Report stt ).4' 4Cis RECEIVED Fire Protection Fire Protection and Life Safety SpecialistskeT' JAN 31 2019 ® CITY"OF TIGARD BUILDING DIVISION F •ire Protection a eria• ls Clean Water Services O&M Building TI The undersigned,acting on behalf of the Contractor,has reviewed the submittal for the COSCO Fire Protection Inc. Job # 24PD5199 general conformance of the design intent of the contract documents. (VZ eititia 01/18/2019 2501 SE Columbia Way, Suite 100 Vancouver,WA 98661 Phone:360-883-6383 Fax: 360-883-6390 Toll Free:800-983-6383 1* Pio "••••• COSCO Fire Protection lite 1'nne°i114)11 and I ill' ,'114 n S her • renkiers COSCO Fire Protection Inc. 2501 SE Columbia Way, Suite 100 Vancouver,WA 98661 Phone:360-883-6383 Fax: 360-883-6390 Toll Free:800-983-6383 ( T Page 1 of 4 II(11S1c ® MICROFAST® QUICK ING® TECHNICAL DATA RESPONSE UPRIGHT SPRINKLER VK300 (K5.6) The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone:269-945-9501 Technical Services:877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page:www.vikinggroupinc.com 1. DESCRIPTION The Viking Microfast® Quick Response Upright Sprinkler VK300 is a small, thermosensitive, glass-bulb spray sprinkler available in several differ- ent finishes and temperature ratings to meet design requirements. The spe- cial Polyester and Electroless Nickel PTFE (ENT) coatings can be used in decorative applications where colors are desired. In addition, these coat- ings have been investigated for installation in corrosive atmospheres and are listed/approved as corrosion resistant as indicated in the Approval Charts. (Note: FM global approves the ENT coating as corrosion resistant. FM Global has no approval classification Polyester coatings as corrosion resistant.) 2. LISTINGS AND APPROVALS c pL os cULus Listed: Category VNIV FM FM Approved: Classes 2002 and 2020 Refer to Approval Charts and Design Criteria for listing and approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Minimum Operating Pressure: 7 psi (0.5 bar)* Maximum Working Pressure: 175 psi (12 bar)wwp. Factory tested hydrostatically to 500 psi (34.5 bar) Testing: U.S.A. Patent No.4,831,870 Thread size: 1/2" NPT, 15 mm BSP Nominal K-Factor: 5.6 U.S. (80.6 metric**) Glass-bulb fluid temperature rated to-65 °F (-55 °C) Overall Length: 2-3/16" (56 mm) *cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi(0.35 bar). Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass Deflector: Brass UNS-C23000 or Copper UNS-C19500 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 For Polyester Coated Sprinklers: Belleville Spring-Exposed For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap- ENT plated Ordering Information: (Also refer to the current Viking price list.) Order Viking Microfast®Quick Response Upright Sprinkler VK300 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass =A, Chrome = F, White Polyester= M-/W, Black Polyester= M-/B, and ENT=JN Temperature Suffix(°F/°C): 135°/57° =A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = G For example, sprinkler VK300 with a 1/2" NPT thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 12978AB Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the Viking website.) Sprinkler Wrench: Standard Wrench: Part No. 21475M/B (available since 2017) Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A(available since 1971) B. Twelve-head capacity: Part No. 01725A(available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. Form No. F_052114 17.10.05 Rev 17.1 Replaces Form No. F_052114 Rev 15.2 (Replaced wrench 10896W/B with 21475M/B) t F Page 2 of 4 NII(ING® MICROFAST® QUICK TECHNICAL DATA RESPONSE UPRIGHT SPRINKLER VK300 (K5.6) The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection,Testing and Maintenance requirements. 7. AVAILABILITY The Viking Microfast®Quick Response Upright Sprinkler VK300 is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Sprinkler Nominal Maximum Ambient Bulb Color Classification Temperature Rating' Ceiling Temperature2 Ordinary 135°F(57°C) 100°F(38°C) Orange Ordinary 155°F(68°C) 100°F(38°C) Red Intermediate 175°F(79°C) 150°F(65°C) Yellow Intermediate 200°F(93°C) 150°F(65°C) Green High 286°F(141 °C) 225°F(107°C) Blue Sprinkler Finishes: Brass,Chrome,White Polyester, Black Polyester, and ENT Corrosion-Resistant Coatings':White Polyester, Black Polyester,and Black PTFE. ENT in all temperature ratings except 135°F(57°C) Footnotes 'The sprinkler temperature rating is stamped on the deflector. s Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 'The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts.These tests cannot and do not represent all possible corrosive environments. Prior to installation,verify through the end-user that the coatings are compat- ible with or suitable for the proposed environment. For automatic sprinklers,the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester, ENT,and PTFE coatings.For ENT coated automatic sprinklers,the waterway is coated. Protective Sprinkler Cap Wrench Flat 21475• • Figure 1: Standard Sprinkler Wrench 21475M/B Form No. F_052114 17.10.05 Rev 17.1 $ Page 3 of 4 ® MICROFAST® QUICK TECHNICAL DATA RESPONSE UPRIGHT SPRINKLER VK300 (K5.6) The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page:www.vikinggroupinc.com Approval Chart 1 (UL) Temperature KEY Microfast®Quick Response j Finish A1 Upright Sprinkler VK300 X• Cscutcheon(it applicable) Maximum 175 PSI (12 bar)WWP Base Part Thread Size Nominal K-Factor Overall Length Listings and Approvals' Number' SIN NPT BSP U.S. metric' Inches mm cULus VdS LPCB NYCE CE 12978 VK300 1/2" 15 mm 5.6 80.6 2-3/16 56 Al, B2 -- -- See footnote 7. -- NOTICE-Product Below-Limited Availability(Contact Local Viking Office) 06661B VK300 1/2" 15 mm 5.6 80.6 2-3/16 56 Al, B2 -- -- See footnote 7. -- Approved Temperature Ratings A- 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and Approved Finishes 1 -Brass,Chrome,White Polyester",and Black Polyester5,6 286°F(141°C) 2-ENT6 B- 155 °F (68 °C), 175°F(79 °C),200 °F (93°C),and 286 °F (141°C) Footnotes 'Base part number is shown.For complete part number,refer to Viking's current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 'This table shows the listings and approvals available at the time of printing.Check with the manufacturer for any additional approvals. °Listed by Underwriters Laboratories Inc.for us in the U.S.and Canada Other colors are available on request with the same Listings and Approvals as the standard colors. 6 cULus Listed as corrosion resistant. Meets New York City requirements,effective July 1,2008 'Accepted for use,City of New York Board of Standards and Appeals,Calendar Number 219-76-SA and City of New York Department of Buildings,MEA 89-92-E,Vol.16. DESIGN CRITERIA- UL (Also refer to Approval Chart 1 above.) cULus Listing Requirements: The Viking Microfast®Quick Response Upright Sprinkler VK300 is cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers. • Designed for use in Light and Ordinary Hazard occupancies. • The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data,the appropriate standards of NFPA, FM Global, LPCB, APSAD,VdS or other similar organizations, and also with the provisions of governmental codes,ordinances, and standards, whenever applicable. Form No. F_052114 17.10.05 Rev 17.1 r Page 4 of 4 II(IF1_" ® MICROFAST® QUICK TECHNICAL DATA RESPONSE UPRIGHT SPRINKLER VK300 (K5.6) The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page:www.vikinggroupinc.com Approval Chart 2 (FM) Temperature KEY Microfast®Quick Response te Al Xf Escutcheon(f applicable) Upright Sprinkler VK300 Maximum 175 PSI(12 bar)WWP Base Part SIN Thread Size Nominal K-Factor Overall Length FM Approvals3 Number' NPT BSP U.S. metric2 Inches mm (Refer also to Design Criteria below.) 12978 VK300 1/2" 15 mm 5.6 80.6 2-3/16 56 Al, B2 NOTICE-Product Below-Limited Availability(Contact Local Viking Office) 06661B VK300 1/2" 15 mm 5.6 80.6 2-3/16 56 Al, B2 Approved Finishes Approved Temperature Ratings 5 A- 135°F(57°C), 155°F(68 °C), 175°F(79°C), 200°F(93 °C), and 286°F(141°C) 1 Brass, Chrome, White Polyester, and Black B- 155°F(68 °C), 175°F (79 °C), 200 °F(93°C), and 286°F (141°C) Polyesters 2- ENT6 Footnotes 'Base part number is shown. For complete part number, refer to Viking's current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 3 This table shows the FM Approvals available at the time of printing.Check with the manufacturer for any additional approvals. 5 Other colors are available on request with the same Approvals as the standard colors. 6 FM approved as corrosion resistant. DESIGN CRITERIA- FM (Also refer to Approval Chart 2 above.) FM Approval Reauirements: The Microfast®Quick Response Upright Sprinkler VK300 is FM Approved as a quick response Non-Storage upright sprinkler as indicated in the FM Approval Guide.For specific application and installation requirements,reference the latest applicable FM Loss Prevention Data Sheets(including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design,ceiling slope and obstructions, minimum and maximum allowable spacing,and deflector distance below the ceiling. NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data,the appropriate standards of NFPA, FM Global, LPCB, APSAD,VdS or other similar organizations,and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Form No. F_052114 17.10.05 Rev 17.1 Replaces Form No. F_052114 Rev 15.2 (Replaced wrench 10896W/B with 21475M/B) � X r r Page 1 of 6 MICROFAST® QUICK II(II13® TECHNICAL DATA RESPONSE PENDENT SPRINKLER VK302 (K5.6) The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page:www.vikinggroupinc.com 1. DESCRIPTION The Viking Microfast°Quick Response Pendent Sprinkler VK302 is a small ther- mosensitive glass bulb spray sprinkler available with various finishes and tempera- ture ratings to meet design requirements. The special Polyester and Electroless Nickel PTFE (ENT)coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive environments and are Listed and Approved as indicated in the Approval Charts. 2. LISTINGS AND APPROVALS cOus cULus Listed: Category VNIV <1> FM Approved: Class Series 2000 VdS VdS Approved: Certificates G414009, G414010, G4040095, and 4880045 LPCB LPCB Approved: Certificate 096e/06 CE Certified: Standard EN 12259-1, certificate of constancy of performance 0832-CPR-S0021 CCCF Approved: Approved by the China Certification Center for Fire Products (CCCF) Q MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 Refer to Approval Chart 1 and Design Criteria cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Minimum Operating Pressure: 7 psi (0.5 bar) Rated to 175 psi (12 bar)water working pressure Factory tested hydrostatically to 500 psi (34.5 bar) Thread size: 1/2" NPT, 15 mm BSP Nominal K-Factor: 5.6 U.S. (80.6 metric"') Glass-bulb fluid temperature rated to-65 °F (-55 °C) Overall Length: 2-1/4" (58 mm) *cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi(0.35 bar). Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass Deflector: Phosphor Bronze UNS-C51000 or Copper UNS-C19500 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 For Polyester Coated Sprinklers: Belleville Spring-Exposed For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap- ENT plated. Ordering Information: (Also refer to the current Viking price list.) Order Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass =A, Chrome = F, White Polyester= M-/W, Black Polyester= M-/B, and ENT=JN Temperature Suffix: 135 °F (57 °C) =A, 155 °F (68 °C) = B, 175 °F (79 °C)= D, 200 °F (93 °C)= E, 286 °F (141 °C) = G Form No. F_033314 18.06.21 Rev 18.1 Replaces Form No. F_033314 Rev 17.1 (Updated MED approval;added LPCB certificate number) T I Page 2 of 6 ® MICROFAST® QUICK TECHNICAL DATA RESPONSE PENDENT SPRINKLER VK302 (K5.6) The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com For example, sprinkler VK302 with a Brass finish and a 155 °F (68 °C)temperature rating = Part No. 12979AB Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the current Viking price list.) Sprinkler Wrenches: A. Standard Wrench: Part No. 10896W/B (available since 2000). B. Wrench for Recessed Pendent Sprinklers: Part No. 13655W/B**(available since 2006) C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool*** Part No. 15915 (available since 2010) "*AW ratchet is required(not available from Viking). ***Allows use from the floor by attaching a length of 1"diameter CPVC tubing to the tool. Ideal for sprinkler cabinets.Refer to Bulletin F_051808. Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A(available since 1971) B. Twelve-head capacity: Part No. 01725A(available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection,Testing and Maintenance requirements. 7. AVAILABILITY The Viking Microfast®Quick Response Pendent Sprinkler VK302 is available through a network of domestic and international dis- tributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. Protective SprinklerWrench Flat Clip ` Protective Sprinkler Cap 10896 0 Figure 1: Standard Sprinkler Wrench 10896W/B Form No. F_033314 18.06.21 Rev 18.1 � 1 Page 3 of 6 NIKING® MICROFAST® QUICK TECHNICAL DATA MICROFAST® PENDENT SPRINKLER VK302 (K5.6) The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page:www.vikinggroupinc.com TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Sprinkler Nominal Maximum Ambient Bulb Color Classification ; Temperature Rating' Ceiling Temperature2 Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange Ordinary 155 °F (68 °C) 100 °F (38 °C) Red Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow Intermediate 200 °F (93 °C) 150 °F (65 °C) Green High 286 °F (141 °C) 225 °F (107 °C) Blue Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT Corrosion-Resistant Coatings3: White Polyester, and Black Polyester. ENT in all temperature ratings except 135 °F (57 °C) Footnotes 'The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts.These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are com- patible with or suitable for the proposed environment. For automatic sprinklers,the coatings indicated are applied to the exposed exterior surfaces only.Note that the spring is exposed on sprinklers with Polyester and ENT coatings. For ENT coated automatic sprinklers,the waterway is coated. ( 1.444 • Sprinkler wrench 13655W/B** for recessed pendent • sprinklers **A 1/2" ratchet is required (not available from Viking) -4111111- Carefully slide the wrench sideways around *41111111- the protective cap, ensuring engagement with the sprinkler wrench flats Figure 2: Wrench 13655W/B for Recessed Pendent Sprinklers Form No. F_033314 18.06.21 Rev 18.1 Page 4 of 6 II(IF13® MICROFAST® QUICK TECHNICAL DATA MICROFAST® PENDENT SPRINKLER VK302 (K5.6) The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Approval Chart 1 (UL) Temperature The Viking Microfast®Quick Response r — Finish KEY Pendent Sprinkler VK302 AIX+—Escutcheon(if applicable) Maximum 175 PSI(12 Bar)WWP Base Thread Size Nominal Overall Listings and Approvals' Part SIN Sprinkler K-Factor Length (Refer also to Design Criteria.) Style Number NPT BSP U.S. metric' Inches mm cULus4 VdS LPCB C E 7 0 8 12979 VK302 Pendent 1/2" 15 mm 5.6 80.6 2-1/4 58 A1Z,B1Y,D2,C2X Al A1Z,B1Y D1Z,C1Y D1W 19780 VK302 Pendent 1/2" -- 5.6 80.6 2-1/4 58 -- -- -- -- -- D3 21354 VK302 Pendent -- 15 mm 5.6 80.6 2-1/4 58 -- -- -- -- -- D3 NOTICE-Product Below-Limited Availability(Contact Local Viking Office) 06662B VK302 Pendent 1/2" 15 mm 5.6 80.6 2-1/4 58 A1Z,B1Y,D2,C2X -- -- -- -- 18021 VK302 Pendent 1/2" 15 mm 5.6 80.6 2-1/4 58 AIX,BIY Al AIX,B1Y Dix,C1Y7 D1W Approved Temperature Ratings Approved Finishes Approved Escutcheons A-135°F(57°C), 155°F(68°C), 175°F 1 -Brass,Chrome,White W-Recessed with the Model F-1 Adjustable Escutcheon only (79°C),200°F(93°C),286°F(141 °C) Polyester56,Black Polyes- X-Standard surface-mounted escutcheon or the B-135°F(57°C), 155°F(68°C), 175°F ter5,6 Viking Micromatic®Model E-1 Recessed Escutcheon (79°C),and 200°F(93°C) 2-ENT5 Y-Standard surface-mounted escutcheon or the C-155°F(68°C), 175°F(79°C),and 3-Chrome Viking Microfast®Model F-1 Adjustable Escutcheon,or recessed with the Viking Micro- 200°F(93°C) matic®Model E-1,E-2,or E-3 Recessed Escutcheon D-155°F(68°C), 175°F(79°C),200°F Z-Standard surface-mounted escutcheon or the (93°C),286°F(141 °C) Viking Microfast®Model F-1 Adjustable Escutcheon Footnotes 1 Base part number shown. For complete part number,refer to Viking's current price schedule. Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 'This table shows the listings and approvals available at the time of printing.Other approvals may be in process. Listed by Underwriters Laboratories Inc.for use in the U.S.and Canada. cULus Listed as corrosion-resistant. 6 Other colors are available on request with the same Listings and Approvals as the standard colors. 'CE Certified,Standard EN 12259-1,EC-certificate of constancy of performance 0832-CPR-S0021. MED Certified,Standard EN 12259-1, EC-0832-MED-1003. DESIGN CRITERIA- UL (Also refer to Approval Chart 1 above.) cULus Listing Requirements: The Viking Microfast®Quick Response Pendent Sprinkler VK302 is cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers. • Designed for use in Light and Ordinary occupancies. • The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed. IMPORTANT:Always refer to Bulletin Form No. F_091699-Care and Handling of Sprinklers.Also refer to Form No. F_080614 for general care, installation,and maintenance information.Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB,APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards,whenever applicable. Form No. F_033314 18.06.21 Rev 18.1 r z Page 5 of 6 ® MICROFAST® QUICK TECHNICAL DATA MICROFAST® PENDENT SPRINKLER VK302 (K5.6) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Approval Chart 2 (FM) -Temperature KEY The Viking Microfast®Quick Response �, Finish Pendent Sprinkler VK302 A1x4 Escutcheon(if applicable) Maximum 175 PSI(12 Bar)WWP Base Part SIN Sprinkler Thread Size Nominal K-Factor Overall Length FM Approvals' Number' Style NPT BSP U.S. metric2 Inches mm (Refer also to Design Criteria.) 12979 VK302 Pendent 1/2" 15 mm 5.6 80.6 2-1/4 58 A1Z,B1Y,D2X,C2 NOTICE-Product Below-Limited Availability(Contact Local Viking Office) 06662B VK302 Pendent 1/2" 15 mm 5.6 80.6 2-1/4 58 A1Z,B1Y,D2X,C2 18021 VK302 Pendent 1/2" 15 mm 5.6 80.6 2-1/4 58 A1Z,B1Y Approved Escutcheons Approved Temperature Ratings X - Standard surface-mounted escutcheon or the A- 135°F(57°C), 155°F(68°C), 175°F(79°C),200°F Viking Micromatic® Model E-1 Recessed (93°C),286°F(141 °C) Approved Finishes Escutcheon B- 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 1-Brass,Chrome,White Polyester', Y - Standard surface-mounted escutcheon or the 200°F(93 °C) and Black Polyester' Viking Microfast®Model F-1 Adjustable Escutcheon, C - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 2-ENT' or recessed with the Viking Micromatic®Model E-1 °F(141 °C) or E-2 Recessed Escutcheon D- 155°F(68°C), 175°F(79°C),200°F(93°C) Z - Standard surface-mounted escutcheon or the Viking Microfast®Model F-1 Adjustable Escutcheon Footnotes ' Base part number shown. For complete part number, refer to Viking's current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. This table shows the FM Approvals available at the time of printing.Other approvals may be in process. 'Other colors are available on request with the same Approvals as the standard colors. 5 FM approved as corrosion proofing for corrosive environments. DESIGN CRITERIA- FM (Also refer to Approval Chart 2 above.) FM Approval Reauirements: The Viking Microfast®Quick Response Pendent Sprinkler VK302 is FM Approved as quick response Non-storage pendent sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT:Always refer to Bulletin Form No. F_091699-Care and Handling of Sprinklers.Also refer to Form No. F_080614 for general care, installation,and maintenance information.Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data,the appropriate standards of NFPA, FM Global, LPCB,APSAD,VdS or other similar organiza- tions, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Form No. F_033314 18.06.21 Rev 18.1 2 1 Page 6 of 6 MICROFAST® QUICK NiluNG® TECHNICAL DATA RESPONSE PENDENT SPRINKLER VK302 (K5.6) The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Ceiling Opening Size: • ' '; 2-5/16" (59 mm) minimum 1/2 - 2-1/2" (64 mm) maximum (15 mm) NPTtft 2-1/8" (54 mm) met Y Imo. T 4 1-1/2" 2-1/4" jo, 1-3/4" 2" Si (38 mm) (57 mm) (51 mm) Min. (45 mm) Max. 4` Installed with a standard Installed with a Microfast Note:At maximum,adapter 1/8" surface-mounted Model F-1 Adjustable is exposed 1/2"(13 mm) escutcheonEscutcheon from face of ceiling Figure 3: Sprinkler Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon Ceiling Opening Size: 2-5/16" (59 mm) minimum P. 2-1/2" (64 mm) maximum 2-1/8" 2-1/8" 4 (54 mm) , , 54 mm 4 1-1/8" 4 1 1-1/8" 1-3/4" (29 mm) 2"" - (29 mm) (45 mm) %, , AMin. (51 mm) Min. I Max. I. Max. Installed with a Installed with a Model Model E-1 Recessed E-2 Thread-on Recessed Escutcheon Escutcheon Figure 4: Sprinkler Dimensions with the Model E-1 and E-2 Recessed Escutcheons Form No. F_033314 18.06.21 Rev 18.1 Replaces Form No. F_033314 Rev 17.1 (Updated MED approval; added LPCB certificate number) i y February 3, 2014 Sprinkler 43a MICROFAST®AND MICRO- NIK1 NG® TECHNICAL DATA FASTHP® QUICK RESPONSE HORIZONTAL SIDEWALL SPRINKLERS (VK305&VK319) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 1. DESCRIPTION Viking Microfast®and MicrofastHP®Quick Response Horizontal Sidewall Sprinklers are small thermosensitive glass bulb spray sprinklers available with various finish- es and temperature ratings to meet design requirements. The special Polyester, Polytetrafluoroethelyne (PTFE), and Electroless Nickel PTFE (ENT) coatings =: can be used in decorative applications where colors are desired. In addition, ,- ` these coatings have been investigated for installation in corrosive atmospheres and are listed/approved as corrosion resistant as indicated in the Approval ' Chart. - " tt 2. LISTINGS AND APPROVALS ,. cOus cULus Listed: Category VNIV FM FM Approved: Class 2020 NYC Approved: MEA 89-92-E, Volume 16 Refer to Approval Chart 1 and Design Criteria on page 43d for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page 43f for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Available since 2003. Minimum Operating Pressure: 7 psi (0.5 bar) Viking Technical Data may be found on Maximum Working Pressure: Sprinkler VK319 is rated for use with water working pressures ranging from the minimum 7 psi (0.5 bar) The Viking Corporation's Web site at up to 250 psi (17 bar)for high-pressure systems. High-pressure(HP) http://www.vikinggroupinc.com. sprinklers can be identified by locating "250" stamped on the deflec- The Web site may include a more recent tor. Sprinkler VK305 is rated to a maximum 175 psi (12 bar)wwp. edition of this Technical Data Page. Factory tested hydrostatically to 500 psi (34.5 bar) Nominal K-Factor: 5.6 U.S. (80.6 metric*) *Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. Glass-bulb fluid temperature rated to-65 °F (-55 °C) Overall Length: 2-11/16" (68 mm) Material Standards: Frame Casting: Brass UNS-C84400 Deflector: Copper UNS-C19500 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Screw: Brass UNS-C36000 Pip Cap: Copper UNS-C11000 and Stainless Steel UNS-S30400 Pip Cap Attachment(for Sprinkler VK319): Brass UNS-C36000 For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed For ENT Coated Sprinklers: Belleville Spring - Exposed, Screw and Pip cap- ENT plated. Ordering Information: (Also refer to the current Viking price list.) Order Quick Response Horizontal Sidewall Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the ap- propriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass =A, Chrome = F, White Polyester= M-/W, Black Polyester= M-/B, Black PTFE = N, and ENT= JN Temperature Suffix(°F/°C): 135°/68° =A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = G For example, sprinkler VK305 with a Brass finish and a 155 °F/68 °C temperature rating = Part No. 12121AB Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.) Form No. F_030103 Replaces page 43a-f, dated December 12, 2013. (Added ENT Finish) 1 Sprinkler 43b February 3, 2014 MICROFAST®AND MICRO- NIKING® TECHNICAL DATA FASTHP® QUICK RESPONSE HORIZONTAL SIDEWALL SPRINKLERS (VK305&VK319) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Sprinkler Wrenches: A. Standard Wrench: Part No. 10896W/B (available since 2000). B.Wrench for recessed sprinklers with protective shields: Part No. 13655W/B*"(available since 2003) **A W'ratchet is required(not available from Viking). Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A(available since 1971) B. Twelve-head capacity: Part No. 01725A(available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking Quick Response Horizontal Sidewall Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. Protective Wrench Sprinkler Shield0 Us Flat N. 11 =%� l 10896 C) Figure 1: Standard Sprinkler Wrench 10896W/B 1 February 3, 2014 Sprinkler 43c NIKING8 MICROFAST®AND MICRO- TECHNICAL DATA FASTHP® QUICK RESPONSE HORIZONTAL SIDEWALL SPRINKLERS (VK305&VK319) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Sprinkler Nominal Maximum Ambient Bulb Color Classification Temperature Rating' Ceiling Temperature2 Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange Ordinary 155 °F (68 °C) 100 °F (38 °C) Red Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow Intermediate 200 °F (93 °C) 150 °F (65 °C) Green High 286 °F (141 °C) 225 °F (107 °C) Blue Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, Black PTFE, and ENT Corrosion-Resistant Coatings': White Polyester, Black Polyester, Black PTFE , and ENT Footnotes 'The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart.These tests cannot and do not represent all possible corrosive environments. Prior to installation,verify through the end-user that the coatings are compat- ible with or suitable for the proposed environment. For automatic sprinklers,the coatings indicated are applied to the exposed exterior surfaces only. For ENT coated sprinklers,the waterway is coated. Note that the spring is exposed on sprinklers with Polyester, PTFE, and ENT coatings. Sprinkler Wrench Part No. 13655W/B* for Recessed Horizontal Sidewall Sprinklers Protective Fit the wrench over the sprinkler Sprinkler and protective shield as shown. Shield I ,I ! I IN i`i` ii i IN 'Note: A 1/2" ratchet is required (not available from Viking). Figure 2: Wrench 13655W/B for Recessed Horizontal Sidewall Sprinklers Sprinkler 43d February 3, 2014 NIKING® MICROFAST®AND MICRO- TECHNICAL DATA FASTHP® QUICK RESPONSE HORIZONTAL SIDEWALL SPRINKLERS(VK305&VK319) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Approval Chart 1 (UL) Temperature KEY Finis Microfast®and MicrofastHP°Quick Response Horizontal Sidewall Sprinklers A1X+- Escutcheon(it applicable) Thread Size Nominal K-Factor Overall Length Listings and Approvals' Base Part SIN Maximum (Refer also to Design Criteria below.) Number Pressure NPT BSP U.S. metric' Inches mm cULus' NYC' LPCB C E (O Maximum 175 PSI(12 Bar)WWP For Light or Ordinary Hazard Occupancies. Deflector must be located 4"to 12"(102 mm to 305 mm)below the ceiling. 12121 VK305 175 psi 1/2" 15 mm 5.6 80.6 2-11/16 68 A1Y,B1X,C2W,D2Z A1Y -- -- -- Maximum 175 PSI WWP For Light Hazard Occupancies Only. Deflector must be located 4"to 6"(102 mm to 152 mm)below the ceiling. cULus NYC LPCB E p 12121 VK305 175 psi 1/2" 15 mm 5.6 80.6 2-11/16 68 A1Y,B1X,C2W, D2Z See Footnote 6. -- Maximum 250 PSI WWP For Light or Ordinary Hazard Occupancies. Deflector must be located 4"to 12"(102 mm to 305 mm)below the ceiling. cULus" NYC' LPCB CE 4 12285 VK319 250 psi 1/2" 15 mm 5.6 80.6 2-11/16 68 A1Y, B1X,C2W, D2Z A1Y -- Approved Temperature Ratings Approved Escutcheons W-Installed with standard surface-mounted escutcheons. A- 135°F(57°C), 155°F(68°C), 175°F(79°C), Approved Finishes X - Installed with standard surface-mounted escutcheons or the 200°F(93°C),and 286°F(141 °C) Viking Microfast® Model F-1 Adjustable Escutcheon, or re- 1 Brass, Chrome, White B-135°F(57°C), 155°F(68°C), 175°F(79°C), Polyester''', Black Polyester''$, cessed with the Viking Micromatic®Model E-1,E-2,E-3,or G-1 and 200°F(93°C) and Black PTFE7 Recessed Escutcheon C- 155°F(68°C), 175°F(79°C),200°F(93 °C), Y - Installed with standard surface-mounted escutcheons or the and 286°F(141 °C) 2-ENT7 Viking Microfast®Model F-1 Adjustable Escutcheon D - 155 °F (68 °C), 175 °F (79 °C), and 200 °F Z - Installed with standard surface-mounted escutcheons or re- (93°C) cessed with the Viking Micromatic Model E-1 Footnotes Base part number shown. For complete part number, refer to Viking's current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3This table shows the listings and approvals available at the time of printing. Other approvals may be in process. 4 Listed by Underwriters Laboratories Inc.for use in the U.S.and Canada. 'Accepted for use, City of New York Department of Buildings,MEA B9-92-E,Vol. 16. e Meets New York City requirements,effective July 1,2008. 'cULus Listed as corrosion-resistant. 8 Other colors are available on request with the same Listings and Approvals as the standard colors. DESIGN CRITERIA- UL (Also refer to Approval Chart 1 above.) cULus Listing Requirements: Quick Response Horizontal Sprinklers VK305 and VK319 are cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for sidewall standard spray sprinklers. • Designed for use in Light and Ordinary Hazard occupancies. • Locate the deflector 4"to 12"(102 mm to 305 mm)below the ceiling. • Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. • Minimum spacing allowed is 6 ft. (1.8 m). • Align the top of the deflector parallel with the ceiling. • Locate no less than 4"(102 mm)from end walls. • Maximum distance from end walls shall be no more than one-half of the allowable distance between sprinklers.The distance shall be measured perpendicular to the wall. • The sprinkler installation and obstruction rules contained in NFPA 13 for sidewall standard spray sprinklers must be followed. IMPORTANT: Always refer to Bulletin Form No. F_091699- Care and Handling of Sprinklers.Also refer to page QR1-3 for general care, in- stallation, and maintenance information.Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB,APSAD,VdS or other similar organizations,and also with the provisions of governmental codes, ordinances,and standards,whenever applicable. t I February 3, 2014 Sprinkler 43e C MICROFAST®AND MICRO- TECHNICAL DATA FASTHP® QUICK RESPONSE HORIZONTAL SIDEWALL SPRINKLERS (VK305&VK319) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Wall Opening Size: 2-5/16" (58,7 mm) minimum 2-1/2" (63,5 rim) maximum 2-7/16" 2-1/16" 2-11/16" (61.9 mm) I (52.4 mm) (68,3 mm) T Minimum l` I 1-1/4" ` 2-1/8" �� ` i C----A I� � i✓ (31,8 mm) 111111..0.0 i✓ (54 mm) �IIIIIIIIIIIII _� i✓ i✓1/2" / i �/ ��� (15 mm) J NPT II HSW Sprinkler 2-5/8" 12121 (VK305) (66,7 mm) Maximum Installed with a standard 1/8" (3,1 mm) Installed with a Microfast surface-mounted escutcheon Model F-1 Adjustable Escutcheon Figure 3: Sidewall Sprinkler VK305 Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon Wall Opening Size: 2-5/16" (58,7 mm) minimum 2-1/2" (63.5 mm) maximum 1-5/8" 1-3/4" (41,3 mm) I Minimum (44,5 mm) "-- IMinimum f ir _ , f otr.. ..,5____�2 1/8" -i2 1/8" _- � -iI(54mm) �IlllllllllllllAlliV1' ��I (54 mm) IN P I I :51 .--- I i NN Pi2-1/4" I 2-5/8" (57,2 mm) (67 mm) Maximum Maximum Installed with a Micromatic Installed with a Model E-2 Model E-1 Recessed Escutcheon Thread-on Recessed Escutcheon Figure 4: Sidewall Sprinkler VK305 Dimensions with the Model E-1 and E-2 Recessed Escutcheons , Sprinkler 43f February 3, 2014 NIKING8 MICROFAST®AND MICRO- TECHNICAL DATA FASTHP® QUICK RESPONSE HORIZONTAL SIDEWALL SPRINKLERS(VK305&VK319) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Approval Chart 2 (FM) Temperature KEY Microfast®Quick Response Horizontal Sidewall Sprinklers(FM) , Finish Maximum 175 PSI VVWP AIX Escutcheon(if applicable) Base Part SIN Maximum Thread Size Nominal K-Factor Overall Length FM Approvals' Number' Pressure NPT BSP U.S. metric' Inches mm (Refer also to Design Criteria below.) 12121 VK305 175 psi 1/2" 15 mm 5.6 80.6 2-11/16 68 A1Y,B1X Approved Escutcheons Approved Temperature Ratings X-Installed with standard surface-mounted escutcheons or the Viking A- 135°F(57°C), 155°F(68°C), 175°F(79°C), Approved Finish Microfast® Model F-1 Adjustable Escutcheon, or recessed with 200°F(93°C),and 286°F(141 °C) 1 -Brass the Viking Micromatic® Model E-1, E-2, E-3, or G-1 Recessed B- 135°F(57°C), 155°F(68°C), 175°F(79°C), Escutcheon and 200°F(93°C) Y-Installed with standard surface-mounted escutcheons or the Viking Microfast®Model F-1 Adjustable Escutcheon Footnotes 'Base part number shown. For complete part number, refer to Viking's current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 3This table shows the FM Approvals available at the time of printing.Other approvals may be in process. DESIGN CRITERIA- FM (Also refer to Approval Chart 2 above.) FM Approval Requirements: Horizontal Sidewall Sprinkler VK305 is FM Approved as a quick response Non-Storage sidewall sprinkler as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing,and deflector distance below the ceiling. NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F 091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD,VdS or other similar organizations,and also with the provisions of governmental codes, ordinances,and standards, whenever applicable. Wall Opening Size with the Model 0-1 Escutcheon: ^ 2-5/8" (66 mm) minimum 1/8" TVA' 3-3/4" (95 mm) maximum ' b (3.2 mm) Adjustable Ad justable-v__, Outer Cup —\ Adapter _ <II Ring \ �`II ... (66 mm)1 ... (102 mm) 0,/� 1111:11 .8111.1,1, 2,r...7. ..157___ ,� �i / ,,., Depth: • - Nil`�j 1-1/16" - (27 mm)_ 1-1/16"1yh Maximum Recess: (27 mm) 1/2" (12.7 mm) Figure 5: Sidewall Sprinkler VK305 Dimensions with the Model G-1 Recessed Escutcheons Form No. F_030103 Replaces page 43a-f, dated December 12, 2013. (Added ENT Finish) COSCO Fire Protection lire riot, • i e & F • tt • ngs COSCO Fire Protection Inc. 2501 SE Columbia Way, Suite 100 Vancouver,WA 98661 Phone:360-883-6383 Fax: 360-883-6390 Toll Free:800-983-6383 Y 1 1 1 tlifijI State Pipe & Supply, Inc. THIS INFORMATION PROVIDED IS BASED ON ASTM GUIDELINES FOR WELDED PIPE SPECIFICATIONS AND ASTM REQUIREMENTS. ACTUAL PIPE AND MATERIAL TEST REPORTS PROVIDED WOULD MEET OR EXCEED THESE GUIDELINES. TEST REPORTS WOULD PROVIDE SPECIFIC AND ACTUAL DETAILS CONCERNING THE MECHANICAL AND CHEMICAL PROPERTIES OF THE ACTUAL PIPE,AS WELL AS ADDITIONAL TESTS RESULTS REQUIRED BY ASTM. SCHEDULE 10**Black and Galvanized Steel ERW Pipe Pipe Size Test Pressure Nominal O.D. I.D. Weight/Foot psi 1" 1.315 1.097 1.410 700 1-1/4" 1.660 1.442 1.810 1200 1-112" 1.900 1.682 2.090 1200 2" 2.375 2.157 2.640 2300 2-1/2" 2.875 2.635 3.530 2500 3" 3.500 3.260 4.340 1290 4" 4.500 4.260 5.620 1000 5" 5.563 5.295 7.780 1010 6" 6.625 6.357 9.300 1020 800* 8.625 8.249 16.960 780 f*8"wall thickness is 0.188, not SCH10 or 0.148"wall thickness. COMPOSITION AND PROPERTIES Chemical and mechanical properties requirements are as prescribed by applicable ASTM standards edition January 2006. Chemical Requirements,Percent(Product) C Mn P S Other Specification Grade max max max max ASTM A53 A 0.250 0.950 0.05 0.045 - 1 Residual elements max:Cu-0.40.Ni-0.40,Cr-0.40,Mo-0.15 and V-.08. These live elements combined shall not exceed 1%. Mechanical Properties-Tensile Requirements Strength-psi. Yield Tensile Specification Grade Min Max Min Max ASTM A53 A 30,000 - 48,000 - NOTE: Elongation requirements vary with nominal area of test specimen and specified minimum tensile strength of the steel grade 9615 S. Norwalk Blvd., Santa Fe Springs,CA 90670 (562)695-5555 FAX: (562)692-1054 www.statepipe.com '1 Y State Pipe &Supply, Inc. THIS INFORMATION PROVIDED IS BASED ON ASTM GUIDELINES FOR WELDED PIPE SPECIFICATIONS AND ASTM REQUIREMENTS. ACTUAL PIPE AND MATERIAL TEST REPORTS PROVIDED WOULD MEET OR EXCEED THESE GUIDELINES. TEST REPORTS WOULD PROVIDE SPECIFIC AND ACTUAL DETAILS CONCERNING THE MECHANICAL AND CHEMICAL PROPERTIES OF THE ACTUAL PIPE,AS WELL AS ADDITIONAL TESTS RESULTS REQUIRED BY ASTM. SCHEDULE 40 Black and Galvanized Steel ERW Pipe Pipe Size Test Pressure Nominal O.D. I.D. Weight!Foot psi 1" 1.315 1.049 1.680 700 1-1/4" 1.660 1.380 2.270 1200 1-1/2" 1.900 1.610 2.720 1200 2" 2.375 2.067 3.660 2300 2-1/2" 2.875 2.469 5.800 2500 3" 3.500 3.068 7.580 2220 4" 4.500 4.026 10.800 1900 5" 5.563 5.047 14.630 1670 6" 6.625 6.065 18.990 1520 8" 8.625 7.981 28.580 1340 COMPOSITION AND PROPERTIES Chemical and mechanical properties requirements are as prescribed by applicable ASTM standards edition January 2006. Chemical Requirements,Percent(Product) C Mn P S Other Specification Grade max max max max ASTM A53 A 0.250 0.950 0.05 0.045 1 Residual elements max:Cu-0.40,Ni-0.40,Cr-0 40,Mo-0.15 and V-.08. These live elements combined shall not exceed 1% Mechanical Properties-Tensile Requirements Stren th-psi. Yield Tensile Specification Grade Min Max Min Max ASTM A53 A 30,000 - 48,000 - NOTE: Elongation requirements vary with nominal area of test specimen and specified minimum tensile strength of the steel grade. 9615 S. Norwalk Blvd., Santa Fe Springs,CA 90670 (562)695-5555 FAX: (562)692-1054 www.statepipe.com 1 Ductile Iron Threa eFittings ,.. r, ._ _ ....., „.„,,,.., , _,, , ..._... .,,_ ,. .,. ,,,,,,,,. . w 1 ��b __.. •.:,. *..,...._ .., , .., ,..._; ... __ ..,.. 4 L ,,, ,,.i.{ .., , ,,, ,, ,,,,,,..,,,, . ,. ,. , , _ _,,, N. , • L • L a n Ir L .F # I /1n.; 4 i to w�, *i Y#.r 9t, d'^dX `r. Ypy y. .x ATINTERNIONAL SMITPL CooPE I')® INTERNATIONAL Ductile Iron Threaded Fittings Specifications • The > branded Ductile Iron threaded fittings are UL Listed and FM Approved at 500 psi • Rated to 300 WSP • Ductile Iron castings conform to ASTM A536 C ® US • Fitting dimensions conform to ASME B16.3 LISTED • Bushings and plugs conform to ASME B16.14 41; • Fittings are 100% air tested APPROVED • NPT threads on all fittings conform to ASME B1.20.1 • Independent lab verification that fittings meet applicable chemical & physical properties • Manufacturing facilities are ISO 9001:2000 and ISO 14001 Temperature Working Pressure, Nonshock PSIG Degrees F 300# Class Threaded Fittings -20 to 100 500 150 500 200 480 250 460 300 440 350 420 — 400 400 450 380 500 360 550 340 600 320 650 300 r f y lir.1- Ductile Iron Fittings - Class 300 UL/FM J tpuM rrr li.iy c (rill us 411> Fig. 35E 3- 90°Elbow LISTED APPROVED A Size Part Number A Packing Weight IN IN Inner Master LB 1/2 35E 3004 1.13 100 200 0.2 3/4 35E 3006 1.31 70 140 0.3 --n ' A 1 35E 3010 1.50 40 80 0.5 ' ; .. 1-1/4 35E 3012 1.75 25 50 0.8 1-1/2 35E 3014 1.94 18 36 1.1 2 35E 3020 2.25 10 20 1.8 2-1/2 35E 3024 2.70 4 8 3.2 Fig. 35RE3- 90°Reducing Elbow B Size A B Packing Weight (-) IN Part Number IN IN Inner Master LB IS _�� 3/4 x 1/2 35RE3006004 1.20 1.22 80 160 0.3 I� 1 x 1/2 35RE3010004 1.26 1.36 70 140 0.4 A 1 x 3/4 35RE3010006 1.38 1.45 50 100 0.4 q' 1-1/4 x 1/2 35RE3012004 1.34 1.53 35 70 0.5 1-1/4 x 3/4 35RE3012006 1.45 1.63 35 70 0.6 1-1/4 x 1 35RE3012010 1.58 1.67 30 60 0.7 1-1/2 x 1/2 35RE3014004 1.52 1.75 30 60 0.6 1-1/2 x 3/4 35RE3014006 1.52 1.75 25 50 0.7 1-1/2 x 1 35RE3014010 1.65 1.80 20 40 0.8 1-1/2 x 1-1/4 35RE3014012 1.82 1.88 18 36 1.0 2 x 1/2 35RE3020004 1.60 1.97 18 36 1.0 2 x 3/4 35RE3020006 1.60 1.97 18 36 1.0 2 x 1 35RE3020010 1.73 2.02 16 32 1.2 I) 2 x 1-1/4 35RE3020012 1.90 2.10 12 24 1.3 2 x 1-1/2 35RE3020014 2.02 2.16 10 20 1.5 U 2-1/2 x 1-1/2 35RE3024014 2.16 2.51 6 12 2.2 C 2-1/2 x 2 35RE3024020 2.39 2.60 6 12 2.5 T I Fig. 35F 3-45°Elbow L Size Part Number A Packing Weight EA IN IN Inner Master LB °4**‘ ' 1/2 35F 3004 0.88 150 300 0.2 3/4 35F 3006 0.98 80 160 0.3 4ttii\It 1 35F 3010 1.13 40 80 0.5 1-1/4 35F 3012 1.29 25 50 0.7 1-1/2 35F 3014 1.44 20 40 1.0 I� IA 2 35F 3020 1.69 10 20 1.6 2-1/2 35F 3024 1.95 4 8 2.7 Fig. 35T3- Tee Size A Packing Weight • Part Number IN IN Inner Master LB or jaMili 1/2 35T 3004 1.13 80 160 0.3 ! IA 3/4 351 3006 1.31 30 60 50 0.5 I� �I 1 35T 3010 1.50 25 0.7 ..�.,.,.. 1-1/4 35T 3012 1.75 10 20 1.1 A IA 1-1/2 351 3014 1.94 10 20 1.5 2 35T 3020 2.25 6 12 2.4 2-1/2 35T 3024 2.70 4 8 4.3 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com 1 fl I. 1 ucti e ron ittings - ass I I I 7 1 (uAtl.rrr PLUS c ® Us 41> Fig. 35RT3-Reducing Tee LISTED APPROVED Size A B C Packing Weight ��1IN Part Number IN IN IN Inner Master LB i C 3/4 x 1/2 35RT3006004 1.20 1.20 1.22 60 120 0.4 a .__. 1 I1 1 x 1/2 35RT3010004 1.26 1.26 1.36 30 60 0.6 1 x 1/2 x 1 35RT3010004010 1.50 1.36 1.50 30 60 0.6 1 x 3/4 35RT3010006 1.38 1.38 1.45 25 50 0.6 1 -a 1 x 3/4 x 3/4 35RT3010006006 1.38 1.31 1.45 35 70 0.6 B A 1 x 3/4 x 1 35RT3010006010 1.50 1.45 1.50 '25 50 0.7 - 1-1/4 x 1/2 35RT3012004 1.34 1.34 1.53 20 40 0.8 1-1/4 x 1/2 x 1-1/4 35RT3012004012 1.75 1.53 1.75 25 50 0.9 1-1/4 x 3/4 35RT3012006 1.45 1.45 1.62 15 30 0.9 1-1/4 x 3/4 x 1-1/4 35RT3012006012 1.75 1.62 1.75 20 40 1.0 1-1/4 x 1 35RT3012010 1.58 1.58 1.67 15 30 1.0 1-1/4 x 1 x 1/2 35RT3012010004 1.34 1.26 1.53 25 50 0.7 1-1/4 x 1 x 3/4 35RT3012010006 1.45 1.38 1.63 20 40 0.8 1-1/4 x 1 x 1 35RT3012010010 1.58 1.50 1.69 20 40 0.9 1-1/4 x 1 x 1-1/4 35RT3012010012 1.75 1.69 1.75 15 30 1.0 1-1/2 x 1/2 35RT3014004 1.41 1.41 1.66 16 32 1.0 1-1/2 x 1/2 x 1-1/4 35RT3014004012 1.81 1.56 1.88 24 48 1.1 1-1/2 x 1/2 x 1-1/2 35RT3014004014 1.94 1.66 1.94 12 24 1.2 1-1/2 x 314 35RT3014006 1.52 1.52 1.75 16 32 1.1 1-1/2 x 3/4 x 1-1/4 35RT3014006012 1.94 1.66 1.88 20 40 1.1 1-1/2 x 3/4 x 1-1/2 35RT3014006014 1.94 1.75 1.94 18 36 1.2 1-1/2 x 1 35RT3014010 1.65 1.65 1.80 12 24 1.2 1-1/2 x 1 x 1/2 35RT3014010004 1.44 1.25 1.69 20 40 0.8 1-1/2 x 1 x 3/4 35RT3014010006 1.50 1.44 1.75 16 32 0.9 1-1/2 x 1 x 1 35RT3014010010 1.65 1.50 1.80 16 32 1.0 1-1/2 x 1 x 1-1/4 35RT3014010012 1.82 1.67 1.88 12 24 1.2 D 1-1/2 x 1 x 1-1/2 35RT3014010014 1.94 1.80 1.94 12 24 1.3 U 1-1/2 x 1-1/4 35RT3014012 1.82 1.82 1.88 12 24 1.4 1-1/2 x 1-1/4 x 1/2 35RT3014012004 1.41 1.34 1.66 16 32 0.9 C 1-1/2 x 1-1/4 x 3/4 35RT3014012006 1.52 1.45 1.75 16 32 1.0 T 1-1/2 x 1-1/4 x 1 35RT3014012010 1.65 1.58 1.80 16 32 1.1 1-1/2 x 1-1/4 x 1-1/4 35RT3014012012 1.82 1.75 1.88 14 28 1.3 1-1/2 x 1-1/4 x 1-1/2 35RT3014012014 1.94 1.88 1.94 14 28 1.4 L 2 x 1/2 35RT3020004 1.49 1.49 1.88 10 20 1.5 E 2 x 3/4 35RT3020006 1.60 1.60 1.97 10 20 1.6 2 x 1 35RT3020010 1.73 1.73 2.02 8 16 1.7 2 x 1 x 2 35RT3020010020 2.25 2.02 2.25 8 16 1.9 2 x 1-1/4- --- -35RT3020012 1.90 1.90 2.10 8 16 1.9 2 x 1-1/4 x 2 35RT3020012020 2.25 2.10 2.25 8 16 2.0 2 x 1=1/2 35RT3020014 2.02 2.02 2.16 8 16 2.1 2 x 1-1/2 x 1/2 35RT3020014004 1.49 1.41 1.88 10 20 1.3 2 x 1-1/2 x 3/4 35RT3020014006 1.60 1.52 1.97 10 20 1.4 2 x 1-1/2 x 1 35RT3020014010 1.73 1.65 2.02 8 16 1.5 2 x 1-1/2 x 1-1/4 35RT3020014012 1.90 1.82 2.10 8 16 1.7 2 x 1-1/2 x 1-1/2 35RT3020014014 2.02 1.94 2.16 8 16 1.8 Fig. 35BT3-Bull Head Tee Size Part Number A B C Packing Weight C IN IN IN IN Inner Master LB oh iiii . I 3/4 x 1 35BT3006010 1.45 1.45 1.37 30 60 0.6 1 x 1 1/4 35BT3010012 1.67 1.67 1.58 20 40 0.9 1 x 1-1/2 35BT3010014 1.80 1.80 1.65 15 30 1.0 li 111. A i B 1-1/4 x 1 x 1-112 35873012010014 1.88 1.80 1.82 15 30 1.2 1-1/4 x 1-1/2 35BT3012014 1.88 1.88 1.82 15 30 1.3 1-1/4 x 2 35BT3012020 2.10 2.10 1.90 10 20 1.6 1-1/2 x 1-1/4 x 2 35BT3014012020 2.16 2.10 2.02 10 20 1.8 1-1/2 x 2 35BT3014020 2.16 2.16 2.02 8 16 1.8 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com ' ) 1�1 Duct' e ron fittings - ass ` 1 I 9.1.4111111'W„, C el US 4114* LISTED APPROVED Fig. 35CP3-Straight Coupling with Ribs ` A III _ Size Part Number A Packing Weight IN IN Inner Master LB 1111 0.1 0.2 1/2 35CP3004 1.38 200 400 3/4 35CP3006 1.63 100 200 1 35CP3010 1.75 60 120 0.4 1-1/4 35CP3012 2.00 35 70 0.5 1-1/2 35CP3014 219 25 50 0.7 2 35CP3020 2.62 15 30 1.2 2-1/2 35CP3024 3.00 9 18 2.2 Fig. 35RC3-Hex Reducing Coupling _ Size Part Number A Packing Weight �' . IN IN Inner Master LB ,. i', j A 1 x 1/2 35RC3010004 1.69 80 160 0.3 j 1 x 3/4 35RC3010006 1.69 60 120 0.4 W 1-1/4 x 3/4 35RC3012006 2.06 40 80 0.6 HA 2 x 1 (not hex) 35RC3020010 2.81 20 40 1.0 Fig. 35HB3-Hex Bushing WA Size Part Number A Packing Weight IN IN Inner Master LB B ' 1 x 1/2 35HB3010004 1.06 180 360 0.2 1 .. ^ 1 x 3/4 35HB3010006 1.06 180 360 0.1 ' - .