• TRANE Submittal ` �' � �i�, r��. .
RECEIVED
JAN 7 ,y 2019
Prepared For: Date: September 11, 2018 CITY OF TIGARD
Hydro Temp Mechanical
Customer P.O. Number: Kee-er (,t. 4cef
Customer Project Number:
Sold To: Job Number:
Job Name:
Durham AWWTF 5020 AC Replacement
Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval.
Product Summary
Qty Product
1 Commercial Rooftop Air Conditioning Units (Midrange)
1 Seismic Curb
The attached information describes the equipment we propose to
furnish for this project, and is submitted for your approval.
Product performance and submittal data is valid for a period of 6 months
from the date of submittal generation. If six months or more has elapsed
Kyle Wolf between submittal generation and equipment release,the product
Trane performance and submittal data will need to be verified. It is the
7257 SW Kable Lane customer's responsibility to obtain such verification.
Portland, OR 97224-7181
Phone: (503) 620-8031
Cell: (503) 828-6788
Fax: (503) 639-1454
J:IJOBSI124171940181Durham AWWTF 5020 AC Replacement-submittal 02.doc
Table Of Contents
Product Summary 1
Commercial Rooftop Air Conditioning Units (Midrange) (Item Al)
Tag Data 3
Product Data 3
Performance Data 3
Mechanical Specifications 5
Unit Dimensions 10
Fan Curve 13
Weight, Clearance&Rigging Diagram 14
Accessory 16
Seismic Curb (Item B1)
Tag Data 23
Product Data 23
Durham AWWTF 5020 AC Replacement September 11,2018
Tag Data -Commercial Rooftop Air Conditioning Units (Midrange) (Qty: 1)
Item Tag(s) Qty Description Model Number
Al 55 ton DW DDP 1 20-75 Ton Packaged Industrial Rooftop ( SXHLF554
Product Data -Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 55 ton DW DDP
DX Cooling only with extended casing
R-410A refrigerant SUBMITTAL REVIEW
55 Ton unit I ❑ NOMAKE EXCEPTIONSCORRECTIONS TAKENNOTED ❑ REVISE AND RESUBMIT
❑ ❑ SUBMIT SPECIFIED ITEM
460 Volt-60 Hertz-3 Phase CHECKING IS ONLY FOR GENERAL CONFORMANCE WITH THE DESIGN CONCEPT
100% Exhaust- 7.5 hp with Statitrac building pressure control OF THE PROJECT AND GENERAL COMPLIANCE WITH THE INFORMATION IN THE
CONTRACT DOCUMENTS. ANY ACTION SHOWN ABOVE, IS SUBJECT TO THE
600 rpm - Exhaust/return fan REQUIREMENTS OF THE PLANS AND SPECIFICATIONS. CONTRACTOR IS
0-1000/o Economizer RESPONSIBLE FOR: DIMENSIONS WHICH SHALL BE FABRICATED AND
CORRELATED AT THE JOB SITE;FABRICATION PROCESSES AND TECHNIQUES OF
Economizer control w/comparative enthalpy CONSTRUCTION:COORDINATION OF HIS WORK THAT OF ALL OTHER TRADES;
AND THE SATISFACTORY PERFORMANCE OF HIS WORK.
Filter gauge
2.00" [51 mm] Spring isolators CUNDIFF ENGINEERING,INC.
7007 S.W.CARDINAL LN.#145 PORTLAND.OREGON 97224
MERV 8 High efficiency throwaway filters 09/21/2018
eDrive, Direct drive plenum (DDP) supply fan INITIALED BY: CMB DATE:
20 hp DDP 120% width
1500 rpm
VAV (DTC)with supply& exhaust/return VFD with bypass
Standard ambient control
cULus
Non-fused unit disconnect switch
Low leak outside air dampers
Corrosion protected condenser coil Contractor to verify
Hinged access doors SCADA tie-in
BACnet communication interface module requirements.
Factory-powered 15A GFI Convenience outlet
Startup Included -Trane Service must start equipment for warranty to be honored
Solid double wall construction
Stainless steel sloped drain pan
Corrosion protected evaporator coil
1st Year Labor warranty air cooled
Refrigerant Warranty First Year Only
Performance Data -Commercial Rooftop Air Conditioning Units (Midrange)
Tags 55 ton DW DDP
Supply airflow(cfm) 18000
Exhaust/Return airflow(cfm) 18000
Cooling entering DB (F) 80.00
Cooling entering WB (F) 67.00
Ambient DB (F) 95.00
Cooling leaving coil DB (F) 56.13
Cooling leaving coil WB (F) 55.35
Cooling leaving unit DB (F) 58.37
Cooling leaving unit WB (F) 56.23
Gross total capacity(MBh) 655.07
Gross sensible capacity (MBh) 481.79
Gross latent capacity(MBh) 173.28
Net total capacity(MBh) 610.69
Net sensible capacity (MBh) 437.41
Net sensible heat ratio (%) 71.62
Fan motor heat(MBh) 44.38
Evaporator face area (sq ft) 38.00
Supply duct static pressure (in H2O) 2.000
Return duct static pressure (in H2O) 0.500
Component S.P. drop (in H2O) 0.860
Total static pressure (in H2O) 3.360
Supply motor bhp (bhp) 16.00
FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 3 of 24
Others
Durham AWWTF 5020 AC Replacement September 11, 2018
Tags 55 ton DW DDP
Supply fan rpm (rpm) 1442
Supply fan efficiency (%) 59.51
Exhaust static pressure (in H2O) 0.500
Exhaust motor bhp (bhp) 7.00
Exhaust fan rpm (rpm) 562
System power(kW) 64.10
EER @ AHRI (EER) 10.6
IEER @ AHRI (EER) 14.0
Minimum circuit ampacity (A) 136.15
Maximum overcurrent protection (A) 150.00
Minimum disconnect switch size (A) 148.00
Recommended dual element(A) 150.00
Compressor 1 count(Each) 4.00
Compressor 1 RLA (A) 20.20
Supply fan motor FLA (A) 27.00
Supply motor count ( ) 1
Supply fan count (Each) 1.00
Condenser fan FLA (A) 10.80
Exhaust fan motor FLA(A) 9.80
Other FLA (A) 1.00
Desired reheat set point (F) 70.00
EDB in HGRH (F) 73.00
EWB in HGRH (F) 64.00
Ambient DB in HGRH (F) 75.00
Ambient WB in HGRH (F) 68.00
R-410A refrigerant charge - circuit 1 (Ib) 34.8
R-410A refrigerant charge - circuit 2 (Ib) 32.0
Installed point load 1 (Ib) 646.0
Installed point load 2 (Ib) 760.5
Installed point load 3 (Ib) 750.8
Installed point load 4 (Ib) 865.4
Installed point load 5 (Ib) 843.8
Installed point load 6 (Ib) 958.3
Installed point load 7 (Ib) 937.8
Installed point load 8 (Ib) 1052.4
Installed point load 9 (Ib) 1041.6
Installed point load 10 (lb) 1156.1
Total installed weight (Ib) 9012.8
First X dimension (ft) 17.24
First Y dimension (ft) 4.01
Installed point load 1 -X (in) 4.000
Installed point load 1 -Y (in) 4.000
Installed point load 2 - X (in) 101.000
Installed point load 2 -Y (in) 87.000
Installed point load 3 -X (in) 187.000
Installed point load 4 -X (in) 274.000
Installed point load 5 - X (in) 370.000
FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 4 of 24
Others
Durham AWWTF 5020 AC Replacement September 11,2018
Mechanical Specifications -Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 55 ton DW DDP
General - R410A
Units shall be specifically designed for outdoor rooftop installation on a roof curb and be completely factory assembled
and tested, piped, internally wired, fully charged with R-410A compressor oil and shipped in one piece. Units shall be
available for direct expansion cooling only, or direct expansion cooling with natural gas, electric, hot water or steam
heating. Filters, outside air system, exhaust air system, optional non-fused disconnect switches and all operating and
safety controls shall be furnished factory installed. All units shall be cULus approved and factory run tested. Cooling
capacity shall be rated in accordance with AHRI Standard 360. All units shall have decals and tags to aid in service and
indicate caution areas. Electrical diagrams shall be printed on long life water resistant material and shall ship attached to
control panel doors.
Casing
Exterior panels shall be zinc coated galvanized steel, phosphatized and painted with a slate grey air-dry finish durable
enough to withstand a minimum of 672 hours consecutive salt spray application in accordance with standard ASTM
B117. Screws shall be coated with zinc-plus-zinc chromate. Heavy gauge steel hinged access panels with tiebacks to
secure door in open position shall provide access to filters and heating sections. Refrigeration components, supply air
fan and compressor shall be accessible through removable panels as standard. Unit control panel, filter section, and
gas heating section shall be accessible through hinged access panels as standard. Optional Double Wall Construction
hinged access doors shall provide access to filters, return/exhaust air, heating and supply fan section. All access doors
and panels shall have neoprene gaskets. Interior surfaces or exterior casing members shall have 1/2"Tuf-Skin
fiberglass insulation. Unit base shall be watertight with heavy gauge formed load bearing members,formed recess and
curb overhang. Unit lifting lugs shall accept chains or cables for rigging. Lifting lugs shall also serve as unit tiedown
points.
