Specifications (38) 8/22/2018
Unit: Aaon RQ Cabinet RQ-005 (920AHUO2)
Location: Tigard OR 97224
Curb: Insulated VibroCurblll
Governing Code: 2014OSSC / IBC2012
SDC: D
Design Wind Speed: 130 MPH
CWS Durham 0 and M Building Remodel
These calculations begin with the assumption that the Thybar curb is
supported around its full perimeter by building structure. Design of building
structure is not the responsibility of Thybar Corporation.
A 31 inch high Thybar Insulated VibroCurblll of minimum 14 gage galvanized
side wall construction will meet the 2014OSSC / IBC2012 requirements for
installing an Aaon RQ Cabinet RQ-005 (920AHUO2) unit in Tigard OR 97224
when manufactured with bulkheads under each isolator and installed according
to the attached drawings.
The unit must be attached to the Thybar Insulated VibroCurblll using 12 gage
restraint brackets. Bracket quantity is determined in the calculations and is
summarized as follows:
Minimum 12 gage bracket quantity: 4
The Thybar Insulated VibroCurblll must be attached to the building structure
using welds or bolts at the curb base flanges. Flange connection minimum bolt
quantity is determined in the calculations and is summarized as follows:
Total connection minimum quantity: 18
As curb manufacturers, Thybar Corporation cannot be expected to provide
appropriate attachment hardware for every possible type of roof structure.
Thybar provides seismic/windload calculations that are based on the material
provided; typically sheet metal curbs. It is the responsibility of others (project
engineer, architect, SEOR, etc) to know enough about the load carrying
capability of the building structure to design a method of attachment to that
structure. Thybar does not design the structure and therefore should not
recommend an attachment method that may create difficulties with existing
field conditions outside of the curb manufacturer's control.
Summary 1
Thybar Corporation 8/22/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
Location Tigard OR 97224
General
Applicable Building Code 20140550/
IBC2012
Seismic Design Category(SDC) D
Unit Manufacturer Aaon
Unit Model RQ Cabinet RQ-005
(920AHUO2)
Length(in) 100.13
Equip Width(in) 44.25
Height(in) 50.5
Weight(Ib) 969
CG„(in) 43.80
CG,,,(in) 19.70
Curb Type Insulated
VibroCurbll I
Curb Length(in) 77.50
Curb Width(in) 39.25
Curb Height(in) 31.00
Minimum Pedestal Thickness(ga) 14
Bulkhead max OC spacing(in) 42
Fy(psi) 30,000
E(psi) 30,000,000
Thickness(in) 0.0670
u 0.3
Curb I(in) 31.0
h/t 463
b/t 627
k, 4.0
1.0
F,(psi) 276
Snow Importance,I 1.2
Snow Load,pf(lb) 824
Curb Design Load,0.75'max(Wind, 1 437
.7'Seismic)+0.755,(lb)=
• F,(psi) 12,000
0.6'F,=F,(psi) 18,000
Wind Load(130mph)Fw(Ib)= 1,091
Exposure Category= B
Rooftop height(ft)= 20
Velocity Pressure coefficient Kz= 0.70
Topography factor Kzt= 1.00
Wind Directionality factor Kd= 0.90
Wind Speed V= 130
Importance factor Iw= N/A
gz= 27.26
GCr 1.90
FE= 1,559
FE M.= 1,663
FE ra„= 312
SEE= 0.715
So,= 0.442
a,= 2.50
Ip= 1.50
Seismic Rr= 2.00
z/h= 1.0
SE(%ofg)= 96.10
S,(%of g). 41.90
Site Coefficient F,= 1.12
Site Coefficient F,= 1.58
Site Soil Classification= D
Seismic Upward Force(Ib),F up= 138.59
ex(in) 6.2625
ey(in) 2.425
Curb Load ax+
Distribution 1.375
Factors ax- 0.625
ay+ 0.555
ay- 0.445
C,„,„(lb/in) 17.7
Curb Loads
C,„,,,(lb/in) 3.48
Shear Wall Factor a, 0.688
R Unit shear,v(lb/in) 25.173
S e Curb Long Unit Overturning,Cu Ob/in) 12.7
u a Dimension Unit Uplift,T(Ib) 614
p c
P t Curb Overturning,Cc(lb/in) 119.3
o I Curb Comer Uplift,Tc(lb/in) 6.13
▪ o Shear Wall Factor a2 0.555
t n Unit shear,v(lb/in) 10.286
s Curb Short Unit Overturning,Cu(lb/in) 4.543
Dimension Unit Uplift,T(Ib) 564.446
Curb Overturning,Cc(lb/in) 24.687
Curb Corner Uplift,Tc(Ib/in) 14.381
Max Shear(lb/in) 18.9
Shear 1,(psi) 282
Curb Verification f,/F, 0.02 <1.0,OK
Max Axial Reaction(lb/in) 17.7
Axial f,(psi) 264
f,/F, 0.95 <1.0,OK
Load Calcs
2
Thybar Corporation 8/22/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
General
Location Tigard OR 97224
Applicable Building Code 2014OSSC/IBC2012
Unit Model RQ Cabinet RQ-005(920AHUO2)
Curb Type Insulated VibroCurblll
Bracket Dimensions
Length(in) 16
Max bending arm(in) 2.2
Max torsion arm(in) 0.001
Minimum Material thickness(ga) 12
Material thickness(in) 0.0970
Fy(psi) 30,000
Area(in2) 1.552
Screws
Screw size/type(#) 10
Quantity of screws 7
Hole size(in) 1/4
Allowable pullout(lb/screw) 1146
Max pullout(lb/bracket) 8,019
Allowable shear(lb/screw) 1,206
Max shear(lb/bracket) 8,445
Torsion on Bracket
Fv=0.4*Fy(psi) 12,000
Max shear(Ib) 602,176
Flexure on Bracket
Fb=0.6*Fy(psi) 18,000
Max shear(Ib) 33,862
Shear on Bracket Attachment Holes
Distance-hole edge to bracket edge 0.375
Max shear(Ib) 3,056
Tension on Bracket
FT=0.4*Fy(psi) 12,000
TMax(Ib) 16,587
Bracket Capacity
(Allowable Load(lb) 3,0561
Bracket Verification
Horizontal Design Load(Ib) 1,437 1,437
Curb Length/Width(in) 77.50 39.25
Shear Wall Factor 0.69 0.55
Design Shear(Ib) 988 797
Unit Design Uplift,Tc(Ib) 614.12 564.45
Unit Uplift,Ta(Ib) 422 313
R=(V2+T22)112 1,075 856
#per side 0.35 0.28
Clip Safety Factor 2
Total Clips Required 4
Unit To Curb 3
