Loading...
Report (117) rp5. ci?- Contractor's Material and Test Certificate` for Aboveground`Piping} PROCEDURE ` \ ,\K i k\Z L c''�� A Upon completion of work,inspection and tests shall be made by the contractor's representative and witnessed by an owner's representative. All defects shall be corrected and system left in service before contractor's personnel finally leave the job. A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners, and contractor. It is understood the owner's representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship,or failure to comply with approving authority's requirements_� or local ordinances. PROPERTY NAME: 1 e� SC-VNI, 1.15 ?DU-C.' UJBI3 PROPERTY ADDRESS: i 3 .4.1.3ao (�2 3� acdl 'T:Trd O' ci7C.CZDATE: `0- - 17 ACCEPTED BY APPROVING AUTHORITIES(NAMES) Cl C T-ct.{'A PLANS ` � y ADDRESS 13 a-6 '5it) A-4QL\ g jO 12p..CPT C 9-7 a` 3 INSTALLATION CONFORMS TO ACCEPTED PLANS `'! YES 0 NO EQUIPMENT USED IS APPROVED 1G YES 0 NO IF NO,EXPLAIN DEVIATIONS HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS KYES ❑NO TO LOCATION OF CONTROL VALVES AND CARE AND MAINTENANCE IF NO,EXPLAIN INSTRUCTIONS HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES? 1.SYSTEM COMPONENTS INSTRUCTIONS i YES ❑NO 2.CARE AND MAINTENANCE INSTRUCTIONS YES ❑NO 3.NFPA 25 YES ❑NO LOCATION SUPPLIES BUILDINGS OF SYSTEM YEAR OF ORIFICE TEMPERATURE MAKE MODEL MANUFACTURE SIZE QUANTITY RATING U tNea\tC sj F40 °tv VLe k I a` -a5_s5 SPRINKLERS :1 TY i3 i '04:511.40iIa i5-i c� i/�CLS,C, k.134,1(7 • DI'l i" 36 '0._e tAN)Lc KA i i.l04 n 'O t 7 I � i o n C: L ` a CPIPE AND TYPE OF PIPE ,p• i- C 0-1).- � . i -f S C,L- FITTINGS TYPE OF FITTINGS ...t •J-C A I 3c t 0 - t_ 0 MAXIMUM TIME TO OPERATE ALARM ALARM DEVICE THROUGH TEST CONNECTION VALVE OR FLOW TYPE. MAKE. _ MODEI MIN SFC INDICATORO 37 �0:„) tyy►G v6e DRY VALVE d� Q.O.D. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. \)( 1t L. M kr ltzle5 TIME TO TRIP TIME WATER ALARM THROUGH TEST WATER AIR TRIP POINT REACHED OPERATED DRY PIPE CONECTION PRESSURE PRESSURE AIR PRESSURE TEST OUTLET PROPERLY OPERATING _ MIN SEC PSI PSI PSI MIN SEC YES NO TEST WITHOUT O.O.D. WITH Q.O D. IF NO,EXPLAIN OPERATION CI PNEUMATIC 0 ELECTRIC El HYDRALIC //f DELUG PREACTION - . SUPERVISED El YES 0 NO DETECTING MEDIA SUPERVISED • YES 0 NO VALVES DOES VALVE OP • - r 'OM THE MANUAL TRIP,REMOTE,OR BOTH ❑ YES 0 NO CONTROL STATIONS IS THERE AN ACCESSIBLE FACILITY IN EA - —Pt"+ IF NO,EXPLAIN FOR TESTING ❑ YES 0 NO 0 e- ACH CIRCUIT OPERATE DOES EA _ 1'CUIT MAXIMUM TIME TO MAKE M•I' SUPERVISION LOSS ALARM? OPERATE VALVE ' _ ,SE OPERATE RELEASE YES NO YES NO IN SEC Page 1 of 2 • • LOCATION MAKE& SETTING STATIC PRESSURE RESIDUAL PRESSURE FLOW RATE PRESSURE &FLOOR