Report (26) mE._c: 1-0\C - 00 v3
9S-k-
TRANS' Submittal
RECEIVED
FEB 212019
Prepared For: Date:February 11, 2019 CITY OF TIGARD
• Latimer HVAC BUILDING DIVISION
Customer P.O. Number:
Customer Project Number:
Sold To: Job Number:
Job Name:
Triangle 3 Suite 401 TI- Controls
Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval.
Product Summary
Qty Product
1 Variable Air Volume Fan Powered Terminal Units
The attached information describes the equipment we propose to
furnish for this project,and is submitted for your approval.
Product performance and submittal data is valid for a period of 6 months
from the date of submittal generation. if six months or more has elapsed
Kyle Wolf between submittal generation and equipment release,the product
Trane performance and submittal data will need to be verified. It is the
7257 SW Kable Lane customer's responsibility to obtain such verification.
Portland, OR 97224-7181
Phone: (503) 620-8031
Cell: (503)828-6788
Fax: (503)639-1454
J:IJOBSI124176117121Triangle 3 Suite 401 TI-submittal 2019-11-02.doc
Table Of Contents
Product Summary 1
Variable Air Volume Fan Powered Terminal Units(Item Al)
Tag Data 3
Product Data 3
Mechanical Specifications 4
Unit Dimensions 8
Accessory 9
Field Wiring 12
Field Installed Options -Part/Order Number Summary
Variable Air Volume Fan Powered Terminal Units 14
Triangle 3 Suite 401 TI-Controls February 11,2019
Tag Data -Variable Air Volume Fan Powered Terminal Units (Qty: 1)
Item Tag(s) Qty Description Model Number
Al No Tag 1 VAV Fan Powered Terminal Units VPEF0500P**DD04AD210-L-WWF03021W-00
0
Product Data -Variable Air Volume Fan Powered Terminal Units
Item: Al Qty: 1
Parallel with electric heat
5" (127 mm)
02 super quiet fan
1/2" [13mm] matte faced insulation
Flanged connection
277/60/1 motor voltage
Single speed motor w/SCR
DDC with on/off electric heat control
Standard actuator
Left hand controls connection
Disconnect switch
Power fuse
480 volt, 3 phase
3.0 kilowatt
2 stages of heat-equal increments
24vac magnetic contactors
Electric heater air flow switch
1 Digital display zone sensor(Fld)
1 Zone CO2 sensor(wall mount) (Fld)
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 3 of 14
Others
Triangle 3 Suite 401 TI-Controls February 11,2019
Mechanical Specifications -Variable Air Volume Fan Powered Terminal Units
Item: Al Qty: 1
General Unit Information
Casing -The unit casing is 22 gauge galvanized steel. Outlet duct connection is flanged.
Total metal encapsulation of all insulation edges. Hanger Brackets provided. Side access is provided.
Filter-A filter is provided on the plenum inlet.
Agency Listing - UL and Canadian UL listed as environmental air terminal unit. UL Control#9N65. All Trane terminal
units are AHRI 880-98 certified.
General Unit Clearance
Leave a minimum of 36"on control box side of unit for adequate service access.Allow at least 12"on remaining sides for
unit clearance.A minimum of one and one half duct diameters of straight duct work, upstream of the air inlet connection,
should be present for optimum airflow measurement performance.Upstream duct work should be the same diameter as
the primary inlet connection.
Electrical Installation Information
For electrical connections, consult field wiring section &equipment IOM.
IMPORTANT: Field Wiring
Most fan-powered VAV terminal units with electric reheat require a neutral connection from building power, however,
some configurations do not. In order to prevent a building wiring issue once the boxes are installed,the wiring diagrams
and field wiring installation for each unit MUST be checked to determine whether the neutral is required or not required.
1/2" Matte -Faced Insulation
The interior surface of the unit casing is acoustically and thermally lined with 1/2", 1.8 lb/cu. ft composite density glass
fiber with high density facing. The insulation is UL listed and meets NFPA-90A and UL 181 standards.All insulation
options will meet the 25/50 smoke developed and flame spread rating (per ASTM E 84 and UL 723 and CAN/ULC
S102-M88) Meets NFPA-90B. The insulation R-value is 1.9.All cut edges of insulation are completely encapsulated in
metal to prevent erosion.
