Specifications (14) RECEDED JAN 2019 Ce.COQ' CI0p�SON BUILDING FIRE ALARM CALCS NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office (503) 255-1966 Fax Job Name: TIGARD CORPORATE CENTER A& PARKING STRUCTURE Job Address: 12123 SW 69TH AVENUE TIGARD, OR 97223 Conductor Wire Gauge I 14 Job Number: Prepared By: Shane Tercek Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) I 3.07 I Date: 11/8/2018 Cable Length In Feet(source to end of line) I 150 Total Circuit Current I 0.168 I Nominal System Voltage I 20.4 I Minimum Device Voltage I 16 I Panel Description: FCI 7100/2D Panel No.: NAC 1.0 Output No.: 1 Point To Point Method EOLv 20.25 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock I I Load Centering Method EOLv I 20.32 I Circuit Within Limits ? YES Dev Device Location Device Model No. & Description CRaandelllla Current Alla m Dista use Frome V It gee e At No. ,I ( Feet) � ,A H/S H '.r.. S 150 2 � ���� ,. �-" � �� _ 75 Cd0.168 20. 1 EXTERIOR FLOW ALARM ASW P-2475W-FR W P5 20.25 2 20.25 34 20.25 4 20.25 5 20.25 6 20.25 7 20.25 8 20.25 9 20.25 10 20.25 111 20.25 12 20.25 13 20.25 144 20.25 15 20.25 16 20.25 17 20.25 18 20.25 10 20.25 20 Tr,r_A Ff1 7100 NAC 1.0 EOLv Calc NAG, 2 CKT (20.4V Nominal).xls OUTPUT 1 NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office (503) 255-1966 Fax Job Name: TIGARD CORPORATE CENTER A& PARKING STRUCTURE Job Address: 12123 SW 69TH AVENUE TIGARD, OR 97223 Conductor Wire Gauge 14 Job Number: Prepared By: Shane Tercek Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) 3.07 Date: 111812018 Cable Length In Feet (source to end of line) 60 Total Circuit Current 0.015 Nominal System Voltage 20.4 Minimum Device Voltage 16 Panel Description: FCI 7100/2D Panel No.: NAC 1.0 Point To Point Method EOLv 20.39 Output No.: 2 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock Load Centering Method EOLv 20.40 Circuit Within Limits ? YES Dev Device Location Device Model No. &Description CandellaRating Current Ala om Previous Device Voltage At Device No. ( Feet) �� r,' ets :.a ,dr z 20.39 �., :;,�. �"�, .�;� �� � :�. �.�._, „ 0.015 60 2ND FLOOR NAC 2.1 &2.2 TRIP 20.39 2 20.39 3 . 20.39 4 20.39 5 20.39 6 20.39 7 20.39 8 20.39 9 20.39 10 20.39 11 20.39 12 20.39 13 20.39 14 20.39 15 20.39 16 20.39 17 20.39 18 20.39 10 20.39 20 Trn_c, Fri 7100 NAC 1.0 EOLv Calc NAC, 2 CKT (20.4V Nominal).xls OUTPUT 2 FACP BATTERY CALCULATIONS CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office, (503) 257-7121 Fax JOB NAME: Tigard Corporate Center Bldg"A" &Parking Structure JOB ADDRESS: 12123 SW 69TH AVENUE TIGARD,OR DATE: 11/8/2018 JOB NUMBER: PANEL DESCRIPTION: FCI 7100/2D BY:Shane Tercek DEVICE TOTAL DEVICE TOTAL STANDBY STANDBY ALARM ALARM DEVICE DESCRIPTION QUANTITY CURRENT CURRENT CURRENT CURRENT 'axy ',4:4;444-iihex"" - . IWOIO e FACP INTERNAL COMPONENTS0.00000 0.000 FCI 7100/2D FACP 1 0.085 0.08500 0.105 0.105 FCI 7100 LCD REMOTE ANNUNCIATOR 0.0500 0.08500 0.075 0.000 FCI ASD-PL PHOTO SMK DET WI BASE 6 0.0002 0.00120 0.005 0.030 FCI MS6 MANUAL PULL STATION WI AMM-2 1 0.0002 0.000200 0.005 0.005 Duct Smoke Det I AMM-2 2 0.0132 0.026400 0.067 0.134 SPKLR FLOW SWITCH WI AMM-2 1 0.0002 0.00020 0.005 0.005 SPKLR SUPV SWITCH WIAMM-2 2 0.0002 0.00040 0.005 0.010 FCI AOM-2 RELAY MODULES 5 0.0002 0.00100 0.005 0.025 NOTIFICATION APPLIANCES r,V � "; � MO 0.168 0.168 Wheelock ASWP-2475W-FW Outside H/S (H) I 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 AUXILLIARY DEVICES %-e.',,4071V717 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 STANDBY TOTAL CURRENT: I I 0.19940 STANDBY HOURS: 24 STANDBY AMP HOURS: 4.78560 0.482 ALARM TOTAL CURRENT: ALARM MINUTES: ALARM AMP HOURS: I 0.05402 TOTAL CALCULATED AMP HOURS 1 4.826 APPLIED SAFETY FACTOR 1.20 MINIMUM AMP HOURS REQUIRED 5.791 SELECTED BATTERY SIZE 12 EACH 12 VOLT, 7 AMP HOUR BATTERIES TCC-A FCI 7100 NAC 1.0 Batt Calc.xls NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office (503) 255-1966 Fax Job Name: Tigard Corporate Center Building-A Job Address: 12123 SW 69th Ave Tigard, OR 97223 Conductor Wire Guage I 14 Job Number: Prepared By: Shane Tercek Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) I 3.07 I Date: 11/5/2018 Cable Length In Feet (source to end of line) I 408 Total Circuit Current I 1.352 I Nominal System Voltage I 20.4 I Panel Description: Silent Knight 5495-7 Power Supply Minimum Device Voltage ( 16 I Panel No.: NAC 2.1I Output No.: 1 Point To Point Method EOLv 18 .59 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock I I Load Centering Method EOLv I 18.71 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At Rating Current Previous Device Device No. ( Feet) rfar, 1 FLOOR 1 HSWC (115) H/S-Cell, White, Hi 115 Cd 0.197 35 20.110.81 2 FLOOR 1 STWC (30) Stb-Ceil,White 30 Cd 0.085 42 19.58 3 FLOOR 1 HSWC (15) H/S-Ceil, White, Hi 15 Cd 0.082 35 19.43 4 FLOOR 1 STWC (30) Stb-Ceil, White 30 Cd 0.085 25 19.29 5 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 26 17 19.20 6 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.06119.08 7 FLOOR 1 HSWC (75) H/S-Ceil, White, Hi 75 Cd 0.148 24 18.94 8 FLOOR 1 STWC (30) Stb-Ceil, White 30 Cd 0.085 38 9 FLOOR 1 STWC (75) Stb-Ceil, White 75 Cd 0.135 37 18.81 18.73 10 FLOOR 1 HSWC (15) H/S-Ceil, White, Hi 15 Cd 0.082 30 18.67 11 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 34 15 Cd 0.061 17 18.64 12 FLOOR 1 STWC (15) Stb-Ceil, White 18.61 13 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 18 14 FLOOR 1 HSWC (75) H/S-Ceil, White, Hi 75 Cd 0.148 30 18.59 18.59 15 18.59 16 18.59 17 18.59 18 18.59 19 18.59 20 OUTPUT 1 Tr`r`_A NAr. 7 1 F_OLv Calc.xls NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office (503) 255-1966 Fax Job Name: Tigard Corporate Center Building-A Job Address: 12123 SW 69th Ave Tigard, OR 97223 Conductor Wire Guage I 14 Job Number: Prepared By: Shane Tercek Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) I 3.07 I Date: 11/5/2018 Cable Length In Feet (source to end of line) I 437 Total Circuit Current I 1.406 I Nominal System Voltage I 20.4 I Panel Description: Silent Knight 5495-7 Power Supply Minimum Device Voltage I 16 I Panel No.: NAC 2.1 Output No.: 2 Point To Point Method EOLv 18.41 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock I Load Centering Method EOLv 18.51 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description CRaandelllla Alarm Distance s Frome V Magee e At NNo. ( Feet) r. y `" e. ,ry . �s 1 .F y, �. _., 62 19.86 1 FLOOR 1 HSWC (150) H/S-Cell, White, Hi 150 Cd 0.242 1 30 Cd 0.085 40 19.58 2 FLOOR 1 STWC (30) Stb-Ceil, White 20 19.39 FLOOR 1 4 3 FLOOR 1 HSWC (30) H/S-Cell, White, Hi 30 Cd 0.102 28 19.27 STWC (15) Stb-Ceil, White 15 Cd 0.061 15 Cd 0.061 17 19.17 5 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 16 19.17 6 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 15 19.019 7 FLOOR 1 STWC (15) Stb-Ceil, White 31 19 88 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 8 22 18.78 9 FLOOR 1 HSWC (30) H/S-Cell, White, Hi 30 Cd 0.102 212 18.718 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 10 18.6 0.061 15 6 11 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd218.616 1 12 FLOOR 1 HSWC (15) H/S-Cell, White, Hi 15 Cd 0.082 13 FLOOR 138 18.52 STWC (15) Stb-Ceil, White 15 Cd 0.061 FLOOR 118.47 15 26 14 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.06126 18.44 STWC (15) Stb-Cell, White 15 Cd 0.061 0.061 13 18.43 FLOOR 1 17 16 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 16 18.43 STWC (15) Stb-Ceil, White 15 Cd 0.061 0.061 14 18.41 98 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd18.41 19 18.41 20 OUTPUT 2 -rrr_A NIA.r. 9 1 EOLv Calc.xls NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office (503) 255-1966 Fax Job Name: Tigard Corporate Center Building-A Job Address: 12123 SW 69th Ave Tigard, OR 97223 Conductor Wire Guage I 14 Job Number: Prepared By: Shane Tercek Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) I 3.07 Date: 11/5/2018 Cable Length In Feet (source to end of line) I 388 Total Circuit Current I 1.347 I Nominal System Voltage I 20.4 I Panel Description: Silent Knight 5495-7 Power Supply Minimum Device Voltage I 16 ( Panel No.: NAC 2.1 Output No.: 3 Point To Point Method EOLv 18.70 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock I I Load Centering Method EOLv I 18.80 I Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At Rating Current Previous Device Device No. ( Feet) ' , _ `,, ir, 9 ?dal;411 . ':::/> i l- 2014 1 FLOOR 1 HSWC (75) H/S-Ceil, White, Hi 75 Cd 0.148 32 19.95 2 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 25 3 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 23 19.7915 Cd 0.061 24 19.63 4 FLOOR 1 STWC (15) Stb-Ceil, White 19.54 5 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 15 6 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 24 19.4015 Cd 0.061 13 19.33 7 FLOOR 1 STWC (15) Stb-Ceil, White 3 8 FLOOR 1 HSWC (15) H/S-Ceil, White, Hi 15 Cd 0.082 20 19.19.322 9 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 17 16 19.08 10 FLOOR 1 STWC (15) Stb-Cell, White 15 Cd 0.061 18.96 11 FLOOR 1 HSWC (75) H/S-Ceil, White, Hi 75 Cd 0.148 31 12 15 Cd 0.061 23 18.89 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 14 18.85 13 FLOOR 1 STWC (15) Stb-Ceil, White 18 85 14 FLOOR 1 STWC (75) Stb-Ceil, White 75 Cd 0.135 31 15 FLOOR 1 HSWC (30) H/S-Ceil, White, Hi 30 Cd 0.102 44 3 18.718.73 16 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 24 1 17 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 12 18.70 18.70 18 18.70 2 0 18.70 20 OUTPUT 3 rt-rs_o nior. 9 1 EnLv Calc.xls NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office (503) 255-1966 Fax Job Name: Tigard Corporate Center Building-A Job Address: 12123 SW 69th Ave Tigard, OR 97223 Conductor Wire Guage I 14 I Job Number: Prepared By: Shane Tercek Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) I 3.07 I Date: 11/5/2018 Cable Length In Feet (source to end of line) I 395 I Total Circuit Current I 1.228 I Nominal System Voltage I 20.4 Panel Description: Silent Knight 5495-7 Power Supply Minimum Device Voltage I 16 I Panel No.: NAC 2.1 Output No.: 4 Point To Point Method EOLv 18.73 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock I I Load Centering Method EOLv 18.91 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet) ,;, 19.91 1 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 65 2 FLOOR 1 HSWC (15) H/S-Ceil, White, Hi 15 Cd 0.082 19 19.77 3 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 18 19.65 4 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 25 19.50 5 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 15 19.41 19.32 6 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 16 2 7 FLOOR 1 HSWC (115) H/S-Ceil, White, Hi 115 Cd 0.197 19 19.22 8 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 22 9 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 22 19.06 10 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 26 18.97 11 FLOOR 1 STWC (30) Stb-Ceil, White 30 Cd 0.085 40 18.86 12 FLOOR 1 HSWC (75) H/S-Ceil, White, Hi 75 Cd 0.148 24 18.80 13 FLOOR 1 STWC (15) Stb-Ceil, White 15 Cd 0.061 19 18.78 14 FLOOR 1 STWC (30) Stb-Cell, White 30 Cd 0.085 27 18.75 15 FLOOR 1 HSWC (15) HIS-Ceil, White, Hi 15 Cd 0.082 38 18.73 18.73 16 18.73 17 18.73 18 18.73 19 18.73 20 OUTPUT 4 -rrr,_A NiAr, 9 1 FOLv Calc.xls NAC EXTENDER BATTERY CALCULATIONS CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office, (503) 255-1966 Fax JOB NAME: Tigard Corporate Center Building-A ADDRESS: 12123 SW 69th Ave. Tigard,OR 97223 DATE: 11/5/18 PANEL DESCRIPTION: NAC 2.1 PREPARED BY:Shane Tercek DEVICE TOTAL DEVICE TOTAL STANDBY STANDBY ALARM ALARM DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT NAC EXTENDER Silent Knight 5495-7 NAC Panel 1 0.075 0.075 0.175 0.175 CIRCUIT#1 Floor-1 M sA , . ''' 0.000 LtlesWhlk HSWC 115 Cd H/S-Ceiling (H) 1 bey, 0.197 0.197 Whlk HSWC 75 Cd H/S-Ceiling (H) 2 0.148 0.296 Whlk HSWC 15 Cd H/S-Ceiling (H) 2 ,' 0.082 0.164 a 0.135 0.135 Whlk STWC 75 Cd Strobe-Ceiling 1 0.0851 0.255 Whlk STWC 30 Cd Strobe-Ceiling 3 Whlk STWC 15 Cd Strobe-Ceiling 5 0.061 0.305 F -- 0.000 s 0.000 s nTOTAL 1.352 /07,17 CIRCUIT#2 Floor-1 .777,73177777,f___ `"_ . 1„ 0.000 Whlk HSWC 150 Cd H/S-Ceiling (H) 1 -F44 0.242 0.242 Whlk HSWC 30 Cd H/S-Ceiling (H) 2 ,,° 0.102 0.204 Whlk HSWC 15 Cd H/S-Ceiling (H) 1 0.082 0.082 Whlk STWC 30 Cd Strobe-Ceiling 1 0.085 0.085 Whlk STWC 15 Cd Strobe-Ceiling 13 0.061 0.793 li4s7rroNtor77t4- 0.000 0.000 0.000 fix, iii,„4.40,y ,,, TOTAL 1.406 CIRCUIT#3 Floor-1 0.000 Whlk HSWC 75 Cd H/S-Ceiling (H) 2 4 `;''';1,;T:AV: 0.148 0.296 Whlk HSWC 30 Cd H/S-Ceiling (H) 1 „ 0.102 0.102 Whlk HSWC 15 Cd H/S-Ceiling (H) 1 FWIETMEWN,M710.082 0.082 Whlk STWC 75 Cd Strobe-Ceiling 1 0.135 0.135 12 . 