Loading...
Report RUSKIN® . All4CA LICENSED t< See Page 2 3900 Dr. Greaves Rd. • Kansas City, MO 64030 * (816) 761-7476 • FAX(816)765-8955 FSD6O-C CORRIDOR DAMPER CLASSIFIED UL555 1 HOUR UL555S CLASS 1 APPLICATION The FSD6O-C meets the requirements for fire, smoke and The FSD6O-C is two dampers in one. It is a one hour fire rated, UL combination fire/smoke dampers established by: labeled Corridor Damper and a 11/2 hour fire rated, Leakage Class 1, UL labeled Combination Fire Smoke Damper. As a Corridor • National Fire Protection Association NFPA Standards Damper it is designed to be used in openings in the ceilings of 90A,92A,928 and 101 wood stud or metal stud constructed interior tunnel corridors. As a • BOCA National Building Codes Combination Fire Smoke Damper it is designed to be used any- " • !CBO Uniform Building Codes where a vertical or horizontal, Leakage Class 1 fire smoke damper • SBCCI Standard Building Codes is needed.The FSD6O-C is also rated for airflow in either direction • ICC International Building Codes with velocities to 2,000 fpm and pressures to 4"w.g. • CSFM California State Fire Marshal Fire Damper Listing STANDARD CONSTRUCTION (#3225-245:102)and Smoke Damper Listing(#3230- 245:110) FRAME 5"x 16 gage(127 x 1.6)galvanized,hat-shaped steel channel. SLEEVES 181/2"x 20 gage(470 x 1.0)galvanized steel. i ,,,.„-t$11,4,0 SEE COMPLETE FM Approvals BLADES 1 ® MARKING Specification Tested Product Airfoil-shaped, double-skin, single piece construction with 14 I C U ON PRODUCT (Option) gage equivalent thickness,maximum 6"(152)wide. BEARINGS Stainless steel sleeve,pressed into frame. UL CLASSIFIED JAMB SEALS UL555 Listing R5531,UL555S Listing R5531 Stainless steel,flexible metal compression type. BLADE SEALS Silicone edge type for smoke seal to 450°F(232"C) and galva- nized steel for flame seal to 1900°F(1083°C). FEATURES LINKAGE The FSD6O-C series offers: Concealed in frame. • EFL (Electric Fuse Link) or PFL (Pneumatic Fuse Link) heat- AXLES actuated release devices permit controlled (rather than instanta- 1/2"(13) plated steel hex. neous) closure through the damper actuator.The EFL and PFL CONTROLLED CLOSURE DEVICE(HEAT-ACTUATED) allow the damper to automatically reopen after a test, smoke EFL(Electric Fuse Link) 165°F(74°C)is standard.212°F(100°C), detection or power failure conditions. 250°F(121°C)or 350°F(177°C)are options. • EFL is standard on dampers with electric actuators. PFL (Pneumatic Fuse Link) 165°F (74°C) is standard. 212°F • PFL is standard on dampers with pneumatic actuators. (100°C)or 285°F(141)are options. • EFL's may be ordered on dampers with pneumatic actuators but UL555S Elevated Temperature Rating require an additional EP switch(consult factory). 250°F(121°C)or 350°F(177°C)depending on actuator. DAMPER SIZES MINIMUM SIZE 8"w x 6"h(203 x 152). MAXIMUM SIZE Single Section—24"w x 24"h(610 x 610) . .d-1----------" 0` -..., OPTIONS .----„ '” - , --- • FM Approvals as Specification Tested Product. ....,,..„ ., -.--- • TS150 FireStat for reopenable operation in dynamic smoke management systems. • DSDF/DSDN Duct Smoke Detector(Flow rated or No-flow). - -- „--- - , • SP100 Switch Package to remotely indicate damper blade posi- .-----,, ``---•..---<,,,6, --„, ,---- --„, ---- , . • Sleeve in lengths other than 181/2" and gages to insure field compliance with UL installation requirements. systems. i NOTES 1. Dampers are furnished actual size to the inside of the sleeve. 2. D imensions shown in parentheses( )indicate millimeters. Spec FSD6O-C-1007/Replaces FSD60136-C-1206 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION. ©Ruskin October 2007 AMCA LICENSED AIR PERFORMANCE DATA 1 amco Ruskin Company certifies that the FSD60-C shown hereon is licensed OERTIRED to bear the AMCA Seal.The ratings ROTIAGS shown are based on tests and pro- cedures performed in accordance • with AMCA Publication 511 and > R 1 it ee comply with the requirements of the petformcsn AMCA Certified Ratings Program. The AMCA Certified Ratings Seal e - nut applies to air performance for the 411101.101111ef FSD60-C. 01111101100110243i 10100114Tita ffiTtRIMIMINIOL UM To determine the AMCA Licensed air performance: Locate the applicable feet per minute face velocity on the bottom of the velocity vs. pressure drop chart below. Move up the chart to the most appropriate size damper line. From the intersection point,move left to determine the pressure drop on the left side of the chart. For other damper sizes refer to Air Performance Data For All Fire and Smoke Dampers spec sheet. VELOCITY vs.PRESSURE DROP 1.0 0.9 i 0.8 ---- 0.6 0.5 , „ . 