Report (26) mE._c: 1-0\C - 00 v3 9S-k- TRANS' Submittal RECEIVED FEB 212019 Prepared For: Date:February 11, 2019 CITY OF TIGARD • Latimer HVAC BUILDING DIVISION Customer P.O. Number: Customer Project Number: Sold To: Job Number: Job Name: Triangle 3 Suite 401 TI- Controls Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval. Product Summary Qty Product 1 Variable Air Volume Fan Powered Terminal Units The attached information describes the equipment we propose to furnish for this project,and is submitted for your approval. Product performance and submittal data is valid for a period of 6 months from the date of submittal generation. if six months or more has elapsed Kyle Wolf between submittal generation and equipment release,the product Trane performance and submittal data will need to be verified. It is the 7257 SW Kable Lane customer's responsibility to obtain such verification. Portland, OR 97224-7181 Phone: (503) 620-8031 Cell: (503)828-6788 Fax: (503)639-1454 J:IJOBSI124176117121Triangle 3 Suite 401 TI-submittal 2019-11-02.doc Table Of Contents Product Summary 1 Variable Air Volume Fan Powered Terminal Units(Item Al) Tag Data 3 Product Data 3 Mechanical Specifications 4 Unit Dimensions 8 Accessory 9 Field Wiring 12 Field Installed Options -Part/Order Number Summary Variable Air Volume Fan Powered Terminal Units 14 Triangle 3 Suite 401 TI-Controls February 11,2019 Tag Data -Variable Air Volume Fan Powered Terminal Units (Qty: 1) Item Tag(s) Qty Description Model Number Al No Tag 1 VAV Fan Powered Terminal Units VPEF0500P**DD04AD210-L-WWF03021W-00 0 Product Data -Variable Air Volume Fan Powered Terminal Units Item: Al Qty: 1 Parallel with electric heat 5" (127 mm) 02 super quiet fan 1/2" [13mm] matte faced insulation Flanged connection 277/60/1 motor voltage Single speed motor w/SCR DDC with on/off electric heat control Standard actuator Left hand controls connection Disconnect switch Power fuse 480 volt, 3 phase 3.0 kilowatt 2 stages of heat-equal increments 24vac magnetic contactors Electric heater air flow switch 1 Digital display zone sensor(Fld) 1 Zone CO2 sensor(wall mount) (Fld) FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 3 of 14 Others Triangle 3 Suite 401 TI-Controls February 11,2019 Mechanical Specifications -Variable Air Volume Fan Powered Terminal Units Item: Al Qty: 1 General Unit Information Casing -The unit casing is 22 gauge galvanized steel. Outlet duct connection is flanged. Total metal encapsulation of all insulation edges. Hanger Brackets provided. Side access is provided. Filter-A filter is provided on the plenum inlet. Agency Listing - UL and Canadian UL listed as environmental air terminal unit. UL Control#9N65. All Trane terminal units are AHRI 880-98 certified. General Unit Clearance Leave a minimum of 36"on control box side of unit for adequate service access.Allow at least 12"on remaining sides for unit clearance.A minimum of one and one half duct diameters of straight duct work, upstream of the air inlet connection, should be present for optimum airflow measurement performance.Upstream duct work should be the same diameter as the primary inlet connection. Electrical Installation Information For electrical connections, consult field wiring section &equipment IOM. IMPORTANT: Field Wiring Most fan-powered VAV terminal units with electric reheat require a neutral connection from building power, however, some configurations do not. In order to prevent a building wiring issue once the boxes are installed,the wiring diagrams and field wiring installation for each unit MUST be checked to determine whether the neutral is required or not required. 