Loading...
Plans GENERAL NOTES AERIAL VIEW OFFICE COPY _ ALL WORK SHALL COMPLY WITH 2017 NATIONAL ELECTRIC CODE(NEC),2015 "'.- ->--- a-,---a,w,--_,,,,Ilo". 4,,,*; --..: - 1 INTERNATIONAL RESIDENTIAL CODE(IRC),2014 NATIONAL BUILDING CODE(NBC),2015 INTERNATIONAL BUILDING CODE(IBC),2015 INTERNATIONAL PLUMBING CODE(IPC),AND - A ALL STATE AND LOCAL BUILDING,ELECTRICAL,AND PLUMBING CODES. �,� x� pp �} 2. DRAWINGS HAVE BEEN DETAILED ACCORDING TO UL LISTING REQUIREMENTS MR 2 Z01y 430 LIABILITY CITY OFTIGA� AM12205.630E ERICAN FORK,UT 84003 The City of Tigard and its r* BUILDING DIVISION �y (, Y 800-377-4480 employees shall not be �x x f , VNVVUBLUERAVENSOLARCOM SITE NOTES g47.' CONFIDENTIAL-THE INFORMATION 1. A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. responsible for discrepancies � � , HEREIN CONTAINED SHALL NOT BE 2. THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS AN UTILITY may VELI DITY OF PERMIT INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES. which appear herein, USED FOR THE BENEFIT OF ANYONE EXCEPT THE ISSUANCE OF A PERMIT 3. THE SOLAR PV INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING,MECHANICAL,OR i BLUERAVENSOLAR NOR SHALL IT BUILDING ROOF VENTS. ` BASED ON CONSTRUCTION BE DISCLOSED IN WHOLE OR IN 4. PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL f DOCUMENTS AND OTHER PART TO OTHERS OUTSIDE EQUIPMENT WILL BE PROVIDED AS PER SECTION[NEC 110.26] jRECIPIENTS ORGANIZATION, 5. THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE i DATA SHALL NOT PREVENT EXCEPT IN CONNEC TION WITH THE y SALE AND USE OF THE RESPECTIVE BETWEEN THE GROUNDING ELECTRODE AND THE PANEL(OR INVERTER)IF SMALLER THAN#6 ji/ THE CODE OFFICIAL FROM EQUIPMENT,WITHOUT THE AWG COPPER WIRE PER NEC 250-64B.THE GROUNDING ELECTRODE CONDUCTOR WILL BE 9REQUIRING THE CORRECTION WRITTEN PERMISSION OF CONTINUOUS,EXCEPT FOR SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER `' OF ERRORS. QRSC 1 05.4 BLUERAVENSOLAR LLC. [NEC 250.64C] O O cD 6. ROOF COVERINGS SHALL BE DESIGNED,INSTALLED,AND MAINTAINED IN ACCORDANCE WITH CC- THIS CODE AND THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF L11 W z d 00 COVERING SHALL SERVE TO PROTECT THE BUILDING OR STRUCTURE. „ , �i1f1COVed t1IaD5 0 0 7. RIGID CONDUIT(AND/OR NIPPLES)MUST HAVE A PULL BUSHING TO PROTECT WIRES. '14 ' �3 2 iY'C'}� .N, .� D O __I N- - r 8. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED j •_%•• ✓e C'D CD �� 0 '' �' U_J CONDUCTOR(USE POLARIS BLOCK OR NEUTRAL BAR) a , �� �ZM "" (- Lo f- (y O 9. ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS " }- Z O '-&1 1- eal I- fr7 00 DISALLOWED ABOVE LIVE PARTS,MEYERS HUBS RECOMMENDED 7 � U O O 10. UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT OFF uJ U U m THE ROOF SURFACE IN ACCORDANCE WITH NEC 110.2,110.3(A-B).300.4 11.SOLADECK JUNCTION BOXES MOUNTED FLUSH W/ROOF SURFACE TO BE USED FOR WIRE � 'ate °� O MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS. � SOLAR CONTRACTOR i-'' y " T� 1- MODULE CERTIFICATIONS WILL INCLUDE UL1703,IEC61646,IEC61730. 1 W �- 'A t„ d 4' 2. IF APPLICABLE,MODULE GROUNDING LUGS MUST BE INSTALLED AT THE MARKED GROUNDING W *� ' " ``* LUG HOLES PER THE MANUFACTURERS'INSTALLATION REQUIREMENTS. 3. AS INDICATED BY DESIGN,OTHER NRTL LISTED MODULE GROUNDING DEVICES MAY BE USED F, IN PLACE OF STANDARD GROUNDING LUGS AS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. ASCE 7-10 WIND SPEED: 120 MPH OCCUPANCY - R3 SHEET INDEX 4. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND GROUND SNOW LOAD: 40 PSF CONSTRUCTION V B ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS. PV1 - COVER SHEET EXPOSURE CATEGORY: C Z 5. CONDUIT POINT OF PENETRATION FROM EXTERIOR TO INTERIOR TO BE INSTALLED AND ZONING: RESIDENTIAL PV2 - PROPERTY PLAN 0 N SEALED WITH A SUITABLE SEALING COMPOUND. SEISMIC DESIGN CATEGORY: CCO 6. DC WIRING LIMITED TO MODULE FOOTPRINT W/ENPHASE AC SYSTEM. PV3 - SITE PLAN Cr) (\[ 7. ENPHASE WIRING SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY W/ PV4 - EQUIPMENT & ATTACHMENT DETAIL 2 -0 o Cr) SUITABLE WIRING CLIPS. SCOPE OF WORK PV5 - ELECTRICAL SINGLE LINE DIAGRAM 8. MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP COEFFICIENT FOR PV6 - ELECTRICAL CALCULATIONS O O w VOC UNLESS NOT AVAILABLE. LL - 9. ALL INVERTERS,MOTOR GENERATORS,PHOTOVOLTAIC MODULES,PHOTOVOLTAIC PANELS, 6 kW DC PHOTOVOLTAIC SOLAR ARRAY & STRING DIAGRAM Z m co o AC PHOTOVOLTAIC MODULES,DC COMBINERS,DC-TO-DC CONVERTERS,SOURCE CIRCUIT ROOF TYPE: Comp Shingle PV7 - MBD CALCS. (IF NEEDED) w >-. COMBINERS,AND CHARGE CONTROLLERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER MODULES: (20) ( )Trinasolar 300 TSM DD05A.08 II PV8 LABELS & LOCATIONS ~ O M O 0 U ,- d o co SYSTEM WILL BE IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4(B). 10. ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. INVERTER(S): Enphase IQ7-60-2-US,---- PV9 - STRING & SE OPTIMIZER RACKING: Unirac Sunframe Microrail Mounting & Racking System PV10 - PLACARD (IF NEEDED - NEC 690.56(B)) DRAWING BY EQUIPMENT LOCATIONS 1. ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY[NEC 110.26]. Eric Thomas2. EQUIPMENT INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING CITY OF TIGARD TEMPERATURE AS SPECIFIED BY[NEC 690.31 (A)-(B)]AND[NEC TABLE 310.15(B)]. REVIE\VED FOR CODE COMPLIANCE DATE 3. ADDITIONAL AC DISCONNECTS SHALL BE PROVIDED WHERE THE INVERTER IS NOT ADJACENT January 29, 2019 TO THE UTILITY AC DISCONNECT,OR NOT WITHIN SIGHT OF THE UTILITY AC DISCONNECT. Approved: t 4. ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING OTCs [ J PROJECT NUMBER TO NEC APPLICABLE CODES. 5JO1 905} 5. ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE Permit#: kip. a d �_.�� WHEN APPROPRIATE. Address: `'172-4:6V� I SHEET NAME ' i L. '�`� COVER SHEET Smite#: - By: r Date: PAGE NUMBER REVISION fK� ,32 II4 PV1 0 LEGEND INV INVERTER&DC DISCONNECT BLUE RAVEN 13280 SW Maddie Lane SUB (E) SUBPANEL LC (N) LOAD CENTER 1220 S 630E STE.430 AMERICAN FORK UT 84003 FRONT OF HOME AC AC DISCONNECT 800-377-4480 WWW.BLUERAVENSOLAR COM M UTILITY METER/SERVICE PANEL CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF N JB JUNCTION BOX ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE ❑ C COMBINER BOX RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE / PV PV REVENUE METER ❑ / EQUIPMENT.WITHOUT THE WRITTEN PERMISSION OF m i j/ FIRE SETBACK BLUERAVENSOLAR LLC. U o ,, U 1 EMT CONDUIT RUN W W N- D a d q (TO BE DETERMINED IN FIELD) 0 z � Q �. O Qoo U 0 N- ° j O PV WIRE STRING Z D W ❑ i I— I.n Hyo d I0 PROPERTY LINE U O C'') Q F— CO Z 00 MP2 II Um AZIMUTH:270° 14 SCALE: 1/16"= 1'-0" 0 0) IR 0' 4' 8' 16 32 PITCH:30° 0 O 124' isaasansiniiiiiiiiii CC a- TSRF:81 ,. ,. ., ❑ a° Iffc Cfc JB a Ii. lg. Pk PSC 0 Ioak 12fnOf. Vic Ci, ale 121, Ito Pt N MP1 z 2 N o AZIMUTH:180° _1 rn N PITCH:27° < CD TSRF:98% f "03 ° O� T2 -5- O H z m >- o o ca H o CO o 0 -- ROOF ATTACHMENTS SHALL BE SPACED U) U a- 0 co NO GREATER THAN 24" ON CENTER IN DRAWING BY ANY DIRECTION WHERE LOCATED Eric Thomas WITHIN 3' OF A ROOF EDGE, HIP, EAVE, OR RIDGE OSSC 3111.5.3 ITEM 3.2 DATE January 29, 2019 PROJECT NUMBER DC SYSTEM SIZE: 6 kW DC 59019054 ROOF TYPE: Comp Shingle 50'-3" SHEET NAME PROPERTY PLAN (20) Trinasolar 300 TSM-DDO5A.08(II) Enphase IQ7-60-2-US,----INVERTER PAGE NUMBER REVISION PV2 0 LEGEND FRONT OF HOME N INV INVERTER&DC DISCONNECT BLUE RAVEN -12" —•- -.