0.4 0.3 - / r..N• ,, ! ...-.. ,l.' d 0.2 3 , i *.***'" , cn u.i ! 1 = i I 0 I -.. Z 1......- i / 7/ , 1 , C...) .og CC 1 W .07 , cr, Eli ! / hil I 1 1 u.1 1 I I - 1 i .03 i 1 .02 1 I , 111/ , ' .01 2 3 4 6 7 8 9 2 3 4 6 7 8 9 100 500 1000 5000 10000 FACE VELOCITY-FEET/MINUTE AMCA Fig.5.3 FSD6O-C APPLICATIONS The illustrations below depict the different installation configurations for the FSD6O-C. Cl WOOD OR METAL STUD DUCTED THROUGH PENETRATION Tha illustration depicts the Cl application in which the FSD6O-C is installed in a ducted fire rated ceiling above the finished ceiling.Actuators can be mounted internally or externally above or below the rated ceiling. *If space is a problem the 91/2" (241)'dimension can be reduced to 63/4" (171) by relocating the EFL, PFL, TS150 or SP100 (consult Ruskin). 3y' r� U, tU ITEM DESCRIPTION A j \ 1. Actuator(location may vary) t2. Damper Frame 91/2"(241) E 1 1 Standard L—-; -—' f' ' 3. TS150 FireStat, EFL or PFL(location may vary) —— r 4. Sleeve(20 gage standard) - 5. Over Center Link �� i 7 6. Mounting Angles 1 x 21/2 x 16 gage 1— __ = i 'v \I 7. Mounting angles 11/2 x 11/2 x 20 gage 4"(102) 111 8. Sleeve to Duct Break-away Connections Standardt i! \\ 9. Single Stud Construction i 10. Steel grille/diffuser(by others) 11 1 1 '., 11. Caulking Material (meets 25/50 flame spread/smoke , } ul u developed criteria) (8-) L C2 WOOD OR METAL STUD WITH V-FRAME DIFFUSER This illustration depicts the C2 application in which the FSD6O-C is applied with a V-Frame diffuser and the fire rated ceiling is the finished ceiling. Access to the actuator is available from the finished ceiling(external mount)or through the diffuser (internal mount). See actuator limitations on back page.Ruskin will configure the assembly based on internal or external mount actuator. *If space is a problem the 141/2"(368)dimension and sleeve length can be shortened(consult Ruskin). 'J `2) ( r"i; ;,, 1 1-was 16"(406) 141/21369) 18 Vi (460) i 6"(406) lama x' 141/21369) i Max. — u; Ruskin Ruskin 161/2"(460) 1 Standard' Standard Max. � \ (5) �`% Sleeve Len th` —! f f Standard" Standard C) I- i 9 V Sleeve Length' 1 r d , y' !� I - l�/11J,L- 1\ , / / n 1 7y 6-, _ ,:-7!,6-, to actuator through diffuser EXTERNAL MOUNT ACTUATOR INTERNAL MOUNT ACTUATOR C3 METAL STUD WITH FLAT FRAME DIFFUSER This illustration depicts the C3 application in which the FSD6O-C is applied with a Flat-Frame diffuser and the fire rated ceiling(metal stud only) is the finished ceiling. Access to the actuator is available from above the finished ceiling (external mount) or through the diffuser (internal mount). Ruskin will configure the assembly based on internal or external mount actuator. *If space is a problem the 141/2"(608)dimension and sleeve length can be shortened(consult Ruskin). Th %� \;) '•�\ -._� :� ::'� .� ' .. t �\ c--) \ I ` '\' + 1\ f I i7�S 4•, I v 14�/z"369 l § — -, r__, '`- 141/2"(369) 16"(406) (-� };p, Ruskin ) 181/2"(460) 16"(406) / Ruskin 181/2"(460) Max. '..1.. `" Standard* Standard Max. Standard` Standard �, �� Sleeve Length' i Sleeve Length' t J r —!rte . S-t � �/4.•: _ G e 'z !;y \ Access to actuator through diffuser EXTERNAL MOUNT ACTUATOR INTERNAL MOUNT ACTUATOR • REQUIRED MOUNTING ANGLES For Cl installations For C3 installations PFMA or Retaining angles(shipped loose) 2 ea 1"x 11/2"x 30"(25 x 38 x 762)minimum 16(1.6)gage retain- ing angle For C2 installations 4 ea special 1"x 21/2"x 16 gage(25 x 64 x 1.6)angle 1eaFAST SUGGESTED SPECIFICATION Combination fire smoke dampers meeting or exceeding the follow- Each fire smoke damper shall be equipped with a "controlled ing specifications shall be furnished and installed at locations closure" quick detect heat-actuated release device to prevent duct shown on plans or as described in schedules. Dampers shall meet and HVAC component damage. Instantaneous damper closure the requirements of NFPA90A, 92A and 92B. Dampers shall be through the use of fusible links is unacceptable. classified for use for installation in tunnel corridor ceilings and shall be classified as Leakage Class 1 Smoke Dampers in accordance Damper frame shall be a structural hat channel and shall be low with the latest version of UL555S. Dampers shall be warranted to profile, high performance type for lowest possible pressure drop. be free from defects in material and workmanship for a period of 5 Damper