Solid Double Wall Construction
The sheet metal liners shall provide a mechanical fastener for insulation and prevent the possibility of loose insulation
fibers from entering the airstream. 16 gauge exterior liners shall be welded to 20 gauge interior liners. All interior
airstream insulation shall be lined, with the exception of the vertical supports, which have foil faced insulation. cULus
approved.
Hinged Access Doors
Hinged access doors shall provide easy access to supply fan, filters, exhaust/return fan, and heating section.These
access doors shall feature double wall construction with dual density insulation sandwiched between heavy gauge
galvanized steel panels for strength and durability
Corrosion Protected Condenser Coil
All Aluminum Microchannel condenser coil protection shall consist of a corrosion resistant coating that shall withstand
ASTM B117 Salt Spray test for 6000 hours and ASTM G85 A2 Cyclic Acidified Salt Fog test for 2400 hours.This coating
shall be added after coil construction covering all tubes, headers and fin edges, therefore providing optimal protection in
more corrosive environments.
Condenser Fans and Motors
All condenser fans shall be vertical discharge, direct drive fans, statically balanced, with steel blades and zinc plated
steel hubs. Condenser fan motors shall be three-phase motors with permanently lubricated ball bearings, built-in current
and thermal overload protection and weathertight slingers over motor bearings.
Evaporator Coil - R410A
Internally enhanced copper tubing of 3/8" or 1/2" O.D. shall be mechanically bonded to heavyduty aluminum fins of
configured design. All coils shall be equipped with thermal expansion valves and factory pressure and leak tested.
Sloped Stainless Steel Drain Pan
The double sloping stainless steel drain pan shall promote runoff
of standingwater from condensation inside the unit.Two drain pipes shall be installed through the base channel on each
side of the unit.The evaporator drain pan shall be constructed of 14 gauge stainless steel. On units 40 tons and larger,
the intermediate drain pan shall be constructed of 16 gauge stainless steel.This shall provide protection in corrosive
environments
Compressors - R410A
FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 5 of 24
Others
Durham AWWTF 5020 AC Replacement September 11,2018
The Trane Scroll compressor shall be industrial grade, direct drive 3600 RPM maximum speed scroll type. The motor
shall be suction gas-cooled hermetic design. Compressor shall have centrifugal oil pump with dirt separator, oil sight
glass, and oil charging valve. Compressor shall also be provided with thermostatic motor winding temperature control to
protect against excessive motor temperatures resulting from over-/under-voltage or loss of charge, high and low
pressure cutouts, and reset relay.
Phase Monitor
Shall protect 3-phase equipment from phase loss, phase reversal, and low voltage. Any fault condition shall produce a
Failure Indicator LED, and send the unit into an emergency stop condition. cULus approved. (Standard on 20-75T units)
Supply Fan
Supply fan motors shall be either open drip-proof or enclosed fan cooled. All supply fans shall be dynamically balanced
in factory. Supply fan shall be test run in unit and shall reach rated rpm. All 60 Hz supply fan motors meet the Energy
Independence Security Act of 2007 (EISA). All 50 Hz supply fan motors meet the U.S. Energy Policy Act of 1992
(EPACT).
Direct-Drive Plenum Supply Fan
Supply fan shall be [one] [two] single width, single inlet 9-blade plenum fan. Fan blades shall be aluminum
backward-inclined airfoil. Plenum fans shall be direct-driven. Entire assembly shall be completely isolated from unit and
fan board by 2" deflection spring isolation. Multiple fan widths shall be available to optimize efficiency. Fan shall not
require routine maintenance such as fan bearing lubrication, belt tensioning and replacement, sheave alignment, and
setscrew torque checks.
Variable Frequency Drive
Unit shall include factory-installed and tested variable frequency drive[s](VFD)to provide motor speed modulation. The
VFD shall receive a 0-10VDC speed signal from the unit controller. The drive will respond to the signal by accelerating
or decelerating to maintain the controlling set point(duct static, space pressure, etc). VFD shall also include the
following features:
1. Designed,constructed, and tested in accordance with NEMA ICS, NFPA,and IEC standards and housed in a plastic
IP20 enclosure.
2. DC link reactors on both the positive and negative rails of the DC bus equal to 3% impedance to minimize power line
harmonics.
3. Full rated output current continuously- 110% of rated current for 60 seconds and 160%of rated current for up to 0.5
second while starting.
4. Isolation between the Drive's power circuitry and control circuitry to ensure operator safety and to protect connected
electronic control equipment
from damage caused by voltage spikes, current surges, and ground loop currents.
5. Audible noise reduction through automatic adjustment of the carrier frequency and frequency avoidance.
6. Rated at 40C with a standard operating range of-10 to 50C(14 to 124F)ambient temperatures and 0 to 95%relative
humidity
7. Self-diagnostics and motor protections such as: cULus listed overload, phase loss, and internal thermal overload.
8. Off/Stop and Auto/Start selector switches to start and stop the AC Drive and determine the speed reference.
a. On units with bypass, an AC Drive/Off/Bypass hand selector switch shall be provided in the unit control box
b. In DRIVE mode speed reference shall be provided by a 0-10 VDC analog input
9. A keypad interface which shall be programmable by language and feature multiple lines for easy reading.
10. Controlled and/or accessible points such as AC Drive Start/Stop, speed reference, and fault diagnostics.
11. Meter points such as motor power in HP, motor power in kW, motor kW-hr, motor current, motor voltage, hours run,
DC link voltage, thermal load
on motor, Thermal load on AC Drive and Heatsink temperature.
FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 6 of 24
Others
Durham AWWTF 5020 AC Replacement September 11,2018
12. Troubleshooting features such as:
a. AC Drive memory storage of the last 10 faults and related operational data
b. Four simultaneous displays: frequency or speed, run time, output amps and output power
c. Keypad which shall display: Reference Signal Value, Output Frequency in Hz or percent, Output Amps, Motor HP,
Motor kW, kW
13. Coated circuit boards for protection against corrosive environments
14. Field readable BACnet points to allow for communication of stauts, setpoints and diagnostics to the BAS.
Bypass control
Shall provide full nominal airflow in the event of drive failure.
Two-inch Spring Isolators
Supply and Exhaust/Return fan (if applicable) assemblies shall be isolated with two-inch nominal deflection to reduce
transmission of vibrations
Modulating 100 Percent Exhaust Fan with Statitrac Control
Two, double-inlet, forward-curved fans shall be mounted on a common shaft with fixed sheave drive. All fans shall be
dynamically balanced and tested in factory before being installed in unit. Exhaust fan shall be test run as part of unit final
run test. Unit shall reach rated rpm before fan shaft passes through first critical speed. Fan shaft shall be mounted on
two grease lubricated ball bearings designed for 200,000-hour average life. Optional extended grease lines shall be
provided to allow greasing of bearings from unit filter section. Fan motor and assembly shall be mounted on common
base to allow consistent belt tension with no relative motion between fan and motor shafts. Entire assembly shall be
completely isolated from unit and fan board by double deflection, rubber in shear isolators or spring isolation on motor
sizes larger than five hp. For both CV and VAV rooftops, the 100 percent modulating exhaust discharge dampers (or
VFD)shall be modulated in response to building pressure.A differential pressure control system, (Statitrac), shall use a
differential pressure transducer to compare indoor building pressure to outdoor ambient atmospheric pressure. The FC
exhaust fan shall be turned on when required to lower building static pressure setpoint. The (Statitrac) control system
shall then modulate the discharge dampers (or VFD)to control the building pressure to within the adjustable, specified
dead band that shall be adjustable at the Human Interface Panel. All 60 Hz exhaust fan motors meet the Energy
Independence Security Act of 2007 (EISA).
0-100 percent modulating economizer
Operated through the primary temperature controls to automatically utilize OA for "free" cooling. Automatically
modulated return and OA dampers shall maintain proper temperature in the conditioned space. Economizer shall be
equipped with an automatic lockout when the outdoor high ambient temperature is too high for proper cooling. Minimum
position control shall be standard and adjustable at the Human Interface Panel or with a remote potentiometer or
through the building management system. A spring return motor shall ensure closure of OA dampers during unit
shutdown or power interruption. Mechanical cooling shall be available to aid the economizer mode at any ambient. Low
leak economizer dampers shall be standard with a leakage rate of 2.5 percent of nominal airflow(400 CFM/ton)at 1"wg.
static pressure.
Economizer Control with Comparative Enthalpy
Two enthalpy sensors shall be provided to compare total heat content of the indoor air and outdoor air to determine the
most efficient air source when economizing.
low-leak economizer dampers
Standard low leak dampers shall be provided with chlorinated polyvinyl chloride gasketing added to the damper blades
and rolled stainless steel jamb seals to the sides of the damper assembly. Dampers shall have a leakage rate of 1% at
1.0 in WC pressure differential
High efficiency throwaway, MERV 8
Shall be two-inch high efficiency MERV 8 media filters with average dust spot efficiency of 25-35 percent and an
average arrestance in excess of 90 percent when tested in accordance with ASHRAE 52-76.
Differential Pressure Gauge
FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 7 of 24
Others
Durham AWWTF 5020 AC Replacement September 11,2018
A factory-installed, dial-type, differential pressure gauge shall be piped to both sides of the filter to indicate status.