�"`" I�I jA 1-1/4 x 1 35HB3012010 1.19 90 180 0.2 1-1/2 x 1 35HB3014010 1.25 75 150 0.4 1-1/2 x 1-1/4 35HB3014012 1.25 75 150 0.3 2 x 1 35HB3020010 1.38 40 80 0.6 2 x 1-1/4 35HB3020012 1.38 40 80 0.6 2 x 1-1/2 35HB3020014 1.38 40 80 0.6 Fig. 35SP3-Square Head Plug 11111 Size Part Number A Packing Weight IN IN Inner Master LB ��� 1/2 35SP3004 0.94 600 1200 0.07 0.1 0.1 i�:a �i A 3/4 35SP3006 1.12 350 700 �IdlingIdling1 35SP3010 1.25 200 400 1-1/4 35SP3012 1.37 100 200 0.3 1-1/2 35SP3014 1.44 80 160 0.4 2 35SP3020 1.50 45 90 0.6 Fig. 35U 3- Union with Brass Seat A , Size A Packing Weight Part Number 0. 1 •�_ IN IN Inner Master LB I 1 35U 3010 2.19 20 40 1.0 1 m 1-1/4 35U 3012 2.50 15 30 1.2 1-1/2 35U 3014 2.62 10 20 1.7 _�V�i 2 35U 3020 3.12 6 12 2.4 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com 74 lj i„../-1-I i ucti e ron Iittin s - ass I I I v g I {aur?,_iu c (3uS ®► Fig. 35X 3- Cross LISTED APPROVED 4--A )14-------) Size A Packing Weight Part Number lung" IN IN Inner Master LB A 1 35X 3010 1.50 20 40 0.9 °. i 1-1/4 35X 3012 1.75 12 24 1.4 k0i -1 II A 1 1/2 35X 3014 1.94 8 16 1.8 ill r2 35X 3020 2.25 6 12 2.8 BB Fig. 35RX3-Reducing Cross - r". Size Part Number A B Packing Weight A IN IN IN Inner Master LB \to ( i 1-1/4 x 1 35RX3012010 1.67 1.58 15 30 1.2 1-11/2/2x 1 35RX3014010 1.80 1.65 12 24 1.4 A 2 x 1 35RX3020010 2.02 1.73 8 16 2.0 Fig. 35C 3- Cap Size Part Number A Packing Weight ®� �i IN IN Inner Master LB 35C 3004 0.87 300 600 0.1 3/4 35C 3006 0.97 0.1 B� A 1 3503010 1.16 110200 220400 0.2 1-1/4 35C 3012 1.28 70 140 0.4 1-1/2 35C 3014 1.33 50 100 0.5 2 35C 3020 1.45 25 50 0.8 2-1/2 35C 3024 1.70 18 36 1.6 Fig. 35BC3-Beam Clamp I-r ��1 Fit Size Part Number A Packing Weight A IN IN Inner Master LB 3/8 35BC3003 0.75 100 200 0.3 �, , 1/2 35BC3004 0.75 80 160 0.5 SNII'I'H-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.cum Warranty and Limitations of Liability SMITH-COOPER INTERNATIONAL(SCI)warrants to its initial purchaser only,that its products which are delivered to this initial purchaser will be of the kind described in the order or price list and will be free of defects in workmanship or material for a period of five years from the date of delivery to our initial purchaser. Should any failure to conform to this warranty appear within five years after the date of the initial delivery to our initial purchaser,SCI will,upon written notification thereof and substantiation that the goods have been stored,installed,maintained and operated in accor- dance with recognized engineering and piping practices and industry standards,correct such defects by suitable repair or replacement (which alternative shall be at the discretion of SCI)of product at SCI's own expense upon return of the defective part to SCI. In the event that SCI elects to replace the defective product,SCI shall pay up to$50 per defective product for total cost of replacement. In the event of multiple claims,such payment shall be no greater than$1,000 for each installation project. This warranty applies only during normal use that meets the above referenced conditions of installation and operation and is absolutely void if the product has been damaged after purchase or if it has been misused,repaired,altered or modified in any manner whatsoever. SCI shall not warranty any of its products if any portion of the product including without limitation,any component,gasket,housing or bolt has been modified,altered,remanufactured or replaced in any manner by any customer,user of the product or third party. Correction of non-conformities,in the manner and for the period of time provided above,shall constitute fulfillment of all liabilities of SCI to our initial purchaser,with respect to the goods,whether based on contract,negligence,strict tort,or otherwise. It is the intention of SCI that no warranty of any kind,whether expressed or implied shall pass through our initial purchaser to any other person or corpora- tion. No returns will be allowed unless prior written permission of SCI is first obtained. Buyers shall be responsible for all costs of transporta- tion as well as a restocking charge. This warranty is exclusively for the benefit of the initial purchaser of this product from SCI and,except to the extent prohibited by ap- plicable law,the foregoing warranty is in lieu of all other warranties,express or implied,including but not limited to warranties of fitness or merchantability. LIMITATIONS OF LIABILITY:SCI shall not under any circumstances be liable for special or consequential damages such as,but not limited to damage to loss of other propertyor equipment,loss of profits or revenue,cost of capital,cost of purchased or replacement ent goods, claims of customers of our initial purchaser,any labor cost for repair or replacement of the product or damage caused by the product. The remedies of our initial purchaser,and all others,set forth herein are exclusive,and the liability of SCI with respect to same shall not, except as expressly provided herein,exceed the price of the SCI products on which such liability is based. ©2010 Smith-Cooper International® 84 SIKI]H (0 R ramtivcwilCA L4 iI'f1IQL,ERUREE-806066400676* •FA1311 $3ZP8 4456 •wwwwmaininichopepenntim 84 Industrial PVF Malleable Iron Cast Iron Ductile Iron ' Bronze Fittings Flanged Fittings Forged Steel Fittings Merchant Steel COOPLETS® Nipples Lead Free Valves Ball Gate Globe Check Butterfly Straight Stops Hose Bibbs/Sillcocks Boiler Drains Specialties Stainless Steel 150#Fittings 3000#Forged Fittings Weld Fittings Sanitary Fittings Compression Fittings Flanges Nipples Pipe &Tubing Valves Grooved Couplings Fittings Valves COOPLET®Adapter Nipples SMITH C 00PE I' ® � INTERNATIONAL Toll Free 800-766-0076 Fax 323-890-4456 www.smithcooper.com 071 r' Victaulic® VicFlexTM Sprinkler Fittings ictau6c° Series AH2 and AH2-CC Braided Flexible Hoses 10.85 • 7 Vic FlexTM (17 Series AH2 Series AH2-CC 1.0 PRODUCT DESCRIPTION Available Sizes by Component • Series AH2 Braided Hose: 31, 36, 48, 60, 72"/790 915, 1220, 1525, 1830mm. Note: length includes adapter nipple and 5.75"/140mm straight reducer. • Series AH2-CC Braided Hose: 31, 36, 48, 60, 727790, 915, 1220, 1525, 1830 mm. Note: length includes captured coupling and 5.757140 mm straight reducer. • Sprinkler Reducers: • Sprinkler Connections: l/ and 3/4"/15 and 20mm • Straight Lengths: 5.75, 9, 137140, 230, 330 mm • 90"Elbows: • Short (typically used with concealed sprinklers) • Long (typically used with recessed pendent sprinklers) • Low Profile Short (for use with Style AB5, AB11 and AB12 Bracket) • Low Profile Long (for use with Style AB5, AB11 and AB12 Bracket) • Inlet Connections: • 1725 mm Grooved IGS • 1725 mm NPT or BSPT adapter nipples for attaching to pipe and fittings outlined in NFPA standards. • 3/4720 mm NPT or BSPT adapter nipples available for VdS. • 11/4"/32mm BSPT adapter nipples available for LPCB. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION,MAINTENANCE OR SUPPORT. • • System No. Location Spec Section Paragraph Submitted By Date 1 Approved Date victaulic.com 10.85 5839 Rev AC Updated 05/2018 ©2018 Victaulic Company.All rights reserved. 1 •ctaul,c° victaulic.com 1.0 PRODUCT DESCRIPTION (Continued) • • Brackets: • Style AB1 for suspended and hard-lid ceilings and sidewalls, allows installation before most ceiling tiles in place • Style AB2 for suspended and hard-lid ceilings and sidewalls, allows for vertical sprinkler adjustment, and installation before most ceiling tiles in place • Style AB3 for surface mount applications, wood, metal and block walls, or ceilings • Style AB4 for hard-lid ceilings with hat furring channel grid systems, allows for vertical sprinkler adjustment • Style AB5 for hard-lid ceilings and sidewalls, allows for vertical sprinkler adjustment • Style AB7 for suspended and hard-lid ceilings • Style AB7 Adjustable for suspended and hard-lid ceilings • Style AB8 for hard-lid ceilings with CD 60/27 profile metal studs (regionally available) • Style AB9 for hard-lid ceilings with hat furring channel grid systems • Style AB10 for Armstrong®TechZoneTM ceilings • Style AB11 for lay-in panel suspended t-grid ceilings or drywall suspended t-grid ceilings, allows for low profile installations (use only with 90° low profile elbows) • Style AB12 for suspended and hard-lid ceilings, allows for vertical sprinkler adjustment, and allows for low profile installation down to 4'/100mm. Maximum Working Temperature • 225°F/107°C Maximum Working Pressure • 200 psi/1375 kPa (FM Approval) • 175 psi/1206 kPa (cULus Listed) • 1600 kPa/232 psi (VdS/LPCB Approved) • 1.4 MPa (CCCf Approved) Connections • To adapter nipple (inlet) via • 1"/25.4 mm Grooved IGS • 1"/25.4 mm NPT or BSPT male thread • 3/4720 mm BSPT male thread (VdS only) • 11/4"/32 mm BSPT male thread (LPCB only) • To sprinkler head (outlet)via 1/" or 3/4'/15 mm or 20 mm Minimum Bend Radius • 7'/178 mm (FM/CCCf Approval) • 2'/51 mm (cULus Listed) • 3776.2 mm (VdS/1 PCR Approved) Maximum Allowable Sprinkler K-Fdcturs • FM (l "/15mm reducer) K5.6/8,1 (S.I.), (3/4"/20mm reducer) K14.0/20,2 (S.I.) • cULus (1/2"/15mm reducer) K8.0/11,5(S.I.), (3/4"/20mm reducer) K14.0/20,2 (S.I.) • VdS/LPCB (l "/15mm reducer) K5.6/8,1 (S.I.), (3A/20mm reducer) K8.0/11,5 (S.I.) 2.0 CERTIFICATION/LISTINGS ® c0 VdS LPCB 0 40 usreo as* . w• NOTE • The VicFlexTMSeries AH2 Hose has been tested and evaluated by Spears®for acceptable use with Spears®CPVC Products and is therefore covered under the Spears®FlameGaurd®Installer Protection Plan. 10.85 5839 Rev AC Updated 05/2018 ©2018 Victaulic Company.All rights reserved. victaulic.com 2 ✓ctaulIc' 1 I I f victaulic.com • 3.0 SPECIFICATIONS— MATERIAL Series AH2 • Flexible Hose: 300-series Stainless Steel • Collar/Weld Fitting: 300-series Stainless Steel • Gasket Seal:Victaulic EPDM • Isolation Ring: Nylon • Nut and Nipple: Carbon Steel, Zinc Plated • Reducer(1"/15 mm or 3/4%20 mm): Carbon Steel, Zinc-Plated • Low Profile Elbows: Stainless Steel Brackets: Carbon Steel, Zinc-Plated Series AH2-CC • Flexible Hose: 300-series Stainless Steel • Collar/Weld Fitting: 300-series Stainless Steel • Gasket Seal:Victaulic EPDM • Isolation Ring: Nylon • Coupling Retainer Ring: Polyethelene • Nut and Nipple: Carbon Steel, Zinc Plated • Reducer (1/2115 mm or 3/4"/20 mm): Carbon Steel, Zinc-Plated • Housing: Ductile iron conforming to ASTM A 536, Grade 65-45-12. Ductile iron conforming to ASTM A 395, Grade 65-45-15, is available upon special request. Coupling Housing Coating: • Orange enamel (North America, Asia Pacific). • Red enamel (Europe). • Hot dipped galvanized. Gasket:' • Grade"E" EPDM (Type A) FireLock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories of Canada Limited, and Approved by Factory Mutual Research for wet and dry (oil free air)sprinkler services within the rated working pressure. Services listed are General Service Guidelines only.It should be noted that there are services for which these gaskets are not compatible.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. • Bolts/Nut: Zinc electroplated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A 449 and physical requirements of ASTM A 183. • Linkage: CrMo Alloy Steel zinc electroplated per ASTM B633 Zn/Fe 5, Type III Finish 10.85 5839 Rev AC Updated 05/2018 ©2018 Victaulic Company.All rights reserved. victaulic.com 3 ✓atauliC victaulic.com 4.0 DIMENSIONS Product Details-Series AH2 Braided Hose Item Description 1 Flexible Hose 0 2 Isolation Ring © p p ° p 0 p 3 Gasket 4 Nut 1;' Mil li;'Mf,lwT 5 Adapter Nipple J 6 Braid A Collar/Weld Fitting B > 8 Sleeve Hose Length Dimensions Hose Length A B inches inches inches mm mm mm 31/790 25.3/641 31/790 36/915 31.3/794 36/915 48/1219 42.3/1073 48/1220 60/1525 54.3/1378 60/1525 72/1830 66.3/1683 72/1830 Series AH2-CC Braided Hose © Item Description O O 0 `j @ 0 O 1 Flexible Hose Oil 2 Isolation Ring \ i, _II1'I Ur ,II 3 Gasket ,1�{I[lIR.�IR IYl� �` 4 Nut 5 Captured Coupling A 6 Braid 7 Collar/Weld Fitting 8 Sleeve Hose Length A B inches inches inches mm mm mm 31/790 24.5/622 29.8/757 36/915 29.5/749 34.8/884 48/1219 41.5/1054 46.8/1189 60/1525 53.5/1359 58.8/1494 72/1830 65.5/1664 70.8/1798 • • 10.85 5839 Rev AC Updated 05/2018 ©2018 Victaulic Company.All rights reserved. victaulic.com 4 ✓ctaulic° r � victaulic.com 4.0 DIMENSIONS (Continued) Standard Reducer r11111111111115111111111111111 111 1111111 5.757140 mm straight reducer Optional Reducers rl 9.0"/229 mm straight reducer IIIIIIIIIIIIIIIIIIIIIIIIIII IIIIIIIIIIIIIIIIIIIII�lllll IIIIIIIIIIIIIIIIIIIIlllll I 13.07330 mm straight reducer 2.62"/ 66.5 mm 2.62"/ '1 66.5mm I' • 6.57"/ _ _ 166.9 mm = _ 4.83"/ _ _ 122.7 mm = _= n N Short 90°elbow reducer Long 90°elbow reducer NOTE • The Short 90°elbow reducer is typically used with concealed sprinklers while the longer 90 elbow is typically used in the installation of recessed pendent sprinklers. • FM/VdS Approved only. Low Profile All �II 4.59'7 _ = 116 mm 2.84"/ 72 mm 1.4"/ 1.4"/ 36mm 36mm Short 90°elbow reducer Long 90°elbow reducer NOTE • Style AB11:When low profiles elbows are used with the Style AB11 bracket,the Low Profile Short Elbow is typically used with concealed sprinklers while the Low Profile Long Elbow is typically used in the installation of recessed pendent sprinklers. • • 10.85 5839 Rev AC Updated 05/2018 ©2018 Victaulic Company.All rights reserved. victaulic.com 5 jctaulia victaulic.com • • 4.1 DIMENSIONS VicFlex Brackets Style AB1 • Suspended Ceilings r; • Hard Lid Ceilings(FM Only) f Item Description r 1 24"/610 mm or 48"/1219 mm Square Bar 2 Patented Center Bracket 3 End Bracket O NOTE • Both sizes FM/VdS/LPCB Approved,cULus listed11?1 O 9 Style AB2 • Suspended Ceilings • Hard-Lid Ceilings Item Description / 1 _ 24"/610mmor48'/1219mm Square Bar 2 + Patented Vertically Adjustable Center Bracket 3 End Bracket NOTE O • Both sizes FM/VdS/LPCB Approved,cULus listed © �I j�9 Style AB3 • Surface Mount Applications raw. • FM/LPCB Approved fro 10.85 5839 Rev AC Updated 05/2018 ©2018 Victaulic Company.All rights reserved. victaulic.com 6 jctaulle r � victaulic.com . - • 4.2 DIMENSIONS VicFlex Brackets Style AB4 ` 0 • Hard-Lid Ceilings with Hat furring � B channel grid system Item Description 1 24"/610 mm or 48"/1219 mm Square Bar 2 Patented Vertically Adjustable Center Bracket 3 End Bracket for Hat Furring Channel ••I111 :� NOTE I � • Both sizes FM/VdS/LPCB Approved,cULus listed. Style AB5 • Hard-Lid Ceilings ', o`• Item Description 1 24"/610 mm or 48"/1219 mm Square Bar 2 Patented Vertically Adjustable Center Bracket 3 End Bracket O I. I NOTE • Both sizes FM/VdS/LPCB Approved,cULus listed. fAtio Style AB7 • Suspended Ceilings • Hard-Lid Ceilings Item Description O 1 24"/610 mm or 48"/1219 mm Square Bar 2 Patented 1-Beet®Center Bracket O 3 End Bracket y ' NOTE • Both sizes FM/VdS/LPCB Approved. • • I 20 Nr Style AB7 Adjustable • Suspended Ceilings • Hard Lid Ceilings ® - Item Description 1 700 mm or 1400 mm Square Bar 2 Patented 1-Beet®Center Bracket 3 End Bracket(adjustable) 0 NOTE �y • Both sizes FM/VdS/LPCB Approved. • 410 • • I I 10.85 5839 Rev AC Updated 05/2018 ©2018 Victaulic Company.All rights reserved. victaulic.com 7 ✓otaullid 4.3 DIMENSIONS VicFlex Brackets Style AB8 • Hard Lid Ceilings � ,� Item Description 1 700mm or 1400mm Square Bar 2 Patented Vertically Adjustable Center Bracket 3 I End Bracket ,j NOTE • Both sizes FM/VdS/LPCB Approved. Style AB10 • Suspended ceilings 0 • Armstrong®TechZone'" .-4" © o r �: 0 Item Description 1'' fr I" 1 6"/152 mm Square Bar i 2 Patented 1-Beer Center Bracket 3 End Bracket NOTE • FM/VdS/LPCB Approved,cULus listed. Style AB11 • Suspended ceilings 0 • Hard-Lid ceilings ` , Item Description 1 _24"/610 mm or 48"/1219 mm Square Bar 2 _ Patented 1-Bee2"Center Bracket 3 End Bracket NOTE -",1 , y O • FM/VdS Approved,cULus listed. 0 1.., CC iii e4 Style AB12 • Suspended ceilings • Hard-Lid ceilings •. Item Description ell `-- '' Style ra12 Drive#2Square Set Screw `\' 11' ' NOTE I;, 0 • FM/VdS Approved. • • 10.85 5839 Rev AC Updated 05/2018 C 2018 Victaulic Company.All rights reserved. victaulic.com 8 ✓ctaulic' , Victaulic° FireLockTM Rigid Coupling ;ctaUl;c* Style 009N 10.64 Qii. Patented 1.0 PRODUCT DESCRIPTION Available Sizes • 1 1/4— 12"/32—300 mm Pipe Material • Carbon steel, Schedule 10, Schedule 40. For use with alternative materials and wall thicknesses please contact Victaulic. Maximum Working Pressure • Up to 365 psi/2517 kPa. Function • Joins carbon steel pipe. • Provides a rigid pipe joint designed to restrict axial or angular movement. 2.0 CERTIFICATION/LISTINGS can ® LPCB yds) C E MTH C104-1a/36 EN 10311 Regulation(EU) No.305/2011 ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION,MAINTENANCE OR SUPPORT. • • System No. Location Spec Section Paragraph F Submitted By Date Approved Date vlctaulic.com 10.64 7072 Rev L Updated 08/2017 ©2017 Victaulic Company.All rights reserved. 1 j taUlia i ' victaulit carr. 3.0 SPECIFICATIONS- MATERIAL • Housing: Ductile iron conforming to ASTM A 536, Grade 65-45-12. Ductile iron conforming to ASTM A 395, Grade 65-45-15, is available upon special request. Housing Coating: (specify choice) L, Orange enamel (North America, Asia Pacific) [j Red enamel (Europe) ❑ Hot dipped galvanized Gasket: (specify choice') Grade"E" EPDM (Type A) FireLock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories of Canada Limited, and Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services within the rated working pressure. 