Thybar Corporation 8/22/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
General
Location Tigard OR 97224
Applicable Building Code 20140SSC/ IBC2012
Unit Model RQ Cabinet RQ-005 (920AHUO2)
Curb Type Insulated VibroCurblll
Material Properties
Fy(psi) 30,000
Material Allowable Stress, Fa 12,000
(psi)
Base Attachment Dimensions
Hole Size (in) 0.625
Number of Holes per
attachment 1
Min. Material thickness (ga) 14
Min. Material thickness (in) 0.1340
Cut out area (in2) 0.307
Base flange width (in) 2.0
Edge distance (in) 11/16
Base shear area (in2) 0.09
Base Attachment Forces
Length Width
Horizontal Design Load (Ib) 1436.86 1436.86
Length (in) 77.50 39.25
Shear(Ib) 988 797
Unit Uplift, Tc(Ib) 422 313
R= (V2 +T22)112 1,075 856
Length Width
Base Attachment Stresses-fa 972 1,549
(psi)
Base Safety Factor 2 2
fa/Fa 0.16 0.26
Base Attachment Minimum 12 6
Quantity
Minimum Base Attachments- 18
Perimeter Distributed
Base Attachment Holes 4
Thybar Corporation 8/22/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
Support Reactions
Unit: RQ Cabinet RQ-005(920AHUO2)
Gravity Load Isolators
Cgmax=W(p)*ax+*ay+/Lt Cg W(P) F(p) N(ns) N L1(in) Ht
=9.5 lb/in X Y 969 1,437 4 4 77.50 50.50
Cgmin=W(P)*ax-*ayAi 43.80 19.70
=3.5 lb/in
Seismic North-South F(p) 4 ht L2 B2
Unit Overturning Cu=F(p)*Ht/2*ax+/L2/B2 1436.86 41 8/16 7.25 77.5 39.25
=16.4 lb/in I ax+ I ax- I ay+ I ay-
1.375 0.624719101 0.555 0.445
Unit Uplift Tu=max(0,C,;W(p)*ax+*ay-/L2)
=8.7 lb/in
Seismic East-West hi:Isolator Height(in) Lx(in)=Max Isolator spacing
Unit Overturning Cu=F(p)*H,/2*ay+/L2/B2 31
41.50 Calculation Summary
=6.6 lb/in Ly(in)=Channel Max Lateral Support Spacing OK
Unit Uplift Tu=max(0,C,,W(p)*ay+*ax/L2) 41.50
=2.3 lb/in
Curb Verification
Transverse Load on Structural Channel Stabilizer Bolt Vertical Channels Isolator Stresses
Channel Height Bolts per isolator,n channels per isolator,n Isolator height:h
=6 in =2 =2 71/4 in
Channel Type Eccentricity Allowance(e): Mn,=Vn,*h1/n Isolator width:W
F,bin.14ga 0.02 in =1,791 in lb =4.0 in
Vb=max(V,,,,Vew,)/n Mew=Ve,.,*h1/n Isolator length:L
wx(Ib/in)=C9+Cu(ns) =247 lb =1,174 in lb =10.0 in
=25.9 lb/in M=Vb*e fbx=Mn,/Sx Isolator Sx BL*tb2/6
wy(lb/in)=F(p)*(N(ns)/N)/2/L1*(ax+) =5 in lb
=811 psi =87.6 in3
=12.7489 lb/in Tb=max(Tn„TeN)/n fist=V„,/(d1) Isolator SY Bw*tb2/6
Mx=Wx*Lx2/8 =181.49 lb =494 psi =35.042 in3.
=5,585 in lb fb=M/S fby=Mew/Sy fby=MO,./Sy
My=wy*Lr2/8 =119 psi =3,048 psi =33 psi
=2,745 in lb f„=V/A f„y=Vew/(2*b*t) fbx=M„/S.
fbx=Mx/Sx =559 psi =370 psi =20 psi
=4,927 psi ft=T/A fbx/Fbx+f„x/F„ fby/Fby
fby=MISy =410.81 psi =.07<1.7,OK 0.00<1.0,OK
=5,744 psi fb/Fb+f,/F„+f,/Ft fby/Fby+fy/F„ fbx/Fbx
fbx/Fbx =.08<1.7,OK =.14<1.7,OK 0.00<1.0,OK
=.23<1.0,OK Isolator Check Channel Loading
fbx/Fbx+fbyFby Tn.=T„*L. Curb Perimeter,P
=.49<1.7,OK =362.98 lb =233.50 in
Vns=F(p)/N*ax+ w=W(p)/P
=494 lb =4.15 lb/in
Tom„=T„*Ln Murex=w*Lx2/8
=94.74 lb =893.53 in*Ib
Vew=F(p)/N*ay+*2 f.=Mmax/Sx
=324 lb =788 psi
fe/Fa
=.02<1.0,OK
Vibro Calcs 5
8/22/2011
Aaon RQ Cabinet Unit
1111111 t hybarTigard OR
III CO '^' SEISMIC/WINDLOAD RESTRAINT BRACKET
rn>-b , kis fi right tl,e fi,5t ti :e,
:".4.2-5,tin e INSTALLATION DETAILS FOR VIBROCURBS
INSTALLATION INSTRUCTIONS:
PLACE RESTRAINTS IN APPROXIMATE LOCATIONS AS SHOWN. ____.
EQUALLY DISTRIBUTE RESTRAINT AS MUCH AS POSSIBLE WHILE AVOIDING INTERFERENCES WITH -
LIFTING LUGS;CONDENSATE DRAIN LINES,UNIT BASE SCREWS,ETC. 1111T
GASKET TOP PERIMETER OF CURB AND RESTRAINTS BEFORE SETTING UNIT.
SEE MATRIX BELOW FOR QUANTITIES REQUIRED PER UNIT.
r
1 1-7 —
,
. ij ' if I. I..
I t II L.,',.,t l I
.:;,oili
I,i' S, 1;,.,1 .ti
I
r T 8 ( --r•
NOTE: .
DRAWINGS ARE CONCEPTUAL,NOT TO SCALE
INNER RESTRAINTS MUST BE FIELD INSTALLED TO ROOF CURB AFTER SETTING UNIT. RESTRAINT DETAIL
Aaon THYCURB MODEL RESTRAINT BRACKET QTY. '� - „,,.I- '.:P-.EE
_ _..
SEISMIC RESTRAINTS PER UNIT TEF I L t, Ii 1 F_i��"'��fi
rl.A „.' RC'[_ 1d1 fil,r.I" T_I 1,F CA°_ PC P PETr,IT-'AII:T-
Aeon RQ Cabinet RQ-005(920AHUO2) ACSWRANB0009RC-01 4
SEISMIC&WINDLOAD BRACKETS ARE DESIGNED&CALCULATED FOR USE IN SEISMIC/WINDLOAD APPLICATIONS WHEN PROVIDED
AS PART OF A SEISMIC/WINDLOAD RATED CURB.
ATTACHMENT OF CALCULATED BRACKETS TO ANY OTHER CURB DOES NOT CONSTITUTE A SEISMIC/WINDLOAD RATED ASSEMBLY.
REVISION DATE: 8/22/2018
testraint Bracket Detail
lin t h ba r Ivl Structural Steel Mounting
UThybar makes;.right.he fss L•.e,
e'''',"r tr r SEISMIC / WIND LOAD VC3 CURB
INSTALLATION OPTIONS
The equipment support should be anchored to structural steel as follows:
* The width of the supporting structural steel shall be at least as wide as the base plate
of the equipment support.
* Bolts, nuts and washers are to be ASTM A307 grade.
* Bolts should be placed in every hole provided in the base plate of the equipment support;
pass through the base plate of the curb and the structural steel; and tightened according
to manufacturers torque specifications. (Figure 1-1)
* Alternatively, the curb may be welded to the structural steel. (Figure 1-2)
Allr [7
BOLT WITH WASHER
(4- DIAMETER MINIMUM)
41/ n111�
fiwrs, STEEL
NUT WITH WASHER i ILO° 111.
STRUCTURAL
Figure 1-1
CENTERED ON 76- 4
EACH BOLT HOLE
/lb
STRUCTURAL 1111tilli1411141 01/1 e00?•°2
STEEL
Z.
