Report (4) M2rvrq- Ln • TRANE Submittal ` �' � �i�, r��. . RECEIVED JAN 7 ,y 2019 Prepared For: Date: September 11, 2018 CITY OF TIGARD Hydro Temp Mechanical Customer P.O. Number: Kee-er (,t. 4cef Customer Project Number: Sold To: Job Number: Job Name: Durham AWWTF 5020 AC Replacement Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval. Product Summary Qty Product 1 Commercial Rooftop Air Conditioning Units (Midrange) 1 Seismic Curb The attached information describes the equipment we propose to furnish for this project, and is submitted for your approval. Product performance and submittal data is valid for a period of 6 months from the date of submittal generation. If six months or more has elapsed Kyle Wolf between submittal generation and equipment release,the product Trane performance and submittal data will need to be verified. It is the 7257 SW Kable Lane customer's responsibility to obtain such verification. Portland, OR 97224-7181 Phone: (503) 620-8031 Cell: (503) 828-6788 Fax: (503) 639-1454 J:IJOBSI124171940181Durham AWWTF 5020 AC Replacement-submittal 02.doc Table Of Contents Product Summary 1 Commercial Rooftop Air Conditioning Units (Midrange) (Item Al) Tag Data 3 Product Data 3 Performance Data 3 Mechanical Specifications 5 Unit Dimensions 10 Fan Curve 13 Weight, Clearance&Rigging Diagram 14 Accessory 16 Seismic Curb (Item B1) Tag Data 23 Product Data 23 Durham AWWTF 5020 AC Replacement September 11,2018 Tag Data -Commercial Rooftop Air Conditioning Units (Midrange) (Qty: 1) Item Tag(s) Qty Description Model Number Al 55 ton DW DDP 1 20-75 Ton Packaged Industrial Rooftop ( SXHLF554 Product Data -Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 55 ton DW DDP DX Cooling only with extended casing R-410A refrigerant SUBMITTAL REVIEW 55 Ton unit I ❑ NOMAKE EXCEPTIONSCORRECTIONS TAKENNOTED ❑ REVISE AND RESUBMIT ❑ ❑ SUBMIT SPECIFIED ITEM 460 Volt-60 Hertz-3 Phase CHECKING IS ONLY FOR GENERAL CONFORMANCE WITH THE DESIGN CONCEPT 100% Exhaust- 7.5 hp with Statitrac building pressure control OF THE PROJECT AND GENERAL COMPLIANCE WITH THE INFORMATION IN THE CONTRACT DOCUMENTS. ANY ACTION SHOWN ABOVE, IS SUBJECT TO THE 600 rpm - Exhaust/return fan REQUIREMENTS OF THE PLANS AND SPECIFICATIONS. CONTRACTOR IS 0-1000/o Economizer RESPONSIBLE FOR: DIMENSIONS WHICH SHALL BE FABRICATED AND CORRELATED AT THE JOB SITE;FABRICATION PROCESSES AND TECHNIQUES OF Economizer control w/comparative enthalpy CONSTRUCTION:COORDINATION OF HIS WORK THAT OF ALL OTHER TRADES; AND THE SATISFACTORY PERFORMANCE OF HIS WORK. Filter gauge 2.00" [51 mm] Spring isolators CUNDIFF ENGINEERING,INC. 7007 S.W.CARDINAL LN.#145 PORTLAND.OREGON 97224 MERV 8 High efficiency throwaway filters 09/21/2018 eDrive, Direct drive plenum (DDP) supply fan INITIALED BY: CMB DATE: 20 hp DDP 120% width 1500 rpm VAV (DTC)with supply& exhaust/return VFD with bypass Standard ambient control cULus Non-fused unit disconnect switch Low leak outside air dampers Corrosion protected condenser coil Contractor to verify Hinged access doors SCADA tie-in BACnet communication interface module requirements. Factory-powered 15A GFI Convenience outlet Startup Included -Trane Service must start equipment for warranty to be honored Solid double wall construction Stainless steel sloped drain pan Corrosion protected evaporator coil 1st Year Labor warranty air cooled Refrigerant Warranty First Year Only Performance Data -Commercial Rooftop Air Conditioning Units (Midrange) Tags 55 ton DW DDP Supply airflow(cfm) 18000 Exhaust/Return airflow(cfm) 18000 Cooling entering DB (F) 80.00 Cooling entering WB (F) 67.00 Ambient DB (F) 95.00 Cooling leaving coil DB (F) 56.13 Cooling leaving coil WB (F) 55.35 Cooling leaving unit DB (F) 58.37 Cooling leaving unit WB (F) 56.23 Gross total capacity(MBh) 655.07 Gross sensible capacity (MBh) 481.79 Gross latent capacity(MBh) 173.28 Net total capacity(MBh) 610.69 Net sensible capacity (MBh) 437.41 Net sensible heat ratio (%) 71.62 Fan motor heat(MBh) 44.38 Evaporator face area (sq ft) 38.00 Supply duct static pressure (in H2O) 2.000 Return duct static pressure (in H2O) 0.500 Component S.P. drop (in H2O) 0.860 Total static pressure (in H2O) 3.360 Supply motor bhp (bhp) 16.00 FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 3 of 24 Others Durham AWWTF 5020 AC Replacement September 11, 2018 Tags 55 ton DW DDP Supply fan rpm (rpm) 1442 Supply fan efficiency (%) 59.51 Exhaust static pressure (in H2O) 0.500 Exhaust motor bhp (bhp) 7.00 Exhaust fan rpm (rpm) 562 System power(kW) 64.10 EER @ AHRI (EER) 10.6 IEER @ AHRI (EER) 14.0 Minimum circuit ampacity (A) 136.15 Maximum overcurrent protection (A) 150.00 Minimum disconnect switch size (A) 148.00 Recommended dual element(A) 150.00 Compressor 1 count(Each) 4.00 Compressor 1 RLA (A) 20.20 Supply fan motor FLA (A) 27.00 Supply motor count ( ) 1 Supply fan count (Each) 1.00 Condenser fan FLA (A) 10.80 Exhaust fan motor FLA(A) 9.80 Other FLA (A) 1.00 Desired reheat set point (F) 70.00 EDB in HGRH (F) 73.00 EWB in HGRH (F) 64.00 Ambient DB in HGRH (F) 75.00 Ambient WB in HGRH (F) 68.00 R-410A refrigerant charge - circuit 1 (Ib) 34.8 R-410A refrigerant charge - circuit 2 (Ib) 32.0 Installed point load 1 (Ib) 646.0 Installed point load 2 (Ib) 760.5 Installed point load 3 (Ib) 750.8 Installed point load 4 (Ib) 865.4 Installed point load 5 (Ib) 843.8 Installed point load 6 (Ib) 958.3 Installed point load 7 (Ib) 937.8 Installed point load 8 (Ib) 1052.4 Installed point load 9 (Ib) 1041.6 Installed point load 10 (lb) 1156.1 Total installed weight (Ib) 9012.8 First X dimension (ft) 17.24 First Y dimension (ft) 4.01 Installed point load 1 -X (in) 4.000 Installed point load 1 -Y (in) 4.000 Installed point load 2 - X (in) 101.000 Installed point load 2 -Y (in) 87.000 Installed point load 3 -X (in) 187.000 Installed point load 4 -X (in) 274.000 Installed point load 5 - X (in) 370.000 FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 4 of 24 Others Durham AWWTF 5020 AC Replacement September 11,2018 Mechanical Specifications -Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 55 ton DW DDP General - R410A Units shall be specifically designed for outdoor rooftop installation on a roof curb and be completely factory assembled and tested, piped, internally wired, fully charged with R-410A compressor oil and shipped in one piece. Units shall be available for direct expansion cooling only, or direct expansion cooling with natural gas, electric, hot water or steam heating. Filters, outside air system, exhaust air system, optional non-fused disconnect switches and all operating and safety controls shall be furnished factory installed. All units shall be cULus approved and factory run tested. Cooling capacity shall be rated in accordance with AHRI Standard 360. All units shall have decals and tags to aid in service and indicate caution areas. Electrical diagrams shall be printed on long life water resistant material and shall ship attached to control panel doors. Casing Exterior panels shall be zinc coated