Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Report
TRANE° Submittal RECEIVED JAN 17 2019 Prepared For: Date: October 31, 2017 CITY OF TIGARD Mechanical Bidders BUILDING DIVISION Customer P.O. Number: Customer Project Number: Sold To: Job Number: Job Name: Taco Bell- Tigard, OR Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval. Product Summary Qty Product 1 7.5 Ton R410A PKGD Unitary Gas/Electric Rooftop 1 12.5 Ton Packaged Gas/Electric Rooftop Units The attached information describes the equipment we propose to furnish for this project,and is submitted for your approval. Product performance and submittal data is valid fora period of 6 months from the date of submittal generation. If six months or more has elapsed Ruthann McCracken between submittal generation and equipment release, the product Trane performance and submittal data will need to be verified. It is the customer's responsibility to obtain such verification. Phone: 866-986-4822 Fax: 502-491-5655 J:IJOBS139151123358121Taco Bell- Tigard, OR sub.doc Table Of Contents Product Summary 1 3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop(Item Al) 3 Tag Data 3 Product Data 3 Mechanical Specifications 4 Unit Dimensions 8 Weight, Clearance&Rigging Diagram 12 Accessory 14 Field Wiring 19 Packaged Gas/Electric Rooftop Units(Item B1) 20 Tag Data 20 Product Data 20 Mechanical Specifications 21 Unit Dimensions 24 Weight, Clearance&Rigging Diagram 26 Accessory 28 Field Installed Options -Part/Order Number Summary 31 3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop 31 Packaged Gas/Electric Rooftop Units 31 Taco Bell-Tigard,OR October 31,2017 Tag Data-3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop (Qty: 1) Item Tag(s) Qty Description Model Number Al No Tag 1 7.5 Ton SZVAV Gas/Electric YHC092F3RMA--F6C1C2A000C0000000000000 RTU 000 Product Data -3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop Item: Al Qty: 1 DX cooling, gas heat High efficiency Convertible configuration 7.5 Ton Dual compressor Major design sequence 208-230/60/3 Microprocessor controls 3ph Medium gas heat 3ph Economizer Reference Enthalpy 0-100% with Barometric Relief Single Zone VAV Hinged panels/2 in pleated filters Mery 8 Standard condenser coil w/hail guard Through the base gas &electrical 3ph Circuit breaker Unpowered convenience outlet(3ph units) Return/supply air smoke detector 3ph Roof curb (Fld) Year 6-10 heat exchanger warranty FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 3 of 31 Others Taco Bell-Tigard,OR October 31,2017 Mechanical Specifications-3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop Item: Al Qty: 1 General The units shall be convertible airflow. The operating range shall be between 115°F and 0°F in cooling as standard from the factory for units with microprocessor controls. Operating range for units with electromechanical controls shall be between 115°F and 40°F. Cooling performance shall be rated in accordance with ARI testing procedures.All units shall be factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check cooling operation, fan and blower rotation, and control sequence before leaving the factory. Wiring internal to the unit shall be colored and numbered for simplified identification. Units shall be cULus listed and labeled, classified in accordance for Central Cooling Air Conditioners. Casing Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Unit's surface shall be tested 672 hours in a salt spray test in compliance with ASTM B117. Cabinet construction shall allow for all maintenance on one side of the unit. Service panels shall have lifting handles and be removed and reinstalled by removing two fasteners while providing a water and air tight seal. All exposed vertical panels and top covers in the indoor air section shall be insulated with a cleanable foil-faced, fire-retardant permanent, odorless glass fiber material. The base of the unit shall be insulated with 1/8 inch, foil-faced, closed-cell insulation. All insulation edges shall be either captured or sealed. The unit's base pan shall have no penetrations within the perimeter of the curb other than the raised 1 1/8 inch high downflow supply/return openings to provide an added water integrity precaution, if the condensate drain backs up. The base of the unit shall have provisions for forklift and crane lifting, with forklift capabilities on three sides of the unit. Unit Top The top cover shall be one piece construction or, where seams exist, it shall be double-hemmed and gasket-sealed. The ribbed top adds extra strength and enhances water removal from unit top. Two-Inch Pleated Filters 2" pleated media filters shall be available on all models. Compressors All units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of unit nameplate voltage. Internal overloads shall be provided with the scroll compressors. Dual compressors are outstanding for humidity control, light load cooling conditions and system back-up applications. Dual compressors are available on 7'/-10 ton models and allow for efficient cooling utilizing 3-stages of compressor operation for all high efficiency models. Notes: Crankcase heaters are optional on YSC(036, 048, 060, 072,090, 102, 120); standard on YHC(036, 048, 060, 072, 092, 102, 120). Indoor Fan The following units shall be equipped with a direct drive plenum fan design (T/YSC120F,T/YHC074F, T/YHC092F,T/YHC102F, 120F). Plenum fan design shall include a backward-curved fan wheel along with an external rotor direct drive variable speed indoor motor. All plenum fan designs will have a variable speed adjustment potentiometer located in the control box. 3 to 5 ton units (high efficiency 3-phase with optional motor)are belt driven, FC centrifugal fans with adjustable motor sheaves. 