blades shall be airfoil shaped with 13 gage(2.3)equivalent years after date of shipment. thickness formed from a single piece of galvanized steel. Bearings shall be stainless steel turning in an extruded hole in the frame. In addition the dampers and their actuators shall have a UL555S Blade edge seals shall be silicone rubber and galvanized steel elevated temperature rating of 250°F (121°C) or 350°F (177°C) mechanically locked in to the blade edge (adhesive type seals are depending upon the actuator. Appropriate electric or pneumatic not acceptable). Each damper shall be supplied with a factory actuators shall be installed by the damper manufacturer at time of mounted sleeve of 181/2" (470) minimum length. Dampers shall be damper fabrication. Electric actuators shall have been energized Ruskin model FSD60-C. hold open tested for a period of at least 1 year with no spring return failures. (Consult Ruskin for detailed CSI MasterFormat Specification). • • • 3900 Dr.Greaves Rd. RusKIN. www)761-7476 8 k,6 995530 RUSK/N E) 3900 Dr. Greaves Rd. • Kansas City, MO 64030 • (816)761-7476 • FAX(816)765-8955 INSTALLATION INSTRUCTIONS ESDSOC AND FSD36C CORRIDOR DAMPER UL555 1 HOUR FIRE RESISTANCE AND UL5555 CLASS 1 AND CLASS 2 LEAKAGE RATINGS - APPLICATION %SSW The FSD60C AND FSD36C is a UL Classified 1 Hour Corridor 01. 44'.10 SEE COMPLETE MARKING damper. It is designed for installation in the ceiling penetrations of ON PRODUCT tunnel corridors. The FSD60C and FSD36C may also be installed as a"standard" 11/2 hour combination fire/smoke damper in walls or floors (Refer to the FSD60 and FSD36 installation instructions when installing as a "standard" 11/2 hour combination fire/smoke California State Fire Marshal Listing No. damper.) The FSD60C and FSD36C closes on loss of power. FSD36C—3225-0245:111 - 3230-0245:112 FSD60C and FSD36C MAXIMUM UL CLASSIFIED SIZE OPPOSED BLADES Single section horizontal—24"w x 24"h(610 x 610). Dimensions shown in parentheses( )indicate millimeters. APPLICATION ILLUSTRATIONS FSD60C AND FSD36C FIG. 1 -ACTUATOR ABOVE RATED CORRIDOR CEILING Cl Installation Through Penetration of Corridor Ceiling i '4 (Wood or Steel Stud Construction) , 111 I 1 9 16"(406)Max. L. — __ 44010111%00. te trill0 __T. __ 1,,,il = . 1... Tam , ir )4, , Igimil= MC ' V 'i smeAmomminomme mom l 41°.' 1IN fliN",. ,dilki 6"(152)Max. t NIIII4 ITEM DESCRIPTION 0 \ -D 0 \§.) 1. Actuator(may be in or out of airstream) 2. Damper Frame 3. TS150, EFL,PFL or SP100(location may vary) FIG.2-ACTUATOR BELOW RATED CORRIDOR CEILING 4. Sleeve 5. Over-Center Link 6. Mounting Angles See Note 5. 0 V'TD 7. Joint,Sleeve to Duct—Break-away Connections / /8. Caulking Material (R\ 9. Steel or Wood Stud Construction(single studs only) i I ill 6"(152)Max. f --- ' _ . F-1 ' 16"(406)Max. r_—--t- '1 I \ i N I L.........___1 11-FSD60/36C-705/Replaces II-FSD36C-1104 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION. ©Ruskin 2005 GENERAL INSTALLATION 1.Opening Clearance screws.A minimum of one screw shall be placed at each end a. C1 Installation of the angle. The opening shall be 1/4"(6)larger than the overall size of the 6.Duct/Sleeve Connections damper and sleeve assembly. a.Break-away Duct/Sleeve Connections b.C2 Installation Rectangular ducts must use one or more of the connections " The opening shall be large enough to allow the grille or dif- depicted below: fuser to overlap the bottom edges of the corridor ceiling and A maximum of two#10(M5)sheet metal screws on each side lay flat against the ceiling material. and the bottom, located in the center of the slip pocket and 2. Ceiling Construction penetrating both sides of the slip pocket may be used. Connections using these slip joints on the top and bottom with The minimum ceiling partition construction will consist of single flat drive slips up to 20" (508) long on the sides may also be 2 x 4 wood studs or metal studs on 24" (610) center to center. used. C3 applications are metal stud only. UL classified 5/8" (16)gyp- b.Round and Oval Break-away Connections sum will be attached to the studs.with 15/s" (41)drywall screws Round and flat oval break-away connections must use either a on 12" (305) centers or no. 6d nails on 7" (178) centers. Refer 4" (102) wide drawband or #10 (M5) sheet metal screws to the framing details included in these instructions. spaced equally around the circumference of the duct as fol- 3. Fasteners and Sealant lows: When fastening the damper to field supplied sleeves, the Duct diameters 