1/2" Matte -Faced Insulation The interior surface of the unit casing is acoustically and thermally lined with 1/2", 1.8 lb/cu. ft composite density glass fiber with high density facing. The insulation is UL listed and meets NFPA-90A and UL 181 standards.All insulation options will meet the 25/50 smoke developed and flame spread rating (per ASTM E 84 and UL 723 and CAN/ULC S102-M88) Meets NFPA-90B. The insulation R-value is 1.9.All cut edges of insulation are completely encapsulated in metal to prevent erosion. Air Valve& Fan Description (Parallel) (Series) The air inlet connection is an 18 gauge galvanized steel cylinder sized to fit standard round duct. A multiple point, averaging flow sensing ring is provided with balancing taps for measuring airflow within +/-5%of unit cataloged airflow. Also provided with each unit is a calibration chart indicating airflow versus flow sensor pressure differential. The damper blade is constructed of a closed cell foam seal mechanically locked between two 22 gauge galvanized steel disks. The damper blade assembly is connected through a cast zinc stub axle and shaft supported by self lubricating bearings.The shaft is cast with a damper position indicator. The valve assembly includes a mechanical stop to prevent over stroking. Air valve leakage <1% at 4". 1002SQ Air Valve/Fan Combination Size (Parallel) (Series) 5" inlet designed for up to 350.0 cfm. Fan is 510.0 cfm. • Fuse Any electric heat unit with a calculated MCA greater or equal to 30 will have a fan fuse provided. Motor Single Speed, direct drive induction, permanent split capacitor type. Thermal overload protection provided. Motors will be designed specifically for use with an open SCR which is standard. Motors will accommodate anti-backward rotation at start up. Motor and Fan assembly are isolated from terminal unit. Electric Heat Coil Factory provided and mounted. Resistance open-type heater, a disc-type automatic thermal primary safety device and manual reset load thermal secondary device. Heater element material is nickel-chromium. The heater terminal box is provided with knockouts for customer power supply. Terminal connections are plated steel with ceramic or phenolic insulators.All fan-powered units with electric reheat are single-point power connections. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 4 of 14 Others Triangle 3 Suite 401 TI-Controls February 11,2019 Magnetic Contactor An electric heater 24 volt contact for use with Direct Digital Control (D.D.C.)or Analog Electronic VAV Controls. Transformer The 50 VA transformer is factory mounted in the fan control box to provide 24 VAC for controls. SCR-Variable Fan Speed Control Switch The SCR speed control device allows the operator infinite fan speed adjustment so the fan output may be modified to achieve exact CFM requirements. Power Fuse Fuses provided on all energized lines of incoming power to interrupt circuit overcurrent conditions. Power Disconnect Switch (for VSEF &VPEF) A factory provided interlocking door disconnect switch located on the electric heater control panel. Airflow Switch An air pressure device designed to disable the heater when the unit fan is off. Flanged Connection A rectangular opening on the unit discharge to accept a 90 degree flanged duct work connection. System Communications The Controller is designed to send and receive data from a Central Control Panel or other Tracer family products, or a VariTrac CCP. Current unit status conditions and set points may be monitored and/or edited via this data communication feature. The network type is a twisted wire pair serial communication. Set points in Nonvolatile Memory(9 Thru 15) 9. Heating Set point Offset-This determines at what point the 1st. stage of reheat turns on. Expressed in degrees below cooling set point, only applicable when local thumb wheel is enabled. 10. Zone temperature, auxiliary temperature, and zone set point calibration corrections(+/- 10.0 F). 11. Flow measurement calibration correction (50 - 150%). 12. Cooling Set point Low Limit-Applies low limit to programmed occupied cooling set point or zone sensor cooling set point(30.0 F- 100.0 F). 13. Heating Set point High Limit-Applies high limit to programmed occupied heating set point or zone sensor heating set point(30.0 F- 100.0 F). 