Figure 1-2
Consult Local Building Codes & FEMA Manual. 412/December 2002 VC3 Structural Installation.dwq
PRINTED:3/26/14
O thybar Concrete Slab Mounting
■ Thybai makes It right yii f, t ti>�%e,
SEISMIC / WIND LOAD VC3 CURB
INSTALLATION OPTIONS
The equipment support should be anchored to concrete as follows:
* Anchor system must comply with applicable building code (Local building code,
International Building Code, Uniform Building Code, etc.).
* Anchor to be Hilti Kwik Bolt TZ, Simpson Strong—Tie or equivalent.
* Anchors are to be placed in every hole provided in the base plate of the curb.
* Anchors are to pass through the base plate & be embedded into the concrete.
* Follow anchor manufacturers instructions for drilling holes, installation anchor and
tightening nut.
ANCHOR WITH NUT & WASHER
(4" DIAMETER MINIMUM,
EMBEDMENT DEPTH AND
EDGE DISTANCE AS REQUIRED
BY FIELD CONDITIONS AND
HARDWARE SELECTION.)
AIL..
CONCRETE
* ,
• . ° G
a as
•
Figure 1-1
11.44L
A.
Z..
°
• A a ..
•d .•
° 1?) a. .a. ° a dd :° •
a
41d
a
•a °' a
d ° 4 •
• °
A
• . a
•
SEISMIC & WINDLOAD BRACKETS ARE DESIGNED & CALCULATED FOR USE IN SEISMIC/WINDLOAD APPLICATIONS WHEN PROVIDED
AS PART OF A SEISMIC/WINDLOAD RATED CURB.
ATTACHMENT OF CALCULATED BRACKETS TO ANY OTHER CURB DOES NOT CONSTITUTE A SEISMIC /WINDLOAD RATED ASSEMBLY.
Consult Local Building Codes & FEMA Manual. 412/December 2002 VC3 Concrete Installation.dwq
PRINTFIl•1/9RHd
ill t bar Wood Beam Mounting
CC)IzPORA` C,'I
■ Thybarnekesittight itte13itir;,e, VIBROCURB ON
WOODEN STRUCTURAL BEAM
INSTALLATION OPTIONS
The curbs can be installed on a wood—beam type roof providing there is adequate
support around entire curb perimeter. The beam load carrying capability is to be
determined by others and the following provisions are acceptable:
* Curb base is the be through—bolted to wood joists of roof support.
* Through bolts are to be manufactured according to ASTM A307.
* Bolts are to be 4" diameter minimum and length as required to positively attach
to building structure.
* Bolts are to be installed in every hole in the roof curb base flange and
tightened according to bolt manufacturer's recommendations.
iAIL
p. INSTALL (1) o
ASTM A307 ALL—THREAD BOLT,
LENGTH AS NECESSARY
IN EACH CURB FLANGE
CURB HOLE AT CURB BASE
���� WOOD BEAM — SIZED
Zi- = BY OTHERS TO PROVIDE
1p CURBOLT G IE
/ CURB LENGTHH A AND WWIDDTH.
v 0
/
V
111114V
5
V
v
1.'11:2
''V
—I1"
THROUGH BOLTED ON BEAM UNDERSIDE
WITH NUT, BOLT AND WASHERTHYBAR CURB SECTION
AS NECESSARY TO ATTACH
CURB TO BUILDING ROOF
SUPPORT STRUCTURE. WOOD BEAM
SIZED BY OTHERS
10
VC3 Wood Beam Mounting.dwg
Print Date:6/12/2012
THYSCR
913BA S. KayOAvenuePORATION
Addison, IL 60101
800-666-CURB(2872)
Fax:630-543-5309
IIII www.thybar.com
Member of
VISCIA
Seismic/130 MPH Wind Load Calculations for a
Aaon B Cabinet RN-009 (920AHUO3) on a
Thybar Insulated VibroCurblll Roofcurb
in Tigard OR 97224
CWS Durham 0 and M Building Remodel
Thybar Order#: 184599
August 22, 2018
- 3CTUl
cOPROp l
�\.,N G I N FF SioZ
cc 19695 -
,1= W.
•REGON
X401'1,19
St4VEN C.6PS� 8.23.18
RENEWAL DATE: 12.31.19
Digitally signed bya Steven C Ball,SE
Steven C Ball, SE
ON:C=US,E shall@johnmanin.com,
0='John A Martin&Associates,Inc',
CN="Steven C Ball,SE'
Date:2018.08.23 13:10:24-07'00'
Z U)
a) This analysis considers the wind and seismic force
I— t° calculations and anchorage of the curb to the structure only. Reviewed by:
Qo The supporting structure shall be reviewed and approved by others. Hossain Ghaffari
m The curb design and unit anchorage to the curb is by Thybar. 08-23-2018
No installation shall take place until the anchorage and supporting
JOHN
H N A.A SRINC.IN structure are approved by the appropriate jurisdiction.
Structural Engineers
This document contains proprietary information from Thybar Corporation. Its contents may not be used for any other
project or location other than the project or location for which it was created without the prior written permission of .
Thybar Corporation.
8/22/2018
Unit: Aaon B Cabinet RN-009 (920AHUO3)
Location: Tigard OR 97224
Curb: Insulated VibroCurblll
Governing Code: 2014OSSC / IBC2012
SDC: D
Design Wind Speed: 130 MPH
CWS Durham 0 and M Building Remodel
These calculations begin with the assumption that the Thybar curb is
supported around its full perimeter by building structure. Design of building
structure is not the responsibility of Thybar Corporation.
A 29 inch high Thybar Insulated VibroCurblll of minimum 14 gage galvanized
side wall construction will meet the 2014OSSC / IBC2012 requirements for
installing an Aaon B Cabinet RN-009 (920AHUO3) unit in Tigard OR 97224
when manufactured with bulkheads installed 25 inches max OC and installed
according to the attached drawings.
The unit must be attached to the Thybar Insulated VibroCurblll using 12 gage
restraint brackets. Bracket quantity is determined in the calculations and is
summarized as follows:
Minimum 12 gage bracket quantity: 4
The Thybar Insulated VibroCurblll must be attached to the building structure
using welds or bolts at the curb base flanges. Flange connection minimum bolt
quantity is determined in the calculations and is summarized as follows:
Total connection minimum quantity: 32
As curb manufacturers, Thybar Corporation cannot be expected to provide
appropriate attachment hardware for every possible type of roof structure.
Thybar provides seismic/windload calculations that are based on the material
provided; typically sheet metal curbs. It is the responsibility of others (project
engineer, architect, SEOR, etc) to know enough about the load carrying
capability of the building structure to design a method of attachment to that
structure. Thybar does not design the structure and therefore should not
recommend an attachment method that may create difficulties with existing
field conditions outside of the curb manufacturer's control.
