Loading...
Report (58) fi7,520/7-WO ? 5s5--A.2_ 54) 6,)‘4.cil Ft IVED MAR 82017 miri)!:TIGARD W VAT FIRE PROTECTION, INC. 9095 S.W. Burnham Tigard, OR 97223 PINK VS WASH SQ 9585 SW WASHINGTON SQ RD #H07 TIGARD, OR 97223 • FIRE PROTECTION EQUIPMENT SUBMITTAL _ tqco Worldwide Contacts www.tyco-fire.com Series RFII — 5.6 K-factor "Royal Flush II" Concealed Pendent Sprinklers Quick & Standard Response, Standard Coverage General stallation or finish. The tip of the Pro- tective Cap can be used to mark the Description center of the ceiling hole into plaster p board or ceiling tiles by gently push- The TYCO Series RFII 5.6 K-factor, ing the ceiling product against the Pro "Royal Flush II" Concealed Pendent tective Cap. When ceiling installation _� ,, Sprinklers Quick Response (3-mm is complete, the Protective Cap is re bulb) and Standard Response (5-mm moved and the Cover Plate/Retainer bulb), are decorative sprinklers featur- Assembly is installed. ti.+.:. ing a flat cover plate designed to con- As an option,the Series RFII Standard ceal the sprinkler.These sprinklers are Response(5-mm bulb)"Royal Flush II" optimal for architecturally sensitive ar- Concealed Pendent Sprinklers can be eas such as hotel lobbies,office build- fitted with a silicone Air and Dust Seal. ings,churches, and restaurants. (Refer to Figure 5.) The Air and Dust • TY3531 (3-mm Bulb) is UL Listed, Seal is intended for sensitive areas CUL Listed, VdS Approved (Certif Each sprinkler includes a Cover Plate/ icate No. G4090007), and NYC Ap- Retainer Assembly and a Sprinkler/ where it is desirable to prevent air and proved (MEA 353-01-E) as Quick Support Cup Assembly. The separa- dust from the area above the ceiling to Response. ble, two-piece assembly design pro- pass through the cover plate. • TY3531 (3-mmis FM and vides the following benefits: Bulb) NOTICE LPCB Approved (Ref. No. 094a/10) • Allows installation of the sprinklers The Series RFII Concealed Pendent Approved as Standard Response. and pressure testing of the fire pro- Sprinklers described herein must be Factory Mutual and LPCB do not tection system prior to installation installed and maintained in compli approve any concealed sprinklers of a suspended ceiling or applica- ance with this document and with the for quick response. tion of the finish coating to a fixed applicable standards of the National ceiling. PP TY3551 (5-mm Bulb) is UL Listed, Fire Protection Association, in addi- C-UL Listed, FM Approved, LPCB • Permits the removal of suspended tion to the standards of any authori- Approved (Ref. No. 094a/9), and ceiling panels for access to building ties having jurisdiction.Failure to do so NYC Approved (MEA 353-01-E) as service equipment without having may impair the performance of these Standard Response. to first shut down the fire protection devices. system and remove sprinklers. Approvals for Air and Dust Seal The owner is responsible for maintain UL and C-UL Listed for use with the • Provides for 1/2 inch (12,7 mm) of ing their fire protection system and de RFII Standard Response Concealed vertical adjustment to allow a mea- vices in proper operating condition. TY3551 sure of flexibility in determining the The installing contractor or sprinkler Sprinkler( ). length of fixed piping to cut for the manufacturer should be contacted Maximum Working Pressure sprinkler drops. with any questions. Maximum 250 psi (17,3 bar) by UL, The Series RFII Sprinklers are shipped C-UL,and NYC with a Disposable Protective Cap.The Sprinkler Protective Cap is temporarily removed p Maximum 175 psi (12,1 bar) by FM, during installation and replaced to help Identification VdS, and LPCB protect the sprinkler during ceiling in- Temperature Rating Number (SIN) 155°F(68°C)Sprinkler with IMPORTANT TY3531 — 3 mm bulb 139°F(59°C) Plate Always refer to Technical Data Sheet TFP700 for the "INSTALLER TY3551 — 5 mm bulb 200°F(93°C)Sprinkler with WARNING" that provides cautions 165°F(74°C) Plate with respect to handling and instal- Technical Discharge Coefficient lation of sprinkler systems and com K=5.6 GPM/psili2(80,6 LPM/bars 2) ponents. Improper handling and in- Data stallation can permanently damage Adjustment a sprinkler system or its components Sprinkler Approvals 1/2 inch(12,7 mm) and cause the sprinkler to fail to Approvals apply only to the service operate in a fire situation or cause it conditions indicated in the Design Cri- Finishes to operate prematurely. teria section. See the Ordering Procedure section. Page 1 of 4 MARCH 2013 TFP181 TFP181 Page 2 of 4 Physical Characteristics 1/2" NPT / r SEALING Frame Bronze ASSEMBLY Support Cup Chrome Plated Steel Guide Pins Stainless Steel FRAME �j� , Deflector Bronze ' ` ' ' CAP Compression Screw Brass / Bulb Glass '• Cap Bronze or Copper SUPPORT Sealing Assembly Beryllium CUP WITH BULB Nickel w/TEFLON ROLL FORMED Cover Plate Brass THREADS Retainer Brass Ejection Spring Stainless Steel 1 COMPRESSION Design SCREW GUIDE Criteria PINS(2) The TYCO Series RFII 5.6 K-factor, ' DEFLECTOR "Royal Flush II" Concealed Pendent I (DROPPED Sprinklers are intended for fire protec- DEFLECTOR _ I i L_�'' POSITION) tion systems designed in accordance L. ti r with the standard installation rules rec- ognized by the applicable Listing or 1 SPRINKLER/SUPPORT CUP Approval agency;for example, UL List- ASSEMBLY ing is based on NFPA 13 and VdS Ap- I I proval is based on the CEA 4001. THREAD INTO I I RETAINER For more information on LPCB and CUP SUPPORT ) WITH THREAD VdS Approvals, contact Tyco Fire Pro- MOUNTINGTIL . . DIMPLES PP Y MOUNTING J tection Products at the following office: SURFACE IS EJECTION Enschede, Netherlands FLUSH WITH SPRING Telephone:31-53-428-4444 CEILING Fax:31-53-428-3377 The Series RFII Concealed Pendent ��� L `---- .a Sprinklers are only listed