Report (66) aRC U.0 I:"D- 1 Sk,i, 's, � -"' icy Bulletin 014 Rev. O OJ 1111111 Model Fl FR Series . rieliabidQuick Responseo Glass Bulb SprinklersCD IIIIMIIIMIIIMIIIIMIIIIIIIIIMIIIM 0 Model F1FR56 Sprinkler Type C IV Standard Spray Upright t� Standard Spray Pendent OCT 2 9 2018 Ilitlit Conventional Upright/Pendent Vertical Sidewall Horizontal Sidewall BUILDING DIVISION Model Fl FR56 Recessed Sprinkler Types Upright Pendent Conventional Standard Spray Pendent Horizontal Sidewall —==_ Model Fl FR56 Concealed Sprinkler Types 410.1r ( 0 Standard Spray Pendent Model F1 FR42, F1 FRXLH & F1 FR28 Sprinkler q . Types Vertical Sidewall Horizontal Sidewall Recessed Standard Spray Upright Pendent/F1/F2 Standard Spray Pendent Model Fl FR40 Sprinkler Types Standard Spray Pendent / ,, ,"' ' r. ' ` Model F1 FR42, F1 FR40, F1 FRXLH & F1 FR28 - aK 4 .zA Recessed Sprinkler Types r , •. Standard Spray Pendent :....-0., 1 , ' 1 Model Fl FR56LL&Fl FR42LL Low Lead Sprinkler Recessed Concealed+ Recessed Types Horizontal Sidewall Pendent Pendent/FP Standard Spray Pendent with less than 0.25% Lead Content iiii Listing & Approvals 0 t The following organizations provide Listings or Approvals for various Model Fl FR series sprinklers. See the Design and Installation table in this Bulletin for information on XLH Upright XLH Pendent XLH Recessed specific listings and approvals applicable to each sprin- Pendent F1/F2 kler. Product Description 1. Underwriters Laboratories Inc. and Certified for Reliable Model F1FR series sprinklers ..�.. Canada(cULus) in accordance with ANSI/UL199. are quick-response automatic sprin- �{ 2. FM Approvals (FM) 3. Loss Prevention Certification Board (LPCB) klers with a glass bulb thermal element. 4. VdS Schadenverhutung GmbH (VdS) Model F1FR series sprinklers are Stan 5. Underwriters Laboratories Inc. and Underwriters dard Spray sprinklers, with the excep Laboratories of Canada Certified for Health Effects tion of the Model F1FR56 Conventional XLH Recessed to NSF/ANSI Standard 61 Annex G (ULH) sprinkler which is an Old-style/Conven- Pendent FP 6. EC Certificate: 0786-CPD-40239 (RA1414), 0786- tional sprinkler. CPD-40251 (RA1425), 0786-CPD-40252 (RA1475) The Model F1FR Series automatic sprinklers utilize a 3.0 (EC) mm frangible glass bulb.These sprinklers have demonstrat- UL Listing Category ed response times in laboratory tests which are five to ten Sprinklers,Automatic&Open (VNIV) times faster than standard response sprinklers. This quick Quick Response Sprinkler response enables the Model Fl FR Series sprinklers to apply water to a fire faster than standard-response sprinklers of the same temperature rating. ' The glass bulb consists of an accurately controlled amount of special fluid hermetically sealed inside a precisely man- ufactured glass capsule. This glass bulb is specially con- structed to provide fast thermal response. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 At normal temperatures, the glass bulb contains the fluid Model F1FR Series sprinklers must be installed with the in both the liquid and vapor phases. The vapor phase can Reliable sprinkler installation wrench identified in the Design be seen as a small bubble. As heat is applied, the liquid and Installation Information table in this Bulletin. Any other expands, forcing the bubble smaller and smaller as the liq- wrench may damage the sprinkler. A leak tight sprinkler joint uid pressure increases. Continued heating forces the liquid can be obtained with a torque of 8 to 18 lb-ft(11 to 24 N-m). • to push out against the bulb, causing the glass to shatter, Do not tighten sprinklers over the maximum recommended opening the waterway and allowing the deflector to distrib- installation torque. Exceeding the maximum recommended ute the discharging water. installation torque may cause leakage or impairment of the - Model F1FR Series sprinklers provide a wide range of op- sprinkler. tions where quick-response, glass bulb sprinklers are used: Recessed Sprinklers • Pendent, recessed pendent, upright, horizontal side- Model F1FR Series Recessed sprinklers are to be installed wall, and vertical sidewall deflectors as shown in Fig. 1, Fig. 2,or Fig.3,as applicable to the spe- • K-factors of 2.8 (40 metric), 4.0 (57 metric), 4.2 (60 cific model being installed.The Recessed Escutcheon Data metric), and 5.6 (80 metric) table in the Bulletin identifies the only recessed escutcheons • Flush, recessed, and concealed installations that are permitted to be used with each Model F1FR Series See the Design and Installation Information table in this Recessed sprinkler.The use of any other recessed escutch- Bulletin for information on the approvals and availability of eon will void all approvals and negate all warranties. specific Model Fl FR series sprinkler configurations. Concealed Sprinklers Model F1FR Recessed Pendent and Recessed Horizon- Model F1FR Series Concealed Pendent sprinklers are to tal Sidewall sprinklers are required to be used with Reliable be installed as shown in Fig. 4 or Fig. 5, as applicable to the Model F1, F2, or FP recessed escutcheons. See the Re- selected cover plate. Model F1FR56 Concealed Pendent cessed Escutcheon Data table in this Bulletin for listing and and Model Fl FR56LL Concealed Pendent sprinklers have approval information with each specific Model F1FR series a factory-installed Model CCP cup. A protective cap is in- sprinkler. Model Fl and F2 recessed escutcheons,shown in stalled at the factory that should remain on the sprinkler until Fig. 1 and 3, are a friction fit assembly allowing for 3/4-inch the sprinkler is installed and should then be reinstalled on (19mm) and 1/2-inch (12.7mm) of adjustment, respectively. the sprinkler until the cover plate is installed.The concealed Model FP recessed escutcheons, shown in Fig. 2, provide a sprinkler assemblies are completed by the installation of a 1/2-inch (12.7mm)threaded adjustment. Model CCP push-on/thread-off cover plate assembly. The Model F1FR56 Concealed Pendent and Model F1FR56LL cover plate and sprinkler cup assemblies are joined using - Concealed Pendent sprinklers are required to be used with a cover plate skirt with flexible tabs for threaded engage- Model CCP cover plates.A standard profile Model CCP coy- ment. A choice of two Model CCP cover plate assemblies er plate is available that provides up to 1/2-inch(12.7mm)of provides either 1/2-inch (13mm)or 5/8-inch (8mm)of cover - cover plate adjustment. In addition, a low profile