— Elk SUB (E) SUBPANEL LC (N) LOAD CENTER 1220 S 630 E STE.430 AMERICAN FORK,UT 84003 AC AC DISCONNECT 800-377-4480 WWW.BLUERAVENSOLAR.COM M UTILITY METER/SERVICE PANEL CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE / USED FOR THE BENEFIT OF JB JUNCTION BOX ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT / BE DISCLOSED IN WHOLE OR IN 0_ PART TO OTHERS OUTSIDE (n C COMBINER BOX RECIPIENTS ORGANIZATION, 1_� EXCEPT IN CONNEC TION WITH THE —/ SALE AND USE OF THE RESPECTIVE (� PV PV REVENUE METER EQUIPMENT,WITHOUT THE 4 Q WRITTEN PERMISSION OF j/ BLUERAVENSOLAR LLC O FIRE SETBACK U > pCu) cs 0 EMT CONDUIT RUN LLJ W [` 0 a / (TO BE DETERMINED IN FIELD) O Z (s) O cf Tj 0 QfCOUml: O 1 PV WIRE STRING < O 'Cl- fr Q W c 2I- 12) HILO O _ f- Z PROPERTY LINE U O M0 " BLOCKING MIGHT BE MP2 % —W) (UI) U m 0, 1' SCALE. 1/8"= -0" NEEDED BETWEEN BOX AZIMUTH:270° / 2 O TRUSSES ON MP2, IF SO, PITCH:30° O D_ USE DETAIL 1 PV40 TSRF:81 /o j co i lP, -- 7 O O 0 ��� / O ca N LU //// /f///// C H a) 0) N �� 2 - o co ►fc Ikc Igc JB 12 a W AC DISCONNECT TO BE LOCATED li 0 WITHIN 10' OF UTILITY METER Ilc Egc Ifc kfC z m ° p o O D VISION OF PROFESSIONAL CERTIFICATIONS - STRUCTURE ONLY FW— o N o U CACC IAC (. C THIS DOCUMENT REPRESENTS A COLLABORATIVE DESIGN EFFORT. THIS SEAL COVERS THE ANALYSIS OF THE EXISTING U) C) .- CL 0 CO STRUCTURE AND ATTACHMENT OF THE NEW SOLAR PANELS TO IT. PE CERTIFIES THAT IT WILL ADEQUATELY SUPPORT ITS OWN W EIGHT AND THE WEIGHT OF THE NEW SOLAR PANELS(STRUCTURAL CALCULATIONS PROVIDED SEPARATELY. IF STRUCTURAL RETROFITS ARE REQUIRED,THEN THEY ARE SPECIFIED ON THESE PLANS-SEE PAGES PV3 a PV4. DRAWING BY ROOF ATTACHMENTS SHALL BE SPACED �c �c �c ►�c �c �c NO GREATER THAN 24" ON CENTER IN O PRofi Eric Thomas ANY DIRECTION WHERE LOCATED , � y ,9i Digitally signed by DATE WITHIN 3' OFA ROOF EDGE, HIP, EAVE, N. January 29, 2019 ' , OR RIDGE OSSC 3111.5.3 ITEM 3.2 MP1 , -, P.� Ryan Hillstrom, PE AZI M UTH:180° PROJECT NUMBER DC SYSTEM SIZE: 6 kW DC PITCH:27° ;t 1 1 Date: 2019.03.1 1 59019054 ROOF TYPE: Comp Shingle TSRF:98% r4f� 4dof , i SHEET NAME (20) Trinasolar 300 TSM DD05A.08(II) iivi1Ls. 11i. :25.56 -06 00 SITE PLAN THIS DOCUMENT HAS BEEN CERTIFIED ELECTRONICALLY USING A DIGITAL IDENTIFICATION CERTIFICATE UNIQUE TO THE SIGNER„PAGE NUMBER REVISION Enphase 1Q7-60-2-US,----INVERTER ISSUED BY A CERTIFICATE AUTHORITY APPROVED BY ADOBE(AATL)AND COMPATIBLE WITH BLUEBEAM AND OTHER COMMON PDF EDITORS(BUT NOT PREVIEWER WINDOWS) IT ALSO SATISFIES THE REQUIREMENTS OF THE DIGITAL SIGNING PV3 0 STANDARD ESTABLISHED BY THE NATIONAL INSTITUTE OF STANDARDS Q TECHNOLOGY(FIPS 156-4) PV ARRAY INFORMATION ROOF ATTACHMENTS SHALL BE SPACED PV MODULE(BEHIND TRIM RAIL) Unirac Sunframe Microrail TRIM RAIL NO GREATER THAN 24" ON CENTER IN ANY DIRECTION WHERE LOCATED 1 PV MODULE COUNT: 20 MODULES WITHIN 3' OF A ROOF EDGE, HIP, EAVE, LANDSCAPE R RAVEN 1 #OF ATTACHMENT POINTS: 64 OR RIDGE OSSC 3111.5.3 ITEM 3.2N N N N jr ARRAY AREA: Module Count x 17.51ft2 = 350.2ft2 -1,-11„�• 48" MAX. MAX. ROOF AREA: 2682.4ft2 1220 S 630E STE 430 AMERICAN FORK,UT 84003 % OF ARRAY/ROOF: 13.1% PORTRAIT jr E N 41 M PI Q1 800-377-4480 ARRAY WEIGHT: Module Count x 501bs = 1000.OIbs 1'-i 1" WWW.BLUERAVENSOLARCOM • DISTRIBUTED LOAD: ArrayWeight_ArrayArea = 2.86 lbs/ft2 MAX. 48"MAX. g ARRAY DETAIL, FRONT VIEW CONFIDENTIAL-THE INFORMATION POINT LOAD: Array Weight_Attachments = 15.61bs/attachment SFM Raised Seal Flashing Scale: 3/8"= I-0" HER INECONTAINED FOR E BENEF T OF NOT BE ANYONE EXCEPT RACKING ATTACHMENTS TO BE Unirac Sunframe Microrail FRAME BLUERAVENSOLAR NOR SHALL IT STAGGERED BY SHIFTING EACH BE DISCLOSED IN WHOLE OR IN SUBSEQUENT ROW OF ATTACHMENTS PORTRAIT PART TO OTHERS OUTSIDE STRUCTURAL ASCE 7-10 WIND SPEED: 120 MPH EXPOSURE CATEGORY: C ONE RAFTER OVER. ® RECIPIENTS ORGANIZATION, DESIGN CRITERIA EXCEPT INCONNECTIONWITHTHE GROUND SNOW LOAD: 40 PSF SEISMIC DESIGN CATEGORY: C . SALE AND USE OF THE RESPECTIVE -------- EQUIPMENT,WITHOUT THE WRITTEN PERMISSION OF � BLUERAVENSOLAR LLC Unirac Sunframe Microrail 11/ rLANDSCAPE }• O co, O JKUNIRAC TRIMRAIL MODULES • W Z O O CO WIDTH i U (O I•— 71- Trinasolar t Trinasolar 300 TSM DD05A.08(II) < a OD O 0 I` Li_ PV MODULE ZDV Q -u � O �._ .� 27 c ARRAY DETAIL, SIDE VIEW < 0 I W co z \ (E) ROOF , ism 1 1 .. Scale: 3/8"= 1-0" H H co Z g [ a UI`t :; MEMBRANE MODULE I W O O m `� 2.5" %upRo Digitally signed co O II Oo UNIRAC SLIDERS AND WIDTH o�� S by Ryan o LH ih - TRIMRAIL ROOF ATTACHMENTS //9. H t f 36 P'. - i I_ o l Hillstrom, PE m I FLASHING Date: 20 9.03. J 2.5" MIN. EMBED. 1�,c,({2. .m ' Q ROOF TYPE: Comp Shingle I- 5/16" STAINLESS STEEL LAG BOLT Nf-441:27' '_. 1- 1 1 :26:29 -06'00' o WITH 2-1/2" MIN. EMBEDMENT ROOF FRAMING TYPE: Manufactured Truss AND FLAT WASHER (� - (E) BUILDING RAFTER OR TOP CHORD(TRUSS)2x4 @ 24"O.C. SIDE VIEW �,TRAFTERS IXI - 400STRUCTURE CEILING JOIST OR BOTTOM CHORD(TRUSS)2x4 @ 24"O.C. 2x4',•24'o/c1EU SOLAR PA/EL ARRAY z 'CY SEE OTHER DETAILS) NEW: o (� C1 .1 Ili 2 x 6'BLOQCIN6•24'o/c J �- BEn�+BOX TRUSSES•ALL STANDOFF LOCATIONS �' ° N_ ATTACH EACH Erin TO TRUSS TOP-C40RD ✓, Q Unirac Sunframe Microrail WSIFIPSONA34CUP %rte' �W o C EASING (13 c N W LL ra,H�G O G O H O Trinasolar 300 TSM-DDO5A.08(II) Z m -a 0 0 _.bra__,,,,,,,,,,,_„_.___ PV MODULE N (13 U)_I—(qXI4I11IIi ' CTIUd co 11 = Pp Q �i �` (E) ROOF ✓ DRAWING BY F 2.5” MEMBRANE11 Eric Thomas W II a � J = 0 M _ —= 4 i _� 1 (LOOP AM TRILSSES•24'o/c CEILRG NOT 5HOLLW UDOD BOX TPoB5E5.24'o/c DATE U UNIRAC SLIDERS January 29, 2019 J 2.5" MIN. EMBED. Q I 1 PROJECT NUMBER L- • FLASHING w 59019054 5/16"STAINLESS STEEL LAG BOLT EXTERIORLO o 1= WITH 2-1/2" MIN. EMBEDMENT eEAF2.6wa-L 3 SHEET NAME DETAIL AND FLAT WASHER (E) BUILDINGBLOCKING UPGRADE_(BOX TRUSSES) PAGE NUMBER REVISION STRUCTURE Me F:NTB. PV4 0 1 11 1 " _,_i_ ._�-_t_ 1 It _ _ 1 11 '- " �_ -- 2 -1 - 6-6 2'-8" 2 -8 6-6 2 1 BLUE 1220 S.630E STE.430 • AMERICAN FORK,UT 84003 41: ro800-377-4480 ...-:1 1: f . WWW.BLUERAVENSOLAR.COM • �f� - �(���,,,�'�� CONFIDENTIAL-THE INFORMATION 0 STRUCTURAL SIDE VIEW HEREIN CONTAINED SHALL NOT BE Scale:3/8"=1'-0" USED FOR THE BENEFIT OF ANYONE EXCEPT RAFTER 2x4 @ 24"OC BLUERAVENSOLAR NOR SHALL IT CEILING JOIST 2x4 @ 24"OC BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE DigitallyEXCE T IIN CONNECORGANIWITHZATION THE SALE AND USE OF THE RESPECTIVE signed by RyanWRIEQUIT T WITHOUT THE ENNPERMISSION OF BLUERAVENSOLAR LLC 8'-10" — 8'-10" — Hillstrom, PE I Date: w z co ° o CO \- (E) LBW \- (E) L3W (E) LBW , Q cO 00r� � � Q _1ti —�— —,�— —�— 201 .1 1 < ca '- o W 181-1" 11 :26:47 -06'00' H co z W O O m 0/tt/LL/ co /11yy 1 11 t " I " J 6'-5" -- 2'-1" -"~- -- 2 -1 '- 6 -5 --- 6-5 1881-3" 0 STRUCTURAL SIDE VIEW z °' d- Scale:3!8"=1-0" J ti Ni RAFTER 2x4 @ 24"OC Q co CEILING JOIST 2x4 @ 24"OC 2 0 7 E0 p o w Z m C o o coLLI >s co -- CO U o Co DRAWING BY Eric Thomas 12'-5" - - 12'-5" DATE \_ - \-- i January 29, 2019 —+--- (_) L3W ---4-- (E) LBW (E) LBW —\,— PROJECT NUMBER 59019054 SHEET NAME 25'-2" EQUIP. DETAIL PAGE NUMBER REVISION PV4.1 0 • / (1) 10 AWG THWN-2,COPPER,BLACK(LINE 1) 20.0 A AC 7'�' (2) 12-2 UF-B W/G,SOLID COPPER MAX 10.0 A AC 7----N.,„ (1) 12-2 UF-B WIG,SOUD COPPER MAX 10.0 A AC (1) 12-2TC-ER,THWN-2,COPPER MAX 10.0 A AC /7- JC (1) 10 AWG THWN-2,COPPER,RED(LINE 2) 240 V AC ,` 3 240 V AC , 2 + 240 V AC 1 (1) 6 AWG BARE,COPPER(EGC) 240 V AC (1) 10 AWG THWN-2,COPPER,WHITE(NEUTRAL) ___,// (1) 10 AWG THWN-2,COPPER,GREEN(EGC) (1) 3/4 INCH EMTCONDUIT (1) 3/4 INCH EMT CONDUIT B I U E R AV E AC DISCONNECT TO BE LOCATED WITHIN 10'OF UTILITY METER 1220 S.630 E STE.430 AMERICAN FORK,UT 84003 ALL CONDUIT TO BE RAN AT LEAST 7/8"ABOVE ROOF SURFACE WHERE EXPOSED TO SUNLIGHT. 