Report (61) ao\ -o0kL SIEMENS 15201 NW Greenbrier Parkway Suite A-4 Beaverton,Oregon 97006 OFFICE, COPY Phone: (503)207-1900 11G Fax:(503)207-1901 PLEASE PROVIDE COMPLETED NFPA 72 RECORD OF COMPLETION AT FINAL INSPECTION FIRE ALARM SUBMITTAL Washington Square Stance Submittal Version Date Siemens Job Number 44OP-250614 Issued for Review 10.18.2018 Siemens Project Manager Moses Frangopolous Proprietary document for approval only TABLE OF CONTENTS SIEMENS BILL OF MATERIALS & COMPONENT SPECIFICATIONS 2 FIRE ALARM POWER SUPPLY BATTERY AND VOLTAGE DROP CALCULATIONS v- BILL OF MATERIALS SIEMENS FIRE ALARM SUBMITTAL Washington Square Stance Fire Alarm System Panel Components Item Model# Siemens Part# Quantity Color Mfg Description 1 E60H-24MCC-FW 4 White Wheelock Multi-Candela Speaker/Strobe-White,Ceiling Mount-High Fidelity 2 PS-8 1 Red Wheelock Wheelock Power Supply 8-Amp 3 STW 2 White Wheelock Exceder Multi-Candela Strobe-White,Wall Mount 4 TRI-R 500-896224 1 Siemens MXL Control Relay Module w/Monitor Point Catalog Cut Sheets not available PROPRIETARY DOCUMENT FOR APPROVAL ONLY 10/18/2018 SIEMENS Data Sheet Fire Safety& Security Products Intelligent Detection Devices TRI Series — Intelligent Initiating Interface Modules [For use with FireFinder® XLS and MXL Panels] Models TRI-D, TRI-R and TRI-S ARCHITECT AND ENGINEER SPECIFICATIONS • Used as an intelligent initiating interface module for the FireFinder XLS and MXL fire-alarm control panels(FACPs) • Interfaces and supervises normally open(N.0)contacts • Integral single-pole,double-throw(SPDT)relay(up to 4 amps),Model TRI-R • Dual input for Model TRI-D • Multi-color light-emitting diode(LED)indicates detector status (green, €,.k ,red) • Simple front-end access to programming port and wiring terminals • Mounts in a 4"square,2-1/8"-deep standard or double gang box e,-ti4 r 01- • ten,;r Dynamic supervision • 5-x-5-inch faceplate included <rF`- • • Two-wire operation • Compatible with Model DPU or FPI-32 field programmer/tester • Electronic-address programming is simple and dependable • ®UL Listed,eULC Listed; CSFM and NYC Fire Department Approved Product Overview The Model TRI-series of intelligent interface The sole purpose of Model TRI-S is to monitor and modules from Siemens—Fire Safety is designed to report the status of the contact,while Model TRI-R provide the means of interfacing direct shorting incorporates an addressable'Form C'relay. The devices to Model MLC for the FireFinder XLS FACP, relay and contact device input for Model TRI-R are or to Model ALD for the MXL system, respectively. controlled at the same address. The relay and input The Model TRI-series of intelligent interface contact can be controlled as a separate function. modules provides the most advanced method of The relay is typically used where control or shunting address programming and supervision—combined of external equipment is required. with sophisticated FACP communication. Each Model TRI-D is a dual-input module that is designed to Model TRI-series interface module incorporates a supervise and monitor two (2)sets of dry contacts. microcomputer chip. In turn,the microcomputer- Model TRI-D requires two(2)address settings. Model chip technology and its sophisticated bi-directional TRI-D is ideal for monitoring a waterflow switch and its communication capabilities with the FACP, achieve respectivf valve tamper switch. the state of an'Intelligent Device.' Model TRI-series has a multi-color LED that flashes Specifications green when operating normally; .b , if unit is in The Model TRI-series of intelligent interface trouble condition,and red to indicate a change of modules is available in three (3) models. Models status command. Model TRI-D flashes two(2)times— TRI Sand TRI-R are designed to monitor a normally once for each address,and the red LED of Model TRI-R open (N.O.) dry contact. The interface module indicates a change of state in the relay. reports the contact's status to the FACP. TRI Series—Intelligent Initiating Interface Modules 61 79 SIEMENS Industry, Inc. Building Technologies Division Specifications — (continued) Electrical Ratings The microcomputer chip for the Model TRI-series of current Draw: 1.5mA devices has the capacity of storing—in memory— [Active or Standby] identification information as well as important Model TRI-R Relay Ratings: operating status information. 4A,125VAC Resistive: 4A,30VDC Siemens—Fire Safety innovative technology allows all Model TRI-series intelligent interface modules to 3.5A,120VAC[0.6 P.F] be programmed and tested,via Model DPU or the 3.0A,30VDC[0.6 P.F] FPI 32 Programmer I Tester. Each of these Inductive: ill, 2.0A,120VAC[0.4 P.F] 2.0A,120VAC[0.35 P.F] programmer 1 testers is a compact, portable and 2.0A,120VAC[0.35 P.F] menu-driven accessory that makes programming and testing an interface device faster,easier and more dependable than previous methods. Mounting Diagram Model DPU or the FPI-32 eliminates the need for mechanical addressingmechanisms(such as: MOUNTINGR -I SLOTSH FOR 4-INCH program jumpers, DIP switches,or rotary dials), swITCt98ox since either programmer I tester device electronically sets the address of the Model TRI- series into the interface's microcomputer-chip, non- 0 O 0/-R volatile memory. Vibration,corrosion and other rR O[utE 1. � s"- RA�DItLF conditions that deteriorate mechanical addressing � 2, �• mechanisms are no longer a cause for concern. ria N MOUNTING The Model TRI-series of intelligent interface [sl s HOLES FOR modules is fitted with screw terminals for 4 w tiytrt NPLATE connection to an addressable circuit,and is fully compatible on the same circuit with all intelligent Model FP; Model IL and Model ID-60-series ° detectors; Model MSI Series addressable manual stations,or any other addressable intelligent MOUNTING SLOTS modules,such as Model CZM or Model ICP. f'OR DOUBLE-GANG SWTCHBOX All Model TRI-series intelligent interface modules are®UL and <.ULC Listed. Details for Ordering Model Part DScription Shipping Weight Number Number -�4 Oz. Kg. TRI-D 500-896226 Dual4nput-Iatellige4it 7 0 Interface Module Single Input[wl relay] TRI-R 500-896224 Intelligent Interface 7 0.2 Module Single-Input TRI-S 500-896225 Intelligent Interface 7 0.2 Module Notice: This marketing data sheet is not intended to be used for system design or installation purposes. For the most up-to-date information,refer to each product's installation instructions. Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard SIEMENS Industry, Inc. Florham Park,NJ 07932 Brampton,Ontario Building Technologies Division Tel:(973)593-2600 (vi-rs) L6T 5E4/Canada July 2012 5/06 FAX:(908)547-6877 Printed In U.S.A. Tel:(905)799-9937 Supersedestsheet dated URL:www.usa.Siemens.com/Fire FAX:(905)799-9858 COOPER Notification POWERPATHT" NAC POWER SUPPLIES ter, PS-EXP PS-6 PS-8 Description The Wheelock Series PS-6 and PS-8 are 24VDC, filtered and The PS-6 and PS-8 Power Supplies are UL Listed under UL regulated, supervised remote power supply/battery chargers are Standard 864, 9th Edition to be used with any 24 volt Listed used for supervision and expanded power driving capability of Fire Regulated notification appliances.They include the capability Alarm Notification Appliance Circuits. The PS-6 provides 6 amps of to synchronize Wheelock strobes and horns and to silence the power distributed across 4 outputs,while the PS-8 provides 8 Amps horn signal when horn/strobes are operating on two wires. across 4 output. In addition the PS-8 provides additional room in the chassis for accessories like an Addressable Control Module,with mounting studs. Approvals The Power Supplies may be connected to any 12V or 24V(FWR or 'Approvals Include:UL Standard 864,1481,California State DC) Fire Alarm Control Panel (FACP) by using a Notification Appliance Fire Marshal(CSFM), Factory Mutual(FM) Circuit (NAC) or a"Dry Contact". Primary applications include NAC •Compliant with NFPA 72 expansion (supports ADA requirements) and auxiliary power to support system accessories.This unit provides filtered and regulated Inputs 24VDC, up to four (4) Class"B", two (2) Class"A", or two (2) Class •120VAC,50/60Hz,4.25 Amps(PS-6/8)and 5.32 Amps "B"and one (1) Class"A"Notification Appliance Circuits.With the (PS-8)Operating Power in Alarm optional plug-in PS-EXP module the unit supports (8) Class"B"or •240VAC,60Hz,2.42 Amps(PS-6E and 3.22 Amps(PS-8E)' (4) Class"A"Notification Appliance Circuits. Additionally,an auxiliary Operating Power in Alarm power output of 2.5 Amps (disconnected upon AC power loss or an 24VDC Battery Backup Connection alarm condition)or up to 0.240 A of constant power on the PS-8 and .Two(2),12V or 24V NAC Initiating Circuits(8-33V at 5mA) 0.075 A of constant power on the PS-6. FWR or DC The Wheelock Power Supplies can accommodate 7 or 12 AH batteries •Two(2)"Dry"Contact initiating Circuits inside its lockable chassis. Using an external battery cabinet it can .Accepts two(2)Class"A"or two(2)Class"B"circuit inputs charge up to 33 AH batteries (pending UL testing). Two FACP NAC .Built in battery charger for sealed lead acid or gel type circuits or two"Dry"contact initiating circuits can be connected to the inputs.These inputs can then be directed to control supervision and batteries power delivery to any combination of the four(4)outputs.Each output is rated at 3.0 Amps (Class"B")or(Class"A")and can be programmed to generate a steady or Code 3 Temporal Horn sound and a strobe Outputs output under alarm condition.Total load for the PS-6 and PS-8 NAC •NAC outputs are 24VDC,3.0 Amps each,power limited circuits must not exceed the power supplies rated output. •8 Amps on PS-8 and 6 Amps on the P5-6 total alarm current The Power Suppliesunder non-alarm condition provides independent supervision for Class"A"and Class"B" FACP NAC circuits. In the event of circuit trouble,the FACP will be notified via the POWERPATH steered input (IN1 or IN2). In addition there are two sets of trouble reporting terminals, one used for AC power loss reporting and the other for all troubles.The AC power loss reporting,on the common trouble terminals and on IN1 or IN2, can be delayed for either 30 seconds or 170 minutes.The AC power loss terminals will always report the trouble within 1 second after loss of AC power. ULr 11> lo® APPROVED ...Features continued on next page •Capable of four(4),Class"B"circuits •Capable of two(2)Class"A"circuits •Capable of one(1)Class"A"circuit and two(2)Class"B"circuits •Capable of(8)Class"B"or four(4)Class"A"circuits with optional PS-EXP module -Temporal(Code 3),constant voltage output,Wheelock Sync output or True input to output follower mode •Built-in Wheelock synchronization mode that can be fed to any or all of the output circuits •Input and output can be synchronized with"lN>OUT SYNC"mode(DSM,2nd POWERPATH'"or FACP with synchronization protocol is required) •Audible silence capability •Filtered and electronically regulated output •2.5 Amp auxiliary power limited output with reset capability.(Removed upon AC loss or alarm.Automatic reset 30 seconds after AC power returns or the alarm condition is over)or 0.075 Amps(PS-6)or 0.240 Amps(PS-8)of auxiliary power limited output which remains on during AC loss or an alarm condition when configured for 24 hour battery backup Supervision •Compatible with 12V or 24V(FWR or DC)FACP •Signaling appliance circuits are supervised and steered to either IN1 or IN2 •10K Ohm,1 Watt(Wheelock Model#MPEOL)End of Line Resistor(EOLR)for supervision of all outputs •37 distinguishable trouble diagnostics •AC loss trouble reported over a separate set of contacts(delay of 1 second) •All troubles are reported over the common trouble contacts(AC loss can have a delay of 30 seconds or 170 minutes) •Automatic switchover to standby battery when AC fails •Thermal and short circuit protection with auto reset •Input and output status LED indicators •AC fail supervision •Battery presence and low battery supervision •Ground Fault Detection,with diagnostics to indicate which circuit fault is on •Latching LED's for NAC trouble annunciation and Diagnostic trouble LED's(latching can be disabled) Power •Not Battery Dependent •Automatic switch over to standby batteries when AC fails •Supports sealed lead acid or gel type batteries •Fused battery protection •Thermal and short circuit protection with auto reset •Supports both 7AH or 12AH batteries in the same cabinet Effective January 2016 Technical Data TD450017EN Supersedes January 2015 Wheelock E5OH & E6OH High Fidelity Speakers & Speaker Strobes Description �,V The Wheelock E50H Wall and E60H Ceiling Speakers and Speaker Strobes are designed for high fidelity sound output for indoor �• applications. With the widest frequency response range(300 to 8000 Hz)in the industry,the EH product line features leading intelligibility with crisp,clear voice messages and tone signaling, ideal for emergency communications, mass notification,and voice 1 , evacuation. Providing a sleek aesthetic appearance,the wall and ceiling appliances feature dual voltage(25/70 VRMS)capability and field-selectable taps from 1/8 to 2 watts. For faster and easier installation,the low profile design incorporates a speaker mounting ,, ;. .ae plate,and each model has al built-in level adjustment feature and snap on cover with no visible mounting screws. For visible signaling to meet the hearing impaired,the Series EH ;` Speaker Strobe models incorporate the low current draw of the RSS ,���• Strobes. • •:� Strobe options for wall mount models include Wheelock patented .: •::.