Model CCP adjustment. Do not install Model F1FR Series Concealed cover plate is also available that provides up to 5/16-inch Pendent sprinklers in ceilings which have positive pressure (8.0mm) of cover plate adjustment. See the Design and In- in the space above. stallation Information and Listed and Approved Temperature Model F1FR Series Concealed Pendent sprinklers require a Ratings tables in this Bulletin for further information on ap- 2-5/8-inch (67mm) diameter hole to be cut in the ceiling. The proved cover plate options. Model RC1 wrench is used to engage the sprinkler wrenching Application surfaces and to install the sprinkler in the fitting. Remove the Model Fl FR Series sprinklers are intended for use in protective cap to install the sprinkler,then reinstall the protective accordance with NFPA 13, FM Property Loss Prevention cap until the cover plate is installed. When inserting or remov- Data Sheets, and the requirements of the Authority Hay- ing the wrench from the sprinkler/cup assembly,care should be ing Jurisdiction. Care must be exercised that the k-factor, taken to prevent damage to the sprinkler. Do not wrench any temperature rating, deflector style, and sprinkler type are other part of the sprinkler/cup assembly. Installation is corn- in accordance with the requirements of the applicable pleted by removing the protective cap from the sprinkler and design and installation standards. In addition, Model pushing the cover plate onto the cup. Final adjustment is made Fl FR Series sprinklers must be used in accordance with by hand turning the cover plate until the skirt flange makes full their listings and approvals, as well as the information contact with the ceiling.Cover plate removal requires turning the provided in this Bulletin. cover plate in the counter clockwise direction.After installation, Installation inspect all sprinklers to ensure that there is a gap between the Glass bulb sprinklers have orange bulb protectors or pro- cover plate and ceiling and that the four cup slots are open and tective caps to minimize bulb damage during shipping,han- free from any air flow impediment to the space above. dling and installation. Reliable sprinkler installation wrench- Concealed cover plate/cup assemblies are listed only for - es are designed to install sprinklers with bulb protectors in use with specific sprinklers.The use of any concealed cover place.Remove the bulb protector at the time when the sprin- plate/cup assembly other than the Reliable Model CCP with kler system is placed in service for fire protection. Removal Model F1FR56 Concealed Pendent and Model F1FR56LL of the bulb protector before this time may leave the bulb vul- Concealed Pendent sprinklers or the use of the Model CCP nerable to damage. Remove bulb protectors by undoing the Concealed cover plate assembly on any sprinkler with which clasp by hand. Do not use tools to remove bulb protectors. it is not specifically listed my prevent good fire protection and will void all guarantees, warranties, listings and approvals. 