0.061 0.732 FRIPAViriT15 Cd Strobe-Ceiling Whlk STWC .,- 0.000 0.000 TOTAL 1-347 CIRCUIT#4 Floor-1 EILIMMIEE 0.000 Whlk HSWC 115 Cd HIS-Ceiling (H) 1 i 0.197 0.197 Whlk HSWC 75 Cd H/S-Ceiling (H) 1 0.148 0.148 Whlk HSWC 15 Cd H/S-Ceiling (H) 2 0.082 0.164 Whlk STWC 30 Cd Strobe-Ceiling 2 n 0.085 0.170 Whlk STWC 15 Cd Strobe-Ceiling 9 0.061 0.549 kaigiii 0.000 - 0.000 F f TOTAL0.000-28 v r� W4. TCC-A NAC 2.1 Batt Calc.xls Page 1 of 2 NAC EXTENDER BATTERY CALCULATIONS CAPITOL ELECTRIC CO., INC. (503)255-9488 Office, (503) 255-1966 Fax JOB NAME: Tigard Corporate Center Building-A ADDRESS: 12123 SW 69th Ave. Tigard,OR 97223 DATE: 11/5/18 PANEL DESCRIPTION: NAC 2.1 PREPARED BY:Shane Tercek DEVICE TOTAL DEVICE TOTAL STANDBY STANDBY ALARM ALARM DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT AUXILIARY DEVICES i atri . _ 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.000 STANDBY TOTAL CURRENT: 0.075 STANDBY HOURS: 24 STANDBY AMP HOURS: 1.800 NAC DEVICE CURRENT 5.333 ALARM TOTAL CURRENT: 5.508 ALARM MINUTES: 5 ALARM AMP HOURS: 0.459 TOTAL CALCULATED AMP HOURS 2.259 APPLIED SAFETY FACTOR 1.20 MINIMUM AMP HOURS REQURED 2.711 SELECTED BATTERY SIZE 12 EACH 12 VOLT, 7 AMP HOUR BATTERIES TCC-A NAC 2.1 Batt Calc.xls Page 2 of 2 • • NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO. INC. (503) 255-9488 Office (503)255-1966 Fax Job Name: Tigard Corporate Center Building-A Job Address: 12123 SW 69th Ave Tigard, OR 97223 Job Number: Conductor Wire Guage 14 Prepared By: Shane Tercek Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) ( 3.07 I Date: 11/5/2018 Cable Length In Feet (source to end of line) I 447 I Total Circuit Current I 1.597 I Nominal System Voltage I 20.4 I Panel Description: Silent Knight 5495-7 Power Supply Minimum Device Voltage I 16 I Panel No.: NAC 2.2 Output No.: 1 Point To Point Method EOLv 18.01 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock Load Centering Method EOLv 18.21 Circuit Within Limits ? YES Dev Device Location Device Model No. &Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet) Fer' .'.zz .�.,'��� s r p : ` ir �e va P ,cai f t 4„ ,_,4v., __-- ' 7 /F. , "'�` ; 1 FLOOR 2 HS-WC (75) H/S-Cell, White, Hi 75 Cd 0.148 38 20.03 2 FLOOR 2 STWC (75) Stb-Ceil, White 75 Cd 0.135 48 19.60 3 FLOOR2 STWC (15) Stb-Ceil, White 15 Cd 0.061 29 19.37 4 FLOOR2 STWC (15) Stb-Ceil, White 15 Cd 0.061 25 19.17 5 FLOOR2 STWC (15) Stb-Ceil, White 15 Cd 0.061 25 18.99 6 FLOOR 2 HSWC (115) H/S-Cell, White, Hi 115 Cd 0.197 31 18.78 7 FLOOR 2 STWC (75) Stb-Ceil, White 75 Cd 0.135 41 18.54 8 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 17 18.46 9 FLOOR 2 STWC (75) Stb-Ceil, White 75 Cd 0.135 26 18.34 10 FLOOR 2 HSWC (30) H/S-Ceil, White, Hi 30 Cd 0.102 21 18.26 11 FLOOR2 STWC (15) Stb-Ceil, White 15 Cd 0.061 19 18.20 12 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 16 18.16 13 FLOOR2 STWC (75) Stb-Ceil, White 75 Cd 0.135 27 18.10 14 FLOOR2 STWC (15) Stb-Ceil, White 15 Cd 0.061 37 18.04 15 FLOOR2 STWC (15) Stb-Ceil, White 15 Cd 0.061 13 18.03 16 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 12 18.02 17 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 22 18.01 18.01 18 18.01 19 18.01 20 - A AI Art 0 0 cnl ,, holr vlc OUTPUT 1 • NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office (503) 255-1966 Fax Job Name: Tigard Corporate Center Building-A Job Address: 12123 SW 69th Ave Tigard, OR 97223 Job Number: Conductor Wire Guage I 14 I Prepared By: Shane Tercek Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) 3.07 Date: 11/5/2018 Cable Length In Feet (source to end of line) I 422 Total Circuit Current I 1.561 I Nominal System Voltage I 20.4 I Panel Description: Silent Knight 5495-7 Power Supply Minimum Device Voltage I 16 I Panel No.: NAC 2.2 Output No.: 2 Point To Point Method EOLv 18.16 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock Load Centering Method EOLv 18.38 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet) .,,. Zr' .. mss a7 ., 1 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 41 20.01 2 FLOOR 2 HSWC (150) H/S-Cell, White, Hi 150 Cd 0.242 30 19.73 3 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 40 19.42 4 FLOOR 2 HSWC (95) H/S-Cell, White, Hi 95 Cd 0.176 22 19.26 5 FLOOR2 STWC (15) Stb-Ceil, White 15 Cd 0.061 27 19.09 6 FLOOR 2 STWC (75) Stb-Ceil, White 75 Cd 0.135 30 18.91 7 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 34 18.74 8 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 38 18.56 9 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 17 18.49 10 FLOOR 2 HSWC (75) H/S-Ceil, White, Hi 75 Cd 0.148 23 18.40 11 FLOOR 2 STWC (95) Stb-Ceil, White 95 Cd 0.163 40 18.28 12 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 20 18.24 13 FLOOR2 STWC (15) Stb-Ceil, White 15 Cd 0.061 18 18.21 14 FLOOR2 STWC (15) Stb-Ceil, White 15 Cd 0.061 18 18.18 15 FLOOR 2 HSWC (75) H/S-Ceil, White, Hi 75 Cd 0.148 24 18.16 16 18.16 18.16 17 18 18.16 19 18.16 20 18.16 -r,.,, A A I A 0 0 Gni „ noir yiQ OUTPUT 2 NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office (503) 255-1966 Fax Job Name: Tigard Corporate Center Building-A Job Address: 12123 SW 69th Ave Tigard, OR 97223 Job Number: Conductor Wire Guage 14 Prepared By: Shane Tercek Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) 3.07 Date: 11/5/2018 Cable Length In Feet (source to end of line) 592 Total Circuit Current 1.235 Nominal System Voltage 20.4 Panel Description: Silent Knight 5495-7 Power Supply Minimum Device Voltage 16 Panel No.: NAC 2.2 Output No.: 3 Point To Point Method EOLv 17.97 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock Load Centering Method EOLv 18.16 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet ) m -� f 1 1* �.. WP �r�.'.,; l „�_s :_ <. .{=,� ��i`�i.'�9-.�s-,� „�....,.,r'.sa...s�.`a.y,a_... ,�. � •.,,.. .... ,..:... ...,,, ky�s"a� �. ,.„. _,��....m ,fF,,?� .e.,, �x.,..¢ 1 FLOOR 2 STWC (75) Stb-Ceil, White 75 Cd 0.135 32 20.16 2 FLOOR 2 HSWC (15) H/S-Ceil, White, Hi 15 Cd 0.082 68 19.70 3 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 42 19.44 4 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 24 19.29 5 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 22 19.17 6 FLOOR 2 STWC (15) Stb-Cell, White 15 Cd 0.061 39 18.97 7 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 25 18.85 8 FLOOR2 STWC (15) Stb-Ceil, White 15 Cd 0.061 31 18.72 9 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 42 18.55 10 FLOOR 2 HSWC (15) H/S-Ceil, White, Hi 15 Cd 0.082 53 18.36 11 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 25 18.28 12 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 27 18.21 13 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 26 18.14 14 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 29 18.09 15 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 19 18.06 16 FLOOR 2 HSWC (15) H/S-Ceil, White, Hi 15 Cd 0.082 46 18.00 17 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 _ 24 17.98 18 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 18 17.97 19 17.97 20 17.97 TCC-A NAC 2.2 EOLv Calc.xls OUTPUT 3 NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office (503) 255-1966 Fax Joh Name: Tigard Corporate Center Building-A Job Address: 12123 SW 69th Ave Tigard, OR 97223 Job Number: Conductor Wire Guage 14 Prepared By: Shane Tercek Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) 3.07 Date: 11/5/2018 Cable Length In Feet (source to end of line) 386 Total Circuit Current 1.222 Nominal System Voltage 20.4 Panel Description: Silent Knight 5495-7 Power Supply Minimum Device Voltage 16 Panel No.: NAC 2.2 Output No.: 4 Point To Point Method EOLv 18.74 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock Load Centering Method EOLv 18.95 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet) ��_�,?�"�,E r 1 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 52 20.01 2 FLOOR2 HSWC (15) H/S-Ceil, White, Hi 15 Cd 0.082 21 19.86 3 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 17 19.75 4 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 16 19.65 5 FLOOR2 STWC (15) Stb-Ceil, White 15 Cd 0.061 15 19.56 6 FLOOR2 STWC (15) Stb-Ceil, White 15 Cd 0.061 16 19.47 7 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 15 19.39 8 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 16 19.32 9 FLOOR 2 HSWC (15) H/S-Ceil, White, Hi 15 Cd 0.082 32 19.18 10 FLOOR 2 HSWC (15) H/S-Ceil, White, Hi 15 Cd 0.082 33 19.05 11 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 32 18.94 12 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 15 18.90 13 FLOOR2 STWC (15) Stb-Ceil, White 15 Cd 0.061 12 18.87 14 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 19 18.82 15 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 12 18.80 16 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 19 18.77 17 FLOOR2 STWC (15) Stb-Ceil, White 15 Cd 0.061 13 18.76 18 FLOOR2 STWC (15) Stb-Ceil, White 15 Cd 0.061 15 18.75 19 FLOOR2 STWC (15) Stb-Ceil, White 15 Cd 0.061 16 18.74 20 18.74 TCC-A NAC 2.2 EOLv Calc.xls OUTPUT 4 NAC EXTENDER BATTERY CALCULATIONS CAPITOL ELECTRIC CO., INC. (503)255-9488 Office, (503)255-1966 Fax JOB NAME: Tigard Corporate Center Building-A ADDRESS: 12123 SW 69th Ave. Tigard,OR 97223 DATE: 11/5/18 PANEL DESCRIPTION: NAC 2.2 PREPARED BY: Shane Tercek DEVICE TOTAL DEVICE TOTAL STANDBY STANDBY ALARM ALARM DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT NAC EXTENDER Silent Knight 5495-7 NAC Panel 1 0.075 0.075 0.175 0.175 CIRCUIT#1 Floor 2 0.000 Whlk HSWC 115 Cd H/S-Ceiling (H) 1 0.197 0.197 Whlk HSWC 75 Cd H/S-Ceiling (H) 1 ' 7 0.148 0.148 Whlk HSWC 30 Cd H/S-Ceiling (H) 1 : <:' s ,!, 0.102 0.102 Whlk STWC 75 Cd Strobe-Ceiling 4 0.135 0.540 Whlk STWC 15 Cd Strobe-Ceiling 10 0.061 0.610 - !$-, .,; ! 0.000 5r' 0.000 ;,._ 0.000 � .,• � �.,> r ,, r ?"% TOTAL 1.597 CIRCUIT#2 Floor 2 0.000 Whlk HSWC 150 Cd H/S-Ceiling (H) 1 §2z< 0.242 0.242 Whlk HSWC 95 Cd H/S-Ceiling (H) 1 tgrzugh751=21 0.176 0.176 Whlk HSWC 75 Cd H/S-Ceiling (H) 2 0.148 0.296 Whlk STWC 95 Cd Strobe-Ceiling 1 0.163 0.163 Whlk STWC 75 Cd Strobe-Ceiling 1 0.135 0.135 Whlk STWC 15 Cd Strobe-Ceiling 90.061 0.549 - W~ 0.000 0.000 %„y , . 7f' kms' TOTAL 1.561 CIRCUIT#3 Floor 2 „, ,..e Fe 0.000 Whlk HSWC 15 Cd H/S-Ceiling (H) 3 0.082 0.246 Whlk STWC 75 Cd Strobe-Ceiling 1 � 0.135 0.135 Whlk STWC 15 Cd Strobe-Ceiling 14 ;•' 0.061 0.854 0.000 111:',W#1•47� 0.000 7`-';;;7177771 0.000 ';'73 ,01F-17700.000 0.000 iz', ,... . . ,.; ,," M -4,�.. ..� •, TOTAL 1.235 CIRCUIT#4 Floor 2 ,, 7 07 0.000 Whlk HSWC 15 Cd H/S-Ceiling (H) 3 ®''li 0.082 0.246 Whlk STWC 15 Cd Strobe-Ceiling 16r 0.061 0.976 „ 0.000 0.000 °" Z'k 0.000 0.000 0.000 r7 Z':, 0.000 °: : ,. it.,' TOTAL 1.222 TCC-A NAC 2.2 Batt Calc.xls Page 1 of 2 NAC EXTENDER BATTERY CALCULATIONS CAPITOL ELECTRIC CO., INC. (503)255-9488 Office, (503) 255-1966 Fax JOB NAME: Tigard Corporate Center Building-A ADDRESS: 12123 SW 69th Ave. Tigard, OR 97223 DATE: 11/5/18 PANEL DESCRIPTION: NAC 2.2 PREPARED BY:Shane Tercek DEVICE TOTAL DEVICE TOTAL STANDBY STANDBY ALARM ALARM DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT AUXILIARY DEVICES ....:. * . %.,*: .11'l /01n. 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.000 STANDBY TOTAL CURRENT: 0.075 STANDBY HOURS: 24 STANDBY AMP HOURS: 1.800 NAC DEVICE CURRENT 5.615 ALARM TOTAL CURRENT: 5.790 ALARM MINUTES: 5 ALARM AMP HOURS: 0.483 TOTAL CALCULATED AMP HOURS 2.283 APPLIED SAFETY FACTOR 1.20 MINIMUM AMP HOURS REQURED 2.739 SELECTED BATTERY SIZE ' 2 EACH 12 VOLT, 7 AMP HOUR BATTERIES TCC-A NAC 2.2 Batt Calc.xls Page 2 of 2 SIRE ALARM DAT SHEETS ° UL FIRE COTROL 7100 SERIES INSTRUMENTS COMPACT ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL 43> APPROVED DESCRIPTION The FCI 7100* Series fire alarm control panel effectivelyrr0g7* combines multiprocessor analog system advantages with a 1174.1 compact,efficient design. Designed for commercial,t designtp . Deand institutional use, it is ideal for life safety applica- tions. The 7100 provides two signaling line circuits, operable " g„ with"straight lay"wire. Each can accommodate 99 analog sensors and 98 addressable monitor and/or control modules for a total of 197 points per circuit,with a system maximum . ; of 394 points. A choice of either front-panel intuitive programming or computer programming via the FCI Field Configuration Pro- - F gram(FCP)facilitates the installation regardless of the com- plexity of the application. ° � • The sophisticated circuitry and powerful analog software . enables it to read specific(default/user)sensitivity levels of each sensor and compensate for any changes due to age or en- vironment.The 7100 incorporates the FCI Listed Integrated Sensitivity Testing(LIST)which meets the NFPA 72 sensi- tivity testing and maintenance requirements.The LIST test- FEATURES ing allows substantial savings in both maintenance and • 80-character Alphanumeric Display service while virtually eliminating unwanted alarms. The Model 7100D (non-FM) features an integral Digital • Intuitive Front Panel Programming Alarm Communicator Transmitter(DACT)with all popular • Two Style 4(Class B)Signaling Line transmission formats and a 16-digit telephone number field. Circuits using"Straight Lay"Wire It is 8-digit Carrier Information Code(CIC) compliant and • Manual/Automatic Sensor Settings also prevents "dialer-runaway"in the event of intermittent system faults. The 7100D is UL Listed for Remote Station, • Individual Sensor Drift Compensation Proprietary and Central Station fire alarm systems. • Listed Integral Sensitivity Testing(LIST) Housed in an attractive, contemporary styled cabinet, the • "Dirty"and"Very Dirty"Sensor 7100 offers ample wiring space and room for batteries up to 7 Indications AH capacity. A variety of optional modules offers a wide range of fea- • Multilevel Sensor Sensitivity Adjustments tures to meet local or specialized requirements. • Day/Night Sensor Sensitivity Adjustments OPTIONAL FEATURES • Alarm Verification per Individual Sensor • Four Levels of System Access Programming • Integral Digital Alarm Communicator With Five Passwords per Level (DACT)(7100-D) • Duplicate Address Indication • Remote 80-Character LCD Display (LCD-7100) • Periodic Trouble Reminder • Remote LED Driver Module(LDM-7100) • Two Style Y(Class B)Regulated • Class A Option Module for Both Signaling Notification Appliance Circuits,Rated Line Circuits and Notification Appliance 1.5 Amp.each Circuits(CAOM) • March Time/Temporal Pattern/Calif.Code • Output for City Master Box, • 500-Event History Log Reverse Polarity Signaling or Releasing • Last Date,Time and Menu Option Printout Solenoid (MCOM) for Programming Verification • RS-232 Isolator/Transient Protection for EDP Device Connection(PTRM) • 120 or 240 VAC Input Operation Patent pending Specifications are provided for information only,are not intended to be used for installation purposes,and are believed to be accurate.However,no responsibility is assumed by Fire Control Instruments,Inc.for their use.Specifications subject to change without notice. ©1999 All Rights Reserved 301 2nd Ave Waltham, MA 02451-1133 USA l'hL: (781)487-0088 FAX: (781)370-4132 9020-0466/Ver. 1.7 OPTIONAL MODULES Remote Serial Display (LCD-7100) The LCD-7100 Remote Serial Display offers an 80-character alphanumeric readout for remote display of all system events.It duplicates all the information on the 7100 Series panel display with the exception of menus. 