3 to 5 ton units (standard and high efficiency 3-phase) have multispeed, direct drive motors. All 6 to 8%ton units(standard efficiency)shall have belt drive motors with an adjustable idler-arm assembly for quick-adjustment to fan belts and motor sheaves. All motors shall be thermally protected. All 10 tons, 6 ton (074), 7%to 8%(high efficiency) units have variable speed direct drive motors. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). Outdoor Fans The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge position. The fan motor shall be permanently lubricated and shall have built-in thermal overload protection. Single Zone VAV-One Zone Variable Air Volume Mode Single zone VAV is designed for use in single zone applications like gymnasiums, auditoriums, manufacturing facilities, retail box stores, and any large open spaces, where there is a lot of diversity in the load profile. Single Zone VAV(SZ FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 4 of 31 Others Taco Bell-Tigard,OR October 31,2017 VAV)is an ideal replacement to yesterdays constant volume(CV)systems, by reducing operating costs while improving occupant comfort. SZ VAV systems combine Trane application, control and system integration knowledge to exactly match fan speed with cooling and heating loads, regardless of the operating condition. Trane algorithms meet/exceed ASHRAE 90.1-2010, SZ VAV energy-saving recommendations, and those of CA Title 24. The result is an optimized balance between zone temperature control and system energy savings. Depending on your specific application, energy savings can be as much as 20+%. Note: Building system modeling in energy simulation software like TRACE is recommended to evaluate performance improvements for your application. SZ VAV is fully integrated into the ReliaTel Control system and is available today. It provides thesimplest and fastest commissioning in the industry through proven factory-installed, wired, and tested system controllers. All control modules, logic and sensors are factory installed, and tested to assure the highest quality and most reliable system available.This means no special programming of algorithms,or hunting at the jobsite for sensors, boards, etc. that need to be installed in the field. Single zone VAV is a quick and simple solution for many applications and is available from your most trusted rooftop VAV system solution provider-Trane. Evaporator and Condenser Coils Internally finned, 5/16"copper tubes mechanically bonded to a configured aluminum plate fin shall be standard. Evaporator coils are standard for all 3 to 10 ton standard efficiency models. Microchannel condenser coils are standard for all 3 to 10 ton standard efficiency models and 4, 5, 6, 7.5, 8.5 ton high efficiency models. The microchannel type condenser coil is not offered on the 4 and 5 ton dehumidification model. Due to flat streamlined tubes with small ports, and metallurgical tube-to-fin bond, microchannel coil has better heat transfer performance. Microchannel condenser coil can reduce system refrigerant charge by up to 50% because of smaller internal volume, which leads to better compressor reliability. Compact all-aluminum microchannel coils also help to reduce the unit weight. These all aluminum coils are recyclable. Galvanic corrosion is also minimized due to all aluminum construction. Strong aluminum brazed structure provides better fin protection. In addition, flat streamlined tubes also make microchannel coils more dust resistant and easier to clean. Coils shall be leak tested at the factory to ensure the pressure integrity. The evaporator coil and condenser coil shall be leak tested to 600 psig.The assembled unit shall be leak tested to 465 psig. The condenser coil shall have a patent pending 1+1+1 hybrid coil designed with slight gaps for ease of cleaning. A plastic, dual-sloped, removable and reversible condensate drain pan with through-the-base condensate drain is standard. Tool-less Hail Guards Tool-less, hail protection quality coil guards are available for condenser coil protection. Controls Unit shall be completely factory-wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Unit shall provide an external location for mounting a fused disconnect device. A choice of microprocessor or electromechanical controls shall be available. Microprocessor controls provide for all 24V control functions.The resident control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes drift from set point,and provides better building comfort.A centralized microprocessor shall provide anti-short cycle timing and time delay between compressors to provide a higher level of machine protection. 24-volt electromechanical control circuit shall include control transformer and contactor High Pressure Control All units include High Pressure Cutout as standard. Phase monitor Phase monitor shall provide 100% protection for motors and compressors against problems caused by phase loss, phase imbalance, and phase reversal. Phase monitor is equipped with an LED that provides an ON or FAULT indicator. There are no field adjustments. The module will automatically reset from a fault condition. Refrigerant Circuits Each refrigerant circuit offer thermal expansion valve as standard. Service pressure ports, and refrigerant line filter driers are factory-installed as standard. An area shall be provided for replacement suction line driers. Gas Heating Section The heating section shall have a progressive tubular heat exchanger design using stainless steel burners FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 5 of 31 Others Taco Bell-Tigard,OR October 31,2017 and corrosion resistant steel throughout. An induced draft combustion blower shall be used to pull the combustion products through the firing tubes. The heater shall use a direct spark ignition (DSI) system. On initial call for heat, the combustion blower shall purge the heat exchanger for 20 seconds before ignition After three unsuccessful ignition attempts,the entire heating system shall be locked out until manually reset at