Report ESC \%;"GCAa-%
i3 Su .0 �LO-3
Taco Bell—Tigard OFFICE COPY
13305 SW Pacific Highway,Tigard OR 97223 V
Electrical Permit#- ELC2018-00828
For Plan Review.
Project Description
Demolition of an existing Taco Bell Restaurant with a 600A 208/120V 3 Phase Service.
New Taco Bell Restaurant with 600A 208V/120V 3 Phase Service.
No increase in load.
All new electrical installation. New LED lighting throughout.
All new building management controls,to control HVAC and Lighting.
All to be installed to engineered drawings dated 10-16-2017, 2 sets included in this package.
CITY OF TIGARD ELECTRICAL PERMIT
111111
COMMUNITY DEVELOPMENT Permit#: ELC2018-00828
13125 SW Hall Blvd.,Tigard OR 97223 503.718.2439 Date Issued: 12/21/2018
TIGARD Parcel: 2S102CB01804
Jurisdiction: Tigard
Site address: 13305 SW PACIFIC HWY
Project: M8036-Taco Bell Tigard Subdivision: None Lot: None
Project Description: Install Electrical Service
Contractor: ADK ELECTRIC, INC. Owner: WEBER COASTAL BELLS LIMITED
9000 NE 90TH STREET WEBER, EDUARD
VANCOUVER,WA 98662 840 CONGER ST
EUGENE, OR 97402
PHONE: 360-546-5155 PHONE:
FAX: 360-576-6975
FEES
Quantity Description Date Amount
3 ea Services or Feeders-200 12/21/2018 $302.10
Specifics: amps or less
1 ea Services or Feeders-201 to 12/21/2018 $133.56
Type of Use: COM 400 amps
Class of Work: NEW 1 ea Services or Feeders-401 to 12/21/2018 $200.34
600 amps
Type of Const: 1 ea 12%State Surcharge- 12/21/2018 $76.32
Occupancy Grp: Electrical
Total $712.32
qA RD Required Items and Reports(Conditions)
This permit is issued subject to the regulations contained in the Tigard Municipal Code, State of OR. Specialty Codes and all other applicable law. All work will
be done in accordance with approved plans. This permit will expire if work is not started within 180 days of issuance, or if work is suspended for more the 180
days. ATTENTION: Oregon law requires you to follow the rules adopted by the Oregon Utility Notification Center. Those rules are set forth in OAR
952-001-0010 through OAR 952-001-0090. You may obtain a copy of the rules or direct questions to OUNC by calling 503.232.1987 or 1.800.332.2344.
Issued By: Permittee Signature:
OWNER INSTALLATION ONLY
The installation is being made on property I own which is not intended for sale,lease or rent.
OWNER'S SIGNATURE Date:
CONTRACTOR INSTALLATION ONLY
SIGNATURE OF SUPR.ELEC' Date:
LICENSE NO.
Call 503.639.4175 by 7:00 a.m.for the next available inspection date.
This permit card shall be kept in a conspicuous place on the job site until completion of the project.
Approved plans are required on the job site at the time of each inspection.
