Submittal Data
OCT - 1 2018
Unit Heaters BUILDING
�����N
Project: StorQuest Tigard - 12516
Submitted By: Portland Mechanical Construction, Inc.
Attention: Paul Hettervig
2000 SE Hanna Harvester Dr
Milwaukie, OR 97222
(503) 656-7400
Supplier: Johnson Air Products
2220 SE 9th Ave
Portland, OR 97293
503-234-5071
Date Submitted: September 25, 2018
2000 SE Hanna Harvester Drive • Milwaukie, Oregon 97222
503/656-7400 • fax 503/655-0620 •toll free 866/656-7400 •www.pmc-g.com
OR CCB# 151807 • WA#CCO1 PORTLMCO24KA• ID#HVCC1213 & PLBC12598
:bDINE
AccuSpec V4.19
Transaction #: 10650318
JOB TITLE: StorQuest
Date: 09/20/2018
Approved By:
Submittal review and approval required prior to listed unit(s) being released for
production and shipment. Unit(s)configured based on information provided. The
Approver is responsible for ensuring the units,options,and accessories meet the job
specifications.
wii: DINE
AccuSpec V4.19
SUBMITTAL SCHEDULE & DATA
Gas- and Oil-Fired Unit Heaters, Infrared Heaters, and Indoor Duct Furnaces
Job Name: StorQuest Date: 09/20/2018
Location: Tigard, OR Engineer:
Submitted by: Danny Ruby Architect:
Contractor:
Unit Tag
UH-1 UH-2
Model Number PTC 55AS0111FBAN PTC 85AS0111FBAN
Quantity of Units 17 3
Btu/Hr Input 55,000 85,000
Btu/Hr Output 51,150 79,050
CFM 1097 1650
Altitude 0-2000 0-2000
Temperature Rise (degrees F) 43 44
External Static Pressure (E.S.P) 0.00 0.00
Total Static Pressure (T.S.P.) 0.00 0.00
Gas Type _ Natural Natural
—
Gas Control Type Single Stage, Direct Single Stage, Direct
Spark Ignition, Spark Ignition,
100% Shut-Off with 100% Shut-Off with
Continuous Retry Continuous Retry
Supply Voltage 115/60/1 115/60/1
Control Voltage 24V 24V
Motor HP 1/8 1/8
Motor RPM 1625 1625
Blower RPM N/A N/A
Heat Exchanger Type Aluminized Steel Aluminized Steel
Heat Heat
Exchanger/Burner Exchanger/Burner
Options &Accessories (See
Attached Pages)
Remarks _
wili��DINE
AccuSpec V4.19
SUBMITTAL SCHEDULE & DATA
Gas- and Oil-Fired Unit Heaters, Infrared Heaters, and Indoor Duct Furnaces
Model Description Qty Tag
PTC 55AS0111FBAN Propeller Unit Heater 17 UH-1
66907 PTC 55AS0111FBAN 17
63174 Thermostat, White Rogers 1C26-101, 50-90°F 17
57873 Recharge Kit for pH Neutralizing Kit 17
PTC 85AS0111FBAN Propeller Unit Heater 3 UH-2
65795 PTC 85AS0111FBAN 3
63174 Thermostat, White Rogers 1C26-101, 50-90°F 3 _
57873 Recharge Kit for pH Neutralizing Kit 3
�IVIODINE
TAG: UH-1
AccuSpec V4.19
PTC MODEL NOMENCLATURE
1,2,3 4,5,6 7 8 9,10 11,12 13 14 15 16
PTC 55 A 5 01 J 11 F B A N
1,2,3 - Product Type
PTC - Separated Combustion, High Efficiency Condensing Propeller Unit
4,5,6 - Furnace Input Rating
55 - 55,000
7 - Heat Exchanger Type
A-Aluminized Steel Heat Exchanger and Burner
8 - Pilot Ignition
S- Direct Spark Ignition
9,10-Motor and Drive Code (Power Code)
01 - 115V motor
11,12-Gas and Valve/Ignition Control Type (Control Code)
11 - Natural, Single Stage, Direct Spark Ignition, 100% Shut-Off with Continuous Retry
13-Fan Guard Type
F - Finger Proof Fan Guard
14-Development Sequence
B - Current
15-Future
A- For Future Use
16-Factory Installed Option
N - None
'3DINE TAG: UH 1
AccuSpec V4.19
GENERAL PERFORMANCE DATA
c us
tiarso
Intertek
General Performance Data
Model PTC 55
At 0' Elevation
Btu/Hr. Input 55,000
Btu/Hr. Output 51,150
Entering Airflow (CFM) 1097
Outlet Velocity 618
Air Temp. Rise (°F) 43
Mounting Height (Max Ft.)1 12
Heat Throw (Max. Mtg. Ft.)2 43
Unit Total Power (Amps) 4.35
Condensate Produced (gal/hr) 0.3
As Configured at 0-2000 Ft. Elevation
Btu/Hr. Input 55,000
Btu/Hr. Output 51,150
Configured Air Temp Rise (°F) 43
Motor Data
Horse Power 1/8
RPM 1625
Type P.S.C.