the thermostat/zone sensor. Units shall be suitable for use with natural gas or propane(field-installed kit)and also comply with the California requirement for low NOx emissions (Gas/Electric Only). Hinged Access Doors Sheet metal hinges are available on the Filter/Evaporator, Supply Fan/Heat, and the Compressor/Control Access Doors. Powered or Unpowered Convenience Outlet This is a GFCI, 120v/15amp, 2 plug, convenience outlet, either powered or unpowered.When the convenience outlet is powered, a service receptacle disconnect will be available. The convenience outlet is powered from the line side of the disconnect or circuit breaker, and therefore will not be affected by the position of the disconnect or circuit breaker. This option can only be ordered when the Through the Base Electrical with either the Disconnect Switch or Circuit Breaker option is ordered. Plenum Fan The following unit shall be equipped with a direct drive plenum fan design (all 10 tons and 7.5-8.5 ton high efficiency units). Plenum fan design shall include a backward-curved fan wheel along with an external rotor direct drive variable speed indoor motor. All plenum fan designs will have a variable speed adjustment potentiometer located in the control box. Economizer This accessory shall be available with or without barometric relief. The assembly includes fully modulating 0-100 percent motor and dampers, minimum position setting, preset linkage, wiring harness with plug, spring return actuator and fixed dry bulb control. The barometric relief shall provide a pressure operated damper that shall be gravity closing and shall prohibit entrance of outside air during the equipment off cycle. Optional solid state or differential enthalpy control shall be available for either factory or field installation. The economizer arrives in the shipping position and shall be moved to the operating position by the installing contractor. Through the Base Gas Piping The unit shall include a standard through the base gas provision. This option shall have all piping necessary including, black steel, manual gas shut-off valve, elbows, and union. The manual shutoff valve shall include a 1/8" NPT pressure tap. This assembly will require minor field labor to install. Through the Base Electrical Access An electrical service entrance shall be provided allowing electrical access for both control and main power connections inside the curb and through the base of the unit. Option will allow for field installation of liquid-tight conduit and an external field-installed disconnect switch. Through the Base Electrical with Circuit Breaker This option is a thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections. The circuit breaker will be installed in a water tight enclosure in the unit with access through a swinging door. Wiring will be provided from the switch to the unit high voltage terminal block. The circuit breaker will provide overcurrent protection, be sized per NEC and UL guidelines, and be agency recognized by UL/CSA. Supply and/or Return Air Smoke Detector Smoke detector shall be factory installed photoelectric smoke detector mounted in the return air section (with or without the economizer or motorized damper option), AND/OR in the supply air fan compartment. The detector will be wired for continuous power whenever the unit is energized. Upon detection of smoke, the detector will shut down all unit operations. Local codes may dictate the location of detectors. Note: Due to the shipping position of the economizer or motorized damper, the return air smoke detector will not be completely factory installed. The wiring harness for the detector will be routed and tied off in the fan compartment for shipping. The smoke detector and barometric damper hood will also be installed in a shipping position in the fan compartment. Accessory -Roof Curb The roof curb shall be designed to mate with the unit's downflow supply and return and provide support and a water tight installation when installed properly. The roof curb design shall allow field fabricated rectangular supply/return ductwork to be connected directly to the curb. Curb design shall comply with NRCA requirements. Curb shall be shipped knocked down for field assembly and shall include wood nailer strips. FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 6 of 31 Others Taco Bell-Tigard,OR October 31,2017 Trane Single Zone Variable Air Volume Control Sequence of Operation (Precedent 17 Plus) General Standby Mode During normal occupied periods, when there is no space cooling or heating demands, the user will be able to choose Continuous or Cycling supply fan operation. During this period, if the supply fan is operating due to a Continuous Fan Mode selection or due to a ventilation request, the supply fan will operate at 50%of the user selected, application specific, maximum airflow. The unit controls will be compatible with BACnet and LonTalk Building Automation System communication interfaces. Cooling Operation Default Operation: During Cooling operation, the control will monitor the Space Temperature and Space Cooling setpoint and with a PI control algorithm determine if active cooling capacity is required. As the Space Temperature deviates from the Space Cooling Setpoint, the unit controller will calculate an active Discharge Air Cooling setpoint that the economizer(if installed)and compressor outputs will be controlled to meet. This active Discharge Air Cooling setpoint will be calculated between the Space Cooling setpoint and a user adjustable minimum (65F Default for Single Zone Variable Air Volume Control). Once the control determines that a discharge air temperature equal to the user selected minimum (65F Default) is required to meet the space cooling demand, if the space demand continues to increase, the supply fan speed will be allowed to increase above its minimum speed proportionally to meet the additional