••'` MCW multi-candela strobe with field selectable candela settings of 15/30/75/110cd or the high intensity MCWH strobe with field selectable 135/185cd. Ceiling mount models are available in Wheelock patented MCC multi-candela ceiling strobe with field selectable intensities of 15/30/75/95cd or the high intensity MCCH strobe with field selectable 115/177cd. The strobe portion of all Series EH Speaker Strobes may be synchronized when used in conjunction with the Wheelock DSM -i".:-.7-:``'7." •' Sync Modules,Wheelock Power Supplies or other manufacturers .:14604474i,,,„ ,,,,'..., .--i4' 'II o- panels incorporating the Wheelock Patented Sync Protocol. Wheelock synchronized strobes offer an easy way to comply with w ADA recommendations concerning photosensitive epilepsy. — Series EH Speaker Strobes are UL Listed for indoor use under Standard 1971 (Signaling Devices for the Hearing-Impaired)and Standard 1480(Speaker Appliances),and ULC listed under CAN/ ULC-S526(Visual-audible Signal Appliances, Fire Alarm)and under CAN/ULC-S541 (Speakers, Fire Alarm). All inputs employ IN/OUT wiring terminals for fast installation using#12 to#18 AWG wiring. Color options for the Series EH Speakers and Speaker Strobes are red and white. ET.N Powering Business Worldwide Technical Data TD450017EN Wheelock E5OH &E6OH High Fidelity Effective January 2016 Speakers&Speaker Strobes Features Drawings • High Fidelity Sound Output 5.00r..T.46— • Efficient design for high intelligibility at minimum wattage across a frequency range of 300 to 8000 HZ , • 6 Field Selectable Settings in 1 Device +'�Il • Wall mount models are available with Field Selectable Candela Settings of 15/30/75/110cd or 135/185cd(Multi-Candela models) 6.°° i' or 1575cd(Single Candela model) ���' VgigRggegei I0,- • Ceiling mount models are available with field selectable candela =10 settings of 15/30/75/95cd or 115/177cd(Multi-candela models) • Field Selectable Taps • 1/8 watt up to 2 watts • 25 or 70 VRMS operation ,,, res-r.--1101.1• Easy-to-Install • Low profile design incorporates speaker mounting plate for faster and easier installation fiao°$°°• Snap on grille cover with no visible mounting screws • Quick installation with IN/OUT screw terminals using#12 to00000000000 0000000000 0000000000 #18 AWG wires • 4" square backbox prevents wire damage \ 0000000 • Series E50H-No extension ring required • Series E60H-Optional Extender(E60 Ext) is available for mounting to 4" square backboxes • Strobe Synchronization Components Figure 1.E5OH(top)and E6OH(bottom)Speakers-Front&Side Views • Meet synchronizing standards with Wheelock's DSM Sync Modules, PS Power Supplies or SAFEPATH products5.00 8 5 • Compliance , • UL 1971, UL 1480, ULC-S526, ULC-S541 - �' • Low frequency requirements of UL 464(520 Hz)to meet +.____,r,_,_ �� NFPAs 520 Hz tone requirements for sleeping areas • California State Fire Marshal(CSFM) 6J4 IIPTI • ADA/NFPA/ANSI/OSHA • FCC Part 15, ICES Note: All CAUTIONS and WARNINGS are identified by the symbol A.All warnings are printed in bold capital letters. L..] A WARNING 07385 s,• PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED-INSTALLATIONr INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING J THIS PRODUCT.VISIT WWW.EATON.COM/MASSNOTIFICATION OR CONTACT EATON FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR °°° °° l ■ WARNINGS COULD RESULT IN IMPROPER APPLICATION,INSTALLATION (I1��---,� Il =�f AND/OR OPERATION OF THESE PRODUCTS II AN EMERGENCY SITUATION, a\ WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. K*, 000 aoa a / Figure 2.E6OH(top)and E6OH(bottom)Speaker Strobes-Front&Side Views General Notes • Strobes are designed to flash at 1 flash per second minimum over their"Regulated Voltage Range:' Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL 1971. 2 EATON www.eaton.com Wheelock E5OH &E6OH High Fidelity Technical Data TD450017EN Speakers&Speaker Strobes Effective January 2016 Table 1. Maximum RMS Current UL/ULC Max Current a 24MCW/24MCC 24MCWH/24MCCH 241575W Regulated Voltage Model Range VDC 15 30 75 95 110 115 135 177 185 E5OH 16.0-33.0 0.060 0.092 0.165 0.220 0.300 0.420 E6OH 16.0-33.0 0.060 0.105 0.189 0.249 0.300 0.420 Table 2. UL Listed Models and Ratings UL Reverberant dBA at 10 Feet b Model 1/8 watts C 1/4 watts 1/2 watts 1 watts 2 watts E5OH Speaker Strobe 73 76 79 82 84 E6OH Speaker 74 77 80 83 85 E6OH Speaker Strobe 74 77 80 82 85 Table 3. Specification&Ordering Information Mounting Sync w/DSM or Model Order# Strobe Candela Red White Lettering Wall Ceiling Options Wheelock Power Supplies Speakers E50H-R 9863 X No Lettering X E,AA E50H-W 9864 X No Lettering X E,AA E50H-ALW 3577 X ALERT X E,AA E60H-R 9867 X No Lettering X E E60H-W 9874 X No Lettering X E E60H-ALW 3554 X ALERT X E Speaker Strobes E50H-24MCW-FR 0092 15/30/75/110 X FIRE X E,BB X E5OH-24MCW-FW 0093 15/30/75/110 X FIRE X E,BB X E5OH-24MCW-ALR 3559 15/30/75/110 X ALERT X E,BB X E50H-24MCW-ALW 3560 15/30/75/110 X ALERT X E,BB X E50H-24MCW-NW 3575 15/30/75/110 X No Lettering X E,BB X E5OH-24MCWH-FR 0094 135/185 X FIRE X E,BB X E5OH-24MCWH-FW 0097 135/185 X FIRE X E,BB X E5OH-24MCWH-ALW 3561 135/185 X ALERT X E,BB X E60H-24MCC-FR 0187 15/30/75/95 X FIRE X E x E60H-24MCC-FW 0188 15/30/75/95 X FIRE X E x E60H-24MCC-NW 0950 15/30/75/95 X No Lettering X E X E60H-24MCC-ALW 3555 15/30/75/95 X ALERT X E x E60H-24MCCH-FR 0189 115/177 X FIRE X E x E6OH-24MCCH-FW 0190 115/177 X FIRE X E X Extender Ring E60EXT-R° 3578 X E60EXT-W° 3757 X Table 4. Specifications Physical Material/Lens(Material type) Red or white textured UV stabilized,colored impregnated engineered plastic.Exceeds 94V-0 UL flammability rating./ GE LEXAN 943A Weight E5OH Speaker:1.5 lbs(0.68 