIMUM OSA AREA CFM PEAK DESIGN cfm/person OSA PERCENTAGE AREA CFM PEAK DESIGN cfm erson OSA PERCENTAGE TU-1-101 NEW BOOK 142 VOLUNTEER COORDINATOR 140 VVR 5 180 54 79 0.5 105 0OCCUPANCY OCCUPANCY /p CFM OCCUPANCY OCCUPANCY /p CFM TU-1-102 CHILDREN'S 144 CHILDREN'S 144 VVR 12 1700 510 916 2.5 105 - VOLUNTEER COORDINATOR 140 148 180 2 1 20 16 0.09 NON-FICTION 232 1350 1440 27 14 15 203 0.14 TU-1-103 CHILDREN'S 144 CHILDREN'S 144 VVR 8 560 168 270 0.5 88 - CHILDREN'S 144 1515 1700 35 18 15 266 0.16 LARGE PRINT AREA 235 675 580 7 3 15 51 0.09 TU-1-104 CHILDREN'S 143 CHILDREN'S 145 VVR 14 1800 540 935 2.6 105 - CHILDREN'S 144 675 560 7 3 15 51 0.09 HOUGHTON ROOM 236 1216 1800 48 24 15 360 0.20 TU-1-105 CHILDREN'S PROGRAM 146 YOUTH SERVICE 148 VVR 8 600 180 237 0.5 92 - CHILDREN'S 145 1180 1800 19 10 15 143 0.08 FICTION 237 960 480 10 5 15 72 0.15 TU-1-106 CHILDREN'S PROGRAM 146 CHILDREN'S PROGRAM 146 VVR 10 900 270 365 1.0 105 - YOUTH SERVICE 148 593 600 11 6 15 84 0.14 NON-FICTION 231 3840 2300 38 19 20 384 0.17 TU-1-107 STAFF ROOM 132 STAFF ROOM 132 VVR 7 460 138 212 0.6 105 {gip CHILDREN'S PROGRAM 146 756 900 5 2 15 35 0.04 REFERENCE 205 640 2235 64 32 15 480 0.21 TU-1-108 STAFF ROOM 132 OFFICE 131 VVR 5 200 60 84 0.5 105 0- STAFF ROOM 132 427 460 4 2 20 40 0.09 PERIODICALS 233 960 2260 72 36 20 720 0.32 TU-1-109 TECH SERVICES 130 MEN 136 VVR 10 1020 306 306 0.5 77 - OFFICE 131 200 200 2 1 20 20 0.10 GROUP STUDY 206/207 210 320 6 3 15 48 0.15 TU-1-110 TECH SERVICES 130 TECH SERVICES 130 VVR 12 1300 390 612 1.7 105 Q©© MEN 136 623 1020 3 2 20 34 0.03 YOUNG ADULT 203 320 1100 32 16 15 240 0.22 TU-1-111 COMPACT STORAGE 127 COMPACT STORAGE 127 VVR 8 500 150 391 1.1 105 �3 TECH SERVICES 130 1122 1300 12 6 20 118 0.09 REFERENCE DESK 204 1140 1120 38 19 15 284 0.25 TU-1-112 HALLWAY 120 CIRC. WORK ROOM 119 VVR 10 1250 375 270 0.5 79 - COMPACT STORAGE 127 898 500 5 3 20 52 0.10 OREGON HISTORY 201 1920 1000 29 14 20 288 0.29 TU-1-113 SELF CHECK CHILDREN'S 143 VVR 16 2400 720 884 0.9 73 - CIRC. WORK ROOM 119 1181 1250 15 7 20 148 0.12 REFERENCE DESK 204 450 465 9 5 15 68 0.15 TU-1-114 CIRC. WORKROOM 119 OFFICE 122 VVR 8 600 180 117 0.5 90 01 CHILDREN'S 143 5010 2400 77 39 15 579 0.24 GROUP STUDY 200 225 220 4 2 15 33 0.15 TU-1-115 CIRC. WORKROOM 119 HALL 188 VVR 8 660 198 458 1.3 105 - OFFICE 122 775 600 8 4 20 84 0.14 FICTION 237 960 1480 10 5 15 72 0.05 TU-1-116 CIRC. WORKROOM 119 