Air Valve& Fan Description (Parallel) (Series)
The air inlet connection is an 18 gauge galvanized steel cylinder sized to fit standard round duct. A multiple point,
averaging flow sensing ring is provided with balancing taps for measuring airflow within +/-5%of unit cataloged airflow.
Also provided with each unit is a calibration chart indicating airflow versus flow sensor pressure differential. The damper
blade is constructed of a closed cell foam seal mechanically locked between two 22 gauge galvanized steel disks. The
damper blade assembly is connected through a cast zinc stub axle and shaft supported by self lubricating bearings.The
shaft is cast with a damper position indicator. The valve assembly includes a mechanical stop to prevent over stroking.
Air valve leakage <1% at 4".
1002SQ Air Valve/Fan Combination Size (Parallel) (Series)
5" inlet designed for up to 350.0 cfm.
Fan is 510.0 cfm.
• Fuse
Any electric heat unit with a calculated MCA greater or equal to 30 will have a fan fuse provided.
Motor
Single Speed, direct drive induction, permanent split capacitor type. Thermal overload protection provided. Motors will
be designed specifically for use with an open SCR which is standard. Motors will accommodate anti-backward rotation
at start up. Motor and Fan assembly are isolated from terminal unit.
Electric Heat Coil
Factory provided and mounted. Resistance open-type heater, a disc-type automatic thermal primary safety device and
manual reset load thermal secondary device. Heater element material is nickel-chromium. The heater terminal box is
provided with knockouts for customer power supply. Terminal connections are plated steel with ceramic or phenolic
insulators.All fan-powered units with electric reheat are single-point power connections.
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 4 of 14
Others
Triangle 3 Suite 401 TI-Controls February 11,2019
Magnetic Contactor
An electric heater 24 volt contact for use with Direct Digital Control (D.D.C.)or Analog Electronic VAV Controls.
Transformer
The 50 VA transformer is factory mounted in the fan control box to provide 24 VAC for controls.
SCR-Variable Fan Speed Control Switch
The SCR speed control device allows the operator infinite fan speed adjustment so the fan output may be modified to
achieve exact CFM requirements.
Power Fuse
Fuses provided on all energized lines of incoming power to interrupt circuit overcurrent conditions.
Power Disconnect Switch (for VSEF &VPEF)
A factory provided interlocking door disconnect switch located on the electric heater control panel.
Airflow Switch
An air pressure device designed to disable the heater when the unit fan is off.
Flanged Connection
A rectangular opening on the unit discharge to accept a 90 degree flanged duct work connection.
System Communications
The Controller is designed to send and receive data from a Central Control Panel or other Tracer family products, or a
VariTrac CCP. Current unit status conditions and set points may be monitored and/or edited via this data
communication feature. The network type is a twisted wire pair serial communication.
Set points in Nonvolatile Memory(9 Thru 15)
9. Heating Set point Offset-This determines at what point the 1st. stage of reheat turns on. Expressed in degrees
below cooling set point, only applicable when local thumb wheel is enabled.
10. Zone temperature, auxiliary temperature, and zone set point calibration corrections(+/- 10.0 F).
11. Flow measurement calibration correction (50 - 150%).
12. Cooling Set point Low Limit-Applies low limit to programmed occupied cooling set point or zone sensor cooling set
point(30.0 F- 100.0 F).
13. Heating Set point High Limit-Applies high limit to programmed occupied heating set point or zone sensor heating
set point(30.0 F- 100.0 F).
14. RTD/Thermistor-Determines what type of zone temperature sensor will be used.
15. Occupied and Unoccupied Outside Air Requirements- Determines the percent of outdoor air required in the zone
for air quality requirements.
D.D.C. Floating Point Actuator
Trane 3 wire, (open,close,common)26GA when 6-pos amp connector is used for Tracer UC210,VV550,or VAV UCM,
otherwise 18GA wires are used. 3.4 VA, 1.7W, 24 VAC, 50/60 Hz. Quarter turn control actuator with linkage release
button.Actuator has a constant drive rate independent of load, a rated torque of 35 in-Ib, a 90-second drive time and is
non-spring return.Travel is terminated by end stops at fully opened and closed positions. An integral magnetic clutch
eliminates motor stall. An integral 3 screw terminal block is provided for field wiring. Operating temperature 32.0 F to
125.0 F.
Additional Status Information (1 thru 8)
In addition to the above set points,the following status information can be transmitted to the Command Control Unit and
Tracer.