1 Services listed are General Service Guidelines only.It should be noted that there are services for which these gaskets are not compatible.Reference should always be made to the latest V, ! for specific gasket service guidelines and for a listing of services which are not compatible. Bolts/Nuts: (specify choice2) Standard: Carbon steel oval neck track bolts meeting the physical and chemical requirements of ASTM A449 (imperial) and ISO 898-1 Class 9.8 (metric). Carbon steel hex nuts meeting the physical and chemical requirements of ASTM A563 Grade B (imperial - heavy hex nuts) and ASTM A563M Class 9 (metric - hex nuts). Track bolts and hex nuts are zinc electroplated per ASTM B633 ZN/FE5, finish Type III (imperial) or Type II (metric). Optional: Stainless steel oval neck track bolts meeting the requirements of ASTM F593, Group 2 (316 stainless steel), condition CW. Stainless steel heavy hex nuts meeting the requirements of ASTM F594, Group 2 (316 stainless steel), condition CW, with galling-resistant coating.2 2 Optional bolts/nuts are available in imperial size only. • • 10.64 7072 Rev L Updated 08/2017 ©2017 Victaulic Company.All rights reserved. victaulic.com 2 ✓ctaulIC 1 I 1 ull;tatilic,LO i • • 4.0 DIMENSIONS Style 009N \,:1 IIAII :1/��:1 I li �it, ion �r \ / IMP �J-` II111 Style 009N Pre-Assembled (Push On Condition) Style 009N Joint Assembled Bolt/Nut Dimensions Weight Actual Maximum Maximum Allow. Pre-assembled Nominal Outside Working End Pipe End (Push On Condition) Joint Assembled Approx. Size Diameter Pressure3 Load3 Separation Qty. Size X Y X Y Z (Each) inches inches psi lb inches inches inches inches inches inches inches lb mm mm kPa N mm mm mm mm mm mm mm kg 1% 1.660 365 790 0.102 3/e x 2 3.13 5.00 2.75 5.00 2.00 1.4 32 42.4 2517 3514 2.54 M10 x 51 79 127 70 127 51 0.6 11/2 1.900 365 1035 0.10 2 3/8 x 2 3.38 5.13 3.00 5.13 2.00 1.5 40 48.3 2517 4604 2.54 M10 x 51 86 130 76 130 51 0.7 2 2.375 365 1616 0.12 %x211 4.00 5.63 3.50 5.63 2.00 1.9 50 60.3 2517 7193 3.05 2 M10 x 63 102 143 89 143 51 0.9 211 2.875 365 2370 0.12 2 3/8 X 21/2 4.50 6.13 4.00 6.13 2.00 2.1 65 73.0 2517 10542 3.05 M10 x 63 114 156 102 156 51 1.0 3.000 365 2580 0.12 Vex 21/2 4.63 6.00 4.13 6.13 2.00 2.1 76.1 mm 76.1 2517 11476 3.05 2 M10 x 63 118 152 105 156 51 1.0 3 3.500 365 3512 0.12 3/e x 21/2 5.13 6.75 4.63 6.75 2.00 2.3 80 88.9 2517 15622 3.05 2 M10 x 63 130 171 117 171 j 51 1.0 4 4.500 365 5805 0.17 3/8 x 211 6.00 7.88 5.63 7.50 2.13 2.9 100 114.3 2517 25822 4.32 2 M10 x63 152 200 143 191 54 1.3 4.250 365 5175 0.17 3/8 x 211 5.63 7.38 5.38 7.38 2.13 3.1 108.0 mm 108.0 2517 23020 4.32 2 M10 x63 152 1.87 137 187 54 1.4 5 5.563 365 8870 0.17 1/2 x 3 7.25 9.25 6.75 9.13 { 2.25 5.0 125 141.3 2000 39456 4.32 2 M12 x 76 184 235 171 232 57 2.3 133.0 mm 5.250 365 7897 0.17 2 1/2 x 3 6.63 9.00 6.38 9.00 I 2.25 4.8 133.0 2517 35106 4.32 M12 x 76 168 229 162 229 57 2.2 139.7 mm 5.500 365 8667 0.17 2 11 x 3 6.88 9.25 6.75 9.13 2.25 4.9 139.7 2517 38529 4.32 M12 x 76 175 235 171 232 57 2.2 6.250 365 11192 0.17 11 x 3% 7.88 10.00 7.38 9.88 � 2.25 5.6 159.0 mm 159.0 2517 49753 4.32 2 M12 x 83 200 254 187 251 57 2.5 6.500 365 12105 0.17 Y2 x 31 8.00 10.25 7.75 10.13 2.25 6.0 165.1 mm 165.1 2517 53813 4.32 2 M12 x 83 203 260 197 257 57 2.7 6 6.625 365 12582 0.17 11 x 31/4 8.38 10.38 7.88 10.13 2.25 6.0 150 168.3 2000 44469 4.32 2 M12 x 83 213 264 200 257 57 2.7 8.500 365 20712 0.17 5/e x 4 10.63 13.25 10.25 10.13 2.63 11.4 216.0 mm 216.0 2517 55968 4.32 2 M16 x101 270 337 260 257 67 5.2 8 8.625 365 21326 0.17 5/a x 4 10.88 13.38 10.25 13.13 2.50 11.4 200 219.1 1620 94863 4.32 2 M16 x 101 276 340 260 333 64 5.2 10 10.750 300 27229 0.25 7/8 x 611 13.75 17.00 13.25 17.13 2.75 22.6 250 273.0 2068 121121 6.4 2 M22 x 165 349 432 337 435 70 10.3 12 12.750 300 38303 0.25 7/8 x 61/2 16.00 19.00 15.50 19.13 2.75 27.6 300 323.9 2068 170380 6.4 2 M22 x 165 406 483 394 486 70 12.5 3 Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.See the Listings/Approvals section of this publication for ratings on other pipe. 4 The allowable pipe separation dimension shown is for system layout purposes only.FireLock EZTM couplings are considered rigid connections and will not accommodate expansion or contraction of the piping system. NOTES • When assembling FireLock EZTM couplings onto end caps,take additional care to make certain the end cap is fully seated against the gasket end stop.For FireLock EZT^"Style 009N couplings,use FireLock No.006 end caps containing the"EZ"marking on the inside face or No.60 end caps containing the"QV EZ"marking on the inside face.Non-Victaulic end cap products shall not be used with Style 009N couplings.IMPORTANT:Gaskets intended for the Style 009 or Style 009V couplings cannot be used with the Style 009N coupling.There is no interchanging of gaskets or housings between coupling styles. • Use Of Flushseal Gaskets For Dry Pipe Systems FireLock EZTM couplings are supplied with FireLock EZT"Grade"E"Type A gaskets.These gaskets include an integral pipe stop,that once installed provides the similar benefits as a FlushSeal gasket for dry pipe systems.It should be noted that standard Victaulic Flush-SealTM gaskets are not compatible and cannot be used with the FireLock EZTM couplings. • • 10.64 7072 Rev L Updated 08/2017 ©2017 Victaulic Company.All rights reserved. VictaUlic,corn 3 �6tauI,ct viCtaulic,coni • 5.0 PERFORMANCE6 Listings/Approval The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Nominal Size cULus" FM Vds LPCB Sch.5 Sch. 10 Sch.40 Sch.5 Sch. 10 Sch.40 inches psi psi psi psi psi psi psi psi mm kPa kPa kPa kPa kPa kPa kPa kPa 1' 232 365 365 175 363 363 363 363 32 1600 2517 2517 1205 2502 2502 2500 2500 11 232 365 365 175 363 363 363 363 40 1600 2517 2517 1205 2502 2502 2500 2500 2 363 365 365 175 363 363 363 363 50 2502 2517 2517 1205 2502 2502 2500 2500 21/2 365 365 175 363 363 363 363 65 N/A 2517 2517 1205 2502 2502 2500 2500 76.1 mm N/A 3656 N/A N/A 3637 N/A 363 363 25176 25027 2500 2500 3 365 365 175 363 363 363 363 80 N/A 2517 2517 1205 2502 2502 2500 2500 4 365 365 175 363 363 363 363 100 N/A 2517 2517 1205 2502 2502 2500 2500 175 363 108.0 mm N/A N/A N/A 1205 2502 3632502 /A N/A 5N/A 290 365 N/A 363 363 232 N/A 125 2000 2517 2502 2502 1600 133.0 mm N/A N/A N/A N/A 256027 N/A N/A N/A 2908 232 139.7 mm N/A 20008 N/A N/A 2 0277 N/A 1600 N/A 159.0 mm N/A N/A N/A N/A 3637 027 N/A N/A N/A 363 165.1 mm N/A 20009 N/A N/A 2 0277 N/A N/A N/A 6 N/A 290 365 N/A 363 363 232 N/A 150 2000 2517 2502 2502 1600 216.0 mm N/A N/A N/A N/A 25027 N/A N/A N/A 8 N/A 290 365 N/A 363 363 232 N/A 200 2000 2517 2502 2502 1600 216.0 mm N/A N/A N/A N/A 256027 N/A N/A N/A 8 N/A 290 365 N/A 363 363 232 N/A 200 2000 2517 2502 2502 1600 10 N/A 300 300N/A 300 300 N/A N/A 250 2068 2068 2068 2068 12N/A 30010 300 N/A 250 300 N/A N/A 300 206810 2068 1724 2068 5 Listed/Approved for wet and dry pipe systems(>—40°F/-40°C)for continuous use in freezing conditions,use of Style 005H Coupling with Silicone Gasket is recommended. Please see the Victaulic [,for details concerning when supplemental lubrication is required. 6 cULus listed for DIN 2458 2.6 mm pipe wall. 7 FM approved for BS 1387 Medium 3.6 mm pipe wall. 8 cULus listed for EN 10220 4.0 mm pipe wall. 9 cULus listed for EN 10255 4.5 mm pipe wall. 10 cUL listed to 250 psi. 11 With optional stainless steel fasteners,cULus Listed to 175psi.The stainless steel fasteners have a marking designation of"316"on the end face of the bolt. • • 10.64 7072 Rev L Updated 08/2017 ©2017 Victaulic Company.All rights reserved. victaulic.com 4 ✓ctaulic victaulic.com • 5.1 PERFORMANCE2 Listings/Approval Speciality Pipe Pipe Size Pressure Rating 1 Pipe Size Pressure Rating Pipe Size Pressure Rating ll cULus FM cULus FM cULus I FM ' inches psi psi inches psi psi inches psi psi kPa kPa kPa kPa kPa kPa BLT 11/4-2 300 365 EZT 11/4_2 300 365 MT 11/4-2 300 365 2068 2517 2068 2517 2068 2517 DF 11/4-4 300 � 365 FF 11/4-4 300 365 MLT 11/4-2 N/A 365 2068 2517 2068 2517 2517 DT 11/4-2 300 365 FLF 11/4-4 N/A 365 ST 11/4-2 N/A 365 2068 2517 2517 2517 EF 11/4-4 175 175 FLT 11/4-2 N/A 365 STF 1Y4-4 N/A 365 1206 1206 2517 2517 EL 11/4-2 300 365 FLTL 11/4-2 N/A 365 TF 2Ya-4 N/A 365 2068 2517 2517 2517 ET40 1 1/a 2 300 365 GL 1 Ya 2 300 365 WLS 1 1/a 2 300 365 2068 2517 2068 2517 2068 2517 EZF I 3-4 300 365 1 1/a 4 300 365 WST 1 1/a 2 N/A 365 2068 2517 2068 2517 2517 MF - 175 175 300 365 6 1_- 1205 1205 XL 11/a 2 2068 2517 NOTES • BLT=BLT steel pipe manufactured by Allied Tube&Conduit Corp. • DF=DYNA-FLOW steel pipe manufactured by Allied Tube&Conduit Corp. • DT=DYNA-FLOW steel pipe manufactured by Allied Tube&Conduit Corp. • EF=EDDY FLOW steel pipe manufactured by Bull Moose Tube Co. • EL=EDDYLITE steel pipe manufactured by Bull Moose Tube Co. • ET40=Eddythread 40 steel pipe manufactured by Bull Moose Tube Co. • EZF=EZ-Flow steel pipe manufactured by Northwest Pipe Co. • EZT=EZ-Thread steel pipe manufactured by Youngstown Tube Co. • FF=Fire-Flo steel pipe manufactured by Youngstown Tube Co. • FLF=Fire-Line Flow steel pipe manufactured by Western International Forest Products Inc. • FLT=Fire-Line Threadable steel pipe manufactured by Western International Forest Products Inc. • FLTL=Fire-Line Threadable Light steel pipe manufactured by Western International Forest Products Inc. • GL=GL steel pipe manufactured by Wheatland Tube Co. • MF=Mega-Flow steel pipe manufactured by Wheatland Tube Co. • MT=Mega-Thread steel pipe manufactured by Wheatland Tube Co. • MLT=MLT steel pipe manufactured by Wheatland Tube Co • ST=STD wall pipe in accordance with ASTM A53. • STF=Steady Flow steel pipe manufactured by AMS Tube Corp. • TF=Tex-Flow steel pipe manufactured by Tex-Tube Co. • WLS=WLS steel pipe manufactured by Wheatland Tube Co. • WST=WST steel pipe manufactured by Wheatland Tube Company. • XL=XL steel pipe manufactured by Allied Tube&Conduit Corp. • • 10.64 7072 Rev L Updated 08/2017 ®2017 Victaulic Company.All rights reserved. victaulic.com 5 ✓ctaulia rox. victaulic.com 6.0 NOTIFICATIONS Not applicable—contact Victaulic with any questions. 7.0 REFERENCE MATERIALS 5.01:Sea ction Guide 009N/009H:Installation Instructions FireLock EZTM Rigid Coupling • • User Responsibility for Product Selection and Suitability Note Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications.All products Victaulic products for a particular end-use application,in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions. standards and project specifications,and the applicable building codes and related Victaulic reserves the right to change product specifications,designs and standard regulations as well as Victaulic performance,maintenance,safety,and warning equipment without notice and without incurring obligations. instructions.Nothing in this or any other document,nor any verbal recommendation, Installation advice,or opinion from any Victaulic employee,shall be deemed to alter,vary,supersede, Reference should always be made to the Victaulic installation handbook or installation or waive any provision of Victaulic Company's standard conditions of sale,installation instructions of the product you are installing.Handbooks are included with each shipment guide,or this disclaimer. of Victaulic products,providing complete installation and assembly data,and are available Intellectual Property Rights in PDF format on our website at www.victaulic.com. No statement contained herein concerning a possible or suggested use of any material, Warranty product,service,or design is intended,or should be constructed,to grant any license Refer to the Warranty section of the current Price List or contact Victaulic for details. under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design,or as a recommendation for the use of such Trademarks material,product,service,or design in the infringement of any patent or other intellectual Victaulic and all other Victaulic marks are the trademarks or registered trademarks of property right.The terms"Patented"or"Patent Pending"refer to design or utility patents Victaulic Company,and/or its affiliated entities,in the U.S.and/or other countries. or patent applications for articles and/or methods of use in the United States and/or other countries. • • 10.64 7072 Rev L Updated 08/2017 C 2017 Victaulic Company.All rights reserved. victaulic.com 6 4tauiicr N :•L TEEL PIPE- 1-411VCUT PRODUC 11,.02 lechanical-T® Bolted Branch Outlets VdS PCB VNIIPO SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLES 920 AND 92ON • Victaulic Mechanical-T®Outlet provides a direct branch connection at any location a hole can be cut in pipe.The hole is cut oversize to receive a"holefinder" locating collar which secures the outlet in position permanently.A pressure responsive gasket seals on the pipe O.D. we' 1111/11:1 Cross-type connections can be achieved by utilizing two upper housings of the same style and size,with the same or differing branch size connections. NOTE:Style 920 and Style 920N housings cannot be mated to each other to achieve a cross connection. Style 920 and Style 92ON Mechanical-T outlets are available with grooved or female threaded STYLES 920 AND 920N STYLE 920 CROSS outlet.Specify choice on order.Units are supplied painted with plated bolts.Galvanized hous- PATENTED ings are available,supplied with plated bolts. All sizes of Style 920 and 92ON are rated at 500 psi/3450kPa working pressure on Schedule 10 and 40 carbon steel pipe.They may also be used on high density polyethylene or poly- butylene(HDPE)pipe. Pressure ratings on HDPE are dependent on the pipe rating.Contact Victaulic for ratings on other pipe.Style 920 and 92ON are not recommended for use on PVC plastic pipe. Standard piping practices dictate that the Mechanical-T Styles 920 and 92ON must be installed so that the main and branch connections are a true 90°angle when permanently attached to the pipeline surface. Additionally,the Vic-Tap Il®hole cutting tool,which allows for hole cutting capabilities on pressurized systems,utilizes the Style 920 Mechanical-T in conjunction with the Series 726 Vic-Ball Valve to create the Style 931 Vic-Tap II Mechanical-T unit.See page 8 for further information. MATERIAL SPECIFICATIONS Housing/Coating:Ductile iron conforming to ASTM A-536,grade 65-45-12,with orange enamel coating. Ductile iron conforming to ASTM A-395,grade 65-45-15,is available upon special request. • Optional:Hot dipped galvanized Gasket: (Specify choice*) • Grade"E"EPDM EPDM(Green color code).Temperature range—30°F to+230°F/-34°C to+110°C. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services. UL Classified in accordance with ANSI/NSF 61 for cold+86°F/+30°C and hot+180°F/+82°C. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade"T"nitrile Nitrile(Orange color code).Temperature range—20°F to+180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range. Not recommended for hot water services over+150°F/+66°C or for hot dry air over+140°F/+60°C. *Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date wwAuuc IS A REGISTERED �Ctaulicr com VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2017 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV N 1.1.02.1 CARBON STEEL PIPE - HOLE CUT PRODUCTS 11.02 Mechanical-T® Bolted Branch Outlets STYLES 920 AND 920N DIMENSIONS 1 Style Max.Work Approx. Size No. Pressure@ Dimensions Weight Each Run x Branch Hole " 1 Nominal Size 920 Diameter T" - Inches or psi +0.13 Inches Inches: cies Inches Inches Ilia i3. < Y > t mm 920N kPa -0.00 mm mm , 'Inm rem mm kg l Z >1 ! 2 x Y2(a)o 920N 500 1.50 2.00 2.53 1.61 5.35 2.75 3.1 � 50 15 3450 38.1 51 64 41 136 70 1.5 Me �� mie v 3/4(a)0 500 1.50 1.97 2.53 1.61 535 2.75 3.1 20 3450 38.1 50 64 41 136 70 1.5 4,01 ‘° 1(a)0 920N 500 1.50 1.85 2.53 1.61 5.35 2.75 3.0 - y • 25 3450 38.1 47 64 41 136 70 1.4 11/4 (a)t° 920N 500 1.75 2.05 2.75 3.00 1.61 5.35 3.00 3.5 3.2 GROOVED OUTLET 32 3450 44.5 52 70 76 41 136 76 1.7 1.5 1/(a)to 920N 500 1.75 2.03 2,75 3.12 1.61 5.35 3.25 3.6 3.2 40 3450 44.5 52 70 79 41 136 83 1.7 1.5 a Y �Z N 2'/z x %z(a)§n 920N 500 1.50 2.21 2.74 _ 1.82 5.64 2.75 3.0 _ 65 15 3450 38.1 56 70 46 143 70 1.4 3/4(a)§0 920N 500 1.50 2.18 2.74 _ 1.82 5.64 2.75 3.0 20 3450 381 55 70 46 143 70 1.4 V 'tit0tit' `' l 1(a)§o 500 1.50 2.06 2.74 - 1.82 5.64 2.75 2.9 01 25 920N 3450 381 52 70 46 143 70 1.4 �1f� 1 Y4 t(a)n.. 920N 500 1.75 2.30 3.00 3.25 1.82 6.29 3.00 3.5 3.2 y � 32 3450 44 5 58 76 83 46 160 76 1.7 1.5 11/2 t(a)o g20N 500 2.00 2.28 3 00 3.25 1.82 6.26 3.25 3.6 3.3 FEMALE THREADED OUTLET 40 3450 50.8 58 76 83 46 159 83 1.7 1.6 1/2(a) 300 1.50 2.22 2.75 225 6.46 3.18 3.9 - 76.1 x 15 920N -2065 38.1 56 70 57 164 81 1.8 • Provides a direct branch connection ata(a) 920N 300 150 2.19 2.75 2.25 6.46 3.18 3.9 any location where a hole can be cut 20 2065 38.1 56 70 - 57 164 81 1.8 in the pipe 1(a) 920N 300 1.50 2.07 2.75 _ 2.25 6.46 3.18 3.8 25 2065 38.1 53 70 57 164 81 1.7 • A pressure responsive gasket provides 1'/4(a)0 920N 500 1.75 2.30 3.00 3.31 1.92 6.29 3.00 3.5 32 the seal 32 3450 44.5 58 76 84 49 160 76 1.6 1.5 1/z(a)° 920N 500 2.00 2.28 3.00 3.31 1.92 6.29 3.25 3.5 3.3 • Request Publication 11.03 for 40 3450 508 58 76 84 49 160 83 1.6 1.5 Mechanical-T cross assemblies 3 x '/(a)° 920N 500 1.50 2.52 3.05 _ 2.28 6.15 2.75 3.4 80 15 3450 38.1 64 78 58 156 70 1.6 • Pressure rated up to 500 psi/3450 kPa 3r(a)0 920N 500 150 2.49 3.05 _ 2.28 6.15 2.75 3.4 - on steel pipe;also available for use 20 3450 38.1 63 78 58 156 70 1.6 with HDPE pipe 1(a) 920N 500 1.50 2.38 3.06 _ 2.28 6.15 2.75 33 25 3450 38.1 61 78 58 156 70 1.6 • Sizes from 2 x 1/2"/50 x 15 mm 1'/4(a)to 920N 500 1.75 2.55 3.25 3.56 2.28 6.15 3.00 3.8 3.7 through 8 x 47200 x 100 mm 32(b) 3450 44.5 65 83 90 58 156 76 1.8 1.8 1'/z(a)to 920N 500 2.00 2.78 3.50 3.56 2.28 6.15 3.25 4.1 3.8 40(b) 3450 50.8 71 89 90 58 156 83 1.9 1.8 2(a)a 920N 500 2.50 2.75 3.50 3.56 2.28 6.75 3.88 4.9 4.6 50 3450 63.5 70 89 90 58 172 99 2.3 2.1 3h x 2 ' 920N 500 2.50 . -3.00 - 3.75 - 244 • 6.72- 3.88 I - 3.8 90 50 3450 63.5 76 95 62 I/I 99 1B IMPORTANT NOTES: TABLE CONTINUED ON PG.3 Style 920 and Style 920N housings cannot be **Center of run to engaged pipe end,female threaded outlet only(dimensions approximate). mated to one another t Available with grooved or female threaded outlet.Specify choice on order. to achieve cross connections. # Center of run to end of fitting. # Female threaded outlets are available to NPT and BSPT specifications. @ See page 7 for Fire Protection approvals and pressure ratings. (a)British Standard female pipe threaded outlet is available as listed.Specify"BSPT"clearly on order. (b)For 76.1 mm threaded outlet,specify 21/2"BSPT clearly on order. §Vds approved for fire protection services ❑LPCB approved for fire protection services 0 Approved for use in China by Tianjin Approvals Company. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2017 VICTAULIC COMPANY.ALL RIGHTS RESERVED. jCtEla.dia. 11.02 2 REV_N I a a• �] CARBON STEEL PIPE - HOLE CUT PRODUCTS 11.02 't,llechanical-T® Bolted Branch Outlets STYLES 920 AND 920N DIMENSIONS Style Max.Work Approx. Size No. Pressure@ Dimensions Weight Each Run x Branch : .,,.....----0`-'144 V##'1"477"- e.timit, w_,..::. Nominal Size 920 Diameter T*' Thd. Grv. W P Z Thd. Grv. Inches or psi +0.13 Inches Inches Inches Inches Inches Inches Lbs. Lbs. V k Z > mm 920N kPa -0.00 mm mm mm mm mm mm kg kg ^ TABLE CONTINUED FROM PAGE 2 .....m.:611 f 4 /z(a)x 500 1.50 3.03 3.56 _ 2.69 7.01 2.75 3.7 VI 100 x 15 920N 3450 38.1 77 90 68 178 70 1.8 MAll.J %(a)D 920N 500 1.50 3.00 3.56 - 2.69 701 2.75 3.7 01 20 3450 38.1 76 90 68 178 70 1.8 L11. 1 y I^IL 1(a)D ! 500 1.50 2.88 3.56 2.69 7.01 2.75 3.6 1 25 920N 3450 38.1 73 90 68 178 70 1.8 GROOVED OUTLET 11/4(a)tx 920N 500 1.75 3.08 3.78 4.00 2.69 7.01 3.00 4.0 3.6 32(b) j 3450 44.5 78 96 102 68 178 76 1.9 1.8 11/2(a)to920N 500 2.00 3.28 4.00 4.00 2.69 7.01 3.25 4.2 3.9 40(b) 3450 50.8 83 102 102 68 178 83 2.0 1.9 Y > 7Z >1 2(a)to 920N 500 2.50 3.25 4.00 4.00 2.69 7.01 3.88 5.0 4.6 r .111 50 3450 63.5 83 102 102 68 178 99 2.3 2.1 V - _ T 2%z(a)t 920 500 2.75 2.88 4.00 4.00 2.69 7.34 4.63 5.86 5.0 r�r r�i' T r11 65 3450 69.9 73 102 102 68 186 118 2.6 2.3 > 500 2.75 2.88 _ 4.00 2.69 7.34 4.63 - 64 ' I 76.1mm 920 3450 69.9 73 102 68 186 118 29 ��� 1-. 3(a)t 500 3.50 3.31 4.50 4.12 2.69 7,73 5.12 8.4 6.4 80 920 3450 88.9 84 114 105 68 196 130 3.8 2 9 FEMALE THREADED OUTLET --- 1'/a(a)D 500 1.75 3.08 3.78 _ 2.63 7.64 3.05 5D _ 108.0 x 32 920N 3450 44.5 78 96 67 194 78 2.3 1 1/2(a)u500 2.00 3.28 4.00 - 2.63 7.64 3.25 5.0 • Provides a direct branch connection at 40 3450 50.8 83 102 67 194 83 2.3 - any location where a hole can be cut 2(a) 920N 500 2.50 3.25 4.00 2.63 7.64 4.00 4.0 in the pipe 50 3450 63.5 83 102 - 67 194 102 1.9 76.1 mm 920 500 2.75 2.88 4.00 4.00 2.63 7.64 4.29 8.0 7.8 • A pressure responsive gasket provides 3450 69.9 73 102 102 67 194 109 3.6 3.5 the seal 3(a) 920 500 3.50 3.31 4.50 4.50 2.63 7.63 4.88 6.8 6.5 80 3450 88.9 84 114 114 67 194 124 3.1 3.0 • Request Publication 11.03 for 5 11/2(a)t I 500 2.00 4.03 4.75 4.75 3.16 9.70 3.69 74 76 Mechanical-T cross assemblies 125 X '40 920 3450 50.8 102 121 121 80 246 94 3.4 3.4 2(a)t 500 2.50 4.00 4.75 4.75 3.16 9.70 4.38 8.2 8.0 • Pressure rated up to 500 psi/3450 kPa 50 , 920 3450 63.5 102 121 121 80 246 111 3.7 3.6 on steel pipe; also available for use 2'/z(a)t 920 500 2.75 3.63 4.75 4.75 3.16 9.70 4.63 8.3 7.9 with HDPE pipe 65 i 3450 69.9 92 121 121 80 246 118 3.8 3.6 76.1 mm D 920 500 2.75 3.75 _ 4.75 3.16 9.70 4.63 _ 8.0 • Sizes from 2 x W/50 x 15mm J 3450 69.9 95 121 80 246 118 3.6 through 8 x 47200 x 100mm 3(a)t i 920 500 350 3.81 5.00 4.63 3.16 9.70 5.31 8.4 8.8 80 i 3450 88.9 97 127 118 80 246 135 3.8 4.0 2 500 2.50 3.75 4.50 _ 3.17 8.00 3.88 8,0 133.0 x 50 920N 3450 63.5 95 114 81 203 99 3.6 _ 3 500 3.50 3.81 5.00 3.00 9.46 5.31 8.0 _ ' 80 920 3450 88.9 97 127 76 240 135 3.6 TABLE CONTINUED ON PG.4 IMPORTANT NOTES: **Center of run to engaged pipe end,female threaded outlet only(dimensions approximate). Style 920 and Style 920N housings cannot be t Available with grooved or female threaded outlet.Specify choice on order. mated to one another # Center of run to end of fitting. to achieve cross connections. # Female threaded outlets are available to NPT and BSPT specifications. @ See page 7 for Fire Protection approvals and pressure ratings. (a)British Standard female pipe threaded outlet is available as listed.Specify"BSPT"clearly on order. (b)For 76.1 mm threaded outlet,specify 21/2"BSPT clearly on order. §Vds approved for fire protection services a LPCB approved for fire protection services 0 Approved for use in China by Tianjin Approvals Company. www.victaulic.com VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.C 2017 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICt.'sluI1e REV N 11.023 r , CARBON STEEL PIPE- HOLE CUT PRODUCTS 11.02 • Mechanical-T® Bolted Branch Outlets STYLES 920 AND 920N DIMENSIONS Style Max.Work Approx. Size No. Pressure@ Dimensions Weight Each Hole V?II Vi 920 Diameter T"' Thd. Grv. W Z' `Inches or psi +0.13 Inches Inches Inches Inches Inches Inches W. Lbs' " 4 Y > < Z 1 mm 920N kPa -0,00 elm mm mm mm mm mm kg kg - t a TABLE CONTINUED FROM PAGE 3 i�� 1 r/t , 500 2.00 3.78 4.50 - 3.30 8.23 3.25 7.0 V 139.7 x - 40 920N 3450 50.8 96 114 84 209 83 3.2 min' "" ant 1 rr�l 2 t 920N 500 2.50 3.75 4.50 - 3.30 8.23 3.88 9.0 ,D. 50 3450 635 95 114 84 209 99 4.1 y I�/I 6 a(a) 500 1.75 4.43 5.13 5.13 3.79 9.15 3.25 5.1 4.8 I-L 150 x 32(b) 920N 3450 44.5 112 130 130 96 232 83 2.3 2.2 GROOVED OUTLET 11/2(a)to 920N 500 2.00 4.40 5.13 5.13 3.79 9.15 3.25 5.4 5.1 40(b) 3450 50.8 112 130 130 96 232 83 2.4 2.3 2(a)to ' 920N 500 2.50 4.38 5.13 5.13 3.79 9.15 3.88 6.0 5.6 50 3450 63.5 111 130 130 96 232 99 2.7 2.5 Y > 7z7 2 Yz 500 2.75 4.01 5.13 5.12 3.69 10.51 4.63 8.3 7.6 } 4 PR 65 920 3450 69.9 110 130 130 94 267 118 3.8 34 VI T 76.1 mm d 920 500 2.7569.9 4.150 - 13221 3.69 10.51 118 _ 8.4 ail ���` T Ir�11 3450 105 94 267 118 3.8 F> �� 3(a)t 920 500 3.50 4.31 5.50 5.13 3.69 10.51 5.31 99 8.4 .1 I 80 3450 88.9 110 140 130 94 267 135 4.5 3.8 V u I. 4(a)to 500 4.50 3.81 5.75 5.38 3.69 10.51 6.25 10.1 10.1 100 920 3450 114.3 97 146 137 94 267 159 4.6 4.6 FEMALE THREADED OUTLET 1 1/2(a) 500 2.00 4.41 5.13 _ 3.63 9.40 3.25 7.8 159.0 x 40 920N _ 3450 50.8 112 130 92 239 83 3.5 2(a) 920N 500 2.50 4.38 5.13 _ 3.63 9.40 3.88 8.0 - • Provides a direct branch connection at 50 3450 63.5 111 130 92 239 99 3.6 any location where a hole can be cut 76.1 mm 920 500 2.75 4.38 5.50 5.13 3.63 9.40 4.63 9.5 9.5 in the pipe 3450 69.9 111 140 130 92 239 118 4.3 4.3 3 500 3.50 4.31 5.50 5.13 3.63 9.40 5.31 8.1 14.0 • A pressure responsive gasket provides 80 920 3450 88.9 110 140 130 92 239 135 3.7 6.4 the seal 108.0 mm 920 500 4.50 4.45 5.38 3.63 9.40 6.12 _ 10.0 3450 114.3 113 137 92 239 155 4.5 • Request Publication 11.03 for 4 500 4.50 3.81 5.75 3.63 9.40 6.25 18.0 Mechanical-T cross assemblies 100 920 3450 114.3 96.80 146 - 92 239 159 8.2 - TABLE CONTINUED ON PG.5 • Pressure rated up to 500 psi/3450 kPa **Center of run to engaged pipe end,female threaded outlet only(dimensions approximate). on steel pipe;also available for use t Available with grooved or female threaded outlet.Specify choice on order. with HDPE pipe # Center of run to end of fitting. • Sizes from 2 x 1/2°150 x 15 mm # Female threaded outlets are available to NPT and BSPT specifications. through 8 x 4°/200 x 100 mm @ See page 7 for Fire Protection approvals and pressure ratings. (a)British Standard female pipe threaded outlet is available as listed.Specify"BSPT"clearly on order. (b)For 76.1 mm threaded outlet,specify 21"BSPT clearly on order. §Vds approved for fire protection services - v LPCB approved for fire-protection services IMPORTANT NOTES: 0 Approved for use in China by Tianjin Approvals Company. Style 920 and Style 920N housings cannot be mated to one another to achieve cross connections. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2017 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ictaulie 11.02_4 REV_N CARBON STEEL PIPE -HOLE CUT PRODUCTS 11.02 • lechanical-T® Bolted Branch Outlets STYLES 920 AND 920N DIMENSIONS Style Max.Work Approx. Size No. Pressure@ Dimensions Weight Each Run x Bran"""""-''''''''''''Able V 5 8 V t Female Nominal Size 920 Diameter T" Thd. Grv. W Y Z Thd. Grv. Inches or psi +0.13 Inches Inches Inches Inches Inches Inches Lbs. Lbs. Y >1 tt Z > mm 920N kPa -0.00 rem mm mm mm mm mini kg kg MENI '' TABLE CONTINUED FROM PAGE 4 ... L 1 1 500 1.50 3.88 4.56 3.79 9.34 2.75 8.0 165.1 x V � � 920N tit �� ml 1 I ffil I 25 1 1/0 920N 5003450 1.7538 4.4399 5.13116 - - 3.7996 9.34237 37.205 8.43.6 -- 32 3450 44.5 113 130 96 237 83 3.8 'ILIYz(a)to 920N 500 2.00 4.41 5.13 5.13 3.79 9.34 3.25 8.4 5.4 40 i 3450 50.8 112 130 130 96 237 83 3.8 2.4 GROOVED OUTLET 2(a)t 1920N 500 2.50 4.38 5.13 5.13 3.79 9.34 3.88 8.5 6.0 50 3450 63.5 111 130 130 96 237 99 3.9 2.7 76.1 mm% 920 500 2.75 4.01 5.13 5.21 3.63 10.51 4.63 8.6 7.6 Y > �Z > 3450 69.9 110 130 132 92 267 118 3.9 3.4 3(a)t e i 920 500 3.50 4.31 5.50 5.13 3.63 10.51 5.31 10.2 8.4 80 j 3450 88.9 110 140 130 92 267 135 4.6 3.8 V = _r PI T 4(a)to 1 500 4.50 3.81 5.75 5.38 3.63 10.51 6.25 10.5 8.4 iA�� i•i, T 100 920 3450 114.3 97 146 137 92 267 159 4.8 3.8 > op .„4_ . 82(a)t500 2.75 5.44 6.19 6.25 4.81 12.42 4.50 11.6 11.6 _ I I 200 x 50 i 920 3450 69.9 138 157 159 122 316 114 5.3 5.3 +--L 2 h(a)t500 2.75 5.07 6.19 6.19 4.81 12.42 4.50 11.6 11.6 65 920 3450 69.9 129 157 157 122 316 114 5.3 5.3 FEMALE THREADED OUTLET --- 76.1 mm d 920 500 275 5.25 - 6.25 4.81 12.42 4.56 _ 11.6 3450 69.9 133 159 122 316 116 5.3 3(a)to 500 3.50 5.31 6.50 6.50 4.81 12.42 5.31 12.6 11.6 • Provides a direct branch connection at 80 920 3450 88.9 135 165 165 122 316 135 5.7 5.3 any location where a hole can be cut 4(a)to 920 500 4.50 4.81 6.75 6.38 4.81 12.42 6.25 15.3 12.5 in the pipe 100 3450 114.3 122 171 162 122 316 159 6.9 5.7 **Center of run to engaged pipe end,female threaded outlet only(dimensions approximate). • A pressure responsive gasket provides t Available with grooved or female threaded outlet.Specify choice on order. the seal * Center of run to end of fitting. • Request Publication 11.03 for # Female threaded outlets are available to NPT and BSPT specifications. Mechanical-T cross assemblies @ See page 7 for Fire Protection approvals and pressure ratings. • Pressure rated up to 500 psi/3450 kPa (a)British Standard female pipe threaded outlet is available as listed.Specify"BSPT"clearly on order. on steel pipe;also available for use (b)For 76.1 mm threaded outlet,specify 21/2"BSPT clearly on order, with HDPE pipe §Vds approved for fire protection services ❑LPCB approved for fire protection services • Sizes from 2 x 1/2750 x 15 mm 0 Approved for use in China by Tianjin Approvals Company. through 8 x 47200 x 100mm IMPORTANT NOTES: Style 920 and Style 920N housings cannot be mated to each other to achieve cross connections. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2017 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ictaiulilc REV N 11.02 5 1 , CARBON STEEL PIPE- HOLE CUT PRODUCTS 11.02.0 2 , Mechanical-T® Bolted Branch Outlets STYLES 920 AND 920N FLOW DATA Flow test data has shown that the total head loss between point(1)and(2)for the Style 920,920N and 929 Mechanical-T®fittings can best be expressed in terms of the pressure difference across the inlet and branch.The pressure difference can be obtained from the relationship below. 0 Cv and Kv Values Values for flow of water at+60°F/+16°C are shown in the table below. Formulas for Cv/Kv Values: i 4P = Qz Where: Op = QzWhere: 0 /�', zQ =C x4P Q=Flow(GPM) Q=Flow(m3/hr)' AP=Pressure Drop(psi) C K°2 pP=Pressure Drop(Bar) �� =Flow Coefficient Q = K„ x DP Kv=Flow Coefficient Exaggerated for clarity Equivalent Length of Outlet Size Schedule 40 Carbon Steel Pipe (per UL 213,Sec.16) OUTLET SIZE (C=120)t FT G,/K,Values ',TUAL 0.0. /inR0OVED"k GROOVED THREADED 0.840 11 I' 21.3 - - 94 1.050 16 [0 26.7 13.7 1 1.315 21 25 33.7 3.. 8 1.8 1 4 1.660 5 h 6 50 48 32 42.7 42.9 41.1 1 Yz 1.900 53 53 40 98.3 11 11 45.4 45.4 2 2.375 112 104 50 603 9 10/z 96 89.1 2 Yz 2.875 20 12/z 119 150 65 73.0 102 128.5 3.000161 76.1 mm 76.1 16* 138.1 3 3.500 14 15 1/2249 237 8088.9 213.4 203.1 4 I 4.500 20 22 421 401 100 114.3 360.8 343.6 t Hazen-Williams coefficient of friction is 120. *Pipe with a wall thickness of 0.165in./4.2mm. • 1"FireLock"Innovative Groove System(IGS)outlet www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2017 VICTAULIC COMPANY.ALL RIGHTS RESERVED. jctaulicP 11.02 6 REV_N t F r r CARBON STEEL PIPE- HOLE CUT PRODUCTS 1 1.02 Mechanical-T® Bolted Branch Outlets STYLES 920 AND 920N FIRE PROTECTION APPROVALS AND PRESSURE RATINGS The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approvals agencies.Contact Victaulic for performance on other pipe and the latest listings and approvals. Approval Agency Run Size Outlet Size Pipe Rated Working Pressures—psi/kPa Nominal: q; Outside Vds Size ,: Diameter Inches/m' "Inches/mm . nim Schedule UL ULC FM LPCB (Style 920) (Style 920N) 21/2-6 2.875-6.625 All 10,40 400 400 400 290 232 362 65-150 73.0-168.3 2755 2755 2755 1999 1599 2496 21/2-4 2.875-4.500All OF 300 300 300 290 232 362 65-100 73.0-114.3 2065 2065 2065 1999 1599 2496 21/2-4 2.875-4.500 All SF 300 300 300 290 232 362 65-100 73.0-114.3 2065 2065 2065 1999 1599 2496 6 6.625 3,4 10 300 300 250 290 232 362 150 168.3 2065 2065 1724 1999 1599 2496 6 6.625 300 300 300 290 232 362 150 168.3 3,4 30,40 2065 2065 2065 1999 1599 2496 8 8.625 21/2 10,40 400 _ — _ 145 — 200 219.1 2755 1000 8 8.625 3,4 10 300 — 250 — 145 200 219.1 2065 1724 1000 8 8.625 3,4 30,40 300 — 300 — 145 _ 200 219.1 2065 2065 1000 NOTES: 10 refers to Listed/Approved Schedule 10 steel sprinkler pipe. 40 refers to Listed/Approved Schedule 40 steel sprinkler pipe. DF refers to Listed/Approved Dyna-Flow steel sprinkler pipe manufactured by American Tube Company. SF refers to Listed/Approved Super-Flo steel sprinkler pipe manufactured by Allied Tube and Conduit Corporation. VIC-TAP II HOLE CUTTING TOOL FOR The Vic-Tap II hole cutting tool is designed for use with the Style 931 Vic-Tap II Mechanical-T unit, 4-8'/100-200MM CARBON STEEL PIPE which is a combination of the Style 920 Mechanical-T and Series 726 Vic-Ball Valve.The Vic-Tap II is capable of tapping into carbon steel pipe systems under pressures up to 500 psi/3450kPa. The Style 931 Vic-Tap II Mechanical-T unit is a full port ball valve which can be mounted on 4"/100mm, 5"/125mm,67150mm and 8"/200 mm diameter pipe.The Style 931 comes with a 21765mm grooved outlet. t .. -, The drill motor is an electric motor with ground fault circuit interrupter(GFCI)in accordance with j safety codes. -- For more information,refer to publication 24.01. 111 ke • www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.W 2017 VICTAULIC COMPANY.ALL RIGHTS RESERVED. iICt8UI.e REV N 11.02..7 1 1 CARBON STEEL PI,' - .1 'RODUCT 1 1.02 Mechanf (1' Bolted Branch Outlets STYLES 920 AND 920N INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. For complete contact information,visit www.victaulic.com 11.02 1480 REV N UPDATED 12/2017 ict auI1e. VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.E 2017 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 11.02 L Victaullic® FireLockTM Fittings ✓ctaullu 10.03 • xizyf 1.0 PRODUCT DESCRIPTION Available Sizes • 11/4—8'/DN32— DN200 Maximum Working Pressure • Pressure ratings for Victaulic FireLockTM Fittings conform to the ratings of Victaulic FireLock EZTM Style 009N couplings (refer to publication 10.64 for more information). Application • FireLockTM fittings are designed for use exclusively with Victaulic couplings that have been Listed or Approved for Fire Protection Services. Use of other couplings or flange adapters may result in bolt pad interference. • Connects pipe, provides change in direction and adapts sizes or components Pipe Materials • Carbon steel 2.0 CERTIFICATION/LISTINGS LISTED ® LPCB vas C E EN 10311 Regulation(EU) No.305/2011 3.0 SPECIFICATIONS - MATERIAL Fitting: Ductile iron conforming to ASTM A536, Grade 65-45-12. Fitting Coating: Li Orange enamel. [1 R• ed enamel in Europe, Middle East, Africa, and India. LI O• ptional: Hot dipped galvanized. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION,MAINTENANCE OR SUPPORT. • • System No, Location Spec Section Paragraph Submitted By Date Approved Date victaulic.cortr • 10.03 1539 Rev N Updated 09/2017 ©2017 Victaulic Company.All rights reserved. 1 ✓ctaulic° victaulic.com . . 4.0 DIMENSIONS hctoE.I C i I �toE u CtoE o El ti5 (i o0 oe.�- o Co Eo � J tocr to4_ 1 1 a o I i No.001 No.003 No.002 No.006 No.001 No.003 No.002 No.006 90°Elbow 45°Elbow Straight Tee Cap Actual Approximate Approximate Approximate Approximate Nominal Outside Weight Weight Weight Weight Size Diameter C to E Each C to E Each C to E Each T Each inches inches inches lb inches lb inches lb inches lb DN mm mm kg mm kg mm kg mm kg 11/4 1.660 - - - - - - 0.82 0.3 0N32 42.4 - - - - - - 21 0.1 11/2 1.900 - - - - - - 0.82 0.4 DN40 48.3 - - - - - - 21 0.2 2 2.375 2.75 1.7 2.00 1.8 2.75 2.4 0.88 0.6 DN50 60.3 70 0.8 51 0.8 70 1.1 22 0.3 2 Y 2.875 3.00 3.1 2.25 2.2 3.00 3.6 0.88 1.0 73.0 76 1.4 57 1.0 76 1.6 22 0.5 3.000 3.00 3.30 2.25 2.4 3.00 3.8 _ _ DN65 76.1 76 1.5 57 1.1 76 1.7 3 3.500 3.38 4.0 2.50 3.1 3.38 5.3 0.88 1.2 DN80 88.9 86 1.8 64 1.4 86 2.4 22 0.5 4.250 4.00 5.7 3.00 5.1 4.00 7.5 - 108.0 102 2.6 76 2.3 102 3.4 - 4 4.500 4.00 6.7 3.00 5.6 4.00 8.7 1.00 2.4 DN100 114.3 102 3.0 76 2.5 102 3.9 25 1.1 5 5.563 4.88 12.6 3.25 8.3 4.88 15.7 1.00 4.1 141.3 124 5.7 83 3.8 124 7.1 25 1.9 5.500 4.88 12.4 3.25 8.2 4.88 15.4 DN125 139.7 124 5.6 82.6 3.7 124 6.9 6.250 5.50 12.6 3.50 9.2 5.50 17.9 - - 158.8 140 5.7 89 4.2 140 8.0 6 6.625 5.50 18.3 3.50 11.7 5.50 22.7 1.00 5.9 DN150 168.3 140 8.3 89 5.3 140 10.3 25 2.7 6.500 5.43 17.6 3.50 11.4 5.50 22.0 165.1 140 7.9 89 5.2 140 9.9 8 8.625 6.81 25.5 4.25 20.4 6.94 38.7 1.13 12.7 DN200 219.1 173 11.6 108 9.3 176 17.6 29 5.8 8.515 6.81 23.1 - - 6.94 33.6 - - 216.3 173 10.5 - - 176 15.2 - - • • 10.03 1539 Rev N Updated 09/2017 ©2017 Victaulic Company.All rights reserved. victaulic.com 2 ✓ctaulic' victaullc.corn • 5.0 PERFORMANCE • Flow Data Size Frictional Resistance Equivalent of Straight Pipe' No.002 Actual Elbows Straight Tee Nominal Outside No.001 No.003 Size Diameter 90°Elbow 45°Elbow Branch Run inches inches feet feet feet feet DN mm meters meters meters meters 1Y4 1.660 - - - - DN32 42.4 - - - - 1 1/2 1.900 - - - - DN40 48.3 - - - - 2 2.375 3.5 1.8 8.5 3.5 DN50 60.3 1.1 0.5 2.6 1.1 2' 2.875 4.3 2.2 10.8 4.3 73.0 1.3 0.7 3.3 1.3 3.000 4.5 2.3 11.0 4.5 DN65 76.1 1.4 0.7 3.4 1.4 3 3.500 5.0 2.6 13.0 5.0 DN80 88.9 1.5 0.8 4.0 1.5 4.250 6.4 3.2 15.3 6.4 108.0 2.0 0.9 4.7 2.0 4 4.500 6.8 3.4 16.0 6.8 DN100 114.3 2.1 1.0 4.9 2.1 5 5.563 8.5 4.2 21.0 8.5 141.3 2.6 1.3 6.4 2.6 5.500 8.3 4.1 20.6 8.3 DN125 139.7 2.5 1.3 6.3 2.5 6250 9.4 4.9 25.0 9.6 158.8 2.9 1.5 7.6 2.9 6 6.625 10.0 5.0 25.0 10.0 DN150 168.3 3.0 1.5 7.6 3.0 6.500 9.8 4.9 24.5 9.8 165.1 3.0 1.5 7.5 3.0 8 8.625 13.0 5.0 33.0 13.0 DN200 219.1 4.0 1.5 10.1 4.0 8.515 13.0 - 33.0 13.0 2163 4.0 - 10.1 4.0 r The flow data listed is based upon the pressure drop of Schedule 40 pipe. • • 10.03 1539 Rev N Updated 09/2017 ©2017 Victaulic Company.All rights reserved. Vic tdtlllt:.COrr) 3 \ctaukc victaulic.com 6.0 NOTIFICATIONS General Notes NOTE: When assembling FireLock EZTM couplings onto end caps, take additional care to make certain the end cap is fully seated against the gasket end stop. For FireLock EZTM Style 009N/009H couplings, use FireLockTM No. 006 end caps containing the "EZ" marking on the inside face or No. 60 end caps containing the "QV EZ" marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009/009V/009H/009N couplings. 7.0 REFERENCE MATERIALS 1.0.64:Victu,, t FireLock! gid Coupling Style 009N X0.02:Victaulicl FireLock'"Rigid Coupling S yle 005H with Vic-Plus''Gasket Systeri 29.01:Victaulic®Terms and Conditions of Sale • • User Responsibility for Product Selection and Suitability Note Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications.All products Victaulic products for a particular end-use application,in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions. standards and project specifications,and the applicable building codes and related Victaulic reserves the right to change product specifications,designs and standard regulations as well as Victaulic performance,maintenance,safety,and warning equipment without notice and without incurring obligations. instructions.Nothing in this or any other document,nor any verbal recommendation, Installation advice,or opinion from any Victaulic employee,shall be deemed to alter,vary,supersede, Reference should always be made to the Victaulic installation handbook or installation or waive any provision of Victaulic Company's standard conditions of sale,installation instructions of the product you are installing.Handbooks are included with each shipment guide,or this disclaimer. of Victaulic products,providing complete Installation and assembly data,and are available Intellectual Property Rights in PDF format on our website at www.victaulic.com. No statement contained herein concerning a possible or suggested use of any material, Warranty product,service,or design is intended,or should be constructed,to grant any license Refer to the Warranty section of the current Price List or contact Victaulic for details. under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design,or as a recommendation for the use of such Trademarks material,product,service,or design in the infringement of any patentor other intellectual Victaulic and all other Victaulic marks are the trademarks or registered trademarks of property right.The terms"Patented"or"Patent Pending"refer to design or utility patents Victaulic Company,and/or its affiliated entities,in the U.S.and/or other countries. or patent applications for articles and/or methods of use in the United States and/or other countries. • • 10.03 1539 Rev N Updated 09/2017 ®2017 Victaulic Company.All rights reserved. victaulic.com 4 ✓ctauliv COSCO Fire Protection Pipe Hangers COSCO Fire Protection Inc. 2501 SE Columbia Way, Suite 100 Vancouver,WA 98661 Phone:360-883-6383 Fax: 360-883-6390 Toll Free:800-983-6383 M o TOLCO' www.tolco.com r NIBCO Revision 12/18/2008 Fig. 200 - "Trimline" Adjustable Band Hanger c UL US LISTED Fig. 200R (Import) - "Trimline" Adjustable Band Hanger w/Retainer Ring to Size Range — 1/2" thru 8" pipe Material — Carbon Steel, Mil. Galvanized to G90 specifications . Function — For fire sprinkler and other general piping -- `v purposes. Knurled swivel nut design permits hanger `' adjustment after installation. 'Qi _ , Features — ' • 1/2 thru 2 Flared ed es ease in t II ti n f sa a o or B I% I all pie types and protect CPVC plasticpipe � , from abrasion. Captured design keeps adjusting ' ,!;i ; ' ; nut from separating with hanger. Hanger is eas- A . ily installed around pipe. �' ;==' A • (21/2" thru 8") Spring tension on nut holds it ,�'�-_--_;;=' securely in hanger before installation. Adjusting nut is easily removed. Fig.200 1"-2" Fig.200 21/2"-8" Approvals — Underwriters' Laboratories listed (1/2" thru 8") in the USA(UL) and Canada(cUL) '0100 for steel and CPVC plastic pipe and Factory Mutual Engineering Approved (3/4" thru 8"). Conforms to '. Federal Specifications WW-H-171 E, Type 10 and `Q - _- Manufacturers Standardization Society SP-69, Type 10. ,' \ 44/--- B , Maximum Temperature — 650°F ' ' /' ii i B Finish — Mil. Galvanized. Stainless Steel materials will1, j L be supplied with (2) hex nuts in place of a knurl nub. („1 /; .+"'" ,,, Order By — Figure number and pipe size A ' Note — Figure 200R (import) with retainer ring and A non-captured knurl nut. `----- \\ ,;_i-, / Fig.200R 21/2"-8" Fig.200R 1/2"-2" Dimensions •Weights Pipe Rod Size Max. Rec. Approx. Size Inch Metric A B Load Lbs. Wt./100 1/2 3/8 8mm or 10mm 31/s 25/s 400 11 3/4 3/8 8mm or 10mm 31/2 21/2 400 11 1 3/8 8mm or 10mm 33/8 25/4 400 12 11/4 3/8 8mm or 10mm 33/4 21/2 400 13 11/2 3/8 8mm or 10mm 37/8 27/s 400 14 2 3/8 8mm or 10mm 41/2 3 400 15 21/2 3/8 10mm 55/8 4% 600 27 3 3/8 10mm 57/s 4 600 29 31/2 3/8 10mm 73/8 51/4 600 34 4 3/8 10mm 7% 5 1000 35 5 1/2 12mm 91/4 61/4 1250 66 6 1/2 12mm 101/8 63/4 1250 73 8 1/2 12mm 131/8 83/4 1250 136 OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA,CA 92879•PH 951 737 5599•FAX. 951.737.0330 CUSTOMER SERVICE•800 786 5266 91 www.tolco.com TOLCO „r„�,,.toico.cm . „NIBCO Revision 9/1/2006 Fig. 65 and Fig. 66 Reversible C-Type Beam Clamps 3/4° and 11/4" Throat Openings Size Range—(Fig. 65 and Fig. 66) 3/8", 1/2" and 5/8" rod Component of State of California OSHPD Approved CO US LISTED Material — Carbon Steel with hardened cup point set screw and Seismic Restraints System jam nut Function — Recommended for hanging from steel beam where flange thickness does not exceed 3/4" (Fig. 65) or 11/4" (Fig. 66). Features — All steel construction eliminates structural deficiencies associated with casting type beam clamps. May be used on top or B bottom flange of the beam. (Beveled lip allows hanging from top flange where clearance is limited.) May be installed with the set D screw in up or down position. Offset design permits unlimited rod ��. adjustment by allowing the rod to be threaded completely through the , clamp. Open design permits inspection of thread engagement. , , r C I�r� Approvals — Underwriters' Laboratories Listed in the USA(UL) and 41W Canada (cUL). Exceeds requirements of the National Fire Protection �� Association (NFPA), Pamphlet 13, 3/8" rod will support 1/2" thru 4" FOft 111 pipe, 1/2" rod will support 1/2" thru 8" pipe. Included in our SeismicIIII '� Restraints Catalog approved by the State of California Office of e# Statewide Health Planning and Development (OSHPD). For additional �� A load, spacing and placement relating to OSHPD projects, please refer 1,�j to the TOLCO Seismic Restraint Systems Guidelines. ` ,, Finish — Plain O Note — Available in Electro-Galvanized and HDG finish. Order By — Figure number, rod size and finish Fig. 65 Patent#4,570,885 B D Fig. 65 Dimensions •Weights �� k �.-� ` A/,M.. C Rod Size Max.Rec. A rox. .416, !� A B C D E F Load Lbs.* Wt./100 ii' 3/8 13/is 3/4 1 7/16 1 610 28 F 1/2 11/2 3/4 1 9/16 11/4 1130 55 5/8 11/2 3/4 1 9/16 11/4 1130 55 * Max. loads for clamp with set screw in up or down position. 1F1 Fig. 66 4.4*1Ø g A Dimensions •Weights440 Rod Size Max. Rec. Approx. A B C D E F Load Lbs.* Wt./100 3/8 13/16 1 1/4 1 7/16 1 610 28 1/2 11/2 11/4 1 9/16 11/4 1130 55 5/8 11/2 11/4 1 9/16 11/4 1130 55 * Max. loads for clamp with set screw in up or down position. OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA,CA 92879•PH: 951 737 5599•FAX 951.737.0330 60 CUSTOMER SERVICE•800.786.5266 www.tolco.com SAMMYS DESCRIPTION/SUGGESTED SPECIFICATIONS Sammy X-Press Revolutionizes The Pipe SammyHanding Trades— The Sammy X-Press®System is designed to provide direct attachment of threaded rod in metal deck s X_ (22-16 gauge)and thin gauge purlin(18-16 gauge),while providing reduced installation costs in terms PI'eSS of time and materials. The X-Press Anchors eliminate the need for costly"armovers"in pipe hanging installations. Current methods offered for thin gauge purlin require use of a time-consuming retaining nut on the threaded portion of the fastener to prevent pullout Installs into 1 and are not designed for use in metal deck.In many instances, access to the backside of the installed fastener is prohibited Metal Deck/ by panel liner or roofing insulation. Sammy X-Press®anchors deliver the performance installers require without the use of a Purlin, or retaining nut! Tubular Steel The patent-pending X-Press Anchors consist of a threaded V fastener and expandable sleeve. The X-Press System features an easy-to-install anchor with expanding anchoring strips that collapse to prevent pullout after installation. The Sammy X-Press®It Installation Tool assures a perfect installation every time offering the added convenience of one-tool efficiency—just drill and drive in seconds! SECONDS! ADVANTAGES Installs in seconds,saving time& Less jobsite material needed. installation costs. No retaining nut required. Use in applications where access to the back of Provides design flexibility. ,1011111--- the installed fastener is prohibited.ie.metal r roof deck,tubular steel,or vapor barrier fabric. Sammy's X-Press, Swivel and Sidewinder The Sammy X-Press expands to provide direct vertical attachment in: (XP) -Metal Deck(22-16 gauge) Patent No. — -Z-Purlin(18-16au e) 6,935,821 9 g The Sammy X-Press Swivel allows you to hang plumb in extreme roof pitches: (5WXP) I' -89°in Z-Purlin Patent Pending -45°in metal deck for 12/12 pitch FOR The Sammy X-Press Sidewinder expands 0....re (5XP) 11F. tAt. to provide horizontal attachment in: OR -16 ga-3/16"steel-purlin,tubular steel. Patent Pending ROOF PITCHES All/ V ConsWction Products S 12 SA Mi'SCall our toll free number 800-387-9692 or visit www.itwconstruction.ca for general information. Visit ITW Buildex's SAMMYS web site www.sammysuperscrew.com for the most current product and technical information. tiny X, Pre APPLICATIONS APPROVALS ''iti, Sprinkler Systems The X Press System has earned the 9R21 and 25ES UL Listing. . . Pipes/Plumbing Electrical Lighting and Fixtures HVAC Equipment and Fixutres , Iltk, '( ..argil INSTALLATION TOOL SAMMY X-PRESS IT" INSTALLATION TOOL INSTALLATION INSTRUCTIONS cr,IT Patent Pending lir , til a 0Y ' 4. -. PART MODEL DESCRIPTION EACH _- a a • NUMBER QTY III •Ay 1 11"� 8194910 UXPIT* Universal X-Press It Tool 1 1,Pre-Drill. a Attach Sleeve. ' Insert Anchor. 