3 = The LCD-7100 contains function keys for Alarm Ac- g „ knowledge, Trouble Acknowledge, Signal Silence, System Reset/Lamp Test and System Drill Test.A key lock must be placed in the"ON"position to enable the function keys with the exception of the "Trouble Ac- knowledge" key which is used to silence the trouble sounder on the LCD-7100. LCD-7100 LEDs on the LCD-7100 are: Alarm, Supervisory, LED Driver Module, System Trouble, Power Fault, System Silenced, NAC (LDM-7100) #1 Silenced and NAC#2 Silenced. This module is designed to mount in a UL Listed re- mote annunciator and provides output for remote panel The LCD-7100 can be surface or flush mounted on a switches and 33 remote LEDs.Three LDM-7100 mod- standard four-gang electrical box and it can be installed ules may be installed in a single annunciator for a total up to 4,000 feet from the main control.The 7100 con- of 99 maximum LEDs per annunciator. trol panel can accommodate up to five (5) remote LCD-7100 annunciators. While Underwriters Laboratories test procedures only allow for testing at ambient temperatures down to Class A Option Module, 32°F, independent laboratory testing of the LDM-7100 (CAOM) indicated satisfactory operation at an ambient of-10°F This module allows Class A operation for both sig- for extended periods of time. naling line circuits and notification appliance circuits. It also provides disconnect switches for each signaling The 7100 control panel can accommodate up to 15 line circuit and a common notification appliance circuit LDM-7100 modules that can be located up to 4,000 feet disconnect switch. from the main control. Municipal Connection Option Module, Printer Transient Module (MCOM) (PTRM) The MCOM provides outputs for local energy city The PTRM provides RS-232 Isolator/Transient Pro- master box, reverse polarity operation, or a releasing tection for EDP Device Connection. solenoid. AGENCY APPROVALS UL(7100) S1869 (LCD-7100,LDM-7100) S 1949 Factory Mutual(7100) 3003549 Factory Mutual(LCD-7100) 3006578 CSFM Approved(7100,LCD-7100) New York City(7100) MEA 307-99E Vol.II 2 of 3 9020-0466 SPECIFICATIONS Primary input power 120 VAC,50/60 Hz,2.0 amps,or 240 VAC,50/60 Hz, 1.0 amp. Output power 4 amp.@ 24 VDC(total) Non-resettable power 1.0 amp. Resettable power 1.0 amp. Two(2)Notif.Appliance Circuits 1.5 amp.each Current Supervisory Alarm 7100-2 0.065 amp. 0.085 amp 7100-2D 0.085 amp. 0.105 amp LCD-7100 0.050 amp. 0.075 amp. LDM-7100 0.035 amp. 0.200 amp. (All LEDs lit) Operating temperature 32- 120°F(0-49°C) Relative humidity 85% (non-condensing) Battery charger capacity 31 AH Alarm and Trouble relay contacts Form"C",2 amps.@ 24 VDC(resistive) Dimensions 7100 16.9"Hx 14.5"W x 3"D(40 x 37 x 7.5 cm) LCD-7100 4 1/2"H x 8 1/4"W x 1 7/8"D( 11.5 x 20.5 x 4.6 cm) LDM-7100 6"W x 4 1/2"H(15.24 x 11.5 CM) Weight(7100) 24 lbs(11 kg) ORDERING INFORMATION Part Number Model Description 1100-1236 7100-2 Analog Addressable Control Panel 1100-1232 7100-2D Analog Addressable Control Panel,with DACT 1100-0399 LCD-7100 Remote Serial Annunciator(80-Character) 1700-0200 LDM-7100 Remote LED Driver Module 1100-1233 CAOM Class A Option combination module with disconnect switches for both signaling line circuits and notification appliance circuits 1100-1234 MCOM Municipal Connection Option Module for local energy city box, reverse polarity signaling,or releasing solenoid 1100-1235 PTRM Printer Transient Module-allows use of RS-232 Serial Port for EDP device connection 1100-1250 7100-2-240 7100-2 for 240 VAC input 1100-1251 7100-2D-240 7100-2D for 240 VAC input 1120-0787 EN-7100 Back Box 1120-0779 CS-7100 Door 1120-0778 T-7100 Transformer, 120 VAC input(replacement) 1120-0801 T-7100-240 Transformer,240 VAC input(replacement) 1120-0781 BSM-2 Basic System Module,2 SLC,(replacement) 1120-0780 BSM-2D Basic System Module,2 SLC,DACT,(replacement) 9020-0466 3 of 3 , ® uL Iliti FIRE CONTROL ADDRESSABLE MODULES INSTRUMENTS APPPOVEO ADDRESSABLE MONITOR MODULES i (AMM-2) kil , 1 The Addressable Monitor Module AMM-2 installs in the signaling line circuit of FCI analog addressable control pan- els.It provides an address for an individual or group of UL Listed normally open(N.O.)initiating devices,such as heat detector,projected beam smoke detector,4-wire smoke de- r ° tector,waterflow switch,manual station,etc.wired in a Class -. B,Style B initiating circuit. The initiating device circuit has a maximum line resistance x of 1,200 ohms. 4. AMM-2 el- v (AMM-2I) . .. The Dual Addressable Monitor Module AMM-2I provides addresses for two(2)individual or groups of UL Listed nor- ,? ,1r mally open (N.O.)initiating devices, such as heat detector, ' projected beam smoke detector, 4-wire smoke detector, waterflow switch,manual station,etc.wired in two Class B, Style B initiating circuits. 241?--"7---I----‘ A red LED on the module indicates operating status of both [ , circuits.A single address switch allows setting of the address - for the first circuit, with the second circuit being automati- cally assigned a sequential address. Each initiating device circuit has a maximum line resis AOM 2, AMM-4 , < 4� tante of 1,500 ohms. � ,; � (AMM-4) The Addressable Monitor Module AMM-4 provides an .,.4A--t r address for a group of UL Listed normally open(N.O.)initi ,,PT - ating devices, such as heat detector,beam smoke detector, ' 4-wire smoke detector, waterflow switch, manual station, ' A etc.wired in a Class A,Style D or Class B,Style B initiating - 3 circuit. ' The initiating device circuit has a maximum line resistance of 1,200 ohms. M500X (AMM-4S) The Addressable Monitor Module AMM-4S performs all the functions of the AMM-4 Module and in addition, pro- y'; vides an address for a group of up to 20 conventional 2-wire smoke detectors wired in a Class A,Style D or Class B,Styleg B initiating circuit. - ': The initiating device circuit has a maximum line resistance -"45:-,t,, g of 25 ohms. � " AOM-MUX,AOM-TEL, AMM-21 Specifications are provided for information only,are not intended to be used for installation purposes,and are believed to be accurate.However,no responsibility is assumed by Fire Control Instruments,Inc.for their use.Specifications subject to change without notice. ©1999 All Rights Reserved 301 2nd Ave Waltham, MA 02451-1133 USA TEL: (781)487-0088 FAX: (781)370-4132 9020-0472/Ver. 1.2 ADDRESSABLE OUTPUT MODULES dio systems to select the alarm tone and/or recorded (AOM-2) voice message to be transmitted to each evacuation zone. The AOM-MUX provides a notification appli- The Addressable Output Module(AOM-2)provides ance circuit that is controlled by either channel audio either a Form"C"relay output or notification appliance source and can be configured as Class B, Style Y or circuit,which may be programmed to operate from ei- Class A,Style Z. ther a trouble or alarm input from any addressable de- The notification appliance circuit can transfer up to vice. An external 24 VDC power source is required 63 watts of audio power to its speakers. when the module is configured as a notification appli- ance circuit module,and can be configured as Class B, FAULT ISOLATOR MODULE Style Y or Class A,Style Z. The module contains an LED which can be latched on by code command from the panel. (M500X) The optional Fault Isolator Module(M500X)installs (AOM-TEL) in the signaling line circuit of FCI analog addressable The Telephone Monitor Module (AOM-TEL) in- control panels.It is used to protect the system against stalls in the signaling line circuit offthe Audio Evacua- wire-to-wire short circuits on the signaling line circuits. tion Unit (AEU) of the FireVac a 7200 Emergency The isolator modules should be spaced between groups Voice Evacuation system. of addressable devices in a circuit to protect the remain- It controls the communications between the corn- der of the circuit.In general,up to 25 addressable de- mand center and the telephone jacks/warden stations. vices may be grouped between isolator modules.In the Wiring to individual telephone jacks and handsets is su- event of a short circuit between any two isolator mod- pervised and may be configured as two-wire(Class B), ules,both modules will immediately switch to an open or fault tolerant, (Class A). Status is reported to the circuit condition and isolate any groups of addressable panel as NORMAL,TROUBLE,or TELEPHONE. devices between them. The remaining devices on the The module contains a panel-controlled LED indica- circuit will continue to operate in a normal fashion.In a tor. Style 4 circuit, the module is generally used at each "T-tap"branch. (AOM-MUX) The M500X has an LED indicator that pulses during The Multiplex Output Module(AOM-MUX)installs normal operation and lights continuously in a short cir- in the signaling line circuit of the Audio Evacuation cuit condition. Unit (AEU) of the FireVac®7200 Emergency Voice Evacuation system.It is used in dual-channel bulk au- TECHNICAL INFORMATION Operating temperature 32 to 120°F(0 to 49°C) Relative humidity 10 to 93% (non-condensing) Dimensions (AMM-2) 1.3"H x 2.75"W x 0.5"D(3.3 x 5.5 x 1.25 cm) (All others) 4.5"H x 4"W x 1.25"D(11.3 x 10.1 x 3.2 cm) AMM-2I AMM-2,-4 AMM-4S AOM-2 AOM-MUX AOM-TEL M500X Supv.current .0006 amp. .0004 amp. .0004 amp. .0004 amp. .0004 amp. .002 amp. .00045 amp. Alarm current .005 amp. .007 amp. .043 amp. .007 amp. .0065 amp. .0065 amp. .005 amp. ORDERING INFORMATION Part No. Model Description 190-00002 AMM-2 Addressable Monitor Module(N/O devices,Style B only) 190- AMM-21 Addressable Monitor Module,2 circuit, (N/O devices,Style B only) 190-00003 AMM-4 Addressable Monitor Module(N/O devices,Style D or B) 190-00013 AMM-4S Addressable Sub-Loop Monitor Module (2-wire detectors,Style D or B)(non-FM) 190-00010 AOM-2 Addressable Output Module 190-00017 AOM-TEL Telephone Monitor Module(FM Pending) 190-00018 AOM-MUX Multiplex Output Module(FM Pending) 190-00100 M500X Fault Isolator Module 252-90001 MB500 Module mounting bracket(Holds up to 8 AMM/AOM modules) 2 of 2 9020-0472 INSTALLATION AND MAINTENANCE INSTRUCTIONS cci FIRE CONTROL INSTRUMENTS 301 2nd Avenue, Waltham, MA 02451-1133 AOM-2R Relay Control Module (781) 487-0088, FAX: (781) 370-4132 Specifications Normal Operating Voltage: 15 to 32 VDC EOL Resistance: Not used Temperature Range: 32°F to 120°F (0°C to 49°C) Humidity: 10% to 93% Noncondensing Dimensions: 41/2"H x 4"W x 11/4'D (Mounts to a 4"square by 21/8"deep box.) Accessories: SMB500 Electrical Box; CB500 Barrier Before Installing quadrant of the module barrier (Figure 2B). This information is included as a quick reference installation 1. Install module wiring in accordance with the job drawings and guide. Refer to the control panel installation manual for detailed appropriate wiring diagrams. system information. If the modules will be installed in an existing 2. Set the address on the module per job drawings. operational system, inform the operator and local authority that 3. Secure module to electrical box (supplied by installer), as the system will be temporarily out of service.Disconnect power to shown in Figure 2A. the control panel before installing the modules. NOTICE: This manual should be left with the owner/user of this equipment. Figure 1. Controls and indicators: n n General Description fj (� The AOM-2R Relay Control Module is intended for use in intelligent, �J 0 J two-wire systems, where the individual address of each module is ;e; 9 58®9 0 — selected using the built-in rotary decade switches. It allows a corn- ®8 3 0 1 2 patible control panel to switch discrete contacts by code command. RB ® 'TERS6 2 The relay contains two isolated sets of Form-C contacts,which oper- i 65 i2zi 4 to ate as a DPDT switch and are rated in accordance with the table in , LOOP ONES AOOPESS the manual. Circuit connections to the relay contacts are not super- c ° o 9 vised by the module. The module also has a panel controlled LED ' U U A78-2318-14 indicator. This module can be used to replace an AOM-2 module that has been configured for Form-C operation. Figure 2A. Module mounting with barrier: 1' Compatibility Requirements I To ensure proper operation, these modules shall be connected to listed compatible system control panels only. 41:2 ._Mounting The AOM-2R mounts directly to 4"square electrical boxes (see � Figure 2B: Figure 2A). The box must have a minimum depth of 21/8". g g Surface mounted electrical boxes (SMB500) are available. E — ® ® • Wiring .'' . D \MII„, NOTE: All wiring must conform to applicable local codes, ordi- nances, and regulations. When using control modules in J�� I lel � �� nonpower limited applications, the CB500 Module Barrier �' i ���� ISOLATED QUADRANT must be used to meet UL requirements for the separation O of power-limited and nonpower-limited terminals and wir- - - ing. The barrier must be inserted into a 4"x4"x21/8"junc- o °° Q° m A78-2611-09 tion box, and the control module must be placed into the barrier and attached to the junction box (Figure 2A). The cm 41.0 00-2100 power-limited wiring must be placed into the isolated Qi Olj A78-2610-07 9000-0468 1 I56-1517-00 Relay Contact Ratings: CURRENT RATING MAXIMUM VOLTAGE LOAD DESCRIPTION APPLICATION 3 A 30 VDC Resistive Non Coded 2 A 30 VDC Resistive Coded .9 A 110 VDC Resistive Non Coded .9 A 125 VAC Resistive Non Coded .5 A 30 VDC Inductive (L/R=5ms) Coded 1 A 30 VDC _ Inductive (L/R=2ms) Coded .5 A 125 VAC Inductive (PF=.35) Non Coded .7 A 75 VAC Inductive (PF=.35) Non Coded AWARNING All relay switch contacts are shipped as shown in Figure 3,but may have transferred during shipping.To ensure that the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module. Figure 3. Relay module wiring diagram: COMMUNICATION LINE 32 VDC Max. SHIELDED-TWISTED PAIR CONNECT MODULES TO LISTED COMPATIBLE IS RECOMMENDED CONTROL PANELS ONLY TO NEXT-1c _/_1__/_i__/_1_ ,'; / 1 FROM PANEL OR I+) DEVICE �/��I��1 4."1111P 14.1'111111' + PREVIOUS DEVICE 1 $ I CONTROL ,_0 ,�,_) , ; MODULE j , RELAY COMMON 2l s a U 1 (_) NORMALLY CLOSED 2 , IF ANY WIRING TO TERMINALS 3-9 IS NONPOWER +i 844—II 1 O. / LIMITED,THE CB500 BARRIER IS REQUIRED.THE CB500 NORMALLY OPEN 2 ! 