Loading...
Report (60) OFFICE COPY tkk"5 Cr4tA60-- CO RECEry Dko Worldwide Fire Protection FEB 1 2 ?019 Contacts www.tyco-fire.com Products CITY OF TIGAR ) BUILDING DIVISIOi` Series TY-B, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General NOTICE The Series TY-B Sprinklers described Description herein must be installed and main- tained in compliance with this docu- "� The TYCO Series TY-B, 5.6 K-factor, ment, as well as with the applicable '" Upright (TY315) and Pendent (TY325) standards of the National Fire Protec- ,_ _ , l' Sprinklers described in this data sheet tion Association,in addition to the stan- l are standard response, standard cov- dards of any other authorities having erage, decorative 5 mm glass bulb jurisdiction.Failure to do so may impair - type spray sprinklers designed for use the performance of these devices. --41:11.- in light,ordinary,or extra hazard,cornThe owner is responsible for main- • . mercial occupancies such as banks, taming their fire protection system hotels,shopping malls,factories,ref in- and devices in proper operating con- eries,and chemical plants. dition. Contact the installing contrac- The recessed version of the Series tor or product manufacturer with any TY-B Pendent Sprinkler,where applica- questions. ble, is intended for use in areas with a finished ceiling.This recessed pendent Sprinkler ` sprinkler uses one of the following: == • A two-piece Style 15 Recessed Identification .., 00111 Escutcheon with recessed adjust- ` ` — ' ment up to 5/8 inch (15,9 mm)from Numbers (SINS) "`, the flush pendent position. • A two-piece Style 20 Recessed TY315 Upright 5.6K, 1/2"NPT TY325 Pendent 5 Escutcheon with recessed adjust- .6K,1/2""NPT • ,.gip• , ment up to 1/2 inch (12,7 mm) from Technical the flush pendent position. The adjustment provided by the Data Operation Recessed Escutcheon reduces the accuracy to which the fixed pipe drops Approvals The glass bulb contains a fluid which to the sprinklers must be cut. Refer to Table A expands when exposed to heat.When Intermediate level versions of Series Maximum Working Pressure the rated temperature is reached, the TY-B Sprinklers are described in Tech- 175 psi(12.1 bar) fluid expands sufficiently to shatter the nical Data Sheet TFP352. Sprinkler 250 psi(17.2 bar)* glass bulb, allowing the sprinkler to guards and shields are described in 'Themaximumactivate and water to flow. working pressure of 250 psi(17.2 bar) Technical Data Sheet TFP780. only applies to the listing by Underwriters Laborato- ries,Inc.(UL). Design Discharge Coefficient Criteria K=5.6 GPM/psis=(80,6 LPM/bari) Temperature Ratings The TYCO Series TY-B, 5.6 K-factor, Refer to Table A Upright (TY315) and Pendent (TY325) Finishes Sprinklers are intended for fire protec- IMPORTANT Sprinkler:Refer to Table B tion systems designed in accordance Always refer to Technical Data Recessed Escutcheon:White Coated, with the standard installation rules Sheet TFP700 for the "INSTALLER Black Coated,Chrome Plated,or Brass recognized by the applicable Listing WARNING" that provides cautions Plated or Approval agency (e.g., UL Listing with respect to handling and instal- is based on the requirements of NFPA lation of sprinkler systems and com- Physical Characteristics 13, and FM Approval is based on the ponents. Improper handling and Frame Bronze requirements of the FM Loss Preven- installation can permanently damage Bettor, Brass/Copper tion Data Sheets). Only the Style 15 a s rinkler s y stem or its com D Sealing Assembly...Stainless Steel w/TEFLON or Style 20 Recessed Escutcheon, as p P Bulb Glass nents and cause the sprinkler to fail Compression Screw Bronze applicable, is to be used for recessed to operate in a fire situation or cause Deflector Bronze pendent installations. it to operate prematurely. Page 1 of 4 JULY 2017 TFP152 TFP152 Page 2 of 4 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON 5 �I 7/16" Y ___------ / �R_ 7-7 (11,1 mm) _ �----_ } :��f:c 4 NOMINAL 2" 1 MAKE-IN ' (50,82 mm) 1 2 D' a do 2" i 1-3/8" 3 (50,8 mm) (34,9 mm) `_F WRENCH 1 f FLATS t / 1/2"NPT** DEFLECTOR* I— 2-7/8"(73,0 mm)DIA. --- CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-B UPRIGHT(TY315)AND PENDENT(TY325)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT,STANDARD RESPONSE Installation