Loading...
Report TRANS` Submittal C\" ---)- S `030(q 1 .. I E Prepared For: Date:January 3, 2019 . HVAC Inc. i3A Ken Alcock BUILDING DIVISION Job Name: Morphe at Washington Sq Mall • 9585 SW Washington Square Road Portand, OR 97223 Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval. Product Summary Qty Product 4 Variable Air Volume Fan Powered Terminal Units The attached information describes the equipment we propose to furnish for this project,and is submitted for your approval. Product performance and submittal data is valid for a period of 6 months from the date of submittal generation. If six months or more has elapsed Chris Smith between submittal generation and equipment release,the product Trane performance and submittal data will need to be verified. It is the 7257 SW Kable Lane customer's responsibility to obtain such verification. Portland, OR 97224-7181 Phone: (503)431-2561 Email: chrisp.smith(a�trane.com J:IJOBS1124175181131Submittal Rev 0.doc Table of Contents Product Summary 1 Variable Air Volume Fan Powered Terminal Units(Items Al -A4) Tag Data 3 Product Data 3 Performance Data 4 Mechanical Specifications 5 Unit Dimensions 7 Accessory 9 Field Wiring 11 Morphe at Washington Sq Mall January 3,2019 Tag Data -Variable Air Volume Fan Powered Terminal Units (Qty:4) Item Tag(s) Qty Description Model Number Al FPVAV-1 1 VAV Fan Powered Terminal Units VSEF12 A2 FPVAV-2 1 VAV Fan Powered Terminal Units VSEF12 A3 FPVAV-3 1 VAV Fan Powered Terminal Units VSEF12 A4 FPVAV-4 1 VAV Fan Powered Terminal Units VSEF10 Product Data-Variable Air Volume Fan Powered Terminal Units All Units Series with electric heat • 06 super quiet fan 1"foil faced insulation Flanged connection 208/60/1 motor voltage Single speed motor w/SCR Standard actuator(TRIAC) Left hand controls connection Bottom access Disconnect switch Power fuse 208 volt, 3 phase Electric heater air flow switch Item: Al,A2 Qty: 2 Tag(s): FPVAV-1, FPVAV-2 12"(305 mm) 12.0 kilowatt 2 stages of heat-equal increments 24vac magnetic contactors Item: A3 Qty: 1 Tag(s): FPVAV-3 12"(305 mm) 6.0 kilowatt 1 stage of heat SCR Electric Heat Control Item: A4 Qty: 1 Tag(s): FPVAV-4 10"(254 mm) 4.0 kilowatt 1 stage of heat SCR Electric Heat Control Note: FPVAV-4 was upsized to a 10"box because the scheduled 03SQ fan is only available in 115V/lph and requires a neutral leg. The 10" box is required to accommodate the smallest 208V/lph fan, 06SQ. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 3 of 13 Others Morphe at Washington Sq Mall January 3,2019 Performance Data -Variable Air Volume Fan Powered Terminal Units Tags FPVAV-1, FPVAV-3 FPVAV-4 FPVAV-2 Design cooling airflow(cfm) 1820 1530 700 Min cooling airflow(cfm) 1345 760 615 Valve heating airflow(cfm) 1345 1530 700 Cooling inlet diameter(in) 12.000 12.000 10.000 Cooling inlet velocity(ft/min) 2317 1948 1283 APD @ cooling airflow(in H2O) 0.201 0.102 0.010 Fan airflow(cfm) 1820 1530 700 Downstream SP(in H2O) 0.250 0.250 0.250 Fan TSP (in H2O) 0.254 0.253 0.251 %of fan range (%) 51.00 36.00 1.00 Fan power(hp) 0.500 0.500 0.500 Plenum EAT(F) 55.00 55.00 55.00 Primary EDB(F) 80.00 80.00 80.00 Operating weight(Ib) 136.0 136.0 135.0 Unit heating a. : -- = e 1530 700 Coil heating capacity(MBh) 40.98 20.49 13.66 Room heat loss (MBh) 10.78 5.93 7.00 Room heating setpoint(F) 88.77 88.77 88.77 Coil EAT(F) 73.48 80.00 80.00 Unit LAT(F) 94.23 92.34 97.98 Coil LAT(F) 94.23 92.34 97.98 Full load amps (A) 37.91 21.25 15.70 Min circuit ampacity(A) 47.39 26.57 19.63 Max overcurrent protection (A) 50.00 30.00 20.00 Electric heater