demand. Alternate Economizer Operation: Under the Default Operation, as described above, the supply fan speed will remain at minimum speed, as determined by the active cooling stages, until the space demand requires an increase in supply airflow. The customer will have the ability to choose to allow the supply fan speed to increase when the economizer is enthalpy enabled in order to realize the maximum cooling capacity of the economizer, prior to energizing compressor outputs, when the space requires active cooling capacity. All cooling capacity demand decisions will function as described in the"Default Operation"section above with the exception of the supply fan speed when the unit has an active cooling demand and the economizer is enthalpy enabled. Heating Operation During Heating operation, the control will monitor the Space Temperature and Space Heating setpoint and with a PI control algorithm determine if active heating capacity is required. As the Space Temperature deviates from the Space Heating Setpoint, the unit controller will increase the supply airflow up to the user selected, application specific, maximum airflow and begin to stage heating outputs (gas or electric)to meet the space demand. The customer will also have the ability to enable Supply Air Tempering control which will allow the unit to bring on one stage of heating when the discharge air temperature falls below the Space Heating Setpoint- 10°F and the unit is operating in a minimum ventilation state with the supply fan running (not actively heating or cooling). The supply fan output will increase to the user selected, application specific, maximum airflow during Supply Air Tempering operation. Supply, Return, and Plenum Air Smoke Detector With this option installed, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. In order for the supply air smoke detector or return air smoke detector to properly sense smoke in the supply air stream or the return air stream, the air velocity entering the smoke detector unit must be between 500 -4000 feet per minute. Equipment covered in this manual will develop an airflow velocity that falls within these limits over the entire airflow range specified in the evaporator fan performance table. Supply and/or Return Smoke Detectors may not be used with the Plenum Smoke Detector. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 7 of 31 Others Taco Bell-Tigard,OR October 31,2017 Unit Dimensions -3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop Item: Al Qty: 1 TOP PANEL EVAPORATOR I\ SECTION ACCESS PANEL CONDENSER FAN CONDENSATE DRAIN(ALT) ,/r. 3/4"-14 NPT DIA.HOLE •`�1����-�S.M.„r.1-.-------..-1 t \ CONDENSER COIL I 4 1/4" !, is I 27 /8" ` ,rUNIT CONTROL WIRE 7/8"DIA.HOLE i '„ SERVICE GAUGE PORT ACCESS 13!8"DIA.HOLE 47 7!8" Fre- UNIT POWER WIRE IiuJ - 1/T NPT GAS CONNECTION r` (80MBH&120MBH) 3/4"NPT GAS CONNECTION CONTROL AND COMPRESSOR ACCESS PANEL (150MBH,200MBH&250MBH) PACKAGED GAS/ELECTRICAL THROUGH THE ISOMETRIC VIEW BASE CONDENSATE 41/8" 27 5/8"-- 7 , NOTES: 1.THRU-THE-BASE ELECTRICAL IS NOT STANDARD ON ALL UNITS. 2.VERIFY ALL DIMENSIONS WITH INSTALLER DOCUMENTS BEFORE INSTALLATION. 4,0m,' f -_, ---- t X11 'IF 33" 32 1/8" SUPPLY RETURN [ ! IMINNINNMENNI.I 4 - 17 1/2" - 9 7/8" - 17 1/2" - 3 5/8" PLAN VIEW UNIT DIMENSION DRAWING 46 7/8" ' HORIZONTAL RETURN 32 1/4" AIR FLOW 23 7/8" SUPPLY 1_ 241/2"9 5!8" ' IiIiiiI I b 1 0 0 L_J l _ I O O 43/4" , 55/8' III Il ��—J• 191/4" 93/8"x-16 3/4"-=- - 3 7/8" 4 1/4" - ii CONDENSATE 5 5/8" I - 88 5/8" - 7 5/8" - - PACKAGED GAS/ELECTRICAL - 53 1/4" DIMENSION DRAWING FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 8 of 31 Others Taco Bell-Tigard,OR October 31,2017 Unit Dimensions-3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop Item: Al Qty: 1 moi"---- NI 0t RETURN 3/4%14 DIA HOLE CONDENSATE DRAIN O O 27 5/8" 4 3/4" ISOMETRIC-PACKAGED COOLING FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 9 of 31 Others Taco Bell-Tigard,OR October 31,2017 Unit Dimensions -3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop Item: Al Qty: 1 -., , _....._____:..._QW, oor ,til 1 ® 0 % m °,71 PANEL 42 ACCESS SIDE e e CONDENSER COIL SIDE E> CONDENSER COIL SIDE ———J THROUGH THE BASE ELECTRICAL (SEE NOTE 1 AND 2) o 2 3/4 L 4 5/8" I � 3 3/4" 4 I THROUGHTHE BASE CONDENSATE 5 7/8" o�-", 5" THROUGHT BASE GAS(SEE NOTE 1 AND 2) 0 40 3/4" NOTES: 1.THRU-THE-BASE GAS AND ELECTRICAL IS NOT STANDARD. PANEL VERIFY OPTION IN PRODUCT DATA IN THIS DOCUMENT. ACCESS SIDE 2.VERIFY WEIGHT,CONNECTION,OPTION CONFIGURATION AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION THRU THE BASE GAS/ELECTRICAL PLAN/ISO VIEW DRAWING FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 10 of 31 Others Taco Bell-Tigard,OR October 31,2017 Unit Dimensions -3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop Item: Al Qty: 1 'ELECTRICAL/GENERAL DATA GENERAL (2X4)(6) HEATING PERFORMANCE Model: YHC092F Oversized Motor HEATING-GENERAL DATA Unit Operating Voltage: 187-253 MCA: N/A Heating Model: Medium Unit Primary Voltage: 208 MFS: N/A Heating Input(BTU): 150,000/105,000 Unit Secondary Voltage 230 MCB: N/A Heating Output(BTU): 120,000/84,000 Unit Ph60 No.Burners: 3 Unit Phase:: 3 No.Stages 2 EER Standard Motor Field Installed Oversized Motor 'Gas Inlet Pressure MCA: 42.4 MCA: N/A Natural Gas(Min/Max): '4.5/14 MFS: 50.0 MFS: N/A LP(Min/Max) 11.0/14.0 MCB: 50.0 MCB: N/A Gas Pipe Connection Size: 3/4" INDOOR MOTOR Standard Motor Oversized Motor Field Installed Oversized Motor Number: '1 Number: N/A Number N/A Horsepower: 3.8 Horsepower: N/A Horsepower N/A Motor Speed(RPM): — Motor Speed(RPM): N/A Motor Speed(RPM): N/A Phase 3 Phase N/A Phase N/A Full Load Amps: 8.5-8.5 Full Load Amps: N/A Full Load Amps: N/A Locked Rotor Amps: _ Locked Rotor Amps: N/A Locked Rotor Amps: N/A COMPRESSOR Circuit 1/2 OUTDOOR MOTOR Number: '2 Number: '1 Horsepower: 4.1/2.4 Horsepower: 0.75 Phase: 3 Motor Speed(RPM): 1100 Rated Load Amps: 15.9/10.0 Phase: 1 Locked Rotor Amps: 110.0/71.0 Full Load Amps: 4.0 Locked Rotor Amps: 9.3 POWER EXHAUST ACCESSORY (3) FILTERS REFRIGERANT (2) (Field Installed Power Exhaust) Type R-410 Phase: N/A Type: Throwaway Horsepower: N/A Furnished: Yes Factory Charge Motor Speed(RPM): N/A Number 4 Circuit#1 5.5 lb Full Load Amps: N/A Recommended 20"x25"x2" Circuit#2 4.2 lb Locked Rotor Amps: N/A NOTES: 1.Maximum(HACR)Circuit Breaker sizing is for installations in the United States only. 2.Refrigerant charge is an approximate value.For a more precise value,see unit nameplate and service instructions. 