Gauge shall maintain a +/- 5 percent accuracy within operating temperature limits of-20°F to 120°F. Gauge shall be
flush-mounted with casing outer wall. Filter sections consisting of pre- and post-filters shall have a gauge for each.
Unit Controller
DDC microprocessor controls shall be provided to control all unit functions. The control system shall be suitable to
control CV or VAV applications. The controls shall be factory-installed and mounted in the main control panel. All
factory-installed controls shall be fully commissioned (run tested) at the factory. The unit shall have a Human Interface
Panel with a 16 key keypad, a 2 line X 40 character clear English display as standard to provide the operator with full
adjustment and display of control data functions.The unit controls shall be used as a stand-alone controller,or as part of
a building management system involving multiple units.
1
The unit shall be equipped with a complete microprocessor control system.This system shall consist of temperature and
pressure (thermistor and transducer) sensors, printed circuit boards (modules), and a unit mounted Humanlnterface
Panel. Modules (boards) shall be individually replaceable for ease of service. All microprocessors, boards and sensors
shall be factory mounted, wired and tested. The microprocessor boards shall be stand-alone DDC controls not
dependent on communications with an on-site PC or a Building Management Network. The microprocessors shall be
equipped with on-board diagnostics, indicating that all hardware, software and interconnecting wiring are
in proper operating condition. The modules (boards) shall be protected to prevent RFI and voltage transients from
affecting the board's circuits. All field wiring shall be terminated at separate, clearly marked terminal strip. Direct field
wiring to the I/O boards is not acceptable. The microprocessor's memory shall be non-volatile EEPROM type requiring
no battery or capacitive backup, while maintaining all data.
2
Zone sensors shall be available in several combinations with selectable features depending on sensor.
3
The Human Interface Panel's keypad display character format shall be 40 characters x 2 lines. The character font shall
be 5 x 7 dot matrix plus cursor. The display shall be Supertwist Liquid Crystal Display(LCD) with blue characters on a
ray/green background which provides high visibility and ease of interface. The display format shall be in clear English.
Two or three digit coded displays are not acceptable.
4
The keypad shall be equipped with 16 individual touch-sensitive membrane key switches. The switches shall be divided
into four separate sections and be password protected from change by unauthorized personnel. The six main menus
shall be STATUS, SETPOINTS, DIAGNOSTICS, SETUP, CONFIGURATION and SERVICE MODE.
BACnet Communication Interface Module
Option shall provide control and monitoring of the rooftop by Tracer SC or a 3rd party building management system
utilizing BACnet protocol.
Unit Interrupt Rating (Standard Short Circuit Current Rating-SCCR)
A 5,000 Amp rating shall be applied to the unit enclosure using a non-fused circuit breaker for disconnect switch
purposes. Fan motors, compressors, and electric heat circuits shall be provided with series rated circuit breakers that
will provide the unit rated level of protection. The unit shall be marked with approved cULus markings and will adhere to
cULus regulations.
Factory Powered GFI Convenience Outlet
A15A, 115V Ground Fault Interrupter convenience outlet shall be factory installed. It shall be wired and powered from a
factory mounted transformer. Unit-mounted, non-fused disconnect with external handle shall be furnished with factory
powered outlet
Non-Fused Disconnect Switch with External Handle
External handle SHALL enable the operator to disconnect unit power with the control box door closed for safety.
Design Special -CompleteCoat
Option shall dip and bake evaporator coils in an electro-mechanically bonded flexible epoxy coating. Coating shall
provide uniform epoxy coating of all surfaces on aluminum fins, copper tubes, coil frames, and heads of evaporator No
associated surfaces shall remain bare. Option shall allow for corrosion resistance without performance degradation.
Coils with coating passed 3000-hour salt spray test. All coil surfaces coated with epoxy material shall give uniform
coverage (min 0.8 mils), without fin bridging. IntelliPak I units with the CompleteCoat option shall keep their cULus
FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 8 of 24
Others
Durham AWWTF 5020 AC Replacement September 11,2018
listing.
Equipment manufactured by Trane that includes required start-up and sold in North America will not be
warranted by Trane unless Trane or its authorized independent Trane commercial sales office performs the
startup on the equipment.
Certified AHRI Performance
Packaged Rooftop units cooling, heating capacities and efficiencies are rated within the scope of the Air-Conditioning,
Heating & Refrigeration Institute (AHRI) Certification Program and display the AHRI Certified®mark as a visual
confirmation of conformance to the certification sections of AHRI Standard 340-360 (I-P) and ANSIZ21.47 and 10 CFR
Part 431 pertaining to Commercial Warm Air Furnaces. The applications in this catalog specifically excluded from the
AHRI certification program are:
-Ventilation modes
-Heat Recovery.
-Units larger than nominal 63 tons in Cooling
-Evaporative Condensers
FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 9 of 24
Others
O T -- ... '- _ ., NOTES: :' C
r- 1 1.VERIFY WEIGHT,CONNECTION,AND ALL DIMENSION WITH
cD 0 /„ ", / o. INSTALLER DOCUMENTS BEFORE INSTALLATION ., '� S
y II I IIg•uIIJ ■IIW(01)°1119 I 2.LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT. v 3
'Ti •V 3.OVERALL UNIT WIDTH INCREASES 5/8"BEYOND LIFTING LUG D
-, �i -��\ • ,�, WITH ULTRA LOW LEAK POWER EXHAUST DAMPERS •" G
II IRIg •)111111 IRP i 01;1!1 90 9/16"4.RETURN AIR OPENING CONFIGURATION FOR USES WITH NO A 3
\ . _ • AIR OPTION,BAROMETRIC RELIEF,AND EXHAUST FAN. „''• y
p > e 5.IF FIELD CONVERTING SUPPLY&RETURN OPENING(S)TO eG -I
0- ; ,,•:99!!D. �y Ilmeu:0,71.' HORIZONTAL OR VERTICAL AIRFLOW,FACTORY MUST VERIFY •' 71
`a •
• �_ ps_ ' IF UNIT OPTIONS WILL ALLOW IT.FACTORY INSTALLATION IS Cl) O
y ALWAYS RECOMMENDED. . Is)
CD CO 0 0
LIFTING POINTS X6 v A
54 50/55 TON PLAN VIEW AMBIENT DAMP 3 43
AMBIENT DAMPER
I CI Zn d
F, CA m
Ci 3
Q
-r--7-7 —_ i I .
vO
A
94 3/16" 87 1/4" 81 5/16"
82 5/16" 81 5/16" .4. Ii I "Q
D
e
1"NPT-F CONDENSATE O
DRAIN(BOTH SIDE) 1"NPT-F CONDENSATE :_. 3
0 DRAIN(BOTH SIDE)
S.
A
1 3/8"DRAIN HOLES
(NOT USED ON UNITS (BOTH SIDE) 93 7/8"88 7/8 co
N o 144 1/8" WITH DDP FANS)
C3
0 184 5116" SEE NOTE 3-'77
74: A'
392 1/2" 1
E
394 9/16" 50 TON FRONT VIEW Q
1 1/8"CONDUIT
SU
50/55 TON LEFT SIDE VIEW D.0 CONTROL CIRCUIT 3
1 1/8"CONDUIT CQ
- 71/16 ., A.CCONTROLCIRCUIT :.
\ 11/8"CONDUIT AC&
•
1 I I II 7 DC CONTROL CIRCUIT
. . �I— 4 1/8"CONN.THRU
BA3/8"
SE FOR POWER SUPPLY
I I—
1 � I
RETURN AIR OPENING . . I• I 8 3/8"
40 7/16" SEE NOTE 4
8 11/16"
45 13/16" e SUPPLY a - 0-9 3/4" 4
CD
(D
15 3/4" -0
m
5 13/16"- 92 3/16"ID ^ 17 3/4" 3
co - 2385/16" - 29" - - 20 1/4"
- 22" fV
0 p
Np 50/55 TON PLAN VIEW OF UNIT co
Durham AWWTF 5020 AC Replacement September 11,2018
Unit Dimensions - Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 55 ton DW DDP
1" _
1"
5/8" 1/2"—d h-
5/8"
1"
3"
/90° 5 5/8"
3 5/8"
1� 1-=----2 3/4" NNN
\..iCY
1 5/8" b 1
5/8" 6 9/16" p p
4 13/16"
5 13/16"
TYPICAL PEDESTAL AND BASE
DIMENSION DRAWING
UNIT BASE
Ll 2 1/2" LIFTING LUG
SHIPS WITH CURB �, 4"LONG
FIELD INSTALLED
GASKET
2 1/2"--14"LONG 3/8" • I
LIFTING LUG
,4 k
1PEDESTAL
2"X 4"NAILER
(FURNISHED WITH KIT)
ROOF CURB
TYPICAL PEDESTAL AND BASE PAN DETAIL TYPICAL ROOF CURB AND BASE PAN DETAIL
DETAIL DETAIL
FLD=Furnished by Trane U.S Inc./Installed by Equipment Submittal Page 11 of 24
Others
•
Durham AWWTF 5020 AC Replacement September 11,2018
Unit Dimensions -Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 55 ton DW DDP
ELECTRICAL/GENERAL DATA
TONS GAS HEATING-PERFORMANCE
Model(Tonnage): SXHLF55(55 Ton) Heating Input:
Unit Operating Voltage Range: 414-506 Heating Output:
Unit Primary Voltage: 460 Capacity Steps:
Unit Hertz: 60
Unit Phase: 3 HEATING-GENERAL DATA
Gas inlet pressure:(in w.c.)