Summary 1
Thybar Corporation 8/22/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
Location Tigard OR 97224
General
Applicable Building Code 20140SSC/
IBC2012
Seismic Design Category(SDC) D
Unit Manufacturer Aaon
Unit Model B Cabinet RN-009
(920AHUO3)
Length(in) 110.63
Equip Width(in) 95.75
Height(in) 50.1
Weight(Ib) 1,971
CG,r(in) 44.70
CG„,(in) 36.10
Curb Type Insulated
VibroCurblll
Curb Length(in) 75.88
Curb Width(in) 54.00
Curb Height(in) 29.00
Minimum Pedestal Thickness(ga) 14
Bulkhead max OC spacing(in) 25
Fy(psi) 30,000
E(psi) 30,000,000
Thickness(in) 0.0670
u 0.3
I (in) 29.0
Curb h/t 433
b/t 373
kv 4.0
kv 1.0
F,(psi) 779
Snow Importance,I 1.2
Snow Load,pf(lb) 1,971
Curb Design Load,0.75•max(Wind, 3,143
.7"Seismic)+0.75S,(lb)=
0.4"Fy=F,(psi) 12,000
0.6•Fy=F,(psi) 18,000
Wind Load(130mph)Fw(lb)= 1,197
Exposure Category= B
Rooftop height(ft)= 20
Velocity Pressure coefficient Kz= 0.70
Topography factor Kzt= 1.00
Wind Directionality factor Kd= 0.90
Wind Speed V= 130
Importance factor Iw= N/A
qz= 27.26
GCr 1.90
Fc= 3,171
3,382
Fs nti,= 634
SDs= 0.715
SDI= 0.442
a,= 2.50
I,= 1.50
Seismic
R,,= 2.00
z/h= 1.0
Ss(%of g)= 96.10
Sr(%of g)= 41.90
Sae Coefficient F,= 1.12
Site Coefficient F,= 1.58
Site Soil Classification= D
Seismic Upward Force(lb),F up= 281.83
ex(in) 10.6125
ey(in) 11.775
Curb Load ax+
Distribution 1.576
Factors ax- 0.424
ay+ 0.623
ay- 0.377
Cr„,,,(lb/in) 51.0
Curb Loads Cm;,,(lb/in) 4.16
Shear Wall Factor a. 0.788
R Unit shear,v(lb/in) 45.850
S e Curb Lona Unit Overturning,Cu(Ib/in) 20.8
u a Dimension Unit Uplift,T(lb) 350
P c Curb Overturning,Cc(lb/in) 147.7
P t
o t Curb Corner Uplift,Tc(lb/in) 3.17
✓ o Shear Wall Factor a, 0.623
t n Unit shear,v(lb/in) 25.804
• s Curb Short Unit Overtuming,Cu(Ib/in) 4.633
•
Dimension Unit Uplift,T(lb) 1219.159
Curb Overturning,Cc(lb/in) 59.176
• Curb Corner Uplift,Tc(lb/in) 22.577
Max Shear(lb/in) 34.4
Shear f,(psi) 513
f,/F„ 0.04 <1.0,OK
Curb Verification
Max Axial Reaction(lb/in) 51.0
Axial f,(psi) 761
f,/F, 0.98 <1.0,OK
Load Calcs 2
Thybar Corporation 8/22/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
General
Location Tigard OR 97224
Applicable Building Code 2014OSSC/IBC2012
Unit Model B Cabinet RN-009(920AHUO3)
Curb Type Insulated VibroCurblll
Bracket Dimensions
Length(in) 16
Max bending arm(in) 2.2
Max torsion arm(in) 0.001
Minimum Material thickness(ga) 12
Material thickness(in) 0.0970
Fy(psi) 30,000
Area(in2) 1.552
Screws
Screw size/type(#) 10
Quantity of screws 7
Hole size(in) 1/4
Allowable pullout(lb/screw) 1146
Max pullout(lb/bracket) 8,019
Allowable shear(lb/screw) 1,206
Max shear(lb/bracket) 8,445
Torsion on Bracket
Fv=0.4*Fy(psi) 12,000
Max shear(Ib) 602,176
Flexure on Bracket
Fb=0.6*Fy(psi) 18,000
Max shear(Ib) 33,862
Shear on Bracket Attachment Holes
Distance-hole edge to bracket edge 0.375
Max shear(Ib) 3,056
Tension on Bracket
FT=0.4*Fy(psi) 12,000
TMax(Ib) 16,587
Bracket Capacity
'Allowable Load(lb) 3,0561
Bracket Verification
Horizontal Design Load(lb) 3,143 3,143
Curb Length/Width(in) 75.88 54.00
Shear Wall Factor 0.79 0.62
Design Shear(Ib) 2,476 1,958
Unit Design Uplift,Tc(Ib) 350.36 1219.16
Unit Uplift,T,(Ib) 276 760
R=(V2+T22)112 2,491 2,100
#per side 0.82 0.69
Clip Safety Factor 2
Total Clips Required 4
Unit To Curb 3
1
Thybar Corporation 8/22/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
General
Location Tigard OR 97224
Applicable Building Code 20140SSC/ IBC2012
Unit Model B Cabinet RN-009 (920AHUO3)
Curb Type Insulated VibroCurblll
Material Properties
Fy(psi) 30,000
Material Allowable Stress, Fa 12,000
(psi)
Base Attachment Dimensions
Hole Size (in) 0.625
Number of Holes per
attachment 1
Min. Material thickness (ga) 14
Min. Material thickness (in) 0.1340
Cut out area (in2) 0.307
Base flange width (in) 2.0
Edge distance (in) 11/16
Base shear area (in2) 0.09
Base Attachment Forces
Length Width
Horizontal Design Load (Ib) 3142.82 3142.82
Length (in) 75.88 54.00
Shear(Ib) 2,441 1,930
Unit Uplift, Tc(Ib) 904 740
R= (V2+T22)112 2,603 2,067
Length Width
Base Attachment Stresses-fa 1,413 1,870
(psi)
Base Safety Factor 2 2
fa/Fa 0.24 0.31
Base Attachment Minimum 20 12
Quantity
Minimum Base Attachments- 32
Perimeter Distributed
Base Attachment Holes 4
1
Thybar Corporation 8/22/2018
ThybarTC3-VC3 Aaon Units TigardOR 055C2014
Support Reactions
Unit: B Cabinet RN-009(920AHUO3)
Gravity Load Isolators
Coo,ax=W(P)*ax+*ay+/L, Cg W(P) F(p) N(ns) N L1(in) H1
=25.5 lb/in X Y 1,971 3,143 4 4 75.88 50.13
C9a,m=W(P)*ax-*ayJLi 44.70 36.10
=4.2 lb/in
Seismic North-South F(p) 4 h1 L2 B2
Unit Overturning Co=F(p)*Hi/2*ax+/L2/B2 3142.82 39 14/16 7.25 75.9 54.00
=30.3 lb/in I ax+ ( ax- I ay+ I ay-
1.576 0.42440678 0.623 0.377
Unit Uplift Tu=max(0,Cx W(p)*ax+*ar/L2)
=14.9 lb/in
Seismic East-West hi:Isolator Height(in) Lx(in)=Max Isolator spacing
Unit Overturning Co=F(p)*Hi/2*ay+/L2/B2 29 39.88 Calculation Summary
=12. lb/in Ly(in)=Channel Max Lateral Support Spacing OK
Unit Uplift Tu=max(0,C,;W(p)*ay+*ax/L2) 55.94
=5.1 lb/in
Curb Verification
Transverse Load on Structural Channel Stabilizer Bolt Vertical Channels Isolator Stresses
Channel Height Bolts per isolator,n channels per isolator,n Isolator height:h
=6 in =2 =2 71/4 in
Channel Type Eccentricity Allowance(e): M.=Y.*hi/n Isolator width:W