14. RTD/Thermistor-Determines what type of zone temperature sensor will be used. 15. Occupied and Unoccupied Outside Air Requirements- Determines the percent of outdoor air required in the zone for air quality requirements. D.D.C. Floating Point Actuator Trane 3 wire, (open,close,common)26GA when 6-pos amp connector is used for Tracer UC210,VV550,or VAV UCM, otherwise 18GA wires are used. 3.4 VA, 1.7W, 24 VAC, 50/60 Hz. Quarter turn control actuator with linkage release button.Actuator has a constant drive rate independent of load, a rated torque of 35 in-Ib, a 90-second drive time and is non-spring return.Travel is terminated by end stops at fully opened and closed positions. An integral magnetic clutch eliminates motor stall. An integral 3 screw terminal block is provided for field wiring. Operating temperature 32.0 F to 125.0 F. Additional Status Information (1 thru 8) In addition to the above set points,the following status information can be transmitted to the Command Control Unit and Tracer. 1. Active cooling temperature set point. 2. Active heating temperature set point. 3. Current unit primary airflow. 4. Current zone temperature. 5. Re-heat status(On/Off). 6. Auxiliary Air Temperature-Available only if the unit has an auxiliary temperature sensor. 7. Failure Indicators-The U.C.M. will indicate the following: *Temperature Sensor Failure *Flow Sensor Failure *Local Zone Sensor Set point Failure 8. Ventilation Ratio. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 5 of 14 Others Triangle 3 Suite 401 TI-Controls February 11,2019 Direct Digital Controller The microprocessor based terminal unit controller provides accurate, pressure independent control through the use of a proportional integral control algorithm and direct control technology. The controller monitors zone temperature set • points, zone temperature and its rate of change, and valve airflow, using a differential pressure signal. Optionally, the controller can monitor either supply duct air temperature or CO2 concentration via appropriate sensors. The controller and pressure transducer are installed and factory wired in an enclosure with 7/8"knockouts for remote control wiring.A • Trane zone sensor is required. Override Commands The following override commands may be received by the Unit Control Module (U.C.M.)from the Tracer System. Control Mode, Action, &Offset(1 thru 12) 1. Control Mode-The U.C.M. Control Mode may be edited from occupied to unoccupied to accommodate night setback/setup. 2. Control Action-The Control Action may be edited from cooling to heating, changing the primary air damper to a heating source. This will accommodate a cooling/heating changeover system. 3. Control Offset- Enabling Control Offset will increase the cooling temperature set point and decrease the heating temperature set point by a control offset value stored at the U.C.M. This function facilitates demand limiting in the occupied mode. 4. Drive damper fully open. 5. Drive damper fully closed. 6. Drive damper to maximum airflow set point. 7. Drive damper to minimum airflow set point. 8. Disable unit fan. 9. Disable unit heat. 10. Reset- Enabling the reset function forces the controller and the flow sensor to recalibrate. 11. Programmable hot water valve drive time. 12. Programmable air valve drive time. Following Unit Set points The following unit set points reside in the U.C.M. in nonvolatile memory. These set points are editable from the Command Unit or Tracer via the communications link. Set points in Nonvolatile Memory(1 thru 8) 1. Occupied cooling temperature set point 60.0 F -80.0 F. 2. Occupied heating temperature set point 60.0 F-80.0 F. 3. Unoccupied cooling temperature set point 60.0 F- 100.0 F. 4. Unoccupied heating temperature set point 30.0 F - 100.0 F. 5. Minimum cooling flow set point(0, 10- 100% of unit equivalent cataloged airflow). 6. Minimum heating flow set point(0, 10- 100% of unit equivalent cataloged airflow). 