kW(kW) 12.00 6.00 4.00 FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 4 of 13 Others Morphs at Washington Sq Mall January 3,2019 Mechanical Specifications-Variable Air Volume Fan Powered Terminal Units Item: Al -A4 Qty: 4 Tag(s): FPVAV-1, FPVAV-2, FPVAV-3, FPVAV-4 General Unit Information Casing -The unit casing is 22 gauge galvanized steel. Outlet duct connection is flanged. Total metal encapsulation of all insulation edges. Hanger Brackets provided. Side access is provided. Filter-A filter is provided on the plenum inlet. Agency Listing -UL and Canadian UL listed as environmental air terminal unit. UL Control#9N65. All Trane terminal units are AHRI 880-98 certified. General Unit Clearance Leave a minimum of 36"on control box side of unit for adequate service access.Allow at least 12"on remaining sides for unit clearance.A minimum of one and one half duct diameters of straight duct work, upstream of the air inlet connection, should be present for optimum airflow measurement performance. Upstream duct work should be the same diameter as the primary inlet connection. Electrical Installation Information For electrical connections, consult field wiring section &equipment IOM. IMPORTANT: Field Wiring Most fan-powered VAV terminal units with electric reheat require a neutral connection from building power, however, some configurations do not. In order to prevent a building wiring issue once the boxes are installed,the wiring diagrams and field wiring installation for each unit MUST be checked to determine whether the neutral is required or not required. 1" [25.4 mm] Foil -Faced Insulation The interior surface of the unit is acoustically and thermally lined with 1", 1.5 lb/cu.ft density glass fiber with a foil facing. The insulation is UL listed and meets NFPA-90A, UL 181 standards, and bacteriological standard ASTM C 665. All insulation options will meet the 25/50 smoke developed and flame spread rating (per ASTM E 84 and UL 723 and CAN/ULC S102-M88) Meets NFPA-90B. The insulation R-value is 4.1.All cut edges of insulation are completely _ encapsulated in metal to prevent erosion. Air Valve& Fan Description (Parallel)(Series) The air inlet connection is an 18 gauge galvanized steel cylinder sized to fit standard round duct.A multiple point, averaging flow sensing ring is provided with balancing taps for measuring airflow within+/-5%of unit cataloged airflow. Also provided with each unit is a calibration chart indicating airflow versus flow sensor pressure differential.The damper blade is constructed of a closed cell foam seal mechanically locked between two 22 gauge galvanized steel disks. The damper blade assembly is connected through a cast zinc stub axle and shaft supported by self lubricating bearings.The shaft is cast with a damper position indicator. The valve assembly includes a mechanical stop to prevent over stroking. Air valve leakage<1%at 4". 1206SQ Air Valve/Fan Combination Size(Series) 12" Inlet designed for up to 2000.0 cfm. Fan is 2650.0 cfm for Std Motor and 2500.0 cfm for ECM Motor. 1006SQ Air Valve/Fan Combination Size(Series) 10" Inlet designed for up to 1400.0 cfm. Fan is 2650.0 cfm for Std Motor and 2500.0 cfm for ECM Motor. Fuse Any electric heat unit with a calculated MCA greater or equal to 30 will have a fan fuse provided. Electric Heat Coil Factory provided and mounted. Resistance open-type heater, a disc-type automatic thermal primary safety device and manual reset load thermal secondary device. Heater element material is nickel-chromium. The heater terminal box is provided with knockouts for customer power supply. Terminal connections are plated steel with ceramic or phenolic insulators. All fan-powered units with electric reheat are single-point power connections. Magnetic Contactor An electric heater 24 volt contact for use with Direct Digital Control (D.D.C.) or Analog Electronic VAV Controls. Transformer The 50 VA transformer is factory mounted in the fan control box to provide 24 VAC for controls. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 5 of 13 Others Morphe at Washington Sq Mall January 3,2019 SCR-Variable Fan Speed Control Switch The SCR speed control device allows the operator infinite fan speed adjustment so the fan output may be modified to achieve exact CFM requirements. Power Fuse Fuses provided on all energized lines of incoming power to interrupt circuit overcurrent conditions. SCR Modulated Electric Heat_SCRP An SCR electric control device for use with FM00(Customer Furnished Controls) or ENCL(Enclosure only No controls)/ENON (No Enclosure& No controls) controls. The SCR is a substitute for magnetic contactors and a RoHS compliant alternative to Mercury contactors. A 24VDc Power Supply is included with this option to power the SCR _ Module. The SCR allows the operator Modulating heat adjustment for precise, silent control of zone temperature. Power Disconnect Switch (for VSEF&VPEF) A factory provided interlocking door disconnect switch located on the electric heater control panel. Airflow Switch An air pressure device designed to disable the heater when the unit fan is off. Flanged Connection A rectangular opening on the unit discharge to accept a 90 degree flanged duct work connection. Standard D.D.C. Floating Point Actuator 18GA wires are used. 3.0 VA, 1.5W, 24 VAC, 50/60 Hz. Quarter turn control actuator with linkage release button. Actuator has a constant drive rate independent of load, a rated torque of 35 in-Ib, a 90-second drive time and is non-spring return. Travel is terminated by end stops at fully opened and closed positions.An integral magnetic clutch eliminates motor stall. An integral 3 screw terminal block is provided for field wiring. Operating temperature 32.0 F to 125.0 F. Controls Option DDOO Electric Actuator Only(Trane Actuator Only) Supply air valve electric actuator with field mounting of unit controller. Electric actuator is a floating point controller and uses three wires. Three screw terminal block is integral to actuator body. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 6 of 13 Others Morphe at Washington Sq Mall January 3,2019 Unit Dimensions -Variable Air Volume Fan Powered Terminal Units Item: Al -A3 Qty: 3 Tag(s): FPVAV-1, FPVAV-2, FPVAV-3 Unit Size VSEF1206SQ Nominal 12"Dia.x 4"Depth Valve Size&Depth _ Nominal 06SQ Fan _ Fan Size • Filter Size 20"x 20"x 1"(QTY 1) 30 LOW VOLTAGE CONTROL BOX\H-5" 4"*1 12" 1>1 1. n 13 Ilk :4:0". AIRFLOW 16 1/2" , L NOTES: 1 40" 1.Allow a minimum 6"plenum inlet clearance for un-ducted installations. FILTER- '' Camlock Bottom Access 2.Filter is secured in filter frame located in unit Airflow See Accessory sheet Plenum inlet. AIRFLOW_� I for exact location 3. For Motor access,remove bottom screws on PLENUM INLET and dimensions.ons. hanger brackets to slide panel as shown in drawing. so" H 4. See Installation Documents for exact hanger ,� bracket location. L 5.Air valve centered between top&bottom panel. x m ELECTRIC 6. Heating coil un-insulated. External insulation may 17" z HEATER PANEL SLIDES be field supplied and installed as required. FOR MOTOR ACCESS it 7.All high&low voltage controls have same-side ur NEC jumpback clearance. 