kg);E5OH Speaker Strobe 1.6 lbs(0.73 kg);E6OH Speaker:1.6 lbs(0.73 kg);E6OH Speaker Strobe 1.7 lbs(0.77 kg); Dimensions E5OH Speaker: 5"W x 5"H x 1.47"D;E5OH Speaker Strobe: 5"W x 6.74"H x 2.58"D;E6OH Speaker:7.38"Diameter x .83"D;E6OH Speaker Strobe:7.38"Diameter x 3.02"D Operating Temperature Indoor:33.8°F to 120.2°F(0°C to 49°C)and maximum humidity of 93% Mounting&Wire Connections Mounting(indoor only) 4"square backbox prevents wire damage;Series E5OH-No extension ring required;Series E6OH-Optional Extender (E60 Ext)is available for mounting to 4"square backboxes,E50 SSB,E50 SB for surface mount of E5OH Wire Connections #12 through#18 AWG Power&General Operating voltage 25/70 VRMS Strobe Output Rating UL 1971,ULC S526 Strobe Flash Rate Strobes are designed to flash at 1 flash per second Synchronization Models Strobes can be synchronized with Wheelock's DSM Sync Modules,PS Power Supplies or SAFEPATH products,using Wheelock patented sync protocol Frequency Range 300 Hz to 8000 Hz a RMS current ratings are per UL maximum RMS method.UL max current rating is the maximum RMS current within the listed voltage range(16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage(16v for 24v units). For audibles the max current is usually at the maximum listed voltage(33v for 24v units). For unfiltered FWR ratings,see installation instructions. b dBA ratings are based on testing under UL Standard 1480. c 1/8 watt tap is for private mode only. d E60 EXT is an attractive extender ring that mounts behind the speaker to permit mounting to a 4"square x 2 1/8"deep electrical box without need for an extension ring on the box. EATON www.eaton.com 3 Technical Data TD450017EN Wheelock E5OH & E6OH High Fidelity Speakers&Speaker Strobes Effective December 2015 Architects and Engineers Specifications Wheelock E50H-The speaker appliances shall be Wheelock E5OH Wheelock E6OH-The speaker appliances shall be Wheelock High Fidelity Speakers,and the High Fidelity Speaker Strobe appli- E6OH High Fidelity Speakers,and the High Fidelity Speaker Strobe ances shall be Wheelock E5OH Speaker Strobes or approved equals. appliances shall be Wheelock Series E6OH Speaker Strobes or The speakers shall be UL Listed under UL 1480 for Fire Protective approved equals.The speakers shall be UL Listed under UL 1480 Service and speakers equipped with strobes shall be listed under UL for Fire Protective Service and speakers equipped with strobes shall 1971 for Emergency Devices for the Hearing-Impaired.In addition, be listed under UL 1971 for Emergency Devices for the Hearing- the strobes shall be certified to meet the requirements of FCC Part Impaired. In addition,the strobes shall be certified to meet the 15,Class A. requirements of FCC Part 15,Class A. All speakers shall be designed for a field selectable input of either 25 All speakers shall be designed for a field selectable input of either 25 or 70 VRMS,with selectable power taps from 1/8 watt to 2 or 70 VRMS,with selectable power taps from 1/8 watt to 2 watts. watts.All models shall have listed sound output of up to 87 dB at All models shall have listed sound output of up to 87 dBA at 10 feet 10 feet and a listed frequency response of 300 to 8000 Hz.The and a listed frequency response of 300 to 8000 Hz.The speaker speaker shall also incorporate a sealed back construction.All inputs shall incorporate a sealed back construction.All inputs shall employ shall employ terminals that accept#12 to#18 AWG wire sizes. The terminals that accept#12 to#18 AWG wire sizes. The strobe portion strobe portion of the appliance shall produce a flash rate of one(1) of the appliance shall produce a flash rate of one(1)flash per second flash per second over the Regulated Voltage Range.The strobe shall over the Regulated Voltage Range and shall be of low current design. be of low current design.Where Multi-Candela Speaker Strobes are Where Multi-Candela Speaker Strobes are specified,the strobe specified,the strobe intensity shall have field selectable settings intensity shall have field selectable settings and shall be rated per and shall be rated per UL 1971 15/30/75/95cd or 115/177cd for UL 1971 at 15/30/75/110cd or 135/185cd for wall mounting. The ceiling mount. The selector switch for selecting the candela shall selector switch for selecting the candela shall be tamper resistant. be tamper resistant. When synchronization is required,the strobe portion of the appliance shall be compatible with Wheelock DSM When synchronization is required,the strobe portion of the sync modules or the Wheelock Power Supplies with built-in Patented appliance shall be compatible with the Wheelock's DSM sync Sync Protocol.The strobes shall not drift out of synchronization at modules or Wheelock Power Supplies with built-in Patented Sync any time during operation. If the sync module or Power Supply fails Protocol.The strobes shall not drift out of synchronization at any to operate, (i,e.,contacts remain closed),the strobe shall revert to a time during operation. If the sync module or Power Supply fails to non-synchronized flash rate. operate, (i.e.,contacts remain closed),the strobe shall revert to a The speaker and speaker strobe appliances shall be designed non-synchronized flash rate. for indoor flush mounting.The speaker and speaker strobe shall The speaker and speaker strobe appliances shall be designed for incorporate a speaker mounting plate with a snap-on grille cover indoor flush mounting to 4"x 2-1/8"electrical boxes without need with no visible screws for a level,aesthetic finish and shall mount to for an extension ring or surface mounting to Wheelock's E50SB standard electrical hardware. The finish of the Series E6OH Speakers • or E5OSSB surface boxes.The speaker and speaker strobe shall and Speaker Strobes shall be white or red. All speaker and speaker incorporate a speaker mounting plate with a snap-on grille cover.The strobe appliances shall be backward compatible. finish of the Series E5OH speakers and speakers strobes shall be The speaker shall be listed to the low frequency requirements of UL white or red. 464(520 Hz)to meet NFPAs 520 Hz tone requirements for sleeping The speaker shall be listed to the low frequency requirements of UL 464 areas. (520 Hz)to meet NFPAs 520 Hz tone requirements for sleeping areas. UL 1971, UL 1480, ULC-S526, ULC-S541,CSFM, FCC. UL 1971, UL 1480, ULC-S526, ULC-S541,CSFM, FCC. Note:Due to continuous