800-377-4480 W WW.BLUERAVENSOLAR.COM (20)Trinasolar 300 TSM-DD05A.08(II) CONFIDENTIAL-THE INFORMATION UL 1703 COMPLIANT HEREIN CONTAINED SHALL NOT BE 20 En hase IQ7-60-2-US MICRO INVERTERS USED FOR THE BENEFIT OF ( ) P ANYONE EXCEPT UL 1741 COMPLIANT BLUERAVENSOLAR NOR SHALL IT 5 MODULES MAX FOR ALL SUB-BRANCH BE DISCLOSED IN WHOLE OR IN HERS OUTSIDE JUNCTION BOX CIRCUIT(S)TO COMPLY WITH VRISE CALCS PART TORECIPIENTS ORGANIZATION, Enphasel0 Combiner 3 (OPTIONAL IF UF-B EXCEPT IN CONNEC TION WITH THE X-IQ X-IQ-AMI-240-3 CABLE USED FOR SALE AND USE OF THE RESPECTIVE (SOLAR LOADS ONLY) ENTIRE HOMERUN) JUNCTION BOX EQUIPMENT,WITHOUT THE WRITTEN PERMISSION OF (E)200A MAIN SERVICE PANEL � BLUERAVENSOLAR LLC. (E)200AI2P MAIN BREAKER (N)20 2P /1 /n —^ (1) MODULES ' \ \ LI OF 10 MODULES ® PV AC DISCONNECT _ 010 Z W O NON-FUSED c , c _ - in (E)200A/2P LOCKABLE,VISIBLE OPEN N J —V (r} Cfl H o ' 30A,240V,2-POLE — < 06 0 Q - • (E)LOADS — I z 0 O Q _1 !� < W -0\ --X10--- 0 JUNCTION BOX O 2 )"-'H co z (J-- O O co C ❑ ❑ (N)25A/2P — (N)20A/2P (1) CIRCUIT _ U O Cr) Q f / /� L, A —��^ OF 10 MODULES \ W C) (,� CO --dm., Li2 ' 1 o L G -,fl V L2 \'O V V N N 0 120/240 VAC �— V a. 60HZ TO UTILITY I — 15 3 0 O GRID J PV BREAKER TO BE LOCATED OPPOSITE END OF BUSSING FROM MAIN BREAKER (E) GROUNDING -..= ELECTRODE Z C N 0 (B 0\1 LL1 (i)I- ii rn N INTERCONNECTION NOTES 1. ONE OF THE METHODS THAT FOLLOWS SHALL BE USED TO DETERMINE THE RATINGS OF116: % �, - m BUSBARS AND PANELBOARDS. (a)THE SUM OF 125 PERCENT OF THE INVERTER(S)OUTPUT � " W CO CIRCUIT CURRENT AND THE RATING OF THE OVERCURRENT DEVICE PROTECTING THE A I el. H- U M a. o (9 BUSBAR SHALL NOT EXCEED THE AMPACITY OF THE BUS BAR. (b)WHERE TWO SOURCES, 11 k etlaig i . I i ONE THE UTILITY AND THE OTHER AN INVERTER ARE LOCATED AT OPPOSITE ENDS OF A -i,,,,,;-. F s ...._.1, -3--......- _..... 1. `'4 , `�€ DRAWING BY BUSBAR THAT CONTAINS LOADS,THE SUM OF 125 PERCENT OF THE INVERTER(S)OUTPUT I ' " "" Eric Thomas CIRCUIT CURRENT AND THE RATING OF THE OVERCURRENT DEVICE PROTECTING THE 4,1f1,010 BUSBAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE BUSBAR[NEC �� I ® "' N _: k- s .t % , ; DATE 705.12(D)(3)]. ,tel ' t January 29, 2019 3. GROUND FAULT PROTECTION IN ACCORDANCE WITH[NEC 215.9]&[NEC 230.95] ] �%' 4. ALL EQUIPMENT TO BE RATED FOR BACKFEEDING. t a.`!� ' ( , 3� I PROJECT NUMBER ��� 3 59019054 DISCONNECT NOTES " ` 1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS w €t OPENED THE CONDUCTORS REMAINING LIVE ARE CONNECTED TO THE SHEET NAME TERMINALS MARKED"LINE SIDE"(TYPICALLY THE UPPER TERMINALS) ' * �g ., 1 ELEC, 3 LINE p�A�j, 2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL,BE t, LOCKABLE,AND BE A VISIBLE-BREAK SWITCH PAGE NUMBER REVISION 3. DC CURRENT CONDUCTORS ARE TO REMAIN OUTSIDE OF BUILDING PRIOR TO PV5 0 EITHER A FUSEABLE SOURCE CIRCUIT MODULE SPECIFICATIONS Trinasolar300TSM-DD05A.08(11) DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS RATED POWER(STC) 300 W TEMPERATURE DATA SOURCE ASHRAE 2%AVG. HIGH TEMP MICROINVERTER TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 10.0 A AC Oregon JUNCTION BOX MAX.CURRENT(ISC X1.25)= 12.5 A AC vd , MODULE VOC 40 V DC STATE g Portland CONDUCTOR(TC-ER,COPPER(90°C)) 12 AWG= MODULEVMP 33 V DC CITYLU E R AV EN MODULE IMP 9.2 ADC WEATHER STATION PORTLAND INTERNATIONAL AP CONDUCTOR RATING= 30 A MODULE ISC 9.8 A DC ASHRAE EXTREME LOW TEMP(°C) -6 AMB.TEMP.AMP.CORRECTION= 0.96 VOC CORRECTION (%/°C) -0.3 °C ASHRAE 2%AVG.HIGH TEMP(°C) 32 ADJUSTED AMP.= 28.8 > 12.5 1220 S.630 E STE.430 VMP CORRECTION(%/°C) -0.4°C JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 10.0 A AC AMERICAN FORK,UT 84003 SERIES FUSE RATING 15 A DC SYSTEM ELECTRICAL SPECIFICATIONS CIR 1 CIR 2 CIR 3 CIR 4 CIR 5 CIR 6 COMBINER BOX MAX.CURRENT(ISC X1.25)= 12.5 A AC 800-377-4480 W W W.BLU ERAVENSOLAR.COM ADJ. MODULE VOC @ ASHRAE LOW TEMP 43.4 V DC NUMBER OF MODULES PER MPPT 10 10 CONDCUTOR(UF-B,COPPER(60°C))= 12 AWG ADJ.MODULE VMP @ ASHRAE 2%AVG.HIGH TEMP 27.6 V DC DC POWER RATING PER CIRCUIT(STC) 3000 3000 CONDUCTOR RATING= 20 A CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE TOTAL MODULE NUMBER 20 MODULES CONDUIT FILL DERATE= 0.8 USED FOR THE BENEFIT OF ANYONE EXCEPT MICROINVERTER SPECIFICATIONS Enphase 107-60-2-US STC RATING OF ARRAY 6000W DC AMB.TEMP.AMP.CORRECTION= 0.96 BLUERAVENSOLAR NOR SHALL IT POWER POINT TRACKING(MPPT) MIN/MAX 22 - 48 V DC AC CURRENT @ MAX POWER POINT(IMP) 10.0 10.0 ADJUSTED AMP.= 15.36 > 12.5 BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE MAXIMUM INPUT VOLTAGE 48 V DC MAX.CURRENT(IMP X 125) 12.5 12.5 EGC ISC= 10.0 A AC RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE MAXIMUM DC SHORT CIRCUIT CURRENT 15 A DC OCPD CURRENT RATING PER CIRCUIT 20 20 MAX.CHANNEL ISC= 12.5 A AC SALE AND USE OF THE RESPECTIVE 20.0 :ONDUCTOR THWN 2,COPPER 90°C = 10 AWG EQUIPMENT,WITHOUT THE MAXIMUM USABLE DC INPUT POWER 350 W MAX.COMB.ARRAY AC CURRENT(IMP) ( ( )) WRITTEN PERMISSION OF MAXIMUM OUTPUT CURRENT 1 A AC MAX.ARRAY AC POWER 4800W AC EGC CONDUCTOR RATING= 20 A BLUERAVENSOLAR LLC. AC OVERCURRENT PROTECTION 20 A CONDUIT FILL DERATE= 1 p p MAXIMUM OUTPUT POWER 240 W AC VOLTAGE RISE CALCULATIONS DIST(FT) VRISE(V) VEND(V) %VRISE 107-5 AMB.TEMP.AMP.CORRECTION= 0.96 W W o� oD- 4 CK WEIGHTED EFFICIENCY 97% VRISE SEC.1(MICRO TO JBOX) 18 0.36 240.36 0.15% ADJUSTED AMP.= 19.2 > 12.5 0 Z co H 0 VRISE SEC.2(J BOX TO COMBINER BOX) 70 2.83 242.83 1.18% COMBINER BOX TO INVERTER RATED AMPS= 20.0 A AC z D co < AC PHOTOVOLATIC MODULE MARKING(NEC 690.52) VRISE SEC.3(COMBINER BOX TO POI) 10 0.51 240.51 0.21% MAIN PV OCPD MAX.CURRENT(RATED AMPS X1.25)= 25 A AC < 0 d- IY w co 2I- I-6 F- ir_ ® NOMINAL OPERATING AC VOLTAGE 240 V AC TOTAL VRISE 1.54% :ONDUCTOR(T1-IWN-2,COPPER(75°C))= 10 AWG F- co Z C3 NOMINAL OPERATING AC FREQUENCY 47-68 HZ AC CONDUCTOR RATING= 35 A W O O m MAXIMUM AC POWER 240 VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL(NEC 690.54) CONDUIT FILL DERATE= 1 -, (f) MAXIMUM AC CURRENT PER CIRCUIT 10.0 A AC AC OUTPUT CURRENT 20.0 A AC AMB.TEMP.AMP.CORRECTION= 0.96 0 MAXIMUM OCPD RATING PER CIRCUIT 20 A AC NOMINAL AC VOLTAGE 240 V AC ADJUSTED AMP.= 33.6 > 25.0 Ct GROUNDING NOTES 10.EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZE ACCORDING TO[NEC 6. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 • • 1. A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690-47]AND 690.45] AND BE A MINIMUM OF#10AWG WHEN NOT EXPOSED TO DAMAGE(#6AWG INSULATED,90°C RATED,WET AND UV RESISTANT,RATED FOR 600V Z N [NEC 250-50]THROUGH[NEC 250-60]SHALL BE PROVIDED.PER NEC, SHALL BE USED WHEN EXPOSED TO DAMAGE). 7.4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER J ti W GROUNDING ELECTRODE SYSTEM OF EXISTING BUILDING MAY BE USED AND 11.GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLOR VOLTAGE TO GROUND MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. f- N N BONDED TO AT THE SERVICE ENTRANCE.IF EXISTING SYSTEM IS INACCESSIBLE, CODED GREEN(OR MARKED GREEN IF#4 AWG OR LARGER) 8.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION 2p OR INADEQUATE,OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL 12. ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF 9.VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS c' t4 2 GROUNDING ELECTRODE WILL BE USED AT THE INVERTER LOCATION CONNECTION SHALL HAVE GROUNDED BUSHINGS AT BOTH ENDS. 10,NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS L W Lts CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. 13.SYSTEM GEC SIZED ACCORDING TO[NEC 690.47],[NEC TABLE 250.66],DC FOLLOWS:DC POSITIVE-RED(OR MARKED RED),DC NEGATIVE-GREY(OR MARKED GREY) V- > C) r� U 2. GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN#8 AWG AND SYSTEM GEC SIZED ACCORDING TO[NEC 250.166],MINIMUM#8AWG WHEN 11.POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED: z gU7 >- - o NO GREATER THAN#6 AWG COPPER AND BONDED TO THE EXISTING GROUNDING INSULATED,#6AWG WHEN EXPOSED TO DAMAGE. DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK) W c U) ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. 