galvanized steel, phosphatized and painted with a slate grey air-dry finish durable enough to withstand a minimum of 672 hours consecutive salt spray application in accordance with standard ASTM B117. Screws shall be coated with zinc-plus-zinc chromate. Heavy gauge steel hinged access panels with tiebacks to secure door in open position shall provide access to filters and heating sections. Refrigeration components, supply air fan and compressor shall be accessible through removable panels as standard. Unit control panel, filter section, and gas heating section shall be accessible through hinged access panels as standard. Optional Double Wall Construction hinged access doors shall provide access to filters, return/exhaust air, heating and supply fan section. All access doors and panels shall have neoprene gaskets. Interior surfaces or exterior casing members shall have 1/2"Tuf-Skin fiberglass insulation. Unit base shall be watertight with heavy gauge formed load bearing members,formed recess and curb overhang. Unit lifting lugs shall accept chains or cables for rigging. Lifting lugs shall also serve as unit tiedown points. Solid Double Wall Construction The sheet metal liners shall provide a mechanical fastener for insulation and prevent the possibility of loose insulation fibers from entering the airstream. 16 gauge exterior liners shall be welded to 20 gauge interior liners. All interior airstream insulation shall be lined, with the exception of the vertical supports, which have foil faced insulation. cULus approved. Hinged Access Doors Hinged access doors shall provide easy access to supply fan, filters, exhaust/return fan, and heating section.These access doors shall feature double wall construction with dual density insulation sandwiched between heavy gauge galvanized steel panels for strength and durability Corrosion Protected Condenser Coil All Aluminum Microchannel condenser coil protection shall consist of a corrosion resistant coating that shall withstand ASTM B117 Salt Spray test for 6000 hours and ASTM G85 A2 Cyclic Acidified Salt Fog test for 2400 hours.This coating shall be added after coil construction covering all tubes, headers and fin edges, therefore providing optimal protection in more corrosive environments. Condenser Fans and Motors All condenser fans shall be vertical discharge, direct drive fans, statically balanced, with steel blades and zinc plated steel hubs. Condenser fan motors shall be three-phase motors with permanently lubricated ball bearings, built-in current and thermal overload protection and weathertight slingers over motor bearings. Evaporator Coil - R410A Internally enhanced copper tubing of 3/8" or 1/2" O.D. shall be mechanically bonded to heavyduty aluminum fins of configured design. All coils shall be equipped with thermal expansion valves and factory pressure and leak tested. Sloped Stainless Steel Drain Pan The double sloping stainless steel drain pan shall promote runoff of standingwater from condensation inside the unit.Two drain pipes shall be installed through the base channel on each side of the unit.The evaporator drain pan shall be constructed of 14 gauge stainless steel. On units 40 tons and larger, the intermediate drain pan shall be constructed of 16 gauge stainless steel.This shall provide protection in corrosive environments Compressors - R410A FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 5 of 24 Others Durham AWWTF 5020 AC Replacement September 11,2018 The Trane Scroll compressor shall be industrial grade, direct drive 3600 RPM maximum speed scroll type. The motor shall be suction gas-cooled hermetic design. Compressor shall have centrifugal oil pump with dirt separator, oil sight glass, and oil charging valve. Compressor shall also be provided with thermostatic motor winding temperature control to protect against excessive motor temperatures resulting from over-/under-voltage or loss of charge, high and low pressure cutouts, and reset relay. Phase Monitor Shall protect 3-phase equipment from phase loss, phase reversal, and low voltage. Any fault condition shall produce a Failure Indicator LED, and send the unit into an emergency stop condition. cULus approved. (Standard on 20-75T units) Supply Fan Supply fan motors shall be either open drip-proof or enclosed fan cooled. All supply fans shall be dynamically balanced in factory. Supply fan shall be test run in unit and shall reach rated rpm. All 60 Hz supply fan motors meet the Energy Independence Security Act of 2007 (EISA). All 50 Hz supply fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). Direct-Drive Plenum Supply Fan Supply fan shall be [one] [two] single width, single inlet 9-blade plenum fan. Fan blades shall be aluminum backward-inclined airfoil. Plenum fans shall be direct-driven. Entire assembly shall be completely isolated from unit and fan board by 2" deflection spring isolation. Multiple fan widths shall be available to optimize efficiency. Fan shall not require routine maintenance such as fan bearing lubrication, belt tensioning and replacement, sheave alignment, and setscrew torque checks. Variable Frequency Drive Unit shall include factory-installed and tested variable frequency drive[s](VFD)to provide motor speed modulation. The VFD shall receive a 0-10VDC speed signal from the unit controller. The drive will respond to the signal by accelerating or decelerating to maintain the controlling set point(duct static, space pressure, etc). VFD shall also include the following features: 1. Designed,constructed, and tested in accordance with NEMA ICS, NFPA,and IEC standards and housed in a plastic IP20 enclosure. 2. DC link reactors on both the positive and negative rails of the DC bus equal to 3% impedance to minimize power line harmonics. 3. Full rated output current continuously- 110% of rated current for 60 seconds and 160%of rated current for up to 0.5 second while starting. 4. Isolation between the Drive's power circuitry and control circuitry to ensure operator safety and to protect connected electronic control equipment from damage caused by voltage spikes, current surges, and ground loop currents. 5. Audible noise reduction through automatic adjustment of the carrier frequency and frequency avoidance. 6. Rated at 40C with a standard operating range of-10 to 50C(14 to 124F)ambient temperatures and 0 to 95%relative humidity 7. Self-diagnostics and motor protections such as: cULus listed overload, phase loss, and internal thermal overload. 8. Off/Stop and Auto/Start selector switches to start and stop the AC Drive and determine the speed reference. a. On units with bypass, an AC Drive/Off/Bypass hand selector switch shall be provided in the unit control box b. In DRIVE mode speed reference shall be provided by a 0-10 VDC analog input 9. A keypad interface which shall be programmable by language and feature multiple lines for easy reading. 10. Controlled and/or accessible points such as AC Drive Start/Stop, speed reference, and fault diagnostics. 