22" (559) and smaller maximum 3 dampers shall be fastened with 1/4-20 (M6) bolts, number 10 screws. (M5) screws,or 1/2" (13) long welds staggered intermittently on • Duct diameters over 22" (559) and including 36" (914) - maximum 5 screws. both sides. Space all fasteners 6" (152) on center and a maxi- • Duct diameters over 36"(914)and up to and including 191" mum 2" (51) from the ends of each corner. A bead of Dow (4851)total perimeter-maximum 8 screws. Corning Silastic 732 RTV, Dow Corning 999 or GE RTV 108 sealant shall be applied between the damper and sleeve. Press ......................... the surface of the sealant in place to dispel the air. Only one ---,--:-.e, .. --- side —side of the damper requires caulking. PLAIN"S"SLIP HEMMED"S"SLIP DOUBLE"S"SLIP INSIDE SUP JOINT 4. Damper Sleeve 1, lrft qj Sleeve thickness must be equal to or thicker than the duct con- c. 14 ==5k nected to it. Sleeve gage requirements are listed in the SMAC- NA Fire, Smoke and Radiation Damper Installation Guide for STANDING s STANDING s STANDING(ALT.) STANDING S p {ANGLE RE:N=ORCED) (BAR REINFORCED) HVAC Systems and in NFPA90A. If a breakaway style duct/sleeve connection is not used, the sleeve shall be a mini- mum of 16 gage (1.6), Damper sleeve shall not extend more __ lia _ "� 3 than 6" (152) beyond the fire wall or partition unless damper is • equipped with an actuator and/or factory installed access door, (ANGLE R IN"FORCED) 6 1`E s`In Coln T Sleeve may extend up to 16"(406)beyond the fire wall or parti- tion on sides equipped with actuator and/or factory installed For flat oval ducts, the diameter is considered the largest(major) access door. Sleeve shall terminate at both sides of wall within dimension of the duct. 1I hese connections are depicted in the dimensions shown. SMACNA Fire,Smoke,and Radiation Damper Installation Guide. 5.Mounting Angles Note: When optional sealing of these joints is desired, the follow- a.Cl Installation ing sealants may be applied in accordance with the sealant menu- Ruskin FAST Angle or Picture Frame Mounting Angles(PFMA) facturer's instructions: are UL tested and may be used in lieu of the following conven- Hardcast,Inc.-Iron Grip 601 Precision-PA2084T tional mounting angles.The mounting angles shall be 11/2" x Eco Duct Seal 44-52 Design Polymerics-DP 1010 11/2"x 20 gage(38 x 38 x 1.6)minimum and shall be fastened c. Flanged Break-away Style Duct/Sleeve Connections. with minimum no. 10(M5) bolts or screws, 3/16"(5) minimum Flanged connection systems manufactured by Ductmate, diameter steel rivets or 1/2"(13)long tack welds. Do not fasten Nexus or Ward are approved break-away when installed as or weld angles together at corners of dampers. Space fasten- shown on the Flanged System Breakaway Connections ers 12"(305)maximum on center. Supplement. b.C2 Installation TDC and TDF roll-formed flanged connections using 3/s"(10) Ruskin FAST Angle or Picture Frame Mounting Angles(PFMA) steel bolts, nuts, and metal cleats as depicted and tested by en may be used above the framing otherwise the mounting angle SMACNA, are approved break away connections 'away above the framing shall be 11/2"x 11/2" x 20 gage(38 x 38 x installed as shown on the Flanged Systems Breakaway .9) minimum and shall be fastened with minimum no. 10(M5) Connections Supplement. bolts or screws, 3/16" (5) minimum diameter steel rivets or 1/2" d.Non-Break-away Duct/Sleeve Connections (13)long tack welds. Do not fasten or weld angles together at If other duct/sleeve connections are used,the sleeve shall be corners of dampers. Space fasteners 12" (305) maximum on a minimum of 16 gage(1.6)for dampers up to 36" (914)wide center.The angle used below the framing shall be 1"x 21/2"x and 24"(610) high and 14 gage(2.0)for dampers exceeding 16 gage(25 x 64 x 1.6) minimum and shall be fastened to the 36"(914)wide x 24"(610)high. damper sleeve like the angle used above the framing. 7.Installation and Maintenance c.C3 Installation To ensure optimum operation and performance, the damper Mounting angles are required only on the topside of the fram- must be installed so it is square and free from racking. Each fire ing.The mounting angles shall be fastened with minimum no. damper should be maintained,cycled and tested at intervals not 10(M5)bolts or screws,3/16"(5)minimum diameter steel rivets less than every six months and in accordance with the latest edi- or 1/2" (13) long tack welds. Space fasteners 12" (305) maxi- tions of NFPA 90A and local codes.Care should be exercised to mum on center.The mounting angles will be secured to the top ensure that such tests are performed safely and do not cause of the ceiling partition with minimum no. 8 x 15/s" (M4 x 41) system damage. ILLUSTRATIONS (CONT) opiii. ,,k4.44140.00.010,000FSD601AN: FSD36C FSD6OC AND FSD36C C2 installation C3 Installation V-Frame Grille Application Flat-Frame Diffuser Application (Wood or Steel Stud Construction) (Steel Stud Construction Only) . ,,,,,,- :41,.