INTERIOR LOBBY 117 VVR 10 1200 360 360 0.5 77 - HALL 188 885 660 9 4 15 66 0.10 TU-1-117 CIRC. DESK 118 CIRC. DESK 118 VVR 8 600 180 276 0.8 105 - INTERIOR LOBBY 117 2239 1200 22 11 15 168 0.14 BLOCK AIRFLOWS - CFM 16,000 3,302 TU-1-118 LIBRARY ENTRY 116 LIBRARY ENTRY 116 VVR 10 1040 312 474 1.3 105 - CIRC. DESK 118 540 600 5 3 15 41 0.07 TU-1-119 HALL 111 ELEV. MACHINE RM 113 VVR 8 700 210 210 0.5 81 - LIBRARY ENTRY 116 915 1040 9 5 15 69 0.07 SYSTEM OSA CALCULATION TU-1-120 COFFEE 110 COFFEE 110 VVR 6 425 120 120 0.5 90 - ELEV. MACHINE RM 113 150 700 1 1 20 10 0.01TU-1-201 ADMIN 221 CORRIDOR 217 VVR 12 970 291 440 0.7 82 - X = 0.206 X = The uncorrected fraction of outdoor air in the total supply. TU-1-202 ADMIN 221 CONFERENCE 224 VVR 8 900 400 400 1.0 102 4e COFFEE 110 250 400 1 1 20 14 0.04 Z = 0.319 Z = The fraction of outdoor air in the supply of the critical zone. TU-1-203 ADMIN 221 OFFICE 223 VVR 14 350 105 290 0.8 105 - CORRIDOR 217 1100 970 9 5 20 92 0.09 Y (% outside air) = X/(1+ X -Z) 23.2% Y = The corrected fraction of outdoor air in the total supply. TU-1-204 ADMIN 221 OFFICE 222 VVR 7 830 249 249 0.5 81 0 CONFERENCE 224 928 900 40 20 20 400 0.44 ASHRAE STD 62 OSA REQUIRED = 3719 OFFICE 223 285 350 3 2 20 32 0.09 TU-1-205 REF WORKROOM 215 REF WORKROOM 215 VVR 16 1300 390 580 1.6 105 00 Design OSA = 3750 TU-1-206 REF WORKROOM 215 ELEC 211 VVR 16 1000 300 311 0.9 105 - OFFICE 222 182 830 2 1 20 16 0.02 REF WORKROOM 215 1368 1300 21 11 20 212 0.16 TU-1-207 REF WORKROOM 215 TRAINING 209 VVR 16 900 270 505 1.4 105 0 ELEC 211 756 1000 5 3 15 40 0.04 TU-2-121 NEW BOOKS 142 NON-FICTION 232 VVR 7 1440 432 885 2.0 105 - TRAINING 209 627 900 16 8 20 160 0.18 TU-2-122 CHILDREN'S 144 LARGE PRINT AREA 235 VVR 10 580 174 270 0.5 92 - TU-2-123 CHILDREN'S 145 HOUGHTON ROOM 236 VVR 10 1800 540 923 2.1 105 - - TU-2-124 CHILDREN'S PROGRAM 146 FICTION 237 VVR 8 480 144 384 0.5 78 - CLOCK AIRFLOWS CFM 22,000 2,488 TU-2-125 NEW BOOKS AV 141 NON-FICTION 231 VVR 8 2300 690 1536 3.0 99 - SYSTEM OSA CALCULATION TU-2-126 HALLWAY 120 REFERENCE 205 VVR 5 2235 671 671 0.7 81 - TU-2-127 HALLWAY 120 PERIODICALS 233 VVR 12 2260 720 720 0.9 85 - X = 0.136 X = The uncorrected fraction of outdoor air in the total supply. TU-2-128 CIRC. WORKROOM 119 GROUP STUDY 206/207 VVR 10 320 96 189 0.5 105 - Z = 0.444 Z = The fraction of outdoor air in the supply of the critical zone. TU-2-129 CIRC. DESK 118 