Plans (17) I
5T
Project: -Untitled1 03/18/2019
Prepared By: 03:35PM
VALIDITY OF PERMIT RECEIVED
THE ACTIVATION OF A L). . , THE ISSUANCE OFA PERMIT
SMOKE DETECTOR SHALL BASED ON CONSTRUCTION
ACTIVATE A VISIBLE AND i DOCUMENTS AND OTHER APR 4 2019
DATA SHALL NOT PREVENT CITY OF TIGARD
AUDIBLE SUPERVISORY THE CODE OFFICIAL FROM
BUILDING DIVISION
SIGNAL AT A CONSTANTLY REQUIRING THE CORRECTION
ATTENDED LOCATION OF ERRCtit. OSSC 105.4
OMSC 606.4.1
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
OFFICE COP"
CITY OF TIGARD
REVIEWED FOR CODE COMPLIANCE
Approvcd:�
OTC: [
Permit#:
Address: 7 y no s imet k Lt,
Suite#:
By: J Date: - 1
•
Packaged Rooftop Builder 1.49p Page 1 of 8
Unit Report For 5T
Project: —Untitled1 03/18/2019
Prepared By: 03:35PM
Unit Parameters Dimensions(ft. in.)&Weight(lb.)***
Unit Moder 48KCEA06A2A5-0A0A0 Unit Length. 6' 2.375"
Unit Size. 06(5 Tons) Unit Width 3' 10.75"
Volts-Phase-Hertz' 230-3-60 Unit Height 3'5.375"
Heating Type. Gas *•* Total Operating Weight 666 lb
Duct Cfg. Vertical Supply/Vertical Return
Medium Heat *** Weights and Dimensions are approximate. Weight does
Single Stage Compressor Models not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes.For exact
dimensions and weights,refer to appropriate product
data catalog.
Lines and Filters
Return Air Filter Type. Throwaway
Return Air Filter Quantity' 4
Return Air Filter Size 16 x 16 x 2
Unit Configuration
Medium Static Option Belt Drive
Al/Cu-Al/Cu
Base Electromechanical Controls
Standard Packaging
Warranty Information
1-Year parts(std.)
5-Year compressor parts(std.)
10-Year heat exchanger-Aluminized(std.)
No optional warranties were selected.
NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.
Ordering Information
Part Number Description Quantity
48KCEA06A2A5-0A0A0 Rooftop Unit 1
Base Unit
Medium Static Option Belt Drive
None
Accessories
CRECOMZR020A02 Standard Low Leak Vertical EconoMi$er IV with solid-state controller 1
Packaged Rooftop Builder 1.49p Page 2 of 8
Certified Drawing for 5T
Project: -'Untitledl 03/18/2019
Prepared By: 03:35PM
NOTES: UNITED P.O.BOY ADDS THIS DOCUMENT[5 THE PROPERTY Df CARRlEI CORPORATION SUBMISSION Of TRUE DRAWINGS OR DOCUMENTS
TECHNOLOGIES sluOusE.XT AXD IS DEE IYFRED UPAS TRE EMPRESS CORDITITH TXAT TRE DOES NOT CONSTITUTE PANT PERFORMANCE OR
CONTENTS 5ILL ROT or DISCLOSED OR USED WITHOUT CARRIER
1. DIMENSIONS ARE IN INCHES DIMENSIONS UNIT J N 11 PHASE) K f3 PHASE) CARRIER 13221 CORPORATION'S WRITTEN CONSENT.
ACCEPTANCE Of CONTRACT.
IN I I ARE IN MILLIMETERS.