F,6in.toga 0.02 in =4,488 in lb =4.0 in
Vb=max(V„a,V,w)/n Mow=Vow*hi In Isolator length:L
wx(lb/in)=C9+Co(ns) =619 lb =2,286 in lb =10.0 in
=55.8 lb/in M=Vb*e fb,=M,,,/Sx Isolator Sx BL*tb2/6
wy(lb/in)=F(p)*[N(ns)/N1/2/L1*(ax+) =12 in lb =2,033 psi =87.6 in3
=32.63139 lb/in Tb=max(T,,,,T,w,)/n fax=Voo/(d*t) Isolator Sy=Bw*tb2/6
Mx=wx*Lx2/8 =296.27 lb =1,238 psi =35.042 in3
=11,088 in lb fb=M/S fby=Mcw/Sy fby=M,,,/Sy
Mr=N'r*tvz/8 =299 psi =5,938 psi =65 psi
=12,763 in lb f„=V/A f„y=V,w,/(2*b*t) fbx=Mw/Sx
fbx=Mx/Sx =1,401 psi =721 psi =51 psi
=9,781 psi f,=T/A fb,/Fbx+fox/F, fby/Fby
toy=M/Sy =670.61 psi =.18<1.7,OK 0.00<1.0,OK
=26,708 psi fb/Fb+f,/F,+ft/F, fb,Fby+f,y/F, fbx/Fbx
fbx/Fbx =.19<1.7,OK =.27<1.7,OK 0.00<1.0,OK
=.45<1.0,OK Isolator Check Channel Loading
fbx/Fbx+fb/Fby Tao=T,*Lo Curb Perimeter,P
=1.69<1.7,OK =592.53 lb =259.75 in
V„o=F(p)/N*ax+ w=W(p)/P
=1,238 lb =7.59 lb/in
Taw=T,*Lc Mot.,=w*Lx2/8
=203.71 lb =1,508.03 in*Ib
Vow=F(p)/N*ay+*2 fa=Mmax/Sx
=631 lb =1,330 psi
fa/F,
=.04<1.0,OK
Vibro Calcs 5
8/22/2011
Aaon B Cabinet Unit
111 thybar Tigard OR
IIICORP ' ,ON SEISMIC/WINDLOAD RESTRAINT BRACKET
n,yGal,; �� r;ynt the rfr3t t;r„e,
veey trr,F INSTALLATION DETAILS FOR VIBROCURBS
INSTALLATION INSTRUCTIONS:
PLACE RESTRAINTS IN APPROXIMATE LOCATIONS AS SHOWN. -._. _
EQUALLY DISTRIBUTE RESTRAINT AS MUCH AS POSSIBLE WHILE AVOIDING INTERFERENCES WITH .—
LIFTING LUGS,CONDENSATE DRAIN LINES,UNIT BASE SCREWS,ETC. [MIT
GASKET TOP PERIMETER OF CURB AND RESTRAINTS BEFORE SETTING UNIT.
SEE MATRIX BELOW FOR QUANTITIES REQUIRED PER UNIT. +_11h1+, I
E �v
iti l I _:.1
\\
f EN
/
--- /
F12,7 TI IJT
^^ 01 EGA 1,E-
=----
NOTE:
DRAWINGS ARE CONCEPTUAL,NOT TO SCALE
INNER RESTRAINTS MUST BE FIELD INSTALLED TO ROOF CURB AFTER SETTING UNIT. RESTRAINT DETAIL
Aaon
THYCURB MODEL RESTRAINT BRACKET QTY. A.'A-1ERIA_. -, ,tiLVAl 1-ZEL STEEL Ct'F if IY m-3 J.
SEISMIC RESTRAINTS PER UNIT
Aaon B Cabinet RN-009(920AHUO3) ACSWRANB0010RC-01 4 -IAC�UUfAI?E ld-i tt I0,:1 TL � f:E.b'i� r-'E.':'' RLSTP=>�iT
SEISMIC&WINDLOAD BRACKETS ARE DESIGNED&CALCULATED FOR USE IN SEISMIC/WINDLOAD APPLICATIONS WHEN PROVIDED
AS PART OF A SEISMIC/WINDLOAD RATED CURB.
ATTACHMENT OF CALCULATED BRACKETS TO ANY OTHER CURB DOES NOT CONSTITUTE A SEISMIC/WINDLOAD RATED ASSEMBLY.
REVISION DATE: 8/22/2018
testraint Bracket Detail
. t hY ba r Ivl Structural Steel Mounting
CORPO?_Ar ON
III Thybar crakes ii right the first Gr;4e,
'`A, t'" SEISMIC / WIND LOAD VC3 CURB
INSTALLATION OPTIONS
The equipment support should be anchored to structural steel as follows:
* The width of the supporting structural steel shall be at least as wide as the base plate
of the equipment support.
* Bolts, nuts and washers are to be ASTM A307 grade.
* Bolts should be placed in every hole provided in the base plate of the equipment support;
pass through the base plate of the curb and the structural steel; and tightened according
to manufacturers torque specifications. (Figure 1-1)
* Alternatively, the curb may be welded to the structural steel. (Figure 1-2)
AllBOLT WITH WASHER
(}" DIAMETER MINIMUM)
r
L:1111vz,
j ono
NUT WITH WASHER ll°401.1 ill 1.111
-41
STRUCTURAL
STEEL
Figure 1-1
CENTERED ON )fi" 4
EACH BOLT HOLE V
co
Adlb
4i1141144111111411
AISTEEL
STRUCTURAL
Figure 1-2
Consult Local Building Codes & FEMA Manual. 412/December 2002 VC3 Structural Installation.dwq
PRINTED:3/26/14
® t hyba r Concrete Slab Mounting
Ili
/.0/ ,, A,ON
111 Thybar makes it right true first tin
every err.^e
SEISMIC / WIND LOAD VC3 CURB
INSTALLATION OPTIONS
The equipment support should be anchored to concrete as follows:
* Anchor system must comply with applicable building code (Local building code,
International Building Code, Uniform Building Code, etc.).
* Anchor to be Hilti Kwik Bolt TZ, Simpson Strong—Tie or equivalent.
* Anchors are to be placed in every hole provided in the base plate of the curb.
* Anchors are to pass through the base plate & be embedded into the concrete.
* Follow anchor manufacturers instructions for drilling holes, installation anchor and
tightening nut.
ANCHOR WITH NUT & WASHER
(i" DIAMETER MINIMUM,
liL A
EMBEDMENT DEPTH AND ll
EDGE DISTANCE AS REQUIRED
__a
BY FIELD CONDITIONS AND
HARDWARE SELECTION.)
pm
CONCRETE
a a •:
° d •
. ° C
d QQ
111
Figure 1-1 I
•
4L11
•
• ei
000
V . .
d d C ..
.
. a .
4
0 (r.:1 ° ° °d a • ad .c'
• •d
}d
d' d
d ' d . a
•d C d •
4 a
. d
d° a • •
SEISMIC & WINDLOAD BRACKETS ARE DESIGNED & CALCULATED FOR USE IN SEISMIC/WINDLOAD APPLICATIONS WHEN PROVIDED
AS PART OF A SEISMIC/WINDLOAD RATED CURB.
ATTACHMENT OF CALCULATED BRACKETS TO ANY OTHER CURB DOES NOT CONSTITUTE A SEISMIC /WINDLOAD RATED ASSEMBLY.
Consult Local Building Codes & FEMA Manual. 412/December 2002 VC3 Concrete Installation.dwq
PRINTPII•4/9R/1d
ls thyba r Wood Beam Mounting
00000tAT,ON
111 Thybar makes ii right rhe first tame, VI B RO C U R B ON
every tine
WOODEN STRUCTURAL BEAM
INSTALLATION OPTIONS
The curbs can be installed on a wood—beam type roof providing there is adequate
support around entire curb perimeter. The beam load carrying capability is to be
determined by others and the following provisions are acceptable:
* Curb base is the be through—bolted to wood joists of roof support.