•----„00.:.---0.-->, ..-,"- ,>:-,,>00.00•••0---- N'''''''''\ -- • 44 0111) , , -....„„"N tAihm. „.„......„.. l's%.ss'ill° ,,,,,,,,,,,,,'''.....' ."--• ,,''`' 7,,,""--1 FIG.3-DAMPER WITH ACTUATOR MOUNTED EXTERNALLY FIG.5-DAMPER WITH ACTUATOR MOUNTED EXTERNALLY 8 C cr\, 9 93 ci) r --, j\---i- i- 1 0 L__,,..____, \ A \ L_ --- 1 1 4 ; --' P4.• 16"(406)Max. c®. , L._ _______J I N, ). 16"(406)Max. 11Ib Immo ...... ..r.11k.`‘..... ........................... MINIAMI s .•11111M 11111111111111 MI 0 AMINIMMIIMMIIMB MN= p i11111.1SONSE1 1 i - WiliMMINUMMIIIMMIL -IMM= ---1.IIIIEIIIIIIII MMLMIC,F. .M ..... 116 ...11._41raffinir..M11011016,. .,4010111.__ ) , FIG.4-DAMPER WITH ACTUATOR MOUNTED INTERNALLY FIG.6-DAMPER WITH ACTUATOR MOUNTED INTERNALLY (Allows access to the actuator through the grille) (Allows access to the actuator through the diffuser) 8 0 0 0 0 cl) 2 5 Q ........... %'..... 1 Illallit IC -..---.- I imii 4 II 0 _ 111.111rL11111E_11n01i1m1111_11I11,m1111-111•11-11•1111•1111■NM411r' M—M.-0M0I, AlitIlM1l11 I1NIM11 0 16 (406)Max. 16"(406)Max. 0 _ _ . _J A11 MOSMMLM4 a..---- 1 ITEM DESCRIPTION ITEM DESCRIPTION 1. Actuator(may be in or out of airstream) 7. Mounting Angles 11/2 x 11/2 x 16 gage min. 2. Damper Frame 8. Joint,Sleeve to Duct—Break-away Connections 3. TS150,EFL,PFL(location may vary) 9. Caulking Material 4. Sleeve 10. Steel Grille/Diffuser(by others) 5. Over-Center Link 11. Steel or Wood Stud Construction(single studs only) 6. Mounting Angles See Note 5. 12. Steel Construction only FRAMING DETAILS (STANDARD) Steel Stud Construction Wood Stud Construction 24"c-c 2C)C Max. ---.1 (610) fvt2#16d Nails; Max. i Min.(Typ) , _ 2 x 4(Nom) ,` r/ Steel Studs / Wood Studs 2 Sheet Metal7 —1I Min. � in Screws Stl.Runner 2"(51) Y 8"(203) 1 1 2"(51) 1 ! 4 f • sls"Min.U.L. Classified iDrywaU Typ. Both Sides Attach with Drywall Screws 12' C � I .\\ L _ _d rI L, -1r --I/ f I ' / Ll // I — / -1 Line Opening with 5/s"Min. / Cut Flanges,Bend Web Drywall Down&Secure to ,s/5"Min.U.L.Classified Runner w/2 Sheet Mtl. Drywall Typ.Both Sides Screws(Typ) Attach w/1-sir Drywall Screws 12"C-C or#6d Nails 7"c-C 3900 Dc Greaves Rd. RUSIiN® Kansas City,MO 6403C 316)761-7476 FAX(816)765-55.5 vv^anv.ruskin.ccm RUSKIN® 3900 Dr. Greaves Rd. • Kansas City, MO 64030 (816)761-7476 • FAX(816)765-8955 EFL ELECTRIC RESETTABLE "FUSE" LINK - OPERATION INSTRUCTIONS SUPPLEMENT APPLICATION f- o z The EFL Electric Resettable "Fuse" Link is a UL Classified heat responsive device is used in conjunction with Ruskin fire/smoke 1 a dampers.The EFL is standard on all fire/smoke dampers ordered ` Wall ,.........„......--- with ''with electric actuators. Fire/smoke dampers ordered with pneu- matic actuators may be ordered with the EFL and an EP ,'" (electro/pneumatic) switch. The EFL closes and locks the damper I 1 I when temperatures exceed 165°F (74°C) or 212°F (100°C) or ....----ti 250°F(121°C)or 350°F(177°C) depending on model ordered and Damper with installed. The EFL must be factory installed and cannot be I Actuator and EFL added in the field. Replacement EFL's may be field installed 0 -" with the approval of the local authority. ' OPERATION L✓"""' Fire Conditions 5 When temperatures in of 165`F ed,the , 212°F(100°C),250°F(121°C) or 350°F(177°C) are detected,th damper will close and lock. Upon cessation of fire conditions the 0 44611r. damper can be reopened by pressing the reset button located on the damper assembly. I, t L Smoke Conditions—When smoke signal is detected,the damper --.....---y, ` _ ° will close and remain closed until the smoke signal ceases(or the smoke detector is reset). The system will then reset and the 4 damper will open. a • The damper may be closed at any time by placing a control switch(optional)in the CLOSED position. • If the EFL is tripped accidentally or during system testing, the ITEM DESCRIPTION EFL must be reset by pressing the RESET button located on the damper assembly. 1. EFL165,EFL212, EFL250 or EFL350 Electric Reset Link • Refer to the appropriate damper installation instructions for 2. Flex Conduit details on damper installation. 