48KC 04 33 3/8 ,14077,1; 14 7/8
2.f9 CENTER OF GRAVITY [8411 13771
CONNECTION SIZES
33 3/8 14 7/8 18 5/8
4""05 [8471 13771 [4721 A 1 3/8' [351 DIA FIELD POWER SUPPLY HOLE
3.MON,DIRECTION OF AIR FLOW 41 3/8 14 7/8 18 5/8 0 2' [50] DIA POWER SUPPLY KNOCKOUT
48KC 06 [1051] [3771 [472]
C 1 3/4' [511 DIA GAUGE ACCESS PLUG
D 7/8" I22]DIA FIELD CONTROL WIRING HOLE
33-3/8
[848] E 3/4"-14 NPT CONDENSATE DRAIN
F 1/2"-14 NPT GAS CONNECTION
G 2 1/2' [641 DIA POWER SUPPLY KNOCK-OUT
32-1/4 ECONOMIZER HOOD 16
1818] (OPTIONAL) [4061
THRU-THE-BASE CHART
FILTER ACCESS PANEL4 THESE HOLES REQUIRED FOR USE
• (TOOL•LESS) COMP. 1 CONDENSER I CRBTNPWROOIA01, 003601
• ACCESS COIL
•PANEL +," •• •• THREADED WIRE REO'D HOLE
INR COIL //0\. - E + CONDUIT SIZE USE SIZES(MAX.)
ACCESS PANEL I �� `_ W 1/2' ACC. 7/8"122.21
��i�\ 25-5/8 (2-7/8 ♦ % 1/2' 24Y 7/8"[22.2]
Ar y M 16521
NIAIR _ [2771 RETURN Y r 3/4" 1001,003) POWER 1 1/8' [28.1]
',,i •��-1 W11il ] 44 SLI '', �, AIR ZWW (003)1/2' FPT GAS 1 3/16" [30.0]
111171
� "�-�� (3 ,
. \�\ � I FOR INGSUFORE ONLYE0,8' lFACTORY OPTION,
ANDLE 2.5/8—I \ ��'� - FITTINGS FOR ONLY%,Y, S 2 ARE PROVIDED
BACK TYP E ALT W SELECT EITHER 3/4'OR I/O'
IYP . •W • CONDENSATE - 17-3/4 ` FOR POWER, DEPENDING ON WIRE SIZE
CURBI co DRAIN OPENING [451] 10011 PROVIDES 3//'FPT THRU CURB
WIDTH I .Y IN OPENING 29-3/e •.
SUPPLY 26-1/2 FLANGE 8 FITTING.
18-1/8 I Z AIR [6731 [7/7] SUPPLY
[4591 AIR
161118 1461/4 12-1/4 - •• `I � _
1611] [363] [312] SEE THRU THE 6- 14
BASE CHART W[1571 . i- ,
1 1
�_ f --- 3 3/8
12-1/8 �[85]
25 LUE [307]
[636] [100] HOOD 18-1/2
11 rc
TOP 14701
d-5/8 10-1/2 1-1/4
11181 [2651 (32]
• _
ELECTRICAL .. •
•
DISCONNECT
LCATION 'r
CONDENSER =_ �1/1 CONTROL BOX • INDOOR BLOWER E STD. I I ILTER
COIL =A. ACCESS PANEL ACCESS • CONDENSATE
=G• DRAIN• 25-1/B —..
=G
J _ 6301
OPTIONAL == - im 16-3/4 I RETURN OUTSIDE
I FACTORY —ill- OPTIONAL - „FE
f� I'. [d21] I AIR AIR
INSTALLED �- 19-1/2
FACTORY F4�• „HANDLE 11-3/8 --SUPPLY AIR— Ay'
L�j/
CONVENIENCE r INSTALLED -e
L OUTLET -M.
I [1681
1494] DISCONNECT O O I I =. O O 2891[1558 I O L ry 539]4
3-3/4 HANDLE -8-3/8 —6-5/8 7 6
(951 46-3/4 30-1/8 [2131 11601 [171] [152]
111871 [7641 26-7/8
7/-3/8 [682] BAROMETRIC
[1888] 31-1/4 RELIEF
17931 FLOW
LEFT AIRPLY f RETURN
FRONT AIR
RIGHT
SHEET DATE SUPERCEDES 48KC 04-06 SINGLE ZONE ELECTRICAL REV
1 OF 2 09-16-14 - COOLING WITH GAS HEAT 48KC000Z81
Packaged Rooftop Builder 1.49p Page 3 of 8
Certified Drawing for 5T
Project: -Untitledl 03/18/2019
Prepared By: 03:35PM
OOIE5 9P.Da.ACO,48
STD. UNIT CORNER CORNER CORNER CORNER C.G. HEIGHT C1ACOdNNIDlY PC1OD5ADTCDIEfN0RL1FIINYL'STEE AWEISRD I TIYTBNPOFEE NX CONSENT.