4 Install. 8152910 XPDB 25/64"Drill Bit 1 To watch a video demonstration of the SammyX-Press,visithttp://www.sammysuperscrew.com/sammyxpress.htm *Tool Includes:Sleeve,Bit Receiver,Hex Wrench,and 25/64"Drill Bit. ITN/ Construction Products Cat our toll free number 800-387-9692 or visit www.itwconstruction.ca for general information. SAMMYS' S 13 Visit ITW Buildex's SAMMVS web site www.sammysupersaew.com for the most current product and technical information. a Sammy X-Press SELECTION CHART SAMMYS X-Press Vertical Mount ROD PART ULTIMATETEST TEST MIN MAX BOX CASE SIZE NUMBER MODEL DESCRIPTION PULLOUT �us LOAD ® LOAD THICK THICK QTY QTY APPLICATION (LBS) LISTED (LBS) A.ersovm (LBS) 1/4" 8181922 XP 200 X-Press 200 1146 185(Luminaire) 027" .125" 25 125 Metal Deck (22ga) 250(Luminaire) .056" (XP) 850(2W'Pipe) 940 Patent No. 1146 185(Luminaire) (2"Pipe) 027" 6,935,821 3/8" 8150922 XP 20 X-Press 20 (22 ga) 250(Luminaire) 1475(4"Pipe) .027" .125" 25 125 Metal Deck 283(Conduit&Cable) 056" 1250(3W'Pipe) .060" 3/8" 8153922 XP 35 X-Press 35 1783 85(Luminaire) 940 (2"Pipe) .105" 125" 25 125 Purlin (16 ga) 250(Luminaire) 1475(4"Pipe) .027" 416(Conduit&Cable) .056" Metal Deck 3/8" 8150922 XP 20 Sammy 1146(22ga) 850(21/2 Pipe) Pre Pour Structural Concrete@ 3000 psi 25 125 (Pre Pour) X-Press 20 Post Pour Range II LWC<_35 PCF(lbs/fta) Metal Deck (Post-Pour) Pre-Pour Structural Concrete @ 3000 psi Post-Pour Range II LWC<35 PCF(lbs/ft r�,� _I—\_._"-\_ _J-41—\_ , ... , ,'.: . , .„ 4:-• •.:-. E ", 6F i SAMMYS X-Press Swivel Head° ROD PART ULTIMATE TEST TEST MIN MAX BOX CASE SIZE NUMBER MODEL DESCRIPTION PULLOUTusLOAD ® LOAD THICK THICK QTY QTYAPPLICATION (LBS) LISTED (LBS) A..noveD (LBS) 750(2"Pipe) 117ott(s)(P) rat170 vertical(Luminaire) Swivel 1061(22 ga Vertical) 80 @ 45°(Luminaire) Patent 3/8" 8294922 SXP 20 Xpress 20 829(452 ga Vertical) 283 vertical 635(2"Pipe) .027" .125" 25 125 Metal Deck (Conduit&Cable) V NIIIMA1 233 @ 45° ROOF 111 (Conduit&Cable) 1500(4"Pipe) 250 vertical(Luminaire) Swivel 1675(16 ga Vertical) 80 @ 90°(Luminaire) 3/8" 8295922 SXP 35 X-Press 35 1558(89°Off Vertical) 500 vertical 635(2"Pipe) .060" .125" 25 125 Purlin (Conduit&Cable) 333 @ 89° (Conduit&Cable) 1/2" 8272957 SXP 2.0 Swivel 1061(22 ga Vertical) .027" .125" 25 125 Metal Deck X-Press 2.0 829(45°Off Vertical) 1/2" 8271957 SXP 3.5 Swivel 1675(16 ga Vertical) .060" .125" 25 125 Purlin X-Press 35 1558(89°Off Vertical) SAMMYS X-Press Horizontal Mount ROD PART ULTIMATETEST • TEST MIN MAX BOX CASE SIZE NUMBER MODEL DESCRIPTION PULLOUT Nus LOAD ® LOAD THICK THICK QTY QTY APPLICATION I , (LBS) LISTED (LBS) APPROVED (LBS) , i* Sidewinder 1250(31/2"Pipe) 3/8" 8293957 SWXP35 X Press35 1798(16ga) 80(Luminaire) .060" .125" 25 125 Purlin 'atent Pending 416(Conduit&Cable) Ism T Construction Products S14 SAMMYSFCall our toll free number 800-387-9692 or visit www.itwconstructioe.cafor general information. Visit I1W Buildex's SAMMYS web site www.sammrsnoersaew.com for the most current product and technical information. SAMMYS X-Press for Seismic Restraint g tb DESCRIPTION m proper FEATURES BENEFITS installation! ` Structural attachment and Reduced installation cost. restraint component combined; Design flexibility. --- ready for selected rod. Less on site material(GO GREEN). i� = Access to the back of fastener not required. Less material coordination. ■ Aesthetically pleasing. Does not require use of a ._IA tori-Purlin r� Metal * 0 retaining nut. , f �' r Nflo ' Quick and easy installation. ' s. R' 4 :8.4' FOR 3/8" AND 1/2" RODS SPECIFICATIONS sc tette SXP 20 AND SXP 35 FOR 3/8"ROD FOR 3/8"ROD AND 1/2"ROD CI.O.EO aEF Structural attachment for installation of branch/end of line restraint using Restrained Pipe Size: Up to Schedule 40 pipe 2"or less 3/8"all thread(.299"OD)or end thread rod(.374"OD). Max Length of SXP 20 for 3/8"Rod:Designed for use in metal deck ranging from 22 ga. Restraint Material: See Maximum Horizontal Load Tables below. through 18 ga.in low slope or pitched roof designs(12/12). Maximum Angle: 45°from horizontal Rod:Designed for use in steel purlin ranging from 16 ga. Material: Carbon Steel through 1/8"in low slope or pitched roof designs(12/12). The Swivels may be used to attach short length of rod to eliminate lateral Screw Description: 1/4" 20 x 1-1/8"with expandable sleeve sway bracing per NFPA 13,9.3.5.3.8,(2007). Finish: Electro-Zinc SXP 2.0 AND SXP 3.5 FOR 1/2"ROD Testing: Tested to GR-63-CORE Standard for performance in Structural attachment for installation of branch/end of line restraint using structural steel in seismic restraint applications as outlined for use in NFPA 13(2007), 1/2"all thread(.405"OD)or end thread rod(.500"OD). 9.3 at an independent test lab.The calculated force used for the testing was equal to that found in a Zone 4 and an 8.4 Richter scale seismic event. SXP 2.0 for i Rod Designed for use in metal deck ranging from 22 ga. Listing for 3/8"Rod: UL 203 listed as pipe hanger File EX 5098 FM through 18 ga.in low slope or pitched roof designs(12/12). -SXP 20(22 ga.)0-45°from horizontal-2"Schedule 40 pipe SXP 3 5 for 1/2"Rod Designed for use in steel purlin ranging from 16 ga. -SXP 35(16 ga.)0-90°from horizontal-3-1/2"Schedule 40 pipe ��us through 1/8"in low slope or pitched roof designs(12/12). UL 203A File EX 15565 Da LISTED The Swivels may be used to attach short length of rod to eliminate lateral Listing for 1/2"Rod: UL 203A File EX 15565 uL°s sway bracing per NFPA 13,9.3.5.3.8,(2007). LISTED SELECTION CHART SAMMYS X-Press Swivels - Seismic Restraint ROD PART MODEL MIN MAX APPLICATION BOX CASE INSTALLATION TOOL SIZE NUMBER THICKNESS THICKNESS QTY QTY 3/8" 8294922 SXP 20 22 ga 18 ga. Metal Deck 25 125 1/2" 8272957 SXP 2.0 22 ga 18 ga. Metal Deck 25 125XPIThe SWXP 35 must be installed 3/8" 8295922 SXP 35 16ga 1/8" Purlin 25 125 8194 910); Tool(Part No. 8194910);pre drilling required. 1/2" 8271957 SXP 3.5 16 ga 1/8" Purlin 25 125 PERFORMANCE TABLES Maximum Rod Length for 1/r=100, 200, 300, and 400 Least Radius of Maximum Rod Length for 1/r(ft) Restraint Shape and Size Nominal Diameter Area(in.') Gyration,r(in.) I/r=100 lir=200 lir=300 lir=400* 3/8 in. 0.07 0.075 0.6 1.3 1.9 2.5 Rods(all thread) 1/2 in. 0.129 0.101 0.8 1.7 2.5 3.4 3/8 in. 0.11 0.094 0.8 1.6 2.4 3.1 Rods(threaded at ends only) 1/2 in. 0.196 0.125 1.0 2.1 3.1 4.2 Reference:NFPA 13,(2007) *Reference:NFPA 13,(2010) ITV Construction Products (all our toll free number 800-387-9692 or visit www.itwconstruction.ca for general information. SAMMYS S 1[J Visit ITW Builder s SAMMYS web site www.sammvsuperscrew.com for the most current product and technical information. , r ,SAMMYS X-Press for Seismic Restraint If ;u a o DESCRIPTION (SIDEWINDER) "EAR.. oft) 4 MENts SWXP 35 FOR 3/8"ROD 1::ISA:) 'tE8tEe t0 Structural attachment for installation of branch/end of line restraint using SC OEC 3/8"threaded rod.Used primarily in purlin,bar joist,or other steel structural U.I.Cl► &E C.D.E. f members.These fastening systems provide a secure and economical attachment to the structure. The SWXP 35 model provides upper structural attachment in a range of steel r',, thicknesses,from 16 ga.through 1/8".An expandable sleeve is included withja each fastener,eliminating need for retaining nut. SPECIFICATIONS ��d,,, Restrained Pipe Size: Up to Schedule 40 pipe 2"or less �� Max Length of li Restraint Material: See Maximum Horizontal Load Tables below. = ' Maximum Angle: 45°from horizontalp. 0 1 Material: Carbon Steel o "' '3� r )) Screw Description: 1/4"-20 X 1-1/8"with expandable sleeve 45 Q�ensure `� proper ; Finish: Electro-Zinc(cap&screw) iinstaltatton[ Testing: BX Report#R-1362 n... Listing: UL 203 as a pipe hanger O UL 203A pending CLISTEDUs SELECTION CHART SAMMYS Sidewinders for Concrete - Seismic Restraint ROD PART MODEL MIN MAX APPLICATION BOX CASE INSTALLATION TOOL SIZE NUMBER THICKNESS THICKNESS QTY QTY The SWXP 35 must be installed 3/8" 8293957 SWXP 35 16 ga. 1/8" Steel Purlin or Bar Joist 25 125 with UXPIT Tool(Part No.8194910); pre-drilling required. PERFORMANCE TABLES Maximum Horizontal Loads for Restraint with 1/r=100, 200, 300, and 400 Restraint Shape and Size Nominal Diameter Area(in?) Least Radius of Maximum Rod Length for lir(ft) Gyration,r(in.) I/r=100 lir=200 lir=300 I/r=400* 3/8 in. 0.07 0.075 0.6 1.3 1.9 2.5 Rods(all thread) 1/2 in. 0.129 0.101 0.8 1.7 2.5 3.4 3/8 in. 0.11 0.094 0.8 1.6 2.4 3.1 Rods(threaded at ends only) 1/2 in. 0.196 0.125 1.0 2.1 3.1 4.2 Reference:NFPA 13,(2007) *Reference:NFPA 13,(2010) ITN/ Construction Products S 16 SAMMYSCall our toll free number 800-387-9692 or visit www.itwconstruction.ca for general information. Visit ITW Builde>i s SAMMVS web site www.sammysuperscrew.com for the most current product and technical information. :•••.••: I COSCO Fire Protection I he mom lion onti Lifi° Srtfct?' Sht�i�tfi+t: • Seismic Bracing COSCO Fire Protection Inc. 2501 SE Columbia Way, Suite 100 Vancouver,WA 98661 Phone:360-883-6383 Fax: 360-883-6390 Toll Free:800-983-6383 o o TOLCO www.tolco.com NIBCO Revision 1/21/2011 Fig. 4L c Xp US LISTED Longitudinal "In-Line" Sway Brace Attachment 411> Size Range — 21/2" through 8" IPS. 0, Material — Carbon Steel Function — For bracing pipe against sway and seismic disturbance. Vs r frtet � Approvals — Underwriter's Laboratories Listed in the USA(UL) and 0 Canada (cUL) 2/" - 8". Approved by Factory Mutual Engineering (FM), � \ 21/2" - 8" pipe. Installation Instructions — The Fig. 4L is the "braced pipe" attachment component of a longitudinal sway brace assembly. It is intended to be D A combined with the "bracing pipe" and TOLCO structural attachment component to form a complete bracing assembly. NFPA 13 and/or OSHPD guidelines should be followed. To Install — Place the Fig. 4L over the pipe to be braced and tighten bolts. Then engage "bracing pipe" into jaw opening and tighten set bolt until hex head snaps off. Jaw attachment can pivot for adjustment to C \ proper brace angle. Finish — Plain I Note — Available in Electro-Galvanized and HDG finish. Order By — Figure number, pipe size and finish. `r- ,, ' n 1 roH, o Dimensions •Weights r..+S---I Bolt Max.Rec. *Max Design Approx. Sizes A C D Size Load Lbs. Load Lbs. Wt./100 253 (cULus) (FM) i 1 II 21/z 67A6 21/2 23/4 1/2 2015 3000 j 3 7 23/4 3�/is 1/2 2015 1550 268 4 81/2 33/8 311/16 1/2 2015 1550 348 0 5 93/4 37/8 4% 1/2 2015 1450 380 Longitudinal Brace 6 111/2 5 51/8 1/2 2015 1450 640 8 131/4 55/8 55/8 1/2 2015 1450 728 'Ilke� *The loads listed are axial loads on the brace.The horizontal load capacity,H,of the � brace is: H=F x sin 0,where 0 the installation angle measured from the vertical. mrFM approved when used with 1",11/4", 11/2"or 2" Sch.40 brace pipe. :Ng.", .: ...........L.. 4-Way Riser Brace (Plan view) TOLCO®brand bracing components are designed to be compatible ONLY with other TOLCO®brand bracing components,resulting in a Listed seismic bracing assembly. DISCLAIMER — NIBCO does NOT warrant against the failure of TOLCO®brand bracing components, in the instance that such TOLCO®brand bracing components are used in combination with products,parts or systems which are not manufactured or sold under the TOLCO®brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit,where non-TOLCO brand bracing components have been,or are used. OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA,CA 92879•PH: 951.737 5599•FAX: 951.737.0330 29 CUSTOMER SERVICE•800.786.5266 www.tolco.com V TO LCD www.tolco.conor NIBCO Revision 1/21/2011 Fig. 980 - Universal Swivel Sway Brace Attachment cOUSLISTEO Size Range — One size fits bracing pipe 1" thru 2", TOLCO 12 gauge channel, and all structural steel up to 1/4" thick. Material — Carbon Steel Component of State of �` California OSHPD Approved Function — Multi-functional attachment to structure or Seismic Restraints System braced pipe fitting. Features — This product's design incorporates a concen- tric attachment opening which is critical to the performance , of structural seismic connections. NFPA 13 (2010) 9.3.5.8.4 *N indicates clearly that fastener table load values are based only on concentric loading. Mounts to any surface angle. Break off bolt head assures verification of proper installation. Installation — The Fig.980 is the structural or transitional A attachment component of a longitudinal or lateral sway brace assembly. It is intended to be combined with the "bracing pipe" and TOLCO "braced pipe" attachment, Fig. 1000, 1001, 2002, 4L, 4A or 4B to form a complete bracing assembly. NFPA 13 and/or OSHPD guidelines should be followed. To Install — Place the Fig. 980 onto the "bracing pipe". Tighten the set bolt until set bolt head breaks off. Attachment can pivot for adjustment to proper brace angle. Approvals — Underwriters Laboratories Listed in the USA (UL) and Canada(cUL). Approved by Factory Mutual Engineering (FM). Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Note — The Fig. 980 Swivel Attachment and the Fig. 1001, Fig. 1000, Fig. 2002, Fig. 4A, Fig. 4B or Fig. 4L Pipe Clamp make up a sway brace system of UL Listed attachments and bracing materials which satisfies the require- ments of Underwriters' Laboratories and the National Fire Protection Association (NFPA) Finish — Plain Note — Available in Electro-Galvanized finish. Order By — Figure number and finish. Pat. #6,273,372, Pat.#6,517,030, Pat.#6,953,174, Pat. #6,708,930, Pat.#7,191,987, Pat.#7,441,730, Pat.#7,669,806 Lateral Brace Dimensions •Weights Max. Design Max. Design Approx. A B H" Load Lbs. Load Lbs.** Wt./100 (cULus) (FM) 51/4 17/8 17/32 2765 2800 132 Available with hole sizes to accommodate up to 3/4"fastener. Consult factory. **The loads listed are axial loads on the brace.The horizontal load capacity, H,of the brace is: H=F x sin 0,where 0 is the installation angle measured from the vertical. TOLCO®brand bracing components are desgined to be compatible ONLY with other TOLCO®brand bracing components, resulting in a Listed seismic bracing assembly. DISCLAIMER — NIBCO does NOT warrant against the failure of TOLCO®brand bracing components, in the instance that such TOLCO®brand bracing components are used in combination with products, parts or systems which are not manufactured or sold under the TOLCO®brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect,incidental or consequential damages of any kind, including but not limited to loss of business or profit,where non-TOLCO brand bracing components have been,or are used. OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA,CA 92879•PH: 951 737 5599•FAX: 951 737.0330 CUSTOMER SERVICE•800.786.5266 150 www.tolco.com TOLCO www.tolco•com o NIBCD Revision 12/3/2008 Fig. 1001 - Sway Brace Attachment Component of State of CO US LISTED California OSHPD Approved Size Range — Pipe size to be braced: 21/2" thru 8" IPS.* Pipe size Seismic Restraints System used for bracing: 1" and 11/4" Schedule 40 IPS. ..••a.o Material — Carbon Steel Function — For bracing pipe against sway and seismic distur- bance. The pipe attachment component of a sway brace system: The Fig. 1001 is used in conjunction with a TOLCO 900 Series fitting and joined together with bracing pipe per NFPA 13, forming a com- plete sway brace assembly. Features — Can be used to brace schedules 7 through 40 IPS. l . Field adjustable, making critical pre-engineering of bracing pipe \_ length unnecessary. Unique design requires no threading of brac- ing pipe. Can be used as a component of a four-way riser brace. Comes assembled and ready for installation. Fig. 1001 has built-in visual verification of correct installation. See installation note below. Installation Note — Position Fig. 1001 over the pipe to be braced and tighten two hex head cone point set bolts until heads bottom out. A minimum of 1" pipe extension is recommended. Brace pipe can be installed on top or bottom of pipe to be braced. Approvals — Underwriters Laboratories Listed in the USA(UL) Maximum Design Load and Canada (cUL). Approved by Factory Mutual Engineering (FM). Sch. 7 - 1600 lbs. Included in our Seismic Restraints Catalog approved by the State Sch. 10 &40 w/1" Brace Pipe - 2015 lbs. of California Office of Statewide Health Planning and Development Sch. 10 & 40 w/11/4Brace Pipe 2765 lbs. (OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic FM Approved Design Loads* Restraint Systems Guidelines. 21/" - 2400 lbs. Finish — Plain 3" 4" 2500 lbs. 5" - 8" - 1500 lbs. Note — Available in Electro-Galvanized and HDG finish. Order By — Indicate pipe size to be braced followed by pipe size used for bracing, figure number and finish. Important Note — The Fig. 1001 is precision manufactured to perform its function as a critical component of a complete brac- ing assembly. To ensure performance,the UL Listing requires that the Fig. 1001 must be used only with other TOLCO bracing products. The Fig 1001 is not intended for use with the Fig. 907 4-Way Longitudinal Brace Attachment. �l 0 4 I 1 .may OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA,CA 92879•PH: 951.737.5599•FAX 951.737.0330 CUSTOMER SERVICE•800 786 5266 www.tolco.com l 1 ®TOLCID Component of State of Fig. 825A - Bar Joist Sway Brace Attachment CaliforniaOSHPDApproved Seismic Restraints System Size Range — One size accommodates all TOLCO Fig. 900 Series sway brace attachments. Maximum Horizontal Design Load 1600 lbs. Material — Carbon Steel 3/8" COUS �� LISTED Function — To attach sway bracing to steel open web structural members. Features — This product's design incorporates a concentric attachment point which is critical to the performance of structural seismic connections. NFPA 13 indicates the importance of concentric loading of connections and fasteners. 1111111‘.Permits secure non-friction connection without drilling or welding. Unique design reinforces point of connection to joist. Break off head bolt design assures verifi4:0 - cation of proper installation. Approvals — Underwriter's Laboratories Listed in the USA(UL)and Canada . / 1110 /!