7. Maximum flow set point(0,10 - 100% of unit equivalent cataloged airflow). 8. Fan Control Offset-This determines at what operating point the fan in a parallel fan powered unit is energized.This can be specified as a function of temperature, degrees above heating set point, or primary airflow. 0.0 F - 10.0 F or 0, 10- 100%of unit equivalent cataloged airflow). Set points in Nonvolatile Memory(16 thru 21) 16. Series Fan Configuration-allows option of series fan powered box to shut off fan and close air valve when unit is unoccupied. Fan will operate in unoccupied mode if reheat is active. 17. Heating set point low limit. 18. Cooling set point high limit. 19. Local heating flow set point enable/disable&set point. 20. Auxiliary analog input mode select for either auxiliary temperature sensor or CO2 detector. 21. Binary input mode select for either generic or occupancy detector. Additional Status Information (9 thru 12) 9. Fan Status (on/off) 10. Calibration Status (calibrating/not-calibrating) 11. BIP state 12. CO2 Concentration-available only if the unit has an auxiliary CO2 sensor. This mode and auxiliary air temperature are mutually exclusive. DDC Sequence of Operation FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 6 of 14 Others Triangle 3 Suite 401 TI-Controls February 11,2019 The unit controller continuously monitors the zone temperature against its set point and varies the primary airflow as required to meet zone set points. Airflow is limited by minimum and maximum airflow set points. Parallel Unit Fan Energization • As the zone temperature reaches the heating set point, the microprocessor controls airflow to the heating temperature set point and energizes the auxiliary fan when necessary. At or below the heating set point, reheat is energized. The heating minimum airflow set point is factory set, field adjustable, and is separate from the cooling minimum set point. Parallel unit fan energization is a function of primary airflow or zone temperature. 1. Primary Airflow-The fan energizes when primary airflow drops below the fan set point airflow.The fan automatically starts when the zone temperature drops to the heating temperature set point. 2. Zone Temperature-The fan energizes when the zone temperature drops to a selectable number of degrees above the heating temperature set point. DDC Controls Option DD04, DD14, DD44& DD74 Basic Operation: On/Off Staged Electric Heat(Normally Open Outputs) (DDC/UCM) (Parallel Units) A voltage signal from the zone sensor indicates the zone temperature is used by the unit controller to determine an error from the set point. This error, as well as primary flow differential pressure, is used to determine damper position within minimum and maximum cooling airflow set points. As the zone temperature drops to the heating set point, primary airflow is controlled to minimum heating flow set point. The fan operation is intermittent in both modes. Staged electric heat is energized. Digital Display Zone Sensor The Digital Display Zone Sensor contains a sensing element, which sends a signal to the U.C.M. A Liquid Crystal Display(LCD)displays set point, or space temperature. Sensor buttons allow the user to adjust set points, and allow space temperature readings to be turned on or off.The Digital Display Zone Sensor also includes a communication jack, for use with a portable edit device, and an override button to change the U.C.M.from unoccupied to occupied. The override button has a cancel feature, which returns the system to unoccupied mode. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 7 of 14 Others Triangle 3 Suite 401 TI-Controls February 11,2019 Unit Dimensions -Variable Air Volume Fan Powered Terminal Units Item: Al Qty: 1 Unit Size VPEF0502SQ • Nominal 5"Dia.x 6 5/8"DepthNtrillillo. Valve Size&Depth Nominal Fan Size 02SQ Fan Filter Size 14"x20"x1"(WY 1) N j1001 TOP VIEW 20"—] 4 1/2" . ..,'> 5" . 