ONSENTR. CONTRACT.
OENOr 9RCCAXgR9R[ID0IEI1NR 1IW0INHONPYTOXIARCATTHTiAwHREIER SIDRDIMfINSNMIOT ANCCCMOENPSTlTAX1NE1NCEETFa DAPNNPSFRqFOl
UNIT WEIGHT WEIGHT(A) WEIGHT(B) WEIGHT(Cl WEIGHT(D)
ONOANCY[IEEONIR
_
LBS. KG. LBS. NG. LBS. KG. LBS. KG. LBS. KG. X Y 2
48KC 04 490 222 120 54 111 50 125 56 135 61 35 3/4 19081 24 3/4[6281 18 7/8[479]
48KC 05 544 246 130 58 126 57 142 6/ 146 66 36 3/4 19331 24 3/4[6281 18 7/8[4791
48KC 08 597 270 141 84 156 70 158 71 142 84 39 1/8 19931 23 1/2[597] 20 1/8[511]
STANDARD UNIT WEIGHT IS WITH LOW GAS HEAT AND WITHOUT PACKAGING.
FOR OTHER OPTIONS AND ACCESSORIES, REFER TO THE PRODUCT DATA CATALOG.
CORNER A CORNER B
0
•
lllll(11111���\� 1:
484848 i
•
CORNER D L CORNER C
X
TOP
•
_ _
- _ •
•
•o �. �. : oov
FRONT
SHEET 081E SNPEACEDIS 48KC 04-06 SINGLE ZONE ELECTRICAL REV
20F2 09-16-14 - COOLING WITH GAS HEAT 48KC000281 _
Packaged Rooftop Builder 1.49p Page 4 of 8
Certified Drawing for 5T
Project: -'Untitledl 03/18/2019
Prepared By: 03:35PM
Service Clearance
y%
y y
* ..0_,..... 0
COS337
LOCATION DIMENSION CONDITION
48-in(1219 mm) •Unit disconnect is mounted on panel
A 18-in(457 mm) •No disconnect,convenience outlet option
•Recommended serviceclearance
12-in(305 mm) •Minimum clearance
42-in(1067 mm) -Surface behind servicer is grounded(e.g.,metal,masonry wall)
8 36-in(914 mm) -Surface behind servicer is electrically non-conductive(e.g.,wood,fiberglass)
Special -Check for sources of flue products within 10-ft.of unit fresh air intake hood
C 36-in(914 mm) •Side condensate drain is used
18-in(457 mm) •Minimum clearance
48-in(1219 mm) •No flue discharge accessory installed,surface is combustible material
42-in(1067 mm) •Surface behind servicer is grounded(e.g.,metal,masonry wall,another unit)
D 36-in(914 mm) •Surface behind servicer is electrically non-conductive(e.g.,wood,fiberglass)
Special •Check for adjacent units or building fresh air intakes within 10-ft.of this unit's
flue outlet
NOTE:Unit not designed to have overhead obstruction.Contact Application Engineering for guidance on any
application planning overhead obstruction or vertical clearances.
