Report TRANS` Submittal C\" ---)- S `030(q 1
.. I E
Prepared For: Date:January 3, 2019
. HVAC Inc. i3A
Ken Alcock BUILDING DIVISION
Job Name:
Morphe at Washington Sq Mall
•
9585 SW Washington Square Road
Portand, OR 97223
Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval.
Product Summary
Qty Product
4 Variable Air Volume Fan Powered Terminal Units
The attached information describes the equipment we propose to
furnish for this project,and is submitted for your approval.
Product performance and submittal data is valid for a period of 6 months
from the date of submittal generation. If six months or more has elapsed
Chris Smith between submittal generation and equipment release,the product
Trane performance and submittal data will need to be verified. It is the
7257 SW Kable Lane customer's responsibility to obtain such verification.
Portland, OR 97224-7181
Phone: (503)431-2561
Email: chrisp.smith(a�trane.com
J:IJOBS1124175181131Submittal Rev 0.doc
Table of Contents
Product Summary 1
Variable Air Volume Fan Powered Terminal Units(Items Al -A4)
Tag Data 3
Product Data 3
Performance Data 4
Mechanical Specifications 5
Unit Dimensions 7
Accessory 9
Field Wiring 11
Morphe at Washington Sq Mall January 3,2019
Tag Data -Variable Air Volume Fan Powered Terminal Units (Qty:4)
Item Tag(s) Qty Description Model Number
Al FPVAV-1 1 VAV Fan Powered Terminal Units VSEF12
A2 FPVAV-2 1 VAV Fan Powered Terminal Units VSEF12
A3 FPVAV-3 1 VAV Fan Powered Terminal Units VSEF12
A4 FPVAV-4 1 VAV Fan Powered Terminal Units VSEF10
Product Data-Variable Air Volume Fan Powered Terminal Units
All Units
Series with electric heat
• 06 super quiet fan
1"foil faced insulation
Flanged connection
208/60/1 motor voltage
Single speed motor w/SCR
Standard actuator(TRIAC)
Left hand controls connection
Bottom access
Disconnect switch
Power fuse
208 volt, 3 phase
Electric heater air flow switch
Item: Al,A2 Qty: 2 Tag(s): FPVAV-1, FPVAV-2
12"(305 mm)
12.0 kilowatt
2 stages of heat-equal increments
24vac magnetic contactors
Item: A3 Qty: 1 Tag(s): FPVAV-3
12"(305 mm)
6.0 kilowatt
1 stage of heat
SCR Electric Heat Control
Item: A4 Qty: 1 Tag(s): FPVAV-4
10"(254 mm)
4.0 kilowatt
1 stage of heat
SCR Electric Heat Control
Note: FPVAV-4 was upsized to a 10"box because the scheduled 03SQ fan is only available in 115V/lph and requires a
neutral leg. The 10" box is required to accommodate the smallest 208V/lph fan, 06SQ.
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 3 of 13
Others
Morphe at Washington Sq Mall January 3,2019
Performance Data -Variable Air Volume Fan Powered Terminal Units
Tags FPVAV-1, FPVAV-3 FPVAV-4
FPVAV-2
Design cooling airflow(cfm) 1820 1530 700
Min cooling airflow(cfm) 1345 760 615
Valve heating airflow(cfm) 1345 1530 700
Cooling inlet diameter(in) 12.000 12.000 10.000
Cooling inlet velocity(ft/min) 2317 1948 1283
APD @ cooling airflow(in H2O) 0.201 0.102 0.010
Fan airflow(cfm) 1820 1530 700
Downstream SP(in H2O) 0.250 0.250 0.250
Fan TSP (in H2O) 0.254 0.253 0.251
%of fan range (%) 51.00 36.00 1.00
Fan power(hp) 0.500 0.500 0.500
Plenum EAT(F) 55.00 55.00 55.00
Primary EDB(F) 80.00 80.00 80.00
Operating weight(Ib) 136.0 136.0 135.0
Unit heating a. : -- = e 1530 700
Coil heating capacity(MBh) 40.98 20.49 13.66
Room heat loss (MBh) 10.78 5.93 7.00
Room heating setpoint(F) 88.77 88.77 88.77
Coil EAT(F) 73.48 80.00 80.00
Unit LAT(F) 94.23 92.34 97.98
Coil LAT(F) 94.23 92.34 97.98
Full load amps (A) 37.91 21.25 15.70
Min circuit ampacity(A) 47.39 26.57 19.63
Max overcurrent protection (A) 50.00 30.00 20.00
Electric heater kW(kW) 12.00 6.00 4.00
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 4 of 13
Others
Morphs at Washington Sq Mall January 3,2019
Mechanical Specifications-Variable Air Volume Fan Powered Terminal Units
Item: Al -A4 Qty: 4 Tag(s): FPVAV-1, FPVAV-2, FPVAV-3, FPVAV-4
General Unit Information
Casing -The unit casing is 22 gauge galvanized steel. Outlet duct connection is flanged.