14.EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, 12.AC CONDUCTORS>4AWG COLOR CODED OR MARKED: I- 0 0 co p 0 3. PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO[NEC 250.21],[NEC TABLE EQUIPMENTS,AND CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN PHASE A OR L1-BLACK,PHASE B OR L2-RED,PHASE C OR L3-BLUE,NEUTRAL- 250.122], AND ALL METAL PARTS OR MODULE FRAMES ACCORDING TO[NEC ACCORDANCE WITH 250.134 OR 250.136(A)REGARDLESS OF VOLTAGE. WHITE/GRAY DRAWING BY 690.46]. *USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY Eric Thomas 4. MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO[NEC WIRING&CONDUIT NOTES BE USED INSIDE 690.42]. 1.ALL CONDUIT SIZES AND TYPES,SHALL BE LISTED FOR ITS PURPOSE AND "USE-2 IS AVAILABLE AS UV WHITE 5. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT APPROVED FOR THE SITE APPLICATIONS 13.IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL DATE THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR 2.ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2,AND SINGLE-CONDUCTOR BE EITHER EMT,FMC,OR MC CABLE IF DC CURRENT COMPLYING WITH NEC 690.31,NEC January 29, 2019 TO ANOTHER MODULE. CABLE LISTED AND IDENTIFIED AS PV WIRE,TYPE TC-ER,OR EQUIVALENT;ROUTED TO 250.118(10).DISCONNECTING MEANS SHALL COMPLY WITH 690.13 AND 690.15 6. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTIONS POINTS SOURCE CIRCUIT COMBINER BOXES AS REQUIRED 14.CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18"BELOW ROOF SURFACE PROJECT NUMBER IDENTIFIED IN THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. 3.ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC COMPLYING WITH NEC 230.6(4)AND SECURED NO GREATER THAN 6'APART PER NEC 59019054 7. ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH 690.8] FOR MULTIPLE CONDUCTORS 330.30(B). AS APPROPRIATE WHEN GROUNDING EQUIPMENT WITH TERMINATION 4.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED SHEET NAME GROUNDING LUGS. AT LEAST 7/8"ABOVE THE ROOF SURFACE AND DERATED ACCORDING TO[NEC TABLE ELEC. CALCS. 8. GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND 310.15(B)(2)(a),NEC TABLE 310.15(B)(3)(a),&NEC 310.15(B)(3)(c)]. GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. 5.EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2,90°C RATED,WET AND UV PAGE NUMBER REVISION 9. GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER,SOLID OR RESISTANT,AND UL LISTED RATED FOR 600V,UV RATED SPIRAL WRAP SHALL BE PV6 STRANDED,AND BARE WHEN EXPOSED. USED TO PROTECT WIRE FROM SHARP EDGES LABEL 1 ,r LABEL 7 .. AT DIRECT-CURRENT EXPOSED RACEWAYS,CABLE TRAYS,COVERS AND ENCLOSURES OF JUNCTION BOXES,AND OTHER A FOR PV DISCONNECTING MEANS WHERE ALL ; _" � -- W o ) ----"s'.- -5TERMINALS OF THE DISCONNECTING MEANS MAY BElf;III- WIRING METHODS;SPACED AT MAXIMUM 10FT SECTION OR WHERE SEPARATED BY ENCLOSURES,WALLS,PARTITIONS, ELECTRIC SHOCK HAZARD ENERGIZED IN THE OPEN POSITION. 3 - CEILINGS,OR FLOORS. TERMINALS ON THE LINE AND [NEC 690.13(B),NEC 705.22] [NEC 690.31(G)(3&4)] BLUE RAVEN LOAD SIDES MAY BE ENERGIZED — IN THE OPEN POSITION _ — — LABEL 8 �� %% LABEL 11 SOLAR PV SYSTEM EQUIPPED FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY tZtt,W PERMANENT DIRECTORY TO BE LOCATED AT 1220 S.630E STE.430 AND CONDUCTORS LEAVING THE ARRAY: - " " i''' AMERICAN FORK,UT 84003 WITH RAPID SHUTDOWN MAIN SERVICE EQUIPMENT LOCATION IF ALL SIGN TO BE LOCATED ON OR NO MORE THAN 3 MAIN DISTRIBUTION UTILITY DISCONNECT(S) ELECTRICAL POWER SOURCE DISCONNECTING "% LABEL 2 TURN RAPID SHUTDOWN POWER TO THIS BUILDING IS ALSO SUPPLIED 800-377-4480 FT AWAY FROM SERVICE DISCONNECTING MEANS (SOLAR ARRAY RAPID SHUTDOWN ,,,,,_)'--=---- -7-----':,-0-,07-11,;:_` • ''',A' AT EACH DC DISCONNECTING MEANS,INCLUDING THE SwirCHTOTHE i1II� FROM A ROOF MOUNTED SOLAR ARRAY WITH SWITCH)ARE GROUPED AND IN LINE OF SITE OF WWW.BLUERAVENSOLAR.COM J `OFF POSITION TO MEANS TO WHICH THE PV SYSTEMS ARE A RAPID SHUTDOWN DISCONNECTING MEANS I �• � DC DISCONNECT AT THE INVERTER. 0 . SHUT DOWN PV SYSTEM CONNECTED AND SHALL INDICATE THE GROUPED AND LABELED WITHIN LINE OF SITE MAIN SERVICE DISCONNECTING MEANS. [NEC 690.53,NEC 690.13(B)] AND REDUCE LOCATION OF ALL IDENTIFIED RAPID SHUTDOWN AND io FT OF THIS LOCATION. CONFIDENTIAL-THE INFORMATION SHOCK HAZARD [NEC 690.56(C)&NEC 705.10]. HEREIN CONTAINED SHALL NOT BE IN THEARRAr SWITCHES IF NOT AT THE SAME LOCATION. MAXIMUM VOLTAGE WCIN 690 56(C)(1)(A)] OF MAX CIRCUIT CURRENT AMPS USED ANYONE FOR THE BENEFIT VE E LABEL 12 SOLAR NOR SHALL T BEN ',,......., --__ ." �---- -- LABEL 9 PERMANENT DIRECTORY TO BE LOCATED AT DISCLOSED IN WHOLE OR IN PART P FOR PV SYSTEMS THAT ONLY SHUT DOWN a SOLAR ARRAY RAPID SHUTDOWN SWITCH TO OTHERS OUTSIDE RECIPIENTS RPV 1 iku ce_ CONDUCTORS LEAVING THE ARRAY: POWER TO THIS BUILDING IS ALSO DENOTING THE LOCATION OF THE SERVICE ORGANIZATION,EXCEPT IN LABEL 3 RA >.viAI �I SIGN TO BE LOCATED ON OR NO MORE THAN 3 SUPPLIED FROM MAIN DISTRIBUTION EQUIPMENT LOCATION IF SOLAR ARRAY RAPID CONNECTION WITH THE SALE AND PHOTOVOLTAIC SYSTEM AT POINT OF INTERCONNECTION,MARKED AT AC TURN RAM RiVIDOWN SWITCH FT AWAY FROM SERVICE DISCONNECTING UTILITY DISCONNECT LOCATED SHUT DOWN DISCONNECT SWITCH IS NOT USE OF THE RESPECTIVE DISCONNECTING MEANS. TODE'OF(POSMONIn MEANS TO WHICH THE PV SYSTEMS ARE GROUPED AND WITHIN LINE OF SITE OF MAIN EQUIPMENT,WITHOUT THE AAC DISCONNECT TO[NEC 690.54,NEC 690.13(B)] SHUT DDEhCONDUCr CONNECTED AND SHALL INDICATE THE SERVICE DISCONNECTING MEANS. WRITTEN PERMISSION OF BLUE CONDUCTORS WITHIN RATED AC OUTPUT CURRENT A THE 0 LOCATION OF ALL IDENTIFIED RAPID SHUTDOWN [NEC 705.10] RAVEN SOLAR LLC. V, EDERGIZED ZEDIN REMAIN SVNUGFfT SWITCHES IF NOT AT THE SAME LOCATION. NOMINAL OPERATING AC VOLTAGE V "' [NEC 690 56(C)(1)(13)] LABEL 13 L � O W' Cl) Q /, ) ® PERMANENT DIRECTORY TO BE LOCATED AT MAIN W W CD a_ CO SERVICE EQUIPMENT DENOTING THE LOCATION 0 z co H O �' LABEL 4 LABEL 10 POWER TO THIS BUILDING IS ALSO SUPPLIED OF THE PV RAPID SHUTDOWN SYSTEM Q CO CJ 0 (` AT POINT OF INTERCONNECTION FOR EQUIPMENT I D SIGN LOCATED AT RAPID SHUT DOWN FROM ROOF MOUNTED SOLAR ARRAY.SOLAR DISCONNECTING MEANS IF SOLAR ARRAY RAPID Z D CD < _J N- CONTAINING OVERCURRENT DEVICES IN CIRCUTS .L DISCONNECT SWITCH[NEC 690.56(C)(3)]. ARRAY RAPID SHUTDOWN DISCONNECT IS SHUT DOWN DISCONNECT SWITCH IS NOT < CD d W co �` SUPPLYING POWER TO A BUSBAR OR CONDUCTOR LOCATED OUTSIDE NEXT TO UTILITY METER. GROUPED AND WITHIN LINE OF SITE OF MAIN 2 [— tf) I— L.t_ d DUAL POWER SUPPLY SUPPLIED FORM MULTIPLE SOURCES,EACH SERVICE j- SERVICE DISCONNECTING MEANS.