EER: 10.6 EER Gas Pipe Connection Size:
IEER: 14.0 EER
COMPRESSOR ELECTRIC HEATER
Compressor 1 Count: 4.00 Each Electric Heater Kw:
Compressor 1 RLA: 20.20 A Electric Heater Full Load Amps:
Compressor 2 Count: Value not available
Compressor 2 RLA: Value not available
Compressor 3 Count: Value not available
Compressor 3 RLA: Value not available
SUPPLY FAN MOTOR EXHAUST/RETURN FAN MOTOR SECTION
Number of Fans: 1.00 Each Number: Value not available
Number of Motors: 1 Horsepower(Each): 100%Exhaust-7.5 hp with Statitrac building pressure control
Total Horsepower: 20 hp DDP 120%width Exhaust/Return Fan Motor FLA: 9.80 A
Supply Fan Motor Full Load Amps: 27.00 A
Supply Fan Efficiency: 59.51
CONDENSER FAN MOTOR FILTERS-TYPE
Number: 6 Type:
Horsepower(each): 1.0 Furnished: YES
Condenser Fan Motor Full Load Amps(Total): 10.8 Number: 20
Recommended Size: 20"x25"x 2"
EVAPORATIVE CONDENSER (7) PREFILTERS
Pump Horsepower: N/A Furnished:
Pump Full Load Amps: N/A Number:
Sump Heater Full Load Amps: N/A Recommended Size:
Sump Heater kW:
REFRIGERANT TYPE 16) FINAL FILTERS-TYPE
Charge Type: R-410A Type:
Factory Charge(Circuit#1): 34.8 lb Furnished:
Factory Charge(Circuit#2): 32.0 lb Number:
Recommended Size:
PREFILTERS
Furnished:
Number:
Recommended Size:
Notes:
1.LOAD 1=Current of the largest motor(compressor or fan motor);LOAD 2=Sum of the currents of all remaining motors;LOAD 3=Current of electric heaters
LOAD 4=Control Power Transformer(20-40 and 24-48 ton units add 3 FL amps for wire sizing formula,50-75 and 59-89 ton units add 6 FL amps)
2.For Electric Heat MCA,MOP,RDE values,calculate for both cooling and heating modes.(When determining LOADS,the compressors
do not operate when the unit is in heating mode)(On 70-89 ton single source units,heating Load 4=12 amps on 200,230 volt units and
9 amps on 460,575 volt units)
3.If selected Max Over Cur is less than the Min Clr Amp,then select the lowest maximum fuse size which is equal to or larger than the Min Cir
Amp,provided the selected fuse size does not exceed 800 amps.
4.If the selected Recommended Dual Element fuse size is greater than the selected Max Over Cur Protection value,then select the Recommended Dual
Element fuse size value to equal the Max Over Protection value.
5.Compressor KW atAHRI rating conditions of 80/67-95
6.Refrigerant charge is an approx.value.For a more precise value,see unit nameplate and service instructions.
7.Sump Heater is an optional feature.
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 12 of 24
Others
Durham AWWTF 5020 AC Replacement September 11,2018
Fan Curve -Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 55 ton DW DDP
3011DPLA01FN
UrgtSze.
20.0 sn vp OperatngArlow:18000 00 cfm
_ / Operatng Safic Fiessure,336 in H2O
%dN0 Operatng RRvk 144200
/60
Gperafng Sake Horse Rower 16 00 bhp
17.5 2500 RRM Wide:0.00
— J Design Tenp,8000 F
70%WO Date 9/11/18
- 2400RPM
ON 15.0- AIIIIIP4ejh
230 RF0
C - 2200 RPM
Illk
r
7CO44
N ��
_
U i:r Tt VIII
�i 1114.
- 700 RM
-'.1 I m•N••...-401 I I PI a I IS PA I IL
a5
:: =
. —
N - 7600 RPM u,ill
1511•: 90%NO
- 1400 RFM `_
1300 RPM
i— -.AiW4*IP 11.1
- 1200 RPM Aliftelippr,
- 1100 RPM
1000 RFM
25 ' `
0.0
0 5000 10000 15000 23000 25000 30000 35000 40000
PirfloN(cfm)
63Hz 125Hfz 250f z 500Hz 1 kHz 2 kHz 4 kHz 8 kHz
Cuba"Noise: -1 -1 -1 -1 -1 -1 -1 -1
Supply Dud: -1 -1 -1 -1 -1 -1 -1 -1
Ram Duct: -1 -1 -1 -1 -1 -1 -1 -1
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 13 of 24
Others
Durham AWWTF 5020 AC Replacement September 11,2018
Weight, Clearance & Rigging Diagram -Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 55 ton DW DDP
Note:
When 2 or more units are to be placed side by side,the distance between the units
fv) should be increased to 150%of the recommended single unit clearance.The units
should also be staggered to reduce span deflection&assure proper diffusion of
exhaust air.
144"
/ 1
11101,00,
t:t%
CLEARANCE
� I
CLEARANCE 96"
36"
72" r 96" rt-t
O O
O O Icc
I cc
tit
O O
U .. �- y II
96"
I �
CLEARANCE
RIGGING AND CLEARANCE
AIR COOLED DRAWING
FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page '14 of 24
Others
Durham AWWTF 5020 AC Replacement September 11,2018
Weight, Clearance & Rigging Diagram -Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 55 ton DW DDP
194 5/16" _, - 29"
"Z'I.&--=I."\:1
Iliiiiii
-.,1\
59) tiiiiii liiiiil)
s
Il(lflr\• i7Dl) Illli •ii)))) I,
Illllii% illi))) lll1l11 • till) y
X
Center of Gravity X: 17.24 ft Point load X location 1: 4.000 in
Center of Gravity Y: 4.01 ft Point load X location 2: 101.000 in
Point load X location 3: 187.000 in
Point Load 1: 646.0 lb Point load X location 4: 274.000 in
Point Load 2: 760.5 lb Point load X location 5: 370.000 in N
Point Load 3: 750.8 lb Point load X location 6: N/A
Point Load 4: 865.4 lb Point load X location 7: N/A
Point Load 5: 843.8 lb Point load X location 8: N/A
Point Load 6: 958.3 Ib Point load X location 9: N/A
Point Load 7: 937.8 Ib Point load X location 10: N/A
Point Load 8: 1052.4 Ib Point load Y location 1: 4.000 in
Point Load 9: 1041.6 IbPoint load Y location 2: 87.000 in
111111
J� PointLoad10: 1156.1 Ib` TlWh9012.8 Ib
0,0 ` �� iilli
Added Weight
1.Double wall: 131
\`\ U Notes:
\ 1.The actual weight is stamped on the unit nameplate.
I IP
2.The weight shown represents the typical unit operating weight for the configuration selected.
I Estimated at+/-10%of the nameplate weight..
3.Add weight to the total unit weight.
4.Design Special weights are not displayed.Any weight added through COD(Custom Order Design)
will not be accounted in the+/-10%estimate
5.When 2 or more units are to be placed side by side,the distance between the units should be
increased to 150%of the recommended single unit clearance.The units should also be staggered
to reduce span deflection&assure proper diffusion of exhaust air.
— 194 5/16" 29"
96" 1
PL 2,X1 PL 4,X2 PL 6,X3 PL 8,X4 PL 10,X5
iiiiii((''•?iiiii) illi'•!?jiiii)
\" _,./ v.s_;,
ltAi( still)) P ((lilt•bll)II)
_`
mit
,!Pull) 1111111•ttlll91
_/ , ••-3',11
Y Q_
PL 1,X1 PL 3,X2 PL 5,X3 PL 7,X4 PL9,X5
X
CENTER OF GRAVITY AND INSTALL WEIGHT X-Y POINTS
AIR COOLED DRAWING
FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 15 of 24
Others
Durham AWWTF 5020 AC Replacement September 11,2018
Accessory -Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 55 ton DW DDP
WARNING /\ AVERTISSEMENT A\ ADVERTENCIA
HAZARDOUS VOLTAGE! TENSION DANGEREUSE! iVOLTAJE PELIGROSO!
DISCONNECT ALL ELECTRIC POWER COUPER TOUTES LES TENSIONS ET DESCONECTE TODA LA ENERGIA ELECTRICA,
INCLUDING REMOTE DISCONNECTS OUVRIR LES SECTIONNEURS A DISTANCE, INCLUSO LAS DESCONEXIONES REMOTAS Y
AND FOLLOW LOCK OUT AND TAG PUIS SUIVRE LES PROCEDURES DE SIGA LOS PROCEDIMIENTOS DE CIERRE Y
PROCEDURES BEFORE SERVICING. VERROUILLAGE ET DES ETIQUETTES AVANT ETIQUETADO ANTES DE PROCEDER AL
INSURE THAT ALL MOTOR TOUTE INTERVENTION. VERIFIER QUE TOUS SERVICIO.ASEGURESE DE QUE TODOS
CAPACITORS HAVE DISCHARGED LES CONDENSATEURS DES MOTEURS SONT LOS CAPACITORES DEL MOTOR HAYAN
STORED VOLTAGE. UNITS WITH DECHARGES. DANS LE CAS D'UNITES DESCARGADO EL VOLTAJE ALMACENADO.