11. Meter points such as motor power in HP, motor power in kW, motor kW-hr, motor current, motor voltage, hours run, DC link voltage, thermal load on motor, Thermal load on AC Drive and Heatsink temperature. FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 6 of 24 Others Durham AWWTF 5020 AC Replacement September 11,2018 12. Troubleshooting features such as: a. AC Drive memory storage of the last 10 faults and related operational data b. Four simultaneous displays: frequency or speed, run time, output amps and output power c. Keypad which shall display: Reference Signal Value, Output Frequency in Hz or percent, Output Amps, Motor HP, Motor kW, kW 13. Coated circuit boards for protection against corrosive environments 14. Field readable BACnet points to allow for communication of stauts, setpoints and diagnostics to the BAS. Bypass control Shall provide full nominal airflow in the event of drive failure. Two-inch Spring Isolators Supply and Exhaust/Return fan (if applicable) assemblies shall be isolated with two-inch nominal deflection to reduce transmission of vibrations Modulating 100 Percent Exhaust Fan with Statitrac Control Two, double-inlet, forward-curved fans shall be mounted on a common shaft with fixed sheave drive. All fans shall be dynamically balanced and tested in factory before being installed in unit. Exhaust fan shall be test run as part of unit final run test. Unit shall reach rated rpm before fan shaft passes through first critical speed. Fan shaft shall be mounted on two grease lubricated ball bearings designed for 200,000-hour average life. Optional extended grease lines shall be provided to allow greasing of bearings from unit filter section. Fan motor and assembly shall be mounted on common base to allow consistent belt tension with no relative motion between fan and motor shafts. Entire assembly shall be completely isolated from unit and fan board by double deflection, rubber in shear isolators or spring isolation on motor sizes larger than five hp. For both CV and VAV rooftops, the 100 percent modulating exhaust discharge dampers (or VFD)shall be modulated in response to building pressure.A differential pressure control system, (Statitrac), shall use a differential pressure transducer to compare indoor building pressure to outdoor ambient atmospheric pressure. The FC exhaust fan shall be turned on when required to lower building static pressure setpoint. The (Statitrac) control system shall then modulate the discharge dampers (or VFD)to control the building pressure to within the adjustable, specified dead band that shall be adjustable at the Human Interface Panel. All 60 Hz exhaust fan motors meet the Energy Independence Security Act of 2007 (EISA). 0-100 percent modulating economizer Operated through the primary temperature controls to automatically utilize OA for "free" cooling. Automatically modulated return and OA dampers shall maintain proper temperature in the conditioned space. Economizer shall be equipped with an automatic lockout when the outdoor high ambient temperature is too high for proper cooling. Minimum position control shall be standard and adjustable at the Human Interface Panel or with a remote potentiometer or through the building management system. A spring return motor shall ensure closure of OA dampers during unit shutdown or power interruption. Mechanical cooling shall be available to aid the economizer mode at any ambient. Low leak economizer dampers shall be standard with a leakage rate of 2.5 percent of nominal airflow(400 CFM/ton)at 1"wg. static pressure. Economizer Control with Comparative Enthalpy Two enthalpy sensors shall be provided to compare total heat content of the indoor air and outdoor air to determine the most efficient air source when economizing. low-leak economizer dampers Standard low leak dampers shall be provided with chlorinated polyvinyl chloride gasketing added to the damper blades and rolled stainless steel jamb seals to the sides of the damper assembly. Dampers shall have a leakage rate of 1% at 1.0 in WC pressure differential High efficiency throwaway, MERV 8 Shall be two-inch high efficiency MERV 8 media filters with average dust spot efficiency of 25-35 percent and an average arrestance in excess of 90 percent when tested in accordance with ASHRAE 52-76. Differential Pressure Gauge FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 7 of 24 Others Durham AWWTF 5020 AC Replacement September 11,2018 A factory-installed, dial-type, differential pressure gauge shall be piped to both sides of the filter to indicate status. Gauge shall maintain a +/- 5 percent accuracy within operating temperature limits of-20°F to 120°F. Gauge shall be flush-mounted with casing outer wall. Filter sections consisting of pre- and post-filters shall have a gauge for each. Unit Controller DDC microprocessor controls shall be provided to control all unit functions. The control system shall be suitable to control CV or VAV applications. The controls shall be factory-installed and mounted in the main control panel. All factory-installed controls shall be fully commissioned (run tested) at the factory. The unit shall have a Human Interface Panel with a 16 key keypad, a 2 line X 40 character clear English display as standard to provide the operator with full adjustment and display of control data functions.The unit controls shall be used as a stand-alone controller,or as part of a building management system involving multiple units. 1 The unit shall be equipped with a complete microprocessor control system.This system shall consist of temperature and pressure (thermistor and transducer) sensors, printed circuit boards (modules), and a unit mounted Humanlnterface Panel. Modules (boards) shall be individually replaceable for ease of service. All microprocessors, boards and sensors shall be factory mounted, wired and tested. The microprocessor boards shall be stand-alone DDC controls not dependent on communications with an on-site PC or a Building Management Network. The microprocessors shall be equipped with on-board diagnostics, indicating that all hardware, software and interconnecting wiring are in proper operating condition. The modules (boards) shall be protected to prevent RFI and voltage transients from affecting the board's circuits. All field wiring shall be terminated at separate, clearly marked terminal strip. Direct field wiring to the I/O boards is not acceptable. The microprocessor's memory shall be non-volatile EEPROM type requiring no battery or capacitive backup, while maintaining all data. 2 Zone sensors shall be available in several combinations with selectable features depending on sensor. 3 The Human Interface Panel's keypad display character format shall be 40 characters x 2 lines. The character font shall be 5 x 7 dot matrix plus cursor. The display shall be Supertwist Liquid Crystal Display(LCD) with blue characters on a ray/green background which provides high visibility and ease of interface. The display format shall be in clear English. Two or three digit coded displays are not acceptable. 