Report (31) 6(201 - coolf-z___ . ... lAACCURATE BALANCING AI. AGENCY INC AIR AND WATER BALANCING • DUCT LEAKAGE TESTING CERTIFIED TEST • ADJUST • BALANCE REPORT Project: Taco Bell Location: 13305 SW Pacific Highway - Tigard, OR. Architect: Rodd Hansen Architect HVAC Contractor: Tri-Tech Heating 4 1,.... a"---- t 1 gutir:g NEBB# 3177 • CCB# 6475 PO Box 653 • E3EAVERTON, OR 97075 • (503) 297-6594 • ABA@AE3AINC.U9 • FAX (5031 292-4E325 AACCURATE Table of Contents BALANCING AGENCY INC Project-Location: Taco Bell - 13305 SW Pacific Highway -Tigard, OR. Page # Table of Contents 1 Certification 2 Terms and Abbreviations 3 Instrument Calibration 4 General Remarks and Summaries 5 RTU Unit Fan Test&Air Outlet Test Reports 6 Exhaust Fan Test&Air Outlet Test Reports 10 Indexed Floor Plan Accurate Balancing Agency, Inc. Page 1 of 12 ACCURATE Certification BALANCING 411, AGENCY INC Project-Location: Taco Bell - 13305 SW Pacific Highway-Tigard, OR. The data presented in this report is a record of system measurements and final adjustments that have been obtained in accordance with the current edition of the NEBB Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems. Any variances from design quantities, which exceed NEBB tolerances, are noted in the Test-Adjust-Balance Report Project Summary. Significant or noteworthy remarks are noted on the General Remarks or on individual test reports. Noted deficiencies are not the TAB firms responsibility to repair. Prior to issuance of this report, Deficiency Reports are forwarded to our contracted agent. Warranty is limited to one year from date of this report. Within that time, any descrepancies, ambiguities, or omissions found in this report will be retested, adjusted, or balanced as needed. A written notification will be required. Submitted and Certified by NEBB TAB Firm: Accurate Balancing Agency, Inc. Certification: 3177 Expiration Date: March 31, 2021 Certification Date: April 1, 2019 Signed and Sealed by NEBB Supervisor: Edward M. May Jr. Accurate Balancing Agency, Inc. Page 2 of 12 AACCURATE Terms and Abbreviations BALANCING AGENCY INC Project-Location: Taco Bell - 13305 SW Pacific Highway-Tigard, OR. AC Air Conditioning Unit AH Air Handler AHU Air Handling Unit AK Area Factor or Flowhood Backpressure Compensation Factor BHP Brake Horsepower BMS Building Management System BTUH British Thermal Units per Hour CEF Ceiling Exhaust Fan CFM Cubic Feet per Minute CRU Computer Room Unit DB Dry Bulb DDC Direct Digital Control EAT Entering Air Temperature EWT Entering Water Temperature EF Exhaust Fan EG Exhaust Grille (Shown as Triangled number on indexed plans) ERU Energy Recovery Unit FPB Fan Powered Box (Terminal Unit which incorporates a fan) FSD Fire/ Smoke Damper GPM Gallons per Minute Head Pressure Difference across the entering and leaving side of a pump HRU Heat Recovery Unit HVAC Heating Ventilation and Air Conditioning HZ Hertz Inches(") Inches of water gauge K Correction factor to the free area needed to calculate CFM LAT Leaving Air Temperature LWT Leaving Water Temperature N/A Not Applicable N/L Not Listed OBD Opposed Blade Damper OAD Outside Air Damper OD Outside Diameter OSA Outside Air Damper PSI Pounds per Square Inch RA Return Air RG Return Grille (Shown as a