1. Active cooling temperature set point.
2. Active heating temperature set point.
3. Current unit primary airflow.
4. Current zone temperature.
5. Re-heat status(On/Off).
6. Auxiliary Air Temperature-Available only if the unit has an auxiliary temperature sensor.
7. Failure Indicators-The U.C.M. will indicate the following:
*Temperature Sensor Failure
*Flow Sensor Failure
*Local Zone Sensor Set point Failure
8. Ventilation Ratio.
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 5 of 14
Others
Triangle 3 Suite 401 TI-Controls February 11,2019
Direct Digital Controller
The microprocessor based terminal unit controller provides accurate, pressure independent control through the use of a
proportional integral control algorithm and direct control technology. The controller monitors zone temperature set
• points, zone temperature and its rate of change, and valve airflow, using a differential pressure signal. Optionally, the
controller can monitor either supply duct air temperature or CO2 concentration via appropriate sensors. The controller
and pressure transducer are installed and factory wired in an enclosure with 7/8"knockouts for remote control wiring.A
• Trane zone sensor is required.
Override Commands
The following override commands may be received by the Unit Control Module (U.C.M.)from the Tracer System.
Control Mode, Action, &Offset(1 thru 12)
1. Control Mode-The U.C.M. Control Mode may be edited from occupied to unoccupied to accommodate night
setback/setup.
2. Control Action-The Control Action may be edited from cooling to heating, changing the primary air damper to a
heating source. This will accommodate a cooling/heating changeover system.
3. Control Offset- Enabling Control Offset will increase the cooling temperature set point and decrease the heating
temperature set point by a control offset value stored at the U.C.M. This function facilitates demand limiting in the
occupied mode.
4. Drive damper fully open.
5. Drive damper fully closed.
6. Drive damper to maximum airflow set point.
7. Drive damper to minimum airflow set point.
8. Disable unit fan.
9. Disable unit heat.
10. Reset- Enabling the reset function forces the controller and the flow sensor to recalibrate.
11. Programmable hot water valve drive time.
12. Programmable air valve drive time.
Following Unit Set points
The following unit set points reside in the U.C.M. in nonvolatile memory. These set points are editable from the
Command Unit or Tracer via the communications link.
Set points in Nonvolatile Memory(1 thru 8)
1. Occupied cooling temperature set point 60.0 F -80.0 F.
2. Occupied heating temperature set point 60.0 F-80.0 F.
3. Unoccupied cooling temperature set point 60.0 F- 100.0 F.
4. Unoccupied heating temperature set point 30.0 F - 100.0 F.
5. Minimum cooling flow set point(0, 10- 100% of unit equivalent cataloged airflow).
6. Minimum heating flow set point(0, 10- 100% of unit equivalent cataloged airflow).
7. Maximum flow set point(0,10 - 100% of unit equivalent cataloged airflow).
8. Fan Control Offset-This determines at what operating point the fan in a parallel fan powered unit is energized.This
can be specified as a function of temperature, degrees above heating set point, or primary airflow. 0.0 F - 10.0 F or 0,
10- 100%of unit equivalent cataloged airflow).
Set points in Nonvolatile Memory(16 thru 21)
16. Series Fan Configuration-allows option of series fan powered box to shut off fan and close air valve when unit is
unoccupied. Fan will operate in unoccupied mode if reheat is active.
17. Heating set point low limit.
18. Cooling set point high limit.
19. Local heating flow set point enable/disable&set point.
20. Auxiliary analog input mode select for either auxiliary temperature sensor or CO2 detector.
21. Binary input mode select for either generic or occupancy detector.
Additional Status Information (9 thru 12)
9. Fan Status (on/off)
10. Calibration Status (calibrating/not-calibrating)
11. BIP state
12. CO2 Concentration-available only if the unit has an auxiliary CO2 sensor. This mode and auxiliary air temperature
are mutually exclusive.
DDC Sequence of Operation
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 6 of 14
Others
Triangle 3 Suite 401 TI-Controls February 11,2019
The unit controller continuously monitors the zone temperature against its set point and varies the primary airflow as
required to meet zone set points. Airflow is limited by minimum and maximum airflow set points.
Parallel Unit Fan Energization
• As the zone temperature reaches the heating set point, the microprocessor controls airflow to the heating temperature
set point and energizes the auxiliary fan when necessary. At or below the heating set point, reheat is energized. The
heating minimum airflow set point is factory set, field adjustable, and is separate from the cooling minimum set point.