and approved with the Series RFII Concealed Cover Plates having a factory applied finish. SOLDER COVER TABS(3) COVER PLATE/RETAINER PLATE NOTICE ASSEMBLY Do not use the Series RFII in applica- FIGURE 1 tions where the air pressure above MODEL RFII CONCEALED SPRINKLER the ceiling is greater than that be- ASSEMBLY low. Down drafts through the Sprin- kler/Support Cup Assembly can delay Installation Do not attempt to compensate for in- sprinkler operation in a fire situation, sufficient adjustment in the Sprinkler The TYCO Series RFII 5.6 K-factor, by under-or over-tightening the Sprin- Oeration "Royal Flush II" Concealed Pendent kler/Support Cup Assembly. Re-adjust pSprinklers must be installed in accor- the position of the sprinkler fitting to When exposed to heat from a fire, the dance with this section. suit. Cover Plate, normally soldered to the General Instructions Step 1. Install the sprinkler only in the the center-line t expolseRetaner theh Sprat tree p kler/Support oints, falls aCup Do not install any bulb-type sprinkler if of thetonspriinklernperpendicular to the Assembl the bulb is cracked or there is a loss mounting surface. y' of liquid from the bulb. With the sprin The Deflector — supported by the kler held horizontally, a small air bub Step 2.Remove the Protective Cap. Guide Pins — then drops down to its ble should be present. The diameter Step 3. With pipe thread sealant ap- operational position. of the air bubble is approximately 1/16 plied to the pipe threads, hand-tighten inch (1,6 mm)for the 155°F (68°C)and the sprinkler into the sprinkler fitting. The glass bulb contains a fluid that ex 3/32 inch(2,4 mm)for the 200°F(93°C) Step 4. Wrench-tighten the sprinkler pands when exposed to heat. When temperature ratings. using only the RFII Sprinkler Wrench. the rated temperature is reached, the (Refer to Figure 3.) Apply the RFII fluid expands sufficiently to shatter the A leak-tight 1/2 inch NPT sprinkler joint Sprinkler Wrench to the Sprinkler as glass bulb,activating the sprinkler and should be obtained by applying a min- shown in Figure 3. allowing water to flow. imum to maximum torque of 7 to 14 Step 5. Replace the Protective Cap ft.-lbs. (9,5 to 19,0 Nm). Higher levels by pushing it upwards until it bottoms of torque can distort the sprinkler In- out against the Support Cup. (Refer let with consequent leakage or impair- to Figure 4.)The Protective Cap helps ment of the sprinkler. prevent damage to the Deflector and TFP181 Page 3 of 4 FACE OF CLEARANCE HOLE CLEARANCE SPRINKLER . DIAMETER HOLE FITTING DIMENSION C J SPRINKLER ibt_ SUPPORT CUP ASSEMBLY 1/2"(12,7 mm) I THREADED 1�1 AI. ilrpi ] ADJUSTMENT I W D FACE ‘ ISI_-. OF CEILING, — 7- /- RETAINING RING ! ..�/ ,,..e MOUNTING 7 A � SURFACE A \ j IMIIII FIGURE 4 , _'_ DISPOSABLE PROTECTIVE CAP :; i i Arms during ceiling installation and/or I ---,__,----T----L r=� finish.You can also use the Protective - Cap to locate the center of the clear- 3/16"to 11/16" MANUFACTURER DEFLECTOR COVER PLATE ance hole by gently pushing the ceiling (4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER material up against the center point of REFERENCE 3/32"(2,4 mm) POSITION ASSEMBLY the Protective Cap. COVER PLATE COVER PLATE NOTICE -PROFILE DEPTH DIAMETER As long as the Protective Cap remains DIMENSION B DIMENSION A in place, the system is considered A:3-1/4 inches(82,6 mm) C:2-3/8 to 2-5/8 inches(60,3 to 66,7 mm) "Out of Service". Step 6.After the ceiling has been com- B:3/16 inches(4,8 mm) D:1-3/4 to 2-1/4 inches(44,5 to 57,2 mm) pleted with the 2-1/2 inch(63,5 mm)di- ameter clearance hole and in prepa- FIGURE2 ration for installing the Cover Plate/ SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS Retainer Assembly, remove and dis- card the Protective Cap.Verify that the Deflector moves up and down freely. If the Sprinkler is damaged and the Ij=l, FRAME IIf�l__ __ Deflector does not move up and down I ARM % __ ��� freely, replace the entire Sprinkler. Do not attempt to modify or repair a I damaged sprinkler. SUPPORT _ ' _ Step 7. When installing an Air and - CUP - Dust Seal, refer to Figure 5; otherwise, I proceed to Step 8. To attach the Air SIM .' and Dust Seal, verify the angle of the 1.11I � ■" outside edge of the seal is oriented ac- cording toFigure 5. Start the edge of ------- the Retainer in the grooved slot of the 7/8"(23 mm) 0 Air and Dust Seal and continue around SQUARE the retainer until the entire Air and Dust Seal is engaged. ALIGN �� `� Step 8. Screw on the Cover Plate/ / Retainer Assembly until the Retainer ARROWS WITH FRAME ARMS / \1_ (shown in Figure 2)or the Air and Dust Seal (shown in Figure 5) contacts the -1 �1 ceiling. Do not continue to screw` on -i the Cover Plate/Retainer Assembly ACCEPTS \� r-'. so that it lifts a ceiling panel out of its 0 1/2"SOCKET \\ / normal position. If you cannot engage DRIVE the Cover Plate/Retainer Assembly FIGURE3 with the Support Cup or you cannot RFII SPRINKLER WRENCH engage the Cover Plate/Retainer As- sembly sufficiently to contact the ceil- ing, you must reposition the Sprinkler Fitting. TFP181 Page 4 of 4 Care and SUPPORT =- SPRINKLER FACE OF ORIENT CUP CEILING -�SEAL Maintenance`_ _ / BEVEL AS WN The TYCO Series RFII 5.6 K-fac- I COVER ;) 1 PLATE j� tor, "Royal Flush II" Concealed Pen- dent Sprinklers must be maintained 1` ASSEMBLY • and serviced in accordance with this ), ,�' section. �` R_E _Before closing a fire protection system � - •,rf, === main control valve for maintenancek� IAIR work on the fire protection system that /=l •'•" ����� ��/ AND DUST 1 1- SEAL it controls, obtain permission to shut m=_----_----• �� LIP OF COVER down the affected fire protection sys- RETAINER PLATE tern from the proper authorities and FIGURE 5 notify all personnel who may be