Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Plans (77)
Duct: 16"diameter Ansul wet chemical fire suppression system. Duct: 16"diameter Model R-102. 6 gallon capacity. Flow point capacity:22 Flows used: 6 21'Type I Hood Single Filter Bank 1W Fusible Links 1W 450F 1 n ISI- -ice I 1N 1N 1N ANSUL 1N 35" 40" 0 Remote Pull 10'-20'from hood. Future Rice Steamers Automatic gas 36"x24" shut off valve. Griddle Manual resetting type. Suppression system#2 iFire System Drawing Note: Receptacles located under hood must shut Front View clown upon fire system actuation. System shall signal building fire alarm if present. Guardian Fire Protection Job: Din Tai Fung Notes; Fire system installed in accordance with Ansul PO Box 1555 9677 SW Washington Square Rd. design, installation and maintenance manual. Albany OR 97321 Tigard OR 97223 System tested in accordance with UL 300. CCB # 100355 exp. 6/20 Date: 09/18 Drawn by: MAF Ansul wet chemical fire suppression system. Model R-102.6 gallon capacity. Duct: 10"x17" Duct: 10"x32" Duct: 10"x23" Flow point capacity: 33 Flows used:25 21'Type I Hood Single Filter Bank 2W 2W 2W 8 ; 8 FA-71_____4 A & , A A A A A A wI 6 0- 0_ IN 1N g 9 g g g g g 1N ANSUL 9 iN 1N 1N IN 1N 3N 3N 1N 1N IN 3g 3g 3g 30" 30"" 30" 30" 30" 25" 25" 30" 30" 30" IN 40" 40" 40" 40" 40" 35" 35" 40" 40" 40". 30" 1N 40" 30" 0 40" Remote Pall 10'-20'from hood. — I " N,__/ '•'�..._--' \ % '�/ `•__/ N-_.i �..._-/ \\.../'I 16"d 13"d 16"d 13"d 13"d 13"d 12"d 13"di I i t I P.I t 18"x36" Rice Oven 5 Hole Wok Unit 14"x15"14"xl5" 3 Hole Wok Unit Automatic gas Stock Steamer Fryer Fryer shut off valve. Pot Range Manual resetting type. Suppression System#3 ._ Note:Receptacles located under hood must shut Fire System Drawing Front View down upon fire system actuation. System shall signal building fire alarm if present. Guardian Fire Protection Job: Din Tai Fung Notes; Fire system installed in accordance with Ansul PO Box 1555 9677 SW Washington Square Rd design, installation and maintenance manual. Albany OR 97321 Tigard OR 97223 System tested in accordance with UL 300. CCB # 100355 exp. 6/20 Date: 10/18 Drawn by:MAF Ansul wet chemical fire system. Model R-102. 3 gallon capacity. Duct: 16"diameter Flow point capacity: 11 3(8" Flow points used: 6 black pipe Fusible IWLinks • 450F 8'Type I Canopy Hood. Single Filter Bank. • ANSUL 1 iN 260 260 260 30" 30" 30" 40" 40" 40" Remote Pull 10'-20'from hood. 28"d 28"d 28"d Automatic gas 3 Hole Wok Unit shut off valve. Manual reset type. Suppression system#4 Fire System Drawing Front View System shall signal building fire alarm system If Present. Guardian Fire Protection Job: Din Tai Fung Notes; Fire system installed in accordance with Ansul PO Box 1555 9677 SW Washington Square RD desib, installation and maintenance manual. Albany OR 97321 Tigard OR 97223 System tested in accordance with UL 300. CCB# 100355 exp 06/20 Date: 09/18 Drawn by: MAF R-102 Restaurant Fire Suppression Manual SECTION 4—SYSTEM DESIGN UL EX3470 ULC EX3470 2014-SEP-01 REV. 11 PAGE 4-1 SYSTEM DESIGN GENERAL INFORMATION The ANSUL R-102 Restaurant Fire Suppression System may be 1. Nozzles must be located 2-8 in. (51-203 mm)into the center used on a number of different types of restaurant cooking appli- of the duct opening, discharging up. See Figure 4-1. ances and hood and duct configurations.The design information listed in this section deals with the limitations and parameters of this pre-engineered system. Those individuals responsible for the design of the R-102 system must be trained and hold a 'Pr current ANSUL certificate