7-I I- 2 ! (-I-) 11110 LIMITED, A NONPOWER LIMITED LABEL,WHICH MUST RELAY COMMON 1 el 6 sit; BE PLACED OVER THE POWER LIMITED TERMINAL NORMALLY CLOSED 1 ! 5-`�1 F 4 NORMALLY OPEN 1 INFORMATION ON THE NAMEPLATE LABEL. L00P ADDRESS MODULE DOES NOT SUPERVISE CONTROLLED CIRCUITS A78-2286-08 9000-0468 2 I56-1517-00 ©FCI 1999 . . mmii Velociti® Series INSST COMENTS by Honeywell AMM-2F Description Addressable Monitor Module The Gamewell-FCI Velociti® Series, addressable monitor module AMM-2F is a single Style B, Class B 1\l initiating device circuit(IDC)with a 47KW end-of-line z resistor. This module provides an address for any ""— ' device or group of devices connected to this circuit on the signaling line circuit (SLC) of the Gamewell- ( r FCI addressable series fire alarm control panel. Any initiating device with normally open (N.O.) dry con- tacts may be made addressable when connected to AMM-2F the AMM-2F module. The Velociti® Series use a communication protocol that substantially increases the speed of communi- Features cation between the sensors and certain Gamewell- • FCI analog addressable fire alarm controls. These Compact size allows easy installation devices operate in a grouped fashion. If one of the • Class B, Style B, initiating circuit devices in the group has a status change, the • 40 Ohm line resistance for each initiating device circuit panel's microprocessor stops the group poll and • Connects to any normally open dry contact device concentrates on the single device. The net effect is response speed up to five times greater than earlier Specifications designs. Supervisory Current: .000375 amps The AMM-2F module can be programmed to provide Alarm Current: .00060 amps a wide variety of input functions to the Gamewell-FCI Operating Temperature: 32° to 120° F (0°to 49° C) addressable series fire alarm control panels. It can Relative Humidity: 10 to 93% be identified as a manual station, heat detector, ple- (non-condensing) num detector, waterflow switch, tamper switch, N.O. End-of-Line Resistance:47K ohms contact, smoke detector, projected beam smoke Dimensions: 1.3"L x 2.5"W x 0.5"D detector, sub loop, remote zone, etc. It can also (3.3 x6.4 x 1.3 cm) serve as a remote system silence, system reset, system acknowledge or drill switch. It is even possi- Ordering Information ble to customize its device type to meet specific job requirements. PartNumber Description The initiating device circuit of the AMM-2F can sup- AMM-2F Addressable monitor module, single port a maximum line resistance of up to 40 ohms circuit, Style B, Class B allowing the use of linear heat detection devices. The compact size facilitates the installation of the module SIGNALING inside manual stations, or mounting boxes of various types of alarm initiating devices. ® ® MEA ='i'I Velociti®is a registered trademark of Honeywell International Inc. UL®is a registered trademark of Underwriters Laboratories Inc. LISTED APPROVED Approved S1949 3023594 227-03-E VOL IV 7300-1703:0102 iso 9001 ■m� ��•- GAMEWELL-FCI "•" "s":"s""s 12 Clintonville Road, Northford,CT 06472-1610 USA•Tel: (203)484-7161 •Fax: (203)484-7118 Specifications are for information only,are not intended for installation purposes,and are subject to change without notice.No responsibility is assumed by Gamewell-FCI for their use. ©2013 Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0626 Rev. E page 1 of 1 Seriesmail VeIociti® K�fiG.', • G me ell Velociti..® Series „5„::,,,:;;, STRUMENTS ASDPL2F, ASD-PTL2F by Honeywell and ASD-PL2FR Description Analog, Addressable Photoelectronic Smoke Sensor The Gamewell FCI Velociti° Series, analog addresser , M � able plug-in smoke sensors with integral communica- tion provide features that surpass conventional sensors. Sensitivity can be programmed in the con trol panel software, and is continuously monitored ': and reported to the panel. Point ID capability allows ' ' each sensor's address to be set, providing exact locations for selective maintenance when the cham- ber ham ber contamination reaches an unacceptable level. ASD-PL2FIASD-PTL2F ASD-PL2FR The ASD-PL2F photoelectric sensor's unique optical sensing chamber is engineered to sense smoke pro- Features duced by a wide range of combustion sources. Dual electronic thermistors add 135°F (57°C) fixed-tern- • Sleek, low-profile design perature thermal sensing on the ASD-PTL2F model. • Visual rotary, decimal switch addressing (01-159) • Built-in functional test switch activated by an external The Velociti® Series use a communication protocol magnet that substantially increases the speed of communica- • Bicolor LEDs flash green whenever the sensor is tion between the sensors and certain Gamewell-FCI addressed, and light steady red on alarm* analog addressable fire alarm controls. These • Optional relay, isolator, or sounder bases devices operate in a grouped fashion. If one of the • devices in the group has a status change, the panel's Low standby current microprocessor stops the group poll and concen- • Analog addressable communication trates on the single device. The net effect is a • Stable communication technique with noise immunity response speed up to five times greater than earlier • Optional remote, single-gang LED Indicator(RA100Z) designs. • Compatible with Gamewell-FCI analog addressable panels Ordering Information Note: *Only the red LED is operative in panels that do not operate in Velociti®mode. Model Description ASD-PL2F Analog, addressable photoelectronic smoke sensor ASD-PTL2F Analog, addressable photoelectronic smoke sensor with thermal sensing ASD-PL2FR Analog, addressable photoelectronic smoke sensor used with the DNR duct base when the remote test is required. An ISO 9001-2000 Company SIGNALING ® ® ® MEA Velociti®is a registered trademark of Honeywell International Inc. q _f proved UL®is a registered trademark of Underwriters Laboratories Inc. LS19 3 3023594 219-02 E Vol.Vl 7272-1703:0121 GAMEWELL-FCI 12 Clintonville Road, Northford,CT 06472-1653 USA•Tel:(203)484-7161 • Fax:(203)484-7118 Specifications are for information only,are not intended for installation purposes,and are subject to change without notice,No responsibility is assumed by Gamewell-FCI for their use. ©2011 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0617 Rev. I page 1 of 2 Installation Specifications ASD-PL2F plug-in sensors use a separate base to ASD-PL2F, ASD-PTL2F, ASD-PL2FR: simplify installation, service, and maintenance. A Dimensions: 2.1"(5.1 cm) height special tool allows maintenance personnel to plug-in Diameter: 4.1"(10.4 cm) installed in the B501 base and remove sensors without using a ladder. 6.1"(15.5 cm)installed in the ti21OLf'base Shipping Weight: 5.2 oz. (147 g) Mount the base on a box which is at least 1.5" (3.8 cm) Operating ASD-PL2F: deep. Suitable mounting base boxes include: Temperature: 32° F to 120° F(0° C to 49° C) ASD-PTL2F: • 4.0"(10.2 cm)square box 32° F to 100° F (0° C to 38° C) • 3.5"(8.9 cm)or 4.0"(10.2 cm)octagonal box UL®-Listed 0-4000 ft./min. (1,219.2 m/min.), • Single-gang box(except relay or isolator bases) Velocity Range: suitable for installation in ducts. • With B200S or B200SR base, mounted on a 4.0" Relative 10-93% (non-condensing) (10.2 cm)octagonal or square box Humidity: Thermal Ratings: Fixed-temperature setpoint • With B224RB or B224B1 base, mounted on a 3.5" 135° F (57° C) (8.9 cm)octagonal box, or a 4.0"(10.2 cm)octagonal or square box Electrical Specifications NOTE: Because of the inherent supervision provided Voltage Range: 15-32 volts DC peak by the SLC, end-of-line resistors are not required. Standby Current: (max.avg.): .0003 A @ 24 VDC Wiring "T-taps" or branches are permitted for Style 4 (one communication every 5 (Class "B")wiring. seconds with LED blink enabled) Maximum Alarm- Current: .0065 A @ 24 VDC (LED) lit). Sensor Spacing Gamewell-FCI recommends that the spacing sensors Bases and Options be used in compliance with NFPA 72. B501 Plug-in sensor base without flange Dimensions: 4.1"(10.4 cm)diameter B210LP Flanged mounting base Dimensions: 6.1"(15.5 cm)diameter B210LPBP Flanged mounting base bulk pack Dimensions: 6.1"(15.5 cm)diameter B224RB Plug-in sensor base with auxiliary Relay Base relay, SPDT, rated 2 amps @ 30 VDC (resistive) Screw terminals: Up to 14 AWG (2.0 mm2) 2 coil latching relay 1 Form C contact UL/CSA Rating: 0.9 A @ 125 VAC, inductive 0.9 A @ 110 VDC, inductive 3 A @ 30 VDC, resistive Dimensions: 6.1"(15.5 cm)diameter Maximum: 25 devices between isolator bases. B200S Intelligent sensor sounder base Dimensions: 6.875"(17.5 cm)diameter B200SR Standard sounder base, UL 8649th Edition compliant, ULC Listed Dimensions: 6.875" (17.5 cm)diameter RA100Z Remote LED Annunciator BCK-200 Black detector covers (box of 10) DNR Duct smoke housing GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1653 USA•Tel: (203)484-7161 •Fax:(203)484-7118 9020-0617 Rev. I page 2 of 2 www.gamewell-fci.com INSTALLATION AND MAINTENANCE INSTRUCTIONS ASD-PL2, ASD-PTL2 and INST UM TERN TS MCS-ACCLIMATE2 Analog Addressable 16 Southwest Park, Westwood, MA 02090 Photoelectric Smoke Sensors (781) 471-3000, FAX: (781) 471-3099 Specifications Operating Voltage Range: 15 to 32 VDC Standby Current: 300uA @ 24 VDC (one communication every 5 sec. with LED flash enabled) Max. Alarm Current (LED on:) 6.5 mA @ 24 VDC Operating Humidity Range: 10% to 93% Relative Humidity, non condensing Operating Temperature Range: 0° to 49°C (32° to 120°F); ASD-PL2 Operating Temperature Range: 0° to 38°C (32° to 100°F); ASD-PTL2 and MCS-Acclimate2 Heat Sensor: 135°F Fixed Temperature Electronic Thermistor Height: 2.0 inches (51 mm) installed in ADB-FL Base Diameter: 6.1 inches (155 mm) installed in ADB-FL Base 4.1 inches (104 mm) installed in B501 Base Weight: 5.2 oz. (147 g) Before Installing This sensor must be installed in compliance with the con- Duct Applications: ASD-PL2 and ASD-PTL2 are listed for trol panel system installation manual. The installation must use in ducts. See Duct Applications Guide A05-1004-XX for meet the requirements of the Authority Having Jurisdiction details on pendant mount applications. Note: These prod- (AHJ). Sensors offer maximum performance when installed ucts are not listed for use inside duct smoke detectors. in compliance with the National Fire Protection Association (NFPA); see NFPA 72. Wiring Instructions All wiring must be installed in compliance with the General Description National Electrical Code, applicable local codes, and any Models ASD-PL2, ASD-PTL2 and MCS-ACCLIMATE2 are special requirements of the Authority Having Jurisdiction. plug-in type smoke sensors that combine a photoelectronic Proper wire gauges should be used. The installation wires sensing chamber with addressable-analog communications. should be color-coded to limit wiring mistakes and ease The sensor transmits an analog representation of smoke system troubleshooting. Improper connections will prevent density over a communication line to a control panel. a system from responding properly in the event of a fire. Rotary-decade switches are provided for setting the sensor's address. Remove power from the communication line before installing sensors. Two LEDs on the sensor are controlled by the panel to indi- cate sensor status. An output is provided for connection to 1. Wire the sensor base (supplied separately) per the wir- an optional remote LED annunciator (P/N RA400Z). Models ing diagram, see Figure 1. MCS-ACCLIMATE2 and ASD-PTL2 combine a photoelectron- 2. Set the desired address on the sensor address switches, is sensing chamber and 135°F (57.2°C) fixed temperature see Figure 2. heat detector. 