3. Junction Box 4. Actuator or EP Switch 5. Over-Center Lock 0,SW/4 SEE COMPLETE 6. Damper Sleeve MARKING C llS ON PRODUCT 7. FAST,PFMA or conventional mounting angles 8. Sleeve to Duct Connection(by others) Pneumatic actuators to be piped per local codes. Electric actuators to be wired per the National Electric Code Addx ane (NEC)and local codes.See actuator for wiring diagrams. Motors - '� If Required wry" I ' Ern L2 EFL Wiring rx9TR A" -1 Compartment < BRN 4110 {�% tf © iTR �- — Control Smoke l ©t detector Switch Panel (if used) t_ J `` ` Manual 120 vac or 240 VAC 4 / Reset Button __.._ Fused Circuit II-EFL-1007/Replaces li-EFL-1104 ©Ruskin 2007 FSTF24 On/Off, Spring Return Fail-Safe, 24 VAC ' ` : Torque 18 in-lb,250°F for 30 min,for fire and smoke dampers Application �� The type FSTF spring-return actuator is intended for the operation of smoke � " and combination fire and smoke dampers in ventilation and air-conditioning systems.The actuator will meet requirements of UL555 and UL555S when tested as an assembly with the damper.Square footage of damper operated will depend on make and model per damper manufacturer UL testing. Operation LISTEDi Mounting of the actuator to the damper axle shaft or jackshaft is via a cold- TEMP.€aa,a C us; weld clamp.Teeth in the clamp and V-bolt dig into the metal of both solid and RE6.E6UIP. hollow shafts maintaining a perfect connection.The specially designed clamp Technical° will not crush hollow shafts.The bottom end of the actuator is held by an anti- Powei :apply 24 VAC±20° ,24 VDC-10° +�� v rotation strap or by a stud provided by the damper manufacturer.The actuator ;`0 ° ° Power Consumption Running 2 W;3 VA is mounted in its fail sate position with the damper blade(s)typically closed. Upon applying power,the actuator drives the damper to the open position.The Power Consumption Holding 1.5 W,2 VA internal spring is tensioned at the same time.If the power supply is interrupted, Transformer Sizing 5 VA(class 2 power source) ;lie spring moves the damper back to its fail-safe position. Shaft Diameter 1/4"to 1/2"round,centers on 1/2" Electrical Connection 3 ft.,18 GA appliance cable,1/2"conduit DiM00004801theamulb connector 0.68"[16.7] Overload Protection electronic throughout 0°to 95°rotation '' - :ter- _ Electrical Protection actuators are double insulated I 1 -� Angle of Rotation 95° .i.--------- . . torque 18 in-lbs[2 Nm]minimum m N 1131] Direction of Rotation can be selected by CCW/CW mounting 1 -. iisz-1 ---- - ) Position Indication visual indicator,0°to 95° (0°is full spring 6 92 [159.5] return position) Standard: "' —"1 = Manual Override No 0 /4 to 1/2" c lf -. _ 9_,K[0.2] [5.2] Running Time(Motor) <75 seconds @ 250°F[121°C] ❑ 1/4"to 5/16" o it* pl v' , Running lime(Fail-Safe) <25 seconds 4 32°F to 122°F[0°C to 50°C] M `0 J Humidity 5 to 95°I°RH non-condensing 0.77°[19.51—I 0.43"[11] 4.3"11141 Ambient Temperature Range 32°F to+122°F[0°C to+50°C] w Storage Temperature Range -40°F to+176°F[-40°C to+80°C] Safety Notes • Housing NEMA 2,IP42,UL enclosure type 2 Housing Material UL94 5VAScrew a conduit fitting into the actuator's bushing.Jacket the actuator's input a Agency Listingst cULus acc.to UL60730-1A/-2-14,CAN/CSA and output wiring with suitable flexible conduit.Properly terminate the conduit E E60730-1:02;Listed to UL 2043-suitable for in a suitable junction box. use in air plenums per Section 300.22(C)of the NEC and Section 602 of the IMC Retrofit Safety Note Noise Level(Motor) <45 dB(A) Use of the FSTF for replacement of other makes of actuators is limited in ci -3Noise Level(Fail-Safe) <62 dB(A) damper area.The FSLF is preferred for direct coupled applications.The FSTF Servicing maintenance free may be applied for linkage applications on dampers 1.5 sq.ft.and smaller at • Quality Standard ISO 9001 velocities under 2000 fpm. . Weight 1.26 lbs.