2. • Technical Data: Sensitivity: Quick-response Thread Size: 1/2-inch NPT standard; ISO 7-R1/2 optional Maximum Working Pressure: 175 psi (12 bar)- 100% Factory tested hydrostatically to 500 psi (34.5 bar) • SIN RA1425, RA1414& RA1435 cULus listed for 250 psi (17 bar) Design and Installation Information Nominal Nominal Nominal Listings Model K-factor Orifice Deflector/ Sprinkler Installation Approval nd Diameter Orientation Height Wrench SIN Ntes Approvals US Metric inches mm inches mm Pendent 2.25 57 D RA1411 cULus 2 F1FR28 2.8 40 3/8 10 Recessed Pendent 2.25 57 GFR2 RA1411 cULus 2 Upright 2.25 57 D RA1421 cULus 1,2 Pendent 2.25 57 D RA1418 VdS F1 FR40 4.0 57 3/8 10 Recessed Pendent 2.25 57 GFR2 RA1418 VdS Pendent 2.25 57 D RA1413 cULus 2 F1FR42 4.2 60 7/16 10 Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2 Upright 2.25 57 D RA1423 cULus 1,2 Pendent 2.25 57 D RA1410 cULus, ULH F1FR42LL 4.2 60 7/16 10 Recessed Pendent 2.25 57 GFR2 RA1410 cULus, ULH F1FRXLH Pendent 2.25 57 D RA1413 cULus 2 (F1FR42 4.2 60 7/16 10 Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2 with Pintle) Upright 2.25 57 D RA1423 cULus 1,2 Pendent 2.25 57 D RA1414 cULus, FM, 1,2,3,4 LPCB, VdS, EC Recessed Pendent 2.25 57 GFR2 RA1414 cULus, FM, 1,2,3,4 LPCB,VdS, EC F1FR56 5.6 80 1/2 15 Concealed Pendent 2.25 57 RC1 RA1414 cULus,VdS,EC 5,6 Upright 2.25 57 D RA1425 cULus, FM, 1,2,3,4 LPCB,VdS, EC "Conventional 2.25 57 D RA1475 LPCB,VdS, EC 4 (Pendent or Upright)" Pendent 2.25 57 D RA1415 cULus, ULH 1 F1FR56LL 5.6 80 1/2 15 Recessed Pendent 2.25 57 GFR2 RA1415 cULus, ULH Concealed Pendent 2.25 57 RC1 RA1414 cULus, ULH 6 Horizontal Sidewall 2.63 67 D RA1435 cULus, FM 1,2,3,7 F1FR56 5.6 80 1/2 15 Recessed Horizontal Sidewall 2.63 67 GFR2 RA1435 cULus, FM 8 F1FR56 5.6 80 1/2 15 Vertical Sidewall 2.25 57 D RA1485 cULus, FM, 1,2,3,9 (Pendent or Upright) LPCB (1)cULus Listed Corrosion Resistant sprinkler when ordered with available Polyester coating. (2)cULus Listed Corrosion Resistant sprinkler when ordered with available Electroless Nickel PTFE plating. (3)Available with FM approved Polyester coating in black or white. (4)Available with LPCB and VdS approved Polyester coating. (5)VdS and EC approvals of the F1FR56 Concealed Pendent sprinkler are for 155°F(68°C)temperature rated sprinklers only.VdS approved sprin- klers must use Norbulb brand glass bulbs with the 1/2-inch(12.7mm)adjustment Model CCP cover plate only. (6) Model F1FR56 Concealed Pendent and Model F1FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates, available as either standard depth with 1/2-inch(12.7mm)of adjustment or low profile with 5/16-inch(8.0 mm)of adjustment. (7)cULus Listing of the F1FR56 Horizontal Sidewall sprinkler is for Light and Ordinary Hazard occupancies only. FM Approval of the F1FR56 Hori- zontal Sidewall sprinkler is for Light Hazard occupancies only. (8)cULus Listing and FM Approval of the F1FR56 Recessed Horizontal Sidewall sprinkler is for Light Hazard occupancies only. (9)The F1FR56 Vertical Sidewall sprinkler is listed and approved for use only in Light Hazard occupancies. Minimum to maximum deflector to ceil- ing distance shall be 4 inches to 12 inches(102mm to 305mm).LPCB approval of the F1FR56 Vertical Sidewall sprinkler is for installation in the Pendent position only. 3. Listed and Approved Temperature Ratings Ordinary Temp. Intermediate Temp. High Temp. Classification Classification Classification