Total metal encapsulation of all insulation edges. Hanger Brackets provided. Side access is provided.
Filter-A filter is provided on the plenum inlet.
Agency Listing -UL and Canadian UL listed as environmental air terminal unit. UL Control#9N65. All Trane terminal
units are AHRI 880-98 certified.
General Unit Clearance
Leave a minimum of 36"on control box side of unit for adequate service access.Allow at least 12"on remaining sides for
unit clearance.A minimum of one and one half duct diameters of straight duct work, upstream of the air inlet connection,
should be present for optimum airflow measurement performance. Upstream duct work should be the same diameter as
the primary inlet connection.
Electrical Installation Information
For electrical connections, consult field wiring section &equipment IOM.
IMPORTANT: Field Wiring
Most fan-powered VAV terminal units with electric reheat require a neutral connection from building power, however,
some configurations do not. In order to prevent a building wiring issue once the boxes are installed,the wiring diagrams
and field wiring installation for each unit MUST be checked to determine whether the neutral is required or not required.
1" [25.4 mm] Foil -Faced Insulation
The interior surface of the unit is acoustically and thermally lined with 1", 1.5 lb/cu.ft density glass fiber with a foil facing.
The insulation is UL listed and meets NFPA-90A, UL 181 standards, and bacteriological standard ASTM C 665. All
insulation options will meet the 25/50 smoke developed and flame spread rating (per ASTM E 84 and UL 723 and
CAN/ULC S102-M88) Meets NFPA-90B. The insulation R-value is 4.1.All cut edges of insulation are completely
_ encapsulated in metal to prevent erosion.
Air Valve& Fan Description (Parallel)(Series)
The air inlet connection is an 18 gauge galvanized steel cylinder sized to fit standard round duct.A multiple point,
averaging flow sensing ring is provided with balancing taps for measuring airflow within+/-5%of unit cataloged airflow.
Also provided with each unit is a calibration chart indicating airflow versus flow sensor pressure differential.The damper
blade is constructed of a closed cell foam seal mechanically locked between two 22 gauge galvanized steel disks. The
damper blade assembly is connected through a cast zinc stub axle and shaft supported by self lubricating bearings.The
shaft is cast with a damper position indicator. The valve assembly includes a mechanical stop to prevent over stroking.
Air valve leakage<1%at 4".
1206SQ Air Valve/Fan Combination Size(Series)
12" Inlet designed for up to 2000.0 cfm. Fan is 2650.0 cfm for Std Motor and 2500.0 cfm for ECM Motor.
1006SQ Air Valve/Fan Combination Size(Series)
10" Inlet designed for up to 1400.0 cfm. Fan is 2650.0 cfm for Std Motor and 2500.0 cfm for ECM Motor.
Fuse
Any electric heat unit with a calculated MCA greater or equal to 30 will have a fan fuse provided.
Electric Heat Coil
Factory provided and mounted. Resistance open-type heater, a disc-type automatic thermal primary safety device and
manual reset load thermal secondary device. Heater element material is nickel-chromium. The heater terminal box is
provided with knockouts for customer power supply. Terminal connections are plated steel with ceramic or phenolic
insulators. All fan-powered units with electric reheat are single-point power connections.
Magnetic Contactor
An electric heater 24 volt contact for use with Direct Digital Control (D.D.C.) or Analog Electronic VAV Controls.
Transformer
The 50 VA transformer is factory mounted in the fan control box to provide 24 VAC for controls.
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 5 of 13
Others
Morphe at Washington Sq Mall January 3,2019
SCR-Variable Fan Speed Control Switch
The SCR speed control device allows the operator infinite fan speed adjustment so the fan output may be modified to
achieve exact CFM requirements.
Power Fuse
Fuses provided on all energized lines of incoming power to interrupt circuit overcurrent conditions.