1 0 IIIII Z • AIRFLOW c NOTES: 161/2' o m 1.Allow a minimum 6"plenum inlet clearance If i for un-ducted installations. 30" 2.Filter is secured in fitter frame located in unit inlet. 1" -1 3.For Motor access,remove bottom screws on rn hanger brackets to slide panel as shown in drawing. A 3 22" r)'-" 4.See Installation Documents for exact hanger o bracket location. co o v x 5.Air valve centered between top&bottom panel. HEATER 6" N, 6.Heating coil un-insulated. External insulation may PANEL SLIDES be field supplied and installed as required. FOR MOTOR ACCESS 7.All high&low voltage controls have same-side AIRFLOW NEC jumpback clearance. DISCHARGE OUTLET 8.Allow 48"of straight duct downstream of 1 unit before first runout and inside of the duct should be equal discharge size. 9.Terminal box access door is side hinged.Allow for 5" 40" -" clearance. 10.A 4 wire power supply required for 48013&575\3 rsingle point connection units. 1 151/2" 14" 151/2" y i_ Approximate 110.0 lb 20" —m Dry Weight Weights reflected may vary ±5.0 lb based upon options DISCHARGE VIEW selected. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 8 of 14 Others I Triangle 3 Suite 401 TI-Controls February 11,2019 Accessory-Variable Air Volume Fan Powered Terminal Units Item: Al Qty: 1 108mm 36mm —3 [1.43751 [1.4375"] 1 , 1 ® U 80mm [3.125"] ■ Specifications Measuring range:0-2000 parts per million(ppm)CO2 Accuracy at 25 degrees C: < 440 ppm CO2+3%of reading] (includes repeatability and calibration uncertainty) Non-linearity: <1.0%full scale(FS) Temperature dependence of output: 0.3%FS/degrees C Long-term stability: <5.0"FS/5-years Recommended calibration interval: 5 years Response time: 1 minute(0-63%) Operating temperature: From 59 to 95 degrees F(15 to 35 degrees C) Storage temperature: From-4 to 158 degrees F(-20 to 70 degrees C) Humidity range: 0-85%relative humidity(RH) Output signals(jumper selectable): 4-20mS,0-20 mA,0-10 Vdc Resolution of analog outputs: 10ppm CO2 Recommended external load: Current output:max.500 ohms Voltage output: min.1000 ohms Power supply: Nominal 24 Vac • Power consumption: <5 VA Warm-up time: <15 minutes Housing material: ABS plastic Mounting holes: For standard Asian,European,and North American junction boxes FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 9 of 14 Others Triangle 3 Suite 401 TI-Controls February 11,2019 Accessory-Variable Air Volume Fan Powered Terminal Units • Item:Al Qty: 1 Notes: 1.When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance. VPCF and VPEF maximum Minimum 1-row coil maximum -.-•-•-.-.-• 2-row coil maximum Pa In.wg Parallel 02SQ—PSC 150 0.60 125 0.50 \ • •.• e 100 0.40 a. o C \� ti & 75 0.30 t . cov s r 0 . e 50 0.20 25 0.10 �•�, 100 200 300 400 500 600 700 Cfm 47 94 142 189 236 283 330 L/s Airflow FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 10 of 14 Others Triangle 3 Suite 401 TI-Controls February 11,2019 Accessory-Variable Air Volume Fan Powered Terminal Units Item: Al Qty: 1 2 7/8" E- 11/16° 1/8" rte+ X111."1 CUTOUT ! S -iC: U 4 3/4" y 3 3/8" Cr I `?. 1/4" I Owes 9/16" jai r _ 01/8"TYP 1 5/16" SENSOR MOUNTING BASE Moirti.C.0'1110 i -IMIIII JI 2 5/8" SPECIFICATIONS DIGITAL ZONE SENSOR Sensor operating temperature 32 to 122°F(0 to 50°C) Setpoint functional range 50 to 89.6°F(0 to 32°C) Storage and operating humidity range 5%to 95%,non-condensing Storage Temperature -40 to 185°F(-40 to 85°C) Accuracy 0.5°F over a range of 55 to 85°F(12.8 to 29.4°C) Mounting 3.24 in(82.55 mm)for 2 mounting screws (supplied) Housing Polycarbonate/ABS blend UV protected, UL 94-5 VAflammabllity rating Agency Listing United States UL listed: UP94,5 VA flammability rating and UL916, energy management equipemtn FCC Part 15,Subpart 6 Canada CUL-C22.2 N.205-M1983 Signal Equipment Industry Canada(Certificate No.:IC6178A-13651127) Europe EMC Directive 89/336/EEC(EMC emissions and susceptibility) EN61326-Commercial Application Emissions EN55011:2007 Gass B limit Immunity EN61000-4-2 EN61000-4-3 EN61000-4-4 EN61000-45 EN61000-4-6 EN61000-4-11 FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 11 of 14 Others Triangle 3 Suite 401 TI-Controls February 11,2019 Field Wiring -Variable Air Volume Fan Powered Terminal Units Item: Al Qty: 1 480 Volt,3 Phase,4 wire L1 L2 L3 N I I I i I I I I I I I I I I T i I • •/ • � . Heater Control Wiring WARNING HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH A\ CAUTION USE COPPER CONDUCTORS ONLY! UNIT TERMINALS ARE NOT DESIGNED Customer Notes: TO ACCEPT OTHER TYPES OF CONDUCTORS. 