in an R-102 training program. The R-102 and the PIRANHA systems use compatible agents and components, therefore, they may be used together for cooking appliance, hood, and duct protection. The primary AUTOMAN Release can be either an R-102 or a PIRANHA � AUTOMAN Release and can actuate up to two additional R-102 or PIRANHA Regulated Actuators. In systems utilizing a 101 2-8IN, remote release, any combination of the maximum number of (51-203mm) regulated actuators can be used. • Both systems must actuate simultaneously. • Each system must be designed and installed per its appropri- FIGURE 4-1 ate manual. oi� • Adjacent appliances requiring protection must be protected 2. In installations where a UL listed damper assembly is with the same type of system, either R-102 or PIRANHA, employed, the duct nozzle can be installed beyond the 8 unless the center-to-center spacing between the adjacent in. (203 mm) maximum, to a point just beyond the damper R-102 and PIRANHA nozzles is no less than 36 in. (914 mm). • When appliances are protected with R 102 nozzles, the assembly that will not interfere with the damper. Exceeding hood and connecting duct above those appliances cannot be the maximum of 8 in. (203 mm)in this way will not void the protected with PIRANHA nozzles. UL listing of the System. • Mixing systems in a common plenum Is not allowed. 3. Previously listed three flow number and five flow number One of the key elements for restaurant fire protection is a correct duct protection detailed in earlier published manual(Part No. system design. This section is divided into 10 sub-sections: 418087-06)can also still be utilized. Nozzle Placement Requirements,Tank Quantity Requirements, DUCT SIZES UP TO 50 IN. (1270 mm) Actuation and Expellant Gas Line Requirements, Distribution PERIMETER/16 IN. (406 mm) DIAMETER Piping Requirements, Detection System Requirements, Manual Pull Station Requirements, Mechanical Gas Valve • One 1W nozzle=one flow number Requirements, Electrical Gas Valve Requirements, Electrical • 50 in. (1270 mm)perimeter maximum Switch Requirements, and Pressure Switch Requirements. . 16 in. (406 mm)diameter maximum Each of these sections must be completed before attempting any installation. System design sketches should be made of all DUCT SIZES UP TO 100 IN. (2540 mm) aspects of design for reference during installation. PERIMETER/32 IN. (812 mm) DIAMETER NOZZLE PLACEMENT REQUIREMENTS • One 2W nozzle=two flow numbers This section gives guidelines for nozzle type, positioning, and • 100 in. (2540 mm) perimeter maximum quantity for duct, plenum, and individual appliance protection. • This section must be completed before determining tank quan- 32 in. (812 mm)diameter maximum tity and piping requirements. The chart below shows the maximum protection available from each duct nozzle. Duct Protection—Single Nozzle 3.0 Gallon 1.5 Gallon All duct protection is UL listed without limitation of maximum duct Description System System length(unlimited length).This includes all varieties of ductworks 2W Nozzle Maximum Maximum both horizontal and vertical including ducts that run at angles to 100 in. (2540 mm) 100 in. (2540 mm) the horizontal and ducts with directional bends. Perimeter Perimeter ►Note: Ducts from multiple hoods connected to a common 1W Nozzle Maximum Maximum ductwork must be protected in compliance with NFPA 96 and 50 in.