September 14,2018
Mr. Brad Satran REVISION
15410 SW Seine Court
Tigard, Oregon 97224
Subject: Satran Residence Deck
15410 SW Seine Court,Tigard,Oregon
MCE Project Number: 180573
Dear Mr. Satran
During the course of construction of the deck and deck cover, it was requested that one of
the upper deck support posts be shifted about 12 inches in order to clear an existing
footing. This meant that the roof post would not align with the deck post below as noted
in the original calculations.
A review was done for the new loading and the specified 6 x 10 PT Hem-Fir#1 beam is
still adequate for the loading. It is acceptable to shift the deck post and footing.
If you have any additional questions or comments,please do not hesitate to contact me.
Respectfully,
Miller Consulting Engineers,Inc. ��`�f C
R01G;° 'GiN` i ,;
�.t, e 96655PE
Kevin M. McCormick, S.E. YNR
Managing Principal - OREGON ocl -e
41, CRY1
t'
EXPIRES• t? 31--2- Iry
Engineering Practical, Diverse. Structural Solutions Since 1978
FOR OFFICE USE ONLY-SITE ADDRESS:
This form is recognized by most building departments in the Tri-County area for transmitting information.
Please complete this form when submitting information for plan review responses and revisions.
This form and the information it provides helps the review process and response to your project.
City of Tigard • COMMUNITY DEVELOPMENT DEPARTMENT
11111 Transmittal Letter
T c;A H l) 13125 SW Hall Blvd. • Tigard, Oregon 97223 • 503.718.2439 • www.tigard-or.gov
TO: 411 o= DATE RECE V
DEPT: BUILDING DIVISION RECE1YED
DEC 10 2018
FROM: �'�, A Jdc.bra°'` CITY OF TIGARD
COMPANY: BUILDING DIVISION
PHONE: 5c5-5
I _ 3 C"2 c( 14.3,:e
RE: / Sy/ w 5„c,,:..... G 4 . Tcns--t-Q Arx I t 0 -CO t((3
(Site Address) (Permit Number)
(Project name or subdivision name and lot number)
ATTACHED ARE THE FOLLOWING ITEMS:
Copies: Description: Copies: De' ription:
Additional set(s) of plans. ' evisions:
Cross section(s) and details. Wall bracing and/or lateral analysis.
Floor/roof framing. Basement and retaining walls.
Beam calculations. 1.\\ Engineer's calculations.
<— Other(explain): 1-e..44-tf -Rv-- \ • - ;,-ems '5i-c, i..,„, pcfg - pi Ace.,---e--.4-
REMARKS:
ce.,---e -. -REMARKS: i 5 cik .
V)Ty
FORFFI E USE ONLY
Routed to Permit Technician: I .te: 12 7
O (1 Initials: M4—
Fees Due: ❑ Yes WNo ee Description Amount Due:
N.)0 i '3 $$/El-
Special
Instructions:
Reprint Permit(per PE): ❑ Yes No [ . Done
Applicant Notified: a Date: 0- tt/i( Initials: f 7\
I:\Building\Forms\TransmittalLetter-Revisions.doc 05/25/2012