affect- OPTIONAL AIR AND DUST SEAL FOR SERIES RFII(TY3551) ed by this action. Absence of the Cover Plate/Retainer If you must remove a sprinkler, do not Ordering Assembly can delay sprinkler opera- reinstall it or a replacement without re- tion in a fire situation. installing the Cover Plate/Retainer As- Procedure sembly. If a Cover Plate/Retainer As- �I When properly installed, there is a y p p ysembly becomes dislodged during nominal 3/32 inch (2,4 mm)air gap be- service,replace it immediately. Contact your local distributor for tween the lip of the Cover Plate and the availability. When placing an order, ceiling, as shown in Figure 2. The owner is responsible for the in- indicate the full product name. This air gap is necessary for proper spection, testing, and maintenance of Sprinkler/Support Cup Assembly operation of the sprinkler. If the ceil- their fire protection system and devic- op requires narem printing after. sprinkler es in compliance with this document, Specify: Series RFII (specify SIN), inginstallation, ensure the new paint as well as with the applicable stan- K=5.6, "Royal Flush II" Pendent Sarin- installation, not seal offany thatothe air gap. dards of the National Fire Protection klers (specify) temperature rating and Association(e.g., NFPA 25), in addition (specify)finish, P/N (specify). Do not pull the Cover Plate relative to to the standards of any other authori- the Enclosure.Separation may result. ties having jurisdiction. Contact the in- 155°F(66°C) 200°F(93°C) Sprinklers which are found to be leak- stalling contractor or sprinkler manu- TY3531 51-792-1-155 51-792-1-200 pfacturer regarding any questions. TY3551 51-790-1-155 51-790-1-200 ing or exhibiting visible signs of corro- sion must be replaced. Automatic sprinkler systems should be Separately Ordered Cover Plate/ inspected,tested,and maintained by a Retainer Assembly: Automatic sprinklers must never be qualified Inspection Service in accor- painted, plated, coated, or other- dance with local requirements and/or Specify: (temperature rating from be- wise altered after leaving the factory. national code. low) Series RFII Concealed Cover Modified sprinklers must be replaced. Plate with(finish), P/N (specify). Sprinklers that have been exposed to 139°F(59°C)(a) 165°F(74°C)(b) corrosive products of combustion, but Grey White have not operated,should be replaced (RAL9002) 56-792-0-135 56-792-0-165 if they cannot be completely cleaned Brass 56-792-1-135 56-792-1-165 by wiping the sprinkler with a cloth or Pure White(c) by brushing it with a soft bristle brush. (RAL9010) 56-792-3-135 56-792-3-165 hite Care must be exercised to avoid dam- Signal(RAL9003) 56-792-4-135 56-792-4-165 age to the sprinklers - before, during, Jet Black and after installation. Sprinklers dam- (RAL9005) 56-792-6-135 59-792-6-165 aged by dropping, striking, wrench Brushed twist/slippage, or the like, must be re- Chrome 56-792-8-135 56-792-8-165 placed.Also,replace any sprinkler that Chrome 56-792-9-135 56-792-9-165 has a cracked bulb or that has lost custom 56-792-X-135 56-792-X-165 liquid from its bulb. (Ref. Installation (a) For use with 155°F(68°C)sprinklers. Section.) (b) For use with 200°F(93°C)sprinklers. Exercise care to avoid damage to (c) Eastern Hemisphere sales only. sprinklers before, during, and after in- Sprinkler Wrench stallation.Replace sprinklers damaged Specify: RFII Sprinkler Wrench, by dropping, striking, wrench twisting, P/N 56-000-1-075. wrench slipping, or the like. Also, re- place any sprinkler that has a cracked Air and Dust Seal bulb or that has lost liquid from its Specify:Air and Dust Seal, bulb.(Refer to the Installation section.) P/N 56-908-1-001. GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446 Telephone+1-215-362-0700 Copyright©2013 Tyco Fire Products,LP. All rights reserved. •¢-SCO TEFLON is trademark of The DuPont Corporation. - tLjCO Worldwide www t co-fire.com Fire Protection Contacts y Products Series TY-FRB, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General NOTICE The TYCO Series TY-FRB Sprinklers - . ' I' . ,. Description described herein must be installed and maintained in compliance with this doc The TYCO Series TY-FRB,5.6 K-factor, ument, as well as with the applicable V is . _ Upright(TY313) and Pendent(TY323) standards of the National Fire Protec- z Sprinklers described in this data sheet tion Association,in addition to the Stan- 4 , ,, are quick response,standard coverage, dards of any other authorities having decorative 3 mm glass bulb-type spray jurisdiction.Failure to do so may impair sprinklers designed for use in light or the performance of these devices. ordinary hazard,commercial occupan- cies such as banks, hotels,and shop- The owner is responsible for maintain- ping malls. ing their fire protection system and -"----- devices in proper operating condition. The recessed version of the Series TY- The installing contractor or sprinkler FRB Pendent Sprinkler,where applica- manufacturer should be contacted with ble, is intended for use in areas with a any questions. finished ceiling.This recessed pendent sprinkler uses one of the following: Sprinkler • A two-piece Style 15 Recessed p Escutcheon with recessed adjust- Identification .