development of our products,specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc.,dba Eaton standard terms and condition3. — `r r=lam WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Eaton 1000 Eaton Boulevard Cleveland,OH 44122 United States Eaton.com Eaton Life safety&mass notification solutions 273 Branchport Ave. Long Branch,NJ 07740 www.eaton.com/massnotification • ©2016 Eaton E_T�IV All Rights Reserved Eaton is a registered trademark. Printed in USA Publication No.TD450017EN All other trademarks are property Powering Business Worldwide January 2016 of their respective owners. HN Series Effective October 2014 HS Series Technical Data TD0O1017EN Supersedes May 2013 ST Series Exceder Strobe, Horn Strobe, and Horn Notification Appliances Description The Wheelock Exceder Series of notification appliances feature a sleek modern design that will please building owners with reduced total cost of ownership. Installers will benefit from its comprehensive feature list, including the most candela options in one appliance, low current draw,no tools needed for setting changes,voltage test points, 12/24VDC operation, universal 6 mounting base and multiple mounting options for both new and retrofit construction. The Wheelock Exceder Series incorporates high reliability and high FIREefficiency optics to minimize current draw allowing for a greater F' 1 R \ number of appliances on the notification appliance circuit.All strobe models feature an industry first of 8 candela settings on a single appliance. Models with an audible feature 3 sound settings(90,95, 99 dB).All switches to change settings,can be set without the use of a tool and are located behind the appliance to prevent tampering. Wall models feature voltage test points to take readings with a voltage meter for troubleshooting and AHJ inspection. II I 'N The Wheelock Exceder Series of wall and ceiling notification appliances feature a Universal Mounting Base(UMB)designed to simplify the installation and testing of horns,strobes,and combination horn strobes.The separate universal mounting base can be pre-wired to allow full testing of circuit wiring before the appliance is installed and the surface is finished. It comes complete with a Contact Cover for protection against dirt,dust,paint and damage to the contacts.The Contact Cover also acts as a shunting device to allow pre-wire testing for common wiring issues. The Contact Cover is polarized to prevent it from being installed incorrectly and prevents the appliance from being installed while it is on the UMB. When the Contact Cover is removed the circuit will show an open until the appliance is installed.The UMB allows for consistent installation and easy replacement of appliances if required.Wall models provide an optional locking screw for extra secure installation,while the ceiling models provide a captivated screw to prevent the screw from falling during installation. Er AT,,,N Powering Business Worldwide Technical Data TD001017EN HN Series Effective October 2014 HS Series ST Series Features • Environmentally friendly • • Sleek modern aesthetics Low current draw • Finger slide switches • Up to 9 models now in 1 appliance draw@ • Voltage test points • 12/24VDC on a single appliance • Multiple voltages • Easy to remember model numbers • 3 Audible settings O Patented • 90, 95,99 dB Note:All CAUTIONS and WARNINGS are identified by the symbol A.All warnings are printed in bold capital letters. • Industry leading-8 candela settings on 1 device • Wall: 15/1575/30/75/95/110/135/185 A WARNING • Ceiling: 15/30/60/75/95/115/150/177 PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING = THIS PRODUCT.VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, .; WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes • Strobes are designed to flash at 1 flash per second minimum over their"Regulated Voltage Range" • All candela ratings represent minimum effective strobe intensity based on UL Standard 1971. • Universal mouting base • Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32°F to • Ceiling and wall 120°F(0°C to 49°C)and maximum humidity of 93% (±2%) UL • Mounts to 5 backbox types: 1 gang, 2 gang,4" square, 464(85% UL 1971). 3.5"octal.&4"octal. (100mm for international customers) • Series Exceder horns are under UL Standard 464 for audible Universal mounting base Contact cover signal appliances(Indoor use only). Compatibility and requirements : �, I . • Synchronize using the Wheelock°Sync Modules or panels with :' � t built-in Wheelock®Patented Sync Protocol `-,`" • Compatible with UL"Regulated Voltage" using filtered VDC or ''' ; ' unfiltered VRMS input voltage _-- ''` .. • � « „'I • Strobes produce 1 flash per second over the"Regulated Voltage" range Common base for wall and ceiling with 5 mounting options Compliance • Voltage test points for quick troubleshooting and easy spot • UL 1971, UL 464, ULC,CSFM, FM checking(wall models only) • ADA/NFPA/ANSI/OSHA • RoHS O''''''' '..:At F IT i 2 EATON www.eaton.com HN Series Technical Data TD001017EN HS Series Effective October 2014 ST Series Table 1. Strobe Ratings per UL Standard 1971 UL Max Current,0 24 VDC/24 FWR 12 VDC Regulated Voltage Model Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 ST 8.0-33.0 0.057 0.070 0.085 - 0.135 0.163 0.182 - 0.205 - - 0.253 0.110 0.140 STC 8.0-33.0 0.061 - 0.085 0.103 0.135 0.163 - 0.182 - 0.205 0.253 - 0.110 - Table 2. Horn Strobe Ratings per UL 1971 &Anechoic at 24VDC UL Max Current°O at Anechoic 99 dBA 24 VDC 12 VDC Regulated Voltage Model Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 HS 8.0-33.0 0.082 0.095 0.102 - 0.148 0.176 0.197 - 0.242 - - 0.282 0.125 0.159 HSC 8.0-33.0 0.082 - 0.102 0.141 0.148 0.176 - 0.197 - 0.242 0.282 - 0.125 - UL Max Current r0 at Anecholc 95 dBA 24 VDC 12 VDC Regulated Voltage Model Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 HS 8.0-33.0 0.073 0.083 0.087 - 0.139 0.163 0.186 - 0.230 - - 0.282 0.122 0.153 HSC 8.0-33.0 0.073 - 0.087 0.128 0.139 0.163 - 0.186 - 0.230 0.272 - 0.122 - UL Max Current°at Anecholc 90 dBA 24 VDC 12 VDC Regulated Voltage Model Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 HS 8.0-33.0 0.065 0.075 0.084 - 0.136 0.157 0.184 - 0.226 - - 0.267 0.120 0.148 HSC 8.0-33.0 0.065 - 0.084 0.120 0.136 0.157 - 0.184 - 0.226 0.267 - 0.120 - t0 UL max current rating is the maximum RMS current within the listed voltage range(16-33 VDC for 24 VDC units).For