[NEC 705.10, H 00 z w O 8 SOURCES:UTILITY GRID AND EQUIPMENT AND ALL ELECTRIC POWER PRODUCTION NEC 690.56(C)(1)] U Q 0 f PV SOLAR ELECTRIC SYSTEM SOURCE LOCATIONS. W ° U co [NEC 705.12(8)(3)] O LABELING DIAGRAM FOR MICRO INV.: MAIN SERVICE PANEL O. LABEL 5 PLACED ADJACENT TO THE BACK-FED BREAKER EXISTING SUB PANEL PV COMBINER < FROM THE INVERTER IF TIE IN CONSISTS OF LOAD OO (IF WHERE POINT OF SUBPANEL- INVERTER OUTPUT CONNECTION SIDE CONNECTION TO BUSBAR. INTERCONNECTION IF USED TO COMBINE AC JUNCTION BOX [NEC 705.12(B)(2)(3)(b)] IS MADE) AC DISCONNECT PV OUTPUT CIRCUITS OR AC COMBINER BOX DO NOT RELOCATE O&O O 0 O 0 THIS OVERCURRENT D D IF BREAKER USED DEVICE DD ° O&O 10 0 0 OR 0 IF BREAKER USED � (ONLY IF 3 OR MORE SUPPLY SOURCES TO OR PLACARD 12 OR Z PLACARD C d" ,., _ A BUSBAR) O �5 U_ CO N in SIGN LOCATED AT LOAD CENTER IF IT (ONLY IF PV ( O I- m 6) N ONLY IF PV THIS EQUIPMENT FED BY MULTIPLE CONTAINS 3 OR MORE POWER SOURCES. INTERCONNECTION I ECTIOt NTERCONNECTION I ECTIO� Q o SOURCES.TOTAL RATING OF ALL [NEC 705.12(B)(2)(3)(C)j CONSISTS OF LOAD CONSISTS OF LOAD — 11 OVERCURRENT DEVICES,EXCLUDING SIDE BREAKER) SIDE BREAKER) W' CO 0 MAIN SUPPLY OVERCURRENT o p w DEVICE,SHALL NOT EXCEED u" — - E— LABELING DIAGRAM FOR STRING INV./DC OPTIMIZER INV.: Z m -0 En 0 AMPACITY OF BUSBAR. MAIN SERVICE PANEL INVERTER(S) O EXISTING SUB PANEL PV COMBINER [– 0N o (, (IF WHERE POINT OF SUBPANEL- u) U LABEL 11 INTERCONNECTION IF USED TO COMBINE • -• ' ' 4' 0 SIGN LOCATED AT AC COMBINER BOX FOR O&0 IS MADE) AC DISCONNECT PV OUTPUT CIRCUITS �� ALL MICRO-INVERTER/AC MODULE IF BREAKER USED DRAWING BY INSTALLS(IF APPLICABLE). CI a 1 O O Eric Thomas RAPID SHUTDOWN TEST OORO &� NOT REQUIRED 0 3 DATE O @ OR 0 IF BREAKER USEDV JUNCTION BOX January 29. 2019 OR PLACARD 12 OR 0 OR COMBINER BOX LABELING NOTES: PLACARD 1. LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS.ELECTRICIAN TO O O PROJECT NUMBER DETERMINE EXACT REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND (ONLY IF PV (ONLY IF PV O 1 O O O 59019054 MAKE APPROPRIATE ADJUSTMENTS. INTERCONNECTION NTERCONNECTION ° 2. LABELING REQUIREMENTS BASED ON THE 2017 NATIONAL ELECTRIC CODE,OSHA STANDARD CONSISTS OF LOAD CONSISTS OF LOAD ° 11 19010.145,ANSI Z535. SIDE BREAKER) SIDE BREAKER) O 7 SHEET NAME 3. MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. LABELS 4. LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED(NEC INTEGRATED DC DISCONNECT 110.21] `ELECTRICAL DIAGRAM SHOWN ABOVE IS FOR LABELING PURPOSES ONLY. NOT AN ACTUAL REPRESENATION OF EQUIPMENT AND CONNECTIONS TO BE INSTALLED. LABEL LOCATIONS PAGE NUMBER REVISION 5. LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8",WHITE ON RED BACKGROUND;REFLECTIVE, PRESENTED MAY VERY DEPENDING ON TYPE OF INTERCONNECTION METHOD AND LOCATION PRESENTED ON PV5 OF 3 LINE DIAGRAM. PV5 LINE DIAGRAM TO REFLECT ACTUAL AND PERMANENTLY AFFIXED[IFC 605.11.1.1] REPRESENTATION OF PROPOSED SCOPE OF WORK. PUS 0 BLU .:. RAVEN Enphase Microinverters VIE";f _, i d E 1220 S.630 E STE.430 Enphase IQ 7 and IQ 7+ Microinverters AMERICAN FORK,UT 84003 INPUT DATA(DC) 1Q7-60-2-US/1Q7-60-B-US IQ7PLUS-72-2-US/IQ7PLUS-72-B-US 800-377-4480 e_ ,„ -- — WWW.BLUERAVENSOLAR.COM Commonly used module pairings 235 1;11-'350 W+ 235 W-440 W t Module compatibility 60-cell PV modules only 60-cell and 72-cell PV modules CONFIDENTIAL-THE INFORMATION 1,gh {5`.°fiErtj smart grid-ready Maximum input DC voltage 48 V 60 V HEREIN CONTAINED SHALL NOT BE ThePeak power tracking voltage 27 V-37 V 27 V-45 V USED FOR THE BENEFIT OF _ _ ANYONE EXCEPT lip �� Enphase 1C t • 1 ,rt3� and Enphase IQ1 hl[crw Operating range 16V-48V 16V-60V BLUERAVENSOLARNORSHALLIT _ � Min/Max start voltage 22V/48 V 22 V/60 V BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE n I 7 7 g dramatically simplify the installation process whlie ) IQ 7 s Max DC short circuitcurrenY(module Isc 15 V 15 A achieving g the highest system efficiency. Overvoltage class DC port II II RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE * r +,, DC port backfeed current 0 A 0 A SALE AND USE OF THE RESPECTIVE t a Part of the Enphase 10 t tem,the 10 7 and PV array configuration 1 x 1 ungrounded array;No additional DC side protection required; EQUIPMENT,WITHOUT THE AC side protection requires max 20A per branch circuit WRITTEN PERMISSION OF 10 Microinverters integrate with the Enase —x, BLUERAVENSOLAR LLC. OUTPUT DATA(AC) IQ 7 Microinverter IQ 7+Microinverter I Envoy-,Enphase 10 atlery, the Enphase ,, ... .. Peak output power 250 VA 295 VA _, Maximum continuous output power 240 VA 290 VA L >- p L Enlighten- monitoring and analysis software. Nominal(L--L)voltage/range2 240 V/ 208 V7 240 V/ 208 V/ W W 0 ‹ 211-264 V 183-229V 211-264 V 183-229 V 0 Z � I— O 10 Series Mloroinverters extend the reliability, Maximum continuous output current 1 0 A(240 V) 1.15 A(208 V) 1.21 A(240 V) 1.39 A(208 V) Z c6 0 standards set forth by previous generations andNominal frequency 60 Hz 60 Hz Ur Cr) c� Extended frequency range 47-68 Hz 47-68 Hz ¢ H z undergo over a million hours of power-on testing, I— H LU 0 AC short circuit fault current over 3 cycles 5.8 Arms 5.8 Arms H z > P enabling Enphase to provide an industry-leading Maximum units per 20 A(L-L)branch circuit° 16(240 VAC) 13(208 VAC) 13(240 VAC) 11(208 VAC) 0 o < warranty of up to 25 years_ Overvoltage class.AC part (II Jl W U C.)AC port backfeed current 0 A 0 A • W Power factor setting 1:0 1.0 0 D Power factor(adjustable) 0,7 leading...0.7 lagging 0.7 leading...0.7 lagging f J a CO EFFICIENCY @240 V @208 V @240 V @208 V Peak CEC efficiency ---- -- %---------9-7.6%97,6 97.5`4 ,97:3% � �� CEC weighted efficiency 97.0% 97.0` 97.0% 97.0 Easy to InstallMECHANICAL DATA Ambient temperature range m -40°C to+65°C - _ • L.ghtweegstand simple Relative humidity range 4%to 100%(condensing) • Faster instaltion+rrth srrgarrnr ,righter t - Tire cabling Connector type(I07-60-2-US&IQ7PLUS=72-2-US) MC4(or Amphenol H4 UTX with additionalQ-DCC-S adapter) Connector type(107-60-B-US&IQ7PLUS-72-B-US) Friends PV2(MC4 intermateable). %ter • Built i (NEC 201A& 17) Built-in rapid shutdown compliant Adaptors for modules with MC4 or UTX connectors: m *^ -PV2 to MC4:order ECA-S20-S22 1 -PV2 to UTX:order ECA-S20-S25 Productive and Reliable Dimensions{WxHxD) 212 mm x 175 mm x 30.2 mm(without bracket) kiI!„•`-- - Weight 1.08 kg(2.38 lbs) trr ed for high powered 6D-celand 72-c�1*mules Cooling Natural convection-No fans M • More than a million hours of testing Approved for wet locations Yes • Class II double-insulated enclosure Pollution degree i, PD3 _ • lit listed Enclosure Class II double-insulated,corrosion resistant polymeric enclosure Environmental category./UV exposure rating NEPvMA Type 6/outdoor cr'PHASE - +s' FEATURES 107 Smart Grid Ready Communication Power Line Communication(PLC) Monitoring Enlighten Manager and MyEnlighten monitoring options. >a� • Complies with advanced grid support eol a and Both options require installation of an Enphase I0 Envoy. 1 frequency-ride-through requirements Disconnecting means The AC and DC connectors have been evaluated and approved by UL for use as the load-break . iill disconnect required by NEC 690 t ' • R ely updates to respond to changing grid requirements Compliance CA Rule 21(UL 1741-SA) UL 62109-1,UL1741/IEEE1547,FCC Part 15 Class B, ICES-0003 Class B, • Configurable for varying grid profiles CAN/CSA-C22.2 NO.107.1-01 • Meets CA Rule 21(UL 1741-SA) This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC-2014 and NEC-2017 section 69012 and C221-2015 Rule 64-218 Rapid Shutdown of PV Systems,for AC and DC conductors,when installed according manufacturer's instructions. 10111) *'he P3 7+Micro is required to support 72-cell modules, ED 1.No enforced DC/AC ratio.See the compatibility calculator athttps://enphase.comfen-us/support/module-compatibility: anima 2.Nominal voltage range can be extended beyond nominal If required by the utility. EMS 3.Limns may vary.Refer to local requirements to define the number of microinverters per branch in your area. SHEET NAME To learn more about Enphase offerings,visit enphase,00rn E To learn more about Enphase offerings,visit enphase.com a EN P H AS E. DATA SHEET J 2018 Enphase Energy.All rights reserved.Ail trademarks or brands used are the property of Enphase Energy,Inc. 2018-D5-24 PAGE NUMBER REVISION DS 0 Emallase IQ Combiner- RAVEN Enoh .seThe Enphase IQCon finer+-`' ,*`e :i Enpha'se * s v_nvov' Gt,IISOli€da es inters onn `::'.0#r'; MODEL NUMBER 1220 S 630E STE 430 10 _ AMERICAN FORK,UT 84003 v r r c 7 _ I. : n IQ Combiner+X-1 -AM1-240-2 IQ Combiner+with Enpitase 1 Envoy"for integrated revenue grade PV production metering V h 1 �r pquILII `f in a 1 r rtr C O �.NSIC12.20+/-0..5%)and optional*consumptic mor€tor=ng(+/-2.5%). 