Motor Amps at 115V 2.20
Clearances to Combustibles
Top and Bottom 6"
Vent/Combustion Air Connector 6"
Access Side 6"
Non-Access Side 6"
Rear 18"
1 At 65°F ambient and unit fired at full-rated input. Mounting height as measured from bottom of unit.
2 Heat Throws are calculated at 65°F ambient with a 43°F air temperature rise with the unit mounted at a
maximum mounting height of 12 feet.
TAG: UH-1
J ?ODINE
AccuSpec V4.19
DIMENSIONS - UNIT
Model PTC Dimensions
KNOCKOUTS FOR
SUPPLY POWER WIRING
CONDUIT ENTRANCE
ADJUSTABLE 0(MINIMUM DISTANCE TO WALL) ---- �,.. A
LOUVERS 3S61 14.90-- (4)318"-16 MTG HOLES N P -1 It !
'^ '' 1 ,-ACCESS
- .,,,,f = PANEL
�_ t(r'''' f
>� COMBUSTION
/^AIR INLET
(OPENING) Igit 1111VtrIT-StrET
I �mRz '"".
: '7 /CONN. L
. 7i-
`� T K
ill
- C FAN CONDENSATE DRAIN - l .- F i-I
3/4'PVC ;- G .
R (APPROX.) - D (OPENING) - -- H
Model Size PTC55
Dimensions (inches)
A 29.8 J 12.81
B 18.13 K 6
C 19.03 L 9.07
D 17 M 3.3
E 16.24 N 1.9 i
F 4.71 P 16
G 7.19 Q2 40.19
H 10.22 R 28.19
I 3.1
Gas Connection 1/2
Fan Diameter 14 - '
Vent Pipe Connection Size 3
Combustion Air Inlet Pipe Connection Size 3
Approx. Shipping Weight 93 lbs.
1 All models have 4 holes for mounting. Listed is the hole diameter and threads per inch to accept
threaded rod.
2 Dimension equals overall "R" dimension plus 12".
TAG: UH-1
Standards
All unit(s)shall include:
ETL design certification for use in both the US and Canada to the ANSI Z83.8 - latest revision,
standard for"Gas Unit Heater and Gas-Fired Duct Furnaces" for safe operation, construction, and
performance
Mechanical Configuration
Condensing furnace section with 93% minimum efficiency provided by an indirect-fired tubular heat
exchanger with individually fired tubes coupled to a secondary recuperative heat exchanger for
maximum heat recovery.
Venting/Combustion Air Arrangement
The unit shall be separated combustion. The venting shall be a power exhausted arrangement with
a separate combustion air intake pipe connection to allow for fresh combustion air from outside the
conditioned space. The unit shall be tested to insure proper ignition when the unit is subjected to
40 mile per hour wind velocities. The unit shall also include a factory mounted differential pressure
switch designed to prevent main burner ignition until positive venting has been proven.
Venting shall be Schedule 40 PVC. For Canadian installations, all vent pipe and components must
be approved to ULC S636.
Unit Casing
The unit heater(s) casing shall be constructed of not less than 20 gauge aluminized steel with
minimization of exposed fasteners.
All exterior casing parts shall be cleaned of all oils and a phosphate coating applied prior to
painting. The exterior casing parts shall then be painted with an electrostatically applied baked-on
gray-green polyester powder paint (7-mil thickness) for corrosion resistance.
The unit shall be furnished with horizontal air deflectors. The deflectors are adjustable to provide
for horizontal directional airflow control (up or down).