�. ment up to 5/8 inch (15,9 mm)from t:. the flush pendent position. Number (SIN) • A two-piece Style 20 Recessed - Escutcheon with recessed adjust- TY313 Upright 5.6K, 1/2""NPT ' ,. ment up to 1/2 inch (12,7 mm) from TY323 Pendent 5.6K, 1/2"NPT _ y' w the flush pendent position. -, The adjustment provided by the Technical Temperature Rating Escutcheon reduces the P accuracy to which the fixed pipe drops Data 135°F(57°C) to the sprinklers must be cut. 155°F(68°C) Intermediate level versions of Series Approvals 175°F(79°C) P UL and C-UL Listed 200°F(93°C) TY FRB Sprinklers are described in FM, LPCB,and VdS Approved 286°F(141°C) Technical Data Sheet TFP357. Sprin- pP kler guards and shields are described CE Certified Finishes in Technical Data Sheet TFP780. Sprinklers with Polyester Finish are UL Sprinkler: Refer to Table A and C-UL Listed as Corrosion-Resis- Recessed Escutcheon:White Coated, tant Sprinklers. Chrome Plated,or Brass Plated Maximum Working Pressure Physical Characteristics 175 psi(12.1 bar) Frame Bronze 250 psi(17.2 bar)* Button Brass/Copper The maximum working pressure of 250 psi Sealing Assembly Stainless IMPORTANT (17.2 bar)only applies to the listing by Un- Steel w/TEFLON Always refer to Technical Data derwriters Laboratories,Inc.(UL). Bulb Glass Sheet TFP700 for the "INSTALLER Discharge Coefficient Compression Screw Bronze WARNING"that provides cautions K=5.6 GPM/psi1t2(80,6 LPM/bar112) Deflector Bronze with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently dam- ` age a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 FEBRUARY 2014 TFP172 TFP172 Page 2 of 4 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON 6* .erri PZ t --- / iNN 5 o=; 7/16" \ -----Y (11,1 mm) gib t '■F 4 I NOMINAL 2" �� /1 MAKE-IN (50,8 mm) I �-- 2 rile 2" SIJ (V 1-3/8" � � �, (50,8 mm) (34,9 mm) ---3 tWRENCH 1 a / I FLATS 1/2"NPT** DEFLECTOR* 2-7/8"(73,0 mm)DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE L, Operation Installation WRENCH RECESS The glass bulb contains a fluid which The TYCO Series TY-FRB,5.6 K-factor, expands when exposed to heat.When Upright(TY313) and Pendent(TY323) (USE ONLY the rated temperature is reached, the Sprinklers must be installed in accor- , e,/...l. END"A") fluid expands sufficiently to shatter the dance with this section. ^�./ glass bulb, allowing the sprinkler to activate and water to flow. General Instructions FIGURE 2 Do not install any bulb-type sprinkler if W-TYPE 6 the bulb is cracked or there is a loss SPRINKLER WRENCH Design of liquid from the bulb.With the sprin- kler held horizontally, a small air WRENCH bub- Criteria ble should be present. The diameter of the air bubble is approximately 1/16 RECESS The TYCO Series TY-FRB,5.6 K-factor, inch (1,6 mm)for the 135°F(57°C)and Upright(TY313)and Pendent(TY323) 3/32 inch(2,4 mm)for the 286°F(141°C) Sprinklers are intended for fire protec- temperature ratings. /r. tion systems designed in accordance with the standard installation rules rec- ognized by the applicable Listing or should be obtained by applying a min Approval agency(such as, UL Listing imum to maximum torque of 7 to 14 is based on the requirements of NFPA ft. lbs. (9,5 to 19,0 Nm). Higher levels 44r, 13, and FM Approval is based on the of torque can distort the sprinkler Inlet PUSH WRENCH requirements of FM's Loss Prevention with consequent leakage or impairment Data Sheets).Only the Style 15 or Style of the sprinkler. INTO ENSURE 20 Recessed Escutcheon is to be used Do not attempt to compensate for ENGAGEMENT for recessed pendent installations. insufficient adjustment in the Escutch- WITH SPRINKLER WRENCHING AREA eon Plate by under-or over-tightening FIGURE 3 the sprinkler. Re-adjust the position of W-TYPE 7 RECESSED the sprinkler fitting to suit. SPRINKLER WRENCH Upright and Pendent Sprinklers The Series TY-FRB Upright and Pen- dent Sprinklers must be installed in accordance with the following instructions. Step 1.Install Pendent sprinklers in the pendent position. Install upright sprin- klers in the upright position. Step 2. With pipe-thread sealant applied to the pipe threads, hand- _ tighten the sprinkler into the sprinkler fitting. TFP172 Page 3 of 4 Step 3. Tighten the sprinkler into the 2-7/8" DIA. sprinkler fitting using only the W-Type (73,0 mm) 6 Sprinkler Wrench(Figure 2).With ref- erence to Figure 1,apply the W-Type 6 2-1/4" DIA. Sprinkler Wrench to the wrench flats. FACE OF (57,2 mm) — Torque sprinklers 7 to 14 ft.-lbs. (9,5 to SPRINKLER 19,0 Nm). FITTING 5/8"(15,9 mm) Recessed Pendent Sprinklers ir , =, ; FLUSH The Series TY-FRB Recessed Pendent 3/8±5/16" I Sprinklers must be installed in accor- (935/8±±-759/1m6 95±79 mm) r '% % } dance with the following instructions. } I �� 1 Step A.After installing the Style 15 or .�–� 1/8" ] I Style 20 Mounting Plate over the sprin- MOUNTING (3,2 mm) kler threads, and with SURFACE pipe-thread I sealant applied to the pipe threads, CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) hand-tighten the sprinkler into the TY-FRB PLATE sprinkler fitting. 4 3/4"(19,1 mm) Step B.Tighten the sprinkler into the FI SERIES TY-FRB RECESSED PENDDENTENT SPRINKLER ASSEMBLY(TY323) sprinkler fitting using only the W-Type WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 7 Recessed Sprinkler Wrench (Figure RECESSED ESCUTCHEON 3).With reference to Figure 1,apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Torque 2-7/8" DIA. sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 (73,0 mm) Nm). FACE OF Step C.After ceiling installation and fin- SPRINKLER — 251/4" 2'I Dm ishing, slide on the Style 15 or Style 20 FITTING ( ) Closure over the Series TY-FRB Sprin- 5/16±1/4" kler and push the Closure over the (7,9±6,4 mm) 1/2"(12,7 mm) Mounting Plate until its flange comes in + FLUSH contact with the ceiling. 