3. Install the sensor into the sensor base. Push the sensor into the base while turning it clockwise to secure it in The ASD-PL2, ASD-PTL2 and MCS-ACCLIMATE2 require place. compatible addressable communications to function 4. After all sensors have been installed, apply power to the properly. Connect these sensors to listed-compatible control unit and activate the communication line. control panels only. 5. Test the sensor(s) as described in the TESTING section of this manual. Spacing FCI recommends spacing sensors in compliance with NFPA ACAUTION 72. In low air flow applications with smooth ceilings, space Dust covers provide limited protection against airborne dust sensors 30 feet apart. For specific information regarding particles during shipping. Dust covers must be removed sensor spacing, placement, and special applications, refer before the sensors can sense smoke. Remove sensors prior to NFPA 72 or the System Smoke Detector Application to heavy remodeling or construction. Guide, available from FCI. 9000-0558 1 I56-2036-01R • Figure 1. Wiring diagram: CAUTION: Do not loop wires under Terminals 1 or 2. Break wire run to provide supervision of con- nections. REMOTE ANNUNCIATOR + _! I w ? :l Liz2 3a_ •a O Ck � U O O U J � OPTIONAL RETURN LOOP coioo-00 Tamper-Resistance Models ASD-PL2, ASD-PTL2 and MCS-ACCLIMATE2 B. Smoke Entry: Aerosol Generator (Gemini 501) include a tamper-resistant capability that prevents their For MCS-ACCLIMATE2 removal from the bracket without the use of a tool. Refer Smoke entry testing should be performed immediately to the base manual for details on making use of this capa- following the magnet test. Magnet test initiates an bility. approximately 10 minute period when the detector's signal processing software routines are not active. Testing Failure to first perform the magnet test will introduce a Before testing, notify the proper authorities that the system time delay before the detector alarms. is undergoing maintenance, and will temporarily be out of service. Disable the system to prevent unwanted alarms. The GEMINI model 501 aerosol generator can be used for smoke entry testing. Set the generator to represent All sensors must be tested after installation and periodi- 4%/ft to 5%/ft obscuration as described in the GEMINI cally thereafter. Testing methods must satisfy the Authority 501 manual. Using the bowl shaped applicator, apply Having Jurisdiction (AI-1J). Sensors offer maximum perfor- aerosol until the panel alarms. mance when tested and maintained in compliance with NFPA 72. C. Direct Heat Method (Hair Dryer of 1000-1500 watts) ASD-PTL2 and MCS-ACCLIMATE2 The sensor can be tested in the following ways: A hair dryer of 1000-1500 watts should be used to test A.Functional: Magnet Test (P/N M02-04-01 or M02-09-00) the thermistors. Direct the heat toward either of the two This sensor can be functionally tested with a test mag- thermistors, holding the heat source approximately 12 net. The test magnet electronically simulates smoke in inches from the detector in order to avoid damaging the the sensing chamber, testing the sensor electronics and plastic housing. The detector will reset only after it has connections to the control panel. had sufficient time to cool. Make sure both thermistors 1. Hold the test magnet in the magnet test area as shown are tested individually. in Figure 3. 2. The sensor should alarm the panel. A sensor that fails any of these tests should be cleaned Two LEDs on the sensor are controlled by the panel as described under CLEANING, and retested. If the to indicate sensor status. Coded signals, transmitted sensor fails after cleaning, it must be replaced and returned from the panel, can cause the LEDs to flash, light for repair. steadily or extinguish. Refer to the control panel tech- nical documentation for sensor LED status operation and expected delay to alarm. 9000-0558 2 I56-2036-01R Figure 2. Rotary decade address switches: When testing is complete, restore the system to nor- mal operation and notify the proper authorities that the system is back in operation. 6789 6789 5 5 Cleaning 4 / 4 / Before removing the detector, notify the proper authorities •� •411100. that the smoke detector system is undergoing maintenance 2� 2� and will be temporarily out of service. Disable the zone 10 1 0 or system undergoing maintenance to prevent unwanted alarms. TENS ONES 1. Remove the sensor to be cleaned from the system. C0146-00 2. Remove the sensor cover by pressing firmly on each of Figure 3. Test magnet position: the four removal tabs that hold the cover in place. 3. Vacuum the screen carefully without removing it. If fur- ther cleaning is required continue with Step 4, other- Magnet Test . Test Magnet wise skip to Step 7. Marker Position 4. Remove the chamber cover/screen assembly by pulling it straight out. 5. Use a vacuum cleaner or clean, compressed air to remove dust and debris from the sensing chamber. 6. Reinstall the chamber cover/screen assembly by sliding LED Status A • , . the edge over the sensing chamber. Turn until it is firm- Indicators ly in place. °p NOT PPO 7. Replace the cover using the LEDs to align the cover and then gently pushing it until it locks into place. Make sure that the thermistors do not become bent under the cover on ASD-PTL2 and MCS-ACCLIMATE2. Magnet Test Marker ©_ _ 8. Reinstall the detector. 9. Test the detector as described in TESTING. b___. Test Magnet 10. Reconnect disabled circuits. 1.=1]./1 Position 11. Notify the proper authorities that the system is back on line. C0145-00 Figure 4. Sensor assembly: 111 I-III\ p .—Sensor 00 NOT PA\NZ Cover 1 - 12 , Sensing =I I= Chamber I ( Cover and Cover Screen abs Removal Ill II II Illy - Sensing �� Chamber . 1 �_ • 1 Optional _ �. Thermistors • IraWils Uiim (ASD-PTL2 and MCS-ACCLIMATE2) ®m S 00124-00 9000-0558 3 I56-2036-01R FIRE CONTROL IL INSTRUMENTS MS SERIES Building Intelligent Networks wwwfirecontrolinstruments.com NON-CODED, MANUA L FIREALARM STATIONS Model MS-2, MS-2H FEATURES The MS-2 manual fire alarm stations are dual • Single and Dual Action Versions action devices.These stations require that • Tumbler Lock for Test and Reset the outer door be lifted to expose the ac- tuation door which is then pulled forward Keyed Alike with FCI Control Panels to operate the alarm toggle switchThe ac- • Rugged Metal Construction tuation door is now locked in the readily • Positive Indication of Operation over observable"alarm"position. t 180 Viewing Angle To reset the station,a key (common to .. FCI control panels) must be inserted and • Surface or Semi-flush Mounting turned 'A turn clockwise, opening the sta- • Shock and Vibration Resistant Lo "`, '1.,1 MS-2 don. Closingthe station resets the switch Institutional Version (MS-2L) automatically. MS-2P • Presignal Version ( ) An optional breakglass rod is available for positive indication of station operation. • Optional"FIRE SUPPRESSION 4 SYSTEM RELEASE" Markings Model MS-2P (Presignal) (MS-2H) �f Operation of the Model MS-2P Presignal ▪ Optional DPST Switch(MS-2-D) d station is similar to that of the MS-2,with MS-2H - the addition of a key-operated switch mounted on the lower door.This switch m ay be used for"general alarm"signaling. Model MS-2L (Institutional) W 4 Operation of the Model MS-2L institu- tional station requires that a special key be used to release the actuation door before it �. , _ MS-6 can be operated. Model MS-2-D (Multiple Contact) The MS-2-D features a DPST switch for multiple signaling via wire lead connections. CO 4* Model MS-6 (Single Action) APPROVED The MS-6 station is a single action device, requiring only the pulling of the action door mEA to release the compressed button switch.It /'"e�::u is available either with terminals(MS-6T)or wire leads(MS-6). c ° `r - .) The station resets in the same manner as S »°"� the MS-2.The reset key is common to FCI control panels. An ISO 9001 Company Specifications are provided for information only,are not intended co be used for installation purposes and are believed to be accurate However,no responsibility is assumed by Fire Control Instruments for their use.Speci- beacions subject to change without notice. ©2003All Rights Reserved ® 9020-0358NER.1.6 Page lof 2 F:71FCONTROL IRE INSTRUMENTS MS SERIES IMMIIIIMIMIIIIIIIMMI Building Intelligent Networks www.firecontrolinstruments.com 01e AG _ , ,,,.,,,4i‘r.,,, 41 0 "Existing Work" 4111111 \ Swi[chbox v,- 4 1%4 _ Model BB-2 Surface Backbox AG ENCYAPPROVALS UL(Std 38) File S2465 FM(MS-2) OJ3A9.AY/12880 (MS-6, MS-6T) I D4A7.AY C.S.F.M. 7150-0694:107 NYC BS&A(MS-2, MS-6) 960-81-SA NYC MEA(MS-2, MS-6) 103-93-E SPECIFICATIONS Material(MS-2,MS-6) Extruded 6063/T5 aluminium Doors(MS-2,MS-6) Clear anodize Switch Type MS-2 Enclosed toggle MS-6 Enclosed push button Contact Material Silver plated bronze or copper Contact Ratings MS-2 6 amp.max.@ 30VDC (resistive) MS-6 0.5 amp.max.@ 30VDC (resistive) Dimensions (overall) MS-2, MS-6 5" H x 3.4"W x 2.8" D (12.7 cm x 8.64 cm x 7.11 cm) ORDERING INFORMATION Part No. Model Description 100-0615 MS-2 Dual action fire alarm station 1100-0634 MS-2H Dual action station with "FIRE SUPPRESSION SYSTEM RELEASE"markings 100-0619 MS-2P Presignal fire alarm station 100-0621 MS-2L Institutional fire alarm station 100-0617 MS-2-D Dual action station with DPST switch 1100-0632 MS-6 Single action station,wire leads 100-0633 MS-6T Single action station,terminals 2520-0023 BB-2 Surface back box for MS-2, MS-6 stations 1120-0206 Package of two replacement breakglass rods for MS-2 station Specifications are provided for information only,are not intended to be used for installation purposes and are believed to be accurate. H ovever,no responsibility is assumed by Fire Control Instruments,for their use.Specifications subject to change without notice. ©2003All Rights Reserved FIRE CONTROL INSTRUMENTS 16 Southwest Park,Westwood,MA 02090 USA •Te1:781-471-3000 • Fax:781-471-3099 • www.firecontrolinstruments.com 9020-03S8NER.1.5/Page 2 of 2 • - . •-- Model 5495 SILENT Distributed Power Module KNIGHT In an emergency, by Honeywell you need maximum power The 5495 Distributed Power Module by Silent Knight is the most powerful and cost-effective power supply available today. It delivers 6 amps of notification appliance circuit power and built-in synchronization for appliances from System Sensor®,Gentex®, AMSECO®, Wheelock and Faraday—what you need to drive power- hungry components like ADA notification appliances. The 5495's advanced microprocessor design is years ahead of the competition. Its switch mode power supply design is up to 50% more efficient than competitive linear mode power supplies.And, ADA retrofits are easier and less expensive with the 5495 because it integrates into current systems without the costly investment in new components. For the most sophisticated and cost-effective notification power supply available, you need the 5495. Call Silent Knight today for more information at 1-800-328-0103. Model 5495 to non-essential high-current accessories like magnetic door t, Distributed Power Module holders T �_ The 5495 is a 6 amp notification power Built-in synchronization for expander that provides its own AC appliances from System power connection, battery charging Sensor®,Gentex®,AMSECO®, circuit, and backup battery for use with fire and security controls such as the Wheelock and Faraday Silent Knight Model 5208 Fire Control • Stand alone operation /Communicator.The 5495 is the cost- • Lightweight design adds to ease of effective solution for powering installation and reduces shipping in " 9 notification appliances required by the costs Americans with Disabilities Act (ADA). Operates with most polarized, UL The 5495 has built-in ANSI cadence Listed notification devices pattern, which can upgrade older control panels that lack cadence • ANSI Cadence pattern output capability. capability built-in I'.I( r Features Connection to Local Fire Control • UL Listed for 6 amps of notification The 5495 may be connected to a local Model 5495 fire control which utilizes Class A or power Class B type notification circuits Distributed Power Module • Power supply's advanced switch operating between 9 and 32 VDC.The mode design reduces damaging control panel's notification circuit is Approvals heat and manages power up to 50% connected to one of the inputs on the • UL Listed more efficiently than other systems 5495. The control panel's notification • MEA 429-92-E Vol XII • Dip switches allow for easy circuit end-of-line resistor is also • CSFM 7300-0559:123 reconfiguration connected across two terminals on the • NFPA 72 • 24 VDC filtered output voltage 5495, which provides supervision • Four power-limited notification between the 5495 and the fire control outputs; 2 Class A or 4 Class B, or 1 panel. Polarized audible and/or visual Class A and 2 Class B notification devices are then connected • Additional continuous auxiliary to the 5495 signal circuits using the output 4.7kS2 end-of-line resistors provided. Since the 5495 draws very little power • 3 amps per output circuit from the control, it is possible to • 2 inputs; 2 Class B or 2 Class A connect one 5495 to each notification • Ground fault detector/indicator circuit on the control panel and still • Independent trouble relay provide full supervision of the • AC loss delay option shuts off power notification circuits all the way back to the control panel. - - . . •- - Model 5495 Distributed Power Module Model 5495 Block Diagram Signal Circuit Output Signal 1 Signal 1 Input Distributed Signal 2 Signal Circuit Output Signal 2 Power Input Module 5495 Signal 3 (Optional) Signal 4 120 VAC Aux. Power 1 Trouble Output Local Fire Control (Alternative to notification circuit trouble.) Supervision Current: Input The 5495 supervises a variety of Standby 75 mA voltage range: 9 - 32 VDC functions including: Alarm 205 mA Battery charging • Low AC power Auxiliary capacity: 35.0 AH • Low battery condition power circuit: 1 Ambient temp.: 32° to 120° F • Earth ground fault Notification (0° to 49° C) • Auxiliary output power limit circuits: 4 Mechanical condition Output Dimensions: 12.25" W x 16" H x • EOL supervision trouble or 3" D (30.88 cm W 2 Class A(Style Z) configuration: power limited condition at an 9 x 40.64 cm H x 4 Class B (Style Y) output (1 Class A& 7.62 D cm) When a trouble condition occurs, 2 Class B) Indicator Lights the 5495 creates a trouble condition on the host control signal Amps per AC power on : Green circuits to which it is connected. the output circuit: 3.0 (6.0 amps total) Battery trouble: Yellow 5495 still maintains the ability to be Notification Ground fault: Yellow activated by the host control. In circuit output: 20.4 to 27.3 VDC addition, the 5495 provides a Form @ 3.0 amps each, Aux trouble: Yellow C trouble relay output as an 4.7 kit EOL Output troubles (1-4): Yellow alternative to using the notification resistor required Ordering Information circuit trouble. on each Class B 5495 Distributed Power Module circuit Electrical Specification No. of inputs 2 AC input: 120 VAC at 2 amps Input Output: 24 VDC at 6 amps configuration: 2 Class B or 2 Class A SILENTEl KNIGHT This document is not intended to be used for installation purposes.Woe try to MADE IN AMERICA keep our product information upt-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are FORM#350395 Rev D subject to change without notice. For more information, contact Silent Knight ©2010 Honeywell International Inc. by Honeywell 12 Clintonville Road, Northford, CT 06472-7161 Phone: (800)328-0103, Fax: (203)484-7118.www.silentknight.com /0„----7 • __ _ . genesi*s® _ ___ __ __ .s NP ' 'fes :.