Furnace Section
The heat exchanger(s) shall be made of 18 gauge aluminized steel tubes and headers. Each heat
exchanger tube shall be individually and directly flame-fired. The heat exchanger tube shall be
crimped to allow for thermal expansion and contraction. The flue collector box shall be made of 20
gauge AL29-4C stainless steel.
The thermal efficiency of the unit(s) shall be a minimum of 93% efficient for all air flow ranges
through the use of a secondary recuperative heat exchanger. The secondary heat exchanger shall
be constructed of AL29-4C stainless steel to withstand the corrosive environment of condensing gas
fired equipment.
The heat exchanger(s) seams and duct connections shall be certified to withstand 0.9" W.C.
external static pressure without burner flame disturbance.
The burner(s) shall be in-shot type, directly firing each heat exchanger tube individually and is
designed for good lighting characteristics without noise of extinction for both natural and propane
gas.
The ignition controller(s) shall be 100% shut-off with continuous retry.
TAG: UH-1
The gas pressure shall be between 6-7" W.0 for natural gas.
The solid state ignition system shall directly light the gas by means of a direct spark igniter each
time the system is energized.
The unit gas controls shall be provided with the following:
Single-stage gas controls with a single-stage combination gas control, an ignition control. The unit
fires at 100%full fire based on a call for heat from a room thermostat.
An automatic reset high limit switch mounted in the air stream to shut off the gas supply in the
event of overheating.
An automatic reset high limit switch mounted on the power exhauster housing to shut off the gas
supply in the event of overheating flue gas temperatures.
A condensate drain line overflow switch that senses if the condensate line is clogged and shuts the
unit heater down. The switch is factory mounted inside the unit cabinet and wired to the unit
controls.
An energy-saver control utilizes stratified ceiling air to heat the space at floor level before turning
on the gas controls. Its operation is independent of the room thermostat and should have a higher
set-point than the room thermostat.The Stat is factory mounted outside the unit and wired into the
contractor convenience box.
A Modine Building Management System (BMS) Board installed in this unit provides an RS485
interface between the unit heater and existing building networks that employ a BACnet or Modbus
protocol.The board works in conjunction with the unit's ignition control module to manage and
report the function of the heater. A BMS network connection is not required to operate the heater,
but allows for expanded control and monitoring ability.
A time delay relay that delays the start of the air mover to allow the heat exchanger a warm-up
period after a call for heat.The time delay relay shall also continue the air mover operation after
the thermostat has been satisfied to remove any residual heat in the heat exchanger.
The unit shall be orificed for 0-2000 feet elevation above sea level.
Electrical
All electrical components shall carry UL, ETL, or CSA certification.
A low voltage terminal board shall be provided for direct wiring connection to an external
thermostat.
A Contractor Convenience Package that consists of an external junction box featuring simple
connection of supply power wiring internally, thermostat wiring to terminals eternally, an On/Off
switch, a single 115V outlet for connection of an external condensate pump, and status indicator
lights to display the operational state of the unit shall be factory mounted on the rear panel of the
casing.
A single 115V to 24V step down transformer shall be provided for all unit controls.
Air Mover
The motor horsepower shall be 1/8 H.P.
The motor wiring shall be in flexible metal BX conduit.
TAG: UH1
The motor shall be controlled by a time delay relay.
Propeller models shall meet the following requirements:
The motor type shall be Single-Speed, Totally Enclosed (TE).
The air mover motor shall be a 115V motor.
Mounting
The unit shall be equipped with tapped holes to accept 3/8"-16 threaded rod for suspension.
Accessories
The following field installed accessory control devices shall be provided with the unit:
A recharge kit for pH neutralizing kit (Item Code 57872). Includes sufficient aggregate for a
complete recharge of the neutralizing kit.
A condensate drain kit consisting of one threaded PVC elbow and two specially designed
condensate traps to allow the unit to operate and drain properly.