4 The keypad shall be equipped with 16 individual touch-sensitive membrane key switches. The switches shall be divided into four separate sections and be password protected from change by unauthorized personnel. The six main menus shall be STATUS, SETPOINTS, DIAGNOSTICS, SETUP, CONFIGURATION and SERVICE MODE. BACnet Communication Interface Module Option shall provide control and monitoring of the rooftop by Tracer SC or a 3rd party building management system utilizing BACnet protocol. Unit Interrupt Rating (Standard Short Circuit Current Rating-SCCR) A 5,000 Amp rating shall be applied to the unit enclosure using a non-fused circuit breaker for disconnect switch purposes. Fan motors, compressors, and electric heat circuits shall be provided with series rated circuit breakers that will provide the unit rated level of protection. The unit shall be marked with approved cULus markings and will adhere to cULus regulations. Factory Powered GFI Convenience Outlet A15A, 115V Ground Fault Interrupter convenience outlet shall be factory installed. It shall be wired and powered from a factory mounted transformer. Unit-mounted, non-fused disconnect with external handle shall be furnished with factory powered outlet Non-Fused Disconnect Switch with External Handle External handle SHALL enable the operator to disconnect unit power with the control box door closed for safety. Design Special -CompleteCoat Option shall dip and bake evaporator coils in an electro-mechanically bonded flexible epoxy coating. Coating shall provide uniform epoxy coating of all surfaces on aluminum fins, copper tubes, coil frames, and heads of evaporator No associated surfaces shall remain bare. Option shall allow for corrosion resistance without performance degradation. Coils with coating passed 3000-hour salt spray test. All coil surfaces coated with epoxy material shall give uniform coverage (min 0.8 mils), without fin bridging. IntelliPak I units with the CompleteCoat option shall keep their cULus FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 8 of 24 Others Durham AWWTF 5020 AC Replacement September 11,2018 listing. Equipment manufactured by Trane that includes required start-up and sold in North America will not be warranted by Trane unless Trane or its authorized independent Trane commercial sales office performs the startup on the equipment. Certified AHRI Performance Packaged Rooftop units cooling, heating capacities and efficiencies are rated within the scope of the Air-Conditioning, Heating & Refrigeration Institute (AHRI) Certification Program and display the AHRI Certified®mark as a visual confirmation of conformance to the certification sections of AHRI Standard 340-360 (I-P) and ANSIZ21.47 and 10 CFR Part 431 pertaining to Commercial Warm Air Furnaces. The applications in this catalog specifically excluded from the AHRI certification program are: -Ventilation modes -Heat Recovery. -Units larger than nominal 63 tons in Cooling -Evaporative Condensers FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 9 of 24 Others O T -- ... '- _ ., NOTES: :' C r- 1 1.VERIFY WEIGHT,CONNECTION,AND ALL DIMENSION WITH cD 0 /„ ", / o. INSTALLER DOCUMENTS BEFORE INSTALLATION ., '� S y II I IIg•uIIJ ■IIW(01)°1119 I 2.LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT. v 3 'Ti •V 3.OVERALL UNIT WIDTH INCREASES 5/8"BEYOND LIFTING LUG D -, �i -��\ • ,�, WITH ULTRA LOW LEAK POWER EXHAUST DAMPERS •" G II IRIg •)111111 IRP i 01;1!1 90 9/16"4.RETURN AIR OPENING CONFIGURATION FOR USES WITH NO A 3 \ . _ • AIR OPTION,BAROMETRIC RELIEF,AND EXHAUST FAN. „''• y p > e 5.IF FIELD CONVERTING SUPPLY&RETURN OPENING(S)TO eG -I 0- ; ,,•:99!!D. �y Ilmeu:0,71.' HORIZONTAL OR VERTICAL AIRFLOW,FACTORY MUST VERIFY •' 71 `a • • �_ ps_ ' IF UNIT OPTIONS WILL ALLOW IT.FACTORY INSTALLATION IS Cl) O y ALWAYS RECOMMENDED. . Is) CD CO 0 0 LIFTING POINTS X6 v A 54 50/55 TON PLAN VIEW AMBIENT DAMP 3 43 AMBIENT DAMPER I CI Zn d F, CA m Ci 3 Q -r--7-7 —_ i I . vO A 94 3/16" 87 1/4" 81 5/16" 82 5/16" 81 5/16" .4. Ii I "Q D e 1"NPT-F CONDENSATE O DRAIN(BOTH SIDE) 1"NPT-F CONDENSATE :_. 3 0 DRAIN(BOTH SIDE) S. A 1 3/8"DRAIN HOLES (NOT USED ON UNITS (BOTH SIDE) 93 7/8"88 7/8 co N o 144 1/8" WITH DDP FANS) C3 0 184 5116" SEE NOTE 3-'77 74: A' 392 1/2" 1 E 394 9/16" 50 TON FRONT VIEW Q 1 1/8"CONDUIT SU 50/55 TON LEFT SIDE VIEW D.0 CONTROL CIRCUIT 3 1 1/8"CONDUIT CQ - 71/16 ., A.CCONTROLCIRCUIT :. \ 11/8"CONDUIT AC& • 1 I I II 7 DC CONTROL CIRCUIT . . �I— 4 1/8"CONN.THRU BA3/8" SE FOR POWER SUPPLY I I— 1 � I RETURN AIR OPENING . . I• I 8 3/8" 40 7/16" SEE NOTE 4 8 11/16" 45 13/16" e SUPPLY a - 0-9 3/4" 4 CD (D 15 3/4" -0 m 5 13/16"- 92 3/16"ID ^ 17 3/4" 3 co - 2385/16" - 29" - - 20 1/4" - 22" fV 0 p Np 50/55 TON PLAN VIEW OF UNIT co Durham AWWTF 5020 AC Replacement September 11,2018 Unit Dimensions - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 55 ton DW DDP 1" _ 1" 5/8" 1/2"—d h- 5/8" 1" 3" /90° 5 5/8" 3 5/8" 1� 1-=----2 3/4" NNN \..iCY 1 5/8" b 1 5/8" 6 9/16" p p 4 13/16" 5 13/16" TYPICAL PEDESTAL AND BASE DIMENSION DRAWING UNIT BASE Ll 2 1/2" LIFTING LUG SHIPS WITH CURB �, 4"LONG FIELD INSTALLED GASKET 2 1/2"--14"LONG 3/8" • I LIFTING LUG ,4 k 1PEDESTAL 2"X 4"NAILER (FURNISHED WITH KIT) ROOF CURB TYPICAL PEDESTAL AND BASE PAN DETAIL TYPICAL ROOF CURB AND BASE PAN DETAIL DETAIL DETAIL FLD=Furnished by Trane U.S Inc./Installed by Equipment Submittal Page 11 of 24 Others • Durham AWWTF 5020 AC Replacement September 11,2018 Unit Dimensions -Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 55 ton DW DDP ELECTRICAL/GENERAL DATA TONS GAS HEATING-PERFORMANCE Model(Tonnage): SXHLF55(55 Ton) Heating Input: Unit Operating Voltage Range: 414-506 Heating Output: Unit Primary Voltage: 460 Capacity Steps: Unit Hertz: 60 Unit Phase: 3 HEATING-GENERAL DATA Gas inlet pressure:(in w.c.) EER: 10.6 EER Gas Pipe Connection Size: IEER: 14.0 EER COMPRESSOR ELECTRIC HEATER Compressor 1 Count: 4.00 Each Electric Heater Kw: Compressor 1 RLA: 20.20 A Electric Heater Full Load Amps: Compressor 2 Count: Value not available Compressor 2 RLA: Value not available Compressor 3 Count: Value not available Compressor 3 RLA: Value not available SUPPLY FAN MOTOR EXHAUST/RETURN FAN MOTOR SECTION Number of Fans: 1.00 Each Number: Value not available Number of Motors: 1 Horsepower(Each): 100%Exhaust-7.5 hp with Statitrac building pressure control Total Horsepower: 20 hp DDP 120%width Exhaust/Return Fan Motor FLA: 9.80 A Supply Fan Motor Full Load Amps: 27.00 A Supply Fan Efficiency: 59.51 CONDENSER FAN MOTOR FILTERS-TYPE Number: 6 Type: Horsepower(each): 1.0 Furnished: YES Condenser Fan Motor Full Load Amps(Total): 10.8 Number: 20 Recommended Size: 20"x25"x 2" EVAPORATIVE CONDENSER (7) PREFILTERS Pump Horsepower: N/A Furnished: Pump Full Load Amps: N/A Number: Sump Heater Full Load Amps: N/A Recommended Size: Sump Heater kW: REFRIGERANT TYPE 16) FINAL FILTERS-TYPE Charge Type: R-410A Type: Factory Charge(Circuit#1): 34.8 lb Furnished: Factory Charge(Circuit#2): 32.0 lb Number: Recommended Size: PREFILTERS Furnished: Number: Recommended Size: Notes: 1.LOAD 1=Current of the largest motor(compressor or fan motor);LOAD 2=Sum of the currents of all remaining motors;LOAD 3=Current of electric heaters LOAD 4=Control Power Transformer(20-40 and 24-48 ton units add 3 FL amps for wire sizing formula,50-75 and 59-89 ton units add 6 FL amps) 2.For Electric Heat MCA,MOP,RDE values,calculate for both cooling and heating modes.