800-377-4480 (X- -Af 1`240-2) str- mlinea 0�, and S'O''age !nsta latlOfS [DV ACCESSORIES(order separately WWW.BLUERAVENSOLARCOM Enphase Mobile Connect' CONFIDENTIAL-THE INFORMATION providing din a Consistent, fe-`,°✓ red solute' for CELLMODEM--&3(461 12-year data plan Plug and play industrial gradecedurar modem with data plan for systems up to 60 HEREIN CONTAINED SHALL NOT BE CELLMODEM-01(33 i 5-year data plan) microinverters_(Available in the US,Canada,Mexico,Puerto Rico,and the US Virgin islands,. USED FOR THE BENEFIT OF residential ntial a Fplic-ati rs_ t offers ..;I J fourANYONE RNOEXCERT �'!! � CELLMvEM-M14 LTECAT-Ml{5-year lin). where is adequate cellular in installation area. BLUERAVENSOLAR NOR SHALL IT series onsumptaon Monitoring CT BE DISCLOSED IN WHOLE OR IN 2-pole input .✓cups and _at n BRPART TO OTHERS OUTSIDE CT-200-SPLIT Split core current transformers enable whole home consumption metering*(+-2.5%j. RECIPIENTS ORGANIZATION, bu.soar assembly. Circuit Breakers EXCEPT IN CONNEC TION WITH THE BRK-154-2-240 Breakers 2 pole,15A,Eaton BR215 SALE AND USE OF THE RESPECTIVE Breaker,2 pole,20A,Ea BR220 EQUIPMENT,WITHOUT THE BRK-20A 2-2d0 WRITTEN PERMISSION OF ELErTR ICAL SPECIFICATIONSBLUERAVENSOLAR LLC. Rating Continuous duty c co System voltage 240 VAC,60 HZ W W 0 Q Eaton BR series bustler rating 125 A Ur Z tet' F -Kt Q U 0 Smart Max.continuous current rating(output to grid) 65 A z Q l` CO Max fusefcircuit rating Output) 90 A • Includes IQ Envoy for communication ctfour2- ole Eaton BR series Distributed{ _r.e. filo L`U,I breakers on8 I`rot in: H Z > 1 andcontrol Branch_.oust lar an storage) p I circuit's=so daopt - — ,.-4,<440,-,---,---e-... „ % • Flexible networking supports Wi-Fi, Max_continuous rating(input froml3 Mbd W O O Ethernet,or cellular Max..:oral branch circuit'breaker rating(-input) l;0, (any combination) dn) LU I- • Provides production metering and optional0 . Production Metering CT 200€�solid core pre �tt<I ed and.wired to l Envoy _! I consumption monitoring CO aMECHANICAL DATA • Supports installation of,the __-- v,__ w_ .... Enphase 0 Aggregator Dimensions(WxHxD) 4cl.,a x;b.5 x„.0 cm 09,4°x 18.3`x 6..;'as � Weight 7.S ked(16.51bs) 4,..-,---, . Ambient:temperature range a10�C to+46 r:�;- U to 115°F)'� % . A .i tSimile Cooling Neal convection,plus heat shield • Eaton BR series panelboard interior Enclosure eiwironmental rating Outdoor. RTI.-certified,NEMA type SR,polycarbonate construction • Up to four 2-pole branch circuits for 240 VAC Wire sizes 20 A to 50 A breaker inputs: 14 to 4 AWG copper r conducts ��� � l ` plug-in breakers(not included) • 60 A breaker branch input: 3 to 1/0 AWS copper conductors lc i o� - Main combined out ,rt: 10 to 2/0 AWG copper conductors �` ▪ SO A total PV or storage branch circuits p� � s Neubal and ground: 14 to 1/0-copper conductors Always follow lascal code requirements for conductor sizing. L ... t41 Altitude To 2000 meters(6;5613 feet) �°' Reliable INTERNET CONNECTION OPTIONS • Durable NRTL certified NEMA type Integrated Wi-Fi 502.11bjt}fn 3R enclosure • Five-year warranty Ethernet 80s�2.Cat`E(or Cat a)UTP Ethernet cable-not included UL listedI Cellular Optional,CELLMODEM-Ql(30)or CELLMODEM-03(40)(not included) • COMPLIANCE 4) Compliance,Combiner IN 1741 CAN/CSA C212 No,107.1 47 CFR,Part 15,Class B,ICES 003 Production metering:ANSI C12.22 accuracy class 0.5(PV production) LISTED EN H Compliance,I0 Envoy LH_916 To learn more about Enphase offerings,visit enphase.com CAWCSA 022.2 No.61010-1 *Consumption mornoring is required for Enphase Storage Systems. To learn more aboutEnphase offerings,visit npta S .cum SHEET NAME 0,a r2i I,.. r ,,, t11 rI€=€_�=BBrv. M r;at rinks:x a BftdS VI tt t € J Ir 41;e a t e L ,I r :rte 1 , .I PHA E. DATA SHEET 1e t-c: PAGE NUMBER REVISION DS 0 . . ,.......„ ...„„, . , .. , „ , , MonoMultiMulti Solutions . . , . . i i £ ' , • : .,. '11 !!! I f" A ,:f...,,,,,f.,„, pLus- FRAMED 60-CH L MODULE BLUE RAVEN . , -,.. , , , . , , , . , . • ! ! -1 . - EE • 1 i --___ _,___- _ LEE__ ._ - ....ENE_„,„_________,_„_____,. . ,.. -_,,,,,__, ___,,,, _,, ,, , ,,,,,_ , . . THE 1, , , vvR Ps,r, ELECTRICAL DATA(STC) 1220 S.630 E STE.430 TSM-0005A08(11) I 280-315W TSM-DDO5A.05(11) 275-310W Peak Power Watts-P.MY MO' 275 280 285 290 zas 300 305 310 315 AMERICAN FORK,UT 84003 ,., ,,,,, A . .,.,.. ,..,...,. ...,...„... ..„.... . . i. .„,...,,, _ ,, ,.,, . ,, ..:,. .„., , ., .. ..„,. .„„,„ • ,. .. ... .. . . .„. ., „,,.„ ,..,,. , , , n' U f' row L ,, : : . , . . . . . . . . .. • , . • . . . . Hu • • , POWei Output Toterarte,P.x(W) 0-+5 Maximum Power Voltage-V,,,,w) 31 4 31 7 3113 37.2 3/5 326 3/9 311 333 800-377-4480 VNAANV.BLUERAVENSOLAR COM WAD Wow,or av 0000.6 wows sw Maximum Power Current-lw(A) 8.76 8.84 8.97 9.01 9.08 9,19 928 9,37 ; 946 CONFIDENTIAL-THE INFORMATION • ' - • ' HEREIN CONTAINED SHALL NOT BE FRAMED 60-CELL MODULE , , , . . . Open Circuit Voltage-1,W-(V) 38.4 38.4 38.5 389 39.6 39.8 40.0 402 , 40.5 USED FOR THE BENEFIT OF - , . . . . . . - . : Short Circuit Current-hr(A) 924 9.42 951 9.66 968 9.77 aus 9.94 . 10.0 BLUERAVENSOLAR NOR SHALL IT . . _ . . . . .. . . . . . • ''' ';.* Module Efficiency no(%) 16.8 17.1 17.4 17.7 18.0 18.3 18.6 189 192 BE DISCLOSED IN WHOLE OR IN •1- PART TO OTHERS OUTSIDE , 5TC Err4cLince1000Win,,,CO Termeature.?5K„Air Kass AMIS. RECIPIENTS ORGANIZATION, "Measwn Weta,xe:.t.3% i EXCEPT IN CONNEC TION WITH THE 60 CE.' ,: ,, , : ' ' , ' : . , , . . . , _ , . . , . . . . . . , . . , _ ,.... : i ELECTRICAL DATA(NOCT) SALE AND USE OF THE RESPECTIVE EQUIPMENT,WITHOUT THE . • . . . . _ WRITTEN PERMISSION OF KONOCRYSTALLINE MODULE : : : -; • ' i i $ - / Maximum Power-13,w(Wp) 205 209 212 216 ' 220 223 227 231 235 BLUERAVENSOLAR LLC. , . . . 1111 6 A A ---.- „---------- ''' 1 1 , Maximum Power veitagew,e(V) 29.1 29.4 29.5 29.9 30.1 302 305 30.7 30.9 • ' • ' ' ›- Maximum Power Current-lw(A) 7.04 7.10 721 724 730 738 7.46 7.53 7.60 -...a. co -rd' 5- ri r • r r r t"a, VO..C., Open Ci rain Vottagedir.(V) 35.7 35.7 35.8 362 36.8 370 37.2 374 375 LJ.J 1-1-1 'Y' o `4' •:t. 0 Z '1. F- -I •q* POWER OUTPUT RANGE ,, .. , Short Circuit Currentto(A) 7,46 7-51 7.68 7.130 7.82 7.89 7.95 8.03 8.10 D c5) < (I) 1-- , , 12......, : 57(1-Wa6.3,Ke at aCCWIne.Arabtent Temperatwe ZaT.WinCSmetlImis < 0 ."1- ct z oo. tdECI!ANI(AL DATA H p.., (v) OD t•-•% I ci 2°/0 ... . 35/138 997/311 V Volot-4,0 0, Solar Cells Monocrystalline 156.75.156.75 mm(6 inches) LI-1 0 0 In eakic view MAXIMUM EFFICIENCY eyt, Maximize limited space wit!"top-end efficiency Cell Orientation 60 cells(6.10) ,. .4- -!' '00 0.1 0000 ArT power uonsity Ilf043 ___...... _ _____ 'II.... IX - Module Dimensions 1650.992.35mm(65.0.39.1.1,38 inches) -J -L - .Low tnerrinal coeitic-wits for greater energy production at high CL CO . i Weight 18.6 kg(41.0 lb) operatinn temper at ices - 0 ,ji-J SW ,,,-„,„„- ,,,,,! :,,,, _. „ Glass 3.2mm(0.13 inches),High Transmission.AR Coated Tempered Glass ii POSITIVE POWER TOLERANCE ii. Backsheet White[0005A,0801)j: ' ', .,1 __.,.. Highly reliable due to stringent quality control , , , -- Black[0005A.0501)] Over 30 in-house tests(UV,TI,HI,and many more) 3543.38 Frame Black Anodized Aluminium Alky(01105A.0800,6005A.05801 •••,,,,r.a,.1,n L4:-..,,,i-.i,--.,a SO,,,....f,:-.,''',,, uttow P`,,, '.. :;'.. , , - .in-house testing goes weil beyond certificaUdo requirements oki/o 1.Bos - - iP 67 or IP 68 rated ,.::,.prenensive sol ,: - "1Y ...