Deflector/ 100°F(38°C) Max.Ambient 150°F(65°C) Max.Ambient 225°F(107°C)Max. • Model Orientation Temp. Temp. Ambient Temp. 135°F(57°C) 155°F(68°C) 175°F(79°C) 200°F(93°C) 286°F(141°C)Temp. Temp. Rating Temp. Rating Temp. Rating Temp. Rating Rating Orange Bulb Red Bulb Yellow Bulb Green Bulb Blue Bulb Pendent cULus F1FR28 Recessed Pendent cULus -- Upright cULus F1FR40 Pendent VdS Recessed Pendent VdS -- Pendent cULus F1FR42 Recessed Pendent cULus -- Upright cULus F1FR42LL Pendent -- cULus, ULH -- Recessed Pendent -- cULus, ULH -- Pendent cULus F1 FRXLH Recessed Pendent cULus -- Upright cULus Pendent cULus, FM, LPCB,VdS, EC Recessed Pendent cULus, FM, LPCB,VdS, EC -- F1FR56 Concealed Pendent* cULus cULus,VdS,EC cULus -- Upright cULus, FM, LPCB,VdS, EC "Conventional (Pendent or Upright)" LPCB,VdS, EC Pendent -- cULus, ULH -- F1FR56LL Recessed Pendent -- cULus, ULH -- Concealed Pendent* -- cULus, ULH -- Horizontal Sidewall cULus, FM F1FR56 Recessed Horizontal Sidewall cULus, FM -- F1FR56 Vertical Sidewall(Pen- dent or Upright) cULus, FM, LPCB * Model F1FR56 Concealed Pendent and Fl FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates. For Ordinary Temperature Classification sprinklers use a 135°F (57°C) temperature rated cover plate. For Intermediate Temperature Classification sprinklers use a 165°F (74°C) temperature rated cover plate. Recessed Escutcheon Data Listed and Approved Recessed Escutcheons Deflector/ Model F1 Model F2 Model FP Model Orientation (Fig. 1 &3) (Fig. 1 &3) (Fig.2) SIN 3/4-inch(19mm) 1/2-inch(12.7mm) 1/2-inch(12.7mm) adjustment adjustment adjustment F1FR28 Recessed Pendent cULus cULus cULus RA1411 F1FR40 Recessed Pendent VdS VdS VdS RA1418 F1FR42 Recessed Pendent cULus cULus cULus RA1413 F1FR42LL Recessed Pendent cULus, ULH cULus, ULH cULus, ULH RA1410 F1FR42XLH Recessed Pendent cULus cULus cULus RA1413 - F1FR56 Recessed Pendent cULus, LPCB,VdS, cULus, FM, LPCB, cULus, VdS, EC RA1414 EC VdS, EC F1FR56LL Recessed Pendent cULus, ULH cULus, ULH cULus, ULH RA1415 F1FR56 Recessed Horizontal Sidewall cULus cULus, FM cULus RA1435 4. —.4.--- 2 1/4"HOLE D/A. [57.2mm] 1 15/16"DIA J [49.2mm] TURN COLLAR I Ti 1" X 1/2" REDUCER UNTIL TIGHT AGAINST SPRINKLER WRENCH BOSS \ \ / FACE OF FITTING —o TO FACE OF CEILING DIMENSION II \ ( Fl ESCUTCHEON II C S II AT MAXIMUM RECESS = 1'[25.4mm] T� L -__ _.1 AT MINIMUM RECESS = 3/8'[9.5mmJ F1 ESCUTCHEON �/1//1 F2 ESCUTCHEON 3/4 rismm] e 1.1.-1,� AT MAXIMUM RECESS = 3/4'[19mm] ADJUSTMENT . I ®�sd� AT MINIMUM RECESS = 3/8'[9.5mm] F2 ESCUTCHEON • _ II, IW 1/2'[12.7mm] t ! Ii4 ADJUSTMENT a 1� ' F1 ESCUTCHEON 1 1/6" AT MAXIMUM RECESS = 7/8[22.2mm] ` U �� [3.2mm] — /AT MINIMUM RECESS = 1-5/8'[41.3mm] F2 ESCUTCHEON `,k4: :i? AT MAXIMUM RECESS = 1-1/8'[28.6mm] SI I�' L AT MINIMUM RECESS = 1-5/8'[41.3mm] 2 27/32"0/4. [72.2mm] Fig. 1 Model F1FR56,F1FR56LL,F1FR42, F1 FR40,F1FR42LL,F1FRXLH&F1FR28 Recessed Pendent sprinkler with Model F1 or F2 escutcheon L =1 II I 1" X 1/2" REDUCER 2 5/8" DIA. [66.7mm] HOLE IN CEILING 2 5/16" DIA. [58.7mm] —_ CUP IL CEILING It m FACE OF FITTING Wi— TO FACE OF CEILING ®���� IIIII�� —s IIIIIII DIMENSION :j: ni -- — ni ii - ii I AT MAXIMUM RECESS = 1-1 2"38mm ,I, Ig 1 ;ir,I 5. [ 1 I I AT MINIMUM RECESS = 1[25.4mmJ A ,4, �, AT MAXIMUM RECESS = 9/16[14.3mm] 1 � � w.