Circled number on indexed plans) RPM Revolutions Per Minute RTU Roof Top Unit SA Supply Air SG Supply Grille (Shown as a Standard number on indexed plans) SFA Service Factor Amperage TAB Test; Adjust; and Balance VAV Variable Air Volume (Terminal Unit which regulates airflow) VEL Velocity WB Web Bulb Accurate Balancing Agency, Inc. Page 3 of 12 1 ACCURATE Instrument Calibration Report BALANCING AGENCY INC Project-Location: Taco Bell - 13305 SW Pacific Highway - Tigard, OR. Instrument Manufacturer I Model # I Serial # I Calibrated I Cal. Due Type Air Evergreen S-PVF-1 1600225 9/6/2018 9/6/2019 Air Pressure Air Evergreen S-PVF-1 1600225 9/6/2018 9/6/2019 Air Velocity Air Evergreen S-PVF-1 1600225 9/6/2018 9/6/2019 Flowhood Temperature Evergreen PR-T-1 1600240 10/26/2018 10/26/2019 Air Temp Temperature Evergreen PR-T-2 1700107 10/26/2018 10/26/2019 Contact Temp Temperature Evergreen PR-T-4-6" 1700236 10/26/2018 10/26/2019 Immersion Temp Humidity Evergreen S-H-3-5" 1800324 11/2/2018 11/2/2018 Humidity Meter Electrical UEI DL389 TRMS 170403164 11/12/2018 11/12/2019 Multimeter Rotation Daniu/APGTech DT-2234C f T307311 10/22/2018 10/22/2019 Tachometer Hydronic Alnor/TSI HM675 71725032 11/15/2018 11/15/2019 Hydrometer Blower Fan Retrotec DM32 4A 407722 9/12/2017 9/12/2022 Control Gauge Accurate Balancing Agency, Inc. Page 4 of 12 ACCURATE General Remarks and Summary BALANCING AGENCY INC Project-Location: Taco Bell - 13305 SW Pacific Highway -Tigard, OR. 1) RTU-1 is a constant volume direct drive air handler which was balanced as shown; unit minimum outside air was determined by direct velocity reading of OSA inlet. 2) RTU-2 is a constant volume belted air handler which was balanced as shown; unit minimum outside air was determined by direct velocity reading of OSA inlet. 3) EF-1 and EF-2 are direct drive exhaust fans which are reported as tested with speed controllers set and marked at final setting. Accurate Balancing Agency, Inc. Page 5 of 12 ACCURATE Air Handling Unit Test Report BALANCINt3 (Packaged/ Direct Drive) AGENCY INC Project-Location: Taco Bell - 13305 SW Pacific Highway - Tigard, OR. Technician: SS/ MM Test Date: Mar 2019 Submittal Data I Unit Designation RTU-1 Service Dining Manufacturer Trane Model Number YHC092F3RMA Serial Number 190211249L Test Data Item Design Actual Total Supply Airflow (CFM Design / Outlet) 3000/3000 2875 External Static Pressure (Inches water gauge) Not Listed 0.46" Total Return Airflow (CFM) 2250 21 1 1 Minimum Outside Air (CFM) 750 728 Motor Horsepower 2.75 BHP Motor Manufacturer Not Listed Motor Frame Not Listed Motor Service Factor 1.0 Full Load Amperage (T1 / T2 / T3) 7.3 1.7/1.6/1.5 Voltage (T1-T2 / Ti-T3 / T2-T3) 208-3-60 211/212/212 Operating Hz. 60 60 Speed Setting Potentiometer Fan (RPM) N/A N/A Static Pressure Profile I Component In (Suction SP) Out(Discharge SP) Differential Pressure Fan -0.34" 0.20" 0.54" Coil / Filter -0.26" -0.34" 0.08" Remarks: I RTU-1 is a constant volume direct drive air handler which was balanced as shown;unit minimum outside air was determined by direct velocity reading of OSA inlet. Accurate Balancing Agency, Inc. Page 6 of 12 ACCURATE Air Outlet Test Report BALANCING AGENCY INC Project-Location: Taco Bell - 13305 SW Pacific Highway -Tigard, OR. Technician: SS / MM Test Date: Mar 2019 System / Unit Design Preliminary Final Test Area Served # Size Type AK VEL CFM VEL CFM VEL. CFM Jo RTU-1 Supply Dining 1 24x24 SG 1.00 450 450 370 370 435 435 97% Dining 2 24x24 SG 1.00 450 450 270 270 405 405 90% Dining 3 24x24 SG 1.00 450 450 305 305 425 425 94% Dining 4 24x24 SG 1.00 450 450 310 310 450 450 100% Dining 5 24x24 SG 1.00 450 450 315 315 450 450 100% Dining 6 24x24 SG 1.00 450 450 335 335 425 425 94% Corridor 7 24x24 SG 1.00 100 100 140 140 90 90 90% Restroom 8 14x14 SG 1.00 100 100 140 140 100 100 100% Restroom 9 14x14 SG 1.00 100 100 40 40 95 95 95% Totals 3000 2225 2875 96% RTU-1 Return Dining 1 24x24 RG 1.05 1071 1125 955 1003 1010 1061 94% Dining 2 24x24 RG 1.05 1071 1125 945 992 1000 1050 93% Totals 2250 1995 2111 94% RTU-1 1 36x15 Inlet 3.81 197 750 245 933 191 728 97% Outside Air Totals 750 933 728 97% Remarks: I RTU-1 is a constant volume direct drive air handler which was balanced as shown; unit minimum outside air was determined by direct velocity reading of OSA inlet. Accurate Balancing Agency, Inc. Page 7 of 12 ACCURATE Air Handling Unit Test Report BALANCING (Packaged/ Belted) AGENCY INC • Project-Location: Taco Bell - 13305 SW Pacific Highway - Tigard, OR. Technician: SS/ MM Test Date: Mar 2019 Submittal Data I Unit Designation RTU-2 Service Kitchen Manufacturer Trane Model Number YHD150G3RHB Serial Number 190210493D Test Data Item Design Actual Total Supply Airflow (CFM Design / Outlet) 4400/4400 4305 External Static Pressure (Inches water gauge) Not Listed 0.70" Total Return Airflow (CFM) 3450 3229 Minimum Outside Air (CFM) 950 928 Motor Horsepower 3.0 Motor Manufacturer Marathon Motor Frame 56HZ Motor Service Factor 1.15 Full Load Amperage (T1 / T2 / T3) 9.4 6.1/6.0/6.1 Voltage (T1-T2 / T1-T3 / T2-T3) 208-3-60 211/212/212 Operating Hz. 60 60 Motor(RPM) 1725 1754 Fan (RPM) Not Listed 594 Motor Sheave l VL40x7/8" Fan Pulley 10.5"ODxl 3/16" Belt(Number) Size (1) BX68 Sheave Centerline Distance 22.5" (Idler) Static Pressure Profile I Component In (Suction SP) Out(Discharge SP) Differential Pressure, Fan -0.47" 0.37" 0.84" Coil / Filter -0.33" -0.47" 0.14" Remarks: I RTU-2 is a constant volume belted air handler which was balanced as shown; unit minimum outside air was determined by direct velocity reading of OSA inlet. Accurate Balancing Agency, Inc. Page 8 of 12 ACCURATE Air Outlet Test Report BALANCING P' AGENCY INC Project-Location: Taco Bell - 13305 SW Pacific Highway -Tigard, OR. Technician: SS/ MM Test Date: Mar 2019 System / Unit Design Preliminary Final Test Area Served # Size Type AK VEL CFM VEL CFM VEL CFM 0/0 RTU-2 Supply Kitchen 1 24x24 SG 1.00 200 200 195 195 190 190 95% Kitchen 2 24x24 SG 1.00 200 200 160 160 195 195 98% Kitchen 3 24x24 SG 1.00 200 200 135 135 200 200 100% Kitchen 4 24x24 SG 1.00 200 200 135 135 200 200 100% Kitchen 5 24x24 SG 1.00 600 600 555 555 575 575 96% Kitchen 6 24x24 SG 1.00 600 600 395 395 570 570 95% Kitchen 7 24x24 SG 1.00 450 450 495 495 460 460 102% Kitchen 8 24x24 SG 1.00 350 350 475 475 360 360 103% Kitchen 9 24x24 SG 1.00 600 600 415 415 570 570 95% Kitchen 10 24x24 SG 1.00 275 275 290 290 285 285 104% Kitchen II 24x24 SG 1.00 125 125 155 155 135 135 108% Kitchen 12 24x24 SG 