3.Value does not include Power Exhaust Accessory. 4.Value includes oversized motor. 5.Value does not include Power Exhaust Accessory. 6.EER is rated at AHRI conditions and in accordance with DOE test procedures. FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 11 of 31 Others Taco Bell-Tigard,OR October 31,2017 Weight, Clearance& Rigging Diagram -3-10 Ton R41OA PKGD Unitary Gas/Electric Rooftop Item: Al Qty: 1 INSTALLED ACCESSORIES NET WEIGHT DATA ACCESSORY WEIGHTS ECONOMIZER 36.0 lb MOTORIZED OUTSIDE AIR DAMPER Q\` r O MANUAL OUTSIDE AIR DAMPER �� BAROMETRIC RELIEF OVERSIZED MOTOR o arii" ``� BELT DRIVE MOTOR o ittet `""i POWER EXHAUST "Tye " THROUGHT THE BASE ELECTRICAUGAS(FIOPS) 18.0 lb �� UNIT MOUNTED CIRCUIT BREAKER(FIOPS) 5.0 lb �... UNIT MOUNTED DISCONNECT(FIOPS) POWERED CONVENIENCE OUTLET(FIOPS) . 1.,e,.. HINGED DOORS(FIOPS) 12.0 lb O HAIL GUARD 20.0 lb d SMOKE DETECTOR,SUPPLY/RETURN 12.0 lb PACKAGED GAS/ELECTRICAL NOVAR CONTROL CORNER WEIGHT STAINLESS STEEL HEAT EXCHANGER REHEAT ROOF CURB 78.0 lb BASIC UNIT WEIGHTS CORNER WEIGHTS CENTER OF GRAVITIY SHIPPING NET OA 340.0 lb CO 249.0 lb (E)LENGHT (F)WIDTH 1124.Olb 1026.Olb O 233.OIb OD 204.01b 41" 23" NOTE: 1. All weights are approximate. 2. Weights for options that are not list refer to Installation guide. 3. The actual weight are listed on the unit nameplate. 4. Refer to unit nameplate and installation guide for weights before scheduling transportation and installation II of unit. 5. The weight shown represents the typical unit operating weight for the configuration selected.Estimated at+/-10%of the nameplate weight.. 6. Verify weight,connection,and all dimension with installer documents before installation. 7. Corner weights are given for information only. 8. Net/Shipping weight of optional accessories should be added to unit weight when ordering factory or field installed accessories. ''",,,,,4406 • ("kvoma . ) 0111111°. N. .mil •', j\'`1'N\ o �;A1 - PACKAGED GAS/ELECTRICAL RIGGING AND CENTER OF GRAVITY FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 12 of 31 Others Taco Bell-Tigard,OR October 31,2017 Weight, Clearance& Rigging Diagram -3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop Item: Al Qty: 1 CLEARANCE FROM TOP OF UNIT 72" CLEARANCE 36" CLEARANCE 48" ri W.I.- 00:190) H— '144Vil RETURN DOWNFLOW CLEARANCE 36" HORIZONTAL CLEARANCE 18" CLEARANCE 36" PACKAGED GAS/ELECTRIC CLEARANCE ROOF OPENING I ' I UNIT OUTLINE I 46" 53 1/4" I I I I_l_ 88 518" PACKAGED GAS/ELECTRIC DOWNFLOW TYPICAL ROOF OPENING FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 13 of 31 Others Taco Bell-Tigard,OR October 31,2017 Accessory -3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop Item: Al Qty: 1 vaimir vow onirA timot 10(111111 41111111110. / 1 / / \ \ \ / / \ N7 \ / --r\ri ___ -- \__ 21 318" 34 5/8" SWING DIAMETER-HINGED DOOR(S)OPTION ACCESSORY FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 14 of 31 Others Taco Bell-Tigard,OR October 31,2017 Accessory -3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop Item: Al Qty: 1 NOTES: RETURN OPENING 1.VERIFY WEIGHT,CONNECTION,AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION SUPPLY OPENING 1 11/16" ¢-18 7/16"--=-- 8 5/8" -.----18 7/16"-----=- 1 11/16" 34 3/8" 1 34 3/8" 46 7/16" 7 7 z„ - 83 15/16" - 49 13/16" - 14" 14" 841/2" 507/16" ROOF TOP CURB(BAYCURB043) ACCESSORY FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 15 of 31 Others 1•NIffm. Taco Bell-Tigard,OR October 31,2017 Accessory -3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop Item: Al Qty: 1 Downflow Duct Connections-Field Fabricated All Flanges- 1 1/4" / \17 3/4" 33 3/4" 3/4" 33 3/4" ACCESSORY-DUCT CONNECTIONS FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 16 of 31 Others Taco Bell-Tigard,OR October 31,2017 Accessory -3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop Item: Al Qty: 1 1144 ��' ECONOMIZER HOOD BAROMETRIC RELIEF HOOD BAROMETRIC RELIEF HOOD 4. 11 111 7 3/4" 12" ACCESSORY-BAROMETRIC RELIEF DAMPER HOOD FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 17 of 31 Others Taco Bell-Tigard,OR October 31,2017 Accessory-3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop Item: Al Qty: 1 kr' 2 ,4144444:411ttttottt --, 1 ,:2••••••,, . 111)1 IIIIL °o ' ECONOMIZER HOOD ECONOMIZER HOOD • 00 MIME MM. 00 16 314" ACCESSORY-ECONOMIZER HOOD FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 18 of 31 Others ... ..-..—_ Taco Bell-Tigard,OR October 31,2017 Field Wiring -3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop Item: Al Qty: 1 L2 L3 HTB1 I I I, c 0 fU* o ‘U' ZONE SENSOR WIRE TABLE WIRE SIZE MAXIMUM WIRE LENGTH 22 GAUGE 1800" 20 GAUGE 3000" 18 GAUGE 4500" 16 GAUGE 7200" 14 GAUGE 11700" NOTE: 1.All wiring and devices shown dashed to be supplied and installed by the customer in accordance with national and local electrical codes. 2.Low voltage control wiring must not be run in conduit with power wiring. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 19 of 31 Others Taco Bell-Tigard,OR October 31,2017 Tag Data -Packaged Gas/Electric Rooftop Units(Qty: 1) Item Tag(s) Qty Description Model Number B1 No Tag 1 12.5 Ton High Eff Gas/Electric YHD150G3RHB--FOC1C2A000C300000000000 RTU 0000 Product Data - Packaged Gas/Electric Rooftop Units Item: B1 Qty: 1 Gas/Electric High efficiency Downflow 12.5 Ton Standard and High Efficiency 208-230/60/3 Reliatel Gas Heat- High Economizer Reference Enthalpy 0-100% with Barometric relief Hinged panels/2" Pleated Filters Mery 8 Standard condenser coil with hail guard Through the base electric/gas Unit Mounted Circuit Breaker Unpowered convenience outlet Return/supply air smoke detector Discharge air sensing tube Roof curb (Fld) Year 6-10 heat exchanger warranty FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 20 of 31 Others Taco Bell-Tigard,OR October 31,2017 Mechanical Specifications -Packaged Gas/Electric Rooftop Units Item: B1 Qty: 1 General -Downflow The units shall be dedicated downflow airflow. The operating range shall be between 115°F and 0°F in cooling as standard from the factory for all units. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall be factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check cooling operation, fan and blower rotation and control sequence, before leaving the factory. Wiring internal to the unit shall be colored and numbered for simplified identification. Units shall be UL listed and labeled, classified in accordance to UL 1995/C 22.2, 236-05 3rd Edition. Packaged Rooftop units cooling, heating capacities, and efficiencies are AHRI certified within scope of AHRI Standard 340/360 (I-P)and ANSIZ21.47 and 10 CFR Part 431 pertaining to Commercial Warm Air Furnaces (gas heating units). Casing - Downflow Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Unit's surface shall be tested 672 hours in a salt spray test in compliance with ASTM 8117. Cabinet construction shall allow for all maintenance on one side of the unit. In order to ensure a water and air tight seal, service panels shall have lifting handles and no more than three screws to remove.All exposed vertical panels and top covers in the indoor air section shall be insulated with a 1/2 inch, 1 pound density foil-faced, fire-resistant, permanent, odorless, glass fiber material. The base of the downflow unit shall be insulated with 1/2 inch, 1 pound density foil-faced, closed-cell material. The downflow unit's base pan shall have no penetrations within the perimeter of the curb other than the raised 11/8 inch high supply/return openings to provide an added water integrity precaution, if the condensate drain backs up.The base of the unit shall have provisions for forklift and crane lifting. Unit Top The top cover shall be one piece, or where seams exist, double hemmed and gasket sealed to prevent water leakage. Filters Two inch standard filters shall be factory supplied on all units Compressors All units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of nameplate voltage. Internal overloads shall be provided with the scroll compressors. All models shall have crankcase heaters, phase monitors and low and high pressure control as standard. Dual compressors are available on all standard efficiency models and 12.5 to 20 tons high efficiency models and allow for efficient cooling utilizing 3 stages of compressor operation (high efficiency models only). 25 tons high efficiency units have 3 compressors for up to 4 stages of compressor operation. Crankcase Heaters These band heaters provide improved compressor reliability by warming the oil to prevent migration during off-cycles or low ambient conditions. Refrigerant Circuits Each refrigerant circuit shall have service pressure ports, and refrigerant line filter driers factory installed as standard. An area shall be provided for replacement suction line driers. Evaporator and Condenser Coils Evaporator Coils (only on T/YS*150, 180, 210, 240, 300G models)- Microchannel evaporator coils will be burst tested by the manufacturer. Internally finned, 5/16"copper tubes mechanically bonded to a configured aluminum plate fin shall be standard for evaporator coils. Coils shall be leak tested to ensure the pressure integrity. The evaporator coil shall be leak tested to 225 psig and pressure tested to 450 psig. Condenser Coils(available on TN**150, 180,210,240, 300G models)-Microchannel condenser coils shall be standard on all units. Coils shall be leak tested to ensure the pressure integrity. The condenser coil shall be leak tested to 225 psig and pressure tested to 450 psig. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 21 of 31 Others Taco Bell-Tigard,OR October 31,2017 Gas Heating Section The heating section shall have a drum and tube heat exchanger design using corrosion resistant steel components. A forced combustion blower shall supply premixed fuel to a single burner ignited by a pilotless hot surface ignition system. In order to provide reliable operation, a negative pressure gas valve shall be used on standard furnaces and a pressure switch on furnaces with modulating heat that requires blower operation to initiate gas flow. On an initial call for heat, the combustion blower shall purge the heat exchanger 45 seconds before ignition. After three unsuccessful ignition attempts, the entire heating system shall be locked out until manually reset at the thermostat. Units shall be suitable for use with natural gas shall also comply with California requirements for low NOx emissions. Condenser Coil The microchannel type condenser coil is standard for the standard efficiency models. Due to flat streamlined tubes with small ports, and metallurgical tube-tofin bond, microchannel coil has better heat transfer performance. Microchannel condenser coil can reduce system refrigerant charge by up to 50% because of smaller internal volume,which leads to better compressor reliability. Compact all-aluminum microchannel coils also help to reduce the unit weight.All-aluminum construction improves re-cyclability. Galvanic corrosion is also minimized due to all aluminum construction. Strong aluminum brazed structure provides better fin protection. In addition, flat streamlined tubes also make microchannel coils more dust resistant and easier to clean. Coils shall be leak tested at the factory to ensure the pressure integrity. The evaporator coil and condenser coil shall be leak tested to 600 psig. The assembled unit shall be leak tested to 465 psig. Outdoor Fans The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge position. The fan motor(s) shall be permanently lubricated and shall have built-in thermal overload protection. Indoor Fan Units above shall have belt driven, FC centrifugal fans with adjustable motor sheaves. Units with standard motors shall have an adjustable idler-arm assembly for quick-adjustment of fan belts and motor sheaves. All motors shall be thermally protected. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). Controls Unit shall be completely factory wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Unit shall provide an external location for mounting a fused disconnect device. ReliaTel controls shall be provided for all 24 volt control functions. The resident control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes drift from set point, and provides better building comfort. A centralized control shall provide anti-short cycle timing and time delay between compressors to provide a higher level of machine protection. High Pressure Cutout This option is offered for units that do not have High Pressure cutout as standard. Discharge Line Thermostat A bi-metal element discharge line thermostat is installed as a standard option on the discharge line of each system. This standard option provides extra protection to the compressors against high discharge temperatures in case of loss of charge, extremely high ambient and other conditions which could drive the discharge temperature higher. Discharge line thermostat is wired in series with high pressure control.When the discharge temperature rises above the protection limit, the bi-metal disc in the thermostat switches to the off position, opening the 24 VAC circuit. When the temperature on the discharge line cools down, the bi-metal disc closes the contactor circuit, providing power to the compressor. When the thermostat opens the fourth time, the ReliaTel control must be manually reset to resume operation on that stage. Tool-less Hail Guards Tool-less, hail protection quality coil guards are available for condenser coil protection. FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 22 of 31 Others Taco Bell-Tigard,OR October 31,2017 Hinged Access Doors Sheet metal hinges are available on the Filter/Evaporator Access Door and the Compressor/Control Access Door.This option is available on all downflow models. Two-Inch Pleated Filters(MERV 8& 13) Two inch pleated media filters shall be available on all models. Reference or Comparative Enthalpy Reference Enthalpy is used to measure and communicate outdoor humidity.The unit receives and uses this information to provide improved comfort cooling while using the economizer. Comparative Enthalpy measures and communicates humidity for both outdoor and return air conditions, and return air temperature. The unit receives and uses this information to maximize use of economizer cooling, and to provide maximum occupant comfort control. Reference or Comparative Enthalpy option shall be available when a factory or field installed Downflow Economizer is ordered. This option is available on all downflow models. Discharge Air Sensing Kit This kit provides true discharge air sensing in heating models. This sensor is a status indicator readable through Tracer or Tracker. The kit is functional only with the ReliaTel Options Module. Reference Enthalpy-Factory Installed This option will be factory installed to measure and communicate outdoor humidity. The unit will receive and use this information to provide improved comfort cooling while using the economizer. Accessory -Roof Curb- Downflow The roof curb shall be designed to mate with the downflow unit and provide support and a water tight installation when installed properly. The roof curb design shall allow field-fabricated rectangular supply/return ductwork to be connected directly to the curb. Curb design shall comply with NRCA requirements. Curb shall be shipped knocked down for field assembly and shall include wood nailer strips. FLD=Furnished by Trane U.S.Inc.I Installed by Equipment Submittal Page 23 of 31 Others Taco Bell-Tigard,OR October 31,2017 Unit Dimensions-Packaged Gas/Electric Rooftop Units Item: B1 Qty: 1 NOTES: 1.GAS CONNECTION PIPE SIZE 1/2" 2.THRU-THE-BASE GAS AND ELECTRICAL IS NOT STANDARD ON ALL UNITS.(SELECTED OPTION:SEE ACCESSORY SHEET) j 3.VERIFY WEIGHT,CONNECTION,AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION 9GAS CONNECTION(SEE NOTE 1) 56 118" % r ,;X111 'i ``" J 0o t" �� 0 8 1/8" DOWNFLOW CONDENSATE p DRAIN CONN 1"NPT , ! . < 26 3/4" 0 50 5/8" , 1 IV,' 111111 7/8"DIA.HOLE 64 11/16" 11 1/16"------- (UNIT CONTROL WIRE) 2"DIA.HOLE 81 5/8" ' A (UNIT POWER WIRE) 3" 22 1/16" 121 11/16" \ 531/16" PACKAGED GAS/ELECTRIC-DOWNFLOW 84 3/4" ISOMETRIC DRAWING 4 1/4" 1 r19 15/16"- ---=,---28 3/4" o 0 26 7/16"-,== 4 1/4" ire km0.10/1 SUPPLY `0 RETURN 68 11/16" 76 5/16" #3� ��Urr 1 t`t�`IP ili L V J 0 • PACKAGED GAS/ELECTRIC-DOWNFLOW PLAN VIEW DRAWING FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 24 of 31 Others Taco Bell-Tigard,OR October 31,2017 Unit Dimensions -Packaged Gas/Electric Rooftop Units Item: B1 Qty: 1 ELECTRICAL /GENERAL DATA GENERAL PERFORMANCE Standard Motor (1)(3) Model(Ton): YHD150G(12.5) Minimum Circuit Ampacity: 64.0 Unit Operating Voltage Range: '187-253 Maximum Fuse Size: 90.0 Unit Primary Voltage: 208 Maximum(HACR)Circuit Breaker: 90.0 Unit Secondary Voltage: 230 Unit Hertz: 60 Standard Oversized Motor (1)(4) Accessory Oversized Motor (i)(4) Unit Phase: 3 Minimum Circuit Ampacity: Minimum Circuit Ampacity: Maximum Fuse Size: Maximum Fuse Size: EER:(5) '12.1 Maximum(HACR)Circuit Breaker: Maximum(HACR)Circuit Breaker: GAS HEATING COMPRESSOR Heating Models: 'High Circuit(s) Heating and 1 Stage Input(Btu/h) 250,000/175,000 Number '2 Heating and 1 Stage Output(Btu/h): 200,000/140,000 Horsepower: 5.6/3.67 Min./Max.Gas Input- Phase: 3 Pressure Natural or LP(in w.c): 2.5/14.0 Rated Load Amps: 27.5/13.6 Gas Connection Pipe Size: 1/2" Locked Rotor Amps: 191.0/100.0 INDOOR MOTOR Standard Motor Standard Oversized Motor (4) Accessory Oversized Motor (4) Number: (3) '1 Number: .. Number: Horsepower: 3.0 Horsepower: Horsepower: Motor Speed(RPM): 1,740 Motor Speed(RPM): Motor Speed(RPM): Phase: 3 Phase: Phase: Full Load Amps: 10.6 Full Load Amps: Full Load Amps: Locked Rotor Amps: 81.0 Locked Rotor Amps: Locked Rotor Amps: OUTDOOR MOTOR POWER EXHAUST COMBUSTION BLOWER (Field Installed Power Exhaust) MOTOR Number '2 Horsepower 'N/A (Gas-Fired Heating only) Horsepower: 0.5 Motor Speed(RPM): N/A Phase: N/A Horsepower: '0.05 Motor speed(RPM): 1,100 Full Load Amps: N/A Motor Speed(RPM): 3500/2800 Fullll Load Phase: 3 3 Locked Rotor Amps: N/A Phase: 1 ad Amps: 2.7 Full Load Amps: 0.5 Locked Rotor Amps: 9.65 Locked Rotor Amps: 0.78 FILTER REFRIGERANT (2) Circuit#1/2 Type: 'Throwaway Type: 'R-410 Furnished: Yes Factory Charge Number 4/4 Circuit#1/2: 12.5 lb/7.1 lb Recommended Size: 20"x20"x2"/20"x25 x2" NOTES: 1. Maximum(HACR)Circuit Breaker sizing is for installations in the United States only. 2. Refrigerant charge is an approximate value.For a more precise value,see unit nameplate and service instructions. 3. Value include Standard Motor. 4. Value include Oversized Motor 5. EER is rated at AHRI conditions and in accordance with DOE test procedures. FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 25 of 31 Others Taco Bell-Tigard,OR October 31,2017 Weight, Clearance & Rigging Diagram -Packaged Gas/Electric Rooftop Units Item: B1 Qty: 1 IIII‘ . . 4°V CLEARANCE 68" (1727.2mm) CLEARANCE 36" iiiiCLEARANCE FROM THE (914.4mm) TOP OF UNIT 72" j (1828.8mm) i rr o 1 CLEARANCE 60" ,o (1524mm)te \ r /� CLEARANCE 48" (1219.2mm) et DOWNFLOW-PACKAGED GAS/ELECTRIC CLEARANCE UNIT OUTLINE ROOF OPENING 76 1/2" .-- 81" 81" i DOWNFLOW-PACKAGED GAS/ELECTRIC ROOF OPENING CLEARANCE FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 26 of 31 Others Taco Bell-Tigard,OR October 31,2017 Weight, Clearance& Rigging Diagram -Packaged Gas/Electric Rooftop Units Item: B1 Qty: 1 Base Unit and Corner Weights only Base unit weights Corner Weights Center of Gravity 1--"---,..------ ,i-1-,.::" � SHIPPING NET AO © © OD E F II 2402.0 lb 1971.0 lb 680.0 lb 515.0 lb 352.0 lb 423.0 lb 50" 33" „11` IN) /)� 1.All weights are approximate. \\\\���\ „.0 2.The actual weight are listed on the unit nameplate. ��� 3.Refer to unit nameplate and installation guide for weights before scheduling transportation and installation of unit. iii, 4.The weight shown represents the typical unit operating weight for the configuration �� G� selected.Estimated at+/_10 %of the nameplate weight.. (l�///ior�,a\11111 tt",t`� „� 5.Ver'rfy weight,connection,and all dimension with installer documents before installation. \\\\���\\\\\`i/fi/) 6.Corner weights are given for information only. 7.NeUShipping weight of optional accessories should be added to unit weight when ordering factory or field installed accessories. / V. .- W ,—..1- Installed Options Net Weight Data (^)� Accessory Weight CORNER WEIGHT Economizer,Manual and Motorized Outside Air Damper 80.0 lb Power Exhaust Roof Curb 235.0 lb Oversized Motor Hail Guard 43.0 lb Hinged Access Doors 27.0 lb Power Cony.Outlet Through the Base Electrical 23.0 lb Circuit Breaker 10.0 lb Disconnect Smoke Detector 7.0 lb Novar Zone Sensor II- High/Low Static Drive Kit LP Gas Conversion Stainless Steel Heat Exchanger \ Stainless Steel Drain Pan VFD / High Efficiency Motor 1.Weights for options are approximate. 2.Weights for options that are not list refer to Installation guide. 4' `.. /' /b Via\\\�\ ir- j i - Al . 141144441144 0 PACKAGED GAS/ELECTRIC RIGGING AND CENTER OF GRAVITY FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 27 of 31 Others Taco Bell-Tigard,OR October 31,2017 Accessory -Packaged Gas/Electric Rooftop Units Item: B1 Qty: 1 ra SWING RADIUS 29 1/2" F+3 ID SECTION q\ ACCESS PANEL \ \ SWING RADIUS 38 1/2" OD SECTION ACCESS PANEL SWING RADIUS 18 1/2" ID FAN SECTION ACCESS PANEL HINGGING ACCESS DOORS ACCESSORY FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 28 of 31 Others Accessory-Packaged Gas/Electric Rooftop Units Item: B1 Qty: 1 idni 1� END PANEL ai 1 1 0 ACCESS PANEL ', 1 > 78 ECONOMIZER HOOD 19 1/2" ECONOMIZER HOOD PLAN VIEW DRAWING FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 29 of 31 Others Taco Bell-Tigard,OR October 31,2017 Accessory- Packaged Gas/Electric Rooftop Units Item: B1 Qty: 1 116 13/16" 22 1/4" 23.1/41,1 26 9/16" 7 1 13/16" 1" I 1 IC n 1 n 69 1/2" 80 5/8" 77" RETURN SUPPLY V N 1 1 13/16" ACCESSORY-ROOF CURB \5/16" 73 7/16" , RETURN 611/16" <------ ---SI I 'SUPPLY I I . 1,>**I') 166 1/2" N. 7 7/16" / �I I I 'r-j: . /I 141/16" 1114111111111110 � 'I 117 3/16" 81" 2" / ACCESSORY-DOWNFLOW DUCT CONNECTIONS FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 30 of 31 Others Taco Bell-Tigard,OR October 31,2017 Field Installed Options -Part/Order Number Summary This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the job. Product Family -3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop Item Tag(s) Qty Description Model Number Al No Tag 1 7.5 Ton SZVAV Gas/Electric RTU YHC092F3RMA--F 6C1C2A000C0000 000000000000 Field Installed Option Description Part/Ordering Number Roof curb BAYCURB043A Product Family - Packaged Gas/Electric Rooftop Units Item Tag(s) Qty Description Model Number B1 No Tag 1 12.5 Ton High Eff Gas/Electric RTU YHD150G3RHB--F OC1C2A000C3000 000000000000 Field Installed Option Description Part/Ordering Number Roof curb BAYCURB027B FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 31 of 31 Others