SCR Modulated Electric Heat_SCRP
An SCR electric control device for use with FM00(Customer Furnished Controls) or ENCL(Enclosure only No
controls)/ENON (No Enclosure& No controls) controls. The SCR is a substitute for magnetic contactors and a RoHS
compliant alternative to Mercury contactors. A 24VDc Power Supply is included with this option to power the SCR _
Module. The SCR allows the operator Modulating heat adjustment for precise, silent control of zone temperature.
Power Disconnect Switch (for VSEF&VPEF)
A factory provided interlocking door disconnect switch located on the electric heater control panel.
Airflow Switch
An air pressure device designed to disable the heater when the unit fan is off.
Flanged Connection
A rectangular opening on the unit discharge to accept a 90 degree flanged duct work connection.
Standard D.D.C. Floating Point Actuator
18GA wires are used. 3.0 VA, 1.5W, 24 VAC, 50/60 Hz. Quarter turn control actuator with linkage release button.
Actuator has a constant drive rate independent of load, a rated torque of 35 in-Ib, a 90-second drive time and is
non-spring return. Travel is terminated by end stops at fully opened and closed positions.An integral magnetic clutch
eliminates motor stall. An integral 3 screw terminal block is provided for field wiring. Operating temperature 32.0 F to
125.0 F.
Controls Option DDOO
Electric Actuator Only(Trane Actuator Only)
Supply air valve electric actuator with field mounting of unit controller. Electric actuator is a floating point controller and
uses three wires. Three screw terminal block is integral to actuator body.
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 6 of 13
Others
Morphe at Washington Sq Mall January 3,2019
Unit Dimensions -Variable Air Volume Fan Powered Terminal Units
Item: Al -A3 Qty: 3 Tag(s): FPVAV-1, FPVAV-2, FPVAV-3
Unit Size VSEF1206SQ
Nominal 12"Dia.x 4"Depth
Valve Size&Depth _
Nominal 06SQ Fan _
Fan Size
• Filter Size 20"x 20"x 1"(QTY 1)
30
LOW VOLTAGE
CONTROL BOX\H-5" 4"*1 12" 1>1 1.
n 13
Ilk :4:0".
AIRFLOW
16 1/2" ,
L
NOTES:
1 40" 1.Allow a minimum 6"plenum inlet clearance
for un-ducted installations.
FILTER- ''
Camlock Bottom Access 2.Filter is secured in filter frame located in unit Airflow
See Accessory sheet Plenum inlet.
AIRFLOW_� I for exact location 3. For Motor access,remove bottom screws on
PLENUM INLET and dimensions.ons. hanger brackets to slide panel as shown in drawing.
so" H 4. See Installation Documents for exact hanger
,� bracket location.
L
5.Air valve centered between top&bottom panel.
x
m ELECTRIC 6. Heating coil un-insulated. External insulation may
17" z HEATER PANEL SLIDES be field supplied and installed as required.
FOR MOTOR ACCESS
it 7.All high&low voltage controls have same-side
ur
NEC jumpback clearance.
8.Allow 48"of straight duct downstream of
L unit before first runout and inside of the duct should
be equal discharge size.
6"
TOP VIEW 9. Terminal box access door is side hinged.Allow for
AIRFLOW clearance.
DISCHARGE OUTLET
10.A 4 wire power supply required for 480&575
< 25" > single point connection units.
11. Attenuator option not available with this unit layout.
�-1 W 12. Cam Lock Bottom Access Door-22"x 26".
d !a! g^ 26 GA galvanized steel with a 1"thick
insulation encapsulated with a 26 GA liner.
13. Optional Bottom Access is centered 3"
from discharge end on the bottom of the unit.
14" 211/2"
Approximate
Dry Weight 136.0 Ib
Weights reflected may vary
19" >< v 51/2' ±5.0 lb based upon options
selected.
DISCHARGE VIEW
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 7 of 13
Others
•
Morphe at Washington Sq Mall January 3,2019
Unit Dimensions -Variable Air Volume Fan Powered Terminal Units
Item: A4 Qty: 1 Tag(s): FPVAV-4
Unit Size VSEF1006SQ
Nominal 10"Dia.x 4"Depth
Valve Size&Depth
Nominal 06SQ Fan
Fan Size
Filter Size 20"x 20"x 1"(QTY 1)
< 3p^ >
LOW VOLTAGE
CONTROL BOX\H-S"G<4" 1-10"—E>1 !'
n F.
.4.y
161/2" '
L
NOTES:
1 40" 1.Allow a minimum 6"plenum inlet clearance
for un-ducted installations.