� /2[12.7mmJ �,,,�� AT MINIMUM RECESS = 1'[25.4mmJ ADJUSTMENT ,,M �_ ' •,,, •3.1/4' DIA. t [82.6mm] • Fig.2 Model F1FR56,F1FR56LL, F1FR42,F1 FR40,F1FR42LL,F1FRXLH&F1FR28 Recessed Pendent sprinkler with Model FP escutcheon 5. FACE OF FITTING TO FACE OF CEILING DIMENSION Fl ESCUTCHEON A AT MAXIMUM RECESS = 1 725.4mm] AT MINIMUM RECESS = 3/879.5mm] N F1 ESCUTCHEON F2 ESCUTCHEON AT MAXIMUM RECESS = 1 3/8'[34.9mm] AT MAXIMUM RECESS = 3/4"[19mm] I / AT MINIMUM RECESS = 2-1/16752.4mm] AT MINIMUM RECESS = 3/8"[9.5mm] F2 ESCUTCHEON AT MAXIMUM RECESS = 1-5/8741.3mm] -2 1/4" HOLE DIA. it 1/8"" AT MINIMUM RECESS = 2-1/16 752.4mm] [57.2mm] [3.2mmJ 1" X 1/2" REDUCER 1 r--,--- ,r I ,\� t (-Vail, -1-7 (1) 1 111* 4"-12" 1 15/16" DIA.\/xxx xiM __ 1111 r\. 5: -- [101.6mm-304.8mm] 1 [49.2mm] ixx11111 2 27/32" DIA. CEILING TO I 11111 11111I -L [72.2mm] DEFLECTOR J �) TURN COLLAR UNTIL TIGHT AGAINST k WRENCH BOSS.SPRINKLER Fl ESCUTCHEON 3/4719mm] ADJUSTMENT -*- F2 F2 ESCUTCHEON 1/2[12.7mm] ADJUSTMENT OI RECESSED HSW W/F1 OR F2 ESCUTCHEON (1) FM APPROVED FOR 4" - 6" [101.6MM - 152.4MM] CEILING TO DEFLECTOR WITH F2 ONLY. Fig.3 Model Fl FR56 Recessed Horizontal Sidewall sprinkler with Model Fl or F2 escutcheon 1" x 1/2" REDUCING TEE OR ELBOW 7 in n r 2 5/8" DIA. HOLE IN CEILING 2 5/16" DIA — CLIP —.,=i i= � lb 1 9/2" MAX. ;;,;;;;;1 , lit-C :11111 ,; ,lig INS /// i� FACE OF FITTING ' // Kg II1I TO FACE OF CEILING DIMENSION CEILING) �° ,�1� .. /A, /////// t , �� 1�2' MAX. �`-- ..�'-�' 15/16" COVER ADJUSTMENT COVER PLATE ASSEMBLY �3 5/76" DIA. SPRINKLER / • CONCEALED, 1/2" ADJUSTMENT 017FGO1A Fig.4 • Model F1 FR56/F1 FR56LL Concealed Pendent sprinkler with standard depth 1/2-inch(12.7mm)adjustment-Model CCP cover plate 6. 1" x 1/2" REDUCING TEE OR ELBOW IllIH, — it IT -, -, 2 5/8" DIA. 2 5/16" DIA — HOLE IN CEILING L- -J CUP —,_�_��_�—; �, 1 1 2 MAX. __ _ IIm-lil / � — FACE OF FITTING ;//"""A 1111111[111 TO FACE OF CEILING „xx,T 1,x/xx.xx DIMENSION U_ aACEILING -__ 44_ """'V 5/16" MAX. 3/4" COVER ADJUSTMENT COVER PLATE / I ASSEMBLY 3 5/16" DIA. SPRINKLER CONCEALED, 5/1 6" ADJUSTMENT 017F602A Fig.5-Model Fl FR56/F1 FR56LL Concealed Pendent sprinkler with low profile 5/16-inch(8.0mm)adjustment-Model CCP cover plate Maintenance Material Data The Model Fl FR Series sprinklers should be inspected and the sprinkler system maintained in accordance with NFPA Frame: DZR Brass, QM Brass, or Low Lead Brass 25. Do not clean sprinklers with soap and water,ammonia or Deflector: CDA Alloy 220, 260, or 510 any other cleaning fluids.Remove dust by using a soft brush Load Screw\Pintle: CDA Alloy 360 or 544 or gentle vacuuming.Replace any sprinkler which has been painted(other than factory applied)or damaged in any way. Cup: CDA Alloy 651 or 693 A stock of spare sprinklers should be maintained to allow Washer: Nickel Alloy 440 or 360,coated with PTFE quick replacement of damaged or operated sprinklers. Adhesive Tape Finishes t') Bulb: Glass Standard Finishes Sprinkler Escutcheon Cover plate') Bronze Brass Chrome Ordering Information Chrome Plated Chrome White Specify: Polyester Plated 1. Sprinkler Model: [F1FR28][F1FR40][F1FR42] Coated(4)(5)(6) White Painted [F1 FR42LL][F1 FRXLH][F1 FR56][F1 