Report (7) ok°kq RECEIVED
1` -'4 MAR 27 2019
CITY OF TIGARD
BUILDING DIVISION
Portland General Electric Company
E
01/31/19 G/
CONTACT: KEY WAY CORP
PHONE: 503-560-2553
CUSTOMER NAME: 72ND AVENUE PROPERTY
ADDRESS: 11720 SW 72ND AVE, TIGARD
SDPM/ENGR: STEVE HURSI WR: M2372397
PHONE: 503-672-5409
3-PHASE SECONDARY LINE-LINE FAULT CURRENT (RMS)
TRANSFORMER DATA PAD MOUNT? YES
XFMR Impedance (%): 5.32 % 3-PH SUBMERSI YES
TRANSFORMER SIZE: 750 KVA XFMR? NO
Secondary VOLTAGE(L to L): 208 v WYE OH BANK? NO
VAULT--> VAULT ( or Pole --> Pole) SECONDARY
Secondary Wire LENGTH: 0 Feet WIRE SIZE
Number of SECONDARY RUNS: 1 Run(s)of:
Secondary WIRE Resistance R: 0.0180 Ohms/1000'
Secondary WIRE Reactance X: 0.0258 Ohms/1000'
VAULT ( or Pole) --> PANEL SECONDARY (or Svc Drop)
Service Wire LENGTH: 85 Feet WIRE SIZE
Number of Service RUNS: 4 Run(s)of: 350 QX UG M
Service WIRE Resistance R: 0.0600 Ohms/1000'
Service WIRE Reactance X: 0.0330 Ohms/1000'
MAXIMUM FAULT CURRENT*: 26,545 Amps
*Maximum fault current based upon transformers/conductors sized for 100% of electrical panel rating.
1000
To Print This Page: "Ctrl M"and choose"Print 3-Phase Data'
RECEIVED
MAR 272019
)F .1 IGARO
Portland General Electric Company DIVISION
�1N,
E
01/31/19 G
CONTACT: KEY WAY CORP
PHONE: 503-560-2553
CUSTOMER NAME: 72ND AVENUE PROPERTY
ADDRESS: 11720 SW 72ND AVE, TIGARD
SDPM/ENGR: STEVE HUE. WR: M2372397
PHONE: 503-672-540::
3-PHASE SECONDARY LINE-LINE FAULT CURRENT (RMS)
TRANSFORMER DATA PAD MOUNT? YES
XFMR Impedance (%): 5.32 % 3-PH SUBMERSI YES
TRANSFORMER SIZE: 750 KVA XFMR? NO
Secondary VOLTAGE (L to L): 208 v WYE OH BANK? NO
VAULT--> VAULT ( or Pole --> Pole) SECONDARY
Secondary Wire LENGTH: 0 Feet WIRE SIZE
Number of SECONDARY RUNS: 1 Run(s) of:
Secondary WIRE Resistance R: 0.0180 Ohms/1000'
Secondary WIRE Reactance X: 0.0258 Ohms/1000'
VAULT ( or Pole) --> PANEL SECONDARY (or Svc Drop)
Service Wire LENGTH: 75 Feet WIRE SIZE
Number of Service RUNS: 5 Run(s) of: 350 QX UG M
Service WIRE Resistance R: 0.0600 Ohms/1000'
Service WIRE Reactance X: 0.0330 Ohms/1000'
MAXIMUM FAULT CURRENT*: 29,319 Amps
11.1aximuni fault current based upon transformers/conductors sized for 100% of electrical panel rating.
1200
To Print This Page: "Ctrl M"and choose"Print 3-Phase Data'