MODEL (FLOWING) REDUCING LET(PSI) OUTLET(PSI) INLET(PSI) OUTLET(PSI) FLOW(GPM) VALVE TEST DROSTATI ydrostatic tests shall be made at not less than 200 PSI(13.6 bars)for 2 hours or 50 PSI(3.4 bars) TEST ; . ' . -ssure in excess of 150 PSI(10.2 bars)for 2 hours. Differential dry-pipe valve clappers shall be left DESCRIPTION open during the test to prevent damage. All aboveground leakage shall be stopped. PNEUMATIC:Establish 40 PSI(2.7 bars)air pressure and measure drop,which shall not exceed Ph PSI(0.1 bars) In 24 hours. Test pressure tanks at normal water level and air pressure and measure air pressure drop,which shall not exceed 1h PSI(0.1 bars)in 24 hours. ALL PIPING HYDROSTATICALLY TESTED AT' -CC1 SI BARS FOR HRS IF NO,STATE REASON DRY PIPING PNEUMATICALLY TESTED a YES 0 NO EQUIPMENT OPERATES PROPERLY 13 YES 0 NO DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS, SODIUM SILICATE OR DERIVITIVES OF SODIUM SILICATE,BRINE,OR OTHER CORROSIVE CHEMICALS WE OT USED FOR TESTING SYSTEMS OR STOPPING LEAKS? YES 0 NO TESTS DRAIN READING OF GUAGE LOCATED NEAR WATER RESIDUAL PRESSURE WITH VALVE TEST IN TEST SUPPLY TEST CONNECTION: PSI ( BARS) CONNECTION OPEN WIDE: PSI( BARS) UNDERGROUND MAINS AND LEAD IN CONNECTIONS TO SYSTEM RISERS FLUSHED BEFORE CONNECTION MADE TO SPRINKLER PIPING VERIFIED BY COPY OF THE U FORM NO.85B Pi YES 0 NO OTHER EXPLAIN FLUSHED BY INSTALLER OF UNDER- GROUND SPRINKLER PIPING K.YES 0 NO r IF POWDER-DRIVEN FASTENERS ARE USED IN 0 YES ❑ NO IF NO,EXPLAIN CONCRETE,HAS REPRESENTATIVE SAMPLE TESTING BEEN SATISFACTORILY COMPLETED? BLANK TESTING NUMBER USED LOCATIONS NUMBER REMOVED GASKETS WELDED PIPING tk YES 0 NO IF YES.... DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING KYES ❑ NO PROCEDURES COMPLY WITH THE REQUIREMENTS OF AT LEAST AWS D10.9,LEVEL AR-3? WELDING DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS r \YES 0 NO QUALIFIED IN COMPLIANCE WITH THE REQUIREMENTS OF AT LEAST AWS D10.9,LEVEL AR-3? DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED QUALITY CONTROL PROCEDURE TO ENSURE THAT ALL DISCS ARE RETRIEVED,THAT OPENINGS IN PIPING ARE GI YES 0 NO SMOOTH,THAT SLAG AND OTHER WELDING RESIDUE ARE REMOVED, y[ AND THAT THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED? CUTOUTS DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE TO irgqYES 0 NO (DISCS) ENSURE THAT ALL CUTOUTS_(DISCS)ARE RETRIEVED? HYDRAULIC NAMEPLATE PROVIDED IF NO,EXPLAIN DATA YES ❑ NO NAMEPLATE DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN REMARKS -� (0-x-`q 1-1`7 NAME OF SPRINKLER CONTRACTOR TEST WITNESSED F• PROPS TY OWNER(S GNED) TIT (T DATE BY FO .'' I — ONTRA CT (SIGNED) TITLE DATE tWilL COre-VvkaNsiNs )1 13 ADDITIONAL EXPLA 0 •ND N I ES Page 2 of 2