* Through bolts are to be manufactured according to ASTM A307.
* Bolts are to be 4" diameter minimum and length as required to positively attach
to building structure.
* Bolts are to be installed in every hole in the roof curb base flange and
tightened according to bolt manufacturer's recommendations.
INSTALL (1) }"o
ASTM A307 ALL—THREAD BOLT,
LENGTH AS NECESSARY
IN EACH CURB FLANGE
CURB HOLE AT CURB BASE
"II WOOD BEAM — SIZED
BY OTHERS TO PROVIDE
:! \`
SUPPORT UNDERENTIRE
LE
CURB LENGTHHAND WIDTH.
trA0
gip
V
�/
V
____...„.
THROUGH BOLTED ON BEAM UNDERSIDE
WITH NUT, BOLT AND WASHER
' THYBAR CURB SECTION
AS NECESSARY TO ATTACH
CURB TO BUILDING ROOF
SUPPORT STRUCTURE. OWOOD BEAM
SIZED BY OTHERS
761 - -
i
VC3 Wood Beam Mounting.dwg
Print Date:6/12/2012
THYBAR CORPORATION
913 S. Kay Avenue
Addison, IL 60101
800-666-CURB(2872)
Fax:630-543-5309
www.thybar.com
Member of
VISCIA
Seismic /130 MPH Wind Load Calculations for a
Aaon A Cabinet RN-008 (920AHU04) on a
Thybar Insulated VibroCurblll Roofcurb
in Tigard OR 97224
CWS Durham 0 and M Building Remodel
Thybar Order#: 184599
August 22, 2018
$iv1'oCTuki
.<..c 0 PR0s
"(,L N,�F sfo
'19695 'P
itt
•RECON
'1tY 1,199
STFl/EN C.OP\ 8.23.18
RENEWAL DATE: 12.31.19
Digitally signed by Steven C Ball,SE
Steven C Ball, SE DN..osi E=sball@johnmaes, n .
O="John A Martin&Associates,Inc",
CN=Steven Ball,SE"
Date:2018.08.23 13:10:39-07'00'
ZN
a; This analysis considers the wind and seismic force
t° calculations and anchorage of the curb to the structure only. Reviewed by:
Qo The supporting structure shall be reviewed and approved by others. Hossain Ghaffari
ta The curb design and unit anchorage to the curb is by Thybar. 08-23-2018
No installation shall take place until the anchorage and supporting
JOHN A. MARTIN structure area roved bytheappropriate urisdiction.
& ASSOCIATES, INC. pp1
Structural Engineers
This document contains proprietary information from Thybar Corporation. Its contents may not be used for any other
project or location other than the project or location for which it was created without the prior written permission of
Thybar Corporation.
8/22/2018
Unit: Aaon A Cabinet RN-008 (920AHU04)
Location: Tigard OR 97224
Curb: Insulated VibroCurblll
Governing Code: 2014OSSC / IBC2012
SDC: D
Design Wind Speed: 130 MPH
CWS Durham 0 and M Building Remodel
These calculations begin with the assumption that the Thybar curb is
supported around its full perimeter by building structure. Design of building
structure is not the responsibility of Thybar Corporation.
A 29 inch high Thybar Insulated VibroCurblll of minimum 14 gage galvanized
side wall construction will meet the 2014OSSC / IBC2012 requirements for
installing an Aaon A Cabinet RN-008 (920AHU04) unit in Tigard OR 97224
when manufactured with bulkheads installed 31 inches max OC and installed
according to the attached drawings.
The unit must be attached to the Thybar Insulated VibroCurblll using 12 gage
restraint brackets. Bracket quantity is determined in the calculations and is
summarized as follows:
Minimum 12 gage bracket quantity: 4
The Thybar Insulated VibroCurblll must be attached to the building structure
using welds or bolts at the curb base flanges. Flange connection minimum bolt
quantity is determined in the calculations and is summarized as follows:
Total connection minimum quantity: 26
As curb manufacturers, Thybar Corporation cannot be expected to provide
appropriate attachment hardware for every possible type of roof structure.
Thybar provides seismic/windload calculations that are based on the material
provided; typically sheet metal curbs. It is the responsibility of others (project
engineer, architect, SEOR, etc) to know enough about the load carrying
capability of the building structure to design a method of attachment to that
structure. Thybar does not design the structure and therefore should not
recommend an attachment method that may create difficulties with existing
field conditions outside of the curb manufacturer's control.
Summary 1
Thybar Corporation 8/22/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
Location Tigard OR 97224
General
Applicable Building Code 2014OSSC/
IBC2012
Seismic Design Category(SDC) D
Unit Manufacturer Aaon
Unit Model A Cabinet RN-008
(920AHU04)
Length(in) 97.88
Equip Width(in) 79.00
Height(in) 44.0
Weight(Ib) 1,370
CG„,(in) 42.70
CG,,,(in) 28.50
Curb Type Insulated
VibroCurbl I I
Curb Length(in) 77.50
Curb Width(in) 39.25
Curb Height(in) 29.00
Minimum Pedestal Thickness(ga) 14
Bulkhead max OC spacing(in) 31
F,(psi) 31000
E(psi) 30,000,000
Thickness(in) 0.0670
u 0.3
I(in) 29.0
Curb - h/t 433
b/t 463
k, 4.0
110 1.0
F.(psi) 507
Snow Importance,I 1.2
Snow Load,pf(lb) 1,439
Curb Design Load,0.75`max(Wind, 2,236
.7'Seismic)+0.75S,(Ib)=
0.4•Fy=F,(psi) 12,000
0.61F,=F,(psi) 18,000
Wind Load(130mph)Fw(lb)= 929
Exposure Category= B
Rooftop height(ft)= 20
Velocity Pressure coefficient Kz= 0.70
Topography factor Kzt= 1.00
Wind Directionality factor Kd= 0.90
Wind Speed V= 130
Importance factor Iw= N/A
qz= 27.26
GCr . 1.90
F,= 2,204
FE = 2,351
FE Mln= 441
Sos= 0.715
So,= 0.442
a,= 2.50
Ip= 1.50
Seismic R,= 2.00
z/h= 1.0
Ss(%ofg)= 96.10
S,(%of g)_ 41.90
Site Coefficient F,= 1.12
Site Coefficient F,= 1.58
Site Soil Classification= D
Seismic Upward Force(Ib),F up= 195.94
ex(in) 6.2375
ey)in) 11
Curb Load ax+ 1.362
Distribution _
