January 3, 2019 BUILDING DIVISION
Plans Examiner
City of Tigard
Building Services
13125 SW Hall Blvd.
Tigard, OR 97223
Re: Tenant Fire Alarm System Additions
Compass Oncology
Tigard Corporate Center Building A
12123 SW 69th Avenue
Tigard, OR 97223
Please find attached building and electrical permit applications, three sets of plans,
calculations, and product submittals for the fire alarm tenant improvements at the address
shown above.
Occupancy Group: B
The fire alarm system design includes the following:
1. Relocate the existing FCI FACP behind the front entry desk.
2. Reuse the existing 2 phone lines for offsite communication.
3. Relocate (1) manual pull station near the front entry.
4. Relocate (2) existing duct smoke detectors and (2) fire smoke dampers.
5. Install new ADA synchronized fire alarm notification devices in the tenant space
including (30) horn strobes & (103) strobes.
6. We will pre-test the fire alarm devices prior to requesting a final fire alarm
inspection.
Please contact me if you have questions or comments.
Respectful) ,
Shane Tercek
Project Manager/Estimator
Fire/Life Safety Division
Capitol Electric Company, Inc.
(503) 262-0405 Direct
shane@cepdx.com
NICET Level III, Fire Alarm Systems #140599
11401 NE Marx • Portland, Oregon 97220-1041 • 503-255-9488 • Fax 503-257-7121
CCB# 48748 • www.capitolelectricco,corn
Turner Submittal #28 31 00-4.0
RECEIVED 28 31 00 - Fire Detection &
Alarm System
JAN 7 2019
Turner Construction-Portland Project: 181019-Compass Oncology-Westside Cancer Center
1155 SW Morrison St.,Suite 600 CITY OF E IGARD 12123 SW 69th Ave
Portland,Oregon 97205 BUILDING DIVISION Portland,Oregon 97223
Phone:(503)226-9825
283100-04 Fire Alarm System - Resubmittal
SPEC SECTION: 28 31 00-Fire Detection&Alarm System SUBMITTAL MANAGER: Eric Mishler(Turner-Portland)
STATUS: Open DATE CREATED: 12/14/2018
ISSUE DATE: 12/14/2018 REVISION: 0
RESPONSIBLE Capitol Electric RECEIVED FROM: John Uhl
CONTRACTOR:
RECEIVED DATE: 12/12/2018 SUBMIT BY: 12/14/2018
FINAL DUE DATE: 12/28/2018 LOCATION:
SUB JOB: COST CODE:
APPROVERS: Steven Castaneda(Corgan)
BALL IN COURT:
Steven Castaneda(Corgan)
DISTRIBUTION:
Ryan Haggerty (American Heating),Mark Morton (Chown Hardware),Steve McCourtney (Delta Fire),Michael Schneider (Turtle Mountain)
,Eric Montoya (American Heating),Aaron Davies (Dallas Glass),Kraig Goode (Dallas Glass),John Uhl (Capitol Electric),Ann Westelin
(Metro Overhead Door),Sean Dyer (American Heating),Barry Kenfield (Metro Overhead Door),Tom Eback (Turtle Mountain),John Tuttle
(American Heating),Scott Unholz (Capitol Electric), Brent Bodwell (Dallas Glass)
DESCRIPTION:
Revised fire alarm system submittal including all revisions required per design team.Please review for general conformance with design intent and
provide engineer stamp on each floor plan.
Please expedite review as revisions included are minor and response time has schedule impacts.
ATTACHMENTS:
983100-04 Fire Alarm System-Resubmittal pdf
SUBMITTAL WORKFLOW
RETURNED
NAME SUBMITTER/ SENT DATE DUE DATE RESPONSE ATTACHMENTS COMMENTS
APPROVER DATE
•
Steven Castaneda Approver 12/28/2018 Pending
BY DATE COPIES TO
Turner Construction-Portland Page 1 of 1 Printed On: 12/14/2018 03:53 PM
NNSI ) iEC
JAN 7 2019 EIVED
CITY OF TIGARO
SUBMITTAL COMMENTS BUILDINGDIVISION EXCEPTIONS NOTED X
NOTED
[ ] RESUBMIT FOR RECORD
Project Name: McKesson Tigard Cancer center [ I NO RESUBMISSION REQUIRED
REVISE AND RESUBMIT
WSP I USA ID# REVIEWED FOR INFORMATION ONLY
Date Received UNREVIEWED
Corrections or comments made on the shop drawings during this review do not relieve
Description 283100-04 Fire Alarm System - Resubmittal contractor from compliance with requirements of the drawings and specifications.
This check is only for review of general conformance with the design concept of
Action: NO EXCEPTIONS NOTED this part of the project and general compliance with the information given in
the contract documents. The contractor is responsible for providing all information
Fabrication,manufacture,or construction may proceedproviding submittal necessary for this review: confirming and correlating all quantities and dimensions:
selecting fabrication processes, techniques and sequences of construction;
complies with the Contract Documents. coordinating work with that of other trades and performing work in a safe and
satisfactory manner. Notations on this drawing do not authorize changes to the
contract documents without written authorization from the owner's representatives.
WSP USA
RAMYADEVI PRAKASAM 12/26/2018
Comments Additional Reviews by:
WSP Response:
1. Confirm the finish with the architect.
2. Confirm the system address and Labeling methodology with the owner.