TAG: UH-2
�DiINE
AccuSpec V4.19
PTC MODEL NOMENCLATURE
1,2,3 4,5,6 7 8 9,10 11,12 13 14 15 16
FTC 85 A S 01 11 F B A N_j
1,2,3 - Product Type
PTC- Separated Combustion, High Efficiency Condensing Propeller Unit
4,5,6 - Furnace Input Rating
85 - 85,000
7 - Heat Exchanger Type
A- Aluminized Steel Heat Exchanger and Burner
8 - Pilot Ignition
S- Direct Spark Ignition
9,10- Motor and Drive Code (Power Code)
01 - 115V motor
11,12-Gas and Valve/Ignition Control Type(Control Code)
11 - Natural, Single Stage, Direct Spark Ignition, 100% Shut-Off with Continuous Retry
13 -Fan Guard Type
F - Finger Proof Fan Guard
14-Development Sequence
B - Current
15 -Future
A- For Future Use
16-Factory Installed Option
N - None
403DINE TAG: UH-2
AccuSpec V4.19
GENERAL PERFORMANCE DATA
c us
Intertek
General Performance Data
Model PTC 85
At 0' Elevation
Btu/Hr. Input 85,000
Btu/Hr. Output 79,050
Entering Airflow (CFM) 1650
Outlet Velocity 619
Air Temp. Rise (°F) 44
Mounting Height (Max Ft.)1 13
Heat Throw (Max. Mtg. Ft.)2 48
Unit Total Power (Amps) 4.35
Condensate Produced (gal/hr) 0.5
As Configured at 0-2000 Ft. Elevation
Btu/Hr. Input 85,000
Btu/Hr. Output 79,050
Configured Air Temp Rise (°F) 44
Motor Data
Horse Power 1/8
RPM 1625
Type P.S.C.
Motor Amps at 115V 2.20
Clearances to Combustibles
Top and Bottom 6"
Vent/Combustion Air Connector 6"
Access Side 6"
Non-Access Side 6"
Rear 18"
At 65°F ambient and unit fired at full-rated input. Mounting height as measured from bottom of unit.
2 Heat Throws are calculated at 65°F ambient with a 44°F air temperature rise with the unit mounted at a
maximum mounting height of 13 feet.
�����90D1NE
TAC; UH-2
AccuSpec V4.19
DIMENSIONS - UNIT
Model PTC Dimensions
KNOCKOUTS FOR
SUPPLY POWER WIRING
CONDUIT ENTRANCE
ADJUSTABLE 0(MINIMUM DISTANCE TO WALL) -A- ' I i
LOUVERS 9.Sfit--14.90-- (4)318"-16 MTG HOLES �`N P 1'
D 7-ACCESS
PANEL
r
fl: I ip,,,,. ..• _.... ,.._m
. f 1 f$ CE
COMBSTIN
,! -AIR INET24: B VEwT'.. ij`f - ONNr L
P , 1 ! (
C „] FAN-- CONDENSATE DRAIN -1 F F- 1
3/4"PVC ( G ..
R (APPROX.) -. D (OPENING) - I--H----?
Model Size PTC85
Dimensions (inches) _
A 35.53 J 6.73
B 20.31 K 8.74
C 22.05 L 12.13
D 22.52 M 3.86
E 18.42 N 1.54
F 4.50 P 22.03
G 7.98 Q2 45.83
H 10.27 R 30.69
1.32
Gas Connection 1/2
__
Fan Diameter —18
Vent Pipe Connection Size 3
Combustion Air Inlet Pipe Connection Size 3
Approx. Shipping Weight 125 lbs.
1 All models have 4 holes for mounting. Listed is the hole diameter and threads per inch to accept
threaded rod.
2 Dimension equals overall "R" dimension plus 12".
Standards TAG: UH-2
All unit(s)shall include:
ETL design certification for use in both the US and Canada to the ANSI Z83.8 - latest revision,
standard for "Gas Unit Heater and Gas-Fired Duct Furnaces" for safe operation, construction, and
performance
Mechanical Configuration
Condensing furnace section with 93% minimum efficiency provided by an indirect-fired tubular heat
exchanger with individually fired tubes coupled to a secondary recuperative heat exchanger for
maximum heat recovery.
Venting/Combustion Air Arrangement
The unit shall be separated combustion. The venting shall be a power exhausted arrangement with
a separate combustion air intake pipe connection to allow for fresh combustion air from outside the
conditioned space.The unit shall be tested to insure proper ignition when the unit is subjected to
40 mile per hour wind velocities. The unit shall also include a factory mounted differential pressure
switch designed to prevent main burner ignition until positive venting has been proven.
Venting shall be Schedule 40 PVC. For Canadian installations, all vent pipe and components must
be approved to ULC S636.