Schneider
Electric
PAGE 1 OF 3
Quotation
Q2C Number: 40660592 Quote Number: 1 Revision Number: 0
Project Name: TACO BELL TIGARD, OR-ACCUSERV EQ
Project Sub-Name:
Project Location: Tagard, OR
Quote Name: TACO BELL TIGARD, OR
Through Addenda Number: 0
Bid Date: 11/15/2017
Consultant/Specifier:
Contractor/Installer:
Sales Representative: JANET GIBSON
Conditions of Sale
This Quotation is subject to Schneider Electric USA,Inc.'s published Conditions of Sale
Payment Terms: STANDARD
Billing Type(s):
Currency: US DOLLARS
Quote Markings
QUOTATION PRINTED 11/15/2017 3:10:00 PM
PAGE 2 OF 3
Q2C Number:40660592 Quote Number:1 Revision Number:0
Project Name: TACO BELL TIGARD,OR-ACCUSERV EQ Quote Name:TACO BELL TIGARD,OR
Item
No. Qty. Catalog Number/Details
001-00 1 Designation:MSB
Square D Standard Swbd
QED-2 Switchboard
Square D Standard Swbd
Designed and Tested in accordance with:
UL 891/NATIONAL ELECTRIC CODE/NEMA PB-2
System Voltage-208Y/120V 3Ph 4W 60Hz
Source Description-Six Circuit Mains
System Ampacity-600A
Bussing-Silver Plated Copper
Neutral Bus-100%
Max Available Fault Current(RMS)-65kA
Enclosure-Type 3R Non-Walk-in
Accessibility:Front Only
Equipment Nameplate White Surface/Black
Letters,Adhesive(Field Installed)
Rodent Barrier
Exterior Paint Color-ANSI 49
Ground Lug provided for each device
Copper Ground Bus
Dimensions
1-36"Wide Section(s)
1-42"Wide Section(s)
1-Dimensions: 78.00"W X 35.5"D X 91.5"H
2-35.5"Deep Enclosure(s)
Approximate Weight: 1871.00 lbs/848.69 kgs
Incoming Requirements
Suitable for Use as Service Entrance When Not
More Than 6 Main Disconnecting Means are
Provided
Entry Point:Left of Lineup,Through the
Bottom
Reverse Feed
Hot Sequence Utility:Portland General
Eletric(OR)
Standard Door Pattern 15in Blank Top,15in MS
Btm
Mains
1-150AT 208V 80%Rated 65 kA 3 Pole UL,
Group Mounted Thermal Magnetic Circuit
Breaker:Type QG
Main One
Padlock Attachment
1-400AS/400AT 208V 80%Rated 65 kA 3 Pole
UL,Group Mounted Electronic Trip
Circuit Breaker:Type LG
Main Four
Standard Trip Unit,Long Time,
Instantaneous
Padlock Attachment
1-200AT 208V 80%Rated 65 kA 3 Pole UL,
Group Mounted Thermal Magnetic Circuit
Breaker:Type QG
Main Two
Padlock Attachment
1-200AT 208V 80%Rated 65 kA 3 Pole UL,
QUOTATION PRINTED 11/15/2017 3:10:00 PM
PAGE 3 OF 3
Q2C Number:40660592 Quote Number:1 Revision Number:0
Project Name: TACO BELL TIGARD,OR-ACCUSERV EQ Quote Name:TACO BELL TIGARD,OR
Item
No. Qty. Catalog Number/Details
Group Mounted Thermal Magnetic Circuit
Breaker:Type QG
Main Three
Padlock Attachment
1-150AT 208V 80%Rated 3 Pole UL,Group
Mounted Thermal Magnetic Prepared
Space:Type QG
Main Five
1-150AT 208V 80%Rated 3 Pole UL,Group
Mounted Thermal Magnetic Prepared
Space:Type QG
Main Six
Common Main Features:
Nameplate-White Surface/Black Letters,
Adhesive(Field Installed)
Estimated days to ship excluding transit:20 working days after
customer release to manufacture.See Conditions of Sale.