1` , I ,7 1 Care and t MOUNTING N 31/82mm" ) i Maintenance SURFACE ( The TYCO Series TY-FRB,5.6 K-factor, Upright(TY313) and Pendent(TY323) CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) Sprinklers must be maintained and ser- TY-FRB PLATE 7/8"(22,2 mm) viced in accordance with this section. FIGURE 5 Before closing a fire protection system SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) main control valve for maintenance WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 work on the fire protection system RECESSED ESCUTCHEON that it controls, obtain permission to shut down the affected fire protection Modified sprinklers must be replaced. standards of any other authorities hav- systems from the proper authorities Sprinklers that have been exposed to ing jurisdiction. Contact the installing and notify all personnel who may be corrosive products of combustion, but contractor or sprinkler manufacturer affected by this action. have not operated,should be replaced regarding any questions. if they cannot be completely cleaned Absence of the outer piece of an by wiping the sprinkler with a cloth or Automatic sprinkler systems are rec- escutcheon, which is used to cover by brushing it with a soft bristle brush. ommended to be inspected, tested, a clearance hole, can delay sprinkler and maintained by a qualified Inspec- operation in a fire situation. Care must be exercised to avoid dam- tion Service in accordance with local The owner must assure that the sprin- age to the sprinklers before,during,and requirements and/or national codes. klers are not used for hanging any after installation. Sprinklers damaged objects and that the sprinklers are only by dropping, striking, wrench twist/ cleaned by means of gently dusting slippage,or the like,must be replaced. with a feather duster; otherwise, non- Also, replace any sprinkler that has a operation in the event of a fire or inad cracked bulb or that has lost liquid from vertent operation may result. its bulb.(Ref. Installation Section.) Sprinklers which are found to be leak- The owner is responsible for the ing or exhibiting visible signs of corro inspection,testing,and maintenance of sion must be replaced. their fire protection system and devices in compliance with this document, as Automatic sprinklers must never be well as with the applicable standards painted, plated, coated, or other- of the National Fire Protection Associa- wise altered after leaving the factory. tion (e.g., NFPA 25), in addition to the TFP172 Page 4 of 4 P/N* 77 - XXX - X - XXX _ � I SPRINKLER TEMPERATURE FINISH RATINGS SIN 1 NATURAL BRASS 135 135°F(57°C) 370 5.6K UPRIGHT(1/2"NPT) TY313 3 PURE WHITE(RAL9010)" POLYESTER 155 155°F(68°C) 371 5.6K PENDENT(1/2"NPT) TY323 q SIGNAL WHITE(RAL9003) 175 175°F(79°C) POLYESTER "Use suffix"1"for ISO 7-1 connection; 9 CHROME PLATED 200 200°F(93°C) for example,77-370-4-175-I ""Eastern Hemisphere sales only 286 286°F(141°C) TABLE A SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for avail- www.tyco-fire.com. ability.When placing an order,indicate the full product name and Part Num- ber(P/N). Sprinkler Assemblies with NPT Thread Connections Specify:Series TY-FRB Upright or Pen- dent (specify) Sprinkler, SIN (specify), K=5.6,Quick Response, (specify)tem- perature rating, (specify) finish, P/N (specify,refer to Table A). Recessed Escutcheon Specify:Style 15 Recessed Escutcheon with(specify*)finish, P/N (specify") Specify: Style 20 Recessed Escutch- eon with(specify*)finish, P/N (specify") *Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2014 Tyco Fire Products,LP. All rights reserved. Vico TEFLON is trademark of The DuPont Corporation. Vico Protection Products Eddythread 40 A Lightweight Schedule 40 Replacement Pipe That Has a Corrosion Resistance Ratio of 1.0 Bull Moose Tube Company has been making pipe for a long time and is recognized as a producer of quality pipe products. Eddythread 40 is designed with the same thoroughness as our other fine pipe products and now our customers have an option to buy a carefully designed replacement for Schedule 40 that: • Has a Corrosion Resistance Ratio of 1.0 • Has a Pressure Rating of 300 psi • Is Lighter Weight Than Schedule 40 • Is Approved by Factory Mutual and Listed by Underwriters Laboratories • Is Produced in Accordance to ASTM A-135 and A-795 • Can be Used With Standard Schedule 40 Threaded Fittings, Couplings and Valves • Is Produced From Steel With Excellent Properties of Strength and Threadability • Can be Used in Wet, Dry, Preaction, and Deluge Type Sprinkler Systems* • Offers Lower Freight Costs EDDYTHREAD 40 SPECIFICATIONS NOMINAL PIPE SIZE (in) WEIGHT(lbs/ft)„ I D. (in) BUN 1 1.461 1.083 70 1 1/4 2.070 1.418 51 1 1/2 2.547 1.654 44 2 3.308 2.123 30 CORROSION RESISTANCE RATIOS NOMINAL PIPE SIZE(in) SCHEDULE • t .,i A.4< 1 1.00 1.00 1 1/4 1.00 1.00 1 1/2 1.00 1.00 2 1.00 1.00 Eddythread 40 can be hot dipped galvanized to meet FM's requirement for dry systems 1819 ClarksonRoad 63 For additional information, C �L Us n41J.`+J) Chesterfield, MO 63017 contact your salesperson today at j ( BULL Monet,TUBE COMPANY (800)325-4467 (800)325-4467 or(636)537-2600 LISTED vvv FAX:(636)537-2645 oosetu inthe USA,or from Canada www.bullmoosetube.com call(800)882-4666 A C R O company e-mail:sales ci bullmoosetube.com APPROVED All information contained herein is accurate as known at the time of publication. But Moose Tube reserves the right to change product specifications without notice and without incurring obligation. 8/08 --.,, � I ucti e ron fittings- ass I I I T QUALITY PLUS CeiUS APPFOVED Fig. 35E 3- 90° Elbow LISTED A Size Part Number A Packing Weight e'\\ in in Inner Master lb + 1/2 35E 3004 1.13 100 200 0.2 3/4 35E 3006 1.31 70 140 0.3 ILnii A 1 35E 3010 1.50 40 80 0.5 . �,■U 1-1/4 35E 3012 1.75 25 50 0.8 1-1/2 35E 3014 1.94 18 36 1.1 2 35E 3020 2.25 10 20 1.8 2-1/2 35E 3024 2.70 4 8 3.2 Fig. 35RE3- 90°Reducing Elbow B Size A B PackingWeight �; in Part Number in in Inner Mster lb , \ 3/4 x 1/2 35RE3006004 1.20 1.22 80 160 0.3 1_11111N\ � - 1 x 1/2 35RE3010004 1.26 1.36 70 140 0.4 A 1 x 3/4 35803010006 1.38 1.45 50 100 0.4 �ER v 1-1/4 x 1/2 35RE3012004 1.34 1.53 35 70 0.5 1-1/4 x 3/4 35RE3012006 1.45 1.63 35 70 0.6 1-1/4 x 1 35RE3012010 1.58 1.67 30 60 0.7 1-1/2 x 1/2 35RE3014004 1.52 1.75 30 60 0.6 1-1/2 x 3/4 35RE3014006 1.52 1.75 25 50 0.7 1-1/2 x 1 35RE3014010 1.65 1.80 20 40 0.8 1-1/2 x 1-1/4 35RE3014012 1.82 1.88 18 36 1.0 2 x 1/2 35RE3020004 1.60 1.97 18 36 1.0 2 x 3/4 35RE3020006 1.60 1.97 18 36 1.0 2 x 1 35RE3020010 1.73 2.02 16 32 1.2 2 x 1-1/4 35RE3020012 1.90 2.10 12 24 1.3 1 2 x 1-1/2 35RE3020014 2.02 2.16 10 20 1.5 2-1/2 x 1-1/2 35RE3024014 2.16 2.51 6 12 2.2 2-1/2 x 2 35RE3024020 2.39 2.60 6 12 2.5 1 Fig. 35F 3-45°Elbow i 1 Size Part Number A Packing Weight t. ' , in in Inner Master lb � , , �j 1/2 35F 3004 0.88 150 300 0.2 3/4 35F 3006 0.98 80 160 0.3 #11\A 1 35F 3010 1.13 40 80 0.5 1-1/4 35F3012 1.29 25 50 0.7 1-1/2 35F 3014 1.44 20 40 1.0 killA 2 35F 3020 1.69 10 20 1.6 2-1/2 35F 3024 1.95 4 8 2.7 Fig. 35T 3- Tee Size A Packing Weight • Part Number in in Inner Master lb !