1. Factory installed. FAILURE TO DO SO MAY CAUSE — — — — Optional or installed by others. DAMAGE TO THE EQUIPMENT. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 12 of 14 Others Triangle 3 Suite 401 TI-Controls February 11,2019 Field Wiring -Variable Air Volume Fan Powered Terminal Units " Item: Al Qty: 1 HEATER TERMINAL DAMPER BOX WIRING ACTUATOR FAN CONTROL WIRING BOX WIRING f ^� r TB,-, TB2-6 TB3-3 T83-1 TB1-2 TB2-5 T83-2 - - __ - 000 000 2ND STG HEAT 11 10 7 8 3 2 , > g DIGITAL DISPLAY ZONE SENSOR S i $ -4,1WI COMM.JACK ,ST SIG HEAT m REMOTE MID. O ®Q OPTIONAL FIELD INSTALLED L DIGITAL DISPLAY ZONE SENSOR J R-FAN BR r T82-6 TBS-, ,, TB2.5 TB3-2 O T833 \\ 24VAC BL ¢ > 0 m \ m I _ _ _ 001 _ _ \ 000 - W L '9'- J1 o 0 0 0 0 O 1 a -m- 2(+) ,(-)J 3 2 1 ZONE SENSOR ACT PRESSURE WI COMM.JACK BIP GND 24V REMOTE EMOTE Mn. ADDRESS D.D.C.IU.C.M. Q .0 SWITCH CONTROL BOARD = R + OPTIONAL FIELD y n BK VQUT L INSTALLED ZONE SENSOR J 0,-04- _ _ ScS� + (T131-1)24V TEL GRN h cv- m � �q- ]. 24V iv e2_0_ `P- a m- ❑ ❑ 'f I 0 A I ''a al SECO2 NSOR GND D R&18)GND rh ZONE GND SET NCD2 GND OUT v (T83-5)NCO2 OPTIONAL FIELD INSTALLED L CO2 SENSOR J D.D.C.1U.C.M. r 1 $ CONTROL BOXPTIONA I WIRELESS Y' TORY �---�/ �J WIRELESS SHIELDED TWISTED PAIR OPTIONAL FACTORY INSTALLED r TB3-5 -T I- TB3-5 Y I COMMUNICATIONS WIRING WIRELESS I 24vAc I B rE> R OL9n.----(TB1-1)24VAC 7 MEM O rCOMMON)---(1134-1) ll 5-t)BIP M I g I g I GRSNC CONTACTS-asI.II D4VAC GND 24V SURETURN�--(r81-2)GND OPTKINAL W55o BeeN Y -NOT CONNECTED L AUX TEMP SENSOR J L J OPTIONAL FIELD INSTALLED L OCCUPANCY SENSOR J NOTE: 1. FACTORY WIRING FIELDWIRING A WARNING — — OPTIONALNALOR ALTERNATE WIRING 2. 1/4"QUICK CONNECT REQUIRED FOR ALL FIELD CONNECTIONS. HAZARDOUS VOLTAGE! ZONE SENSOR TERMINALS 1(-)AND 2(+)REQUIRE SHIELDED TWISTED PAIR WIRING FOR DISCONNECT ALL ELECTRIC POWER COMMUNICATIONS JACK EQUIPPED ZONE SENSOR OPTION. INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. 4- I NO ADDITIONAL WIRING REQUIRED FOR NIGHT SETBACK OVERRIDE(ON/CANCEL). FAILURE TO DISCONNECT POWER • <-1THE OPTIONAL BINARY INPUT CONNECTS BETWEEN TB4-1(BIP)AND 24VAC(HOT)FROM BEFORE SERVICING CAN CAUSE TRANSFORMER.INPUT CAN BE RECONFIGURED AS AN OCCUPANCY INPUT VIA THE COMMUNICATIONS INTERFACE. SEVERE P//E��/7\RSONAL INJURY OR DEATH CAUTION 6. I AS SHIPPED,THE AUX INPUT IS CONFIGURED AS AN AUX TEMP INPUT.THE AUX INPUT CAN BE USE COPPER CONDUCTORS ONLY! ' RECONFIGURED AS A CO2 SENSOR INPUT VIA THE COMMUNICATIONS INTERFACE. UNIT TERMINALS ARE NOT DESIGNED S TERMINAL NOT TO BE USED WITH VARITRANE. TO ACCEPT OTHER TYPES OF CONDUCTORS. 8. I ZONE SENSOR TERMINALS 6 AND 7 REQUIRE SHIELDED TWISTED PAIR FAILURE TO DO SO MAY CAUSE WIRING FOR OPTIONAL USE OF COMMUNICATIONS JACK. DAMAGE TO THE EQUIPMENT. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 13 of 14 Others • Triangle 3 Suite 401 TI-Controls February 11,2019 Field Installed Options -Part/Order Number Summary This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the job. Product Family-Variable Air Volume Fan Powered Terminal Units Item Tag(s) Qty Description Model Number Al No Tag 1 VAV Fan Powered Terminal Units VPEF0500P**DDO 4AD210-L-WWF03 021 W-000 Field Installed Option Description Part/Ordering Number Digital display zone sensor X13790886010 Zone CO2 sensor(wall mount) X13790422010 FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 14 of 14 Others