8.Allow 48"of straight duct downstream of L unit before first runout and inside of the duct should be equal discharge size. 6" TOP VIEW 9. Terminal box access door is side hinged.Allow for AIRFLOW clearance. DISCHARGE OUTLET 10.A 4 wire power supply required for 480&575 < 25" > single point connection units. 11. Attenuator option not available with this unit layout. �-1 W 12. Cam Lock Bottom Access Door-22"x 26". d !a! g^ 26 GA galvanized steel with a 1"thick insulation encapsulated with a 26 GA liner. 13. Optional Bottom Access is centered 3" from discharge end on the bottom of the unit. 14" 211/2" Approximate Dry Weight 136.0 Ib Weights reflected may vary 19" >< v 51/2' ±5.0 lb based upon options selected. DISCHARGE VIEW FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 7 of 13 Others • Morphe at Washington Sq Mall January 3,2019 Unit Dimensions -Variable Air Volume Fan Powered Terminal Units Item: A4 Qty: 1 Tag(s): FPVAV-4 Unit Size VSEF1006SQ Nominal 10"Dia.x 4"Depth Valve Size&Depth Nominal 06SQ Fan Fan Size Filter Size 20"x 20"x 1"(QTY 1) < 3p^ > LOW VOLTAGE CONTROL BOX\H-S"G<4" 1-10"—E>1 !' n F. .4.y 161/2" ' L NOTES: 1 40" 1.Allow a minimum 6"plenum inlet clearance for un-ducted installations. FILTER iC''° 2.Filter is secured in filter frame located in unit Airflow Camlock Bottom Access Plenum inlet. See Accessory sheet AIRFLOW c— I for exact location 3. For Motor access,remove bottom screws on PLENUM INLET and dimensions. hanger brackets to slide panel as shown in drawing. _ 50" I T4. See Installation Documents for exact hanger v bracket location. L A 5.Air valve centered between top&bottom panel. x m ELECTRIC 6. Heating coil un-insulated. External insulation may 17" z HEATER PANEL SLIDES be field supplied and installed as required. FOR MOTOR ACCESS 7.All high&low voltage controls have same-side re w NEC jumpback clearance. 1 8.Allow 48"of straight duct downstream of LoJ unit before first runout and inside of the duct should be equal discharge size. 6" TOP VIEW 9. Terminal box access door is side hinged.Allow for AIRFLOW clearance. DISCHARGE OUTLET 10.A 4 wire power supply required for 480&575 25" single point connection units. 11. Attenuator option not available with this unit layout. W 12. Cam Lock Bottom Access Door-22"x 26". U U 3" 26 GA galvanized steel with a 1"thick insulation encapsulated with a 26 GA liner. 13. Optional Bottom Access is centered 3" from discharge end on the bottom of the unit. 14" 211/2" I Approximate Dry Weight 135.0 lb Weights reflected may vary 19" > 51/2" ±5.0 lb based upon options selected. DISCHARGE VIEW FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 8 of 13 Others • Morphe at Washington Sq Mall January 3,2019 Accessory -Variable Air Volume Fan Powered Terminal Units Item: Al -A4 Qty: 4 Tag(s): FPVAV-1, FPVAV-2, FPVAV-3, FPVAV-4 Notes: 1.When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance. VSCF and VSEF maximum Minimum 1-row coil maximum -.- - - -.-. 2-row coil maximum Pa In,wg Series D6SQ—PSG 1 t--- i —I— I',..- - ''1N 199 0.80 _ ; '5% 174 0.70 150 0.60 J ,„ , ' ,� 125 0.50 z '',., j y 100 0.40 . F... (1) k " : t 75 0.30 1 4'. ---� 4 ' r t3 50 0.20 >~., ;' ( P �, ,t �e ', 25 0.10 - # 4 . , l at 7 0 0.00 k 1 ...... 