•�� 1A II iI 1/2 3573004 1.13 80 160 0.3 3/4 3513006 1.31 30 60 0.5 1 3513010 1.50 25 50 0.7 �...� 1-1/4 35T 3012 1.75 10 20 1.1 A it A 1-1/2 35T3014 1.94 0 20 1.5 2 35T 3020 2.25 6 12 2.4 - 2-1/2 35T 3024 2.70 4 8 4.3 111 SNII'T'H-COOPER INTERNATIONAL' • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • ccww.smithcooper.com Ct , I ucti e ron rttings- ass I I I I QUAL 3 CelUS APPPOVED A Fig. 35CP3 -Straight Coupling with Ribs LISTED 111111111111111 f Size Part Number A Packing Weight in in Inner Master lb - 1/2 35CP3004 1.38 200 400 0.1 0.2 3/4 35CP3006 1.63 100 200 1 35CP3010 1.75 60 120 0.4 1-1/4 35CP3012 2.00 35 70 0.5 1-1/2 35CP3014 2.19 25 50 0.7 2 35CP3020 2.62 15 30 1.2 2-1/2 35CP3024 3.00 9 18 2.2 Fig. 35RC3 -Hex Reducing Coupling 8 Size in Part Number A Packing Weight fH; in lb 0.3 ® A 1 x 1/2 35RC3010004 1.69 80 160 1 x 3l4 35RC3010006 1.69 60 120 0.4 0.6 A _ 1-1/4 x 3/4 35RC3012006 2.06 40 Inner Master 80 2 x 1 (not hex) 35RC3020010 2.81 20 40 1.0 Fig. 35HB3 -Hex Bushing Size Part Number A Packing Weight B i in in Inner Master lb 1 x 1/2 35HB3010004 1.06 180 360 0.2 1 x 3/4 35HB3010006 1.06 180 360 0.1 �� A 1-1/4 x 1 35HB3012010 1.19 90 180 0.2 • illi I 1-1/2 x 1 35HB3014010 1.25 75 150 0.4 1-1/2 x 1-1/4 35HB3014012 1.25 75 150 0.3 2 x 1 35HB3020010 1.38 40 80 0.6 2 x 1-1/4 35HB3020012 1.38 40 80 0.6 2 x 1-1/2 35HB3020014 1.38 40 80 0.6 IN Fig. 35SP3 -Square Head Plug rt/x.,- ;,-1.t' sO.4,1t,zi Size Part Number A Packing Weight in in Inner Master lb '44J1.5 1/2 35SP3004 0.94 600 1200 0.07 I A 3(4 35SP3006 1.12 350 700 0.1 1 35SP3010 1.25 200 400 0.1 1-1/4 35SP3012 1.37 100 200 0.3 1-1/2 35SP3014 1.44 80 160 0.4 2 35SP3020 1.50 45 90 0.6 Fig. 35U 3- Union with Brass Seat A Size Part Number A Packing Weight ��l�, in in Inner Master lb K'I. - -la I 1 35U 3010 2.19 20 40 1.0 h ml 1-1/4 35U 3012 2.50 15 30 1.2 1-1/2 35U 3014 2.62 10 20 1.7 1.1 ��1� 2 35U 3020 3.12 6 12 2.4 113 SM{I'I'EI-COOPER INTERNATIONAL`' • TOLI, FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com Ductile Iron Threaded Fittings am + : to .?,-,en,k t x` 1‘.. .«:-.,..,- �,�F�es., . 4x�.:a#» W. 'rn .. st a' } r't 4,Atsx,�to 1- h! �1jT3F'y�` " - h .`..raA+a .r.4'4h.i hi;.._:,ti• h 7, -t< rs * ^ 'r, .:.:s. w .y. .R'# Y " 4'�+'a.los • .ts"tt Ort `ifs_ µ� .,44,i.';`..::',4, :*7. ,,,r.;,,,4:,-,.1,...::::::...,..,11.4:so's:3:::'4,..: + ' • , * ,, .;..t * ' -Ai*,,\.-. ..,.':1.4 ,*'.g.:.4 SMITH C ooPI R6 INTERNATIONAL Ductile Iron Threaded Fittings Specifications • 4413 branded ductile iron threaded fittings are UL Listed and FM Approved at 500 psi • Rated to 300 WSP (20 Ductile iron castings conform to ASTM A536 C US • LISTED • Fitting dimensions conform to ASME B16.3 • Bushings and plugs conform to ASME B16.14 4414> • Fittings are 100% air tested APPROVED • NPT threads on all fittings conform to ASME B1.20.1 • Independent lab verification that fittings meet applicable chemical &physical properties • Manufacturing facilities are ISO 9001:2008 and ISO 14001 Temperature Working Pressure, Nonshock psiG Degrees F 300#Class Threaded Fittings -20 to 100 500 150 500 200 480 250 ' :7:0,4: 460 300 440 350 k ..: r 420 400 400 450 ra 380 500 360 550 W4,,7,*1 340 600 320 650 300 -,„ 1 ucti e ron fittings- ass I I I Y I (41.1;11r/i W$.. C (1) US 44:10 APPROVED - Fig. 35E 3-90° Elbow LISTED A Size Part Number A Packing Weight M .. _._. , in in Inner Master lb f 1/2 35E 3004 1.13 100 200 0.2 V"\` 1 3/4 35E 3006 1.31 70 140 0.3 " ' A 1 35E 3010 1.50 40 80 0.5 1111 1-1/4 35E 3012 1.75 25 50 0.8 1-1/2 35E 3014 1.94 18 36 1.1 2 35E 3020 2.25 10 20 1.8 2-1/2 35E 3024 2.70 4 8 3.2 Fig. 35RE3- 90°Reducing Elbow B Size Part Number A B Packing Weight in in in Inner Master lb ��\ 3/4 x 1/2 35RE3006004 1.20 1.22 80 160 0.3 1 x 1/2 35RE3010004 1.26 1.36 70 140 0.4 I- 1 x 3/4 35RE3010006 1.38 1.45 50 100 0.4 ;.` in VA 1-1/4 x 1/2 35RE3012004 1.34 1.53 35 70 0.5 1-1/4 x 3/4 35RE3012006 1.45 1.63 35 70 0.6 1-1/4 x 1 35RE3012010 1.58 1.67 30 60 0.7 1-1/2 x 1/2 35RE3014004 1.52 1.75 30 60 0.6 1-1/2 x 3/4 35RE3014006 1.52 1.75 25 50 0.7 1-1/2 x 1 35RE3014010 1.65 1.80 20 40 0.8 1-1/2 x 1-1/4 35RE3014012 1.82 1.88 18 36 1.0 2 x 1/2 35RE3020004 1.60 1.97 18 36 1.0 2 x 3/4 35RE3020006 1.60 1.97 18 36 1.0 2 x 1 35RE3020010 1.73 2.02 16 32 1.2 i 2 x 1-1/4 35RE3020012 1.90 2.10 12 24 1.3 i. 2 x 1-1/2 35RE3020014 2.02 2.16 10 20 1.5 2-1/2 x 1-1/2 35RE3024014 2.16 2.51 6 12 2.2 2-1/2 x 2 35RE3024020 2.39 2.60 6 12 2.5 Fig. 35F 3-45°Elbow Uf. Size Part Number A Packing Weight A in in Inner Master lb 1/2 35F3004 0.88 150 300 0.2 it 3/4 35F 3006 0.98 80 160 0.3 1 35F 3010 1.13 40 80 0.5 1-1/4 35F 3012 1.29 25 50 0.7 1-1/2 35F 3014 1.44 20 40 1.0 1�I �A 2 35F 3020 1.69 10 20 1.6 2-1/2 35F 3024 1.95 4 8 2.7 Fig. 35T 3- Tee Size A Packing Weight Part Number in in Inner Master lb .31=IL A 1/2 351 3004 1.13 80 160 0.3 3/4 1 35T 3006 35T 3010 1.31 1.50 30 60 25 50 0.5 $ 1_ il0.7 1-1/4 35T 3012 1.75 10 20 1.1 4----i'i A 1-1/2 35T 3014 1.94 10 20 1.5 2 35T 3020 2.25 6 12 2.4 2-1/2 35T 3024 2.70 4 8 4.3 111 S\ITTI1-COOPER INTERNATIONAL' • TOE!. FREE 1-800-766-0076 • FAX(323)890-4456 • www.sminccooper.com tiucti e ron ittings- ass I I II Q ,..