(1270 mm) 50 in. (1270 mm) all local codes. Perimeter Perimeter The R-102 system uses different duct nozzles depending on the size of duct being protected. R-102 Restaurant Fire Suppression Manual SECTION 4—SYSTEM DESIGN UL EX3470 ULC EX3470 2014-SEP-01 REV. 11 PAGE 4-5 Plenum Protection Option 2:The 1W nozzle must be placed perpendicular,8-12 in. 0. The R-102 system uses the 1W nozzle or the 1N nozzle for (203-304 mm)from the face of the filter and angled to plenum protection. The 1W nozzle is stamped with 1W and the center of the filter.The nozzle tip must be within .the 1N nozzle is stamped with 1 N, indicating they are one-flow 2 in. (50 mm)from the perpendicular center line of the nozzles and must be counted as one flow number each. When filter. See Figure 4-8. protecting a plenum chamber, the entire chamber must be 12IN,(305mm) protected regardless of filter length. MAXIMUM 4IN. , N., VERTICAL PROTECTION—GENERAL (101 mm) —__ ._---_._. 5 N. 04 1W NOZZLE—SINGLE AND V �+/BANK PROTECTION Imp , MINIMUM mm) One 1W nozzle will protect 4 linear feet(1.2 m)of plenum. The I V. " maximum distance from the end of the hood to the first and last NOZZLE TIP ,;p nozzle must be no more than 2 ft(0.6 m). After the first nozzle, MUST BE WITHIN Jr THIS AREA : any additional nozzles must be positioned at a maximum of 4 ft Air " lir' (1.2 m)apart down the entire length of the plenum.The plenum width must not exceed 4 ft(1.2 m). (The 1W nozzle can be used ��"�., on single or V-bank filter arrangements.) See Figure 4-6. FIGURE 4-8 000200 2FT(0.8m) MAXIMUM HORIZONTAL PROTECTION—OPTION 1 4 Fr(1.2m) 1N NOZZLE SINGLE BANK PROTECTION 4FT(1.2m)MAXIMUM /---CaN,4FT(1.2m) 2 FT(0.6 m)MAXIMUM MAXIMUM o' One 1N nozzle will protect 10 linear feet(3.0 m)of single filter bank MAXI UMplenum.The nozzle(s)must be mounted in the plenum,2 to 4 in. '" (50 to 102 mm)from the face of the filter, centered between the <0.0000;,: ;; .1114161°'-- filter height dimension, and aimed down the length, The nozzle J must be positioned 0-6 in. (0-152 mm)from the end of the hood to the tip of the nozzle. See Figure 4-9. � '°" --mo i/' lIi :1I /.�" �,!J "� ./— ► 2-4 IN. 10 MAXIMUMF (3 0 ) lio C FIGURE 4-6 00019( 000201 id When protecting plenums with the 1W nozzle, two options of •„-P `� coverage are available: Option 1:The 1W nozzle must be on the center line of the `til single or"V" bank filter and positioned within 1-20 in. (26-508 mm) above the top edge of the filter. See 1/4,,,, ' 000202 Figure 4-7. E FIGURE 4-9 M20AXIMIN.(508UM mm) ::.:,_ , ,4" 1 IN.(26 mm) -- I MINIMUM 14. ii 20 IN.(508 mm) MAXIMUM 1 IN.(28 m m) MINIMUM FIGURE 4.7 000199 • R-102 Restaurant Fire Suppression Manual SECTION 4—SYSTEM DESIGN UL EX3470 ULC EX3470 2014-SEP-01 REV. 11 PAGE 4-9 Fryer—Single Nozzle Protection (Continued) Maximum Area Dimensions—Single Nozzle Fryer Protection (Continued) Max. Size Max. Size Overall Type of Nozzle Height Nozzle Frypot Only With Dripboard Nozzle Above Top of Fryer Location b-14.5 in. x 16.5 in. 14.5 in. x 26.5 in. 290 16 in. to 21 in. See Figure 4-17 ►(368 mm x 419 mm) (368 mm x 673 mm) (406 to 533 mm) 19.5 in. x 19 in. 19.5 in. x 25 3/8 in. 290 13 in.to 16 in. See Figure 4-17 ►(495 mm x 482 mm) (495 mm x 644 mm) (330 to 406 mm) 19.5 in. x 19 in. 19.5 in. x 25 3/8 in. 3N See Figure 4-18 See Figure 4-18 .(495 mm x 482 mm) (495 mm x 644 mm) 18 in. x 18 in. 18 in. x 27 3/4 in. 3N 25 in.to 35 in. See Figure 4-19 ►(457 mm x 457 mm) (457 mm x 704 mm) (635 mm to 889 mm) I ` 1 I I I 1 I I I ``1- 1 1 `Y I 441111011111110. ; I 4100 � I I TOP OF FRYER I I I 1114140011 <" I i I I r.41111. 44q1140.'-A `U I FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD %Air. 1 _-- ` ` ,NON?, 290 NOZZLE TIP POSITIONED OVER THE MIDPOINT OF THE HAZARD AREA±3 IN. RIGHT-TO-LEFT .4 moo (76 mm)FROM THE MIDPOINT ALONG THE LONGEST SIDE OF THE HAZARD AND± 000010 CENTERLINE 1 IN.