cs i,2-2
Packaged Rooftop Builder 1.49p Page 5 of 8
Performance Summary For 5T
Project: —Untitled1 03/18/2019
Prepared By: 03:35PM
Part N um ber:48KCEA06A2A5-0A0A0
ARI SEER. 14.10
Base Unit Dimensions
Unit Length. 74.4 in
Unit Width 46.8 in
Unit Height 41.4 in
Operating Weight
Base Unit Weight 597 lb
Medium Heat 9 lb
Medium Static Option Belt Drive. 10 lb
Accessories
Standard Low Leak Vertical EconoMi$er IV with solid-state controller 50 lb
Total Operating Weight 666 lb
Unit
Unit Voltage-Phase-Hertz. 230-3-60
Air Discharge. Vertical
Fan Drive Type. Belt
Actual Airflow. 2000 CFM
Site Altitude. 0 ft
Cooling Performance
Condenser Entering Air DB. 95.0 F
Evaporator Entering Air DB. 80.0 F
Evaporator Entering Air WB. 67.0 F
Entering Air Enthalpy 31.44 BTU/lb
Evaporator Leaving Air DB. 58.6 F
Evaporator Leaving Air WB. 57.3 F
Evaporator Leaving Air Enthalpy 24.57 BTU/lb
Gross Cooling Capacity 61.84 MBH
Gross Sensible Capacity. 46.23 MBH
Compressor Power Input 5.19 kW
Coil Bypass Factor 0.058
Heating Performance
Heating Airflow. 2000 CFM
Entering Air Temp' 70.0 F
Leaving Air Temp. 113.1 F
Gas Heating Input Capacity ____ 115.0 MBH
Gas Heating Output Capacity 93.0 MBH
Temperature Rise 43.1 F
Thermal Efficiency(%) 81.0
Supply Fan
External Static Pressure. . 0.50 in wg
Options/Accessories Static Pressure
Economizer 0.12 in wg
Total Application Static(ESP + Unit Opts/Acc.). 0.62 in wg
Fan RPM- 1248
Fan Power 1.22 BHP
NOTE. Selected IFM RPM Range: 1035-1466
Electrical Data
Voltage Range. 187-253
Compressor#1 RLA. 15.9
Compressor#1 LRA. 110
Outdoor Fan Motor Qty 1
Packaged Rooftop Builder 1.49p Page 6 of 8
}
Performance Summary For 5T
Project: -Untitled1 03/18/2019
Prepared By: 03:35PM
Outdoor Fan FLA(ea). 1.4
Indoor Fan Motor Type. MED
Indoor Fan Motor FLA' 8.3
Combustion Fan Motor FLA(ea). 0.48
Power Supply MCA. 30
Power Supply MOCP(Fuse or HACR). 45
Disconnect Size FLA. 29
Disconnect Size LRA• 185
Electrical Convenience Outlet' None
Control Panel SCCR:5kA RMS at Rated Symmetrical Voltage
Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 87.5 87.2 87.5
125 Hz 82.7 79.5 82.5
250 Hz 75.5 66.6 76.1
500 Hz 71.2 63.9 73.6
1000 Hz 67.8 63.2 71.3
2000 Hz 62.1 57.3 67.1
4000 Hz 63.9 53.2 64.1
8000 Hz 59.5 45.7 60.0
A-Weighted 74.6 69.2 77.0
Advanced Acoustics
tik
E 0
161
r
N.w
Advanced Accoustics Parameters
1. Unit height above ground. 30.0 ft
2. Horizontal distance from unit to receiver 50.0 ft
3. Receiver height above ground. 5.7 ft
4. Height of obstruction. 0.0 ft
5. Horizontal distance from obstruction to receiver 0.0 ft
6. Horizontal distance from unit to obstruction. 0.0 ft
Detailed Acoustics Information
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall
A 87.5 82.5 76.1 73.6 71.3 67.1 64.1 60.0 89.2 Lw
B 61.3 66.4 67.5 70.4 71.3 68.3 65.1 58.9 76.7 LwA
C 55.1 50.1 43.7 41.2 38.9 34.7 31.7 27.6 56.8 Lp
D 28.9 34.0 35.1 38.0 38.9 35.9 32.7 26.5 44.3 LpA
Packaged Rooftop Builder 1.49p Page 7 of 8
h
Performance Summary For 5T
Project: —Untitledl 03/18/2019
Prepared By: 03:35PM
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA
C Sound Pressure Levels at Specific Distance from Unit, Lp
D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.
Fan Curve
zo 3
1900RPM
,, 2100RPM
18
1B '
1�
6 1.4 \ .segHPS
\ \ `, ,
12 \
L —
9
W
i10 �'.
2
d
U og
i6 _ \ \
(f) 7t](FiPM
3.00=.P
\ \111111=16k 200
5JCRPM1 '11PBHP
— 1 100
07581-P
02
00 —� . 1 i 1A f ` 4. -I 1 , 1 1
00 03 06 09 12 15 18 21 24 21 33 33
Airflow(CFM-thousands)
RPM=1248 BHP=1.22 MaximumRPM=2100 MaximumBHP=2.90
Note:Pleasecontactapplicationengineeringforselectionsoutsidetheshadedregion.
SC-System Curve RP-RatedPoint
Packaged Rooftop Builder 1.49p Page 8 of 8