VARIABLE SPEED DRIVE,REFER COMPORTANT DES ENTRAINEMENTS A PARA LAS UNIDADES CON EJE DE
TO DRIVE INSTRUCTIONS FOR VITESSE VARAIBLE,SE REPORTER AUX DIRECCION DE VELOCIDAD VARIABLE,
CAPACITOR DISCHARGE. INSTRUCTIONS DE L'ENTRAINEMENT POUR CONSULTE LAS INSTRUCCIONES PARA LA
DECHARGER LES CONDENSATEURS. DESCARGA DEL CONDENSADOR.
FAILURE TO DO THE ABOVE
BEFORE SERVICING COULD RESULT NE PAS RESPECTER CES MESURES DE EL NO REALIZAR LO ANTERIORMENTE
IN DEATH OR SERIOUS INJURY. PRECAUTION PEUT ENTRAINER DES INDICADO,PODRIA OCASIONAR LA MUERTE
BLESSURES GRAVES POUVANT ETRE 0 SERIAS LESIONES PERSONALES.
MORTELLES.
CAUTION IMPORTANT!
USE COPPER CONDUCTORS ONLY! DO NOT ENERGIZE UNIT
UNTIL CHECK-OUT AND
UNIT TERMINALS ARE NOT DESIGNED TO START-UP PROCEDURE HAS
ACCEPT OTHER TYPES OF CONDUCTORS. BEEN COMPLETED.
FAILURE TO DO SO MAY CAUSE DAMAGE TO
THE EQUIPMENT.
ATTENTION
e ,
N'UTILISER QUE DES CONDUCTEURS EN
CUIVRE!
LES BORNES DE L'UNITE NE SONT PAS
CONCUES POUR RECEVOIR D'AUTRES TYPES
DE CONDUCTEURS.
L'UTILISATION DE TOUTAUTRE CONDUCTEUR HEATING
PEUT ENDOMMAGER L'EQUIPEMENT. SECTIONID
PRECAUCION \ SECTION CONDENSER
IUTILICE UNICAMENTE CONDUCTORES DE
COBRE!
LAS TERMINALES DE LA UNIDAD NO ESTAN
DISENADAS PARAACEPTAR OTROS TIPOS DE
CONDUCTORES.
SI NO LO HACE,PUEDE OCASIONAR DANO AL
EQUIPO.
- `
UEVILE PREFIX LOCATION CODE CONNECT STEAM OR CIRCUIT#2 CIRCUIT#1
AREA - - --LOCATION HOT WATER VALVE AS aq ELECTRIC HEAT 200V/230V/60 HZ MAIN UNIT CONTROL
--- SHOWN WHEN REQUIRED
UNITS ONLY
1 INSIDE UNIT CONTROL BOX 4U15
37M HYDRONIC HEAT 36AL 117 118 119 1 1TB120R 3
2 CONDENSER SECTION I ACTUATOR I 4TB2,4S15
514
3 AIR HANDLER SECTION I I I L1 L2 L3 I I L1 L2 L3
BLK WHT
4 HEATING SECTION __ _-
SPLICE SPLICE
5 EXTERNAL FIELD MOUNTED DEVICE -- --
Note: I I !I !I I' I 1111
—
All wiring and components shown dashed to be I 0-) t_I I a- I I a
supplied and installed by the customer in Q
accordance with local electrical codes. T1 T2 I
483A 1 L1 L2 L3 L1 L2 L3
484A LINE VOLTAGE LINE VOLTAGE
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 16 of 24
Others
Durham AWWTF 5020 AC Replacement September 11, 2018
Accessory -Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 55 ton DW DDP
NOTES:
ALL WIRING AND COMPONENTS SHOWN DASHED TO BE SUPPLIED AND INSTALLED BY THE
CUSTOMER IN ACCORDANCE WITH LOCAL ELECTRICAL CODES.
CUSTOMER CONNECTIONS-MAIN UNIT CONTROL(CIRCUIT#1)-ARE LOCATED IN THE
CONDENSER SECTION FOR 20 THRU 75 TON UNITS.
SEE CUSTOMER CONNECTION WIRE RANGE TABLE FOR ACCEPTABLE WIRE SIZES FOR
CONNECTION TO MAIN UNIT TERMINAL BLOCK(1TB1/4TB2)OR DISCONNECT
SWITCH(1S14/4S15).
<4 I WIRES TO THE OPTIONAL STEAM AND/OR HOT WATER HEAT VALVE ARE SUPPLIED WITH
THE UNIT.WIRE CONNECTIONS TO THE VALVE TO BE MADE BY THE CUSTOMER.
<6 OPTIONAL 5U57 REMOTE ZONE TEMP SENSOR IS USED FOR UNOCCUPIED HEAT/COOL
TEMP CONTROL SENSING.
WHEN 5U69 REMOTE ZONE TEMP SENSOR IS USED,REMOVE 5U58 INTERGRAL ZONE
TEMP SENSOR ATTACHED TO TERMINALS S1 AND S2.
<8 WIRES USE SHIELDED TWISTED PAIR WIRE.
<9 J USE SHIELDED TWISTED PAIR WIRE.WRAP SHIELDS WITH TAPE TO PREVENT CONTACT
WITH GROUND.
<10 REMOVE JUMPER(1TB4-15&1TB4-16)AND INSTALL HIGH DUCT TEMP T-STAT/OR
FIELD SUPPLIED DEVICE.
REMOVE JUMPER(1TB4-17&1TB4-18)WHEN FIELD SUPPLIED
EXTERNAL AUTO/STOP SWITCH(5S67)IS INSTALLED.
CHANGEOVER(5K87)AVAILABLE ONLY ON HYDRONIC HEAT UNITS OR MODULATING
GAS HEAT UNITS.
ALARM OUTPUT SWITCHES ON ANY MANUAL RESET DIAGNOSTIC.
<14 OPTIONAL HEAT MODULE AUX.TEMP(5RT16)IS USED FOR MORNING WARM-UP
CONTROL ON UNITS WITH HEATING OPTION.
TERMINAL BLOCK 1TB17 AND ASSOCIATED WIRING REQUIRED WITH GBAS(1U51)OPTION.
DEMAND LIMIT RELAY(5K89)TO BE PROVIDED BY CUSTOMER.
< 161 VENTILATION OVERRIDE MODE CONTACTS RATED 12MA@ 24VDC MINIMUM
(5K90-5K91-5K92-5K93-5K94)TO BE PROVIDED BY CUSTOMER.
<7 WIRE NODES 533&534 REQUIRED WITH BAS/NETWORK COMM MODULE(1U54)OPTION.
USE SHIELDED TWISTED PAIR WIRE.
<18 FIELD CONNECTIONS TO DRIVE VAV BOXES FULL OPEN DURING NIGHT SETBACK MODE.
< 191 15A FUSE REPLACEMENT IS REQUIRED FOR 50 THRU 60 TON-0.50 KVA TRANSFORMER
WITH 200V-230V-460V OR 575V UNIT VOLTAGE.
20A FUSE REPLACEMENT IS REQUIRED FOR 50 THRU 60 TON-0.50 KVA TRANSFORMER
WITH 380V OR 415V UNIT VOLTAGE.
< CONTACTS RATED 12 MA @ 24VDC MINIMUM.
CONNECT TO 24VAC CLASS 2 CIRCUITS ONLY.
REMOVE JUMPER WHEN OPTIONAL FIELD SUPPLIED OUTSIDE AIR SENSOR
(3RT3)IS INSTALLED AND THE UNIT DOES NOT HAVE ECONOMIZER.
<24 FIELD SUPPLIED AND INSTALLED OCCUPIED/UNOCCUPIED CONTACTS(5K86)
FOR USE ON UNITS WITHOUT REMOTE PANEL WITH NIGHT SETBACK(5U58).
GBAS 0-5V OPTION CONNECTIONS.
<26 GBAS 0-WV OPTION CONNECTIONS.
FOR GBAS INPUTS A11-AI4,"GBAS 0-5V"REQUIRES 0-5V VDC
AND"GBAS 0-WV"REQUIRES 0-10VDC.
<281 "ACTIVE DIAGNOSTICS(B05)"APPEARS WITH BOTH"GBAS 0-5V"AND"GBAS 0-10V".
<291 SEE FUSE REPLACEMENT TABLE ON VFD PANEL FOR VFD POWER FUSES(F40,F41,F42).
<30 SWITCH A53,LOCATED ON THE VFD,MUST BE SET TO"U"(OFF).
FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 17 of 24
Others
Durham AWWTF 5020 AC Replacement September 11,2018
Accessory -Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 55 ton DW DDP
FUSE REPLACEMENT TABLE
CONDENSER FAN FUSE UNIT VOLTAGE 200 230 380 415 460 575
1F1 THRU 1F6 CLASS RK5 TIME DELAY 25A 25A 15A 15A 15A 15A
CONTROL POWER FUSE I
0.25 0.30 0.50 0.75 1.00 1.50
CONTROL(1T1)TRANSFORMER RATING KVA KVA KVA KVA KVA KVA
20-30 TON 6.25A 6.25A -- 10A -- --
40 TON 15A 20A -- 20A -- --
1F7 50-60 TON -- -- 15A -- 20A --
CLASS CC-TYPE
FNQ-R 70-75 TON -- -- -- -- 15A 20A
ELECTRIC HEAT FUSE 4F19 THRU 4F36,4F46,47,48 CLASS K5 60A
COMPRESSOR PROTECTION FUSE 1F44&1F45 TYPE MTH 6A
TRANSFORMER CIRCUIT FUSE 1F72 THRU 1F74 TYPE FNQ-R 15A
VFD PROTECTION FUSES(CLASS"r FUSES)OPTIONAL SUPPLY VFD 1 F57-1 F62,OPTIONAL EXHAUST/RETURN VFD 1 F63-1F65
UNIT FUSE 3 HP 5 HP 7.5 HP 10 HP 15 HP 20 HP 25 HP 30 HP 40 HP 50 HP
_VOLTAGE RATING
200V/60/3 600V 40A 60A 80A 100A 150A 200A 225A 300A 350A N/A
BELT DRIVE 230V/60/3 600V 30A 45A 70A 90A 125A 175A 200A 250A 300A N/A
MOTOR
20-130 UNITS 380V/50/3 600V 15A 30A 45A 50A 90A 100A 125A 150A 200A N/A
415V/50/3 600V 15A 30A 45A 50A 90A 100A 125A 150A 200A N/A
460V/60/3 600V 15A 25A 35A 45A 60A 90A 100A 125A 150A 200A
575V/60/3 600V 15A 15A 25A 35A 50A 70A 60A 100A 125A 175A
UNIT FUSE 15 HP 15 HP
OPTIONAL VOLTAGE RATING 3 HP 5 HP 7.5 HP 10 HP 1K-1.6K 1.7K-2.4K 20 HP 25 HP 30 HP
DIRECT DRIVE RPM RPM
MOTOR 20-59 200V/60/3 600V 40A 60A 80A 100A 150A 150A 200A 225A 300A
UNITS 230V/60/3 600V 25A 45A 70A 90A 125A 125A 175A 200A 250A
460V/60/3 600V 15A 25A 35A 45A 70A 60A 90A 100A 125A
575V/60/3 600V 15A 15A 25A 35A 50A 50A 70A 80A 100A
UNIT FUSE 15 HP 15 HP 30 HP 30 HP
VOLTAGE RATING 10HP 1K-1.6K 1.7K-2.4K 20HP 1K-1.6K 1.7-2.4K 40HP SOHP
OPTIONAL RPM RPM RPM RPM
DIRECTMDIVE 200V/60/3 600V 125A 175A 150A 200A 300A 150A 350A N/A
MOTOR 230V/60/3 600V 95A 150A 125A 175A 250A 250A 300A N/A
60-89 TON
460V/60/3 600V 45A 70A 60A 90A 125A 125A 150A 200A
575V/60/3 600V 40A 60A 50A 70A 125A 100A 125A 175A
CUSTOMER CONNECTION WIRE RANGE
NOTES: UNITS WITH MAIN POWER UNITS WITH MAIN POWER
A.BLOCK SIZE&DISCONNECT SIZE TERMINAL BLOCK(ALL VOLTAGES) DISCONNECT SWITCH(ALL VOLTAGES)
ARE BLOCK SIZE WIRE QTY CONNECTOR WIRE RANGE DISCONNECT SIZE WIRE QTY CONNECTOR WIRE RANGE
CALCULATED BY SELECTING THE 335 AMP (1) #6-350MCM 100 AMP (1) #14-1/0
SIZE Ibu AMr (t) #4-500 MCM -- --250 AMP (1) #4-350 kcmil
GREATER THAN OR EQUAL TO 1.15 X 840 AMP (2) #2-600 MCM 400 AMP (1)OR #1-600 kcmil OR
(SUM OF.UNIT LOADS).SEE UNIT — (2) #1-250 kcmil
LITERATURE FOR UNIT LOAD
VALUES. 600 AMP (2) 250-500 MCM
1000 AMP (3) 3/0-500 kcmil
OPTIONAL CONVENIENCE OUTLET FUSE 200V/60/3 230V/60/3 380V/50/3 415V/50/3 460V/60/3 575V/60/3
1F55 AND 1 F56(TIME DELAY TYPE FNQ-R FUSE) 12A 10A N/A N/A 5A 4A
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 18 of 24
Others
Durham AWWTF 5020 AC Replacement September 11,2018
Accessory -Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 55 ton DW DDP
0 0 0 I
WARNING / AVERTISSEMENT A ADVERTENCIA
HAZARDOUS VOLTAGE! TENSION DANGEREUSE! iVOLTAJE PELIGROSO!
DISCONNECT ALL ELECTRIC POWER COUPER TOUTES LES TENSIONS ET DESCONECTE TODA LA ENERGIA ELECTRICA,
INCLUDING REMOTE DISCONNECTS OUVRIR LES SECTIONNEURS A DISTANCE, INCLUSO LAS DESCONEXIONES REMOTAS Y
AND FOLLOW LOCK OUT AND TAG PUIS SUIVRE LES PROCEDURES DE SIGA LOS PROCEDIMIENTOS DE CIERRE Y I
PROCEDURES BEFORE SERVICING. VERROUILLAGE ET DES ETIQUETTES AVANT ETIQUETADOANTES DE PROCEDERAL
INSURE THATALL MOTOR TOUTE INTERVENTION. VERIFIER QUE TOUS SERVICIO.ASEGURESE DE QUE TODOS
CAPACITORS HAVE DISCHARGED LES CONDENSATEURS DES MOTEURS SONT LOS CAPACITORES DEL MOTOR HAYAN
STORED VOLTAGE. UNITS WITH DECHARGES. DANS LE CAS D'UNITES DESCARGADO EL VOLTAJE ALMACENADO.
VARIABLE SPEED DRIVE,REFER COMPORTANT DES ENTRAINEMENTS A PARA LAS UNIDADES CON EJE DE
TO DRIVE INSTRUCTIONS FOR VITESSE VARAIBLE,SE REPORTER AUX DIRECCION DE VELOCIDAD VARIABLE,
CAPACITOR DISCHARGE. INSTRUCTIONS DE L'ENTRAINEMENT POUR CONSULTE LAS INSTRUCCIONES PARA LA
DECHARGER LES CONDENSATEURS. DESCARGA DEL CONDENSADOR.
FAILURE TO DO THE ABOVE
BEFORE SERVICING COULD RESULT NE PAS RESPECTER CES MESURES DE EL NO REALIZAR LO ANTERIORMENTE
IN DEATH OR SERIOUS INJURY. PRECAUTION PEUT ENTRAINER DES INDICADO,PODRIA OCASIONAR LA MUERTE
BLESSURES GRAVES POUVANT ETRE 0 SERIAS LESIONES PERSONALES.
MORTELLES.
CAUTION IMPORTANT!
USE COPPER CONDUCTORS ONLY! DO NOT ENERGIZE UNIT
UNTIL CHECK-OUT AND
UNIT TERMINALS ARE NOT DESIGNED TO START-UP PROCEDURE HAS
ACCEPT OTHER TYPES OF CONDUCTORS. BEEN COMPLETED.
5GE LAU
FAILURE TO DO SO MAY CAUSE DAMAGE TO EMERGENcv EXTERNAL AUTO/STOP
THE EQUIPMENT. wnv ZONE I STOP SWITCH 1 SWITCH
RESET OPTION IT--0\�-1 r_b\o-
ATTENTION I ZSUSI ONE I I I 10 21 I I I 11 21 I
N'UTILISER QUE DES CONDUCTEURS EN I RESET I I 1 r I L- 1_J
TEMP r -I r 1
CUIVRE! 1 SENSOR 435 431 434 438
I L
1
LES BORNES DE L'UNITE NE SONT PAS Y Y 1 L___ n
CONCUES POUR RECEVOIR D'AUTRES TYPES 425 424 I
DE CONDUCTEURS. - - I 1I
L'UTILISATION DE TOUTAUTRE CONDUCTEUR a 5U57 _ 1TB4 - I I
' PEUT ENDOMMAGER L'EQUIPEMENT I REMOTE 1 O 408 -- --1 408 418 12- -1-
ZONE 2D 409 -- r---1--2409 424 13- I 1 1
I TEMP I^___L__3 410 403 14---�-{- �I
PRECAUCION
SENSOR 1-
-4 412 435 15-1-,U
IUTILICE UNICAMENTE CONDUCTORES DE -s 411 431 16 -
COBRE! - - rr 6 417 434 17]_ 11 1-— J
--- 1
nr---T--7 413 438 18 -1 1
LAS TERMINALES DE LA UNIDAD NO ESTAN r-I-----T--8 414 437 19- -I I
DISENADAS PARA ACEPTAR OTROS TIPOS DE r-r---T--9 415 537 20— I
CONDUCTORES. ---4t^r -10 416 538 21---4I I
_ I
I I 11 425 436 22-4
SI NO LO HACE,PUEDE OCASIONAR DANO AL - - I I I I
1 I
EQUIPO. I I
r---I-C 5u69 a I I I 5U68 I
REMOTE ZONE PANEL 4
�
38 I
DEVICE PREFIX LOCATION CODE _ I
_cZONE TEMP - - I 437
AREA LOCATION 1 SENSOR i I
1 INSIDE UNIT CONTROL BOX a - - 408 I_c ii ZONE
TEMPI I I ..