(0.57 kg.) ✓ Part no. Clarnp side spring return o FSTF120 US CW Ncs FSTF120.1 US OW(bulk pack) • FSTF120.1 CCW CCW(bulk pack) FSTF120-S US CW CW 7,a FSTF120-S.1 US CW(bulk pack') 2 FSTF120-S.1 CCW CCW(bulk pack) v t UL File XAPx,.E108966 0 ,.,434. � i%er,�aiiiOc8664054989. ... --; ' ,yb BELIMO FSTF24 US On/Off, Spring Return Fail-Safe, 24 VAC Accessories KH-TF US Crankarm for Shafts to 1l2" KH-TF-1 US Crankarm for Shafts with 1/4"slot C(Blk) I 1 Common KH-TF-1.1 US Grankarm for Shafts with 1/4"slot H (Red) I 2 Hot TF-P Anti-Rotation Bracket TOOL-06 8 mm and 10 mm Wrench /3\ �ZDB-TF Angle of Rotation Limiter for TF ZG-TF2 Crankarm Adaptor Kit(includes mounting hardware) ZG-73 IF mounting tubes and hardware kit ZG-TF112 Crankarm Adaptor Kit(includes ZG-113 and KH-TF) • Ax. ZS-100 Weather Shield-Galvaneal ZS-150 Weather Shield-Polycarbonate 24 VAC/DC BAE165 US 165°F electric thermal sensor.SPST NC Detector or relay •• F&S Damper AH Croke id combination fire and smoke dampers shall he pio stied N,L2, with Belimo FSTF,FSLF,FSNF,or FSAF actuators.All substitutions must be HOT or COM approved before submission of bid.Damper and actuator shall have UL 555S Fusible link F&S Listing for 250°F&/or 350°F.Actuator shall have been tested to UL 2043 per or smoke requirements of IMC 602.2 and NEC 300.22(c).Where position indication is damper required-S models with auxiliary switches or damper blade switches wit be Actuator provided per code requirements. To alarm Whiff i'ilia trams .: system AProvide overload protection and disconnect as equii ed. Typical smoke or fusible link damper wiringi A. Actuators may also be powered by 24 VDC. Detector or relay F&S Damper A Actuators may be powered in parallel.Power consumption must be 165°F a observed. /� HOT N,L2, 7s Ground present on some models. I or COM Meets cULus requirements without the need of an electrical ground connection. Manual Actuator reset cn To alarm system o Typical containment damper control wiring N,L2,Com Hot 45 75 Parallel Actuator Wiring • 6J ., . hE ,. .� s" iwai�Al1Et ,.;,, ,i .< ,, ,. A FSLF24(-S)(-FC)14 d i Q ..__._........ FSLI230(-S) US L ....__ On/Off,Spring Return,350°F for Half Hour,15 Seconds Cycle Time up <,o N c, N. Application The type FSLF spring-return actuator is intended for the operation of smoke and combination fire and smoke dampers in ventilation and air-conditioning systems.The actuator will meet requirements of UL555 and UL555S when tested as an assembly i with the damper and will meet requirements of UBC for 15 second opening and closing.Square footage of damper operated will depend on make and model and the y temperature required. Fi Operation ` Mounting of the actuator to the damper axle shaft or jackshaft is via a cold-weld \.: ;; t clamp.Teeth in the clamp and V-bolt dig into the metal of both solid and hollow shafts maintaining a perfect connection.The specially designed damp will not crush hollow shafts.The bottom end of the actuator is held by an anti-rotation strap or by a stud ETE° 44°5 UL M>; provided by the damper manufacturer. TEMP.IND.7.° REG.£0918. The actuator is mounted in its fail-safe position with the damper blade(s)closed.Upon applying power,the actuator drives the damper to the open position.The internal Technical Data PSL -S rC} ;l'SLT U(-S)US spring is tensioned at the same time.If the power supply is interrupted,the spring Power supply moves the damper back to its fail-safe position. FSLF24(-SX-FC)US 24 VAC±20%,50/60 Hz FSLF230(-S)US 230 VAC±10%,50/60 Hz • Power consumption running 50/60 Hz,15 VA SAFETY NOTES 24 VAC holding 50/60 Hz,3.5 VA The actuator contains no components which the user can replace or repair. end stop 50/60 Hz 25 VA 24 VAC Connect via safety isolating transformer,Class 2 supply. 230 VAC running 50/60 Hz 17 VA 1/2"Threaded Connector holding 50/60 Hz 6.5 VA Screw a conduit fitting into the actuators metal bushing.Jacket the actuators end stop 50/60 Hz 27 VA input wiring with suitable flexible conduit.Properly terminate the conduit in a Fusing* suitable junction box. FSLF24 1 amp slow blow 3/8"Flex Connector(-FC models) FSLF230 0.125 amp slow blow Mount the flexible conduit into the actuators metal bushing by means of the Transformer sizing 25 VA per 24 VAC actuator provided screw with a torque of 1.2 Nm.Jacket the actuators input wiring with Electrical connection suitable flexible conduit.Properly terminate the conduit in a suitable junction box. FSLF24 US 3 ft,18 ga,2 color coded leads FSLF230 US 3 ft,18 ga,3 color coded leads Dimensions(Inches[rant]) FSLF...-S US 3 ft,18 ga,appliance cable Overload protection electronic throughout 0 to 95°rotation —....._. 7a:•._._. o auto-restart after temporary overload(FSLF230 5 5 5- 4.1 US grounded enclosure) [173] „• ,� ,7..._0.4E [11] ..-[281 Control microprocessor ttt Angle of rotation 95° U 791 I Torque 30 in-1b[3.5 Nm]minimum I o .