1.00 600 600 505 505 565 565 94% Totals 4400 3910 4305 98% RTU-2 Return Kitchen 1 24x24 RG 1.05 1095 1150 1015 1066 1095 1150 100% Kitchen 2 24x24 RG 1.05 1095 1150 980 1029 1065 1118 97% Kitchen 3 24x24 RG 1.05 1095 1150 825 866 915 961 84% Totals 3450 2961 3229 94% RTU-2 l 60x17 Inlet 7.19 132 950 152 1 093 129 928 98% Outside Air Totals 950 1093 928 98% Remarks: RTU-2 is a constant volume belted air handler which was balanced as shown;unit minimum outside air was determined by direct velocity reading of OSA inlet. Accurate Balancing Agency, Inc. Page 9 of 12 ACCURATE Fan Test Report BALANCING (Direct Drive) AGENCY INC Project-Location: Taco Bell - 13305 SW Pacific Highway - Tigard, OR. Technician: SS / MM Test Date: Mar 2019 Submittal Data I Unit Designation EF-1 Service Kitchen Hood Manufacturer Stratovent Model Number SV-DU50HFA Serial Number Job#3664748 Test Data I Item Design Actual Total Airflow (CFM Design / Outlet) 1050/ 1050 1077 Total Static Pressure (Inches water gauge) 1.0" N/A Motor Horsepower 1/2 Motor Manufacturer HSSA Motor Frame 48Y Motor Service Factor 1.0 Full Load Amperage (T1 / T2 / T3) 5.5 4.4 Voltage (T1-T2 / Tl-T3 / T2-T3) 115-1-60 121-1-60 Operating Hz. 60 60 Speed Setting Speed Controller Fan (RPM) N/A N/A Static Pressure Profile I Component In (Suction SP) Out(Discharge SP) Differential Pressure Fan N/A N/A N/A Remarks: I EF-1 and EF-2 are direct drive exhaust fans which are reported as tested with speed controllers set and marked at final setting. Accurate Balancing Agency, Inc. Page 10 of 12 ACCURATE Fan Test Report QALANCINr (Direct Drive) AGENCY INC Project-Location: Taco Bell - 13305 SW Pacific Highway-Tigard, OR. Technician: SS / MM Test Date: Mar 2019 Submittal Data I Unit Designation EF-2 Service Restrooms/Kitchen Manufacturer Stratovent Model Number SV-DR3OHFA Serial Number Job//3664748 Test Data Item Design Actual Total Airflow (CFM Design / Outlet) 570/570 603 Total Static Pressure (Inches water gauge) 0.50" N/A Motor Horsepower 1/4 Motor Manufacturer HSSA Motor Frame 48Y Motor Service Factor 1.0 Full Load Amperage (T1 / T2 / T3) 3.0 2.4 Voltage (T1-T2 / T1-T3 / T2-T3) 115-1-60 121-1-60 Operating Hz. 60 60 Speed Setting Speed Controller Fan (RPM) N/A N/A Static Pressure Profile I Component In (Suction SP) Out(Discharge SP) Differential Pressure Fan N/A N/A N/A Remarks: I EF-1 and EF-2 are direct drive exhaust fans which are reported as tested with speed controllers set and marked at final setting. Accurate Balancing Agency, Inc. Page 11 of 12 liegliACCURATE Air Outlet Test Report BALANCING ® AGENCY INC • Project-Location: Taco Bell - 13305 SW Pacific Highway-Tigard, OR. Technician: SS/MM Test Date: Mar 2019 System / Unit Design Preliminary Final Test Area Served # Size Type AK VEL CFM VEL CFM VEL CFM %o EF-1 1 62x14 Hood 5.92 177 1050 252 1492 182 1077 103% Kitchen Hood Totals 1050 1492 1077; 103% EF-2 Restroom 1 12x12 EG 1.00 140 140 240 240 150 150 107% Restroom 2 12x12 EG 1.00 130 130 230 230 140 140 108% Kitchen 3 10x10 EG 0.53 566 300 875 464 590 313 104% Totals 570 934 603 106% Remarks: l EF-1 and EF-2 are direct drive exhaust fans which are reported as tested with speed controllers set and marked at final setting. Accurate Balancing Agency, Inc. Page 12 of 12