2 CONDENSER SECTION - - 409---y-C 2 COMMON 5K8866 I��
I I I I OCCUPIED/ 2 j I
3 AIR HANDLER SECTIONL—410----C 3 SACSP UNOCCUPIED 24
HEAT 7 D--413—A I1 I I CONTACTS
4 HEATING SECTION lI,—412----C4 MODE - - - -
COOL 8 D-1-414 I I
5 EXTERNAL FIELD MOUNTED DEVICE I )1
J I,_417_--y-C6GND g� I
SYS ON 9 O- 415 1413---[{7 HEAT I C Jt-3(/'J'])
Note:
SERVICE 10D--416-A L-537 --C J1-1(+)
All wiring and components shown dashed to be I l--414----C 8 COOL 5U66
supplied and installed by the customer in -C s1 GND 11 D--417—I I L- REMOTE
accordance with local electrical codes. I 415----C 9 SVS ON 538 I� Jt-2(-) HUMAN
L--1-CI_ INTERFACE
S2 COMM(+)12 D- 418b -q03 ---C J2-1(+) MODULE
I I 416---I-C10 SERVICE I
24 VAC 14 D--403 /
I L-436 ---C J2-2(-) J2-3
5U58 5U59 1
REMOTE EARTH y
REMOTE PANEL a PANEL I GROUND
WITH NSB -
FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 19 of 24
Others
Durham AWWTF 5020 AC Replacement September 11,2018
Accessory -Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 55 ton DW DDP
A\ WARNING AN AVERTISSEMENT A ADVERTENCIA
HAZARDOUS VOLTAGE! TENSION DANGEREUSE! iVOLTAJE PELIGROSO!
DISCONNECT ALL ELECTRIC POWER COUPER TOUTES LES TENSIONS ET DESCONECTE TODA LA ENERGIA ELECTRICA,
INCLUDING REMOTE DISCONNECTS OUVRIR LES SECTIONNEURS A DISTANCE, INCLUSO LAS DESCONEXIONES REMOTAS Y
AND FOLLOW LOCK OUT AND TAG PUIS SUIVRE LES PROCEDURES DE SIGA LOS PROCEDIMIENTOS DE CIERRE Y
PROCEDURES BEFORE SERVICING. VERROUILLAGE ET DES ETIQUETTES AVANT ETIQUETADO ANTES DE PROCEDERAL
INSURE THAT ALL MOTOR TOUTE INTERVENTION. VERIFIER QUE TOUS SERVICIO.ASEGURESE DE QUE TODOS
CAPACITORS HAVE DISCHARGED LES CONDENSATEURS DES MOTEURS SONT LOS CAPACITORES DEL MOTOR HAYAN
STORED VOLTAGE. UNITS WITH DECHARGES. DANS LE CAS D'UNITES DESCARGADO EL VOLTAJE ALMACENADO.
VARIABLE SPEED DRIVE,REFER COMPORTANT DES ENTRAINEMENTS A PARA LAS UNIDADES CON EJE DE
TO DRIVE INSTRUCTIONS FOR VITESSE VARAIBLE,SE REPORTER AUX DIRECCION DE VELOCIDAD VARIABLE,
CAPACITOR DISCHARGE. INSTRUCTIONS DE L'ENTRAINEMENT POUR CONSULTE LAS INSTRUCCIONES PARA LA
DECHARGER LES CONDENSATEURS. DESCARGA DEL CONDENSADOR-.
FAILURE TO DO THE ABOVE
BEFORE SERVICING COULD RESULT NE PAS RESPECTER CES MESURES DE EL NO REALIZAR LO ANTERIORMENTE
IN DEATH OR SERIOUS INJURY. PRECAUTION PEUT ENTRAINER DES INDICADO,PODRIAOCASIONAR LA MUERTE
BLESSURES GRAVES POUVANT ETRE 0 SERIAS LESIONES PERSONALES.
MORTELLES.
CAUTION IMPORTANT!
USE COPPER CONDUCTORS ONLY! DO NOT ENERGIZE UNIT
UNTIL CHECK-OUT AND
UNIT TERMINALS ARE NOT DESIGNED TO START-UP PROCEDURE HAS
ACCEPT OTHER TYPES OF CONDUCTORS. BEEN COMPLETED.
FAILURE TO DO SO MAY CAUSE DAMAGE TO5K9- -
THE EQUIPMENT. - _ -
VENTILATION
ATTENTION OVERRIDE 5K89 5K92 5RT16 — —
MODEACONTACTS DEMAND VENTILATION 6 HEAT I 5K93
16 LIMIT 15 OVERRIDE I MODULE VENTILATION 16
N'UTILISER QUE DES CONDUCTEURS EN r 1 CONTACTS 21 MODE C CONTACTS AUX TEMP I 1 OVERRIDE
1 i
CUIVREI L —� _T J LV,r—-iJa r'b—I�, I 14 I MODE DCONTACTS
523 524 I L -1 I ,( 4 r 1
LES BORNES DE L'UNITE NE SONT PAS 489 490 1 r
CONCUES POUR RECEVOIR D'AUTRES TYPES I 527 528 L J
529 530
DE CONDUCTEURS. IJI 475 476
L I
I
L'UTILISATION DE TOUT AUTRE CONDUCTEUR I I I I I 1
PEUT ENDOMMAGER L'EQUIPEMENT I I TB5 is I I I 1
I -1 ass 475 12 - 1 --J I 1
PRECAUCION I 2 490 476 13-- ' �
IUTILICE UNICAMENTE CONDUCTORES DE L_ 1- 3 523 528 14-J J
7 -4 524 529 15
COBRE! _..)r -1 -5 525 530 16
LAS TERMINALES DE LA UNIDAD NO ESTAN I 1---
6 526 531 17
--7 527 532 18-
DISENADAS PARAACEPTAR OTROS TIPOS DEI
CONDUCTORES. r rn 1
9 550 534 20- n 1
SI NO LO HACE,PUEDE OCASIONAR DANO AL i ?3 r,-101 426 444 22---1--1 I I
EQUIPO. 1
I I I I I
I I I I I I I
DEVICE PREFIX LOCATION CODE 525 1 I I I I I I
427 426.. _ 443 I I 531 1
_ I 526 _.
AREA LOCATION J —i �l�I ---I 44 1 1 532
I INSIDE UNIT CONTROL-BOX - L� I -J 1 _...,__�. � I_ 1 I 1 1
2 CONDENSER SECTION 1 S gI 16 23 r J L� H
L I 1
3 AIR HANDLER SECTION VENTILATION 1 1 ho_J
I
OVERRIDE 3RT3 /_,_,_1., L
4 HEATING SECTION MODE B CONTACTS I OPTIONAL 1 1 5K87 I I I -°-I I O I
OUTSIDECHANGEOVER I
5 EXTERNAL FIELD MOUNTED DEVICE AIR I 21 CONTACTS I 1 VENTILATIONI 5K94 16 I
SENSOR _ - 1 OVERRIDE
Note: 1 I MODE E CONTACTS I
All wiring and components shown dashed to be
supplied and installed by the customer in 5U70
accordance with local electrical codes. REMOTE 534 533
MINIMUM
POSITION ‘M"VaS
I
POTENTIOMETER
TRACER
-549 wHT
1r BLU COMMUNICATIONS 17
RED 1`-- 550
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 20 of 24
Others
Durham AWWTF 5020 AC Replacement September 11,2018
•
Accessory -Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 55 ton DW DDP
A\ WARNING A\ AVERTISSEMENT AN ADVERTENCIA
HAZARDOUS VOLTAGE! TENSION DANGEREUSE! IVOLTAJE PELIGROSO!
DISCONNECT ALL ELECTRIC POWER COUPER TOUTES LES TENSIONS ET DESCONECTE TODA LA ENERGIA ELECTRICA,
INCLUDING REMOTE DISCONNECTS OUVRIR LES SECTIONNEURS A DISTANCE, INCLUSO LAS DESCONEXIONES REMOTAS Y
AND FOLLOW LOCK OUT AND TAG PUIS SUIVRE LES PROCEDURES DE SIGA LOS PROCEDIMIENTOS DE CIERRE Y
PROCEDURES BEFORE SERVICING. VERROUILLAGE ET DES ETIQUETTES AVANT ETIQUETADO ANTES DE PROCEDER AL
INSURE THAT ALL MOTOR TOUTE INTERVENTION. VERIFIER QUE TOUS SERVICIO.ASEGURESE DE QUE TODOS
CAPACITORS HAVE DISCHARGED LES CONDENSATEURS DES MOTEURS SONT LOS CAPACITORES DEL MOTOR HAYAN
STORED VOLTAGE. UNITS WITH DECHARGES. DANS LE CAS D'UNITES DESCARGADO EL VOLTAJE ALMACENADO.