Parallel unit fan energization is a function of primary airflow or zone temperature.
1. Primary Airflow-The fan energizes when primary airflow drops below the fan set point airflow.The fan automatically
starts when the zone temperature drops to the heating temperature set point.
2. Zone Temperature-The fan energizes when the zone temperature drops to a selectable number of degrees above
the heating temperature set point.
DDC Controls Option DD04, DD14, DD44& DD74
Basic Operation: On/Off Staged Electric Heat(Normally Open Outputs) (DDC/UCM)
(Parallel Units)
A voltage signal from the zone sensor indicates the zone temperature is used by the unit controller to determine an error
from the set point. This error, as well as primary flow differential pressure, is used to determine damper position within
minimum and maximum cooling airflow set points. As the zone temperature drops to the heating set point, primary
airflow is controlled to minimum heating flow set point. The fan operation is intermittent in both modes. Staged electric
heat is energized.
Digital Display Zone Sensor
The Digital Display Zone Sensor contains a sensing element, which sends a signal to the U.C.M. A Liquid Crystal
Display(LCD)displays set point, or space temperature. Sensor buttons allow the user to adjust set points, and allow
space temperature readings to be turned on or off.The Digital Display Zone Sensor also includes a communication jack,
for use with a portable edit device, and an override button to change the U.C.M.from unoccupied to occupied. The
override button has a cancel feature, which returns the system to unoccupied mode.
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 7 of 14
Others
Triangle 3 Suite 401 TI-Controls February 11,2019
Unit Dimensions -Variable Air Volume Fan Powered Terminal Units
Item: Al Qty: 1
Unit Size VPEF0502SQ
• Nominal 5"Dia.x 6 5/8"DepthNtrillillo.
Valve Size&Depth
Nominal
Fan Size 02SQ Fan
Filter Size 14"x20"x1"(WY 1)
N j1001
TOP VIEW
20"—]
4 1/2"
. ..,'>
5" .
1
0 IIIII
Z
• AIRFLOW c NOTES:
161/2' o
m 1.Allow a minimum 6"plenum inlet clearance
If i
for un-ducted installations.
30" 2.Filter is secured in fitter frame located in unit inlet.
1"
-1 3.For Motor access,remove bottom screws on
rn hanger brackets to slide panel as shown in drawing.
A
3
22"
r)'-" 4.See Installation Documents for exact hanger
o bracket location.
co
o v
x 5.Air valve centered between top&bottom panel.
HEATER 6"
N, 6.Heating coil un-insulated. External insulation may
PANEL SLIDES be field supplied and installed as required.
FOR MOTOR ACCESS 7.All high&low voltage controls have same-side
AIRFLOW NEC jumpback clearance.
DISCHARGE OUTLET
8.Allow 48"of straight duct downstream of 1
unit before first runout and inside of the duct should
be equal discharge size.
9.Terminal box access door is side hinged.Allow for
5" 40" -"
clearance.
10.A 4 wire power supply required for 48013&575\3
rsingle point connection units.
1
151/2" 14" 151/2"
y i_
Approximate 110.0 lb
20" —m
Dry Weight
Weights reflected may vary
±5.0 lb based upon options
DISCHARGE VIEW selected.
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 8 of 14
Others
I
Triangle 3 Suite 401 TI-Controls February 11,2019
Accessory-Variable Air Volume Fan Powered Terminal Units
Item: Al Qty: 1
108mm 36mm
—3 [1.43751
[1.4375"]
1 , 1
®
U
80mm
[3.125"]
■
Specifications
Measuring range:0-2000 parts per million(ppm)CO2
Accuracy at 25 degrees C: < 440 ppm CO2+3%of reading]
(includes repeatability and calibration uncertainty)
Non-linearity: <1.0%full scale(FS)
Temperature dependence of output: 0.3%FS/degrees C
Long-term stability: <5.0"FS/5-years
Recommended calibration interval: 5 years
Response time: 1 minute(0-63%)
Operating temperature: From 59 to 95 degrees F(15 to 35 degrees C)
Storage temperature: From-4 to 158 degrees F(-20 to 70 degrees C)
Humidity range: 0-85%relative humidity(RH)
Output signals(jumper selectable): 4-20mS,0-20 mA,0-10 Vdc
Resolution of analog outputs: 10ppm CO2
Recommended external load: Current output:max.500 ohms
Voltage output: min.1000 ohms
Power supply: Nominal 24 Vac
•
Power consumption: <5 VA
Warm-up time: <15 minutes
Housing material: ABS plastic
Mounting holes: For standard Asian,European,and North American junction boxes
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 9 of 14
Others
Triangle 3 Suite 401 TI-Controls February 11,2019
Accessory-Variable Air Volume Fan Powered Terminal Units
• Item:Al Qty: 1
Notes:
1.When attenuator is required, add inlet attenuator pressure
to discharge static pressure for final fan performance.
