Report (64) `? .,(.-?- -0 \ 0 ooct 1 5.\,Q
Fire Marshal's Offices ,�;�1 162,e_ Qd . �/51,(1,,,3, 1
Al.
WO
North Division South Division East Division
4755 SW Griffith Dr. 7401 SW Washo Court 320 Warner Milne Rd
Beaverton, OR 97076 Tualatin, OR 97062 PO Box 351
(503)526-2469 (503)612-7000 Oregon City, OR 97045
Fax (503)526-2538 Fax(503)612-7003 (503)652-1365
Fax(503)657-791
Page 1 oft Building Survey Report AEC;
FMZ : (to be filled out by TVF&R) Code Edition: OSSC 2014 , __ 04
Name of Facility: The Fields Apartments yy t ^�,F0g k:,),-,
'1,jt 3 F4 91/7"4�i7 ,,
Name of Building: Building 4 6
Address: 7820 SW Hunziker Rd, Tigard, OR 97223
Owner:DBG Properties LLC Telephone No. ( 503 )816.74084
Architect: Otak Architects Inc Telephone No. ( 503 )415-2393
Architect Address: 808 SW Third Ave, Suite 300, Portland, OR 97204
ITEM COMM DESCRIPTION
1. Occupancy R-2 Type IUse 48 Apartments Capacity 267
2. Construction Type VA Year Built 2018/2019
3. Area(Sq.Ft.) 13,824 Total Largest Floor None Basement None
4. Stories 4 No. Height High Rise ❑Y ON
5 a. Exterior Wall Construction 1 hr All WF-1 hr
b. Opening Protection None Not required due to fire separation distance.
6. Interior Wall Construction 1 hr Interior bearing walls are 1 hour WF.
7. Floor Construction 1 hr 1 hour wood floor assembly with gyperete.
8. Roof Construction 1 hr 1 hour wood roof assembly.
9. Attic Draft Stops None No. None Required
10a. Occ.Sep.Wall Construction 1 hr No. R-2 from S-1
b. Opening Protection None
1 la. Area Sep.Wall Construction None No.
b. Opening Protection None
12a. Smoke Barrier Wall Construction None No.
b. Opening Protection None
13a. Corridor Wall Construction 1 hr 1 hour WF
b. Opening Protection 30 min Doors
14a. Corridor Ceiling Construction 1 hr 1 hour wood floor assembly with gyperete.
b. Opening Protection None
15a. Shafts 2 hr No. 2 Type WF w/GB
b. Opening Protection Yes Automatic fire damper
Building Survey Report
FMZ : (to be filled out by TVF&R)
Name of Facility: The Fields Apartments
ITEM COMM. DESCRIPTION
16a. Stair Enclosure 2 hr No.2 I WF w/GB
b. Opening Protection 90 min Rated door assemblies
17. Stairs YES No. 2
18. Ramps NO No.0
19. Interior Finish Class Room Corridor Exit Enclosure
20. Exits YES No.4 Total Width 136"
21. Exit Hardware Type YES See hardware schedule
22a. Exit Signs/Illumination YES See electrical drawings
b. Emergency Lighting YES See electrical drawings
23. Auto Sprinkler Coverage YES Full Coverage NFPA 13
24. Standpipe Class/Locations YES Class I in Stair 1
25. Fire Alarm Type/Coverage YES Full Coverage
26. Heating,Ventilation&Air Conditioning SC Type Unit Heaters Fuel Electric Trickle Vents
27. Electrical Installation
28. Stage/Platform NO
29. Hazardous Area NO
30. Other
Comments:
Alternate Materials&Methods
TVF&R Use Only
Inspected By: Date No.Attachments