--.”,,, N P 7- 1 2 NP7- 12FR Sealed Rechargeable Lead-Acid Battery •NOMINAL VOLTAGE: 1 2V •CHARGE RETENTION(shelf life) 1211, 7.QA1 1 at 68°F(20°C): •NOMINAL CAPACITY: 1 month 97% 20 hr.rate of 0.35A to 10.5V 7.OAh 3 months 91% 10 hr.rate of 0.65A to 10.5V 6.SAh 6 months 85% Terni 5 hr.rate of 1.19A to 10.2V 5.95Ah 1 hr.rate of 4.20A to 9.60V 4.2Ah •LIFE EXPECTANCY: .185 f.004 STANDBY USE 3 to 5 years IN •WEIGHT(approx.): 6.17 pounds CYCLE USE (approx.): 060 oz0 (2.80 kgs.) 100%depth of discharge 250 cycles �{ 50%depth of discharge 550 cycles i �A� a •ENERGY DENSITY(20 hr.rate): 30%depth of discharge 1200 cycles o $ �� _ 1.49 WH/cubic inch(91.0 WH/liter) •SEALED CONSTRUCTION: t INCH=MM •SPECIFIC ENERGY(20 hr.rate): Can be operated in any position 250 6.35 13.6 WH/pound(30 WH/kg) without leakage. I .185 4.70 mill .124 3.15 •INTERNAL RESISTANCE OF CHARGED •STANDARD TERMINAL: 098 2.49 BATTERY: Quick Disconnect.187 .031±.004 30 milliohms(approx.) or Optional.250 °060 1.52 .031 0.79 •MAXIMUM DISCHARGE CURRENT •HOUSING MATERIAL: ABS Resin .020 0.51 WITH STANDARD TERMINALS: • .004 0.10 Dimensions 40 amperes •OPTIONAL: Container and cover made from •MAXIMUM SHORT-DURATION Flame Retardant ABS DISCHARGE CURRENT: (UL94-VO/L.O.I.>28%) 210 amperes •OPERATING TEMPERATURE RANGE: ��1 8 CHARGE 5°F to 122°F �j �I (-15°C to 50°C) 65 I e e 0 DISCHARGE -4°F to 140°F (2.56±0.04) J mo 6 (5.95±004) H ,- v c I m : m .W 4'G•., M +10 f tel ai"`'_ -, DIMENSIONS:MM (INCHES) UL listing pending-File No MH16464 (1-S-0 E __, ...., ,„, ...., ..9000 ner . T. , TM 1 *p. ower/Fu/l Solutions Publication No: US-NP7-12-02 •July 2005 DISCHARGE CHARACTERISTIC TEMPERATURE EFFECTS IN RELATION CURVES AT 25°C (77° ) TO BATTERY CAPACITY (V) (V) (V) 12V 6V 4V Battery Battery Battery (%) NP Temperature 25°C(77°F) -1 120 13.0 6.5-4.33 51111.1.111111.11111111.11111111111111 J ���' liglag�1`i•'�' . > 100 P — -- 1U- 6.0-4.0 < 00� ci _�111\\1�1111113 BO C 11.0- s.5-3.67."11,1�,��'o.zo r.1(AO.OSC U 0 '0 ' z 60 10.0- 5.0-333 9.0^ 4.5-3.0..,'II '1cA0.6CA4CA I,1 4 40 ••II 1CA e.a• a.0-267::' 11111 2CA IMI 1111111 Lu c 20 • I 111111111.1 --- 3CA I 0 1 z 4 b e 10 20 40 60 2 4 6 e 16 w -20 -10 0 10 20 30 40 50 (°C) l' min .f h—.i -24 14 32 - 50 68 86 104 122 (°F) Discharge lime Temperature SELF DISCHARGE CHARACTERISTICS OPEN CIRCUIT VOLTAGE VS REMAINING CAPACITY (%) (6) AT 25°C(77°F) 100 \I c 14.0 J :: . O ecD v 12.0 2 120°C(613°F) w .. ... 40°C(104°F) 30°C(86°F) c .. 25 ' ! 11.0 i 0 � 10.0 I 3 6 9 12 15 18 0 20 40 00 80 100 , STORAGE TIME(MONTHS) REMAINING CAPACITY(%) CYCLE SERVICE LIFE IN RELATION FLOAT SERVICE LIFE TO DEPTH OF DISCHARGE TESTING CONDITIONS:DISCHARGE CURRENT:0.17C AMP.(EV.1.71//CELL) a CHARGING CURflENT.0.09C AMP. -J TESTING CONDITIONS:FLOATING VOLTAGE 2.25 TO 2.30V/CELL a CHARGING VOLUME:125%OF DISCHARGED CAPACITY .7s AMBIENT TEMPERATURE:20°C TO 22'C(64°F TO 72°F) ¢ (AH%) AMBIENT TEMPERATURE:20°C TO 25°C(68°F TO 77°F) ¢ (AH%) • 120 0 120 n. 100 a 100v� d .v 800 • 80 o 50 .:` LLI c' c7 40 z 60 100%000 50%0.0.0. 30%DEPTH OF DISCHARGE Z Y0 W z V 40 Fc 0 1 2 3 4 5 5.5 • d L 20 LIFE(YEARS) , a 200 400 600 800 1000 1200 1400 NUMBER OF CYCLES When the battery will be used by current in excess of 3C,consult with EnerSys prior to use. CHARGING METHODS(At 20°C) Cycle use: Maximum charging current 1.75A Charging voltage 14.4 to 15.0V CAUTION •Avoid short circuit Standby use: Float charging voltage 13.50 to 13.80V •Do not charge in a sealed container. EnerSys EnerSys EMEA Represented by: EFP.O. Box 14145 Brussels, Belgium Ener Sm Reading, PA 19612-4145 Tel:+32(0)2 247 94 47 USA EnerSys Asia '.----''''''''-'—'s Tel:+1-610-208-1991 Guandong, China +1-800-538-3627 Tel:+86 755 689 9220 Printed in U.S.A. www.enersys.com ©2005 EnerSys.All rights reserved. Trademarks are the property of EnerSys and its affiliates unless otherwise noted. ' H` VAC SYSTEMS 1# � , : / innovr- LOW.FbW OJC`SR',I,Del-d,7echno1'31 4-Wire Low-FlowSYSTEMSENSOR Duct Smoke DetectorS Model DH100ACDCLP 4-Wire Photoelectric k �, 10 „- Duct Smoke Detector with Low-Flow ,,,,,,/ 7,..„-- - /4141 '' -, Technology ", rf` `� C Product Overview Air velocity rating from The System Sensor Innovair''"DH100ACDCLP is a 4-wire photoelectric air 100 to 4000 feet per minute duct smoke detector capable of sensing smoke in air velocities from 100 to (0.5 to 20.32 m/sec.) 4,000 feet per minute (0.5 to 20.32 m/sec). This Innovair features Low-Flow Patented interconnectabillity for multi- technology that enables duct smoke detection throughout a broad range of air- fan shutdown (up to ten air handlers) flow environments. Many difficult to solve HVAC applications occur in low air- Patented telescopic sampling tube flow duct applications where reliable smoke detection is critical. Innovair with Patented cover tamper trouble signal Low-Flow technology can detect smoke at air speed velocities of 100 feet per 24 VAC/DC or 120/240 VAC operation minute or greater, while continuing the same reliable performance to 4,000 feet per minute. High-Low voltage barrier The two available form C relay contacts provide reliable performance for the Equipped with two DPDT Form C relay contacts management of fans, blowers and air conditioning systems. These HVAC devices can be configured to prevent the spread of toxic smoke and fire gasses Built-in reset button through a protected area Outside mounting tabs The Innovair family is designed for simplified installation and easy mainte- Easy and quick mounting to round nance. The modular construction allows for easy cleaning and uncomplicated or rectangular ducts from 1'-12' field replacement of the UL recognized power and sensor boards. The patented (0.3-3.7 meters) wide cover missing feature insures the cover is securely tightened following routine Easy to clean cleaning and maintenance. The patented interconnectability feature allows mul- UL recognized field-replaceable tiple Innovairs to communicate with each other. In the event smoke is detected, power and sensor boards the Innovair will signal the remaining interconnected detectors to initiate their Remote test station option _ relays for smoke control. Remote sounder option WARNING: Duct smoke detectors have specific limitations. Transparent cover for convenient DUCT SMOKE DETECTORS ARE: visual inspection NOT a substitute for an open area smoke detector, UL 268A listed NOT a substitute for early warning detection, and NOT a replacement for a building's regular fire 3-year warranty detection system. ® Refer to NFPA 72 and 90A for additional information about the proper application of duct smoke detectors. LISTED Architectural/Engineering Specifications The air duct smoke detector shall be a System Sensor Model DH100ACDCLP Series Duct Smoke Detector. The detector housing shall be UL listed per UL 268A specifically for use in air handling systems. The detector shall operate at air veloci- ties of 100 feet per minute to 4000 feet per minute (0.5 to 20.32 m/sec.). The unit shall be capable of controlling up to ten (10) air handling systems when interconnected with other detectors. The detector shall be capable of providing a trou- ble signal in the event that the front cover is removed. It shall be capable of local testing via magnetic switch or remote testing using the SSK451 Multi-Signaling Accessory or the RTS451KEY Remote Test Station. The unit shall be reset by local reset button or remote test station. The duct smoke detector housing shall incorporate an airtight smoke chamber in compliance with UL 268A, Standard for Smoke Detectors for Duct Applications. The housing shall be capable of mounting to either rectangular or round ducts without adapter brackets. An integral filter system shall be included to reduce dust and residue effects on detector and housing, thereby reducing maintenance and servicing. Sampling tubes shall either be telescoping or be easily installed by passing through the duct housing after the housing is mounted to the duct. The unit shall provide a spacial separation of no less than 14" (6.4 mm) and/or a physical barrier between the high and low voltage terminals. The enclosure shall meet all applicable NEC and NFPA standards regarding electrical junction boxes. Terminal connections shall be of the strip and clamp method suitable for 12-18 AWG wiring. Wiring Guide System wiring diagram for 4-wire duct smoke detectors AVAILABLE POWER INPUTS AVAILABLE POWER INPUTS CONNECT POWER SOURCE POWER INPUTS ACCEPT TO APPROPRIATE TERMINALS 24 VDC,24 VAC 50-60 HZ, 9 10 A B C 9 10 A B C OF EACH DETECTOR.SEE 120 VAC HZ,OR SPECIFICATIONS FOR 220/240 VACAC 5 50-60-60 HZ. } ? ® ® ADDITIONAL POWER SUPPLY CONNECT POWER SOURCE 24V� 120 INFORMATION. TO APPROPRIATE TERMINALS 120,� Y I OF EACH DETECTOR. VAC 24V VAC 220/240 220/240 VAC VAC ALARM AUXILIARY CONTACTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN,ETC. FOR FAN SHUTDOWN,ETC. le ) AUX.CONTACT RATINGS 16 6 17 7 18 8 16 6 17 7 18 8 10A @ 30 VDC RESISTIVE i, (, 0 , ' FOR WIRING OF AUXILIARY 1OA @ 250 VAC100mA MINIMUM @ 5 VDC N.C. C. N.O. N.O. N.C. N.C. C. N.O. to._ . N.C. DEVICES,REFER TO NOT INTENDED FOR MANUFACTURER'S CONNECTION TO CONTROL INSTALLATION INSTRUCTIONS PANELS. .yp of •y0 OR CONTACT MANUFACTURER. ALARM AUXILIARY CONTACTS SHOWN IN ALARM AUXILIARY CONTACTS SHOWN IN NOTE:THE SUPERVISORY RELAY NOW STANDBY.CONTACTS TRANSFER DURING STANDBY.CONTACTS TRANSFER DURING PROVIDES A"FORM C"CONTACT FOR ALARM AS INDICATED BY THE ARROWS. ALARM AS INDICATED BY THE ARROWS, CUSTOMIZED APPLICATIONS. FOR STANDARD APPLICATIONS,ONLY SUPERVISORY TROUBLE CONTACTS SUPERVISORY TROUBLE CONTACTS THE"NO"CONTACT IS USED TROUBLE CONTACT RATING - - 2.0 A @ 30 VDC resistive �,�14 3 14 3 I �.7 0---0-0 TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY. TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY. CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS REMOVED OR WHEN TAMPER FEATURE TIMES OUT.OPEN REMOVED OR WHEN TAMPER FEATURE TIMES OUT.OPEN CONTACTS SIGNAL TROUBLE CONDITION TO PANEL CONTACTS SIGNAL TROUBLE CONDITION TO PANEL +/ I I I 5, 5 Ill ALARM ALARM CONTACTS SHOWN ALARM • CONTACTS SHOWN INITIATION INITIATION OPEN IN STANDBY. INITIATION OPEN IN STANDBY. LOOP ` CONTACTS CONTACTS CLOSE CONTACTS CONTACTS CLOSE \\\\ 4, IN ALARM. 4 IN ALARM. 1 I I I I— UL LISTED 4-WIRE FIRST DETECTOR IN THE LOOP LAST DETECTOR IN THE LOOP SIFIED TOR PPEEBY PANEL MANUFACTURER CONTROL PANEL DH100ACDC DH100ACDCU ANUFACTURER Specifications Size Storage Temperature Range 14%" (37 cm.) Length —22° to +158°F (-30° to +70°C) 51/" (14 cm.) Width 2%" (7 cm.) Depth Operating Humidity Range 10%to 93% relative humidity non-condensing Shipping Weight 3% lbs. (1.7 kg.) Air Duct Velocity 100 to 4000 ft./min. (0.5 to 20.32 m/sec.) Operating Temperature Range 32° to 131°F (0° to 55°C) Electrical Ratings— DH100ACDCLP (Includes Detector) Power supply voltage: 20-29 VDC 24 VAC 50-60-Hz 120 VAC 50-60 Hz 220/240 VAC 50-60 Hz Input capacitance: 270 pF max. 270 pF max. N/A N/A Reset voltage: 3.0 VDC min. 2.0 VAC min. 10 VAC min. 20 VAC min. Reset time (with RTS451): .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec. Reset time (by power down): 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. Power up time: 34 sec. max. 34 sec. max. 34 sec. max. 34 sec. max. Alarm response time: 2 to 17 sec. 2 to 17 sec. 2 to 17 sec. 2 to 17 sec. Sensitivity Test: See detector label See detector label See detector label See detector label Power Supply Voltage 20-29 VDC 24 VAC 50-60 Hz 120 VAC 50-60 Hz 220/240 VAC 50-60 Hz CURRENT REQUIREMENTS(USING NO ACCESSORIES) Max.standby current 15 mA 35 mA RMS 25 mA RMS* 15 mA RMS* Max.alarm current 70 mA 125 mA RMS 35 mA RMS' 25 mA RMS' CONTACT RATINGS Alarm initiation contacts(SPST) 2.0A @ 30 VAC/DC(0.6 power factor) ACCESSORY CURRENT LOADS AT 24 VDC Alarm auxiliary contacts(DPDT) 10A @ 30 VDC DEVICE STANDBY TROUBLE ALARM 10A @ 250 VAC APA451 12.5mA Max. n/a 30mA Max. Note:Alan-n auxiliary contacts must switch 100mA minimum at 5VDC.Alarm auxiliary contacts shall not be PA400 OmA n/a 15mA Max. connected to inititaing circuits of control panels.Use the alarm initiation contact for this purpose. RA400Z OmA n/a 10mA Max. Trouble contacts(SPDT) 2.0A @ 30 VDC(resistive) RTS451/RTS451 KEY 12mA* n/a 7.5mA Max. SSK451 5mA Max. 9mA Max, 30mA Max. 