FILTER iC''°
2.Filter is secured in filter frame located in unit Airflow
Camlock Bottom Access Plenum inlet.
See Accessory sheet
AIRFLOW c— I for exact location 3. For Motor access,remove bottom screws on
PLENUM INLET and dimensions. hanger brackets to slide panel as shown in drawing. _
50" I T4. See Installation Documents for exact hanger
v bracket location.
L
A
5.Air valve centered between top&bottom panel.
x
m ELECTRIC 6. Heating coil un-insulated. External insulation may
17" z HEATER PANEL SLIDES be field supplied and installed as required.
FOR MOTOR ACCESS
7.All high&low voltage controls have same-side
re
w NEC jumpback clearance.
1
8.Allow 48"of straight duct downstream of
LoJ unit before first runout and inside of the duct should
be equal discharge size.
6"
TOP VIEW 9. Terminal box access door is side hinged.Allow for
AIRFLOW clearance.
DISCHARGE OUTLET
10.A 4 wire power supply required for 480&575
25" single point connection units.
11. Attenuator option not available with this unit layout.
W 12. Cam Lock Bottom Access Door-22"x 26".
U U 3" 26 GA galvanized steel with a 1"thick
insulation encapsulated with a 26 GA liner.
13. Optional Bottom Access is centered 3"
from discharge end on the bottom of the unit.
14" 211/2"
I
Approximate
Dry Weight 135.0 lb
Weights reflected may vary
19" > 51/2" ±5.0 lb based upon options
selected.
DISCHARGE VIEW
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 8 of 13
Others
•
Morphe at Washington Sq Mall January 3,2019
Accessory -Variable Air Volume Fan Powered Terminal Units
Item: Al -A4 Qty: 4 Tag(s): FPVAV-1, FPVAV-2, FPVAV-3, FPVAV-4
Notes:
1.When attenuator is required, add inlet attenuator pressure
to discharge static pressure for final fan performance.
VSCF and VSEF maximum
Minimum
1-row coil maximum
-.- - - -.-. 2-row coil maximum
Pa In,wg Series D6SQ—PSG
1 t--- i —I— I',..- - ''1N
199 0.80 _ ;
'5%
174 0.70
150 0.60 J ,„ , ' ,�
125 0.50 z '',., j
y 100 0.40 . F...
(1) k
" :
t 75 0.30 1 4'.
---� 4 ' r
t3 50 0.20 >~., ;' ( P �, ,t
�e ',
25 0.10 - # 4 . ,
l at 7
0 0.00 k 1 ......
400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2600 et
m
189 283 378 472 566 661 755 550 944 1038 1133 1227 1322 Ua
Airflow
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 9 of 13
Others
•
Morphe at Washington Sq Mall January 3,2019
Accessory -Variable Air Volume Fan Powered Terminal Units
Item: Al -A4 Qty:4 Tag(s): FPVAV-1, FPVAV-2, FPVAV-3, FPVAV-4
BOTTOM ACCESS DIMENSIONAL DATA
Bottom Access Bottom Access
Fan Size Opening Size Cam Lock C
Ax B Cover Size
16.00"x 16.00" 18.00"x 18.00" 3.00"
02SQ
(406mm x 406mm) (457mm x 457mm) (76 mm)
03SQ 16.00"x 16.00" 18.00"x 18.00" 4.00"
04SQ (406mm x 406mm) (457mm x 457mm) (101 mm)
O6SQ 20.00"x 24.00" 22.00"x 26.00" 5.00"
075Q (508mm x 609mm) (559mm x 660mm) (127 mm)
uI_
Primary
Airflow
Flow Rigg
Tubing 1�1
Air
Valve
I I
I _
I I
I I
� P
I I
1 I
A
r 1
1
BOTTOM
ACCESS
b C Lo- SEE CHART 0 C
B
Airflow
Plenum Inlet
—1
I —1
L I I J
�
TOP VIEW ( I (76 mm)
o
Panel slides
Fitter Airflow for Motor access
Discharge Outlet
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 10 of 13
Others
•
Morphe at Washington Sq Mall January 3,2019
Field Wiring -Variable Air Volume Fan Powered Terminal Units
Item: Al -A4 Qty:4 Tag(s): FPVAV-1, FPVAV-2, FPVAV-3, FPVAV-4
208 Volt,3 Phase
L3 L2 L1
I I I
I � I
I I I T
• • •
•
Heater
Control
Wring
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS
BEFORE SERVICING.
FAILURE TO DISCONNECT POWER
BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH
A\ CAUTION
USE COPPER CONDUCTORS ONLY!