Unit Casing
The unit heater(s) casing shall be constructed of not less than 20 gauge aluminized steel with
minimization of exposed fasteners.
All exterior casing parts shall be cleaned of all oils and a phosphate coating applied prior to
painting. The exterior casing parts shall then be painted with an electrostatically applied baked-on
gray-green polyester powder paint (7-mil thickness) for corrosion resistance.
The unit shall be furnished with horizontal air deflectors. The deflectors are adjustable to provide
for horizontal directional airflow control (up or down).
Furnace Section
The heat exchanger(s) shall be made of 18 gauge aluminized steel tubes and headers. Each heat
exchanger tube shall be individually and directly flame-fired. The heat exchanger tube shall be
crimped to allow for thermal expansion and contraction. The flue collector box shall be made of 20
gauge AL29-4C stainless steel.
The thermal efficiency of the unit(s) shall be a minimum of 93% efficient for all air flow ranges
through the use of a secondary recuperative heat exchanger. The secondary heat exchanger shall
be constructed of AL29-4C stainless steel to withstand the corrosive environment of condensing gas
fired equipment.
The heat exchanger(s) seams and duct connections shall be certified to withstand 0.9" W.C.
external static pressure without burner flame disturbance.
The burner(s) shall be in-shot type, directly firing each heat exchanger tube individually and is
designed for good lighting characteristics without noise of extinction for both natural and propane
gas.
The ignition controller(s) shall be 100% shut-off with continuous retry.
TAG: UH-2
The gas pressure shall be between 6-7" W.0 for natural gas.
The solid state ignition system shall directly light the gas by means of a direct spark igniter each
time the system is energized.
The unit gas controls shall be provided with the following:
Single-stage gas controls with a single-stage combination gas control, an ignition control. The unit
fires at 100% full fire based on a call for heat from a room thermostat.
An automatic reset high limit switch mounted in the air stream to shut off the gas supply in the
event of overheating.
An automatic reset high limit switch mounted on the power exhauster housing to shut off the gas
supply in the event of overheating flue gas temperatures.
A condensate drain line overflow switch that senses if the condensate line is clogged and shuts the
unit heater down. The switch is factory mounted inside the unit cabinet and wired to the unit
controls.
An energy-saver control utilizes stratified ceiling air to heat the space at floor level before turning
on the gas controls. Its operation is independent of the room thermostat and should have a higher
set-point than the room thermostat. The Stat is factory mounted outside the unit and wired into the
contractor convenience box.
A Modine Building Management System (BMS) Board installed in this unit provides an RS485
interface between the unit heater and existing building networks that employ a BACnet or Modbus
protocol.The board works in conjunction with the unit's ignition control module to manage and
report the function of the heater. A BMS network connection is not required to operate the heater,
but allows for expanded control and monitoring ability.
A time delay relay that delays the start of the air mover to allow the heat exchanger a warm-up
period after a call for heat.The time delay relay shall also continue the air mover operation after
the thermostat has been satisfied to remove any residual heat in the heat exchanger.
The unit shall be orificed for 0-2000 feet elevation above sea level.
Electrical
All electrical components shall carry UL, ETL, or CSA certification.
A low voltage terminal board shall be provided for direct wiring connection to an external
thermostat.
A Contractor Convenience Package that consists of an external junction box featuring simple
connection of supply power wiring internally, thermostat wiring to terminals eternally, an On/Off
switch, a single 115V outlet for connection of an external condensate pump, and status indicator
lights to display the operational state of the unit shall be factory mounted on the rear panel of the
casing.
A single 115V to 24V step down transformer shall be provided for all unit controls.
Air Mover
The motor horsepower shall be 1/8 H.P.
The motor wiring shall be in flexible metal BX conduit.
TAG: UH-2
The motor shall be controlled by a time delay relay.
Propeller models shall meet the following requirements:
The motor type shall be Single-Speed, Totally Enclosed (TE).
The air mover motor shall be a 115V motor.
Mounting
The unit shall be equipped with tapped holes to accept 3/8"-16 threaded rod for suspension.
Accessories
The following field installed accessory control devices shall be provided with the unit:
A recharge kit for pH neutralizing kit (Item Code 57872). Includes sufficient aggregate for a
complete recharge of the neutralizing kit.
A condensate drain kit consisting of one threaded PVC elbow and two specially designed
condensate traps to allow the unit to operate and drain properly.