---xnerrappararratil PA' ,,. , .Pip resistant Cables Photovoltaic Technology cabie 4.0mre(0,006 inches?), )),...al to success.trim)WO- , a,distils,- 'a .10055 EL double inspection i a products 51 ww,Pe COUr:- .r.,...1fl is at*lot/twat,oar dub ii'.f, s A t Selective emitter,advanced surface texturing I V CURVES OF PV MODUL P(1105W) 1000 mm(39.4 inches) ,acn castomm in Cod,market and stir trlt a ant _wt._ Connector - _ 'Irina TS4 it'v.),:ative,£,daDe Product;with we s,-1 ay-) www ,s ,-,-:,),:nitted to 63ild`on strategic,matuaw wria Certified to withstand the most challenging ---' Type 1 or Type 2 -c,loficial collaWaptrUnwith installers.do‘, yew i':44162X environmental conditions 3 \ \ Fire Type slat;itddorS and ottco poi ti iv?",".., VIAV . us 2400 Pa w \ind load W *0 55 TEMPERATURE RATINGS MAXIMUM RATINGS ..'5400 Pa snow;Dad i Comprehensive Products 35 mm hail stones at 7 km/h Noctiko,Caa,t,,g Cell Thaparataa) 445C(±25C} Operational Temperature -40-.85°C - 9 . a la aa ,a a, a, Temperature Coefficient of NY.% -0.3945/5C Maximum System Voltage 1000V DC(IEC) And System Certificates yon Temperature Coefficient of tha -029%/C 1000V DC(UL) 161215/1EC51730151.17030ECL17000t 62a18 P.-V CURVES OF PV MC;)tii.,..,..r',`,", -S.0 9,Xn:Quality Managerawd System Temperature Coefficient of isc 0.05%/c Max Series Fuse Rating ISA(Power 8285W) ,,.. Dtt 14001:Enviromnentalmanlmeor System mu ?OA(Power 1290W) 1.114064:Greenhouse gases ErrisslawsWerifiragort 0140AS ISOM:Occupation Heditn wd Safety wr tt. MO NOT connect Fg,0 Colrbiner Box withlwo or more wings i,, Martagetr*nt S,..-ietem LINEAR PERFORMANCE WARRANTY g 1. . ,,,,,,,,,„, paratelcoonection} te c10 Year Product Warranty°25 Year Linear Power Warranty __,.... us „ -"..', IA WARRANTY PACKAGING CONFIGURATION .4.= IM1 :Ststs, ' . sal 10 year Product Workmanship Warranty Modules per box:30 pieces - . .. - ......,.. l.: . .iiiiiillialM3lillla-aor-.- ii i iiiil .. „ ,two.3,wersermw to rradwwwww.1 y..0., ii 29liiorc .. ii, -ii.ieg,o, zs year Phew Power Warranty -, Modules per 40 container:1340 meres l*el 2, < .- ),f, rrjrigr.:2.',C"ns ,„.• )..4));.,.,_.,,,,,,, ___, ._„ -,..- ... - , - Tr , CAUTION;READ SAFETY/SAD INSTALLATION INSTRUCTIONS BEFORE USING THE PRODUCT, , .,.. 1,,, 4,44,..Nt 0 i inasolar a T:ioa LIHO.c”Vixit?,,Ity St4ndard Step wan4my „, ........ Irina-solar .2017 Irina Solar Limited.All rights reserved,Specifications included in this datasheet are subject to change without notice. version number;TSM_EN.,..2018_A www.trinasotancom SHEET NAME DATA S H E ET PAGE NUMBER REVISION DS 0 BLUE RAVEN .. .,_ . , _ , , S la FLA PV RO F=MOUNT COMBINER/i:NCLOSURE �k c .. , � 220 S.630 E STE.430 �j��� AMERICAN FORK,UT 84003 Basic Features 4� 800377-4480 • Stamped Seamless Construction WWW.BLUERAVENSOLARCOM • 18 Gauge Galvanized Steel / CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE • Powder Coated surfaces USED FOR THE BENEFIT OF • Flashes into the` roof deck ANYONE EXCEPT • 3 Roof deck knockouts .���, .75��, I�� � �� BLUERAVENSOLAR NOR SHALL IT C s BE DISCLOSED IN WHOLE OR IN • 5 Centering dimple$ kir entry/ex PART TO OTHERS OUTTIOE Ilttln(7$ Cr G�ndl!!t / EXCE TRECI IIN CONS OEPIENT CRTION WITHTIANIZAOTHE y --al SALE AND USE OF THE RESPECTIVE LIJ • 2 Position Ground lug installed EQUIPMENT,WITHOUT THE �A L1 WRITTEN PERMISSION OF • Mounting [Iardware Included BLUERAVENSOLAR LLC. SolaDeck Model SD 0783 a >- - � � � W ,t' Q Q SolaDeck UL.50 Type 3R Enclosures c� � .....1 N: Z 0 U- Q d Available Models: < • Z c`? Model SD 0783 (3"fixed Din Raii} W o I— ~ co z •> co - Model SD Q786 (6"slotted Din Rail) U O p Q O) cc U W • J SolaDeck UL 1741 Combiner/Enclosures a m Models SD 0783 41 and SD 0786-41 are labeled and ETL listed UL STD 1741 according to the UL STD 1741 for photovoltaic combiner enclosures. � Max Rated 600VDC, 120AMPS 6-4 '�999 Model SD 0783-41 3" Fixed Din Rail fastened using Norlock System f y y " Typical System Configuration 4 Din Rail Mounted Fuse Holders 600VDC 30 AMP - 1-Power Distribution Block 600VDC 175AMP 1-Bus Barwith UL lug Model SD 0786-41 6"Slotted Din Rail fastened using steel studs **Typical System Configuration 4-Din Rail Mounted Fuse Holders 6QQVDC 30 AMP 4-Din Rail Mounted Terminal Blocks 99„- 99999 -9----,„-------9*999,.-091.: Bus Bars with UL lug "Fuse holders and terminal blocks - 9999 ��� added in the field must be UL listed or recognized and meet 600 VDC 30 AMP s 110C for fuse holders,600V 50 AMP2 ,,, 90C for rail mounted terminal blocks s t tl and 600 V 175 AMP 80C for Power �` Distribution Blocks. Use Copper Wires :" Conductors. , Cover is trimmed to allow Model SD 0783 41,wired with Model SD 0786-41,wired with conduit or fittings,base is Din Rail mounted fuse holders, Din Rail mounted fuse holders, center dimpled for fitting bus bar and power distribution terminal blocks and bus bars. locations. block. ise.) 1-0, 4w 4 is s-',.4„... 44444: SHEET NAME RSTC Enterprises, Inc • 2219 Heimstead Road•Eau Cliare, WI 54703 DATA SHEET For product information call 1(866) 367-7782 PAGE NUMBER REVISION DS 0 .:� ; U RAVEN VEN ME : 11N .,r,,, SYSTEM BONDING & GROUNDING :. " : usu : IrAME 1220 S.630E STE 430 AMERICAN FORK UT 84003 su r' D b`A ' PAGE 800-377 4480 WWW.BLUERAVENSOLAR COM '.,arrrrrr rrrrrarrrrerrrrs rarirrrr CONFIDENTIAL THE INFORMATION � `:: � aI`- � m� ®—Aim H USED THE BENEFITOF HEREIN SHALL NOT BE E y • ANYONE EXCEPT 11111 ! BLUERAVENSOLAR NOR SHALL IT I j c; BE DISCLOSED IN WHOLE OR IN IPART TO OTHERS OUTSIDE N MEM 1 ' EXCEPT RECIPIENTS CONNECOTION WITHOTHE IIIII M X40 , SALE AND USE OF THE RESPECTIVE � ;!. ,fir EQUIP4IENT,WITHOUT THE I. - wr=-. --«sw_- —�.� - .. MINI e� Js e 1 } fit' BLUERAVENSOLAR LLC. WRITTEN PERMISSION OF j � i lit 1 iiiii i ~ www O 00 NMI i . o 0Z 't E- -, � 111111 Z D cC rn UQ u < 0 d- f Z c3 V all 111: "` "` ` T.__ E-W BONDING PATH:E-W m:00....... 400 module bonding 2 H in H W op iiiiij_ is accomplished with 2 pre-installed bonding clips v 0 0 i I_.iiiiri which engage on the secuthe MicrorailTM w v w and splice. o EINI _1_ a. co I I a I ; I E I gI ; I IJ i s I ' 1 ` 1 I I I gl I I. I I I I1 I Star Washer is . WEEB . G �, .�. Single Use Only Sir ' Use my �' ,,,,00, 1000000.4100.. TERMINAL TORQUE, Install Conductor and a 464 torque to the totlowing: 'E MINA i,TORQUE, TERMINAL TORUE, . :;$•„ .,4t-op - AWG: 55in-Lbs Install Cor ctor and Install Conductor and -s AWG:25 in-lbs torque to thefollowing: torque to the following: I 10-1 AWG:20 in-Lbs 14 A - Sin-Lbs 6-14 AWG:7 t-Lbs N-S BONDING PATH: N-S system bonding is LUG DETAIL & TORQUE INFO LUG ETAIL & TORQUE INFO LUG DETAIL & TOROUE INFO accomplished through a N-S bonding clip.Insert each Ilsco Lay-In Lug (GBL-4DBT) !Esc() Flange Lug(SGB-4) Wiley WEEBLug (6.7) end of the N-S bonding clip onto a module frame • 10-32 mounting hardware • 1/4"mounting hardware • 1/4" mounting hardware flange k=stem is banded with a single array edge, • Torque = 5 ft-lb • Torque = 75 in-lb • Torque = 10 ft-lb however fr Is recommended that -S bonding �` AWG 4-14-Solid or Stranded • AWG 4-14-Solid or Stranded • AWG 6-14-Solid or Stranded m • installed on both for ease of maintenance OTE: ISOLATE COPPER FROM ALUMINUM CONTACT TO PREVENT CORROSION s -e za ; Maintenance ;Nage 5) System bonding is accomplished through modules. System grounding accomplished by attaching a ground lug to any module SHEET NAME DATA SHEET at a location on the module specified by the module manufacturer. PAGE NUMBER REVISION DS 0 j Intertek AUTHORIZATION TO