(25 mm)FROM THE MIDPOINT ALONG THE SHORTEST SIDE OF THE HAZARD FRYER WITHOUT DRIPBOARD AND AIMED AT THE MIDPOINT OF THE COOKING AREA. FRYER WITH DRIPBOARD NOTE: 3N NOZZLE TIP MUST BE LOCATED WITHIN THE PERIMETER OF THE SURFACE FIGURE 4-17 AREA WITHIN THE FRONT HALF OF THE FRY POT AND AIMED AT THE CENTER. 0(1221111 FIGURE 4-19 34 IN.(863 mm)MAXIMUM DIAGONAL DISTANCE BETWEEN NOZZLE AND CENTER OF HAZARD AREA ---- Its T -.-j' 21 in.(534mm)k%�wr' " .y I I I MINIMUM I "•,-... I -'• 1 I `''`-4.'-' I VERTICAL '�► NOZZLE 411111111111 HEIGHT 1111041 __, FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD 314 NOZZLE TIP POSITIONED ANYWHERE ALONG OR WITHIN PERIMETER OF COOKING SURFACE AND AIMED TO THE CENTER OF THE COOKING AREA. FIGURE 4-18 002297 R-102 Restaurant Fire Suppression Manual SECTION 4—SYSTEM DESIGN UL EX3470 ULC EX3470 2014-SEP-01 REV. 11 PAGE 4-13 c. Range Protection The R-102 system uses five different nozzles for the protection of ranges. Two of the design options require a one-flow nozzle 10 IN. and three of the design options require two-flow nozzles. (254MAXIMUMmm) NOTICE . (81212 mm) A 13 in. (330 mm) diameter wok pan is the 1N Allik MAXIMUM largest wok size that can be protected on NOZZLE ranges. AIMING POINT When protecting hot top ranges, the entire cooking surface must be protected. 10 11. 1411 (254 mm) MAXIMUM Range Protection 1N (1-Flow) Nozzle-High Proximity 000540 Application FIGURE 4-28 No Obstructions Single and multiple burner ranges can be protected using a 1N ► nozzle. The nozzle is stamped with 1 N, indicating that this is a one-flow nozzle and must be counted as one flow number. When using this nozzle for range protection, the maximum length of the burner grates being protected with a single nozzle must not exceed 32 in. (812 mm)and the maximum area of the burner grates must not exceed 384 in.2(24774 mm2)per nozzle. When protecting a range, the 1N nozzle must be located a maximum of 10 in. (254 mm) from each burner grate centerline and must be aimed at the center of the cooking surface. See Figures 4-27 and 4-28. T41. 401N. 4 142—I 1016 mm 301N, / (76255) `1 006599 FIGURE 4-27 • SECTION 4—SYSTEM DESIGN R-102 Restaurant Fire Suppression Manual UL EX3470 ULC EX3470 PAGE 4-18 REV. 11 2014-SEP-01 Griddle Protection 1N(1-Flow) Nozzle—High Proximity Griddle Protection 290(2-Flow)Nozzle—High Proximity Application Application The R-102 system uses four different nozzles for the protection Option 1 —Nozzle Center Located of griddles.One of the applications requires a 1-flow nozzle and 30 in.to 50 in. (762 mm to 1270 mm)above the cooking surface. three of the applications require a 2-flow nozzle. This high proximity application uses the 290 nozzle. High Proximity Application:35 in.to 40 in. (889 to 1016 mm) above the cooking surface. 1.-The nozzle is stamped with 290 indicating this is a 2-flow nozzle and must be counted as two flow numbers. This high proximity application uses the 1N nozzle. One 290 nozzle will protect a maximum cooking area of 720 in.2 ►The nozzle is stamped with 1N indicating this is a one-flow (46451 mm2)with a maximum dimension of 30 in. (762 mm). nozzle and must be counted as one flow number. When using this nozzle for high proximity applications, the One 1N nozzle will protect a maximum cooking area of 1080 in.2 nozzle must be positioned within 1 in. (25 mm) of the center (69677 mm2)with the maximum longest side of 36 in.