UNIT TERMINALS ARE NOT DESIGNED Customer Notes:
TO ACCEPT OTHER TYPES OF
CONDUCTORS. 1. Factory installed.
FAILURE TO DO SO MAY CAUSE — — — — Optional or installed by others.
DAMAGE TO THE EQUIPMENT.
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 11 of 13
Others
Morphe at Washington Sq Mall January 3,2019
Field Wiring -Variable Air Volume Fan Powered Terminal Units
Item: Al,A2 Qty: 2 Tag(s): FPVAV-1, FPVAV-2
NOTES'
i. FACTORY WIRING
FIELD WIRING
—--—--—--—OPTIONAL OR ALTERNATE WIRING
2 ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE
NATIONAL ELECTRIC CODE(NEC),STATE AND LOCAL REQUIREMENTS.
3.I CAPACITOR IS INSTALLED ON FAN HOUSING.
FROM HEATER /\
TERMINAL BOX 4.I DISCONNECT SWITCH,OPTIONAL FUSE AND MOTOR SPEED CONTROL ACTUATORS ARE LOCATED
^ ` EXTERNAL TO CONTROL BOX.
< 5 CLASS2CONTROLS TRANSFORMER PROVIDED IN ALL UNITS.
BK
666//� //W\/ I
0 .._J. /DISCONNECT
BK666666 W
< I MOTOR SPEED CTRL
0BK MOTOR
W M
o W
3"-S
\W W
BR0
\o
TERMINAL BLOCK
0 0
BL o 24V O V < B I < 3.I //
a)� BRJ W
TRANSFORMER
0 o CAPACITOR
I- I < 4I
FUSE 0
�__
FAN RELAY w/24VAC COIL
o ils
2 4
CCW(OPEN) 24VAC
DAMPER COMMON M Damper
Actuator
CONTROL Load:4 VA
CW(CLOSE)_-- Factory Installed
1 3
FAN FAN RELAY w24VAC COIL
CONTROL BR
ON/OFF
Y(GND)
TO VAV
CONTROLLER 24VAC
POWER
BL(24VAC)
ELECTRIC 1ST STAGE HEAT URN OPTIONAL
HEATER COM BR STAGED HEATER CONTRACTORS ARE 24 VAC 12VA MAX/COIL(MERCURY CONTACTORS).
CONTROL ELECTRIC 10VA MAX/COIL(MAGNETIC CONTACTORS).
2ND STAGE HEAT --__MO HEATER
3RD STAGE HEAT RED
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 12 of 13
Others
Morphe at Washington Sq Mall January 3,2019
Field Wiring -Variable Air Volume Fan Powered Terminal Units
Item: A3,A4 Qty: 2 Tag(s): FPVAV-3, FPVAV-4
NOTES.
1. FACTORY WIRING
FIELD WIRING
—--—--—--—OPTIONAL OR ALTERNATE WIRING
2 ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE
NATIONAL ELECTRIC CODE(NEC)STATE AND LOCAL REQUIREMENTS.
FROM HEATER < 3 CAPACITOR IS INSTALLED ON FAN HOUSING.
TERMINAL BOX
DISCONNECT SWITCH,OPTIONAL FUSE AND MOTOR SPEED CONTROL ACTUATORS ARE LOCATED
EXTERNAL TO CONTROL BOX.
< 5. CLASS 2 CONTROLS TRANSFORMER PROVIDED IN ALL UNITS.
BK / /W�/
/ ( /DISCONNECT
BK ddd
/DISCONNECT
—I MOTOR SPEED CTRL
o
BK MOTOR •
\
:i1i)
W W
\?J
TERMINAL BLOCK
O O
BL 24V Y < 3.
I(o BR
•v TRANSFORMER
0 o CAPACITOR
I' FUSE
FAN RELAY w/24VAC COIL
0110
2 4
CCW(OPEN)
^ 24VAC
COMMON �� \ Damper
DAMPER U Actuator
CONTROL Load:4 VA
CW(CLOSE) - Factory Installed
FAN RELAY w/24VAC COIL
R GND 1
FAN
CONTROL BR 24VAC
ON/OFF
TO VAV Y(GND)
CONTROLLER
24VAC
POWER BL(24VAC)
BL(24VAC)
Y(GND) OPTIONAL THE ELECTRIC HEATER 0-10VDC MODULATION
ELECTRIC SCR CONTROL SIGNAL MUST BE<0.2VDC
HEATER DC COM GRY ELECTRIC TO GUARANTEE HEAT IS OFF.
