Report RECEIVED
JUN 12 2018
Tualatin Valley Fire & Rescue CITY OFTIGARD
Tualatin Valley Fire Flow and Hydrant Worksheet BUILDING DIVJ ')N
Fire & Rescue
North Operating Center Central Operating Center South Operating Center
20665 SW Blanton Street 11945 SW 70th Avenue 7401 SW Washo Court,Ste 101
Aloha,OR 97007 Tigard,OR 97223 Tualatin,OR 97062
Phone:503-259-1400 Phone: 503-649-8577 Phone: 503-259-1500
Fax:503-259-1224 Fax: 503-642-4814 Fax: 503-259-1520
Fire Flow and Hydrant Worksheet
This worksheet is required to be submitted to and approved by the Authority Having Jurisdiction (AHJ)before any permits for
new building construction, building expansion or fire hydrants will be issued by any building department within the TVF&R
District. For assistance completing this form,see the Fire Flow and Hydrant Worksheet Instructions or call the Operating
Center nearest you.
SECTION 1 - Preparer Information
a. Preparer Name: Christina West, AIA Date: 6/11/2018
Phone: 503-913-6501 Fax: n/a E-mail: christina.west@otak.com
b. Architect/Engineer of Record: Brian R. Fleener, AIA
Phone: 503-415-2400 Fax: n/a E-mail: brian.fleener@otak.com
SECTION 2 - General Building Information
a. Project Name: SW Atlanta Storage Facility
Project Address: 7800 SW Atlanta Street
City: Tigard County: Washington County Zip: 97223
b. Construction Type: Type IIA and IIIA
c. Total Bldg Area: 120,252 sq ft(as defined by the OSSC)
Total Fire Area: 120,252 sq ft(as defined by the OFC)
Bldg Fire Flow: 5000 GPM (base amount without adjustment for occupancy hazard classification)
d. Describe Fire Area: (if more than one fire area,include an 8 1/2 x 11 or 11 x 17 drawing indicating the various fire areas)
Building contains two fire areas, separated by a three hour rated podium between Level 1 (Type I-A
construction, 22,289 sf)and Levels 2-5(Type Il-A construction, 97,963 sf).
e. Type of Occupancy or Use of Building: S-1: Commercial - Storage Units I
Page 1 Revised: August 2011
IFire Flow and Hydrant Worksheet (continued)
SECTION 3 -Occupancy Hazard
a. Percentage of Occupancy Hazard Classifications(see Worksheet Instructions-tables 1 and 2)
Occupancy Hazard Classification Fire Area Total Fire Area Percent of Fire Area
Light Hazard 0 SF / 120,252 SF x 100 = 0
Ordinary Hazard Grp 1 120252 SF / 120,252 SF x 100 = 100
Ordinary Hazard Grp 2 (HPCS I & II) 0 SF / 120,252 SF x 100 = 0
Extra Hazard Grp 1 (HPCS III) 0 SF / 120,252 SF x 100 = 0 %
Extra Hazard Grp 2 (HPCS IV& HH) 0 SF / 120,252 SF x 100 = 0
Total must equal 100% 100 %
b. Calculated Fire Flow
Occupancy Hazard Classification Factor Fire Area Fire Flow Bldg Fire Flow
Light Hazard 0.75 x 0 % x 5000 GPM = 0 GPM
Ordinary Hazard Grp 1 0.85 x ## % x 5000 GPM = 4250 GPM
Ordinary Hazard Grp 2 1 x 0 % x 5000 GPM = 0 GPM
Extra Hazard Grp 1 1.15 x 0 % x 5000 GPM = 0 GPM
Extra Hazard Grp 2 1.25 x 0 % x 5000 GPM = 0 GPM
c. Required Fire Flow with Occupancy Hazard Adjustment 4250 GPM
SECTION 4- Minimum Number of Fire Hydrants Required
Refer to Table C105.1 below(2010 OR Fire Code, Appendix C)for the minimum number of hydrants required.
Required Fire Flow: 4250 GPM
TABLE C105.1
NUMBER AND DISTRIBUTION OF FIRE HYDRANTS
FIRE-FLOW REOUIREI4 NT MINIMUM NUMBER
((Wm) OF HYDRANTS
1,,710 or IPg.42 1 i
2,000-2,250
2,500 3
3,4(00 3
E
3500-4,000 4
4,500-5,000 5
5,5(X1
6,000 6
6,500-7,000 7
7,500 or more 8 or more
Page 2 Revised: August 2011
Fire Flow and Hydrant Worksheet (continued) J
SECTION 5- Reduction of Fire Flow
Reduced by 75% for an approved automatic sprinkler system, installed in accordance with NFPA 13 or
NFPA 13R (choose multiplier 0.25 in Section 6).
SECTION 6 - Required Fire Flow
Fire Flow: 4250 GPM x 0.25 1500 GPM
(Min.=1500, Max.=3000)
SECTION 7-Available Fire Flow to the Building
Manually enter available fire flow here. Please attach documentation of the flow test that was conducted. It
must include date, time and location of static/residual and flow hydrants, as well as the tester's name, phone
number and address.
Test Results: 4889 GPM
Page 3 Revised: August 2011
TUALATIN VALLEY WATER DISTRICT Test#: 1250
FIRE HYDRANT FLOW TEST REPORT Hydrant ID #: 1S1W36D32FH50
Location: SW 68TH PKWY &SW PACIFIC HWY Date: 11128/2016
Test made by: HERB &JAMES
Witness: Time: 1:20
Project name:
Discharge coefficient: .54816
Inside dia. of outlet= 4.5 inches
Pitot reading = 45 psi Pitot 2 = 0 psi
Observed flow rate = 2220,5 gpm
Flow method: HOSE MONSTER
Static pressure: 89 psi Residual pressure: 73 psi
Flow at 20psi residual pressure (calculated): 4889 gpm 1 ``'e4l�i6
Location map: To be attached to test report and to show which hydrants were
used to monitor residual pressure and flow.
Gage information:
Static and residual pressure gage: 3602536332 Pitot gage: 2-A5F6U-20-1
Hydrant information:
Hydrant ID Year Make Notes
Flow hydrant: 1S1W36D32FH50 2005 WATEROUS see map for location
Read hydrant: 1 S1 W36D43FH50 1985 WATEROUS see map for location
Remarks:
The mapping,flow or pressure information contained herein reflects conditions on the date and
time of the test. Tualatin Valley Water District makes no representation as to the system's
ability to meet specific fire flow requirements. Future system capability may differ from the
flows reported herein because of subsequent modifications to the district's system and/or
because flow and pressure may vary by time of day and season. Test gage callibration
information available upon request.