(914 mm). of the cooking surface and pointed vertically down. See Figure When using this nozzle for griddle protection,the nozzle must be 4-41 and 4-42. positioned along the cooking surface perimeter to a maximum of CENTER LINE OF GRIDDLE 2 in. (50 mm) inside the perimeter, and aimed to the midpoint of SAURFNY DAIRECCE t 1TION IN.(25 mm)IN the cooking surface. See Figure 4-39 and 4-40. I I I I NOTICE I I 50 IN. (i270mmE ) P When using this type of griddle protection, I MAXIMUM I TI only five flow numbers are allowed on a 1.5 i OF290 gal (5.7 L)system and only 11 flow numbers NOZZL are allowed on a 3 gal(11.4 L)system. 30IN. HEIGHT I I (762mm) MINIMUM HEIGHT OF 290 TOZZLE IP I_ MIDPOINT OF— i COOKING SURFACE J I j 1 I I 1_ j -� 1 1.-- I _� FIGURE 4-41 000244 1N NOZZLE LOCATED ALONG COOKING ANY SIDE OF GRIDDLE SURFACE WITHIN SURFACE 0-2 IN.(0-50 mm)OF COOKING EDGE ,+_COOKING SURFACE EDGE.NOZZLE MUST BE AREA AIMED AT MIDPOINT OF COOKING NOZZLE 1 IN.(25 mm) SURFACE. FIGURE 4-39 LOCATION MAXIMUM 000241 11111111 1 I NOZZLE LOCATION I 0-2 IN.(0-50 mm) )/1 ._ t NSIDE PERIMETER I 40 IN. -►1 LI-- OFCOOKINGSURFACE 1 (1016 mm) IIIL I /' I I MAHEIMT M L p r AREA COOKING % OF 1N NOZZLE TIP 1 IN.(25 mm) / � NOZZLE I35 IN.(889 mm) MAXIMUM j 1 I MINIMUM EDGE I I I HEIGHT OF--1. I / 1 I OF 1N ( NOZZLE TIP CENTER OF GRIDDLE SURFACE OR A COOKING I 1 MAXIMUM DIMENSION OP 20.6 IN. SURFACE __ �`I f (523 mm)FROM NOZZLE CENTERLINE TO FURTHEST CORNER OF GRIDDLE _111.11111■ FIGURE 4-42 000773 • FIGURE 4-40 R-702 Restaurant Fire Suppression Manual SECTION 4—SYSTEM DESIGN UL EX3470 ULC EX3470 2014-SEP-01 REV. 11 PAGE 4-27 Wok Protection 2. A 1N nozzle will protect a wok 11 in. (279 mm) minimum The R-102 system uses two different nozzles for the protection diameter up to 24 in.(609 mm)maximum diameter.The wok of woks. depth must be no less than 3 in. (76 mm) and no greater ► than 6 in. (152 mm). The nozzle is stamped with 1N indi- 1. A 260 nozzle will protect a wok 14 in. (355 mm) minimum cating that this a one-flow nozzle and must be counted as diameter up to 30 in.(762 mm)maximum diameter.The wok one flow number. When using this nozzle, the nozzle must depth must be no less than 3.75 in. (95 mm)and no greater be positioned anywhere along or within the perimeter of the than 8 in. (203 mm). wok, aimed at the center, 30 in. to 40 in. (762 mm to 1016 ► The nozzle is stamped with 260 indicating that this is a mm)above the hazard surface,as shown in Figure 4-65. two-flow nozzle and must be counted as two flow numbers. When using this nozzle, the nozzle must be positioned as NOTICE shown in Figure 4-64. When using this type of wok protection, only five flow numbers are allowed on a NOZZLE MUST BE POSITIONED WITHIN 1 IN.(25 mm)RADIUS 1.5 gal (5.7 L) system, and only eleven OF THE CENTER OF THE WOK,POINTED VERTICALLY DOWN flow numbers are allowed on a 3 gal(11.4 L)system. (1' 14 0fil \ I I 40 1N. / i (1016 mm) 260 NOZZLE 0. `�� ion 21° 1 t (\\1 i I '� 1 30 IN � � (762 mm) 35-45 N. MINIMUM DEPTH �I (889-1143 mm) 3.0 IN.(70 mm) , MAXIMUM DEPTH MINIMUM DEPTH 3.75 IN.(95 mm) MAXIMUM DEPTH 8 IN.(203 mm) I 8.0 IN.(152 mm) 11 IN.(279 mm)MINIMUM DIAMETER 24 IN.(609 mm)MAXIMUM DIAMETER t ► FIGURE 4-65 14 IN.(356 mm)MINIMUM DIAMETER 909261 30 IN.