strobes the UL max current is usually at the minimum listed voltage(16 VDC for 24 VDC units).For audibles the max current is usually at the maximum listed voltage(33 VDC for 24 VDC units).For unfiltered ratings,see installation instructions. Table 3. Horn Ratings per UL Anechoic Model Legend Regulated Voltage Model Range VDC 99 dB 95 dB 90 dB HN = Horn R = Red HN 16-33.0 0.064 0.044 0.022 ST = Strobe A = Agent Lettering(strobes only) HNC 16-33.0 0.084 0.044 0.022 HS = Horn Strobe AL = Alert Lettering(strobes only) HN 8.0-17.5 0.047 0.026 0.017 C = Ceiling Mount N = No Lettering(strobes only) HNC 8.0-17.5 .0.047 0.026 0.017 W = White Example 1:STRC=Strobe,Red,Ceiling Mount Table 4. Specification&Ordering Information Example 2:HSR=Horn Strobe,Red,Wall Mount sync w/DSM or Example 3:HSW=Horn Strobe,White,Wall Mount Wheelock Power 12/24 Mounting Example 4:STW-AL=Strobe,White,Wall Mount,Alert Lettering Model Strobe Candela Supplies VDCO Options p Horn Strobes - HSR 15/1575/30/75/95/110/135/185 X X UMB© •0 �- � HSW 15/1575/30/75/95/110/135/185 X X UMBO -- 1 0 HSRC 15/30/60/75/95/115/150/177 X X UMB® t HSWC 15/30/60/75/95/115/150/177 X X UMBO Llivy ' Strobes fs, - f STR 15/1575/30175/95/110/135/185 X X UMBO "-..' STW 15/1575/30/75/95/110/135/185 X X UMBO r STRC 15/30/60/75/95/115/150/177 X X UMBO STWC 15/30/60/75/95/115/150/177 X X UMBO .i, 40.,,, , , ,,,401 Horn HNR 1 X X UMB® be.� HNW0e/ - ft. , X X UMB© J I HNRC X X UMBO Example:HSR Example:HSWC HNWC (7.:'''''''''J X X UMBD 0 12 VDC models feature 15&15/75 settings OO UMB=Universal Mounting Base EATON www.eaton.com 3 • Technical Data TD001017EN HN Series Effective October 2014 HS Series ST Series Architects and Engineers Specifications The notification appliances shall be Wheelock Exceder Series HS Audible Strobe appliances,Series ST Visual Strobe appliances and Series HN Audible appliances or approved equals.The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired)for Indoor Fire Protection Service.The Series HS and HN Audibles shall be UL Listed under Standard 464(Fire Protective Signaling).All Series shall meet the requirements of FCC Part 15 Class B.All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel(FACP)with the ability to operate from 8 to 33 VDC. Indoor wall models shall incorporate voltage test points for easy voltage inspection. The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one(1)flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan®lens.The Series shall be of low current design.Where multi- candela appliances are specified,the strobe intensity shall have 8 field selectable settings at 15, 15/75,30,75,95, 110, 135, 185 candela for wall mount and 15,30,60,75,95, 115, 150, 177 candela for ceiling mount.The selector switch for selecting the candela shall be tamper resistant.The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required (e.g.,ADA compliance).Appliances with candela settings shall show the candela selection in a visible location at all times when installed. The audible shall have a minimum of three(3)field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3)audible outputs. The Series HS Audible Strobe,ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow mounting to a-single-gang,double-gang,4-inch square,3.5-inch octal,4-inch octal or 100mm European'type back boxes.Two wire appliance wiring shall be capable of directly connecting to the mounting base.Continuity checking of the entire NAC circuit prior to attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel(FACP).The mounting base shall be the same base among all horn, strobe, horn strobe,wall and ceiling models.All notification appliances shall be backwards compatible. The Series HS and ST wall models shall have a low profile measuring 5.24" H x 4.58"W x 2.19" D. Series HN wall shall measure 5.24" H x 4.58"W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68"x 2.63" D.Series HNC ceiling shall have a diameter of 6.68"x 1.50" D. When synchronization is required,the appliance shall be compatible with Wheelock's DSM Sync Modules,Wheelock Power Supplies or other manufacturer's panels with built-in Wheelock Patented Sync Protocol.The strobes shall not drift out of synchronization at any time during operation. If the sync protocol fails to operate,the strobe shall revert to a non-synchronized flash-rate and still maintain(1)flash per second over its Regulated Voltage Range.The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation when used with Wheelock synchronization protocol. Wall Appliances:UL Standard 1971, UL Standard 464,California State Fire Marshal(CSFM), ULC, FM, RoHS Ceiling Appliances:UL Standard 1971, UL Standard 464,California State Fire Marshal(CSFM), ULC, FM, RoHS Note:Due to continuous development of our products,specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc.,dba Cooper Notification standard terms and conditions. NI!� Member WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Eaton 1000 Eaton Boulevard Cleveland,OH 44122 United States Eaton.com Eaton Cooper Notification 273 Branchport Ave. Long Branch,NJ 07740 CooperNotification.com ©2014 Eaton All Rights Reserved Eaton is a registered trademark. E_T.N Printed in USA Publication No.T0001017EN All other trademarks are property Powering Business Worldwide October 2014 of their respective owners. POWERPATH°'Operating Modes(refer to Installation Manual): Normal Mode: Provides constant 24 VDC output upon initiation by a voltage to input IN1 or IN2 or by a contact opening on DRY1 or DRY2.The unit returns to standby mode when the input is deactivated. Wheelock Sync Mode: Provides signals for synchronization of patented Wheelock audible and strobe notification appliances.Audibles can also be silenced in this mode while the strobes continue to flash. In>Out Sync Mode:Accepts a synchronization signal on the input to provide a coded output or synchronized output.This signal may come from a FACP,another POWERPATH or a Wheelock DSM synchronization module.Caution:Do not use strobes on coded output circuits. True Input Follower Mode: Accepts a coded signal on the input to provide a coded output with the same timing as the input. The signal may come from a FACP, another POWERPATH or other coded source. Caution: Do not use strobes on coded output circuits. Temporal Mode: Codes the output voltage in a code-3 temporal pattern to drive audible appliances such as horns, bells or chimes.Caution:Do