(When determining LOADS,the compressors do not operate when the unit is in heating mode)(On 70-89 ton single source units,heating Load 4=12 amps on 200,230 volt units and 9 amps on 460,575 volt units) 3.If selected Max Over Cur is less than the Min Clr Amp,then select the lowest maximum fuse size which is equal to or larger than the Min Cir Amp,provided the selected fuse size does not exceed 800 amps. 4.If the selected Recommended Dual Element fuse size is greater than the selected Max Over Cur Protection value,then select the Recommended Dual Element fuse size value to equal the Max Over Protection value. 5.Compressor KW atAHRI rating conditions of 80/67-95 6.Refrigerant charge is an approx.value.For a more precise value,see unit nameplate and service instructions. 7.Sump Heater is an optional feature. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 12 of 24 Others Durham AWWTF 5020 AC Replacement September 11,2018 Fan Curve -Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 55 ton DW DDP 3011DPLA01FN UrgtSze. 20.0 sn vp OperatngArlow:18000 00 cfm _ / Operatng Safic Fiessure,336 in H2O %dN0 Operatng RRvk 144200 /60 Gperafng Sake Horse Rower 16 00 bhp 17.5 2500 RRM Wide:0.00 — J Design Tenp,8000 F 70%WO Date 9/11/18 - 2400RPM ON 15.0- AIIIIIP4ejh 230 RF0 C - 2200 RPM Illk r 7CO44 N �� _ U i:r Tt VIII �i 1114. - 700 RM -'.1 I m•N••...-401 I I PI a I IS PA I IL a5 :: = . — N - 7600 RPM u,ill 1511•: 90%NO - 1400 RFM `_ 1300 RPM i— -.AiW4*IP 11.1 - 1200 RPM Aliftelippr, - 1100 RPM 1000 RFM 25 ' ` 0.0 0 5000 10000 15000 23000 25000 30000 35000 40000 PirfloN(cfm) 63Hz 125Hfz 250f z 500Hz 1 kHz 2 kHz 4 kHz 8 kHz Cuba"Noise: -1 -1 -1 -1 -1 -1 -1 -1 Supply Dud: -1 -1 -1 -1 -1 -1 -1 -1 Ram Duct: -1 -1 -1 -1 -1 -1 -1 -1 FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 13 of 24 Others Durham AWWTF 5020 AC Replacement September 11,2018 Weight, Clearance & Rigging Diagram -Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 55 ton DW DDP Note: When 2 or more units are to be placed side by side,the distance between the units fv) should be increased to 150%of the recommended single unit clearance.The units should also be staggered to reduce span deflection&assure proper diffusion of exhaust air. 144" / 1 11101,00, t:t% CLEARANCE � I CLEARANCE 96" 36" 72" r 96" rt-t O O O O Icc I cc tit O O U .. �- y II 96" I � CLEARANCE RIGGING AND CLEARANCE AIR COOLED DRAWING FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page '14 of 24 Others Durham AWWTF 5020 AC Replacement September 11,2018 Weight, Clearance & Rigging Diagram -Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 55 ton DW DDP 194 5/16" _, - 29" "Z'I.&--=I."\:1 Iliiiiii -.,1\ 59) tiiiiii liiiiil) s Il(lflr\• i7Dl) Illli •ii)))) I, Illllii% illi))) lll1l11 • till) y X Center of Gravity X: 17.24 ft Point load X location 1: 4.000 in Center of Gravity Y: 4.01 ft Point load X location 2: 101.000 in Point load X location 3: 187.000 in Point Load 1: 646.0 lb Point load X location 4: 274.000 in Point Load 2: 760.5 lb Point load X location 5: 370.000 in N Point Load 3: 750.8 lb Point load X location 6: N/A Point Load 4: 865.4 lb Point load X location 7: N/A Point Load 5: 843.8 lb Point load X location 8: N/A Point Load 6: 958.3 Ib Point load X location 9: N/A Point Load 7: 937.8 Ib Point load X location 10: N/A Point Load 8: 1052.4 Ib Point load Y location 1: 4.000 in Point Load 9: 1041.6 IbPoint load Y location 2: 87.000 in 111111 J� PointLoad10: 1156.1 Ib` TlWh9012.8 Ib 0,0 ` �� iilli Added Weight 1.Double wall: 131 \`\ U Notes: \ 1.The actual weight is stamped on the unit nameplate. I IP 2.The weight shown represents the typical unit operating weight for the configuration selected. I Estimated at+/-10%of the nameplate weight.. 3.Add weight to the total unit weight. 4.Design Special weights are not displayed.Any weight added through COD(Custom Order Design) will not be accounted in the+/-10%estimate 5.When 2 or more units are to be placed side by side,the distance between the units should be increased to 150%of the recommended single unit clearance.The units should also be staggered to reduce span deflection&assure proper diffusion of exhaust air. — 194 5/16" 29" 96" 1 PL 2,X1 PL 4,X2 PL 6,X3 PL 8,X4 PL 10,X5 iiiiii((''•?iiiii) illi'•!?jiiii) \" _,./ v.s_;, ltAi( still)) P ((lilt•bll)II) _` mit ,!Pull) 1111111•ttlll91 _/ , ••-3',11 Y Q_ PL 1,X1 PL 3,X2 PL 5,X3 PL 7,X4 PL9,X5 X CENTER OF GRAVITY AND INSTALL WEIGHT X-Y POINTS AIR COOLED DRAWING FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 15 of 24 Others Durham AWWTF 5020 AC Replacement September 11,2018 Accessory -Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 55 ton DW DDP WARNING /\ AVERTISSEMENT A\ ADVERTENCIA HAZARDOUS VOLTAGE! TENSION DANGEREUSE! iVOLTAJE PELIGROSO! DISCONNECT ALL ELECTRIC POWER COUPER TOUTES LES TENSIONS ET DESCONECTE TODA LA ENERGIA ELECTRICA, INCLUDING REMOTE DISCONNECTS OUVRIR LES SECTIONNEURS A DISTANCE, INCLUSO LAS DESCONEXIONES REMOTAS Y AND FOLLOW LOCK OUT AND TAG PUIS SUIVRE LES PROCEDURES DE SIGA LOS PROCEDIMIENTOS DE CIERRE Y PROCEDURES BEFORE SERVICING. VERROUILLAGE ET DES ETIQUETTES AVANT ETIQUETADO ANTES DE PROCEDER AL INSURE THAT ALL MOTOR TOUTE INTERVENTION. VERIFIER QUE TOUS SERVICIO.ASEGURESE DE QUE TODOS CAPACITORS HAVE DISCHARGED LES CONDENSATEURS DES MOTEURS SONT LOS CAPACITORES DEL MOTOR HAYAN STORED VOLTAGE. UNITS WITH DECHARGES. DANS LE CAS D'UNITES DESCARGADO EL VOLTAJE ALMACENADO. VARIABLE SPEED DRIVE,REFER COMPORTANT DES ENTRAINEMENTS A PARA LAS UNIDADES CON EJE DE TO DRIVE INSTRUCTIONS FOR VITESSE VARAIBLE,SE REPORTER AUX DIRECCION DE VELOCIDAD VARIABLE, CAPACITOR DISCHARGE. INSTRUCTIONS DE L'ENTRAINEMENT POUR CONSULTE LAS INSTRUCCIONES PARA LA DECHARGER LES CONDENSATEURS. DESCARGA DEL CONDENSADOR. FAILURE TO DO THE ABOVE BEFORE SERVICING COULD RESULT NE PAS RESPECTER CES MESURES DE EL NO REALIZAR LO ANTERIORMENTE IN DEATH OR SERIOUS INJURY. PRECAUTION PEUT ENTRAINER DES INDICADO,PODRIA OCASIONAR LA MUERTE BLESSURES GRAVES POUVANT ETRE 0 SERIAS LESIONES PERSONALES. MORTELLES. CAUTION IMPORTANT! USE COPPER CONDUCTORS ONLY! DO NOT ENERGIZE UNIT UNTIL CHECK-OUT AND UNIT TERMINALS ARE NOT DESIGNED TO START-UP PROCEDURE HAS ACCEPT OTHER TYPES OF CONDUCTORS. BEEN COMPLETED. FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT. ATTENTION e , N'UTILISER QUE DES CONDUCTEURS EN CUIVRE! LES BORNES DE L'UNITE NE SONT PAS CONCUES POUR RECEVOIR D'AUTRES TYPES DE CONDUCTEURS. L'UTILISATION DE TOUTAUTRE CONDUCTEUR HEATING PEUT ENDOMMAGER L'EQUIPEMENT. SECTIONID PRECAUCION \ SECTION CONDENSER IUTILICE UNICAMENTE