QUOTATION PRINTED 11/15/2017 3:10:00 PM
REV DESCRIPTION BY DATE — ---- -- --/--/-- — — — -- / /
RECO F
SWITCHBOARD GENERAL NOTES
PRODUCT DESCRIPTION & RATINGS
Power System Data (' allfl
208Y/120V 3Ph 4W 60Hz / 3 Phase Wye CATV
`
Solidly Grounded ` '
T—bus T—bus System Short Circuit Current Rating: 65kA RMS BUILDING DIVISION
19.5 in 19.5 in Incoming Section 1 Cable Through the Bottom Left of Lineup
Bus System Data
600A Silver Plated Copper Main Bus
(2) .25x1.50 IN/6x38 mm Cu Bus Bar Per Phase/Neutral
(1) .25x.875 IN/6x22 mm Cu Ground Bus
Enclosure Data
====== o000000o Type 3R Free Standing
O 0=====
0 0 0 0 0 0 o Exterior Paint Color: ANSI 49
000000 00000000 Front Accessibility Only Required
9 0000000= Handling: Rollers
3 ==�= ==13.5 Rodent barriers
Portland General Elec (OR) �=
❑ 1.5H Corrosion Resist Base Channels
Nameplate Mounting Type: Adhesive (Field Installed)
❑ Equipment Nameplate: White Surface/Black Letters
15 / Device Nameplate: White Surface / Black Letters
i
EUSERC DWG 332, 354 ❑ Base channels cannot be removed from EUSERC switchboard line—ups
❑ Utility sealing hardware installed for unmetered bus compartments
13
CLIP �PS Estimated Shipping Weight
CT DWG 320 15 /PS Shipping Split 1 1871.00 lbs / 848.69 kgs
Complete Lineup 1871.00 lbs / 848.69 kgs
91 .50 3 SS.
[2324] Code Standards
EUSERC Terminations W U.L. Deadfront and suitable for use as Service Entrance
DWG 327, 345, 347, 354
rthan sixdisconnecting means are rovided.
� � when not more (6) d sc ec g ea p
o ��
o SSS. Rating Nameplates
ST1— Deadfront — Section Bus 600A
**`. ST2— Service Entrance — Section Bus 600A
22.5 •• PRODUCT INFORMATION
--- ------- •S• Wiring,
-----
-----0 63• • • 63 All wiring to be Machine Tool Wire type
0 0 0 0 0 0 0 0 Instruction Bulletins
-----
. Reference 80043-055 For Handling, Installation,
0 0 0 0 0 0 0 Anchoring, Inspection And Maintenance Information
22.5 0 0- 0 0 0=13.5 Product Accessories/Options
r
1 .50 J SECT 1 SECT 2
[38] 36.00 42.00
[914] [1067]
SS 1
78.00
[1981]
Lineup
78.00
[1981] INCHES
DUAL DIMENSIONS: MILLIMETERS
JOB NAME: TACO BELL TIGARD, OR — ACCUSERV EQ EQUIPMENT DESIGNATION: MSB
JOB LOCATION: 418 EQUIPMENT TYPE: QED-2 Switchboard
DRAWN BY: (Q2C) DRAWING TYPE: GENERAL NOTES
ENGR: SQUARED-
DATE:
QUAREQDATE: November 15 2017 by Schneider Elactrlc
DRAWING STATUS: QUOTE DWG#F40660592-01 I PG 1 OF 2 I REV —
•
REV DESCRIPTION BY DATE — — -- _ --/--/-- — ---- -- —/ /
— ---- -- --/--/-- — ---- -- --/--/ — ---- / /
39.03
[991]
.50 3.03
REAR COVER [13] 35.50 [77]
HANDLES USED [902]
ON BAYS WIDER H 24.00 , 11 .00 TOP VIEW — FRONT
THAN 42.00/[1067] [610] I [279]
C
91 .50
[2324] 37.00
90.00 31 .00 — [940]
[2286] 2.50 f— [787]
[64]1
1 f + � `
21.00 1 .50 14.25 3.1 11 .85,
35.50 [533] [38] [362] , [301]
[902] j } t o 0 f
2.8�o
12.50 16..40
' ' [318]
36.00 42.00 a
LEFT SIDE VIEW .75/[19] DIA t
X [914] [1067]
MTG HOLES OFFSET
3.00/[76] TYP DUAL DIMENSIONS: INCHES
FROM SIDE MILLIMETERS
FLOOR PLAN — FRONT
NOTE: JOB NAME: TACO BELL TIGARD, OR — ACCUSERV EQ EQUIPMENT DESIGNATION: MSB
A MINIMUM OF 2.00/[51] JOB LOCATION: 418 EQUIPMENT TYPE: QED-2 Switchboard
CLEARANCE BEHIND THE DRAWN BY: (020) DRAWING TYPE: SIDE, TOP VIEW & FLOOR PLAN
SWITCHBOARD IS REQUIRED
FOR TOP COVER OVERHANG. ENGR: SQUARE Er
DATE: November 15 2017 by Schneider EI.e«Te
DRAWING STATUS:QUOTE Dwc#F40660592-01 I PG 2 OF 2 I REV —
REV DESCRIPTION BY - DATE -- -- --/--/--
- - -- --/--/ - - --- -- -
UCT BARRIERTh1/4,
• —0—
___J
QG 150A 3P
LG 400A 3P
<
QG 200A 3P
ate^ <
QG 200A 3P
< � 5 PS,.