not use strobes on coded output circuits. Specifications and Ordering Information Model Number Order Input Voltage/Current Approvals Code UL CSFM FM PS-6 105530 6 amp,red enclosure X X X PS-6B 100257 6 amp,black enclosure X X X PS-8 105531 8 amp,red enclosure X X X PS-8B 105830 8 amp,black enclosure X X X PS-6EXP 105083 6 amp power supply with preinstalled expansion module X X X PS-8EXP 105084 8 amp power supply with preinstalled expansion module X X X PS-EXP 105534 4 class B or 2 class A expansion module X X X PS-EXP-RETRO 105527 Field upgrade kit for models prior to January 2010* X X X Input Circuit Input Voltage and Current X=Approved Input voltage Range 8 to 33 VDC *=Pending Input Current @ 12 VDC 0.005 amps #=Contact Technical Input Current @ 24 VDC 0.005 amps Support for additional inforamation on upgrade Output Circuit Output Voltage and Current options Four(4)Class B or Two(2)Class A or One(1)Class A and Two(2)Class"B"or 24 VDC @ up to 3 amps per curcuit 8 Class B or 4 Class A (optional PS-EXP module necessary) Continuous duty up to 3 Amps per circuit,up to 4 Amps maximum per panel Standby Current 0.129 Amps Alarm Current 0.129 Amps Primary PS-6(120 VAC models) 105 to 130 VAC,50/60 Hz @ 4.25 Amps Primary PS-8(120VAC models) 105 to 130 VAC 50/60 Hz @ 5.32 Amps Primary PS-6E(240 VAC models) 210 to 260 VAC,50/60 Hz @ 2.42 Amps Primary PS-8E(240 VAC models) 210 to 260 VAC 50/60 Hz @ 3.22 Amps Secondary Power Charging Capacity 32 Amp hours @ 0.750 Amps per hour Enclosure can house up to two 12 AH batteries Aux Output CP Mode PS-6 up to 75 mA PS-8 up to 250 mA MP Mode 2.5A during non alarm Model Dimensions Weight Comments PS-6/PS-6B 17"H x 13"W x 3.5"D 11.51bs.(Ship)9.4Ibs(Unit) Small profile PS-8/PS-8B 17"H x 15"W x 5.5"D 17.71bs(Ship)15.6Ibs(Unit) Additional room for modules PS-EXP 4.3"H x 3.7"W x 1"D 11 b.(Ship&Unit) Plugs into main pcb on all models Architects and Engineers Specifications • The power supply shall be Wheelock POWERPATHT" Series PS-8, or equivalent.The unit shall be stand alone power supply intended for powering fire alarm notification appliances via its own Notification Appliance Circuit(s) (NAC).The unit shall be UL 864 Listed for power limited operation of outputs and comply with NFPA 70(NEC),article 760. The power supply shall support a full 8A of notification power even if the battery is in a degraded mode and only AC power is connected. The power supply shall be activated by a standard Notification Appliance Circuit(NAC)from any Fire Alarm Control Panel (FACP) or a "Dry contact"opening.The units shall be 8 ampere,24 VDC, regulated and filtered, supervised remote power supply/charger. It shall operate over the voltage range of 8 to 33 VDC or FWR.The primary application of the unit shall be able to expand fire alarm system capabilities for additional NAC circuits to support ADA requirements and to provide auxiliary power to support system accessories or functions.The power supply shall provide four Class"B", two Class"A", or two Class"B"and one Class"A"NAC circuit(s). Eight Class"B"or Four Class"A"circuits shall be available with an optional PS-EXP module.The PS-8 unit shall supply up to 240 mA of auxiliary power that is available during both non-alarm and alarm or auxiliary power of not less than 2.5A at 24 VDC during non-alarm. The power supply shall be capable of charging batteries of up to 33 ampere hours per NFPA 72 at maximum rate of 0.750 Amps per hour. Input activation options shall be from not less than two NAC circuits or Dry Contact closures.These inputs shall have the capability of being directed to any combination of the four NAC circuit outputs. Each NAC circuit output shall be rated at 3 amperes for Class"B" applications or 3 amperes each for Class"A".The outputs shall be programmable to generate a steady or Temporal (Code 3) output and or a synchronized strobe or horn output.The power supply shall provide independent loop supervision for either Class"A"or Class "B''FACP NAC circuits and shall have the capability to"steer"all alarm or trouble conditions to either incoming NAC circuit.The units shall have common trouble terminals.The power supply shall be powered from a 120 VAC source with a current consumption of xx amperes max.The unit shall incorporate short circuit protection with auto reset.The power supply shall incorporate a built in battery charger for lead acid or gel type batteries with automatic switchover to battery back up in the event of AC power failure.The charger shall incorporate fused protection for the batteries and have the ability to report low battery and/or no battery condition(s). Standby current for battery back up shall be 0.129 Amps max.The power supply shall have the ability to latch trouble LED's so the circuit in trouble can be identified.The cabinet dimensions shall be 17"H x 15"W x 5.5"D. The power supply shall be Wheelock POWERPATHT"Series PS-6,or equivalent.The unit shall be stand alone power supply intended for powering fire alarm notification appliances via its own Notification Appliance Circuit(s) (NAC).The unit shall be UL 864 Listed for power limited operation of outputs and comply with NFPA 70(NEC),article 760. The power supply shall support a full 6A of notification power even if the battery is in a degraded mode and only AC power is connected. The power supply shall be activated by a standard Notification Appliance Circuit (NAC)from any Fire Alarm Control Panel (FACP) or a "Dry contact"opening.The units shall be 6 ampere,24 VDC, regulated and filtered,supervised remote power supply/charger. It shall operate over the voltage range of 8 to 33 VDC or FWR.The primary application of the unit shall be able to expand fire alarm system capabilities for additional NAC circuits to support ADA requirements and to provide auxiliary power to support system accessories or functions.The power supply shall provide four Class"B", two Class"A", or two Class"B"and one Class"A"NAC circuit(s). Eight Class"B"or Four Class"A"circuits shall be available with an optional PS-EXP module.The PS-6 unit shall supply up to 200 mA of auxiliary power that is available during both non-alarm and alarm or auxiliary power of not less than 2.5A at 24 VDC during non-alarm. The power supply shall be capable of charging batteries of up to 33 ampere hours per NFPA 72 at a maximum rate of 0.750 Amps per hour. Input activation options shall be from not less than two