YOUNG ADULT 203 VVR 10 1100 330 330 0.5 81 - Y (% outside air) = X/(1+ X -Z) 19.6% Y = The corrected fraction of outdoor air in the total supply. TU-2-130 INTERIOR LOBBY 117 REFERENCE DESK 204 VVR 6 1120 336 570 1.3 105 - ASHRAE STD 62 OSA REQUIRED = 4322 TU-2-131 LOBBY ENTRY 116 OREGON HISTORY 201 VVR 10 900 300 768 1.0 88 - Design OSA = 4400 TU-2-132 INTERIOR LOBBY 117 REFERENCE DESK 204 VVR 12 465 140 258 0.6 105 - TU-2-133 LIBRARY ENTRY 116 GROUP STUDY 200 VVR 10 220 66 107 0.5 105 - TU-2-134 LIBRARY ENTRY 116 FICTION 237 VVR 10 1480 444 546 1.3 105 - GENERAL NOTES: 1. ENTERING AIR TEMPERATURE 55'F. 2. ALL HEATING COILS MUST MEET SUMMER CONDITIONS OF 120'F ENTERING WATER TEMP., LEAVING AIR TEMP. OF 75'F AND GPM AS INDICATED. 3. PROVIDE MINIMUM OF 36" CLEARANCE IN FRONT OF CONTROL BOXES. SUMMER WINTER ENTERING WATER TEMPERATURE 120'F ENTERING WATER TEMPERATURE 140T LEAVING AIR TEMPERATURE 75'F LAT AND GPM AS INDICATED NOTES: (jI 3-WAY CONTROL VALVE Q THIS UNIT SERVES A ROOM WITH OPERABLE WINDOW(S). PROVIDE PROXIMITY SWITCH IN ALL OPERABLE WINDOWS IN AREA SERVED BY UNIT. SWITCH TO BE MOUNTED AND CONTROLLED AS SHOWN ON DETAIL 7/M6.2 AND 3/M7.2. UNIT WILL SHUT DOWN WHEN WINDOW IS OPEN. Q OCCUPANCY SENSOR CONTROL. SEE DETAIL 3/M7.1 KEY DD = DUAL DUCT VV = VARIABLE AIR VOLUME TERMINAL UNIT VVR = VARIABLE AIR VOLUME TERMINAL UNIT WITH REHEAT COIL. CVR = CONSTANT AIR VOLUME TERMINAL UNIT WITH REHEAT COIL. FPS = FAN POWERED SERIES BOX. FPP = FAN POWERED PARALLEL BOX TU - X - XXX TERMINAL UNIT NUMBER FLOOR UNIT IS LOCATED ON AIR HANDLER NUMBER TERMINAL UNIT 0 0 O0 LC)N CO CO (!) W X L H N 00 eC,U (n g/W X ›° C gl ill< >- Nr C7 Vi 1 m O CO Date DrawingTitle o 0 Revisions c1/2I/O4 RECORD DRAWINGS 19 May Date 003 N EQUIPMENT SCHEDULE 0 SRG PARTNERSHIP INC 6666 :6 RECORD DRAWING Tigard . Project 6 MECHANICAL 0 brary L' N NOTE: Documents have been corroded os data 808 S.W. 3rd Avenue New Consultant Project No 0)L. supplied by Contractor aid Revision/Change J r`' CO Girder do not necessarily show all Portland, Oregon .� N ARCHITECTURE PLANNING INTERIORS 97204-2426 Construction DocumentsDrawing o .Field exp g/kidder► PAE Consulting Engineers Inc. FAX 503.226.2930 Drawn by No 0i br to crnent o!'nen work Lo E 621 SW Morrison Street,Suite 200 Portland,Oregon 97205 RRK o ° DATE : z Tigard, Oregon Checked by Q, T:503.222.1917 F:503.294.0272 www.srgpartnership.com N G M 0 • 3 c L.., �3 ) °