VPCF and VPEF maximum
Minimum
1-row coil maximum
-.-•-•-.-.-• 2-row coil maximum
Pa In.wg Parallel 02SQ—PSC
150 0.60
125 0.50 \
• •.•
e 100 0.40
a.
o
C \�
ti
& 75 0.30 t .
cov
s
r
0 . e
50 0.20
25 0.10 �•�,
100 200 300 400 500 600 700 Cfm
47 94 142 189 236 283 330 L/s
Airflow
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 10 of 14
Others
Triangle 3 Suite 401 TI-Controls February 11,2019
Accessory-Variable Air Volume Fan Powered Terminal Units
Item: Al Qty: 1
2 7/8"
E- 11/16°
1/8"
rte+ X111."1
CUTOUT
! S -iC:
U
4 3/4" y 3 3/8"
Cr I
`?. 1/4"
I
Owes
9/16"
jai
r _ 01/8"TYP
1 5/16"
SENSOR MOUNTING BASE
Moirti.C.0'1110
i -IMIIII
JI
2 5/8"
SPECIFICATIONS DIGITAL ZONE SENSOR
Sensor operating temperature 32 to 122°F(0 to 50°C)
Setpoint functional range 50 to 89.6°F(0 to 32°C)
Storage and operating humidity range 5%to 95%,non-condensing
Storage Temperature -40 to 185°F(-40 to 85°C)
Accuracy 0.5°F over a range of 55 to 85°F(12.8 to 29.4°C)
Mounting 3.24 in(82.55 mm)for 2 mounting screws
(supplied)
Housing Polycarbonate/ABS blend
UV protected,
UL 94-5 VAflammabllity rating
Agency Listing
United States UL listed: UP94,5 VA flammability rating and UL916,
energy management equipemtn FCC Part 15,Subpart 6
Canada CUL-C22.2 N.205-M1983 Signal Equipment
Industry Canada(Certificate No.:IC6178A-13651127)
Europe EMC Directive 89/336/EEC(EMC emissions and susceptibility)
EN61326-Commercial Application
Emissions
EN55011:2007 Gass B limit
Immunity
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-45
EN61000-4-6
EN61000-4-11
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 11 of 14
Others
Triangle 3 Suite 401 TI-Controls February 11,2019
Field Wiring -Variable Air Volume Fan Powered Terminal Units
Item: Al Qty: 1
480 Volt,3 Phase,4 wire
L1 L2 L3 N
I I I i
I I I
I I I
I I I I T
i I
• •/ •
� .
Heater
Control
Wiring
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS
BEFORE SERVICING.
FAILURE TO DISCONNECT POWER
BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH
A\ CAUTION
USE COPPER CONDUCTORS ONLY!
UNIT TERMINALS ARE NOT DESIGNED Customer Notes:
TO ACCEPT OTHER TYPES OF
CONDUCTORS. 1. Factory installed.
FAILURE TO DO SO MAY CAUSE — — — — Optional or installed by others.
DAMAGE TO THE EQUIPMENT.
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 12 of 14
Others
Triangle 3 Suite 401 TI-Controls February 11,2019
Field Wiring -Variable Air Volume Fan Powered Terminal Units
" Item: Al Qty: 1
HEATER
TERMINAL DAMPER
BOX WIRING ACTUATOR FAN CONTROL
WIRING BOX WIRING
f ^� r TB,-, TB2-6 TB3-3 T83-1
TB1-2 TB2-5 T83-2
- -
__ - 000 000
2ND STG HEAT
11 10 7 8 3 2 ,
>
g DIGITAL DISPLAY ZONE SENSOR
S i $ -4,1WI COMM.JACK
,ST SIG HEAT m REMOTE MID.