CONTROL 0-10VDC ORN HEATER
FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 13 of 13
Others
RECEIVED
Printed Date: 01/07/2019
IiGREENHECK Job: Morphe TI Store #040
Building Value in Air. iA ' 2019
Mark: EF-1
GIT-v ' TIGARD Model: SP-A190
—14.625–,-- --14.875 1{ D �+ P-A190
j 1 f Ceiling Exhaust Fan
5.5 = c 13.25 Standard Construction Features:
II -Corrosion resistant galvanized steel scroll and housing-Sound absorbing
1 insulation-White designer non-yellowing grille-Outlet duct collar with integral
spring loaded backdraft damper-Double inlet forward curved wheel-Plug type
disconnect-Adjustable mounting brackets-Field rotatable discharge
Selected Options &Accessories:
—13.25-- -- 10.625 -- Motor with Thermal Overload
r_81 — Motor with CSA Approval
Motor with 40 Degree C Ambient Temperature
Motor rated for continuous use
MOUNTING UL/cUL 507 Listed-Electric Fan
BRACKET9 6 [ ..
1 Solid State Speed Control,6 Amp,Shipped Loose
Designer Grille
Polypropylene Wheel Material
Energy Star Rated
Can Be Used to Comply with:ASHRAE 62.2,California Title 24,and Washington
State Energy Code
Dimensional
Quantity 1
Weight w/o Ace's(Ib) 17
Weight w/Acc's(Ib) 18 0.28
Performance 0 24 .- , -
Requested Volume(CFM) 140
Actual Volume(CFM) 140 0.20 -
Total External SP(in.wg) 1 0.1 a� \ ,' '
1 3
Fan RPM 998 C 0.16 • : .
*FLA(A) 1.3 f e
Elevation(ft)ft . 108
I 20.12 ._ \
Airstream Temp.(F) 70 2 ;•"b'
0_
Air Density(Ib/ft3) 1 0.075 c) �
I -0 0.08
Sones 0.5 co
0.04 ° \�
4° Ss.. -,-toll - . _ t
0.00 -.._._ \ ..
0 20 40 60 80 100 120 140 160 180
Motor Volume(CFM)
Motor Mounted Yes
0 Operating point at Total External SP
**Input Watts(W) 18 Fan curve
Voltage/Cycle/Phase 115/60/1 - -..-.-.System curve
Enclosure ODP
Notes:
All dimensions shown are in units of in. MCC'
*FLA is approximate and will vary slightly with the motor. WORIDWIDE
Sones-calculated using AMCA 301 at 5 ft oERTInED
**Wattage is approximate and may vary between motors. MIME
sound
mo.EmenT 4.
a*o
mrennnnnnm.ine. '
Generated by:jfisher@johnsonair.com
CAPS 4.28.1333 Y:\AaronCormack\Secured Jobs 2019\M-R\Morphe Store#040.gfcj Page 2 of 3
Printed Date: 01/07/2019
GREENHECK Job: Morphe TI Store #040
Building Value in Air. Mark: EF-1
Model: SP-A190
AMCA
amca
WORIDWIDE
CERTIFIED
RRTIRGS
sounD
RIR
ane
PEKORAIAACE
RIR to
MOVEMERT 4i
ARD CORTROI
RSSOCIRTIOR QO,
IRTERRRTIORnL. inc.
AMCA Licensed for Sound and Air Performance Without Appurtenances (Accessories). Power rating (BHP/kW) does not
include transmission losses.
Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings
shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication
311 and comply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation
type B: Free inlet, Ducted outlet. Performance ratings include the effects of an inlet grille and backdraft damper. Speed
(RPM) shown is nominal. Performance is based on actual speed of test. The watt ratings shown are at free air. The
sound ratings shown are for loudness values in spherical sones at 5 ft. (1.5m) in a spherical free field calculated per
Annex B of AMCA 311. Values shown are for installation type B: ducted outlet spherical sone levels. The AMCA
Certified Ratings Seal applies to sone ratings only.
The AMCA licensed air and/or sound performance data has been modified for installation, appurtenances or
accessories, etc. not included in the certified data. The modified performance is not AMCA licensed but is provided to
aid in selection and applications of the product.
Generated by:jfisher@johnsonair.com
CAPS 4.28.1333 Y:\AaronCormack\Secured Jobs 2019\M-R\Morphe Store#040.gfcj Page 3 of 3