Factors ax 0.616
ay+ 0.639
ay- 0.361
C,,,,(Ib/in) 32.0
Curb Loads C,,,,(lb/in) 3.94
Shear Wall Factor a, 0.691
R Unit shear,v(lb/in) 39.383
S e Curb Long Unit Overtuming,Cu(Ib/in) 17.7
u a Dimension Unit Uplift,T(Ib) 324
p c Curb Overturning,Cc(lb/in) 174.6
p t
o i Curb Corner Uplift,Tc(lb/in) 3.31
✓ o Shear Wall Factor a, 0.639
t n Unit shear,v(lb/in) 18.446
s Curb Short Unit Overturning,Cu(Ibfin) 4.068
Dimension Unit Uplift,T(Ib) 814.698
Curb Overturning,Cc(lb/in) 41.415
Curb Corner Uplift,Tc(Ib/in) 20.757
• Max Shear(lb/in) 29.5
Shear f,(psi) 441
fiFy <1.0,OK
Curb Verification 0.04
Max Axial Reaction(lb/in) 32.0
Axial f,(psi) 478
f,/F, 0.94 <1.0,OK
Load Calcs 2
Thybar Corporation 8/22/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
General
Location Tigard OR 97224
Applicable Building Code 20140SSC/IBC2012
Unit Model A Cabinet RN-008(920AHU04)
Curb Type Insulated VibroCurblll
Bracket Dimensions
Length(in) 16
Max bending arm(in) 2.2
Max torsion arm(in) 0.001
Minimum Material thickness(ga) 12
Material thickness(in) 0.0970
Fy(psi) 30,000
Area(in2) 1.552
Screws
Screw size/type(#) 10
Quantity of screws 7
Hole size(in) 1/4
Allowable pullout(lb/screw) 1146
Max pullout(lb/bracket) 8,019
Allowable shear(lb/screw) 1,206
Max shear(lb/bracket) 8,445
Torsion on Bracket
Fy=0.4*Fy(psi) 12,000
Max shear(Ib) 602,176
Flexure on Bracket
Fb=0.6*Fy(psi) 18,000
Max shear(Ib) 33,862
Shear on Bracket Attachment Holes
Distance-hole edge to bracket edge 0.375
Max shear(Ib) 3,056
Tension on Bracket
FT=0.4*Fy(psi) 12,000
TMax(lb) 16,587
Bracket Capacity
'Allowable Load(Ib) j 3,0561
Bracket Verification
Horizontal Design Load(Ib) 2,236 2,236
Curb Length/Width(in) 77.50 39.25
Shear Wall Factor 0.69 0.64
Design Shear(Ib) 1,546 1,430
Unit Design Uplift,Tc(lb) 323.71 814.70
Unit Uplift,Tc(Ib) 224 521
R=(V2+122)"2 1,562 1,521
#per side 0.51 0.50
Clip Safety Factor 2
Total Clips Required 4
Unit To Curb 3
Thybar Corporation 8/22/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
General
Location Tigard OR 97224
Applicable Building Code 2014OSSC/ IBC2012
Unit Model A Cabinet RN-008 (920AHU04)
Curb Type Insulated VibroCurblll
Material Properties
Fy(psi) 30,000
Material Allowable Stress, Fa 12,000
(psi)
Base Attachment Dimensions
Hole Size (in) 0.625
Number of Holes per
attachment 1
Min. Material thickness (ga) 14
Min. Material thickness (in) 0.1340
Cut out area (in2) 0.307
Base flange width (in) 2.0
Edge distance (in) 11/16
Base shear area (in2) 0.09
Base Attachment Forces
Length Width
Horizontal Design Load (Ib) 2236.39 2236.39
Length (in) 77.50 39.25
Shear(Ib) 1,546 1,430
Unit Uplift, Tc(Ib) 224 521
R= (V2 +T22)112 1,562 1,521
Length Width
Base Attachment Stresses-fa 1,060 1,652
(psi)
Base Safety Factor 2 2
fa/Fa 0.18 0.28
Base Attachment Minimum 16 10
Quantity
Minimum Base Attachments- 26
Perimeter Distributed
Base Attachment Holes 4
Thybar Corporation 8/22/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
Support Reactions
Unit:A Cabinet RN-008(920AHU04)
Gravity Load Isolators
C9mam=W(P)*ax+*ay+/L, Cg W(P) F(p) N(ns) N L1(in) H1
=15.6 lb/in X Y 1,370 2,236 4 4 77.50 44.00
C9mi„=W(P)*a,-*ay.JL, 42.70 28.50
=3.9 lb/in
Seismic North-South F(p) Lc h, L2 B2
Unit Overturning C„.F(p)*H,/2*a„+/L2/B2 2236.39 41 8/16 7.25 77.5 39.25
=22.4 lb/in ax+ I ax- I ay+ I ay-
1.382 0.617624521 0.639 0.361
Unit Uplift Tu=max(0,C,;W(p)*a,+*ay/L2)
=13.5 lb/in
Seismic East-West hi:Isolator Height(in) L„(in)=Max Isolator spacing
Unit Overturning Cu=F(p)*H,/2*ay+/L2/B2 29 41.50 Calculation Summary
=10.3 lb/in Ly(in)=Channel Max Lateral Support Spacing OK
Unit Uplift Tu=max(0,C,;W(p)*ay+*ay/L2) 41.50
=3.4 lb/in
Curb Verification
Transverse Load on Structural Channel Stabilizer Bolt Vertical Channels Isolator Stresses
Channel Height Bolts per isolator,n channels per isolator,n Isolator height:h
=6 in =2 =2 71/4 in
Channel Type Eccentricity Allowance(e): M„s=Vas*h,/n Isolator width:W
F,bin.)aqa 0.02 in =2,802 in lb =4.0 in
Vb=max(V„,,Va,,,)/n Me1.,=Ve,,,*hi In Isolator length:L
w„(lb/in)=C9+Cu(ns) =386 lb =1,585 in lb =10.0 in
=38. lb/in M=Vb*e fb,=MniS, Isolator Sx BL*tb2/6
wy(lb/in)=F(p)*IN(ns)/N]/2/L1*(a,+) =8 in lb =1,269 psi =87.6 in3
=19.94539 lb/in Tb=max(Tne,Taw)/n 1,„=V„„/(d1) Isolator Sy Bw*tb2/6
M,=w,*L,2/8 =280.99 lb =773 psi =35.042 in3
=8,177 in lb fb=M/S fby=Me„/Sy fby=MeuJSy
My=wy*Ly2/8 =187 psi =4,118 psi =45 psi
=4,294 in lb f„=V/A fy,=Ve11,/(2*b*t) fb,=Mna/S,
fb,=M,/S, =875 psi =500 psi =32 psi
=7,213 psi f,=T/A fb/Fb,+f,„/F„ fby/Fby
fby=My/Sy =636.03 psi =.11 <1.7,OK 0.00<1.0,OK
=8,986 psi fb/Fb+f,/F,+f,/F, fb JFby+fy/F„ fb/Fb,
fb/Fb, =.13<1.7,OK =.19<1.7,OK 0.00<1.0,OK
=.33<1.0,OK Isolator Check Channel Loading
fb,/Fb,+fby/Fby T„a=Tu*Le Curb Perimeter,P
=.75<1.7,OK =561.98 lb =233.50 in
V„,=F(p)/N*a,+ w=W(p)/P
=773 lb =5.87 lb/in
Tew=T„*Lc Mme,=w*L,2/8
=139.39 lb =1,263.34 in*lb
Vow=F(p)/N*ay+*2 fa=M,„,„/S„
=437 lb =1,114 psi
fu/F,
=.03<1.0,OK
Vibro Calcs 5
8/22/2011
I
Aaon A Cabinet Unit
II t hybar Tigard OR
III CORPORA
OIOI HON SEISMIC/WINDLOAD RESTRAINT BRACKET
Thybat rodkes it
e
right the est rine,
every re INSTALLATION DETAILS FOR VIBROCURBS
;
INSTALLATION INSTRUCTIONS:
PLACE RESTRAINTS IN APPROXIMATE LOCATIONS AS SHOWN. __
EQUALLY DISTRIBUTE RESTRAINT AS MUCH AS POSSIBLE WHILE AVOIDING INTERFERENCES WITH
LIFTING LUGS,CONDENSATE DRAIN LINES,UNIT BASE SCREWS,ETC.