-Y u C43us APPROVED Fig. 35RT3-Reducing Tee LISTED L Size Part Number A B C Packing Weight in in in in Inner Master Ib s_--, C 3/4 x 1/2 35013006004 1.20 1.20 1.22 60 120 0.4 1 x 1/2 35RT3010004 1.26 1.26 1.36 30 60 0.6 -r 1 x 1/2 x 1 35073010004010 1.50 1.36 1.50 30 60 0.6 �`'-'t _,_..F=, 1 x 3/4 35073010006 1.38 1.38 1.45 25 50 0.6 (-) 1 x 3/4 x 3/4 35973010006006 1.38 1.31 1.45 35 70 0.6 B A 1 x 3/4 x 1 35RT3010006010 1.50 1.45 1.50 25 50 0.7 1-1/4 x 1/2 35073012004 1.34 1.34 1.53 20 40 0.8 1-1/4 x 1/2 x 1-1/4 35RT3012004012 1.75 1.53 1.75 25 50 0.9 1-1/4x3/4 3501'3012006 1.45 1.45 1.62 15 30 0.9 1-1/4 x 3/4 x 1-1/4 35RT3012006012 1.75 1.62 1.75 20 40 1.0 1-1/4 x 1 35073012010 1.58 1.58 1.67 15 30 1.0 1-1/4 x 1 x 1/2 35RT3012010004 1.34 1.26 1.53 25 50 0.7 1-1/4 x 1 x 3/4 35013012010006 1.45 1.38 1.63 20 40 0.8 1-1/4 x 1 x 1 35RT3012010010 1.58 1.50 1.69 20 40 0.9 1-1/4 x 1 x 1-1/4 35073012010012 1.75 1.69 1.75 15 30 1.0 1-1/2 x 1/2 35RT3014004 1.41 1.41 1.66 16 32 1.0 1-1/2 x 1/2x 1-1/4 35RT3014004012 1.81 1.56 1.88 24 48 1.1 1-1/2 x 1/2 x 1-1/2 35RT3014004014 1.94 1.66 1.94 12 24 1.2 1-1/2 x 3/4 35RT3014006 1.52 1.52 1.75 16 32 1.1 1-1/2 x 3/4 x 1-1/4 35RT3014006012 1.94 1.66 1.88 20 40 1.1 1-1/2 x3/4 x 1-1/2 35073014006014 1.94 1-75 1.94 18 36 1.2 1-1/2 x 1 35RT3014010 1.65 1.65 1.80 12 24 1.2 1-1/2 x 1 x 1/2 35R13014010004 1.44 1.25 1.69 20 40 0.8 1-1/2 x 1 x 3/4 35RT3014010006 1.50 1.44 1.75 16 32 0.9 1-1/2 x 1 x 1 35873014010010 1.65 1.50 1.80 16 32 1.0 1-1/2 x 1 x 1-1/4 35RT3014010012 1.82 1.67 1.88 12 24 1.2 1-1/2 x 1 x 1-1/2 35RT3014010014 1.94 1.80 1.94 12 24 1.3 1-1/2 x 1-1/4 35913014012 1.82 1.82 1.88 12 24 1.4 s, 1-1/2 x 1-1/4 x 1/2 35RT3014012004 1.41 1.34 1.66 16 32 0.9 1-1/2 x 1-1/4 x 3/4 35RT3014012006 1.52 1.45 1.75 16 32 1.0 1-1/2 x 1-1/4 x 1 35013014012010 1.65 1.58 1.80 16 32 1.1 - 1-1/2 x 1-1/4 x 1-1/4 35RT3014012012 1.82 1.75 1.88 14 28 1.3a= ;, 1-1/2 x 1-1/4 x 1-1/2 35013014012014 1.94 1.88 1.94 14 28 1,4 1 7 ,y 2 x 1/2 35073020004 1.49 1.49 1.88 10 20 1.5 : a ,' 2 x 3/4 35813020006 1.60 1.60 1.97 10 20 1.6 �'� 2 x 1 35RT3020010 1.73 1.73 2.02 8 16 1.7 2 x 1 x 2 35RT3020010020 2.25 2.02 2.25 8 16 1.9 2 x 1-1/4 35RT3020012 1.90 1.90 2.10 8 16 1.9 2 x 1-1/4 x 2 35013020012020 2.25 2.10 2.25 8 16 2.0 2 x 1-1/2 35RT3020014 2.02 2.02 2.16 8 16 2.1 2 x 1-1/2 x 1/2 35R13020014004 1.49 1.41 1.88 10 20 1.3 2 x 1-1/2 x 3/4 35RT3020014006 1.60 1.52 1.97 10 20 1.4 2 x 1-1/2 x 1 35813020014010 1.73 1.65 2.02 8 16 1.5 2 x 1-1/2 x 1-1/4 35RT3020014012 1.90 1.82 2.10 8 16 1.7 2 x 1-1/2 x 1-1/2 35813020014014 2.02 1.94 2.16 8 16 1.8 Fig. 35BT3-Bull Head Tee 1 Size Part Number A B C Packing Weight JUNI in in in in Inner Master lb �C 3/4 x 1 35B13006010 1.45 1.45 1.37 30 60 0.6 • 1�1I 1 x 1-1/4 35B13010012 1.67 1.67 1.58 20 40 0.9 �.._� 1 x 1-1/2 35B13010014 1.80 1.80 1-65 15 30 1.0 (-A-) B > 1-1/4 x 1 x 1-1/2 35673012010014 1.88 1.80 1.82 15 30 1.2 1-1/4x 1-1/2 35B13012014 1.88 1.88 1.82 15 30 1.3 - 1-1/4x2 35B13012020 2.10 2.10 1.90 10 20 1.6 1-1/2 x 1-1/4 x 2 35B13014012020 2.16 2.10 2.02 10 20 1.8 1-1/2 x 2 35B13014020 2.16 2.16 2.02 8 16 1.8 S>\.I111 14:001)ER I!'I'ER\A'I'IONAL4 • '['OLI, FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com 112 Ductile Iron Fittings-Class 300 UL/FM QUA I .3 c03us APPROVED - a , A Fig. 35CP3 -Straight Coupling with Ribs LISTED Size 3!4 A Packing Weight in Part Number in Inner Master lb I:II _ 1(2 35003004 1381 200 400 0.1 ,............. 35003006 63 100 200 0.2 1 35003010 1.75 60 120 0.4 1-1/4 35CP3012 2.00 35 70 0.5 1-1/2 35003014 2.19 25 50 0.7 2 35CP3020 2.62 15 30 1.2 2-1/2 35003024 3.00 9 18 2.2 Fig. 35RC3 -Hex Reducing Coupling Size Part Number A Packing Weight (U. - in in Ib ® A 1 x 1/2 1 x 3/4 35803010004 1.69 80 160 0.3 35803010006 1.69 60 120 0.4 0.6 1-1/4 x 3/4 35803012006 2.06 40 Inner Master 80 2 x 1 (not hex) 35803020010 2.81 20 40 1.0 Fig. 35HB3 -Hex Bushing Size Part Number A Packing Weight 1 0 B in in Inner Master lb { ' 1 x 1/2 35HB3010004 1.06 180 360 0.2 I�II �A 1 x 3/4 35HB3010006 1.06 180 360 0.1 11 1-1/4 x 1 35HB3012010 1.19 90 180 0.2 1-1/2 x 1 35HB3014010 1.25 75 150 0.4 1-1/2 x 1-1/4 35HB3014012 1.25 75 150 0.3 2 x 1 35HB3020010 1.38 40 80 0.6 2 x 1-1/4 35HB3020012 1.38 40 80 0.6 2 x 1-1/2 35HB3020014 1.38 40 80 0.6 ,'-'.il Fig. 35SP3 -Square Head Plug iz. Size A Packing Weight in Part Number in Inner Master lb 1/2 35SP3004 0.94 600 1200 0.07 • A 3/4 35SP3006 1.12 350 700 0.1 1101 111111#1111111111111 I I 1 35SP3010 1.25 200 400 0.1 1-1/4 35SP3012 1.37 100 200 0.3 1-1/2 35SP3014 1.44 80 160 0.4 2 35SP3020 1.50 45 90 0.6 Fig. 35U 3-Union with Brass Seat A Size Part Number A Packing Weight y in in Inner _ Master lb .,,.,.; Yl.i.-,i,:::,0', sivalaqiews "III 1 35U 3010 2.19 20 40 1.0 1 1/4 35U 3012 2.50 15 30 1.2 1 ''..., 1-1/2 35U 3014 2.62 10 20 1.7 Ilm��_i.r� 2 35U 3020 3.12 6 12 2.4 113 S\IITII-COOPER INTERNATIONAL' • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com :::',Wi ' Ductile Iron Fittings- Class 300 UL/FM I QUA rrmus c � uS �I APPROVED Fig. 35X 3- Cross LISTED A 4-)1(-) Size A Packing Weight Part Number jillitialin in Inner Master lb A 1 35X 3010 1.50 20 40 0.9 I 1-1/4 35X 3012 1.75 12 24 1.4 -� 1 U1 IA 1-1/2 35X 3014 1.94 8 16 1.8 2 35X 3020 2.25 6 12 2.8 nlaril B B Fig. 35RX3-Reducing Cross ' " �'` ' Size A B Packing Weight ~ __)..til il in Part Number in in Inner Master lb 4 x 1 35RX3012010 1.67 1.58 15 30 1.2 I IA1-1/2 x 1 35RX3014010 1.80 1.65 12 24 1.4 h;• I 2 x 1 35RX3020010 2.02 1.73 8 16 2.0 Fig. 35C 3- Cap Size Part Number in A Packing Weight p /n Inner Master lb A 1/2 3/4 35C 3004 0.87 300 600 0.1 35C 3006 0.97 30 200 400 0.1 1 35C 