NAC circuits or Dry Contact closures.These inputs shall have the capability of being directed to any combination of the four NAC circuit outputs. Each NAC circuit output shall be rated at 3 amperes for Class"B" applications or 3 amperes each for Class"A".The outputs shall be programmable to generate a steady or Temporal (Code 3) output and or a synchronized strobe or horn output.The power supply shall provide independent loop supervision for either Class"A"or Class 'B"FACP NAC circuits and shall have the capability to"steer"all alarm or trouble conditions to either incoming NAC circuit.The units shall have common trouble terminals.The power supply shall be powered from a 120 VAC source with a current consumption of xx amperes max.The unit shall incorporate short circuit protection with auto reset.The power supply shall incorporate a built in battery charger for lead acid or gel type batteries with automatic switchover to battery back up in the event of AC power failure.The charger shall incorporate fused protection for the batteries and have the ability to report low battery and/or no battery condition(s).Standby current for battery back up shall be 0.130 Amps max.The power supply shalt have the ability to latch trouble LED's so the circuit in trouble can be identified.The cabinet dimensions shall be 17"H x 13"W x 3.5"D. AWARNING:PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING THIS PRODUCT.FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION,INSTALLA- TION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. NOTE:Due to continuous development of our products,specifications and offerings are subject to change without notice in accor- dance with Wheelock Inc.standard terms and conditions. WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 1 YEAR WARRANTY 59100 PS-6&8 06/11 NJ Location 273 Branchport Ave. Long Branch,NJ 07740 P:800-631-2148 F:732-222-8707 www.coopernotification.com Cooper Notification is Wheelock MEDC SAFEPATH° WAVE COOPER Notification iv r, G a 41 a bpi ,. 0004 fir; 0,0004, e 01,0 4 bbobbi kjbgb:44.1 Vitt 04,0,0,0011 yN�F FAPS-A2 SIEMENS BATTERY&VOLTAGE DROP CALCULATIONS FIRE ALARM SUBMITTAL Washington Square Stance FAPS-A2 SPECIFICATIONS FAPS-A2 BATTERY CALCULATIONS FAPS-A2 PANEL 24 Hours(A)Requirement for Standby Charge: PS-S MODEL 15 Minutes(B)Requirement for Alarm Charge: 15%Design Voltage Drop(20%Max Voltage Drop) 20%(C)Spare Battery Capacity: 3.00 Amp Max Current Draw Per Output 0.13 Amp(F)Standby Total Current Draw 2.50 Amp Max Current Draw Per AUX Output 0.66 Amp(G)Alarm Total Current Draw 8.00 Amp Max Current Draw Per Panel 3.1 Amp Hr(H)Design Standby Charge=(A x F) 14 AWG Wire Gauge 0.2 Amp Hr(J)Design Alarm Charge=(B x G)/60 20.4 VDC Voltage at First Device' 0.7 Amp Hr(K)Additional Capacity Charge=(C x((A x F)+(B x G)160)) 0.13 Amp Standby Current Draw 3.9 Amp Hr(AH)Battery Amp Hour requirement=(H+J+K) 0.13 Amp Alarm Current Draw 7.0 Amp Hr Battery Size 32.0 Amp Hr Max Battery Charging Capacity FAPS-A2 VOLTAGE DROP CALCULATION,RESULTS PERCENT STANDBY ALARM PERCENT OUTPUT VOLTAGE CURRENT CURRENT CURRENT LABEL VOLTAGE DROP DROP DRAW DRAW DRAW OUTPUT-1 NA2-1- 0.57 Volt 2.80% 0.00 Amp 0.53 Amp 17.80% OUTPUT-2 NA2-2- 0.00 Voll 0.00% 0.00 Amp 0.00 Amp 0.00% OUTPUT-3 NA2-3- 0.00 Volt 0.00% 0.00 Amp 0.00 Amp 0.00% OUTPUT-4 NA2-4- 0.00 Volt 0.00% 0.00 Amp 0.00 Amp 0.00% AUX OUTPUT NA2-AX- 0.00 Volt 0.00% 0.00 Amp 0.00 Amp 0.00% Total Current Draw 0.00 Amp 0.53 Amp 6.68% FAPS-A2 VOLTAGE DROP CALCULATIONS OUTPUT-1 LABEL CD MODEL STANDBY ALARM DISTANCE VOLTAGE' Alarm Voltage Drop=VD=R x la FAPS-A2 74V PS-8 ( �'''r[ ,'a", 20.400 170.17 Ft (L)Total Circuit Length(One Leg) NA2-1-01 Wad E60H-24MCC-FW 0.105 41.58 ft 20.396 3.14 Ohm Wire Resistance Per 1000 Feet NA2-1-02 30cd E60H-24MCC-FW 0.105 39.08 fl 20.305 1.07 Ohm (R)Total Circuit Resistance(Both Legs) NA2-1-03 15cd STW 0.057 17.50 ft 20.260 0.00 Amp (Is)Total Current Draw(Standby) NA2-1-04 15cd STW 0.057 14.67 0 20.246 0.53 Amp (la)Total Current Draw(Alarm) NA2-1-05 Wad E60H-24MCC-FW 0.105 21.33 ft 20.221 19.83 Volt (20.4-(la x R))Applied Voltage at Last Device' NA2-1-06 30cd E6SH-24MCC-FW- 0.105 36.00 ft 20.161 0.57 Volt (VD)Voltage Drop 2.80% Percent Voltage Drop 17.80% Percent Current Drew Output-1 OUTPUT-2 _ /ABEL/ABEL._.._. Cl) MODEL T Y ALARM DISTANCE VOLTAGE' Voltage Drop=VD=L`R'la rod i..Tar&ma uPiliT-, .... " Dial Circuit Length(One leg) FAPS-AZ PS-8 - - �.; , 3.14 Ohm Wire Resistance Per 1000 Feet _- ----_.. 0.00 Oh... --(R)-Totut Cirouit R^sis a"c•(B"h Legs) 0.00 Amp (Is)Total Current Draw(Standby) 0.00 Amp (la)Total Current Draw(Alarm) 20.40 Volt (20.4-(la x R))Applied Voltage at Last Device' 0.00 Volt (VD)Voltage Drop 0.00% Percent Voltage Drop 0.00% Percent Current Draw Output-2 4'wws PROPRIETARY DOCUMENT FOR APPROVAL ONLY 10/18/2018 FAPS-A2 VOLTAGE DROP CALCULATIONS CONTINUED OUTPUT-3 LABEL CD MODEL STANDBY ALARM DISTANCE VOLTAGE' Voltage Drop=VD=L'R'la FAPS-A2 PS-8 �i , 20.400 0.00 Ft (L)Total Circuit Length(One Leg) 3.14 Ohm Wire Resistance Per 1000 Feet 0.00 Ohm (R)Total Circuit Resistance(Both Legs) 0.00 Amp (Is)Total Current Draw(Standby) 0.00 Amp (la)Total Current Draw(Alarm) 20.40 Volt (20.4-(la x R))Applied Voltage at Last Device' 0.00 Volt (VD)Voltage Drop 0.00% Percent Voltage Drop 0.00% Percent Current Draw Output-3 OUTPUT-4 LABEL CD MODEL STANDBY ALARM DISTANCE VOLTAGE' Voltage Drop=VD=L`R`la FAPS-A2 PS-8 _m 20.400 0.00 Ft (L)Total Circuit Length(One Leg) 3.14 Ohm Wire Resistance Per 1000 Feet 0.00 Ohm (R)Total Circuit Resistance(Both Legs) 0.00 Amp (Is)Total Current Draw(Standby) 0.00 Amp (la)Total Current Draw(Alarm) 20.40 Volt (20.4-(lax R))Applied Voltage at Last Device' 0.00 Volt (VD)Voltage Drop 0.00% _Percent Voltage Drop 0.00% Percent Current Draw Output-4 AUX OUTPUT LABEL CD MODEL STANDBY ALARM DISTANCE VOLTAGE' Voltage Drop=VD=L`R'la FAPS-A2 PS-8 k' 20.400 0.00 Ft (L)Total Circuit Length(One Leg) 3.14 Ohm Wire Resistance Per 1000 Feet 0.00 Ohm (R)Total Circuit Resistance(Both Legs) 0.00 Amp (Is)Total Current Draw(Standby) 0.00 Amp (la)Total Current Draw(Alarm) 20.40 Volt (20.4-(lax R))Applied Voltage at Last Device' 0.00 Volt (VD)Voltage Drop 0.00% Percent Voltage Drop 0.00% Percent Current Draw Aux Output w ..... Note-1;24 Volt derated by 15%to 20.4 Volts. Note-2;Point to Point Voltage Drop Calculation. Note-3;Line Voltage Drop Calculation PROPRIETARY DOCUMENT FOR APPROVAL ONLY 10/18/2018