� (( t 11 (cUL). For additional load, spacing and placement information relating to OSHPD r 444110projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Installation Instructions — The Fig. 825A is the structural attachment com- '((�� �►` ponent of a longitudinal or lateral sway brace assembly. It is intended to be combined with a TOLCO transitional attachment, "bracing pipe" and a TOLCO 41100 "braced pipe" attachment to form a complete bracing assembly. NFPA 13 and/or , •t'(�� OSHPD guidelines should be followed. To Install — Place the Fig. 825A on the steel beam,tighten the cone point set bolts until bolt heads break off. Attach other TOLCO transitional attachment fit- ting, Fig. 909, 910, 980 or 986. Transitional fitting attachment can pivot for adjustment to proper brace angle. Maximum Design Load 1600 Lbs. Important Structural Note: The TOLCO Fig. 825A has significant UL established design loads, however, structural issues related to the Bar joist shown attached steel joist member require restricted location installation to various roof materials for all bracing. Steel Joist Manufacturers require that all 6,1 Max. earthquake bracing connections be within 6" of the cord panel point. Installation of the Fig. 825A is not restricted —��������► to the two outer third sections of the joist. For greater design loads, refer to TOLCO Fig. 825. \ oatf \\ v Finish — Plain �I Order By — Figure number and finish Shown with Patent#6,098,942 Fig.980 MIMMIIAra, �.. May pivot in t>" any direction V Cooper B-Line, Inc.'s ("Cooper B-Line") seismic bracing components are designed to be compatible only with other Cooper B-Line bracing components, resulting in a listed seismic bracing assembly. Cooper B-Line's warranty for seismic bracing components will be the warranty provided in Cooper B-Line's standard terms and conditions of sale made available by Cooper B-Line,except that,in addition to the other exclusions from Cooper B-Line's warranty,Cooper B-Line makes no warranty relating to Cooper B-Line's seismic bracing components that are combined with products not provided by Cooper B-Line. COOPER B-LINE 1375 Sampson Ave•Corona,CA 92879•800.786.5266•FAX:951.737.0330 www.tolco.com COOPER B-Line TOLBraceTM Seismic Calculations Cosco Fire Protection Project Address: Clean Water Services 2501 SE Columbia Way,Suite �-��� Vancouver,WA 98661 16060 SW 85th Ave. 360-883-6383 Palming 8rsirsessWcrtdwde Tigard, OR 67508 Job#PD5199 Calculations based on 2013 NFPA Pamphlet#13 Brace Information TOLCOTM Brace Components Maximum Spacing 24'0"(7.32 m) TOLCOTM Component Fig. Number Adjusted Load Maximum Brace Length 71 0" (2.13 m) Fig.4LA Clamp 707 lbs(321 kg) Bracing Material 1" Sch.40 Fig.980 Universal Swivel 1425 lbs(646 kg) 45° Min. *Calculation Based on CONCENTRIC Loading Angle from Vertical *Please Note:These calculations are for TOLCOTM components only.Use of any other components voids these calculations and the listing of the assembly. Least Rad.of Gyration 0.42"(11 mm) �� Assembly Detail UR Value 200 Max Horizontal Load 1310 lbs(594 kg) 6EINE 1OtCOfIG9p UMYEH;.AL SWAY '. Force Factor(Cp) 0.5 '".u" "`""�" Fastener Information TOLCO Fastener Orientation NFPA Type H Maximum LoadZ 4,*230 lbs(104 kg) ry y Diameter 1/2in. Length 4-1/2in. " "" "�A Type Lag-Screw Brace Identification on Plans LONG. 1 Orientation of Brace Longitudinal Size and Type of Pipe �R !1W 0ii ,► Total Length Total Calculated Load 4"Sch.40 Steel Pipe(101.6 mm) / �y( 24ft(7.3 m) 197 lbs(89 kg) 7/506 HE 1-18-2019 OREGON co Y L p EXPIRATION DATE:12/31/20 Percentage added for Fittings and Sprinklers 15% 30 lbs(13.61 kg) Total Adjusted Load of all pipe within Zone of Influence 226 lbs(103 kg) (TOLBraceTM'Version 8) Use of TOLBraceM is subject to terms and conditions per the end user license agreement TOLBraceTM Seismic Calculations Clean Water Services Job#PD5199 16060 SW 85th Ave. a Powivrnrj Baseness.Waldo& Brace Identification LONG. 1 Brace Type(Per NFPA#13) NFPA Type H Braced Pipe 4" Sch.40 Steel Pipe Spacing of Brace 24' 0" (7.32 m) Orientation of Brace Longitudinal Bracing Material 1" Sch.40 Maximum Brace Length 7'0" (2.13 m) Slenderness Ratio used for Load Calculation 200 True Angle of Brace for Calculation 45° Type of Fastener 1/2in.x 4-1/2in. Lag-Screw Length of Fastener 4-1/2in. Summary of Pipe within Zone of Influence 4"Sch.40 Steel Pipe(101.6 mm) 124ft(7.3 m) Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 226 lbs(103 kg) Material Capacity 1310 lbs(594 kg) Fastener Capacity 230 lbs(104 kg) Fig.4LA Clamp 707 lbs(321 kg) Fig.980 Universal Swivel 1425 lbs(646 kg) Structural Member WOOD I-BEAM Calculations prepared by Dan Furno *The description of the Structural Member is for informational purposes only. TOLBrace''software calculates the brace assembly only,not the structure it is attached to. Calculated with TOLBrace""8 Visit us at www.tolco.com TOLBraceTM Seismic Calculations Cosco Fire Protection Project Address: Clean Water Services 2501 SE Columbia Way,Suite �i�• Vancouver,WA 98661 N 16060 SW 85th Ave. 360-883-6383 Puwanrxreusr.'esswtrtdunde Tigard, OR 67508 Job#PD5199 Calculations based on 2013 NFPA Pamphlet#13 Brace Information TOLCOTM Brace Components Maximum Spacing 24'0"(7.32 m) TOLCOTM Component Fig. Number Adjusted Load 7'0"(2.13 m Fig. 1001 Clamp 1425 lbs(646 Maximum Brace Length ) kg) Bracing Material 1" Sch.40 Fig.980 Universal Swivel 1425 lbs(646 kg) 45° Min. *Calculation Based on CONCENTRIC Loading Angle from Vertical *Please Note:These calculations are for TOLCOTM components only.Use of any other components voids these calculations and the listing of the assembly. Least Rad.of Gyration 0.42".(11 mm) Assembly Detail L/R Value 200 lbs (594 kg) TOLCO FIG. 980 1310 Max Horizontal Load UNIVERSAL SWAY BRACE Force Factor(Cp) 0.5 ATTACHMENT STEEL PIPE 411 r4 Fastener Information Fastener Orientation NFPA Type E 4 Maximum Load 740 lbs (336 kg) ee ;� • Diameter 3/4in. (19 mm) TOLCO FIG. 1001 ✓. Length 5-1/2 in. (140 mm) FAST CLAMP 411k♦ Type Dual Lag Bolts-Fig.906 Brace Identification on Plans Lat. 1 Orientation of Brace Lateral Size and Type of Pipetr * Total Length Total Calculated Load 4"Sch.40 Steel Pipe(101.6 mm) �� := �4"��'• 24ft(7.3 m) 197 lbs(89 kg) 2"Sch.10 Steel Pipe(50.8 mm) 77506 PE 200ft(61 m) 422 lbs(191 kg) 1-18-2019 OREGON `FSR10 /N�P� `FSR L p EXPIRATION DATE:12/31/20 Percentage added for Fittings and Sprinklers 15% 93 lbs(42.19 kg) Total Adjusted Load of all pipe within Zone of Influence 712 lbs(323 kg) {TOLBraceTM Version 8) Use of TOLBraceTM is subject to terms and conditions per the end user license agreement 1 I I TOLBraceTM Seismic Calculations Clean Water Services Job#PD5199 16060 SW 85th Ave. Fa'•N Pawing Awl:ass tW4dlvida Brace Identification Lat. 1 Brace Type(Per NFPA#13) NFPA Type E Braced Pipe 4" Sch.40 Steel Pipe Spacing of Brace 24'0" (7.32 m) Orientation of Brace Lateral Bracing Material 1" Sch.40 Maximum Brace Length 7'0" (2.13 m) Slenderness Ratio used for Load Calculation 200 True Angle of Brace for Calculation 45° Type of Fastener 3/4 x 5-1/2 (19 x 140 mm) Dual Lag Bolts Perpendicular to Beam -TOL( Length of Fastener 5-1/2 in.(140 mm) Summary of Pipe within Zone of Influence 4"Sch.40 Steel Pipe(101.6 mm) 24ft(7.3 m) 2"Sch.10 Steel Pipe(50.8 mm) 200ft(61 m) Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 712 lbs (323 kg) Material Capacity 1310 lbs(594 kg) Fastener Capacity 740 lbs (336 kg) Fig. 1001 Clamp 1425 lbs(646 kg) Fig.980 Universal Swivel 1425 lbs(646 kg) Structural Member Wood Beam Calculations prepared by Dan Furno *The description of the Structural Member is for informational purposes only. TOLBrace""software calculates the brace assembly only,not the structure it is attached to. Calculated with TOLBrace""8 Visit us at www.tolco.com TOLBraceTM Seismic Calculations Cosco Fire Protection Project Address: Clean Water Services 2501 SE Columbia Way,Suite Vancouver,WA 98661 E.T•N 16060 SW 85th Ave. 360-883-6383 Pow ag ArsonsWrr+divo Tigard, OR 67508 Job#PD5199 Calculations based on 2013 NFPA Pamphlet#13 Brace Information TOLCOTM Brace Components Maximum Spacing 35'0"(10.67 m) TOLCOTM Component Fig. Number Adjusted Load Maximum Brace Length 7 0"(2.13 m) Fig. 1001 Clamp 1425 lbs(646 kg) Bracing Material 1"Sch.40 Fig.980 Universal Swivel 1425 lbs(646 kg) 45° Min. *Calculation Based on CONCENTRIC Loading Angle from Vertical *Please Note:These calculations are for TOLCOTM components only.Use of any other components voids these calculations and the listing of the assembly. Least Rad.of Gyration 0.42" (11 mm) Assembly Detail LIR Value 200 Max Horizontal Load 1310 lbs(594 kg) TOLCO FIG. 980 BRACE Force Factor(Cp) 0.5 UNIVERSALASTWTACHMENT STEEL PIPE .; Fastener Information 'I Fastener Orientation NFPA Type B G1 `'f''�. Maximum Load 2050 lbs (930 kg) °0.,, 1 �f ♦4' Diameter 1/2n. (12 mm) TOLCO FIG. 1001 Y,. FAST CLAMP 4♦' Length N/A �• Type Bolt I Brace Identification on Plans LAT.2 Orientation of Brace Lateral Size and Type of Pipe 1 "•F / Total Length Total Calculated Load 4"Sch.40 Steel Pipe(101.6 mm) N � = t 1!x t• / 35ft(10.7 m) 287 lbs(130 kg) 1.25"Sch.10 Steel Pipe(31.75 m • /� 174ft(53 m) 219 lbs(99 kg) 77506 PE 1"Sch.40 Steel Pipe(25.4 mm) 1-18-2019 57ft(17.4 m) 58 lbs(26 kg) ......,OREGON 4)/ )- p EXPIRATION DATE:12/31/20 Percentage added for Fittings and Sprinklers 15% 85 lbs(38.56 kg) Total Adjusted Load of all pipe within Zone of Influence 649 lbs(294 kg) {TOLBraceTM Version 8} Use of TOLBraceTM is subject to terms and conditions per the end user license agreement y w TOLBraceTM Seismic Calculations Clean Water Services Job#PD5199 16060 SW 85th Ave. E 1T•N 9owof easinessWaktwidu Brace Identification LAT.2 Brace Type(Per NFPA#13) NFPA Type B Braced Pipe 4" Sch.40 Steel Pipe Spacing of Brace 35'0" (10.67 m) Orientation of Brace Lateral Bracing Material 1" Sch.40 Maximum Brace Length 7'0" (2.13 m) Slenderness Ratio used for Load Calculation 200 True Angle of Brace for Calculation 45° Type of Fastener 1/2(12mm) Bolt Length of Fastener N/A Summary of Pipe within Zone of Influence 4"Sch.40 Steel Pipe(101.6 mm) 35ft(10.7 m) 11.25"Sch.10 Steel Pipe(31.75 mm) 174ft(53 m) 1"Sch.40 Steel Pipe(25.4 mm) 57ft(17.4 m) Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 649 lbs (294 kg) Material Capacity 1310 lbs(594 kg) Fastener Capacity 2050 lbs(930 kg) Fig. 1001 Clamp 1425 lbs(646 kg) Fig.980 Universal Swivel 1425 lbs(646 kg) Structural Member I-BEAM Calculations prepared by Dan Furno *The description of the Structural Member is for informational purposes only. TOLBrace'"software calculates the brace assembly only,not the structure it is attached to. Calculated with TOLBrace'°8 Visit us at www.tolco.com • f • TOLBraceTM Seismic Calculations Cosco Fire Protection Project Address: Clean Water Services 2501 SE Columbia Way,Suite �'�.� Vancouver,WA 98661 16060 SW 85th Ave. Pow e,r4 fidsrrwsslWrvtdwrde 360-883-6383 Tigard, OR 67508 Job#PD5199 Calculations based on 2013 NFPA Pamphlet#13 Brace Information TOLCOTM Brace Components Maximum Spacing 45'0"(13.72 m) TOLCOTM Component Fig. Number Adjusted Load m) Maximum Brace Length 7'0"�2.13 Fig.4LA Clamp 707 lbs(321 kg) Bracing Material 1"Sch.40 Fig.980 Universal Swivel 1425 lbs(646 kg) An le from Vertical 45° Min. *Calculation Based on CONCENTRIC Loading g *Please Note:These calculations are for TOLCOTM components only.Use of any other components voids these calculations and the listing of the assembly. Least Rad.of Gyration 0.42"(11 mm) Assembly Detail UR Value 200 Max Horizontal Load 1310 lbs (594 kg) F�Y[Rl"4 SWAY __ Force Factor(Cp) 0.5 40 Fastener Information Fastener Orientation NFPA Type B //`L Maximum Load 2050 lbs(930 kg) Diameter 1/2n. (12 mm) -- ' Length N/A II FIGIPS Type Bolt Brace Identification on Plans LONG 2 Orientation of Brace Longitudinal Size and Type of Pipe ��R fS• // Total Length Total Calculated Load ANA 4"Sch.40 Steel Pipe(101.6 mm) y' 45ft(13.7 m) 369 lbs(167 kg) C 77506 PE 1-18-2019 OREGON C N Y L . 4 EXPIRATION DATE:12/31/20 Percentage added for Fittings and Sprinklers 15% 55 lbs(24.95 kg) Total Adjusted Load of all pipe within Zone of Influence 424 lbs(192 kg) (TOLBraceT"'Version 8) Use of TOLBraceTM is subject to terms and conditions per the end user license agreement Y • TOLBraceTM Seismic Calculations Clean Water Services Job#PD5199 16060 SW 85th Ave. F.1•N Poww„,q ai,,r c woow,de Brace Identification LONG 2 Brace Type(Per NFPA#13) NFPA Type B Braced Pipe 4" Sch.40 Steel Pipe Spacing of Brace 45' 0" (13.72 m) Orientation of Brace Longitudinal Bracing Material 1" Sch.40 Maximum Brace Length 7'0" (2.13 m) Slenderness Ratio used for Load Calculation 200 True Angle of Brace for Calculation 45° Type of Fastener 1/2(12mm) Bolt Length of Fastener N/A Summary of Pipe within Zone of Influence 4"Sch.40 Steel Pipe(101.6 mm) 45ft(13.7 m) Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 424 lbs (192 kg) Material Capacity 1310 lbs(594 kg) Fastener Capacity 2050 lbs(930 kg) Fig.4LA Clamp 707 lbs (321 kg) Fig.980 Universal Swivel 1425 lbs(646 kg) Structural Member I-BEAM Calculations prepared by Dan Furno *The description of the Structural Member is for informational purposes only. TOLBrace""software calculates the brace assembly only,not the structure it is attached to. Calculated with TOLBrace""8 Visit us at www.tolco.com COSCO FIRE PROTECTION 2501 SE COLUMBIA WAY, SUITE 100 VANCOUVER, HYDRAULIC CALCULATIONS FOR CLEAN WATER SERVICES - O&M BUILDING 16060 SW 85TH AVENUE TIGARD, OR 97223 DRAWING NUMBER: FP-3 DATE : DEC 11, 2018 -DESIGN DATA- REMOTE AREA NUMBER: E REMOTE AREA LOCATION : AREA E •- 0 X1 OCCUPANCY CLASSIFICATION: Light Hazard .,[+i/ ^.�� DENSITY: . 10 gpm/sq. ft . m 77506 PE AREA OF APPLICATION: 1500 (906) sq. ft . 1-18-2019 OREGON COVERAGE PER SPRINKLER: 168 sq. ft . 9iy Q-°co TYPE O :QR NUMBERFOFPRINKLERS SPRINKLERSASU CALCULATED : S10 vF'Q4'Y L � L . 0 HOSE-STREAM DEMAND OUTSIDE : 100 gpm EXPIRATION DATE:12/31/20 TOTAL WATER REQUIRED (INCLUDING HOSE) : 284 . 1 gpm FLOW AND PRESSURE (AT BASE OF RISER) : 184 gpm @ 60 . 1 psi TYPE OF SYSTEM: PREACTION WATER SUPPLY Source : CITY MAIN Test Date : 06/07/18 Test By : WYATT FIRE PROTECTION Location: SOUTH END OF HALL BLVD . Static : 98 psi Residual : 76 psi Flow: 1764 . 0 gpm Source Elevation Relative to Finished Flow Level : 13 ft . INSTALLING CONTRACTOR Name :COSCO FIRE PROTECTION Address : 2501 SE COLUMBIA WAY, SUITE 100 Phone : 360-883-6383 Certification number : 67508 NAME OF DESIGNER: DAN FURNO AUTHORITY HAVING JURISDICTION: CITY OF TIGARD NOTES : REMOTE AREA REDUCED 33% FOR QR SPRINKLERS AND 14 ' -3 CEILING HEIGHT PER NFPA 13 (2013) 11 . 2 . 3 . 2 . 3 Calculations performed by HASS under license # 380812802 , granted by HRS SYSTEMS, INC . (Notes continue after pipe calculations results . ) 4 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE : 12/11/2018SYSTEMS\HASS86\DATA\CLEAN WATER SERVICES O&M - AREA E . SDF JOB TITLE : CLEAN WATER - AREA D WATER SUPPLY ANALYSIS Static : 98 . 00 psi Resid: 76 . 00 psi Flow: 1764 . 0 gpm 120 . 0 LEGEND 100 . 0 _ 1 ' Available pressure 1A1 97 . 25 psi @ 284 . 1 gpm A 2 5 Required pressure G 80 . 0 65 . 32 psi @ 284 . 1 gpm P \ \ 1A Avail . OnSite Demand Press E 97 . 25 psi @ 184 . 1 gpm S 2A2 / S 60 . 0 2A q Req. OnSite Demand Press . E 65 . 32 psi @ 184 . 1 gpm ( A. Source Supply Curve 40 . 0 B. System Demand Curve i C . Available at Source 20 . 0 I - B 0 . 0 - -- — -- - -14 . 7 400600 800 1000 1200 1400 1600 1800 2000 FLOW (GPM) )te : (1) Dashed Lines indicate extrapolated values from Test Results (2) On Site pressures are based on hose stream deduction at the source SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATA: `12/11/2018SYSTEMS\HASS86\DATA\CLEAN WATER SERVICES O&M - AREA E . SDF JOB TITLE : CLEAN WATER - AREA D NFPA WATER SUPPLY DATA SOURCE STATIC RESID . FLOW AVAIL . TOTAL REQ'D NODE PRESS . PRESS . @ PRESS . @ DEMAND PRESS . TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) SRC 98 . 0 76 . 0 1764 . 0 97 . 2 284 . 1 65 . 3 AGGREGATE FLOW ANALYSIS : TOTAL FLOW AT SOURCE 284 . 1 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100 . 0 GPM OTHER HOSE STREAM ALLOWANCES 0 . 0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 184 . 1 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES (FT) (PSI) (GPM) 201 9 . 0 K= 5 . 60 10 . 1 17 . 8 202 9 . 0 K= 5 . 60 10 . 4 18 . 1 203 9 . 0 K= 5 . 60 11 . 0 18 . 6 204 9 . 0 K= 5 . 60 9 . 0 16 . 8 205 9 . 0 K= 5 . 60 11 . 1 18 . 6 206 9 . 0 K= 5 . 60 9 . 4 17 . 2 207 9 . 0 K= 5 . 60 11 . 0 18 . 5 208 9 . 0 K= 5 . 60 13 . 4 20 . 5 209 9 . 0 K= 5 . 60 11 . 0 18 . 6 210 9 . 0 K= 5 . 60 11 . 9 19 . 3 21L 12 . 0 - - - - 14 . 1 - - - 22L 12 . 0 - - - - 14 . 5 - - - 23L 12 . 0 - - - - 15 . 4 - - - 24L 12 . 0 - - - - 12 . 4 - - - 25L 12 . 0 - - - - 12 . 7 - - - 26L 12 . 0 - - - - 13 . 0 - - - 27L 12 . 0 - - - - 15 . 3 - - - 28L 12 . 0 - - - - 15 . 2 - - - 29L 12 . 0 - - - - 15 . 3 - - - 30L 12 . 0 - - - - 16 . 7 - - - B1 12 . 0 - - - - 17 . 6 - - - B2 12 . 0 - - - - 18 . 0 - - - B3 12 . 0 - - - - 18 . 6 - - - M1 12 . 0 - - - - 18 . 9 - - - P1 12 . 0 - - - - 33 . 9 - - - P2 10 . 0 - - - - 51 . 5 - - - A4 18 . 0 - - - - 50 . 4 - - - TOR 18 . 0 - - - - 52 . 7 - - - BOR 1 . 0 - - - - 60 . 1 - - - BF2 -4 . 0 - - - - 62 . 3 - - - BF1 -4 . 0 - - - - 67 . 3 - - - UG1 -4 . 0 - - - - 67 . 4 - - - SRC 1 . 0 SOURCE 65 . 3 184 . 1 4 r SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 . k DATE : 12/11/2018SYSTEMS\HASS86\DATA\CLEAN WATER SERVICES O&M - AREA E . SDF JOB TITLE : CLEAN WATER - AREA D NFPA3 PIPE DATA Pipe Tag K-fac Add Fl Add Fl To Fit : L C (Pt) To Node El (ft) PT (q) Node/ Nom ID Eq. Ln . F (Pe) Nc Frm Node El (ft) PT Tot . (Q) Disch Act ID (ft . ) T Pf/ft . (Pf) Pipe : 1 5 . 60 17 . 8 Disch 32 . 00 100 10 . 1 201 9 . 0 10 . 1 0 . 0 1 . 000 T : 3 . 6 3 . 57 -1 . 3 21L 12 . 0 14 . 1 17 . 8 1 . 049 35 . 57 0 . 148 5 . 2 Pipe : 2 5 . 60 18 . 1 Disch 32 . 00 100 10 . 4 202 9 . 0 10 . 4 0 . 0 1 . 000 T : 3 . 6 3 . 57 -1 . 3 22L 12 . 0 14 . 5 18 . 1 1 . 049 35 . 57 0 . 151 5 . 4 Pipe : 3 5 . 60 18 . 6 Disch 32 . 00 100 11 . 0 203 9 . 0 11 . 0 0 . 0 1 . 000 T : 3 . 6 3 . 57 -1 . 3 23L 12 . 0 15 . 4 18 . 6 1 . 049 35 . 57 0 . 159 5 . 7 Pipe : 4 5 . 60 16 . 8 Disch 32 . 00 100 9 . 0 204 9 . 0 9 . 0 0 . 0 1 . 000 T : 3 . 6 3 . 57 -1 . 3 24L 12 . 0 12 . 4 16 . 8 1 . 049 35 . 57 0 . 132 4 . 7 Pipe : 5 5 . 60 18 . 6 Disch 13 . 00 100 11 . 1 205 9 . 0 11 . 1 0 . 0 1 . 000 E : 1 . 4 5 . 00 -1 . 3 25L 12 . 0 12 . 7 18 . 6 1 . 049 T : 3 . 6 18 . 00 0 . 160 2 . 9 Pipe : 6 5 . 60 17 . 2 Disch 32 . 00 100 9 . 4 206 9 . 0 9 . 4 0 . 0 1 . 000 T : 3 . 6 3 . 57 -1 . 3 26L 12 . 0 13 . 0 17 . 2 1 . 049 35 . 57 0 . 137 4 . 9 Pipe : 7 5 . 60 18 . 5 Disch 32 . 00 100 11 . 0 207 9 . 0 11 . 0 0 . 0 1 . 000 T : 3 . 6 3 . 57 -1 . 3 27L 12 . 0 15 . 3 18 . 5 1 . 049 35 . 57 0 . 158 5 . 6 Pipe : 8 5 . 60 20 . 5 Disch 11 . 00 100 13 . 4 208 9 . 0 13 . 4 0 . 0 1 . 000 E : 1 . 4 5 . 00 -1 . 3 28L 12 . 0 15 . 2 20 . 5 1 . 049 T : 3 . 6 16 . 00 0 . 191 3 . 1 Pipe : 9 5 . 60 18 . 6 Disch 32 . 00 100 11 . 0 209 9 . 0 11 . 0 0 . 0 1 . 000 T : 3 . 6 3 . 57 -1 . 3 29L 12 . 0 15 . 3 18. 6 1 . 049 35 . 57 0 . 159 5 . 6 Pipe : 10 5 . 60 19 . 3 Disch 32 . 00 100 11 . 9 210 9 . 0 11 . 9 0 . 0 1 . 000 T : 3 . 6 3 . 57 -1 . 3 30L 12 . 0 16 . 7 19 . 3 1 . 049 35 . 57 0 . 171 6 . 1 Pipe : 11 0 . 0 0 . 0 12 . 00 100 14 . 1 21L 12 . 0 14 . 1 17 . 8 B1 . 250 ---- 0 . 00 0 . 0 22L 12 . 0 14 . 5 17 . 8 1 . 442 12 . 00 0 . 031 0 . 4 Pipe : 12 0 . 0 17 . 8 21L 8 . 00 100 14 . 5 22L 12 . 0 14 . 5 18 . 1 202 B1 . 250 ---- 0 . 00 0 . 0 23L 12 . 0 15 . 4 35 . 9 1 . 442 8 . 00 0 . 114 0 . 9 Pipe : 12A 0 . 0 35 . 9 22L 3 . 08 100 15 . 4 23L 12 . 0 15 . 4 18 . 6 203 B1 . 250 T : 5 . 7 5 . 71 0 . 0 B1 12 . 0 17 . 6 54 . 5 1 . 442 8 . 79 0 . 247 2 . 2 k SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE : '12/11/2018SYSTEMS\HASS86\DATA\CLEAN WATER SERVICES O&M - AREA E . SDF JOB TITLE : CLEAN WATER - AREA D Pipe Tag K-fac Add Fl Add Fl To Fit : L C (Pt) To Node El (ft) PT (q) Node/ Nom ID Eq. Ln . F (Pe) NC Frm Node El (ft) PT Tot . (Q) Disch Act ID (ft . ) T Pf/ft . (Pf) Pipe : 12A1 0 . 0 0 . 0 9 . 08 100 12 . 4 24L 12 . 0 12 . 4 16 . 8 B1 . 250 ---- 0 . 00 0 . 0 25L 12 . 0 12 . 7 16 . 8 1 . 442 9 . 08 0 . 028 0 . 3 Pipe : 12B 0 . 0 16 . 8 24L 2 . 92 100 12 . 7 25L 12 . 0 12 . 7 18 . 6 205 B1 . 250 ---- 0 . 00 0 . 0 26L 12 . 0 13 . 0 35 . 4 1 . 442 2 . 92 0 . 112 0 . 3 Pipe : 12C 0 . 0 35 . 4 25L 10 . 00 100 13 . 0 26L 12 . 0 13 . 0 17 . 2 206 B1 . 250 ---- 0 . 00 0 . 0 27L 12 . 0 15 . 3 52 . 6 1 . 442 10 . 00 0 . 232 2 . 3 Pipe : 12D 0 . 0 52 . 6 26L 1 . 08 100 15 . 3 27L 12 . 0 15 . 3 18 . 5 207 B1 . 250 T : 5 . 7 5 . 71 0 . 0 B2 12 . 0 18 . 0 71 . 1 1 . 442 6 . 79 0 . 405 2 . 7 Pipe : 12E 0 . 0 0 . 0 2 . 92 100 15 . 2 28L 12 . 0 15 . 2 20 . 5 B1 . 250 ---- 0 . 00 0 . 0 29L 12 . 0 15 . 3 20 . 5 1 . 442 2 . 92 0 . 041 0 . 1 Pipe : 12F 0 . 0 20 . 5 28L 10 . 00 100 15 . 3 29L 12 . 0 15 . 3 18 . 6 209 B1 . 250 ---- 0 . 00 0 . 0 30L 12 . 0 16 . 7 39 . 1 1 . 442 10 . 00 0 . 134 1 . 3 Pipe : 12G 0 . 0 39 . 1 29L 1 . 08 100 16 . 7 30L 12 . 0 16 . 7 19 . 3 210 B1 . 250 T : 5 . 7 5 . 71 0 . 0 B3 12 . 0 18 . 6 58 . 4 1 . 442 6 . 79 0 . 281 1 . 9 Pipe : 12H 0 . 0 0 . 0 13 . 92 100 17 . 6 B1 12 . 0 17 . 6 54 . 5 23L B2 . 000 ---- 0 . 00 0 . 0 B2 12 . 0 18 . 0 54 . 5 2 . 157 13 . 92 0 . 035 0 . 5 Pipe : 121 0 . 0 54 . 5 Bl 5 . 17 100 18 . 0 B2 12 . 0 18 . 0 71 . 1 27L B2 . 000 ---- 0 . 00 0 . 0 Ml 12 . 0 18 . 9 125 . 6 2 . 157 5 . 17 0 . 163 0 . 8 Pipe : 12J 0 . 0 0 . 0 8 . 08 100 18 . 6 B3 12 . 0 18 . 6 58 . 4 30L B2 . 000 ---- 0 . 00 0 . 0 Ml 12 . 0 18 . 9 58 . 4 2 . 157 8 . 08 0 . 040 0 . 3 Pipe : 12K 0 . 0 58 . 4 B3 4E : 17 . 1 11 . 17 100 18 . 9 M1 12 . 0 18 . 9 125 . 6 B2 B2 . 000 T : 8 . 6 34 . 26 0 . 0 P1 12 . 0 33 . 9 184 . 0 2 . 157 D : 8 . 6 45 . 43 0 . 331 15 . 0 Pipe : 12L 0 . 0 0 . 0 101 . 00 120 33 . 9 P1 12 . 0 33 . 9 184 . 0 M1 2 . 500 4E : 24 . 0 36 . 00 0 . 9 P2 10 . 0 51 . 5 184 . 0 2 . 469 T : 12 . 0 137 . 00 0 . 122 16 . 7 Pipe : 12M 0 . 0 0 . 0 150 . 00 120 51 . 5 P2 10 . 0 51 . 5 184 . 0 P1 4 . 000 4E : 40 . 0 60 . 00 -3 . 5 A4 18 . 0 50 . 4 184 . 0 4 . 026 T : 20 . 0 210 . 00 0 . 011 2 . 4 I( SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE : 12/11/2018SYSTEMS\HASS86\DATA\CLEAN WATER SERVICES O&M - AREA E . SDF ` JOB TITLE : CLEAN WATER - AREA D Pipe Tag K-fac Add Fl Add Fl To Fit : L C (Pt) To Node El (ft) PT (q) Node/ Nom ID Eq. Ln . F (Pe) NC Frm Node El (ft) PT Tot . (Q) Disch Act ID (ft . ) T Pf/ft . (Pf) Pipe : 14 0 . 0 0 . 0 200 . 00 120 50 . 4 A4 18 . 0 50 . 4 184 . 0 P2 B4 . 000 5E : 65 . 0 65 . 00 0 . 0 TOR 18 . 0 52 . 7 184 . 0 4 . 260 265 . 00 0 . 009 2 . 3 Pipe : 15 0 . 0 0 . 0 17 . 00 120 52 . 7 TOR 18 . 0 52 . 7 184 . 0 A4 B8 . 000 G: 5 . 0 5 . 00 7 . 4 BOR 1 . 0 60 . 1 184 . 0 8 . 249 22 . 00 0 . 000 0 . 0 Pipe : 16 0 . 0 0 . 0 205 . 00 140 60 . 1 BOR 1 . 0 60 . 1 184 . 0 TOR D8 . 000 2E : 62 . 0 62 . 00 2 . 2 BF2 -4 . 0 62 . 3 184 . 0 8 . 390 267 . 00 0 . 000 0 . 1 Pipe : 17 0 . 0 Fixed Pressure Loss Device BF2 -4 . 0 62 . 3 184 . 0 BOR 5 . 0 psi, 184 . 0 gpm BF1 -4 . 0 67 . 3 184 . 0 Pipe : 18 0 . 0 0 . 0 E : 31 . 0 370 . 00 140 67 . 3 BF1 -4 . 0 67 . 3 184 . 0 BF2 D8 . 000 2T118 . 0 156 . 00 0 . 0 UG1 -4 . 0 67 . 4 184 . 0 8 . 390 G : 7 . 0 526 . 00 0 . 000 0 . 1 Pipe : 19 0 . 0 0 . 0 E : 22 . 0 10 . 00 140 67 . 4 UG1 -4 . 0 67 . 4 184 . 1 BF1 D6 . 000 T : 47 . 0 74 . 00 -2 . 2 SRC 1 . 0 65 . 3 184 . 1 6 . 280 G: 5 . 0 84 . 00 0 . 001 0 . 1 NOTES (HASS) : (1) Calculations were performed by the HASS 8 . 8 D computer program in accordance with NFPA13 (2016) under license no . 380812802 granted by HRS Systems, Inc . 208 Southside Square Petersburg, TN 37144 (931) 659-9760 (2) The system has been calculated to provide an average imbalance at each node of 0 . 006 gpm and a maximum imbalance at any node of 0 . 197 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 16 . 2 ft/sec at pipe 12K . (4) Items listed in bold print on the cover sheet are automatically transferred from the calculation report . (5) Available pressure at source node SRC under full flow conditions is 96 . 99 psi with a flow of 332 . 90 gpm. a ! SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 EA'1'L : '12/11/2018SYSTEMS\HASS86\DATA\CLEAN WATER SERVICES O&M - AREA E . SDF JOB TITLE : CLEAN WATER - AREA D (6) PIPE FITTINGS TABLE HASS Pipe Table Name : standard.pip PAGE : A MATERIAL: S40 HWC : 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkV1v BfyVly GatVly AlmChk DPV1v NTee F F45E11 1 . 049 2 . 00 5 . 00 2 . 