VARIABLE SPEED DRIVE,REFER COMPORTANT DES ENTRAINEMENTSA PARA LAS UNIDADES CON EJE DE
TO DRIVE INSTRUCTIONS FOR VITESSE VARAIBLE,SE REPORTER AUX DIRECCION DE VELOCIDAD VARIABLE,
CAPACITOR DISCHARGE. INSTRUCTIONS DE L'ENTRAINEMENT POUR CONSULTE LAS INSTRUCCIONES PARA LA
DECHARGER LES CONDENSATEURS. DESCARGA DEL CONDENSADOR.
FAILURE TO DO THE ABOVE
BEFORE SERVICING COULD RESULT NE PAS RESPECTER CES MESURES DE EL NO REALIZAR LO ANTERIORMENTE
IN DEATH OR SERIOUS INJURY. PRECAUTION PEUT ENTRAINER DES INDICADO,PODRIA OCASIONAR LA MUERTE
BLESSURES GRAVES POUVANT ETRE 0 SERIAS LESIONES PERSONALES.
MORTELLES.
CAUTION IMPORTANT!
USE COPPER CONDUCTORS ONLY! DO NOT ENERGIZE UNIT
UNTIL CHECK-OUT AND
UNIT TERMINALS ARE NOT DESIGNED TO START-UP PROCEDURE HAS
ACCEPT OTHER TYPES OF CONDUCTORS. BEEN COMPLETED.
NO-614 -
FAILURE TO DO SO MAY CAUSE DAMAGE TO 22HUMIDIFICATION NC-615 -
THE EQUIPMENT. OM-616 --)
ATTENTION
.7>
ALARM NO-448 -1
OUTPUT
N'UTILISER QUE DES CONDUCTEURS EN :OM-449 _
CUIVRE! E> (24 VAC MAX) NC -450 -
LES BORNES DE L'UNITE NE SONT PAS 18>
VAV BOX NO-445--
CONCUES POUR RECEVOIR D'AUTRES TYPES RELAY :OM—446-—-
DE CONDUCTEURS. 22 24 VAC MAX NC-447--
L'UTILISATION DE TOUT AUTRE CONDUCTEUR I
PEUT ENDOMMAGER L'EQUIPEMENT. i
1TB16
PRECAUCION (- 1 507 445 12---JJ
2 508 446 13----1
IUTILICE UNICAMENTE CONDUCTORES DE 3 509 447 14---J
COBRE! 4 541 448 15----J
6 542 450 16
LAS TERMINALES DE LA UNIDAD NO ESTAN 17 J
DISENADAS PARA ACEPTAR OTROS TIPOS DE I - 6 543 -————
CONDUCTORES.
614
7 544 18---—
614
8 545 61519-----
SI NO LO HACE,PUEDE OCASIONAR DANO AL PUEDE OCASIONAR DANO AL ----9 546 616 20-————
-10 612 21
EQUIPO.
i r_-- 11 613 22
DEVICE PREFIX LOCATION CODE i
I
AREA LOCATION I
1 INSIDE UNIT CONTROL BOX ,(. 5U108
613 -(-) SPACE
2 CONDENSER SECTION
612 -(+) -IUMIDITYSENSOR
3 AIR HANDLER SECTION
4 HEATING SECTION -546 -NC HEAT MODE RELAY OUTPUT
"---545 -CON (HYDRONIC HEAT OR MODULATING 22
5 EXTERNAL FIELD MOUNTED DEVICE " -544 -NO GAS HEAT)
Note: H—-543 -NC VO
All wiring and components shown dashed to be 542 -CON RELAY <22
supplied and installed by the customer in —-541 -NO OUTPUT
accordance with local electrical codes.
—-509 -NC DIRTY 22
--508 -COM FILTER
L--507 -NO (601) \25 I
508 -(-) 0-10 VDC
--509 -(*) (A01) 26
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 21 of 24
Others
Durham AWWTF 5020 AC Replacement September 11,2018
Accessory -Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 55 ton DW DDP
DANFOSS VARIABLE FREQUENCY DRIVE
PROGRAMMING PARAMETERS
MENU PARAMETER DESCRIPTION SETTING
SET ONLY FOR
1-21 MOTOR POWER APPLICATIONS USING
3HP HIGH EFFICIENCY
MOTORS
SET ONLY FOR
LOAD/MOTOR 1-22 MOTOR VOLTAGE 200/230V 60HZ
380/415V 50HZ
APPLICATIONS
1-24 MOTOR CURRENT SET BASED ON
MOTOR NAMEPLATE
1-25 MOTOR NOMINAL SPEED 1800 RPM
1-73 FLYING START ENABLED
BRAKES 2-01 DC BRAKE CURRENT 0%
REFERENCE/ 3-15 REFERENCE 1 SOURCE ANALOG INPUT 53<30
RAMPS 3-41 RAMP 1 RAMP UP TIME 30 SECONDS
3-42 RAMP 1 RAMP DOWN TIME 30 SECONDS
LIMITS/ 4-12 MOTOR SPEED LOW LIMIT 22HZ
WARNINGS 4-18 CURRENT LIMIT 100%RATED CURRENT
DIGITAL 5-40[0] FUNCTION RELAY 1 NO ALARM
IN/OUT 5-40[1] FUNCTION RELAY 2 RUNNING
14-01 SWITCHING FREQUENCY 4.5KHZ
14-12 FUNCTION AT MAINS DEBATE
SPECIAL IMBALANCE
FUNCTIONS 14-20 RESET MODE AUTOMATIC RESET X 3
14-60 FUNCTION AT OVER DEBATE
TEMPERATURE
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 22 of 24
Others
Durham AWWTF 5020 AC Replacement September 11,2018
Tag Data -Seismic Curb (Qty: 1)
Item Tag(s) Qty
B1 No Tag 1
Product Data -Seismic Curb
Item: B1 Qty: 1
FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 23 of 24
Others
Crystal Distribution, Inc.
CDI 17560 Tyler Street NW
Elk River, MN 55330
Phone:763.391.7790
CUSTOM CURB ADAPTERS
Toll Free: 1.888.234.7001
CDI QUOTE #1097785
CURBS
Line Quantity CDI Part # Description Tag
A 1 C2-0014-3225 Straight Curb
Conforming
Assembled, No Pitch, 14 in
New Model: SXHL50 (PARTIAL PERIMETER)
; Estimated Weight 645.85 lbs
B 1 C9-0014-096-ER100 Equipment Rails
Conforming
Assembled, No Pitch, 14 in, Length 96 in
New Model:CDI ER100
Wood Nailer; Removable Cover
TRANE
Attn: S*HC / S*HF C50 / 55 Tag:
S*HG D50 / D55
S*HF F50 / 55
(* =E,F,L,S,X)
94 3/8"
268 1/8"
96 7/16"
73 13/16"
33 5/16"
25 13/16"
3 3/8"H
ALL BRACES DROPPED
1 3/16" FROM TOP
84 1/2" RETURN SUPPLY
AIR80 3/8" 95 15/16"
76 5/8" AIR
13"
7 13/16"
6" FILLER PANEL IN RA
7 1/2"
SLEEPER RAIL
TO BE 1 3/8 LOWER
THAN CURB HEIGHT
* Verify existing curb OD
* Verify supply and return openings
* Note any changes
DIMENSIONS ARE 3RD ANGLECTION * Call with any questions
AS FOLLOWS: PROJE
IASAOmm, �� * Fax back if drawing is OK as is
APPROVALS DATE TITLE:
DRAWN: O.OLIVARES 5/4/07
TRANE
CHECKED,
•
MOMT: ROOF CURB
17560 TYLER ST NW FILE NAME: DRAWING NO.: REV:
C D tEL763K RIVE1-77R,90 MN 55330
ECO u3225: 3225
0539
(763)3917851 SCALE: 1:42 SHEET:1 OF 1
CCUSTOM CURB ADAPTERS
Calculation Requirements
Seismic Engineering Data:
• Required:
Project Locations (Address or Lat./Long. )
Mean Roof Height
Unit Weight and Dimensions
• Optional (These can be assumed but may be contained in the project specification)
Design Code Reference
Unit Center of Gravity or Corner Weights
Importance Factor(Ip)
Component Amplification Factor(k)
Component Response Modification Factor(Rp)
Spectral Acceleration (SD,SD1,Sos)
Fastening Data:
• Required Information:
Curb Location and Attachment Material Below Curb
Gauge of base frame of unit
• Optional:
Fasteners Size and type
Wind Engineering Data:
• Required:
Project Locations (Address or Lat./Long. )
Building Height
Unit Weight and Dimensions
Topographical Factor(KJ—Is the location on the top half of a hill or on a ridge?
• Optional (These can be assumed but may be contained in the project specifications)
Design Code Reference
Unit Center of Gravity or Corner Weights
Wind Directional Factor(Kd)
Velocity Pressure Exposure(KZ)
Basic Wind Velocity(V)
Velocity Pressure(qh)
Gust Factor(G)
Net Force Coefficient(Cf)
Importance Factor(I)
Risk Category( I, II, III & IV)
Exposure Category(A-D)
Fastening Data:
• Required Information:
Curb Location and Attachment Material Below Curb
Gauge of base frame of unit
• Optional:
Fasteners Size and type