CONDUCTORES DE COBRE! LAS TERMINALES DE LA UNIDAD NO ESTAN DISENADAS PARAACEPTAR OTROS TIPOS DE CONDUCTORES. SI NO LO HACE,PUEDE OCASIONAR DANO AL EQUIPO. - ` UEVILE PREFIX LOCATION CODE CONNECT STEAM OR CIRCUIT#2 CIRCUIT#1 AREA - - --LOCATION HOT WATER VALVE AS aq ELECTRIC HEAT 200V/230V/60 HZ MAIN UNIT CONTROL --- SHOWN WHEN REQUIRED UNITS ONLY 1 INSIDE UNIT CONTROL BOX 4U15 37M HYDRONIC HEAT 36AL 117 118 119 1 1TB120R 3 2 CONDENSER SECTION I ACTUATOR I 4TB2,4S15 514 3 AIR HANDLER SECTION I I I L1 L2 L3 I I L1 L2 L3 BLK WHT 4 HEATING SECTION __ _- SPLICE SPLICE 5 EXTERNAL FIELD MOUNTED DEVICE -- -- Note: I I !I !I I' I 1111 — All wiring and components shown dashed to be I 0-) t_I I a- I I a supplied and installed by the customer in Q accordance with local electrical codes. T1 T2 I 483A 1 L1 L2 L3 L1 L2 L3 484A LINE VOLTAGE LINE VOLTAGE FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 16 of 24 Others Durham AWWTF 5020 AC Replacement September 11, 2018 Accessory -Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 55 ton DW DDP NOTES: ALL WIRING AND COMPONENTS SHOWN DASHED TO BE SUPPLIED AND INSTALLED BY THE CUSTOMER IN ACCORDANCE WITH LOCAL ELECTRICAL CODES. CUSTOMER CONNECTIONS-MAIN UNIT CONTROL(CIRCUIT#1)-ARE LOCATED IN THE CONDENSER SECTION FOR 20 THRU 75 TON UNITS. SEE CUSTOMER CONNECTION WIRE RANGE TABLE FOR ACCEPTABLE WIRE SIZES FOR CONNECTION TO MAIN UNIT TERMINAL BLOCK(1TB1/4TB2)OR DISCONNECT SWITCH(1S14/4S15). <4 I WIRES TO THE OPTIONAL STEAM AND/OR HOT WATER HEAT VALVE ARE SUPPLIED WITH THE UNIT.WIRE CONNECTIONS TO THE VALVE TO BE MADE BY THE CUSTOMER. <6 OPTIONAL 5U57 REMOTE ZONE TEMP SENSOR IS USED FOR UNOCCUPIED HEAT/COOL TEMP CONTROL SENSING. WHEN 5U69 REMOTE ZONE TEMP SENSOR IS USED,REMOVE 5U58 INTERGRAL ZONE TEMP SENSOR ATTACHED TO TERMINALS S1 AND S2. <8 WIRES USE SHIELDED TWISTED PAIR WIRE. <9 J USE SHIELDED TWISTED PAIR WIRE.WRAP SHIELDS WITH TAPE TO PREVENT CONTACT WITH GROUND. <10 REMOVE JUMPER(1TB4-15&1TB4-16)AND INSTALL HIGH DUCT TEMP T-STAT/OR FIELD SUPPLIED DEVICE. REMOVE JUMPER(1TB4-17&1TB4-18)WHEN FIELD SUPPLIED EXTERNAL AUTO/STOP SWITCH(5S67)IS INSTALLED. CHANGEOVER(5K87)AVAILABLE ONLY ON HYDRONIC HEAT UNITS OR MODULATING GAS HEAT UNITS. ALARM OUTPUT SWITCHES ON ANY MANUAL RESET DIAGNOSTIC. <14 OPTIONAL HEAT MODULE AUX.TEMP(5RT16)IS USED FOR MORNING WARM-UP CONTROL ON UNITS WITH HEATING OPTION. TERMINAL BLOCK 1TB17 AND ASSOCIATED WIRING REQUIRED WITH GBAS(1U51)OPTION. DEMAND LIMIT RELAY(5K89)TO BE PROVIDED BY CUSTOMER. < 161 VENTILATION OVERRIDE MODE CONTACTS RATED 12MA@ 24VDC MINIMUM (5K90-5K91-5K92-5K93-5K94)TO BE PROVIDED BY CUSTOMER. <7 WIRE NODES 533&534 REQUIRED WITH BAS/NETWORK COMM MODULE(1U54)OPTION. USE SHIELDED TWISTED PAIR WIRE. <18 FIELD CONNECTIONS TO DRIVE VAV BOXES FULL OPEN DURING NIGHT SETBACK MODE. < 191 15A FUSE REPLACEMENT IS REQUIRED FOR 50 THRU 60 TON-0.50 KVA TRANSFORMER WITH 200V-230V-460V OR 575V UNIT VOLTAGE. 20A FUSE REPLACEMENT IS REQUIRED FOR 50 THRU 60 TON-0.50 KVA TRANSFORMER WITH 380V OR 415V UNIT VOLTAGE. < CONTACTS RATED 12 MA @ 24VDC MINIMUM. CONNECT TO 24VAC CLASS 2 CIRCUITS ONLY. REMOVE JUMPER WHEN OPTIONAL FIELD SUPPLIED OUTSIDE AIR SENSOR (3RT3)IS INSTALLED AND THE UNIT DOES NOT HAVE ECONOMIZER. <24 FIELD SUPPLIED AND INSTALLED OCCUPIED/UNOCCUPIED CONTACTS(5K86) FOR USE ON UNITS WITHOUT REMOTE PANEL WITH NIGHT SETBACK(5U58). GBAS 0-5V OPTION CONNECTIONS. <26 GBAS 0-WV OPTION CONNECTIONS. FOR GBAS INPUTS A11-AI4,"GBAS 0-5V"REQUIRES 0-5V VDC AND"GBAS 0-WV"REQUIRES 0-10VDC. <281 "ACTIVE DIAGNOSTICS(B05)"APPEARS WITH BOTH"GBAS 0-5V"AND"GBAS 0-10V". <291 SEE FUSE REPLACEMENT TABLE ON VFD PANEL FOR VFD POWER FUSES(F40,F41,F42). <30 SWITCH A53,LOCATED ON THE VFD,MUST BE SET TO"U"(OFF). FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 17 of 24 Others Durham AWWTF 5020 AC Replacement September 11,2018 Accessory -Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 55 ton DW DDP FUSE REPLACEMENT TABLE CONDENSER FAN FUSE UNIT VOLTAGE 200 230 380 415 460 575 1F1 THRU 1F6 CLASS RK5 TIME DELAY 25A 25A 15A 15A 15A 15A CONTROL POWER FUSE I 0.25 0.30 0.50 0.75 1.00 1.50 CONTROL(1T1)TRANSFORMER RATING KVA KVA KVA KVA KVA KVA 20-30 TON 6.25A 6.25A -- 10A -- -- 40 TON 15A 20A -- 20A -- -- 1F7 50-60 TON -- -- 15A -- 20A -- CLASS CC-TYPE FNQ-R 70-75 TON -- -- -- -- 15A 20A ELECTRIC HEAT FUSE 4F19 THRU 4F36,4F46,47,48 CLASS K5 60A COMPRESSOR PROTECTION FUSE 1F44&1F45 TYPE MTH 6A TRANSFORMER CIRCUIT FUSE 1F72 THRU 1F74 TYPE FNQ-R 15A VFD PROTECTION FUSES(CLASS"r FUSES)OPTIONAL SUPPLY VFD 1 F57-1 F62,OPTIONAL EXHAUST/RETURN VFD 1 F63-1F65 UNIT FUSE 3 HP 5 HP 7.5 HP 10 HP 15 HP 20 HP 25 HP 30 HP 40 HP 50 HP _VOLTAGE RATING 200V/60/3 600V 40A 60A 80A 100A 150A 200A 225A 300A 350A N/A BELT DRIVE 230V/60/3 600V 30A 45A 70A 90A 125A 175A 200A 250A 300A N/A MOTOR 20-130 UNITS 380V/50/3 600V 15A 30A 45A 50A 90A 100A 125A 150A 200A N/A 415V/50/3 600V 15A 30A 45A 50A 90A 100A 125A 150A 200A N/A 460V/60/3 600V 15A 25A 35A 45A 60A 90A 100A 125A 150A 200A 575V/60/3 600V 15A 15A 25A 35A 50A 70A 60A 100A 125A 175A UNIT FUSE 15 HP 15 HP OPTIONAL VOLTAGE RATING 3 HP 5 HP 7.5 HP 10 HP 1K-1.6K 1.7K-2.4K 20 HP 25 HP 30 HP DIRECT DRIVE RPM RPM MOTOR 20-59 200V/60/3 600V 40A 60A 80A 100A 150A 150A 200A 225A 300A UNITS 230V/60/3 600V 25A 45A 70A 90A 125A 125A 175A 200A 250A 460V/60/3 600V 15A 25A 35A 45A 70A 60A 90A 100A 125A 575V/60/3 600V 15A 15A 25A 35A 50A 50A 70A 80A 100A UNIT FUSE 15 HP 15 HP 30 HP 30 HP VOLTAGE RATING 10HP 1K-1.6K 1.7K-2.4K 20HP 1K-1.6K 1.7-2.4K 40HP SOHP OPTIONAL RPM RPM RPM RPM DIRECTMDIVE 200V/60/3 600V 125A 175A 150A 200A 300A 150A 350A N/A MOTOR 230V/60/3 600V 95A 150A 125A 175A 250A 250A 300A N/A 60-89 TON 460V/60/3 600V 45A 70A 60A 90A 125A 125A 150A 200A 575V/60/3 600V 40A 60A 50A 70A 125A 100A 125A 175A CUSTOMER CONNECTION WIRE RANGE NOTES: UNITS WITH MAIN POWER UNITS WITH MAIN POWER A.BLOCK SIZE&DISCONNECT SIZE TERMINAL BLOCK(ALL VOLTAGES) DISCONNECT SWITCH(ALL VOLTAGES) ARE BLOCK SIZE WIRE QTY CONNECTOR WIRE RANGE DISCONNECT SIZE WIRE QTY CONNECTOR WIRE RANGE CALCULATED BY SELECTING THE 335 AMP (1) #6-350MCM 100 AMP (1) #14-1/0 SIZE Ibu AMr (t) #4-500 MCM -- --250 AMP (1) #4-350 kcmil GREATER THAN OR EQUAL TO 1.15 X 840 AMP (2) #2-600 MCM 400 AMP (1)OR #1-600 kcmil OR (SUM OF.UNIT LOADS).SEE UNIT — (2) #1-250 kcmil LITERATURE FOR UNIT LOAD VALUES. 