FR56LL] Special Application Finishes 2. Sprinkler Deflector/Orientation: [Pendent][Recessed Sprinkler Escutcheon Cover plate(') Pendent][Upright][Conventional][Horizontal Sidewall] Electroless Nickel Electroless Nickel Bright Brass [Recessed Horizontal Sidewall][Vertical Sidewall] PTFE s PTFE 3. Sprinkler threads: [1/2-inch NPT][ISO 7-R1/2] Bright Brass Bright Brass Black Plating 4. Sprinkler Temperature Rating: [135°F (57°C)][155°F Black Plated Black Plated Black Paint Black Paint(2)16) Black Paint Off White (68°C)][175°F(79°C)][200°F(93°C)][286°F(141°C)] Off White(2)(6) Off White Satin Chrome 5. Sprinkler Finish Chrome Dull Chrome Dull 6. Escutcheon Model: [F1][F2][FP] (1)Other finishes and colors are available on special order. Consult the 7. Escutcheon Finish (where applicable) factory for details.Custom color painted sprinklers may not retain their 8. Cover plate Model: [standard profile CCP 1/2-inch UL Corrosion resistance listing.Coverplate custom paint is semi-gloss, (12.7mm) adjustment][low profile CCP 5/16-inch unless specified otherwise. (2) cULus Listed only. (8.0mm) adjustment] (3) 200°F(93°C)maximum. 9. Cover plate Temperature Rating: [135°F(57°C)for use (4) cULus listed "corrosion resistance" applies to SIN Numbers RA1435 with Ordinary Temperature sprinklers][165°F (74°C) (HSW), RA1485(VSW), RA1425 (Upright), RA1414 (Pendent) and for use with Intermediate Temperature sprinklers] RA1415 (Pendent) in standard black or white. Corrosion resistance in 10. Cover plate Finish • other polyester colors is available upon request. (5) FM Approvals finish as"Polyester coated"applies to SIN Number RA1414,RA1435 and RA1425 in standard black or white. Note: When Model F1 FR Series Recessed sprinklers are ordered, the (6)LPCB and VdS Approved finish applies only to RA1425, RA1414,RA1418 sprinklers and escutcheons are packaged separately. (VdS)and RA1475. (7)cULus listed Corrosion Resistant 7. Reliable. . . For Complete Protection . Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. • Automatic sprinklers • Deluge valves • Flush automatic sprinklers • Detector check valves • Recessed automatic sprinklers • Check valves • Concealed automatic sprinklers • Electrical system • Adjustable automatic sprinklers • Sprinkler emergency cabinets • Dry automatic sprinklers • Sprinkler wrenches • Intermediate level sprinklers • Sprinkler escutcheons and guards • Open sprinklers • Inspectors test connections • Spray nozzles • Sight drains • • Alarm valves • Ball drips and drum drips • Retarding chambers • Control valve seals • Dry pipe valves • Air maintenance devices • Accelerators for dry pipe valves • Air compressors • Mechanical sprinkler alarms • Pressure gauges • Electrical sprinkler alarm switches • Identification signs • Water flow detectors • Fire department connection The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for almost 100 years. Manufactured by Reliable Automatic Sprinkler Co., Inc. Recycled ® (800)431 1588 Sales Offices Paper Reliable (800)844381--61058581 48 6051 Sales Corporate Offices Fax Revision lines indicate updated or new data. 11.111111111111111.1111.1111111111.11111111111.11. (914)829 2042 www.reliablesprinkler.com Internet Address EG.Printed H U.S.A.10/16 P/N 9999970300