Step 2. With pipe-thread sealant applied to the pipe threads, hand- WRENCH RECESS The TYCO Series TY-B, 5.6 K-factor, tighten the sprinkler into the sprinkler Upright (TY315) and Pendent (TY325) fitting. {USE ONLY Sprinklers must be installed in accor- Step 3. Tighten the sprinkler into the ...... END"A") dance with this section. sprinkler fitting using only the W-Type '� General Instructions 6 Sprinkler Wrench(Figure 2).With ref- FIGURE 2 Do not install any bulb type sprinkler erence to Figure 1,apply the W-Type 6 W-TYPE 6 if the bulb is cracked or there is a loss Sprinkler Wrench to the wrench flats. SPRINKLER WRENCH of liquid from the bulb. With the sprin Torque sprinklers 7 to 14 ft. lbs.(9,5 to kler held horizontally,a small air bubble 19,0 Nm). should be present.The diameter of the Recessed Pendent Sprinklers WRENCH air bubble is approximately 1/16 inch The Series TY-B Recessed Pendent RECESS (1,6 mm) for the 135°F (57°C) to 3/32 Sprinklers must be installed in accor- inch (2,4 mm) for the 360°F (182°C) dance with the following instructions. 0°7°- ) °, temperature ratings. Step A.After installing the Style 15 or r A leak-tight 1/2 inch NPT sprinkler joint Style 20 Mounting Plate, as applica- t I� should be obtained by applying al min- ble,over the sprinkler threads and with imam-to-maximum torque of 7 to 14 pipe-thread sealant applied to the pipe ., ft.-lbs. (9,5 to 19,0 Nm). Higher levels threads,hand-tighten the sprinkler into \�, of torque may distort the sprinkler inlet the sprinkler fitting. and cause leakage or impairment of the PUSH WRENCH sprinkler. Step B. Tighten the sprinkler into the IN TO ENSURE sprinkler fitting using only the W-Type ENGAGEMENT Do not attempt to compensate for 7 Recessed Sprinkler Wrench (Figure WITH SPRINKLER insufficient adjustment in the escutch- 3).With reference to Figure 1,apply the WRENCHING AREA eon plate by under- or over-tightening W-Type 7 Recessed Sprinkler Wrench the sprinkler. Readjust the position of to the sprinkler wrench flats. Torque FIGURE 3 the sprinkler fitting to suit. sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 W-TYPE 7 RECESSED Nm). SPRINKLER WRENCH Upright and Pendent Sprinklers The Series TY-B Upright and Pendent Step C.After the ceiling is installed or Sprinklers must be installed in accor- the finish coat is applied, slide on the dance with the following instructions. Style 15 or Style 20 Closure over the Step 1.Install pendent sprinklers in the Series TY-B Sprinkler and push the Closure over the Mounting Plate until pendent position; install upright sprin- klers in the upright position. its flange contacts the ceiling. TFP152 Page 3 of 4 Care and - 2-7/8"DIA. - (73,0 mm) Maintenance 2-1/4"DIA. The TYCO Series TY-B, 5.6 K-factor, FACE OF — (57,2 mm) Upright (TY315) and Pendent (TY325) SPRINKLER Sprinklers must be maintained and ser- FITTING 5/8"(15,9 mm) viced in accordance with this section. + \ _ em FLUSH I Before closing a fire protection system 3/8±5/16" —� main control valve for maintenance (9,5±7,9 mm) 1 'r / work on the fire protection system 1 / --- j that it controls, obtain permission to I MOUNTING 1/8" J shut down the affected fire protection (3,2 mm) system from the proper authorities SURFACE ___y_ and notify all personnel who may be CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) affected by this action. TV B PLATE 3/4"(19,1 mm) Absence of the outer piece of an escutcheon, which is used to cover FIGURE 4 a clearance hole, can delay sprinkler SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY(TY325) operation in a fire situation. WITH TWO-PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 RECESSED ESCUTCHEON The owner must assure that the sprin- klers are not used for hanging any objects and that the sprinklers are only _ 2-7/8"DIA. cleaned by means of gently dusting (73,0 mm) with a feather duster; otherwise, non- FACE OF operation in the event of a fire or inad- SPRINKLER 2-1/4"DIA. _ vertent operation may result. FITTING (57,2 mm) Sprinklers which are found to be 5/16±1/4" leaking or exhibiting visible signs of (7,9±6,4 mm) 1/2"(12,7 mm) corrosion must be replaced. + FLUSH Automatic sprinklers must never be I 7 + 1 painted, plated, coated, or other- �` wise altered after leaving the factory. } I memr Modified