(762 mm)MAXIMUM DIAMETER FIGURE 4-64 000281 R-102 Restaurant Fire Suppression Manual SECTION 4—SYSTEM DESIGN UL EX3470 ULC EX3470 2014-SEP-01 REV. 11 PAGE 4-67 DISTRIBUTION PIPING REQUIREMENTS(Continued) Distribution Piping Requirements—3.0 Gallon System 1. The maximum length between the start of the first branch SUPPLY line and the start of the last branch line must not exceed TEE 24 ft (7.3 m). When the supply line is split, the combined total of both legs of the supply line (from the start of the first branch line to the start of the last branch line) must not �t V 000266 exceed 24 ft(7.3 m). See Figure 4-134. COMBINED LENGTH OF BOTH LEGS OF SUPPLY 2. The total length of all branch lines must not exceed 36 ft LINE MUST NOT 3 BRANCH LINES (10.9 m). See Figure 4-134. EXCEED 24 FT(7.3 m) 3. Use a 3/8 in, union to connect the tank adaptor to the 3/8 in. supply line. 4. A maximum of two nozzles are allowed per duct branch line. 2W NOZZLE .� 1N NOZZLE 5. The requirements of the following table must not be1111 exceeded: 1N NOZZLE 230 NOZZLE / 245 NOZZLE 12N NOZZLE (BRANCH LINE IN BOLD) COMBINED LENGTH MUST 000502 NOT EXCEED 36 FT(10.9 m) FIGURE 4-134 ►3.0 GALLON SYSTEM Duct Plenum Appliance Requirements Supply Line Branch Line Branch Line Branch Line Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in. Maximum Length 40 ft 8 ft 4 ft 12 ft (12.1 m) (2.4 m) (1.2 m) (3.6 m) Maximum Rise 6 ft 4 ft 2 ft 2 ft (1.8 m) (1,2 m) (0.6 m) (0.6 m) Maximum 90° 9 4 4 6 Elbows Maximum Tees 1 2 2 4 Maximum Flow 11 4 2 4 Numbers "Exceptions: 1.Twelve flow numbers are allowed in any one tank for duct and plenum protection only. 2.Twelve flow numbers are allowed with any one tank using only two-flow appliance nozzles. 3.Twelve flow numbers are allowed with any one tank using only three-flow appliance nozzles. Special Instructions: 1.Twelve flow numbers are allowed when four Dean Industries GTI Gas Fryers are protected at low proximity as shown in Figure 4-86 on Page 4-32.The discharge piping must be as shown in Figure 4-67 on Page 4-32. 2. For certain McDonald's applications,11.5 flow numbers are allowed when udng a combination of one 2W duct nozzle,one 12N electrostatic precipitator nozzle, one 1N plenum nozzle,and four two-flow appliance nozzles.Contact the Applications Engineering Department for additional Information. SECTION 4—SYSTEM DESIGN R-102 Restaurant Fire Suppression Manual UL EX3470 ULC EX3470 PAGE 4-68 REV. 11 2014-SEP-01 DISTRIBUTION PIPING REQUIREMENTS(Continued) Distribution Piping Requirements — 6.0 Gallon Manifolded LENGTH OF PIPING MUST NOT EXCEED 24 FT. (7.3 in)FROM START OF FIRST BRANCH LINE System TO START OF LAST BRANCH LINE As an option to piping two 3.0 gallon tanks separately, two 3.0 gallon tanks can be manifolded together to share a common agent distribution line. Only 3.0 gallon tanks connected to the • same regulator can be manifolded. The following requirements must be met when manifolding: START OF LAST 1. All piping must be 3/8 in. Schedule 40. 40. BRANCH LINE 2. See Figure 4-136 for tank connections. 3. The length of supply line piping between the start of the first li A branch line and the start of the last branch line must not exceed 24 ft (7.3 m). See Figure 4-135. When the supply line is split, the combined total of both legs of the supply line(from the start of the first branch line to the start of the 2WNOzzLEs1N last branch line) must not exceed 24 ft(7.3 m). / ', NOZZLE 4. The combined length of all branch lines must not exceed 36 ft(10.9 m). See Figure 4-135. 0 5. A maximum of 22 flow numbers are allowed. iN NOZZLE 6. The requirements of the following table must not be iN exceeded. NOZZLE 41011"'. 