3010 1.16 110 220 0.2 1-1/4 35C 3012 1.28 70 140 0.4 1-1/2 35C 3014 1.33 50 100 0.5 2 35C 3020 1.45 25 50 0.8 - 2-1/2 35C 3024 1.70 18 36 1.6 Fig. 35BC3-Beam Clamp Size A Packing Weight qr II, in Part Number in Inner Master lb s 1111 3/8 35BC3003 0.75 100 200 0.3 ■' 1/2 35BC3004 0.75 80 160 0.5 %' _ IIS S\[ITIT-COOPER INTERNATIONAL' • TOLL FREE 1-800-766-0076 • FAX(323)890-44% • wIAV,amithcooper.com 114 Pipe Hangers Fig.200- "Trimline" Adjustable Band Hanger (B-Line Fig.B317ONF) ®TOLCO Fig.200F- "Trimline" Adjustable Band Hanger with Felt Lining (B-Line Fig.B317ONFF) Fig.200C - "Trimline" Adjustable Band Hanger with Plastic Coated (B-Line Fig.B317ONFC) LISTED ' Fig.200S - "Trimline" Adjustable Band Hanger with Non-Captured Nut Size Range: Fig. 200 - 1/2" (15mm)thru 8" (200mm)pipe Material: Steel, Pre-Galvanized to G90 specifications 4. Function: For fire sprinkler and other general piping purposes. Knurled -- swivel nut design permits hanger adjustment after installation. Features: ,.� ® • (1/2" (15mm)thru 2" (50mm)) Flared edges ease installation for all pipe types and protect CPVC plastic pipe from abrasion. Captured design keeps adjusting nut from separating with hanger. Hanger is easily n B installed around pipe. A For hanger with non-captured nut order Fig. 200S. • (21/2" (65mm)thru 8" (200mm)) Spring tension on nut holds it securelyin ‘ ' ' ._--..---• P g � hanger before installation.Adjusting nut is easily removed. Approvals: Underwriters Laboratories listed (1/2" (15mm)thru 8" (200mm)) Fig 200-1/2.200-3/4 in the USA(UL)and Canada (cUL) for steel and CPVC plastic pipe and Fig.200-1 to 200-2 Fig.200-21/2 to 200-8 Factory Mutual Engineering Approved (FM) (3/4" (20mm)thru 8" (200mm)). Conforms to Federal Specifications WW-H-171 E&A-A-1192A,Type 10 and Manufacturers Standardization Society ANSI/MSS SP-69 &SP-58, Type 10. , * Maximum Temperature: 650°F(343°C) Finish: Pre-Galvanized. Stainless Steel materials will be supplied with (2) hex nuts in place of a knurl nut. ., " Order By: Figure number and pipe size r' Designed to meet or exceed requirements of # c FM DS 2-0. x`* - c. . Fig.200 ii ' Fig.200C Fig.200F Pipe Size Rod Size A B Approx.Wt./100 Part No. in. (mm) in. (mm) in. (mm) lbs. (kg) 200-1/2 1/2" (15) 3/e"-16 31/8" (79.4) 25/8" (66.7) 11 (5.01 200-3/4 3/4" 120) 3/8"-16 31/8" (79.41 21/2" (63.5) 11 (5.01 sr 200-1 1" (251 3/8"-16 33/8" (85.7) 25/8" 166.7) 12 (5.5) 200-11/4 11/4" (32) 3/8"-16 33/4" (94.0) 27/8" (73.0) 13 (5.9) 200-11/2 11/2" (40) 3/8"-16 3y8" (98.4) 27/8" (73.0) 14 (6.4) 200-2 2'' 150) 3/8"-16 41/2" (114.3) 3" (76.3) 15 (6.9) 200-21/2 21/2" (65) 3/8"-16 55/8" (142.9) 41/8° (104.7) 27 (12.3) 200-3 3" 175) 3/8"-16 57/e" (149.1) 4" (101.6) 29 (13.3) Fig.200S 200-31/2 31/2" 190) 3/a"-16 73/8" (187.3) 51/4" (133.3) 34 (15.6) 200-4 4" 0001 3/8"-16 73/8" (187.3) 5" (127.0) 35 (16.01 200-5 5" (125) 1/2"-13 91/8" (231.81 61/4" (158.7) 66 (30.2) 200-6 6" (150) 1/2".13 101/8" (257.2) 63/4" (171.4) 73 (33.4) 200-8 8" (200) 1/2"-13 131/8" (333.4) 83/4" 1222.21 136 (62.3) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. • B-lane Fire Protection Solutions 21 by Es"t*N Threaded Accessories B3205 - Threaded Rod (right-hand threads - both ends) (ToLco Fig.103) ��r' • B3205L - Threaded Rod (right& left hand threads) / TL -1 Size Range: 3/8"-16 thru 3"-4 rod Specify Length1� � Material: Steel ,,� Function: Recommended for use as a hanger support in hanger assemblies. TL X11 Rod is threaded on both ends with right hand threads of the length shown.Also I11)�. available with left and right hand threads-specify Fig B3205L when ordering. %' A Thread Size Maximum Temperature: 750°F(399°C) Finish: Plain.Contact B-Line for alternative finishes and materials. Order By: Part number, rod size, length and finish Standard Design Load Thread Size Thread Length TL 650°F(343°C) 750°F(399°C) Part No. A in. (mm) Lbs. (k1,4 Lbs. (kN) B3205-3/8 X'L' 3/8"-16 21/2 (63.5) 730 (3.25) 572 (2.54) B3205-1/2 x'L' 1/2"-13 21/2 (63.5) 1350 (6.00) 1057 (4.70) B3205-5/8 x'L' 5/8"-11 21/2 (63.5) 2160 (9.61) 1692 (7.52) B3205-3/4 x'L' 3/4"-10 3 (76.2) 3230 (14.37) 2530 (11.25) 83205-7/8 x'L' 7/8"-9 31/2 (88.9) 4480 (19.93) 3508 (15.60) B3205-1 x'L' 1"-8 4 (101.6) 5900 (26.24) 4620 (20.55) B3205-11/a x'L' 11/8"-7 41/2 (114.3) 7450 (33.14) 5830 (25.93) B3205-11/4 x'L' 11/4"-7 5 (127.0) 9500 (42.25) 7440 (33.09) B3205-11/2 x'L' 11/2"-6 6 (152.4) 13800 (61.38) 10807 (48.07) 133205-13/4 x'L' 13/4"-5 7 (177.8) 18600 (82.73) 14566 (64.79) B3205-2 x'L' 2"-41/2 8 (203.2) 24600 (109.42) 19625 (87.29) 113205-21/4 x'L' 21/4"-41/2 9" (228.6) 32300 (143.67) 25295 (112.51) • B3205-21/2 x'L' 21/2"-4 10 (254.0) 39800 (177.03) 31169 (138.64) B3205-23/4 x'L' 23/4"-4 11" (279.4) 49400 (219.73) 38687 (172.08) B3205-3 x'L' 3"-4 12" (304.8) 60100 (267.32) 47066 (209.35) ATR -All Threaded Rod 120" (3.05m) Lengths (TOLCo Fig.loo) -,, Fig. 99 -All Threaded Rod Cut To Length ,i,o1, Size Range: 3/8"-16 thru 11/2"-6 rod in 120"(3.05m)lengths or cut to length l l Material: Steel • a 9d Maximum Temperature: 750°F(399°C) i Finish: Plain.Contact B-Line for alternative finishes and materials. `pj 4 ot Order By: Part number, rod diameter and finish Part No.-Size x Length Threads Recommended Load Approx.Wt./100 Ft. ATR Fig.99 Per Inch Lbs. (kN) Lbs. (kg) ATR 1/4"x 120 99-1/4"x length 20 240 (1.07) 12 (5.44) ATR 3/s"x 120 99-3/e"x length 16 730 (3.24) 29 (13.15) ATR 1/2"x 120 99-1/2"x length 13 1350 (6.00) 53 (24.04) ATR 5/8"x 120 99-5/s"x length 11 2160 (9.60) 89 (40.37) ATR 3/4"x 120 99-3/4"x length 10 3230 (14.37) 123 (55.79) ATR 7/8"x 120 99-7/s"x length 9 4480 (19.93) 170 (77.11) ATR 1"x 120 99-1"x length 8 5900 (26.24) 225 (102.06) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. --Line■ Pipe Hangers&Supports 236 Revised 4/28/2014 by :T•