'NOTE:When a unit is powered at the120VACor220/240VACinput,any Wiring diagram for DH100ACDCLP to APA451 combination of accessories may be used such that the given accessory loads are: 60 mA or less in the standby state; 110 mA or less in the alarm state. DH100ACDCLP APA451 Alarm Signal 15 O Alarm Important Interconnect Notes Aux.Power+ 0 •When using the interconnect feature, all interconnected units must be powered with the same, independent supply. Sup.N.0. el O Power •Polarity must be maintained throughout the interconnect wiring. Sup.COM 0 Connect terminal 12 on unit 1 to terminal 12 on unit 2 and so on. Similarly, connect terminal 1 on unit 1 to terminal 1 on unit 2 Aux.Power— 20 O Common and so on. NOTE: Wiring diagram shown is for DH100ACDCLP 4-wire duct Wiring diagram for DH100ACDCLP to SSK451 and interconnect smoke detector system equipped without a control panel. feature FIELD NOTE: A trouble condition is indicated when the green LED JUMPER FORCED is not illuminated. TEMPORAL PATTERN COMMON.0 Wiring diagram for the RTS451/RTS451KEY and TEMPORAL SELECT•0 I 15 ALARM SIGNAL ALARM SIGNAL 0O3 NOS SUPERVISORY interconnect feature SUPERVISORY SIGNAL ® ( 4 t CONTACT - RESET 0 0 RESET DH100ACDCLP RTS451/RTS451KEY TEST © 10 TEST Alarm Signal 15 0 (Red LED)Alarm POWER(-) ® ® AUX.POWER(-) POWER(+) 019 AUX.POWER(+1 Aux.Power+ 19 0 (Green LED) 1* l 2 INTERCONNECT+ I Power I O INTERCONNECT- I Sup.N.0. D i SSK451 DHIUNIT DCLP I I Sup.COM 0 l FIELD INSTALLEDUMLER 12 INTERCONNECT+ J 0 INTERCONNECT- Aux.Power 20 O DH100ACDCLP Coil Note: UNIT Reset 0 0 Please note that the magnetic coil supplied with the RTS451/RTS451KEY is not Field required when these accessories are used with the DH100 detectors.The function- Test 11 alit of the magnetic coil has been designed into the circuitryof the Innovair duct Installed Y g g Interconnect— iO Jumper smoke detectors. 0 Wiring diagrams for optional accessories Interconnect+ 12 Unit 1 *NOTE:For RTS451 KEY only 15 I I (+) 15 I I (+) without a Control Panel. ALARM SIGNAL(+) , , ALARM SIGNAL(+) DH100ACDCLP RTS451 does not have a terminal 6. UNIT 2 NOTE:Wiring diagram shown is for Aux POWER(—) AUX POWER(—) i I o RED Interconnect—O DH100ACDCLP 4-wire duct 20 I I —1 20 smoke detector system equipped without a control panel. Interconnect+ 12 NOTE:A trouble condition is indicated DUCT DETECTOR PA400(OPTIONAL) DUCT DETECTOR RA400Z OPTIONAL) when the green LED is not DH100ACDCLP AUDIBLE ALERT DIi100ACDCLP REMOTO(LED) ANNUNCIATOR illuminated. Ordering Information Part No. Description DH100ACDCLP 4-wire photoelectric duct detector with low-flow technology A5069 Replacement photoelectric detector board A5064 Replacement 4-wire power board Accessories ST-1.5 Metal sampling tube duct widths 1'-2'(0.3-0.6 m) MOD400R Sensitivity test module ST-3 Metal sampling tube duct widths 2'-4'(0.6-1.2 m) RA400Z Remote annunciator alarm LED ST-5 Metal sampling tube duct widths 4'-8'(1.2-2.4 m) F36-09-11 Replacement air filters(two per package) ST-10 Metal sampling tube duct widths 8'-12'(2.4-3.7 m) M02-04-00 Test magnet T80-71-00 Replacement telescoping sampling tube P48-21-00 End cap for metal sampling tubes P48-55-00 Replacement end cap for T80-71-00 S08-39-01 Photo replacement screen SSK451 Multi-Signaling accessory PA400W Mini-Alert sounder RTS451KEY Remote test station with key lock PS24LOW Mini-Alert add-on strobe RTS451 Remote test station PS12/24SLENSW Wall-mount "SMOKE" lens APA451 Remote annunciator with piezo alarm Accessories System Sensor provides system flexibility with a variety of accessories, including two remote test stations, and several different means of visible and audible system annunciation. As with our duct detectors, all duct smoke detector accessories are UL listed. N.. . . \ ' 7 G ® ® 0 I\ ® l Lu / Irll III ` ALARM \ I ' ALARM POWER \ r \ G M 1 \ 1 1 Q = � © �l 0 K IIIII E IIID / RESET f 0 . , e ti 1 APA451 RTS451KEY PA400W RTS451 RA400Z Piezo Annunciator Remote Test Station Mini-Alert Sounder Remote Test Station Remote Annunciator (UL S4011) with Key(UL 52522) (UL S3593) (UL 52522) (UL S2522) shown with PS24LOW add- on strobe(PS12/24SLENSW smoke lens option available) , @ @I / Oo • 0000000 Orae' /00 0 —. • 0000000 r >00 0000000000 on. , M ,00 0 ROM 000000 0 ,,,M, 004 )00 0 AW. 0000000000 `J 00080000000000 00' U � SSK451 0000000000 Mr 00, ,OO 0000000000 0000000000 00oc K multi-Signaling Accessory 0000000000 < >oX88 OSSK451 00< C >00 (UL 268A) ` Multi-Signaling shown with PS24LOW add-on Accessory r / N strobe(PS12/24SLENSW (UL 268A) smoke lens option available) System Sensor Sales and Service System Sensor Headquarters System Sensor Canada System Sensor in China System Sensor-Far East System Sensor-India 3825 Ohio Avenue Ph: 905.812.0767 Ph:86.29.524.6253 Ph: 85.22.191.9003 Ph:91.124.637.1770 x.2700 St.Charles, IL 60174 Fx:905.812.0771 Fx: 86.29.524.6259 Fx:85.22.736.6580 Fx:91.124.637.3118 Ph:800/SENSOR2 System Sensor Europe System Sensor in Singapore System Sensor-Australia Fx:630/377-6495 Ph:44.1403.276500 Ph:65.273.2230 Ph:613.54.281.142 Documents-on-Demand Fx:44.1403.276501 Fx:65.273.2610 Fx:613.54.281.172 800/736-7672 x3 www.systemsensor.com ©2002 System Sensor.The company reserves the right to change product specifications without notice. A05-1044-003.7/02.#980 ® UL FIRE CONTROL IFC FSATD-L, ATD-RL I NST ENT LOW PROFILE ADDRESSABLE THERMAL SENSOR DESCRIPTION The ATD-L, ATD-RL Low profile Addressable Thermal Sensors contain a state-of-the-art electronic dual thermistor sensing circuit for fast response.These sensors provide open area coverage with 50 foot spacing capability, and are de- � signed for use with FCI analog addressable fire alarm control panels. i The sensors are continually monitored to measure any change in their sensitivity due to temperature.Two LEDs on ; each sensor light upon alarm and provide a local 360°visibil 4454-, ity of alarm indication.The LEDs flash each time the unit is e, 4 interrogated. �� The sensors are of plug-in construction and are directly in- `,0 terchangeable in the same base with the ASD-IL and '',` ASD-PL low profile sensors. The bases include a tam- per-proof feature which,when activated,prevents removal of the sensor without the use of a tool. The sensors may be functionally tested by applying a test FEATURES magnet according to the test procedures. They should be cleaned at least once a year by removing them from their bases and vacuuming the dust from the sensing chamber. • Compatible with FCI Analog Remote LED annunciator capability is available as an op- Addressable Control Panels tional accessory. • Attractive Low-Profile ORDERING INFORMATION • High Coverage Part no. Model Description (50 Foot Mounting Centers) 114-90003 ATD-L Fixed Temp.Sensor • Easy Plug-in of the Head to Base 115-90005 ATD-RL Fixed Temp./Rate of Rise Sensor • High Velocity Performance 110-90005 ADB-FL Standard base w/flange and ring 110-31A60 B501 Base w/o flange • Built-in Signal Processing 110-90004 B224RB Base w/SPDT relay output • Built-in Tamper-resistant Feature rated 2 amps @ 30 VDC(resistive) • Built-in Test Switch 110-90006 B224BI Isolator base for Style 7 operation • o 130-3100G B501BH Plug-in sensor base with sounder 360 View Angle of Dual Alarm LEDs 138-01005 RA-400Z Remote alarm indicator • Optional Self-contained Sounder 110-9010N Detector sensitivity test kit SPECIFICATIONS Sensitivity: ATD-L 135°F(57°C)fixed temperature set point ATD-RL 15°F/min. (9.4°C/min)rate of rise Operating voltage 15-32 VDC(peak) Remote LED current .065 amp. Relay Contacts(B224RB Base) Form"C",2A @ 30 VDC resistive,0.3A @ 110 VDC inductive,0.3A @ 120 VAC with.35 or greater power factor, lA @ 30 VDC with.6 or greater power factor Operating/installation temperature -4 to 100°F(-20 to 38°C) Relative humidity 10 to 93%(non-condensing) Weight 3.6 oz(104 gm) Dimensions 2.0"H x 4.0"Dia. (5.1 x 10.2 cm) Specifications are provided for information only,are not intended to be used for installation purposes,and are believed to be accurate.However,no responsibility is assumed by Fire Control Instruments,Inc.for their use.Specifications subject to change without notice. ©1999 All Rights Reserved 301 2nd Ave Waltham, MA 02451-1133 USA TEL: (781)487-0088 FAX: (781)370-4132 9020-0489/Ver. 1.1 f! 1GameweII ISeries Fici FIRE RUMETLNDNR/DNRW Duct eNsaubm Ua iiIAiMM by Honeywell O11111RG nuuaUHHg Description Intelligent Non-Relay Photoelectric Duct Smoke Housing The InnovairFlexTM Series, DNR intelligent, non-relay pho . toelectric duct smoke detector, and the DNRW watertight, non-relay photoelectric duct smoke detector feature a piv _ •F• r� oting housing that fits both square and rectangular foot- prints.These detectors are capable of mounting to a round s or rectangular duct. The DNR/DNRW detectors can be • z • used with the E3 Series®and 7100 Systems. u Note: The InnovairFlexTM Series, DNR requires the Veloc iti®Series, ASD-PL2F Sensor and AOM-2RF, if relays are required for the fan control. InnovairFlex-DNR/DNRW The DNRW duct smoke detector,with its NEMA 4 rating, is Listed as a watertight enclosure providing protection against falling dirt, rain, and windblown dust,splashing and Features hose directed water.These features allow operators to use • Photoelectric, integrated low flow technology the detector in the most extreme environments. • Air velocity rating from 100 ft/min to 4,000ft/min The units sense smoke in the most challenging conditions, (0.5m/s to 20.32m/sec) operating in airflow speeds of 100 to 4,000 feet per minute, • Versatile mounting options: square or rectangular temperatures of-4°F to 158°F,and a humidity range of 0 to configuration 95 percent(non-condensing). • Broad ranges for operating temperature(-4°F to 158°F) and humidity(0%to 95% non-condensing) An improved cover design isolates the sensor head from • Patented sampling tube installs from front or back of the the low-flow feature for simple maintenance. A cover detector with no tools required tamper feature was added to indicate a trouble signal for a • removed or improperly installed sensor cover. The New Cover tamper signal InnovairFlex housing provides a 3/4-inch conduit knockout • Increased wiring space with a newly added 3/4-inch and ample space to facilitate easy wiring and mounting of conduit knockout the relay module. • Available space within housing to accommodate the mounting of the relay module The InnovairFlex duct smoke detector can be customized • Easily accessible code wheels on sensor head (sold to meet local codes and specifications without additional separately) wiring. The new InnovairFlex product line is compatible • Clear cover for convenient visual inspection with all previous Innovair models, including remote test accessories. • UL 268A Listed • Remote testing capability WARNING:Duct smoke detectors have specific limitations. • Requires SLC line power only DUCT SMOKE DETECTORS ARE: • NEMA Type 4 UL Listed for non-hazardous indoor and NOT a substitute for an open area smoke detector, outdoor applications(DNRW only) NOT a substitute for early warning detection, and NOT a • UV Resistant, UL Listed housing and cover material replacement for a building's regular fire detection system. (DNRW only) Refer to NFPA 72 and 90A for additional duct smoke detector 2911 application information. An ISO 9000-2000 Company SIGNALING E3 Series®and Velotic®are registered trademarks and InnovairFlexT°is a trademark of Honeywell International,Inc. LISTED 2911 GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 Specifications are for information only,are not intended for installation purposes,and are subject to change without notice.No responsibility is assumed by Gamewell-FCI for their use. ©2009 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9021-60475 Rev.A page 1 of 4 Architectural/Engineering Specifications The air duct smoke detector shall be a System Sensor InnovairFlexTM DNR Intelligent Non-Relay Photoelectric Duct Smoke Detec- torand DNRW Watertight NEMA4 Duct Smoke Detector.The detector housing shall be UL Listed per out 268A specifically for use in air handling systems.The flexible housing of the duct smoke detector fits both square and rectangular footprints. The detector shall operate at air velocities of 100 ft/min to 4,000 ft/min (0.5 m/sec to 20.32 m/sec).The unit shall be capable of providing a trouble sig- nal in the event that the sensor cover is removed or improperly installed. It shall be capable of local testing via magnetic switch or remote testing using the RTS451 KEY remote test station. Terminal connections shall be of the strip and clamp method suitable for 12-18 AWG wiring. Physical Specifications Size: Rectangular Dimensions: 14.38 in (37 cm)Length; 5 in (12.7 cm)Width;2.5 in(6.6 cm}Depth Square Dimensions: 7.75 in (19.7 cm)Length; 9 in (22.9 cm)Width;2.5 in (6.35 cm) Depth Weight: 1.6 lb(0.73 kg) Environmental Rating: NEMA4(DNRW only) Operating Temperature Range: —4°to 158°F(-20°to 70°C) Storage Temperature Range: —0°2:°to9510/508 158°F(-30°to 70°C) Operating Humidity Range: to relative humidity non condensing Air Duct Velocity: 100 to 4000 ft/min (0.5 to 20.32 m/sec) Electrical Ratings For information on electrical specifications, refer to the InnovairFlex DNR Duct Smoke Detector Installation Instructions, P/N 156-3051-001 R. Trouble Accessory Current Loads at 24 VDC Device Standby RA400Z 0 mA 12 mA Max. RTS451/RTS451 KEY 0 mA 12 mA Max. Installing the InnovairFlex Sampling Tube The InnovairFlex sampling tube may be installed from the front or back of the detector.The tube locks securely into place and can be removed by releasing the front or rear locking tab. (Figure 3 illustrates thefvront locking tab). A � +ted f; �� -4t4,4.44. 