1 N 0 }� NOZZLE 4 © I 2 FLOW APPLIANCE NOZZLE (BRANCH LINES IN BOLD) COMBINED LENGTH MUST NOT EXCEED 36 FT(10.9 El) FIGURE 4-135 000zu ►6.0 GALLON SYSTEM Duct Plenum Appliance Requirements Supply Line Branch Line Branch Line Branch Line Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in. Maximum Length 32 ft 8 ft 4 ft 12 ft (9.7 m) (2.4 m) (1.2 m) (3.6 m) Maximum Rise 6 ft O ft 2 ft 2 ft (1.8 m) (1.2 m) (0.6 m) (0.6 m) Maximum 90° 8 4 4 6 Elbows Maximum Tees 2 2 2 4 Maximum Flow 22 4 2 4 Numbers SECTION 4-SYSTEM DESIGN R-102 Restaurant Fire Suppression Manual UL EX3470 ULC EX3470 PAGE 4-70 REV. 11 2014-SEP-01 DISTRIBUTION PIPING REQUIREMENTS(Continued) Distribution Piping Requirements-9.0 Gallon System This optional configuration consists only of three 3-gallon tanks, all pressurized from a single double-tank nitrogen cartridge with expellant gas hoses connected as shown in Figure 4-138.Tanks - - No. 1 and No.2 must be connected directly to the regulator with separate expellant gas hoses and Tank No.3 must be connected •)���I�II��i�f to Tank No.2 with a third expellant gas hose as shown in Figure I 4-136. Each tank must be connected to an independent distribu- tion piping network as shown in Figure 4-138. Distribution piping requirements for each network must be as follows: "�"r� -�I 1. The maximum length between the start of the first branch 111111111111111 _� line and the start of the last branch line must not exceed 24 ft (7.3 m). When the supply line is split, the combined n� total of both legs of the supply line (from the start of the first branch line to the start of the last branch line) must not exceed 24 ft(7.3 m). See Figure 4-134. 3.0 3.0 3.0 2. The total length of all branch lines must not exceed 36 ft GALLON GALLON GALLONTANK TANK TANK (10.9 m). See Figure 4-139. , NO.3 NO.2 NO.1 3. Use a 3/8 in. union to connect the tank adaptor to the 3/8 in. supply line. •i---- 4. A maximum of two nozzles are alloweder duct branch line. TWO TANK ENCLOSURE 3 GALLON REGULATED DOUBLE TANK NITROGEN p ASSEMBLY(PART NO. RELEASE ASSEMBLY, CARTRIDGE OR 43032 35. When using this 9.0 gallon system configuration, no mani- HO ES AND GR(INCLUDES OMMETS) REGULATEDN (EG 0-30 ATEDETS) RCARTRIDGEEGU folding of distribution piping is allowed. ACTUATOR ASSEMBLY ONLY) 6. When an AUTOMAN Regulated Release is utilized in this NOTE: WHEN THREE 3.0 GALLON TANKS ARE CONNECTED TO ONE configuration,additional regulator actuators cannot be used. AUTOMAN REGULATED RELEASE ASSEMBLY,NO ADDITIONAL gREGULATED ACTUATOR(S)ASSEMBLIES CAN BE USED. 7. Only 3-gallon tanks can be utilized in this configuration. FIGURE 4-138 8. The requirements of the following table must not be 00BI 26 exceeded for each 3-gallon tank: 9.0 GALLON SYSTEM Duct Plenum Appliance Requirements Supply Line Branch Line Branch Line Branch Line Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in. Maximum Length 40 ft 8 ft 4 ft 12 ft (12.1 m) (2.4 m) (1.2 m) (3.6 m) Maximum Rise E ft 4 ft 2 ft 2 ft (1.8 m) (1.2 m) (0.6 m) (0.6 m) Maximum 90° 9 4 4 6 Elbows Maximum Tees 1 2 2 4 Maximum Flow 11* 4 2 4 Numbers "Exceptions: 1.Twelve flow numbers are allowed in any one tank for duct and plenum protectlan ONLY, 2.Twelve flow numbers are allowed with any one taut using only two-flow appliance nozzles, 3.Twelve flow numbers are allowed with any one tank using only three-flow appliance nozzles, Special instructions: 1. When four Dean Industries Gil Gas Fryers are protected at low proximity as shown in Figure 4-68 on Page 4-32,the discharge piping must be as shown in Figure 4-87 en Page 4-32. 2.For certain McDonald's applications,11.5 flow numbers are allowed when using a combination of one 2W duct nozzle,one 12N electrostatic precipitator nozzle, one 1N plenum nozzle,and four two-flow appliance nozzles.Contact the Applications Engineering Department for additional information.