MARK B L U E R A This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) , 1220 S 630 E STE 430 Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing " AMERICAN FORK,UT 84003 Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing 800-377-4480 Report. WWW BLUERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be HEREIN CONTAINED SHALL NOT BE applied only at the location of the Party Authorized To Apply Mark. USEDiANYX ed O THEBENEFIT OF BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE Applicant: Unirac, Inc Manufacturer: Jiaxing Pacific Energy Equipment Corp. RECIPIENNTSTSORGANIZATION,, EXCEPT IN CONNEC TION WITH THE No. 8 Haiwan Ave SALE AND USE OF THE RESPECTIVE 1411 Broadway Blvd NE Hangzhou Bay Bdao New Area EQUIPMENT,WITHOUT THE Address: Address: WRITTEN PERMISSION OF Albuquerque, NM 87102 Haiyan Economic Development Area BLUERAVENSOLAR LLC. Jiaxing City, Zhejiang Province Country: USA Country: China W W ( o 00 Klaus Nicolaedis Lili Zeng z d" 0 _-__‘1 •i- Contact: Jason Mayfield Contact: George Huang Z rn H 0 ti ti 505-462-2190 510-979-1920 < C� 1- Q LU o Phone: 505-400-2949 Phone: 650-799-7627ir) I- UJ O FAX: NA FAX: NA H c�0 O < o0 klaus.nicolaedis@unirac.com Izeng@ccmfg.com LiJ Email: Email: - U) 1_11 jasonm@unirac.com george@ccmfg.com 0D Party Authorized To Apply Mark: Same as Manufacturer a m Report Issuing Office: Lake Forest,CA Control Number: 5003278 Authorized by: "/ ` for Dean Davidson, Certification Manager GUS x,� ; Intertek This documentsupersedes all previous Authorizations to Mark for the noted Report Number. This Authorization to M ark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client.Intertek's responsibility and liability are limited to the terms and conditions of the agreement.Intertek assumes no liability to any party,other than to the Client inaccordance with the agreement,forany loss,expense or damage occasioned by the use of this Authorization to.Mark.Only the.Client isauthorized to permit copying or distribution of this Authorization to Mark and then only in its entirety.Use.of Intertek's Certification mark is restricted tothe conditions laid out in the agreement and in this Authorization to M ark.Any furtheruse of the Intertek name for the sale or advertisement of the tested material,product or service must first be approved in writing by Intertek..Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the agreement,they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. Intertek Testing Services NA Inc. 545 East Algonquin Road,Arlington Heights, IL 60005 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 UL 2703 Issued:2015/01/28 Ed: 1 Mounting Systems, Mounting Devices, Clamping/Retention Devices, Standard(s): and Ground Lugs for Use with Flat-Plate Photovoltaic Modules and Panels Photovoltaic Mounting System, Sun Frame Micro Rail- Installed Using Unirac Installation Manual, Rev Product: PUB2017FEB16 Brand Name: Unirac SHEET NAME Models: Unirac SFM DATA SHEET ATM for Report 102393982LAX-002 Page 1 of 2 ATM Issued: 2-Mar-2017 PAGE NUMBER REVISION ED 16,_315(1-Jul-16)M andatory DS 0 1 gof �� I M _ ills le° � $ TOOLS & ASSEMBLY DETAILS 1111.111° GRACED y__ MI' kiL o f o t ti TEC O TA SHEET PAGERAVEN k xA � Y TOOLS REQUIRED OR RECOMMENDED FOR Esse-6:w DER LAYOUT&INSTALLATION: v =_.w q .. „`.KK� .z�` 'x. ,«t�z �'.,szf �,.; ..,•< t r,s, "'�` za,Itr `- :° � r*;�' x ,,L•4.mac-•' ,x#!'= `r t",,, ,z :,. _, -.,: <, ,,t , i r.;; ---'a ��`„ot.O. ”, ,,s •, *+,,.. E AMERICAN FORK.UT 84003 TAPE MEASURE 1220 S 630E STE 430 t'Cd.. }, ,+" ✓gw =;,,,v,..4,i� k ', +* -•. it �` ,,,,-ort.,..,�.... .CHALK LINE £.< R s . t i{$ yy2'` �' v : • ... .,. 800-377-4480 ' ,<<`` `✓ yr , t 3 a HAROMMERFING CRAYON WWW.BLUERAVENSOLAR.COM a ¢ • I -"S : ° ^i.. ,- ;�.. '�'x - ae ' * •moi *,,A`x ^,. HAMMER -r"tin .x �� ;, x� a CONFIDENTIAL THE INFORMATION y"' t j COMPATIBLE SEALANT AND DISPENSER f a mfr4 *lt f`f vt• , ' I rtc DRILL WITH EITHER 1/%"BIT FORGRKAND �^ HEREIN CONTAINED SHALL NOT BE '`` ,#a,> _ .� ` :4-4• ±1+,^ "" USED FOR THE BENEFIT OF fr ' ` UNIRAC CUSTOM STRUCTURAL SCREW,OR 7/32` ANYONE EXCEPT €a �° i BIT FOR LAG BOLT BLUERAVENSOLAR NOR SHALL IT t # ..a` '• DRIVER SOCKET(OPTIONAL rra' BE DISCLOSED IN WHOLE OR IN .',.' , ,i� 2• 14401'-x' mss. ,;. =4 •0-,1,:-., f MPACTWITN! S «`4: . c, 3 �t e. ,,,..4•,'„v. �$a , ":°:'. •t r Y;+ HEX DRIVER FOR UNIRAC CUSTOM STRUCTURAL . PART TO OTHERS OUTSIDEca< r r t + f. y�r x ak RECIPIENTS ORGANIZATION, i* om, ' SCREW) % ` a n NNEC TION WITH THE �+ y' �r� '�� �` r`" � � y, »v< .. , '�. , t� : EXCEPT IN CO ' r' ` ,'.' _ SALE AND USE OF THE RESPECTIVE •,, ; • ' ,�,« ' 1 ''' ., ;;''fir :` : 'q` •' ,: 1 SFM RAISED SEAL FLASHING COMPON€NTS: EQUIPMENT,WITHOUT THE ,L \',",..''.04 rirtf3'11. .47f,): , r r • _,� „ s t { 1.FASTENER: WRITTEN PERMISSION OF t a + s e r art it,,,,,„:',,'''',:.:4;11.< '',,l,":1‘. #�' •LAG BOLTS/1,F BLUERAVENSOLAR LLC. lC �l i. '" z „'6 4,xsb, 5 . yi 4.,'f,:. Rglite 7'W,, t',* ?Vlft**AP(Llt% .:t a -,li.O - , k: f-,,'s / ,�. t a.': ' } � v•'s •UNIRAC CUSTOM STRUCTU Wal SC 571 ' � ��- . •GRK STRUCTURAL RAL SCREW,5/1 ' r TABLE OF CONTENTS: PG INSTALLATION NOTES: L i j O LI-O CO Q 't 2.5/16'ID EDPM SEALING WASHER LLI d Tools&Assembly Details 1 A.It is not necessary or advisable to use nails or other fasteners to secure the perimeter of the flashing. z Quick.Steps for Installation 2 3.SFM MOUNT ASSEMBLY(VARIOUS)WITH SLIDER B.The SFM Raised Seal Flashing is made to work with standard and high-defimbon composition/asphalt and (L r ~ Q • 4.SFM RAISED SEAL FLASHING wood shingle roofs with 5`to 5.5/8'courses ¢ OD U Cl) Z Q S.COMP SHINGLE ROOF C Mounts should not be installed in areas of the roof susceptible to ice damming.Ponding water can travel < (� z upward under shingles and reach the bolt penetration. LS} H LLj C3 D.Fastener length specification and capacity verification are the responsibility of the installer. O O Q W U U --) co W PUB2017JAN11 Q uj J CO in ill 1; SU ' QUICKINSTALLATIONSTEPS - � LAS MUTATION T • rDE PAGE 7.--At,-0 ----,--r04.Z.1%1%i;4-.°''''44 ' 'TWO'O''''''-974tO,-• PO.:.',;'O.,;‘°7°,`_ro. _otOotoOO,:aioo_,,b,2.oio".. `•S err , +�'-•, �>�'� a %� 110e1 > .§ `�tzu i a ,fes ' '�. 1 fliii;#4,44,:ttii,'t-41 ,:-,"'--,---':'-;tilirt;t444,-441-0* 11..4:441-ilattOtto.iget., :**4411-q,--,4„,.,-„wilgt PREPARING SHINGLES: Use roofing DRILL PILOT HOLES: Holding the drill ROOF SEALANT: Fill pilot hole with OPTIONAL SEALANT ON FLASHING: bar to break seals between 1st and square to the rafter,drill 3"deep pilot appropriate sealant. Apply a circle shaped bead of sealant 2nd,and 2nd and 3rd shingle courses. hole into center of rafter using 1/8" around the attachment hardware hole Be sure to remove all nails to allow aircraft extension bit for 5/16'GRK. of the flashing before insertion Do correct placement offlashing.See SFM or Unirac Custom Structural Screw,or not use excessive sealant. installation guide for.proper flashing 7/32'aircraft extension bit for 5/16' placement. lag. 1,1,!-;-;4?: )2, : �` . gam � . POSITION FLASHING: Slide the PLACE SLIDER: Place slider with INSTALL FASTENER & TIGHTEN: COMPLETE FLASHING INSTALLATION: not up underneath the 2nd course assembly over the flashing flute, Install fastener with sealing washer. Repeat previous steps to install all of shingles,so that the bottom edge ensuring that the slider sits flat on the Swivel the slider to gauge proper mounts. of the flashing does not overhang the flashing surface. torque when driving the fastener. downslope edge of the 1st course of Tighten until slider stops: swiveling SHEET NAME shingles. easily. DATA SHEET PAGE NUMBER REVISION DS 0