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2600 et m 189 283 378 472 566 661 755 550 944 1038 1133 1227 1322 Ua Airflow FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 9 of 13 Others • Morphe at Washington Sq Mall January 3,2019 Accessory -Variable Air Volume Fan Powered Terminal Units Item: Al -A4 Qty:4 Tag(s): FPVAV-1, FPVAV-2, FPVAV-3, FPVAV-4 BOTTOM ACCESS DIMENSIONAL DATA Bottom Access Bottom Access Fan Size Opening Size Cam Lock C Ax B Cover Size 16.00"x 16.00" 18.00"x 18.00" 3.00" 02SQ (406mm x 406mm) (457mm x 457mm) (76 mm) 03SQ 16.00"x 16.00" 18.00"x 18.00" 4.00" 04SQ (406mm x 406mm) (457mm x 457mm) (101 mm) O6SQ 20.00"x 24.00" 22.00"x 26.00" 5.00" 075Q (508mm x 609mm) (559mm x 660mm) (127 mm) uI_ Primary Airflow Flow Rigg Tubing 1�1 Air Valve I I I _ I I I I � P I I 1 I A r 1 1 BOTTOM ACCESS b C Lo- SEE CHART 0 C B Airflow Plenum Inlet —1 I —1 L I I J � TOP VIEW ( I (76 mm) o Panel slides Fitter Airflow for Motor access Discharge Outlet FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 10 of 13 Others • Morphe at Washington Sq Mall January 3,2019 Field Wiring -Variable Air Volume Fan Powered Terminal Units Item: Al -A4 Qty:4 Tag(s): FPVAV-1, FPVAV-2, FPVAV-3, FPVAV-4 208 Volt,3 Phase L3 L2 L1 I I I I � I I I I T • • • • Heater Control Wring WARNING HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH A\ CAUTION USE COPPER CONDUCTORS ONLY! UNIT TERMINALS ARE NOT DESIGNED Customer Notes: TO ACCEPT OTHER TYPES OF CONDUCTORS. 1. Factory installed. FAILURE TO DO SO MAY CAUSE — — — — Optional or installed by others. DAMAGE TO THE EQUIPMENT. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 11 of 13 Others Morphe at Washington Sq Mall January 3,2019 Field Wiring -Variable Air Volume Fan Powered Terminal Units Item: Al,A2 Qty: 2 Tag(s): FPVAV-1, FPVAV-2 NOTES' i. FACTORY WIRING FIELD WIRING —--—--—--—OPTIONAL OR ALTERNATE WIRING 2 ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE(NEC),STATE AND LOCAL REQUIREMENTS. 3.I CAPACITOR IS INSTALLED ON FAN HOUSING. FROM HEATER /\ TERMINAL BOX 4.I DISCONNECT SWITCH,OPTIONAL FUSE AND MOTOR SPEED CONTROL ACTUATORS ARE LOCATED ^ ` EXTERNAL TO CONTROL BOX. < 5 CLASS2CONTROLS TRANSFORMER PROVIDED IN ALL UNITS. BK 666//� //W\/ I 0 .._J. /DISCONNECT BK666666 W < I MOTOR SPEED CTRL 0BK MOTOR W M o W 3"-S \W W BR0 \o TERMINAL BLOCK 0 0 BL o 24V O V < B I < 3.I // a)� BRJ W TRANSFORMER 0 o CAPACITOR I- I < 4I FUSE 0 �__ FAN RELAY w/24VAC COIL o ils 2 4 CCW(OPEN) 24VAC DAMPER COMMON M Damper Actuator CONTROL Load:4 VA CW(CLOSE)_-- Factory Installed 1 3 FAN FAN RELAY w24VAC COIL CONTROL BR ON/OFF Y(GND) TO VAV CONTROLLER 24VAC POWER BL(24VAC) ELECTRIC 1ST STAGE HEAT URN OPTIONAL HEATER COM BR STAGED HEATER CONTRACTORS ARE 24 VAC 12VA MAX/COIL(MERCURY CONTACTORS). CONTROL ELECTRIC 10VA MAX/COIL(MAGNETIC CONTACTORS). 2ND STAGE HEAT --__MO HEATER 3RD STAGE HEAT RED FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 12 of 13 Others Morphe at Washington Sq Mall January 3,2019 Field Wiring -Variable Air Volume Fan Powered Terminal Units Item: A3,A4 Qty: 2 Tag(s): FPVAV-3, FPVAV-4 NOTES. 1. FACTORY WIRING FIELD WIRING —--—--—--—OPTIONAL OR ALTERNATE WIRING 2 ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE(NEC)STATE AND LOCAL REQUIREMENTS. FROM HEATER < 3 CAPACITOR IS INSTALLED ON FAN HOUSING. TERMINAL BOX DISCONNECT SWITCH,OPTIONAL FUSE AND MOTOR SPEED CONTROL ACTUATORS ARE LOCATED EXTERNAL TO CONTROL BOX. < 5. CLASS 2 CONTROLS TRANSFORMER PROVIDED IN ALL UNITS. BK / /W�/ / ( /DISCONNECT BK ddd /DISCONNECT —I MOTOR SPEED CTRL o BK MOTOR • \ :i1i) W W \?J TERMINAL BLOCK O O BL 24V Y < 3. I(o BR •v TRANSFORMER 0 o CAPACITOR I' FUSE FAN RELAY w/24VAC COIL 0110 2 4 CCW(OPEN) ^ 24VAC COMMON �� \ Damper DAMPER U Actuator CONTROL Load:4 VA CW(CLOSE) - Factory Installed FAN RELAY w/24VAC COIL R GND 1 FAN CONTROL BR 24VAC ON/OFF TO VAV Y(GND) CONTROLLER 24VAC