00 5 . 00 6 . 00 1 . 00 10 . 00 2 . 00 5 . 00 1 . 00 2 . 469 6 . 00 12 . 00 4 . 00 14 . 00 7 . 00 1 . 00 10 . 00 10 . 00 12 . 00 3 . 00 4 . 026 10 . 00 20 . 00 6 . 00 22 . 00 12 . 00 2 . 00 20 . 00 20 . 00 20 . 00 4 . 00 PAGE : B MATERIAL : THNWL HWC : 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVly BfyVly GatV1v AlmChk DPV1v NPTee 1 . 442 4 . 00 8 . 00 3 . 00 9 . 00 8 . 00 1 . 00 12 . 00 12 . 00 8 . 00 2 . 157 6 . 00 12 . 00 3 . 00 14 . 00 8 . 00 1 . 00 12 . 00 12 . 00 12 . 00 4 . 260 13 . 00 26 . 00 8 . 00 29 . 00 16 . 00 3 . 00 26 . 00 26 . 00 26 . 00 8 . 249 21 . 00 41 . 00 15 . 00 53 . 00 14 . 00 5 . 00 37 . 00 37 . 00 41 . 00 PAGE : D MATERIAL: DIRON HWC : 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G N Ell Tee LngEll ChkVly BfyVly GatVly NPTee 6 . 280 22 . 00 47 . 00 14 . 00 51 . 00 16 . 00 5 . 00 47 . 00 8 . 390 31 . 00 59 . 00 22 . 00 76 . 00 20 . 00 7 . 00 59 . 00 COSCO FIRE PROTECTION " t ' 2501 SE COLUMBIA WAY, SUITE 100 VANCOUVER, HYDRAULIC CALCULATIONS FOR CLEAN WATER SERVICES - O&M BUILDING 16060 SW 85TH AVENUE TIGARD, OR 97223 DRAWING NUMBER: FP-5 DATE : DEC 11, 2018 -DESIGN DATA- Ar REMOTE AREA NUMBER: D REMOTE AREA LOCATION: AREA D \C"71c4llr ON / OCCUPANCY CLASSIFICATION: ORDINARY HAZARD 2 ., /� 411 DENSITY : . 20 gpm/sq. ft . ` 77506 PE AREA OF APPLICATION: 1500 (1110) sq. ft . 1-18-2019 OREGON CO COVERAGE PER SPRINKLER: 130 sq. ft . v 94, ,LpC TYPE OF SPRINKLERS CALCULATED :QR SSU F,pRY L 0 O ��P NUMBER OF SPRINKLERS CALCULATED : 10 HOSE-STREAM DEMAND OUTSIDE : 250 gpm EXPIRATION DATE:12/31/20 TOTAL WATER REQUIRED (INCLUDING HOSE) : 528 . 3 gpm FLOW AND PRESSURE (AT BASE OF RISER) : 278 . 3 gpm @ 54 . 2 psi TYPE OF SYSTEM:WET WATER SUPPLY Source : CITY MAIN Test Date : 06/07/18 Test By : WYATT FIRE PROTECTION Location : SOUTH END OF HALL BLVD . Static : 98 psi Residual : 76 psi Flow: 1764 . 0 gpm Source Elevation Relative to Finished Flow Level : 13 ft . INSTALLING CONTRACTOR Name : COSCO FIRE PROTECTION Address : 2501 SE COLUMBIA WAY, SUITE 100 Phone : 360-883-6383 Certification number : 67508 NAME OF DESIGNER: DAN FURNO AUTHORITY HAVING JURISDICTION: CITY OF TIGARD NOTES : REMOTE AREA REDUCED 33% FOR QR SPRINKLERS AND 14 ' -3 CEILING HEIGHT PER NFPA 13 (2013) 11 . 2 . 3 . 2 . 3 Calculations performed by HASS under license # 380812802 , granted by HRS SYSTEMS, INC . (Notes continue after pipe calculations results . ) y A SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE : 12/11/2018SYSTEMS\HASS86\DATA\CLEAN WATER SERVICES O&M - AREA D . SDF A JOB TITLE : CLEAN WATER - AREA D WATER SUPPLY ANALYSIS Static : 98 . 00 psi Resid: 76 . 00 psi Flow : 1764 . 0 gpm 120 . 0 LEGEND 100 . 0 _CI 1 g Available pressure lA 1 //,` 95 . 64 psi @ 528 . 3 gpm A 2 q Required pressure G 80 . 0 59 . 76 psi @ 528 . 3 gpm P 1A Avail . Onsite Demand Press R E 95 . 64 psi @ 278 . 3 gpm S 60 . n • 2A 2 2A q Req. OnSite Demand Press . 59 . 76 psi @ 278 . 3 gpm ( A. Source Supply Curve P 40 . 0 B. System Demand Curve C . Available at Source i 20 . 0 B 0 . 0 ......-----..-.......-............ _____________ -.----___---____-----.........................-............________ -14 . 7 400600 800 1000 1200 1400 1600 1800 2000 FLOW (GPM) )te : (1) Dashed Lines indicate extrapolated values from Test Results (2) On Site pressures are based on hose stream deduction at the source r SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE : 9.2/11/2018SYSTEMS\HASS86\DATA\CLEAN WATER SERVICES O&M - AREA D . SDF JOB TITLE : CLEAN WATER - AREA D NFPA WATER SUPPLY DATA SOURCE STATIC RESID . FLOW AVAIL . TOTAL REQ'D NODE PRESS . PRESS . @ PRESS . @ DEMAND PRESS . TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) SRC 98 . 0 76 . 0 1764 . 0 95 . 6 528 . 3 59 . 8 AGGREGATE FLOW ANALYSIS : TOTAL FLOW AT SOURCE 528 . 3 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 250 . 0 GPM OTHER HOSE STREAM ALLOWANCES 0 . 0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 278 . 3 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES (FT) (PSI) (GPM) 101 14 . 2 K= 5 . 60 21 . 6 26 . 0 102 14 . 2 K= 5 . 60 21 . 6 26 . 0 103 14 . 2 K= 5 . 60 21 . 8 26 . 1 1 104 14 . 2 K= 5 . 60 22 . 2 26 . 4 105 14 . 2 K= 5 . 60 22 . 8 26 . 8 106 14 . 2 K= 5 . 60 23 . 9 27 . 4 107 14 . 2 K= 5 . 60 28 . 2 29 . 8 108 14 . 2 K= 5 . 60 28 . 3 29 . 8 109 14 . 2 K= 5 . 60 28 . 5 29 . 9 110 14 . 2 K= 5 . 60 29 . 0 30 . 2 Al 14 . 2 - - - - 36 . 6 - - - A2 14 . 2 - - - - 36 . 7 - - - A3 14 . 2 - - - - 37 . 7 - - - A4 18 . 0 - - - - 41 . 9 - - - TOR 18 . 0 - - - - 46 . 8 - - - BOR 1 . 0 - - - - 54 . 2 - - - BF2 -4 . 0 - - - - 56 . 5 - - - BF1 -4 . 0 - - - - 61 . 5 - - - UG1 -4 . 0 - - - - 61 . 7 - - - SRC 1 . 0 SOURCE 59 . 8 278 . 3 4 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE : 12/11/2018SYSTEMS\HASS86\DATA\CLEAN WATER SERVICES O&M - AREA D . SDF JOB TITLE : CLEAN WATER - AREA D NFPA3 PIPE DATA Pipe Tag K-fac Add Fl Add Fl To Fit : L C (Pt) To Node El (ft) PT (q) Node/ Nom ID Eq. Ln . F (Pe) Nc Frm Node El (ft) PT Tot . (Q) Disch Act ID (ft . ) T Pf/ft . (Pf) Pipe : 1 5 . 60 26 . 0 Disch 7 . 75 120 21 . 6 101 14 . 2 21 . 6 0 . 0 B2 . 000 ---- 0 . 00 0 . 0 102 14 . 2 21 . 6 26 . 0 2 . 157 7 . 75 0 . 006 0 . 0 Pipe : 2 5 . 60 26 . 0 Disch 7 . 92 120 21 . 6 102 14 . 2 21 . 6 26 . 0 101 B2 . 000 ---- 0 . 00 0 . 0 103 14 . 2 21 . 8 52 . 0 2 . 157 7 . 92 0 . 023 0 . 2 Pipe : 3 5 . 60 26 . 1 Disch 8 . 50 120 21 . 8 103 14 . 2 21 . 8 52 . 0 102 B2 . 000 ---- 0 . 00 0 . 0 104 14 . 2 22 . 2 78 . 2 2 . 157 8 . 50 0 . 048 0 . 4 Pipe : 4 5 . 60 26 . 4 Disch 7 . 75 120 22 . 2 104 14 . 2 22 . 2 78 . 2 103 B2 . 000 ---- 0 . 00 0 . 0 105 14 . 2 22 . 8 104 . 6 2 . 157 7 . 75 0 . 083 0 . 6 Pipe : 5 5 . 60 26 . 8 Disch 8 . 42 120 22 . 8 105 14 . 2 22 . 8 104 . 6 104 B2 . 000 ---- 0 . 00 0 . 0 106 14 . 2 23 . 9 131 . 3 2 . 157 8 . 42 0 . 126 1 . 1 Pipe : 6 5 . 60 27 . 4 Disch 59 . 33 120 23 . 9 106 14 . 2 23 . 9 131 . 3 105 B2 . 000 T: 12 . 0 12 . 00 0 . 0 A2 14 . 2 36 . 7 158 . 7 2 . 157 71 . 33 0 . 179 12 . 8 Pipe : 7 5 . 60 29 . 8 Disch 8 . 50 120 28 . 2 107 14 . 2 28 . 2 0 . 0 B2 . 000 ---- 0 . 00 0 . 0 108 14 . 2 28 . 3 29 . 8 2 . 157 8 . 50 0 . 008 0 . 1 Pipe : 8 5 . 60 29 . 8 Disch 7 . 75 120 28 . 3 108 14 . 2 28 . 3 29 . 8 107 B2 . 000 ---- 0 . 00 0 . 0 109 14 . 2 28 . 5 59 . 5 2 . 157 7 . 75 0 . 029 0 . 2 Pipe : 9 5 . 60 29 . 9 Disch 8 . 42 120 28 . 5 109 14 . 2 28 . 5 59 . 5 108 B2 . 000 ---- 0 . 00 0 . 0 110 14 . 2 29 . 0 89 . 4 2 . 157 8 . 42 0 . 0-6-2- 0 . 5 Pipe : 10 5 . 60 30 . 2 Disch 59 . 33 120 29 . 0 110 14 . 2 29 . 0 89 . 4 109 B2 . 000 T : 12 . 0 12 . 00 0 . 0 Al 14 . 2 36 . 6 119 . 6 2 . 157 71 . 33 0 . 106 7 . 6 Pipe : 11 0 . 0 0 . 0 14 . 25 120 36 . 6 Al 14 . 2 36 . 6 119 . 6 110 4 . 000 ---- 0 . 00 0 . 0 A2 14 . 2 36 . 7 119 . 6 4 . 026 14 . 25 0 . 005 0 . 1 Pipe : 12 0 . 0 119 . 6 Al 20 . 50 120 36 . 7 A2 14 . 2 36 . 7 158 . 7 106 4 . 000 2E : 20 . 0 20 . 00 0 . 0 A3 14 . 2 37 . 7 278 . 3 4 . 026 40 . 50 0 . 024 1 . 0 Pipe : 13 0 . 0 0 . 0 151 . 00 120 37 . 7 A3 14 . 2 37 . 7 278 . 3 A2 4 . 000 7E : 70 . 0 90 . 00 -1 . 6 A4 18 . 0 41 . 9 278 . 3 4 . 026 T : 20 . 0 241 . 00 0 . 024 5 . 9 y SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: '12/11/2018SYSTEMS\HASS86\DATA\CLEAN WATER SERVICES O&M - AREA D . SDF JOB TITLE : CLEAN WATER - AREA D Pipe Tag K-fac Add Fl Add Fl To Fit : L C (Pt) To Node El (ft) PT (q) Node/ Nom ID Eq. Ln . F (Pe) NC Frm Node El (ft) PT Tot . (Q) Disch Act ID (ft . ) T Pf/ft . (Pf) Pipe : 14 0 . 0 0 . 0 200 . 00 120 41 . 9 A4 18 . 0 41 . 9 278 . 3 A3 B4 . 000 5E : 65 . 0 65 . 00 0 . 0 TOR 18 . 0 46 . 8 278 . 3 4 . 260 265 . 00 0 . 018 4 . 9 Pipe : 15 0 . 0 0 . 0 17 . 00 120 46 . 8 TOR 18 . 0 46 . 8 278 . 3 A4 B8 . 000 G: 5 . 0 5 . 00 7 . 4 BOR 1 . 0 54 . 2 278 . 3 8 . 249 22 . 00 0 . 001 0 . 0 Pipe : 16 0 . 0 0 . 0 205 . 00 140 54 . 2 BOR 1 . 0 54 . 2 278 . 3 TOR D8 . 000 2E : 62 . 0 62 . 00 2 . 2 BF2 -4 . 0 56 . 5 278 . 3 8 . 390 267 . 00 0 . 001 0 . 1 Pipe : 17 0 . 0 Fixed Pressure Loss Device BF2 -4 . 0 56 . 5 278 . 3 BOR 5 . 0 psi, 278 . 3 gpm BF1 -4 . 0 61 . 5 278 . 3 Pipe : 18 0 . 0 0 . 0 E : 31 . 0 370 . 00 140 61 . 5 BF1 -4 . 0 61 . 5 278 . 3 BF2 D8 . 000 2T118 . 0 156 . 00 0 . 0 UG1 -4 . 0 61 . 7 278 . 3 8 . 390 G: 7 . 0 526 . 00 0 . 001 0 . 3 Pipe : 19 0 . 0 0 . 0 E : 22 . 0 10 . 00 140 61 . 7 UG1 -4 . 0 61 . 7 278 . 3 BF1 D6 . 000 T : 47 . 0 74 . 00 -2 . 2 SRC 1 . 0 59 . 8 278 . 3 6 . 280 G: 5 . 0 84 . 00 0 . 002 0 . 2 NOTES (HASS) : (1) Calculations were performed by the HASS 8 . 8 D computer program in accordance with NFPA13 (2016) under license no . 380812802 granted by HRS Systems, Inc . 208 Southside Square Petersburg, TN 37144 (931) 659-9760 (2) The system has been calculated to provide an average imbalance at each node of 0 . 003 gpm and a maximum imbalance at any node of 0 . 059 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 13 . 9 ft/sec at pipe 6 . (4) Items listed in bold print on the cover sheet are automatically transferred from the calculation report . (5) Available pressure at source node SRC under full flow conditions is 1 94 . 84 psi with a flow of 618 . 29 gpm. 4 A SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE : 12/11/2018SYSTEMS\HASS86\DATA\CLEAN WATER SERVICES O&M - AREA D . SDF * JOB TITLE : CLEAN WATER - AREA D (6) PIPE FITTINGS TABLE HASS Pipe Table Name : standard.pip PAGE : A MATERIAL : S40 HWC : 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkViv BfyViv GatVly AlmChk DPV1v NTee F F45E11 4 . 026 10 . 00 20 . 00 6 . 00 22 . 00 12 . 00 2 . 00 20 . 00 20 . 00 20 . 00 4 . 00 PAGE : B MATERIAL : THNWL HWC : 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkV1v BfyViv GatVly AlmChk DPV1v NPTee 2 . 157 6 . 00 12 . 00 3 . 00 14 . 00 8 . 00 1 . 00 12 . 00 12 . 00 12 . 00 4 . 260 13 . 00 26 . 00 8 . 00 29 . 00 16 . 00 3 . 00 26 . 00 26 . 00 26 . 00 8 . 249 21 . 00 41 . 00 15 . 00 53 . 00 14 . 00 5 . 00 37 . 00 37 . 00 41 . 00 PAGE : D MATERIAL: DIRON HWC : 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G N Ell Tee LngEll ChkVly BfyViv GatVly NPTee 6 . 280 22 . 00 47 . 00 14 . 00 51 . 00 16 . 00 5 . 00 47 . 00 8 . 390 31 . 00 59 . 00 22 . 00 76 . 00 20 . 00 7 . 00 59 . 00 W * S •y Hydraulic Summary Job Number:24PD5199-Clean Water services Report Description:Light Hazard(1) Job Job Number Design Engineer 24PD5199 Tim Carpenter Job Name: State Certification/License Number Clean Water Services 67508 Address 1 AHJ 16060 SW 85th Ave. City of Tigard Address 2 Job Sitet8uilding Tigard,OR 97223 Address 3 Drawing Name Clean Water- FP2-Building F Piping Plan.cad System Remote Area(s) Most Demanding Sprinkler Data Occupancy Job Suffix 5.6 K-Factor 14.82 at 7.000 Light Hazard Clean Water services Hose Allowance At Source Density Area of Application 100.00 0.10gpm/ft2 1500ft2(Actual 1158ft2) Additional Hose Supplies Number Of Sprinklers Calculated Coverage Per Sprinkler Node Flow(aom) 14 145ft2 re.40,4#4*.,r"14' 77506 PE 1-18-2019 Total Hose Streams OREGON 100.00 v co System Flow Demand Total Water Required(Including Hose Allowance) 9N e)OO 232.68 332.68 vFQ l l�P� Maximum Pressure Unbalance In Loops L 0'N 0.000 Maximum Velocity Above Ground EXPIRATION DATE:12/31/20 20.43 between nodes 9 and 10 Maximum Velocity Under Ground 5.34 between nodes 4 and 5 Volume capacity of Wet Pipes Volume capacity of Dry Pipes 399.82ga1 Supplies Hose Flow Static Residual Flow Available Total Demand Required Safety Margin Node Name (gpm) (psi) (psi) @ (gpm) (psi) @ (gpm) (psi) (psi) 1 Water Supply 100.00 98.000 76.000 1764.00 96.995 332.68 52.103 44.892 Contractor Contractor Number Contact Name Contact Title 24PC0190 Tim Carpenter Design/PM Name of Contractor Phone Extension Cosco Fire Protection 360-883-6383 Address 1 FAX 2501 SE Columbia Way#100 360-883-6390 Address 2 Email Vancouver,WA 98661 tcarpenter@coscofire.com Address 3 Web-Site www.coscofire.com ©M.E.P.CAD,Inc. 411 AutoSPRINK 2018 v14.0.3.0 6/9/2018 3:47:12PM Page 1 Til M. i Hydraulic Graph Job Number:24PD5199-Clean Water services Report Description:Light Hazard(1) Water Supply at Node 1 100 tatic Pressure 98.000 90 80 1764.00 @ 76.000 70 60 'a 232.68 @ 52.103 50 332.68 with hose streams tll N 40 System demand curve 30 20 10 0 7 ulliii111 111111111 11 111 1 1 1 1 111111111 1 1 1 1 1 1 1 I I I I I I I I I I I 1 1 1 1 1 1 1 I I I I I I I I 1 0350 700 1050 1400 1750 2100 2450 2800 3150 3500 Water flow,gpm - Myriam!.Graph Water Supply at Node 1 Static:Pressure 98.000 Residue!:Pressure 76.000 @ 1764.00 Available Pressure et Time of rest 96.995 @ 332.68 System Demand 52.103 @ 232.68 System Demand(Doodled Hose Mowaace at Same) 52.103 @ 332.68 ©M.E.P.CAD,Inc. 1111 AutoSPRINK 2018 v14.0.3.0 6/9/2018 3:47:14PM Page 2 N r �� Summary Of Outflowing Devices Job Number:24PD5199-Clean Water services i5 Report Description:Light Hazard(1) Actual Flow Minimum Flow K-Factor Pressure Device (gpm) (gpm) (K) (Psi) Sprinkler 100 20.77 14.47 5.6 13.750 Sprinkler 101 20.46 14.47 5.6 13.344 Sprinkler 102 17.79 14.47 5.6 10.093 Sprinkler 103 16.46 14.47 5.6 8.634 Sprinkler 104 15.72 14.47 5.6 7.878 Sprinkler 105 17.23 14.47 5.6 9.468 Sprinkler 106 15.43 14.47 5.6 7.593 Sprinkler 107 15.20 14.47 5.6 7.369 Sprinkler 108 17.09 14.47 5.6 9.308 Sprinkler 109 15.79 14.47 5.6 7.949 Sprinkler 110 14.95 14.47 5.6 7.127 Sprinkler 111 15.07 14.47 5.6 7.241 I* Sprinkler 112 14.82 14.47 5.6 7.000 Sprinkler 206 15.93 14.47 5.6 8.088 4* Most Demanding Sprinkler Data ©M.E.P.CAD,Inc. =?1 AutoSPRINK 2018 v14.0.3.0 6/9/2018 3:47:15PM Page 3 PV1, 1r - IA p 1., Mode Analysis 1 Job Number:24PD5199-Clean Water services Report Description:Light Hazard(1) Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 1 -5'-0 S 52.103 232.68 100 15'-4'% Spr(-13.750) 13.750 20.77 101 15'-7'% Spr(-13.344) 13.344 20.46 102 15'-1'% Spr(-10.093) 10.093 17.79 103 15'-4'% Spr(-8.634) 8.634 16.46 104 15'-7'% Spr(-7.878) 7.878 15.72 105 15'-1'% Spr(-9.468) 9.468 17.23 106 15'-10'% Spr(-7.593) 7.593 15.43 107 15'-7'% Spr(-7.369) 7.369 15.20 108 15'-1'% Spr(-9.308) 9.308 17.09 109 15'-4'% Spr(-7.949) 7.949 15.79 110 15'-10 Spr(-7.127) 7.127 14.95 111 15'-7'% Spr(-7.241) 7.241 15.07 112 15'-10 Spr(-7.000) 7.000 14.82 206 15'-4'% Spr(-8.088) 8.088 15.93 2 , -5'-0 E(30'-6%) 52.068 , 3 -5'-0 E(22'-1) 52.044 4 -5'-0 E(16'-8%) 51.825 5 -5'-0 50.707 6 1'-1'% 47.772 7 15-3 PO(T-5) 9.684 8 14'-0'% PO(T-5) 12.139 9 2'-11 40.132 10 14'-0'% P0(7'-5) 16.454 11 15'-3 PO(T-5) 10.327 12 14'-0% PO(T-5) 12.900 13 15'-3 P0(7'-5) 9.520 14 14'-0% PO(T-5) 11.944 ©M.E.P.CAD,Inc. `0F4 AutoSPRINK 2018 v14.0.3.0 6/9/2018 3:47:16PM Page 4 h.r K It l ♦ Y M r-1 ' Hydraulic Analysis Job Number:24PD5199-Clean Water services Report Description:Light Hazard(1) Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length ea Route 1 --BL 1.4420 14.82 2.91 120 0.015862 9'-1'% Pf 0.145 112 15'-10 14.82 5.6 7.000 Sprinkler Pe 0.096 111 15-7% 7.241 9'-1''/ Pv BL 1.4420 29.88 5.87 120 0.058087 10'-4 Pf 0.600 111 15-71/2 15.07 5.6 7.241 Sprinkler Pe 0.108 109 15-41/2 7.949 10'-4 Pv BL L 1.4420 45.67 8.97 120 0.127314 4'-61/2 Pf 1.524 109 15-41/2 15.79 5.6 7.949 Sprinkler, 7'-5 Pe 0.048 13 15-3 9.520 PO(T-5) 11.-11% Pv BL 1.4420 62.76 12.33 120 0.229188 0'-10'% Pf 1.900 13 15-3 17.09 9.520 Flow(q)from Route 4 7-5 Pe 0.523 14 14'-0% 11.944 P0(7-5) 8'-3% Pv CM 2.1570 62.76 5.51 120 0.032248 6'-01/2 Pf 0.195 14 14'-0'% 11.944 Pe 8 14'-0%z 12.139 6'-0'% Pv CM 2.1570 126.07 11.07 120 0.117198 6'-6 Pf 0.762 8 14'-0'% 63.31 12.139 Flow(q)from Route 2 Pe 12 14'-0%z 12.900 6'-6 Pv CM 2.1570 191.46 16.81 120 0.253898 14'-0 Pf 3.553 12 14'-0'% 65.39 12.900 Flow(q)from Route 3 Pe 10 14'-0'% 16.454 14'-0 Pv CM 2.1570 232.68 20.43 120 0.364184 39'-5'% Pf 18.848 10 14'-0% 41.22 16.454 Flow(q)from Route 7 12'-3'% Pe 4.830 9 2'-11 40.132 2fE(6'-2),f(-0.000) 51'-9 Pv DY 2.4690 232.68 15.59 120 0.188622 0'-0 Pf 6.863 9 2'-11 40.132 Pe 0.777 6 1'-1'% 47.772 BFP(-6.863) 0'-0 Pv UG 4.2600 232.68 5.24 150 0.008763 12'-0 Pf 0.279 6 1'-1'% 47.772 19'-10'% Pe 2.655 5 -5-0 50.707 E(19'-10%) 31-10'% Pv UG _ 4.2200 232.68 5.34 140 0.010424 77'-2 Pf 1.118 5 -5-0 50.707 30'-1'/x Pe 4 -5-0 51.825 2EE(6'-8%),E(16'-8%) 107-3% Pv UG 6.2800 232.68 2.41 140 0.001504 75-0 Pf 0.219 4 -5-0 51.825 70'-11 Pe 3 -5'-0 52.044 GV(4'-8%),3E(22'-1) 145-11 Pv UG 8.3900 232.68 1.35 140 0.000367 35-0 Pf 0.024 3 -5'-0 52.044 30'-6'% Pe 2 -5'-0 52.068 E(30'-6%) 65-6% Pv UG 6.2800 232.68 2.41 140 0.001504 23'-0 Pf 0.035 2 -5-0 52.068 Pe 1 -5-0 52.103 Water Supply 23'-0 Pv 100.00 Hose Allowance At Source 1 332.68 we Route 2 BL 1.4420 14.95 2.94 120 0.016127 9'-1'% Pf 0.147 110 15-10 14.95 5.6 7.127 Sprinkler Pe 0.096 107 15-7% 7.369 9'-1% Pv BL 1.4420 30.15 5.92 120 0.059050 10'-4 Pf 0.610 107 15'-7'% 15.20 5.6 7.369 Sprinkler Pe 0.108 206 15-4% 8.088 10'-4 Pv BL 1.4420 46.08 9.05 120 0.129406 4'-6% Pf 1.549 206 15-4% 15.93 5.6 8.088 Sprinkler, 7-5 Pe 0.048 7 15-3 9.684 P0(7-5) 11'-111/2 Pv BL 1.4420 63.31 12.44 120 0.232917 0'-10% Pf 1.931 7 15-3 17.23 9.684 Flow(q)from Route 5 7'-5 Pe 0.523 8 14'-0'% 12.139 P0(7-5) 8'-3'% Pv G Route 3 BL 1.4420 15.43 3.03 120 0.017100 10'-4 Pf 0.177 106 15-10% 15.43 5.6 7.593 Sprinkler Pe 0.108 104 15-7% 7.878 10'-4 Pv BL 1.4420 31.15 6.12 120 0.062712 10'-4 Pf 0.648 104 15-7% 15.72 5.6 7.878 Sprinkler Pe 0.108 103 15-4% 8.634 10'-4 Pv ,,©M.E.P.CAD,Inc. do AutoSPRINK 2018 v14.0.3.0 6/9/2018 3:47:18PM Page 5 1 v, ;i- Hydraulic Analysis Job Number:24PD5199-Clean Water services Report Description:Light Hazard(1) Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length BL 1.4420 47.60 9.35 120 0.137446 4'-6'% Pf 1.645 103 15'-4'% 16.46 5.6 8.634 Sprinkler, 7'-5 Pe 0.048 11 15'-3 10.327 PO(T-5) 11'-11% Pv BL 1.4420 65.39 12.85 120 0.247314 0'-10'% Pf 2.050 11 15'-3 17.79 10.327 Flow(q)from Route 6 7'-5 Pe 0.523 12 14'-0'% 12.900 P0(7-5) 8'-3% Pv ow Route 4 BL 1.4420 17.09 3.36 120 0.020646 5'-9'% Pf 0.273 108 15'-1'% 17.09 5.6 9.308 Sprinkler, 7'-5 Pe -0.061 13 15'-3 9.520 PO(T-5) 13'-3 Pv GO Route 5 BL 1.4420 17.23 3.39 120 0.020973 5'-91/2 Pf 0.278 105 15'-1'% 17.23 5.6 9.468 Sprinkler, 7'-5 Pe -0.061 7 15'-3 9.684 P0(7'-5) 13'-3 Pv w Route 6 BL 1.4420 17.79 3.50 120 0.022252 5'-9'% Pf 0.294 102 15'-1% 17.79 5.6 10.093 Sprinkler, 7'-5 Pe -0.061 11 15'-3 10.327 PO(7'-5) 13'-3 Pv GO Route 7 BL 1.4420 20.46 4.02 120 0.028808 10'-4 Pf 0.298 101 15'-7'/ 20.46 5.6 13.344 Sprinkler Pe 0.108 100 15'-4'% 13.750 10'-4 Pv BL 1.4420 41.22 8.10 120 0.105309 5'-4'% Pf 2.133 100 15'-4'% 20.77 5.6 13.750 Sprinkler, 14'-10'% Pe 0.571 10 14'-0%z 16.454 2P0(7'-5) 20'-3 Pv Equivalent Pipe Lengths of Valves and Fittings(C=120 only) ` C Value Multiplier Actual Inside Diameter 4.87 Value Of C 100 130 140 150 ( Schedule 40 Steel Pipe Inside Diameter ) =Factor Multiplying Factor 0.713 1.16 1.33 1.51 (,,©M.E.P.CAD,Inc. 4,15AutoSPRINK 2018 v14.0.3.0 6/9/2018 3:47:18PM Page 6 i Hydraulic Analysis \ Job Number:24PD5199-Clean Water services ~` Report Description:Light Hazard(1) Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length Pipe Type Legend Units Legend Fittings Legend AO Arm-Over Diameter Inch ALV Alarm Valve BL Branch Line Elevation Foot AngV Angle Valve CM Cross MainFlow m b Bushing DN Drain 9p BaIV Ball Valve DR Drop Discharge gpm BFP Backflow Preventer DY Dynamic Velocity fps BV Butterfly Valve FM Feed Main Pressure psi C Cross Flow Turn 90° FR Feed Riser Length Foot cplg Coupling MS Miscellaneous Friction Loss psi/Foot Cr Cross Run OR Outrigger HWC Hazen-Williams Constant CV Check Valve RN Riser Nipple DeIV Deluge Valve Pt Total pressure at a point in a pipe SP Sprig DPV Dry Pipe Valve ST Stand Pipe Pn Normal pressure at a point in a pipe E 90°Elbow UG Underground Pf Pressure loss due to friction between points EE 45°Elbow Pe Pressure due to elevation difference between indicated Eel 11'/,°Elbow points Ee2 22W Elbow Pv Velocity pressure at a point in a pipe f Flow Device fd Flex Drop FDC Fire Department Connection fE 90°FireLock(TM)Elbow fEE 45°FireLock(TM)Elbow flg Flange FN Floating Node fT FireLock(TM)Tee g Gauge GIoV Globe Valve GV Gate Valve Ho Hose Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PRV Pressure Reducing Valve PrV Pressure Relief Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap ©M.E.P.CAD,Inc. 49 AutoSPRINK 2018 v14.0.3.0 6/9/2018 3:47:18PM Page 7 FOR OFFICE USE ONLY— SITE ADDRESS: This form is recognized by most building departments in the Tri-County area for transmitting information. Please complete this form when submitting information for plan review responses and revisions. This form and the information it provides helps the review process and response to your project. COMMUNITY of Tigard • NITY DEVELOPMENT DEPARTMENT 14 IPIII Transmittal Letter T I G A R D 13125 SW Hall Blvd. • Tigard, Oregon 97223 • 503.718.2439 • tigard-or.gov-. TO: Plans Examiner DATE RECEIVED: DEPT: BUILDING DIVISION iECEIVED JAN 31 2019 FROM: Dan Furno CITY OF- fIGARD COMPANY: Cosco Fire Protection 3UIL®ING DIVISIONi. PHONE: 360-335-5907 RE: 16580 SW 85th Ave. FPS2018-00078 (Site Address) (Permit Number) Clean Water Services (Project name or subdivision name and 1. n : ber) ATTACHED ARE. THE FOLLOW Copies: Description: Copies: Description: 3 Additional set(s) of plans. IlOP CLI Revisions: Cross section(s) and details. Wall bracing and/or lateral analysis. Floor/roof framing. Basement and retaining walls. Beam calculations. Engineer's calculations. 3 Other(explain): Material submittal,hydraulic and seismic calculations. REMARKS: Revisions to fire sprinkler submittal documents. / r FOR OFFICE I1SE ONLY Routed to Permit Technician:` Date: ��---- — CI Initials: Fees Duel Yes n No Fee Description: Amount Due: --Ji. ;pl c.__,, ��; ,_ $ 91,c) $ $ $ Special Instructions: Reprint Permit(per PE): n Yes C No ❑ Done Applicant Notified: ;, Date: r:LZ( 7 //c Initials: 1:\Building\Forms\TransmittalLetter-Revisions.doc 05/25/2012