600 AMP (2) 250-500 MCM 1000 AMP (3) 3/0-500 kcmil OPTIONAL CONVENIENCE OUTLET FUSE 200V/60/3 230V/60/3 380V/50/3 415V/50/3 460V/60/3 575V/60/3 1F55 AND 1 F56(TIME DELAY TYPE FNQ-R FUSE) 12A 10A N/A N/A 5A 4A FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 18 of 24 Others Durham AWWTF 5020 AC Replacement September 11,2018 Accessory -Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 55 ton DW DDP 0 0 0 I WARNING / AVERTISSEMENT A ADVERTENCIA HAZARDOUS VOLTAGE! TENSION DANGEREUSE! iVOLTAJE PELIGROSO! DISCONNECT ALL ELECTRIC POWER COUPER TOUTES LES TENSIONS ET DESCONECTE TODA LA ENERGIA ELECTRICA, INCLUDING REMOTE DISCONNECTS OUVRIR LES SECTIONNEURS A DISTANCE, INCLUSO LAS DESCONEXIONES REMOTAS Y AND FOLLOW LOCK OUT AND TAG PUIS SUIVRE LES PROCEDURES DE SIGA LOS PROCEDIMIENTOS DE CIERRE Y I PROCEDURES BEFORE SERVICING. VERROUILLAGE ET DES ETIQUETTES AVANT ETIQUETADOANTES DE PROCEDERAL INSURE THATALL MOTOR TOUTE INTERVENTION. VERIFIER QUE TOUS SERVICIO.ASEGURESE DE QUE TODOS CAPACITORS HAVE DISCHARGED LES CONDENSATEURS DES MOTEURS SONT LOS CAPACITORES DEL MOTOR HAYAN STORED VOLTAGE. UNITS WITH DECHARGES. DANS LE CAS D'UNITES DESCARGADO EL VOLTAJE ALMACENADO. VARIABLE SPEED DRIVE,REFER COMPORTANT DES ENTRAINEMENTS A PARA LAS UNIDADES CON EJE DE TO DRIVE INSTRUCTIONS FOR VITESSE VARAIBLE,SE REPORTER AUX DIRECCION DE VELOCIDAD VARIABLE, CAPACITOR DISCHARGE. INSTRUCTIONS DE L'ENTRAINEMENT POUR CONSULTE LAS INSTRUCCIONES PARA LA DECHARGER LES CONDENSATEURS. DESCARGA DEL CONDENSADOR. FAILURE TO DO THE ABOVE BEFORE SERVICING COULD RESULT NE PAS RESPECTER CES MESURES DE EL NO REALIZAR LO ANTERIORMENTE IN DEATH OR SERIOUS INJURY. PRECAUTION PEUT ENTRAINER DES INDICADO,PODRIA OCASIONAR LA MUERTE BLESSURES GRAVES POUVANT ETRE 0 SERIAS LESIONES PERSONALES. MORTELLES. CAUTION IMPORTANT! USE COPPER CONDUCTORS ONLY! DO NOT ENERGIZE UNIT UNTIL CHECK-OUT AND UNIT TERMINALS ARE NOT DESIGNED TO START-UP PROCEDURE HAS ACCEPT OTHER TYPES OF CONDUCTORS. BEEN COMPLETED. 5GE LAU FAILURE TO DO SO MAY CAUSE DAMAGE TO EMERGENcv EXTERNAL AUTO/STOP THE EQUIPMENT. wnv ZONE I STOP SWITCH 1 SWITCH RESET OPTION IT--0\�-1 r_b\o- ATTENTION I ZSUSI ONE I I I 10 21 I I I 11 21 I N'UTILISER QUE DES CONDUCTEURS EN I RESET I I 1 r I L- 1_J TEMP r -I r 1 CUIVRE! 1 SENSOR 435 431 434 438 I L 1 LES BORNES DE L'UNITE NE SONT PAS Y Y 1 L___ n CONCUES POUR RECEVOIR D'AUTRES TYPES 425 424 I DE CONDUCTEURS. - - I 1I L'UTILISATION DE TOUTAUTRE CONDUCTEUR a 5U57 _ 1TB4 - I I ' PEUT ENDOMMAGER L'EQUIPEMENT I REMOTE 1 O 408 -- --1 408 418 12- -1- ZONE 2D 409 -- r---1--2409 424 13- I 1 1 I TEMP I^___L__3 410 403 14---�-{- �I PRECAUCION SENSOR 1- -4 412 435 15-1-,U IUTILICE UNICAMENTE CONDUCTORES DE -s 411 431 16 - COBRE! - - rr 6 417 434 17]_ 11 1-— J --- 1 nr---T--7 413 438 18 -1 1 LAS TERMINALES DE LA UNIDAD NO ESTAN r-I-----T--8 414 437 19- -I I DISENADAS PARA ACEPTAR OTROS TIPOS DE r-r---T--9 415 537 20— I CONDUCTORES. ---4t^r -10 416 538 21---4I I _ I I I 11 425 436 22-4 SI NO LO HACE,PUEDE OCASIONAR DANO AL - - I I I I 1 I EQUIPO. I I r---I-C 5u69 a I I I 5U68 I REMOTE ZONE PANEL 4 � 38 I DEVICE PREFIX LOCATION CODE _ I _cZONE TEMP - - I 437 AREA LOCATION 1 SENSOR i I 1 INSIDE UNIT CONTROL BOX a - - 408 I_c ii ZONE TEMPI I I .. 2 CONDENSER SECTION - - 409---y-C 2 COMMON 5K8866 I�� I I I I OCCUPIED/ 2 j I 3 AIR HANDLER SECTIONL—410----C 3 SACSP UNOCCUPIED 24 HEAT 7 D--413—A I1 I I CONTACTS 4 HEATING SECTION lI,—412----C4 MODE - - - - COOL 8 D-1-414 I I 5 EXTERNAL FIELD MOUNTED DEVICE I )1 J I,_417_--y-C6GND g� I SYS ON 9 O- 415 1413---[{7 HEAT I C Jt-3(/'J']) Note: SERVICE 10D--416-A L-537 --C J1-1(+) All wiring and components shown dashed to be I l--414----C 8 COOL 5U66 supplied and installed by the customer in -C s1 GND 11 D--417—I I L- REMOTE accordance with local electrical codes. I 415----C 9 SVS ON 538 I� Jt-2(-) HUMAN L--1-CI_ INTERFACE S2 COMM(+)12 D- 418b -q03 ---C J2-1(+) MODULE I I 416---I-C10 SERVICE I 24 VAC 14 D--403 / I L-436 ---C J2-2(-) J2-3 5U58 5U59 1 REMOTE EARTH y REMOTE PANEL a PANEL I GROUND WITH NSB - FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 19 of 24 Others Durham AWWTF 5020 AC Replacement September 11,2018 Accessory -Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 55 ton DW DDP A\ WARNING AN AVERTISSEMENT A ADVERTENCIA HAZARDOUS VOLTAGE! TENSION DANGEREUSE! iVOLTAJE PELIGROSO! DISCONNECT ALL ELECTRIC POWER COUPER TOUTES LES TENSIONS ET DESCONECTE TODA LA ENERGIA ELECTRICA, INCLUDING REMOTE DISCONNECTS OUVRIR LES SECTIONNEURS A DISTANCE, INCLUSO LAS DESCONEXIONES REMOTAS Y AND FOLLOW LOCK OUT AND TAG PUIS SUIVRE LES PROCEDURES DE SIGA LOS PROCEDIMIENTOS DE CIERRE Y PROCEDURES BEFORE SERVICING. VERROUILLAGE ET DES ETIQUETTES AVANT ETIQUETADO ANTES DE PROCEDERAL INSURE THAT ALL MOTOR TOUTE INTERVENTION. VERIFIER QUE TOUS SERVICIO.ASEGURESE DE QUE TODOS CAPACITORS HAVE DISCHARGED LES CONDENSATEURS DES MOTEURS SONT LOS CAPACITORES DEL MOTOR HAYAN STORED VOLTAGE. UNITS WITH DECHARGES. DANS LE CAS D'UNITES DESCARGADO EL VOLTAJE ALMACENADO. VARIABLE SPEED DRIVE,REFER COMPORTANT DES ENTRAINEMENTS A PARA LAS UNIDADES CON EJE DE TO DRIVE INSTRUCTIONS FOR VITESSE VARAIBLE,SE REPORTER AUX DIRECCION DE VELOCIDAD VARIABLE, CAPACITOR DISCHARGE. INSTRUCTIONS DE L'ENTRAINEMENT POUR CONSULTE LAS INSTRUCCIONES PARA LA DECHARGER LES CONDENSATEURS. DESCARGA DEL CONDENSADOR-. FAILURE TO DO THE ABOVE BEFORE SERVICING COULD RESULT NE PAS RESPECTER CES MESURES DE EL NO REALIZAR LO ANTERIORMENTE IN DEATH OR SERIOUS INJURY. PRECAUTION PEUT ENTRAINER DES INDICADO,PODRIAOCASIONAR LA MUERTE BLESSURES GRAVES POUVANT ETRE 0 SERIAS LESIONES PERSONALES. MORTELLES. CAUTION IMPORTANT! USE COPPER CONDUCTORS ONLY! DO NOT ENERGIZE UNIT UNTIL CHECK-OUT AND UNIT TERMINALS ARE NOT DESIGNED TO START-UP PROCEDURE HAS ACCEPT OTHER TYPES OF CONDUCTORS. BEEN COMPLETED. FAILURE TO DO SO MAY CAUSE DAMAGE TO5K9- - THE EQUIPMENT. - _ - VENTILATION ATTENTION OVERRIDE 5K89 5K92 5RT16 — — MODEACONTACTS DEMAND VENTILATION 6 HEAT I 5K93 16 LIMIT 15 OVERRIDE I MODULE VENTILATION 16 N'UTILISER QUE DES CONDUCTEURS EN r 1 CONTACTS 21 MODE C CONTACTS AUX TEMP I 1 OVERRIDE 1 i CUIVREI L —� _T J LV,r—-iJa r'b—I�, I 14 I MODE DCONTACTS 523 524 I L -1 I ,( 4 r 1 LES BORNES DE L'UNITE NE SONT PAS 489 490 1 r CONCUES POUR RECEVOIR D'AUTRES TYPES I 527 528 L J 529 530 DE CONDUCTEURS. IJI 475 476 L I I L'UTILISATION DE TOUT AUTRE CONDUCTEUR I I I I I 1 PEUT ENDOMMAGER L'EQUIPEMENT I I TB5 is I I I 1 I -1 ass 475 12 - 1 --J I 1 PRECAUCION I 2 490 476 13-- ' � IUTILICE UNICAMENTE CONDUCTORES DE L_ 1- 3 523 528 14-J J 7 -4 524 529 15 COBRE! _..)r -1 -5 525 530 16 LAS TERMINALES DE LA UNIDAD NO ESTAN I 1--- 6 526 531 17 --7 527 532 18- DISENADAS PARAACEPTAR OTROS TIPOS DEI CONDUCTORES. r rn 1 9 550 534 20- n 1 SI NO LO HACE,PUEDE OCASIONAR DANO AL i ?3 r,-101 426 444 22---1--1 I I EQUIPO. 