�/'�3 from 32°F to 350°F[0°C to 177°C] 2:"e 4 1 3 relNI,�far [Qsl Direction of rotation spring can be selected by CCW/CW mounting , . �. OJ2 �� L min 0.5`e a Position indication visual indicator,0°to 95° [el — — //y [12.'] Running time motor <15 sec at rated voltage and torque 042' 32°F to+122°F[0°C to+50°C] [ g toil spring <15 seconds at rated voltage and torque a 075•[191 Humidity 5 to 95%RH non-condensing .. . 4 g Ambient temperature 32°F to 122°F[0°C to 50°C] 224' Ca Storage temperature -40°F to 176°F[-40°C to 80°C] 1$71 °; Housing NEMA type 1 'im'1kiiii i. 40 24,[5] e Housing material zinc coated steel Gears permanently lubricated Agency listings cULus acc.to UL60730-1A/-2-14,CAN/CSA *Individual Fusing or Breakers are not required by Belimo. E60730 1.CSA C22.2 Ne.24 93 The FSLF24 draws higher peak current when driving against any type of stop.Given 00 Servicing maintenance free the technology of fuses&breakers,this requires the value of fuse or breaker to be Quality standard ISO 9001 increased to avoid nuisance opening or tripping. A 1 amp slow blow should be used Weight for 24VAC.A 0.125 amp slow blow should be used for 230VAC. FSLF24(-S)US 3.4 lbs[1.7 kg],(+O.3 lbs(+0.14 kg]) FSLF230(-S)US 4.0 lbs[1.8 kg],(+0.3 lbs[+0.14 kg]) FSLF24-SR)4,15 FSLF230S tksr rI Auxiliary switch 2 x SPST 0.5 A inductive,3A resistive @ 120/ 250VAC,minimum 1 mA @ 5 VDC,.3 A ind,.5A res @ 24VDC,UL listed,10°and 85°. Double insulated 8C0413-903$ W64054089. 2oa-ni 8396 1N A/CBBEAN 1 FSLF24(-S)(-FC) US, - On/Off,Spring Return,350°F for Hall Hour,15 Seconds Cycle TimeBELIMO =rlis ..,` The typical fire and smoke damper requires from 5-15 in-lb of torque per square X INSTALLATION NOTES foot at 250°F-350°F under dynamic load(2000 fpm velocity).The FSLF is a single section damper actuator.For the multi section dampers,use the FSNF series. j`\ Provide overload protection and disconnect as required. This is a direct coupled actuator.If linkages are needed use the FSNF series. %\ CAUTION Equipment Damage! Actuators may be connected in parallel. • Power consumption and input impedance must be observed. ,i3'` No ground on 24 V models •\ S4 makes to SC when the actuator is powered open. For end position indication,interlock control,fan startup,etc., FSLF24-S US and FSLF230-S US incorporate two built-in Single section Two section for auxiliary switches. for one two FSLF actuators /\ Double insulated FSLF actuator • A WARNING Live Electrical Components! U During installation,testing servicing and troubleshooting of this product.it may be Typical Specification necessary to work with live electrical components.Have a qualified licensed electrician or i,,.yii ii `,ti�# #il at{SeC Actuators these tasks.Failure to follow all electrical safetyprecautions when exposed component perform other individual who has been properly trained in handling live elects All smoke and combination fire and smoke dampers shall beprovided with Belimo a posed to live electrical p components could result in death or serious injury. FSLF,FSNF,or FSAF actuators.No substitutions allowed.Damper and actuator shall have UL555S Listing for 250°F(350°F)and shall comply with UBC if required by local codes.Where proof of closure switches are required,blade switches,actuator .- auxiliary sln itches,or proximity switches hes are allowed.ed. S 24V 230V Replacement Applications C=BIk N=Blu I.1 Common,Neutral The number one"equal or better"requirement for use as a replacement for obsolete H_Red L1=Brn —410.......„!—I-2 Hot defective motors is the UL555S listing of the Belimo actuator with the damper for the I 1—3 Ground application. The local authority having jurisdiction sets the requirements. In some No ground on 21 V models cases a permit and inspection may be required. FSLF24 us FSLF23o US Go to www.belimo.us/firesmoke for a Cross Reference from old damper actuators to Belimo.Extensive retrofit installation instructions are available,along with technical training information. CAUTION 24V 230V Caution must be used when replacing failed motors with new Berne actuators. C=BIk N=Blu 1 1 �'- Many old motors did not have internal springs and depended on external springs o on the side of the damper or wrapped around the damper shaft to close the H=Red L1=Brn 2 2 damper Old motor springs must be removed or disabled. Do not remove fusible i link springs it they had only fire and no smoke functions God Gndco In some cases a BAE 16>5 or equal thermal sensor must be installed I A 0 Parallel Actuator Wiring E o o. Violet I---S1 _ ff • Violet I—S2 o 2 10=A 5 to rayI ,.,,, S671!) 85° FSLF2,,..,,,,.US FSLF230- i ='nxiliary switch wiring for FSLF24-S US,FSLF23O-S US 800.543_903B 2