QG 150A 3P
1 < rVV16_ "2PS,-
SPACE AND QG 150A 3P
MOUNTING 600A INTERIOR
�- FOR UTIL •
CO CT'S
L_ _
C
2 PAIR STUDS
Ground Bus per UL891
•
SECTION 1 co SECTION 2
JOB NAME: TACO BELL TIGARD, OR - ACCUSERV EQ EQUIPMENT DESIGNATION: MSB
JOB LOCATION: 418 EQUIPMENT TYPE: QED-2 Switchboard
DRAWN BY: (Q2C) DRAWING TYPE: ONE LINE
ENGR: SQUARED-
DATE: November 15 2017 by fWrNr Electric
DRAWING STATUS:QUOTE DWG#040660592-01 I PG 1 OF 2 I REV —
•
• REV DESCRIPTION BY DATE — -- --/--1 -- /--/
---- -- --/--/-- -- _ --/--/ ---- /—
POWER STYLE QED-2 SWITCHBOARD LEGEND
PLA Padlock Attachment—Fixed
SECT CKT GMD DEVICE/FRAME TRIP FUSE/ LUG/WIRE INFORMATION
NO NO HEIGHT RATING AMP TRIP #P DESIGNATION N/P
QTY PHASE WIRE RANGE QTY NEUT WIRE RANGE ACCESSORIES / NOTES
— — — Equipment Nameplate — — — MSB Yes — — — — _
1 UCT — 600A — — — Portland General Elec (OR) No 2 Pair Studs 2 Pair Studs
2 M1 4.5 in QG 150A — 3P MAIN 1 OF 6 Yes 1 #4 — 300 kcmil 1 #4 — 300 kcmil PLA
2 M4 6 in LG 400A 400A S—LI 3P MAIN 4 OF 6 Yes 2 3/0 — 250 kcmil 2 3/0 — 250 kcmil PLA
2 M2 4.5 in QG 200A — 3P MAIN 2 OF 6 Yes 1 #4 — 300 kcmil 1 #4 — 300 kcmil PLA
2 M3 4.5 in QG 200A — 3P MAIN 3 OF 6 Yes 1 #4 — 300 kcmil 1 #4 — 300 kcmil PLA
2 M5 4.5 in QG (PS) (150A) — 3P MAIN 5 OF 6 Yes 1 #4 — 300 kcmil 1 #4 — 300 kcmil
2 M6 4.5 in QG (PS) (150A) — 3P MAIN 6 OF 6 Yes 1 #4 — 300 kcmil 1 #4 — 300 kcmil
NAMEPLATE INFORMATION: JOB NAME: TACO BELL TIGARD, OR — ACCUSERV EQ EQUIPMENT DESIGNATION: MSB
MOUNTING TYPE: Adhesive (Field Installed) _ JOB LOCATION: 418 EQUIPMENT TYPE: QED-2 Switchboard
EQUIPMENT: White Surface/Black Letters DRAWN BY: (Q2C) DRAWING TYPE: SCHEDULE
DEVICE: White Surface / Black Letters ENGR: SQUARE 0
DATE: November 15 2017 by aa.wa..El•etrle
DRAWING STATUS:QUOTE DWG#040660592-01 I PG 2 OF 2 I REV —