O ®Q
OPTIONAL FIELD INSTALLED
L DIGITAL DISPLAY ZONE SENSOR J
R-FAN
BR r T82-6 TBS-,
,, TB2.5 TB3-2
O T833
\\ 24VAC BL
¢ > 0 m \ m I
_ _ _ 001
_ _ \ 000
- W L '9'- J1 o 0 0 0 0 O 1 a -m- 2(+) ,(-)J 3 2 1
ZONE SENSOR
ACT PRESSURE WI COMM.JACK
BIP GND 24V REMOTE EMOTE Mn.
ADDRESS D.D.C.IU.C.M. Q
.0
SWITCH CONTROL BOARD = R + OPTIONAL FIELD
y n BK VQUT L INSTALLED ZONE SENSOR J
0,-04-
_ _ ScS� + (T131-1)24V
TEL GRN h cv- m � �q- ]. 24V
iv e2_0_ `P- a m- ❑ ❑ 'f I 0 A I ''a al SECO2 NSOR GND D R&18)GND
rh ZONE GND SET NCD2 GND OUT v (T83-5)NCO2
OPTIONAL FIELD INSTALLED
L CO2 SENSOR J
D.D.C.1U.C.M. r 1
$ CONTROL BOXPTIONA
I WIRELESS Y'
TORY
�---�/ �J WIRELESS
SHIELDED TWISTED PAIR OPTIONAL FACTORY INSTALLED r TB3-5 -T I- TB3-5 Y I
COMMUNICATIONS WIRING WIRELESS I 24vAc I B
rE> R OL9n.----(TB1-1)24VAC 7 MEM
O rCOMMON)---(1134-1) ll
5-t)BIP M I g I g I
GRSNC CONTACTS-asI.II D4VAC GND 24V
SURETURN�--(r81-2)GND OPTKINAL
W55o BeeN
Y -NOT CONNECTED L AUX TEMP SENSOR J L J
OPTIONAL FIELD INSTALLED
L OCCUPANCY SENSOR J
NOTE:
1. FACTORY WIRING
FIELDWIRING A WARNING
— — OPTIONALNALOR ALTERNATE WIRING
2. 1/4"QUICK CONNECT REQUIRED FOR ALL FIELD CONNECTIONS. HAZARDOUS VOLTAGE!
ZONE SENSOR TERMINALS 1(-)AND 2(+)REQUIRE SHIELDED TWISTED PAIR WIRING FOR DISCONNECT ALL ELECTRIC POWER
COMMUNICATIONS JACK EQUIPPED ZONE SENSOR OPTION. INCLUDING REMOTE DISCONNECTS
BEFORE SERVICING.
4- I NO ADDITIONAL WIRING REQUIRED FOR NIGHT SETBACK OVERRIDE(ON/CANCEL). FAILURE TO DISCONNECT POWER
• <-1THE OPTIONAL BINARY INPUT CONNECTS BETWEEN TB4-1(BIP)AND 24VAC(HOT)FROM BEFORE SERVICING CAN CAUSE
TRANSFORMER.INPUT CAN BE RECONFIGURED AS AN OCCUPANCY INPUT VIA THE COMMUNICATIONS
INTERFACE. SEVERE P//E��/7\RSONAL INJURY OR DEATH
CAUTION
6. I AS SHIPPED,THE AUX INPUT IS CONFIGURED AS AN AUX TEMP INPUT.THE AUX INPUT CAN BE USE COPPER CONDUCTORS ONLY!
' RECONFIGURED AS A CO2 SENSOR INPUT VIA THE COMMUNICATIONS INTERFACE.
UNIT TERMINALS ARE NOT DESIGNED
S TERMINAL NOT TO BE USED WITH VARITRANE. TO ACCEPT OTHER TYPES OF
CONDUCTORS.
8. I ZONE SENSOR TERMINALS 6 AND 7 REQUIRE SHIELDED TWISTED PAIR FAILURE TO DO SO MAY CAUSE
WIRING FOR OPTIONAL USE OF COMMUNICATIONS JACK. DAMAGE TO THE EQUIPMENT.
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 13 of 14
Others
• Triangle 3 Suite 401 TI-Controls February 11,2019
Field Installed Options -Part/Order Number Summary
This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order
numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of
material for the job.
Product Family-Variable Air Volume Fan Powered Terminal Units
Item Tag(s) Qty Description Model Number
Al No Tag 1 VAV Fan Powered Terminal Units VPEF0500P**DDO
4AD210-L-WWF03
021 W-000
Field Installed Option Description Part/Ordering Number
Digital display zone sensor X13790886010
Zone CO2 sensor(wall mount) X13790422010
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 14 of 14
Others