sprinklers must be replaced. MOUNTING wo (3,21/8m"m)J Sprinklers that have been exposed to SURFACE corrosive products of combustion, but have not operated,should be replaced if they cannot be completely cleaned CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) by wiping the sprinkler with a cloth or TY-B PLATE 7/8"(22,2 mm) by brushing it with a soft bristle brush. FIGURE 5 Care must be exercised to avoid SERIES TY-B RECESSED PENDENT SPRINKLERASSEMBLY(TY325) damage to the sprinklers before, WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 during, and after installation. Sprin- RECESSED ESCUTCHEON klers damaged by dropping, striking, wrench twist/slippage,or the like,must Automatic sprinklers are recommended Sprinkler Assemblies with NPT be replaced. Also, replace any sprin- to be inspected,tested,and maintained Thread Connections kler that has a cracked bulb or that has by a qualified Inspection Service in Specify: Series TY-B Upright or lost liquid from its bulb. (Ref. Installa- accordance with local requirements Pendent (specify) Sprinkler, SIN tion Section.) and/or national codes. (specify), K=5.6, Standard Response, Thereafter, annual inspections per (specify) temperature rating, (specify) NFPA 25 are required;however,instead ___ finish, P/N(specify, refer to Table B) of inspecting from the floor level, aRecessed Escutcheon random sampling of close-up visual Warranty Specify: Style 15 Recessed Escutch- inspections should be made. eon with(specify*)finish,P/N(specify') For warranty terms and conditions,visit The owner is responsible for the www.tyco-fire.com. Specify: Style 20 Recessed Escutch- inspection,testing,and maintenance of eon with(specify')finish,P/N(specify') their fire protection system and devices in compliance with this document, as Ordering 'Refer to Technical Data Sheet TFP770 well as with the applicable standards Sprinkler Wrench of the National Fire Protection Asso- Procedure Specify: W-Type 6 Sprinkler Wrench, ciation (e.g., NFPA 25), in addition to P/N 56-000-6-387 Contact your local distributor for avail the standards of any other authorities ability.When placing an order, indicate Specify: W-Type 7 Sprinkler Wrench, having jurisdiction.Contact the install- the full product name and Part Number P/N 56-850-4-001 ing contractor or product manufacturer (P/N) with any questions. r TFP152 Page 4 of 4 BULB SPRINKLER FINISH(7) K SPRINKLER TEMPERATURE LIQUID TYPE RATING COLOR NATURAL CHROME POLYESTER** BRASS PLATED 135°F(57°C) Orange UPRIGHT 155°F(68°C) Red (TY315) and 175°F(79°C) Yellow PENDENT 200°F(93°C) Green 1,2,3,4,5,6, (TY325) 5.6 Figure 1 286°F(141°C) Blue 1/2" 360°F(182°C) Mauve NPT 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT1,2,3,4, 175°F(79°C) Yellow (TY325)* Figures 4 and 5 200°F(93°C) Green 286°F(141°C) Blue 1,2 Notes: 1. Listed by Underwriters Laboratories,Inc.(UL) 2. Listed by Underwriters Laboratories,Inc.for use in Canada(C-UL) 3. Approved by FM Global(FM Approvals) 4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/03) 5. VdS Approved(For details contact Tyco Fire Suppression&Building Products,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377) 6. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/05) 7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. * Installed with Style 15(1/2"NPT)5/8-Total Adjustment Recessed Escutcheon,as applicable "*Frame and deflector only N/A-Not Applicable TABLE A SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS LABORATORY LISTINGS AND APPROVALS P/N* 77 - XXX - X - XXX 1 SIN SPRINKLER TEMPERATURE FINISH RATINGS 570 5.6K UPRIGHT(1/2"NPT) TY315 1 NATURAL BRASS 135 135°F(57°C) 571 5.6K PENDENT(1/2"NPT) TY325 3 PURE WHITE(RAL9010)*` 155 155°F(68°C) POLYESTER 4 SIGNAL WHITE(RAL9003) 175 175°F(79°C) POLYESTER 5 JET BLACK(RAL9005) 200 200°F(93°C) POLYSTER 9 CHROME PLATED 286 286°F(141°C) 360 360°F(182°C) " Use suffix°l"for ISO 7-1 connection;for example,77-570-4-175-I *" Eastern Hemisphere sales only 000 OPEN*** ***OPEN indicates sprinkler assembly without Glass Bulb,Button,and Sealing Assembly TABLE B SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446)Telephone+1-215-362-0700 Copyright©2017 Tyco Fire Products, LP. All rights reserved. ticc TEFLON is a registered trademark of DuPont Fire Protection Products