1 I I I I I I I I I I I I DEVICE PREFIX LOCATION CODE 525 1 I I I I I I 427 426.. _ 443 I I 531 1 _ I 526 _. AREA LOCATION J —i �l�I ---I 44 1 1 532 I INSIDE UNIT CONTROL-BOX - L� I -J 1 _...,__�. � I_ 1 I 1 1 2 CONDENSER SECTION 1 S gI 16 23 r J L� H L I 1 3 AIR HANDLER SECTION VENTILATION 1 1 ho_J I OVERRIDE 3RT3 /_,_,_1., L 4 HEATING SECTION MODE B CONTACTS I OPTIONAL 1 1 5K87 I I I -°-I I O I OUTSIDECHANGEOVER I 5 EXTERNAL FIELD MOUNTED DEVICE AIR I 21 CONTACTS I 1 VENTILATIONI 5K94 16 I SENSOR _ - 1 OVERRIDE Note: 1 I MODE E CONTACTS I All wiring and components shown dashed to be supplied and installed by the customer in 5U70 accordance with local electrical codes. REMOTE 534 533 MINIMUM POSITION ‘M"VaS I POTENTIOMETER TRACER -549 wHT 1r BLU COMMUNICATIONS 17 RED 1`-- 550 FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 20 of 24 Others Durham AWWTF 5020 AC Replacement September 11,2018 • Accessory -Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 55 ton DW DDP A\ WARNING A\ AVERTISSEMENT AN ADVERTENCIA HAZARDOUS VOLTAGE! TENSION DANGEREUSE! IVOLTAJE PELIGROSO! DISCONNECT ALL ELECTRIC POWER COUPER TOUTES LES TENSIONS ET DESCONECTE TODA LA ENERGIA ELECTRICA, INCLUDING REMOTE DISCONNECTS OUVRIR LES SECTIONNEURS A DISTANCE, INCLUSO LAS DESCONEXIONES REMOTAS Y AND FOLLOW LOCK OUT AND TAG PUIS SUIVRE LES PROCEDURES DE SIGA LOS PROCEDIMIENTOS DE CIERRE Y PROCEDURES BEFORE SERVICING. VERROUILLAGE ET DES ETIQUETTES AVANT ETIQUETADO ANTES DE PROCEDER AL INSURE THAT ALL MOTOR TOUTE INTERVENTION. VERIFIER QUE TOUS SERVICIO.ASEGURESE DE QUE TODOS CAPACITORS HAVE DISCHARGED LES CONDENSATEURS DES MOTEURS SONT LOS CAPACITORES DEL MOTOR HAYAN STORED VOLTAGE. UNITS WITH DECHARGES. DANS LE CAS D'UNITES DESCARGADO EL VOLTAJE ALMACENADO. VARIABLE SPEED DRIVE,REFER COMPORTANT DES ENTRAINEMENTSA PARA LAS UNIDADES CON EJE DE TO DRIVE INSTRUCTIONS FOR VITESSE VARAIBLE,SE REPORTER AUX DIRECCION DE VELOCIDAD VARIABLE, CAPACITOR DISCHARGE. INSTRUCTIONS DE L'ENTRAINEMENT POUR CONSULTE LAS INSTRUCCIONES PARA LA DECHARGER LES CONDENSATEURS. DESCARGA DEL CONDENSADOR. FAILURE TO DO THE ABOVE BEFORE SERVICING COULD RESULT NE PAS RESPECTER CES MESURES DE EL NO REALIZAR LO ANTERIORMENTE IN DEATH OR SERIOUS INJURY. PRECAUTION PEUT ENTRAINER DES INDICADO,PODRIA OCASIONAR LA MUERTE BLESSURES GRAVES POUVANT ETRE 0 SERIAS LESIONES PERSONALES. MORTELLES. CAUTION IMPORTANT! USE COPPER CONDUCTORS ONLY! DO NOT ENERGIZE UNIT UNTIL CHECK-OUT AND UNIT TERMINALS ARE NOT DESIGNED TO START-UP PROCEDURE HAS ACCEPT OTHER TYPES OF CONDUCTORS. BEEN COMPLETED. NO-614 - FAILURE TO DO SO MAY CAUSE DAMAGE TO 22HUMIDIFICATION NC-615 - THE EQUIPMENT. OM-616 --) ATTENTION .7> ALARM NO-448 -1 OUTPUT N'UTILISER QUE DES CONDUCTEURS EN :OM-449 _ CUIVRE! E> (24 VAC MAX) NC -450 - LES BORNES DE L'UNITE NE SONT PAS 18> VAV BOX NO-445-- CONCUES POUR RECEVOIR D'AUTRES TYPES RELAY :OM—446-—- DE CONDUCTEURS. 22 24 VAC MAX NC-447-- L'UTILISATION DE TOUT AUTRE CONDUCTEUR I PEUT ENDOMMAGER L'EQUIPEMENT. i 1TB16 PRECAUCION (- 1 507 445 12---JJ 2 508 446 13----1 IUTILICE UNICAMENTE CONDUCTORES DE 3 509 447 14---J COBRE! 4 541 448 15----J 6 542 450 16 LAS TERMINALES DE LA UNIDAD NO ESTAN 17 J DISENADAS PARA ACEPTAR OTROS TIPOS DE I - 6 543 -———— CONDUCTORES. 614 7 544 18---— 614 8 545 61519----- SI NO LO HACE,PUEDE OCASIONAR DANO AL PUEDE OCASIONAR DANO AL ----9 546 616 20-———— -10 612 21 EQUIPO. i r_-- 11 613 22 DEVICE PREFIX LOCATION CODE i I AREA LOCATION I 1 INSIDE UNIT CONTROL BOX ,(. 5U108 613 -(-) SPACE 2 CONDENSER SECTION 612 -(+) -IUMIDITYSENSOR 3 AIR HANDLER SECTION 4 HEATING SECTION -546 -NC HEAT MODE RELAY OUTPUT "---545 -CON (HYDRONIC HEAT OR MODULATING 22 5 EXTERNAL FIELD MOUNTED DEVICE " -544 -NO GAS HEAT) Note: H—-543 -NC VO All wiring and components shown dashed to be 542 -CON RELAY <22 supplied and installed by the customer in —-541 -NO OUTPUT accordance with local electrical codes. —-509 -NC DIRTY 22 --508 -COM FILTER L--507 -NO (601) \25 I 508 -(-) 0-10 VDC --509 -(*) (A01) 26 FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 21 of 24 Others Durham AWWTF 5020 AC Replacement September 11,2018 Accessory -Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 1 Tag(s): 55 ton DW DDP DANFOSS VARIABLE FREQUENCY DRIVE PROGRAMMING PARAMETERS MENU PARAMETER DESCRIPTION SETTING SET ONLY FOR 1-21 MOTOR POWER APPLICATIONS USING 3HP HIGH EFFICIENCY MOTORS SET ONLY FOR LOAD/MOTOR 1-22 MOTOR VOLTAGE 200/230V 60HZ 380/415V 50HZ APPLICATIONS 1-24 MOTOR CURRENT SET BASED ON MOTOR NAMEPLATE 1-25 MOTOR NOMINAL SPEED 1800 RPM 1-73 FLYING START ENABLED BRAKES 2-01 DC BRAKE CURRENT 0% REFERENCE/ 3-15 REFERENCE 1 SOURCE ANALOG INPUT 53<30 RAMPS 3-41 RAMP 1 RAMP UP TIME 30 SECONDS 3-42 RAMP 1 RAMP DOWN TIME 30 SECONDS LIMITS/ 4-12 MOTOR SPEED LOW LIMIT 22HZ WARNINGS 4-18 CURRENT LIMIT 100%RATED CURRENT DIGITAL 5-40[0] FUNCTION RELAY 1 NO ALARM IN/OUT 5-40[1] FUNCTION RELAY 2 RUNNING 14-01 SWITCHING FREQUENCY 4.5KHZ 14-12 FUNCTION AT MAINS DEBATE SPECIAL IMBALANCE FUNCTIONS 14-20 RESET MODE AUTOMATIC RESET X 3 14-60 FUNCTION AT OVER DEBATE TEMPERATURE FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 22 of 24 Others Durham AWWTF 5020 AC Replacement September 11,2018 Tag Data -Seismic Curb (Qty: 1) Item Tag(s) Qty B1 No Tag 1 Product Data -Seismic Curb Item: B1 Qty: 1 FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 23 of 24 Others Crystal Distribution, Inc. CDI 17560 Tyler Street NW Elk River, MN 55330 Phone:763.391.7790 CUSTOM CURB ADAPTERS Toll Free: 1.888.234.7001 CDI QUOTE #1097785 CURBS Line Quantity CDI Part # Description Tag A 1 C2-0014-3225 Straight Curb Conforming Assembled, No Pitch, 14 in New Model: SXHL50 (PARTIAL PERIMETER) ; Estimated Weight 645.85 lbs B 1 C9-0014-096-ER100 Equipment Rails Conforming Assembled, No Pitch, 14 in, Length 96 in New Model:CDI ER100 Wood Nailer; Removable Cover TRANE Attn: S*HC / S*HF C50 / 55 Tag: S*HG D50 / D55 S*HF F50 / 55 (* =E,F,L,S,X) 94 3/8" 268 1/8" 96 7/16" 73 13/16" 33 5/16" 25 13/16" 3 3/8"H ALL BRACES DROPPED 1 3/16" FROM TOP 84 1/2" RETURN SUPPLY AIR80 3/8" 95 15/16" 76 5/8" AIR 13" 7 13/16" 6" FILLER PANEL IN RA 7 1/2" SLEEPER RAIL TO BE 1 3/8 LOWER THAN CURB HEIGHT * Verify existing curb OD * Verify supply and return openings * Note any changes DIMENSIONS ARE 3RD ANGLECTION * Call with any questions AS FOLLOWS: PROJE IASAOmm, �� * Fax back if drawing is OK as is APPROVALS DATE TITLE: DRAWN: O.OLIVARES 5/4/07 TRANE CHECKED, • MOMT: ROOF CURB 17560 TYLER ST NW FILE NAME: DRAWING NO.: REV: C D tEL763K RIVE1-77R,90 MN 55330 ECO u3225: 3225 0539 (763)3917851 SCALE: 1:42 SHEET:1 OF 1 CCUSTOM CURB ADAPTERS Calculation Requirements Seismic Engineering Data: • Required: Project Locations (Address or Lat./Long. ) Mean Roof Height Unit Weight and Dimensions • Optional (These can be assumed but may be contained in the project specification) Design Code Reference Unit Center of Gravity or Corner Weights Importance Factor(Ip) Component Amplification Factor(k) Component Response Modification Factor(Rp) Spectral Acceleration (SD,SD1,Sos) Fastening Data: • Required Information: Curb Location and Attachment Material Below Curb Gauge of base frame of unit • Optional: Fasteners Size and type Wind Engineering Data: • Required: Project Locations (Address or Lat./Long. ) Building Height Unit Weight and Dimensions Topographical Factor(KJ—Is the location on the top half of a hill or on a ridge? • Optional (These can be assumed but may be contained in the project specifications) Design Code Reference Unit Center of Gravity or Corner Weights Wind Directional Factor(Kd) Velocity Pressure Exposure(KZ) Basic Wind Velocity(V) Velocity Pressure(qh) Gust Factor(G) Net Force Coefficient(Cf) Importance Factor(I) Risk Category( I, II, III & IV) Exposure Category(A-D) Fastening Data: • Required Information: Curb Location and Attachment Material Below Curb Gauge of base frame of unit • Optional: Fasteners Size and type