POWER BL(24VAC) BL(24VAC) Y(GND) OPTIONAL THE ELECTRIC HEATER 0-10VDC MODULATION ELECTRIC SCR CONTROL SIGNAL MUST BE<0.2VDC HEATER DC COM GRY ELECTRIC TO GUARANTEE HEAT IS OFF. CONTROL 0-10VDC ORN HEATER FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 13 of 13 Others RECEIVED Printed Date: 01/07/2019 IiGREENHECK Job: Morphe TI Store #040 Building Value in Air. iA ' 2019 Mark: EF-1 GIT-v ' TIGARD Model: SP-A190 —14.625–,-- --14.875 1{ D �+ P-A190 j 1 f Ceiling Exhaust Fan 5.5 = c 13.25 Standard Construction Features: II -Corrosion resistant galvanized steel scroll and housing-Sound absorbing 1 insulation-White designer non-yellowing grille-Outlet duct collar with integral spring loaded backdraft damper-Double inlet forward curved wheel-Plug type disconnect-Adjustable mounting brackets-Field rotatable discharge Selected Options &Accessories: —13.25-- -- 10.625 -- Motor with Thermal Overload r_81 — Motor with CSA Approval Motor with 40 Degree C Ambient Temperature Motor rated for continuous use MOUNTING UL/cUL 507 Listed-Electric Fan BRACKET9 6 [ .. 1 Solid State Speed Control,6 Amp,Shipped Loose Designer Grille Polypropylene Wheel Material Energy Star Rated Can Be Used to Comply with:ASHRAE 62.2,California Title 24,and Washington State Energy Code Dimensional Quantity 1 Weight w/o Ace's(Ib) 17 Weight w/Acc's(Ib) 18 0.28 Performance 0 24 .- , - Requested Volume(CFM) 140 Actual Volume(CFM) 140 0.20 - Total External SP(in.wg) 1 0.1 a� \ ,' ' 1 3 Fan RPM 998 C 0.16 • : . *FLA(A) 1.3 f e Elevation(ft)ft . 108 I 20.12 ._ \ Airstream Temp.(F) 70 2 ;•"b' 0_ Air Density(Ib/ft3) 1 0.075 c) � I -0 0.08 Sones 0.5 co 0.04 ° \� 4° Ss.. -,-toll - . _ t 0.00 -.._._ \ .. 0 20 40 60 80 100 120 140 160 180 Motor Volume(CFM) Motor Mounted Yes 0 Operating point at Total External SP **Input Watts(W) 18 Fan curve Voltage/Cycle/Phase 115/60/1 - -..-.-.System curve Enclosure ODP Notes: All dimensions shown are in units of in. MCC' *FLA is approximate and will vary slightly with the motor. WORIDWIDE Sones-calculated using AMCA 301 at 5 ft oERTInED **Wattage is approximate and may vary between motors. MIME sound mo.EmenT 4. a*o mrennnnnnm.ine. ' Generated by:jfisher@johnsonair.com CAPS 4.28.1333 Y:\AaronCormack\Secured Jobs 2019\M-R\Morphe Store#040.gfcj Page 2 of 3 Printed Date: 01/07/2019 GREENHECK Job: Morphe TI Store #040 Building Value in Air. Mark: EF-1 Model: SP-A190 AMCA amca WORIDWIDE CERTIFIED RRTIRGS sounD RIR ane PEKORAIAACE RIR to MOVEMERT 4i ARD CORTROI RSSOCIRTIOR QO, IRTERRRTIORnL. inc. AMCA Licensed for Sound and Air Performance Without Appurtenances (Accessories). Power rating (BHP/kW) does not include transmission losses. Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings include the effects of an inlet grille and backdraft damper. Speed (RPM) shown is nominal. Performance is based on actual speed of test. The watt ratings shown are at free air. The sound ratings shown are for loudness values in spherical sones at 5 ft. (1.5m) in a spherical free field calculated per Annex B of AMCA 311. Values shown are for installation type B: ducted outlet spherical sone levels. The AMCA Certified Ratings Seal applies to sone ratings only. The AMCA licensed air and/or sound performance data has been modified for installation, appurtenances or accessories, etc. not included in the certified data. The modified performance is not AMCA licensed but is provided to aid in selection and applications of the product. Generated by:jfisher@johnsonair.com CAPS 4.28.1333 Y:\AaronCormack\Secured Jobs 2019\M-R\Morphe Store#040.gfcj Page 3 of 3