1 f�� 6: ,-; # b& R xg^ as { a r ,' �� u.W.0 _�•��.� �. ,,_� "'-'., .-:,w , 7... �.� �ice•. � ....��.._.,�x � Figure 1 Figure 2 Figure 3 - 12 Clintonville Road,Northford,CT 06472-1610GAMEWELL USA•Tel:FCI (203)484-7161 •Fax:(203)484-7118 9021-60475 Rev.A page 2 of 4 www.gamewell-fci.com J Wiring for Intelligent Non-Relay Duct Smoke Detector cora. -_i-.M► LINE (+) COMM. LINE LINE(-) —1-110'1 I I I UL/FM LISTED 1ST 2ND CONTROL DETECTOR DETECTOR PANEL IN LOOP IN LOOP Figure 4 System Wiring Diagram for DNR + RA RA400Z RA 4 REMOTE ALARM LED OPTION 1 PER UNIT Figure 5 DNR to RA400Z TEST COIL+ et EXTERNAL TEST COIL- ®(I POWER HS' _ 4 t COMM+ OUT(CON'S ONLY) + e RTS451,lTS451 KEY COMM- REMOTE TEST STATION RAIRTS- LED OPTION RA+ PER UNIT RTS+ ', TEST COIL OPTION 1 PER UNIT B5mA.CURRENT DRAW Figure 6 DNR to RTS451/RTS451 Key Important Notes: • The use of either RTS451 or RTS451 KEY requires the installation of an accessory coil, DCOIL,sold separately. For additional information,refer to the DNR or DNRW Duct Smoke Detector Installation Instructions, P/N 156-3051-001 R and the Duct Application Smoke Detectors Application Guide. • The RTS451/RTS451 KEY test coil circuit requires an external 24 VDC power supply which must be UL Listed. GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 www.gamewell-fci.com 9021-60475 Rev.A page 3 of 4 Accessories Q , +om Qc,ncnr n virloc V. ,c+om flovihili+v .ri+h . o+"nF orr occnrioc rL i, ., ,+s.,r.r +o+oV+c+o+innc and,ifforon+m !.f ible and audible system annunciation.As with our duct smoke detectors, all duct smoke detector accessories are UL Listed. ,, :k, Figure 7 RTS451 UL S2522 Figure 8 RTS451KEY UL S2522 Figure 9 RA400Z UL S2522 Ordering Information Part Number Description DNR Intelligent non-relay photoelectric low-flow duct smoke detector DNRW Watertight intelligent non-relay photoelectric low-flow duct smoke detector Accessories Part Number Description Part Number Description DCOIL Remove test coil required with RTS451/RTS451 KEY ETX Metal exhaust tube duct width 1ft(0.3m) DST1 Metal sampling tube duct width up to 1 ft(0.3m) M02-04-00 Test magnet DST1.5 Metal sampling tube duct widths 1 ft to 2 ft(0.3 to 0.6 m) P48-21-00 End cap for metal sampling tubes DST1.5 Metal sampling tube duct widths 1 ft to 2 ft(0.3 to 0.6 m) RA400Z Remote annunciator alarm LED DST3 Metal sampling tube duct widths 2 ft to 4 ft(0.6 to 1.2 m) RTS451 Remote test station DST5 Metal sampling tube duct widths 4 ft to 8 ft(1.2 to 2.4 m) RTS451 KEY Remote test station with key lock DST10 Metal sampling tube duct widths 8 ft to 12 ft(2.4 to 3.7 m) DH4000E-1 Weatherproof enclosure GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA•Tel:(203)484-7161 • Fax:(203)484-7118 9021-60475 Rev.A page 4 of 4 www.gamewell-fci.com HN Series Effective November 2016 HS Series Technical ata TD4550049EN Supersedes October 2014 ST Series Exceder Strobe, Horn Strobe, and Horn Notification Appliances Description ¢ 4 The Wheelock Exceder Series of notification appliances i feature a sleek modern design that will please building owners " •.,I' t with reduced total cost of ownership. Installers will benefit from `" } its comprehensive feature list, including the most candela options in one appliance, low current draw, no tools needed for setting ° C,- changes, voltage test points, 12/24VDC operation, universal mounting base and multiple mounting options for both new and - retrofit construction. I. The Wheelock Exceder Series incorporates high reliability and high ''"- efficiency optics to minimize current draw allowing for a greater , number of appliances on the notification appliance circuit.All strobe models feature an industry first of 8 candela settings on a single Vii; w appliance. Models with an audible feature 3 sound settings (90, 95, 99 dB).All switches to change settings, can be set without the use N of a tool and are located behind the appliance to prevent tampering. ,,r Wall models feature voltage test points to take readings with a r 'E voltage meter for troubleshooting and AHJ inspection. '::1 The Wheelock Exceder Series of wall and ceilingnotification f appliances feature a Universal Mounting Base (UMB) designed to simplify the installation and testing of horns, strobes, and j;p'I combination horn strobes.The separate universal mounting base can be pre-wired to allow full testing o.f circuit wiring before the appliance is installed and the surface is finished. It comes complete with a Contact Cover for protection against dirt, dust, paint and damage to the contacts.The Contact Cover also acts as a shunting device to allow pre-wire testing for common wiring issues. The Contact Cover is polarized to prevent it from being installed , incorrectly and prevents the appliance from being installed while it is on the UMB. When the Contact Cover is removed the circuit will show an open until the appliance is installed.The UMB allows for consistent installation and easy replacement of appliances if required.Wall models provide an optional locking screw for extra secure installation,while the ceiling models provide a captivated screw to prevent the screw from falling during installation. 1 ET°N Powering Business Worldwide Technical Data TD450049EN HN Series Effective November 2016 HS Series ST Series Features • Environmentally friendly • Low current draw • Sleek modern aesthetics • Finger slide switches • Up to 9 models now in 1 appliance draw • Voltage test points • 12/24VDC on a single appliance • Multiple voltages • Easy to remember model numbers • 3 Audible settings O Patented • 90, 95, 99 dB Note: Please read these specifications and associated installation instruc tions,before using,specifying,or installing this product.Visit Eaton.com/ • Industry leading-8 candela settings on 1 device massnotification for current installation instructions. • Wall: 15/1575/30/75/95/110/135/185 . Ceiling: 15/30/60/75/95/115/150/177 General Notes • Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range': • All candela ratings represent minimum effective strobe intensity ��„ based on UL Standard 1971. • Series Exceder Strobe products are Listed under UL Standards ` ,• 1971 and 464 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (±2%) UL 464(85% UL 1971). ��, _ • Series Exceder horns are under UL Standard 464 for audible - signal appliances (Indoor use only). : - Compatibility and requirements • Synchronize using the Wheelock®Sync Modules or panels with built-in Wheelock®Patented Sync Protocol • Compatible with UL"Regulated Voltage" using filtered VDC or • Universal mouting base unfiltered VRMS input voltage • Ceiling and wall • Strobes produce 1 flash per second over the "Regulated • Mounts to 5 backbox types: 1 gang, 2 gang,4" square, Voltage" range 3.5" octal. &4" octal. (100mm for international customers) Universal mounting base Contact cover Compliance • UL 1971, UL 464, ULC, CSFM, FM 'it ' • ADA/NEPA/ANSI/OSHA � � RoHS s � �;� y�� �1 1 i a , Common base for wall and ceiling with 5 mounting options • Voltage test points for quick troubleshooting and easy spot checking (wall models only) _......._...... (�i v b 0 g_ ,,.. 1 1 1 1 2 EATON www.eaton.com HN Series Technical Data TD450049EN HS Series Effective November 2016 ST Series Table 1. Strobe Ratings per UL Standard 1971 UL Max Current® 24 VDC/24 FWR 12 VDC Regulated Voltage Model Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 ST 8.0-33.0 0.057 0.070 0.085 - 0.135 0.163 0.182 - 0.205 - - 0.253 0.110 0.140 ►STC 8.0-33.0 0.061 - 0.085 0.103 0.135 0.163 - 0.182 - 0.205 0.253 - 0.110 - Table 2. Horn Strobe Ratings per UL 1971 &Anechoic at 24 VDC UL Max Current®at Anechoic 99 dBA 24 VDC 12 VDC Regulated Voltage Model Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 HS 8.0-33.0 0.082 0.095 0.102 - 0.148 0.176 0.197 - 0.242 - - 0.282 0.125 0.159 0.HSC 8.0-33.0 0.082 - 0.102 0.141 0.148 0.176 - 0.197 - 0.242 0.282 - 0.125 - UL Max Current®at Anechoic 95 dBA 24 VDC 12 VDC Regulated Voltage Model Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 HS 8.0-33.0 0.073 0.083 0.087 - 0.139 0.163 0.186 - 0.230 0.282 0.122 0.153 HSC 8.0-33.0 0.073 - 0.087 0.128 0.139 0.163 - 0.186 - 0.230 0.272 - 0.122 - UL Max Current®at Anechoic 90 dBA 24 VDC 12 VDC Regulated Voltage Model Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 HS 8.0-33.0 0.065 0.075 0.084 - 0.136 0.157 0.184 - 0.226 - - 0.267 0.120 0.148 HSC 8.0-33.0 0.065 - 0.084 0.120 0.136 0.157 - 0.184 - 0.226 0.267 - 0.120 - ,O UL max current rating is the maximum RMS current within the listed voltage range(16-33 VDC for 24 VDC units).For strobes the UL max current is usually at the minimum listed voltage(16 VDC for 24 VDC units).For audibles the max current is usually at the maximum listed voltage(33 VDC for 24 VDC units).For unfiltered ratings,see installation instructions. Table 3. Horn Ratings per UL Anechoic Model Legend Regulated Voltage Model Range VDC 99 dB 95 dB 90 dB HN = Horn R = Red HN 16-33.0 0.064 0.044 0.022 ST = Strobe A = Agent Lettering(strobes only) HNC 16-33.0 0.084 0.044 0.022 HS = Horn Strobe AL = Alert Lettering(strobes only) HN 8.0-17.5 0.047 0.026 0.017 C = Ceiling Mount N = No Lettering(strobes only) HNC 8.0-17.5 0.047 0.026 0.017 W = White Example 1:STRC=Strobe,Red,Ceiling Mount Table 4. Specification&Ordering Information Example 2:HSR=Horn Strobe,Red,Wall Mount w!DSM or Example 3:HSW=Horn Strobe,White,Wall Mount sWhencelock Power 12/24 Mounting Example 4:STW-AL=Strobe,White,Wall Mount,Alert Lettering Model Strobe Candela Supplies VDC® Options Horn Strobes HSR 15/1575/30/75/95/110/135/185 X X UMB® _y , 'i HSW 15/1575/30/75/95/110/135/185 X X UMBO t� HSRC 15/30/60/75/95/115/150/177 X X UMB© • i /i •., 14-' HSWC 15/30/60/75/95/115/150/177 X X UMBO 't , , a: Strobes � - ', , STR 15/1575/30/75/95/110/135/185 X X UMB® - :/ - 4 s� STW 15/1575/30/75/95/110/135/185 X X UMB® STRC 15/30/60/75/95/115/150/177 X X UMBO . _.,,,,,,,6\00 STWC 15/30/60/75/95/115/150/177 X X UMBO .4 ,,. Horn , HNR 434C47440NWAI XX UMBO ,�,,/ n X X UMB© HNRC 1' 44 X X UMB OO HNWC �. X X UMBC) Example: HSR Example:HSWC O 12 VDC models feature 15&15/75 settings CO UMB=Universal Mounting Base EATON www.eaton.com 3 A Technical Data TD450049EN HN Series Effective November 2016 HS Series ST Series Architects and Engineers Specifications The notification appliances shall be Wheelock Exceder Series HS Audible Strobe appliances, Series ST Visual Strobe appliances and Series HN Audible appliances or approved equals.The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired)for Indoor Fire Protection Service.The Series HS and HN Audibles shall be UL Listed under Standard 464(Fire Protective Signaling).All Series shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP) with the ability to operate from 8 to 33 VDC. Indoor wall models shall incorporate voltage test points for easy voltage inspection. The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1)flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan®lens.The Series shall be of low current design.Where multi- candela appliances are specified,the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110, 135, 185 candela for wall mount and 15,30, 60, 75, 95, 115, 150, 177 candela for ceiling mount.The selector switch for selecting the candela shall be tamper resistant.The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required (e.g.,ADA compliance).Appliances with candela settings shall show the candela selection in a visible location at all times when installed. The audible shall have a minimum of three(3) field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3) audible outputs. The Series HS Audible Strobe, ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow mounting to a single-gang, double-gang,4-inch square,3.5-inch octal, 4-inch octal or 100mm European type back boxes.Two wire appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel (FACP).The mounting base shall be the same base among all horn, strobe, horn strobe,wall and ceiling models.All notification appliances shall be backwards compatible. The Series HS and ST wall models shall have a low profile measuring 5.24" H x 4.58"W x 2.19" D. Series HN wall shall measure 5.24" H x 4.58"W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68" x 2.63" D. Series HNC ceiling shall have a diameter of 6.68" x 1.50" D. When synchronization is required, the appliance shall be compatible with Wheelock's DSM Sync Modules,Wheelock Power Supplies or other manufacturer's panels with built-in Wheelock Patented Sync Protocol.The strobes shall not drift out of synchronization at any time during operation. If the sync protocol fails to operate,the strobe shall revert to a non-synchronized flash-rate and still maintain (1)flash per second over its Regulated Voltage Range.The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation when used with Wheelock synchronization protocol. Wall Appliances: UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM, RoHS Ceiling Appliances: UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM, RoHS Note:Due to continuous development of our products,specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc.,dba Eaton standard terms and conditions. wawa WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Eaton 1000 Eaton Boulevard Cleveland,OH 44122 United States Eaton.com Eaton Life safety&mass notification solutions 273 Branchport Ave. Long Branch,NJ 07740 Eaton.com/massnotification ©2016 Eaton EAll Rights Reserved A N Printed in USA Eaton is a registered trademark. Publication No.TD450049EN All other trademarks are property Powering Business Worldwide November 2016 of their respective owners.