Report (57) ` . i Tualatin Valley Fire & Rescue Tualatin Valley Fire Flow and Hydrant Worksheet Fire & Rescue North Operating Center Central Operating Center South Operating Center 20665 SW Blanton Street 11945 SW 70th Avenue 7401 SW Washo Court,Ste 101 Aloha,OR 97007 Tigard,OR 97223 Tualatin,OR 97062 Phone:503-259-1400 Phone: 503-649-8577 Phone: 503-259-1500 Fax:503-259-1224 Fax: 503-642-4814 Fax: 503-259-1520 Fire Flow and Hydrant Worksheet This worksheet is required to be submitted to and approved by the Authority Having Jurisdiction (AHJ) before any permits for new building construction, building expansion or fire hydrants will be issued by any building department within the TVF&R District. For assistance completing this form, see the Fire Flow and Hydrant Worksheet Instructions or call the Operating Center nearest you. SECTION 1 - Preparer Information a. Preparer Name: Taylor Liserre Date: 7/9/2018 Phone: 503-668-3151 Fax: E-mail: taylor@allcountysurveyors.com b. Architect/Engineer of Record: Ray Moore Phone: 503-668-3151 Fax: E-mail: raym@allcountysurveyors.com SECTION 2 - General Building Information a. Project Name: Tigard Taco Bell Project Address: 13305 SW Pacific Highway City: Tigard County: Washington County Zip: 97223 b. Construction Type: Type V-B c. Total Bldg Area: 2,105 sq ft(as defined by the OSSC) Total Fire Area: 2,105 sq ft(as defined by the OFC) Bldg Fire Flow: 1500 GPM (base amount without adjustment for occupancy hazard classification) d. Describe Fire Area: (if more than one fire area,include an 8 1/2 x 11 or 11 x 17 drawing indicating the various fire areas) The entirety of the proposed"Explorer Lite Medium 40"Taco Bell Building. e. Type of Occupancy or Use of Building: C-P - Professional Commercial Page 1 Revised: August 2011 IFire Flow and Hydrant Worksheet(continued) I SECTION 3 - Occupancy Hazard a. Percentage of Occupancy Hazard Classifications(see Worksheet Instructions-tables 1 and 2) Occupancy Hazard Classification Fire Area Total Fire Area Percent of Fire Area Light Hazard 780 SF I 2,105 SF x 100 = 37.05 % Ordinary Hazard Grp 1 885 SF I 2,105 SF x 100 = 42.04 % Ordinary Hazard Grp 2(HPCS I & II) 440 SF I 2,105 SF x 100 = 20.9 % Extra Hazard Grp 1 (HPCS III) 0 SF I 2,105 SF x 100 = 0 % Extra Hazard Grp 2 (HPCS IV& HH) 0 SF I 2,105 SF x 100 = 0 % Total must equal 100% 99.99 % b. Calculated Fire Flow Occupancy Hazard Classification Factor Fire Area Fire Flow Bldg Fire Flow Light Hazard 0.75 x 37 % x 1500 GPM = 417 GPM Ordinary Hazard Grp 1 0.85 x 42 % x 1500 GPM = 536 GPM Ordinary Hazard Grp 2 1 x 21 % x 1500 GPM = 314 GPM Extra Hazard Grp 1 1.15 x 0 % x 1500 GPM = 0 GPM Extra Hazard Grp 2 1.25 x 0 % x 1500 GPM = 0 GPM c. Required Fire Flow with Occupancy Hazard Adjustment 1267 GPM SECTION 4- Minimum Number of Fire Hydrants Required Refer to Table C105.1 below(2010 OR Fire Code, Appendix C)for the minimum number of hydrants required. Required Fire Flow: 1267 GPM TABLE C105.1 NUMBER AND DISTRIBUTION OF FIRE HYDRANTS I FIRE-FLOW REQUIREMENT !ANNUM NUMBER (gPm) OF HYDRANTS 1,750 ont • 1 2,000-2,250 2 2,50) 3 3, ) 3 3,500-4, 4 4,500-5„0,00 5 5,500 6 6,000 6 6,500-7,000 7 7,500 or more 8 or more Page 2 Revised: August 2011 Fire Flow and Hydrant Worksheet (continued) SECTION 5 - Reduction of Fire Flow Reduced by 75%for an approved automatic sprinkler system, installed in accordance with NFPA 13 or NFPA 13R (choose multiplier 0.25 in Section 6). SECTION 6 - Required Fire Flow Fire Flow: 1267 GPM X 1 1500 GPM (Min.= 1500,Max.=3000) SECTION 7 -Available Fire Flow to the Building Manually enter available fire flow here. Please attach documentation of the flow test that was conducted. It must include date, time and location of static/residual and flow hydrants, as well as the tester's name, phone number and address. Test Results: GPM Page 3 Revised: August 2011