GASKET TOP PERIMETER OF CURB AND RESTRAINTS BEFORE SETTING UNIT. {; UNIT
SEE MATRIX BELOW FOR QUANTITIES REQUIRED PER UNIT. !
/ I #I I„
( I TO _ 'LA,
NI .. . �.
it
IF I< `I FP:
/
/ L1r_t,iLj.i.
�-� 1=1..
CRA I:_
NOTE:
DRAWINGS ARE CONCEPTUAL,NOT TO SCALE
INNER RESTRAINTS MUST BE FIELD INSTALLED TO ROOF CURB AFTER SETTING UNIT. RESTRAINT DETAIL
Aaon THYCURBMODEL RESTRAINT BRACKET QTY. [JAlf=F'IAL. 44`,'-',1:IZ EC ;TG L1GI1,4 PTV'. !:)Ii
SEISMIC RESTRAINTS PER UNIT
Aaon A Cabinet RN-OW(920AHU04) ACSWRANB0009RC-01 4 rI L1 r-�,/`/Ah-'E Iii IT I -'II TSI" =1--�EA,' I'E`" fit_-T r=,[�l T.
SEISMIC&WINDLOAD BRACKETS ARE DESIGNED&CALCULATED FOR USE IN SEISMIC/WINDLOAD APPLICATIONS WHEN PROVIDED
AS PART OF A SEISMIC/WINDLOAD RATED CURB.
ATTACHMENT OF CALCULATED BRACKETS TO ANY OTHER CURB DOES NOT CONSTITUTE A SEISMIC/WINDLOAD RATED ASSEMBLY.
REVISION DATE 8/22/2018
testraint Bracket Detail
la t hyba rlvl • Structural Steel Mounting
CO 'ocAl CThi
III Thybat makes it right the first time,
eve,/tit,e SEISMIC / WIND LOAD VC3 CURB
INSTALLATION OPTIONS
The equipment support should be anchored to structural steel as follows:
* The width of the supporting structural steel shall be at least as wide as the base plate
of the equipment support.
* Bolts, nuts and washers are to be ASTM A307 grade.
* Bolts should be placed in every hole provided in the base plate of the equipment support;
pass through the base plate of the curb and the structural steel; and tightened according
to manufacturers torque specifications. (Figure 1-1)
* Alternatively, the curb may be welded to the structural steel. (Figure 1-2)
BOLT WITH WASHER
(}" DIAMETER MINIMUM)
illr
Lumer,
jme
NUT WITH WASHER iL
STRUCTURAL III
MilV STEEL
Figure 1-1
CENTERED ON XI" 4
EACH BOLT HOLE V
A I b
4
4 I I I I I I I iiii I 411111 '11 4 1 1 I I illi 11.111.•I"
STRUCTURAL
STEEL
Figure 1-2
Consult Local Building Codes & FEMA Manual. 412/December 2002 VC3 Structural Installation.dwg
PRINTED:3/26/14
® t hyba r Concrete Slab Mounting
CORPONNAiION
N Thybar makes it right me f/st t//me,
1,0y time
SEISMIC / WIND LOAD VC3 CURB
INSTALLATION OPTIONS
The equipment support should be anchored to concrete as follows:
* Anchor system must comply with applicable building code (Local building code,
International Building Code, Uniform Building Code, etc.).
* Anchor to be Hilti Kwik Bolt TZ, Simpson Strong—Tie or equivalent.
* Anchors are to be placed in every hole provided in the base plate of the curb.
* Anchors are to pass through the base plate & be embedded into the concrete.
* Follow anchor manufacturers instructions for drilling holes, installation anchor and
tightening nut.
4111 ANCHOR NT &
G" DIAMETER MINIMUUM,WASHER
EMBEDMENT DEPTH AND
EDGE DISTANCE AS REQUIRED
BY FIELD CONDITIONS AND
HARDWARE SELECTION.)
1111111
111
CONCRETE
° •
* .
° d
. as . ° . 111
Q Q
•
Figure 1-1
.
• m
a
a a ..
. • $•' •
• a •
a a a . a
•
a e a
a a • 4 4. , v
. a
•
SEISMIC & WINDLOAD BRACKETS ARE DESIGNED & CALCULATED FOR USE IN SEISMIC/WINDLOAD APPLICATIONS WHEN PROVIDED
AS PART OF A SEISMIC/WINDLOAD RATED CURB.
ATTACHMENT OF CALCULATED BRACKETS TO ANY OTHER CURB DOES NOT CONSTITUTE A SEISMIC /WINDLOAD RATED ASSEMBLY.
Consult Local Building Codes & FEMA Manual. 412/December 2002 VC3 Concrete Installation.dwq
PRIMTFfl•4/7A/14.
.,
m t hy ba r Wood Beam Mounting
coizi'oitA, ON
■ Thyba„N,ekeslcright the fit sttime, VIBROCURB ON
.very tire
WOODEN STRUCTURAL BEAM
INSTALLATION OPTIONS
The curbs can be installed on a wood—beam type roof providing there is adequate
support around entire curb perimeter. The beam load carrying capability is to be
determined by others and the following provisions are acceptable:
* Curb base is the be through—bolted to wood joists of roof support.
* Through bolts are to be manufactured according to ASTM A307.
* Bolts are to be 2” diameter minimum and length as required to positively attach
to building structure.
* Bolts are to be installed in every hole in the roof curb base flange and
tightened according to bolt manufacturer's recommendations.
INSTALL (1) "0
ASTM A307 ALL-THREAD BOLT,
LENGTH AS NECESSARY
IN EACH
CURBA HOLE AT CURB CURB BASE
Hie WOOD BEAM - SIZED
V
C BY OTHERS TO PROVIDE
/�'/2 r yLE SUPPORTUNDERENTIRE
�� i1j CURB LENGTH AND WIDTH.
V0V
\
11114V /
' V
V
V
V
V
�N
THROUGH BOLTED ON BEAM UNDERSIDE
WITH NUT, BOLT AND WASHER THYBAR CURB SECTION
AS NECESSARY TO ATTACH
CURB TO BUILDING ROOF
SUPPORT STRUCTURE. 1 i,, WOOD BEAM
400110:00 SIZED BY OTHERS
VC3 Wood Beam Mounting.dwg
Print Date:6/12/2012
THYBAR CORPORATION
913 S. Kay Avenue
Addison, IL 60101
800-666-CURB(2872)
Fax:630-543-5309
www.thybar.com
Member of
VISCIA
Seismic /130 MPH Wind Load Calculations for a
Aaon RQ Cabinet RQ-006 (920AHU05) on a
Thybar Insulated VibroCurblll Roofcurb
in Tigard OR 97224
CWS Durham 0 and M Building Remodel
Thybar Order#: 184599
August 22, 2018
0,..UCTLij1
4v0 PROF�Ss�
(4,x-GN
IF9
'14
19695
M REGON
4101Y1,199%
SrFVEN C•SP'\ 8.23.18
RENEWAL DATE: 12.31.19
Digits*signed by Steven C Ball,SE
ON:C=US,
SE
E-sball@johnmartin.com,O�"John
Steven C Ball, $E A Martin&Associates,Inc",
CN-,`Steven C Ball,SE"
Date:2018.08.23 13:10:52.07'00'
Z N
RThis analysis considers the wind and seismic force Reviewed by:
calculations and anchorage of the curb to the structure only. Hossain Ghaffari
cr o The supporting structure shall be reviewed and approved by others.
co The curb design and unit anchorage to the curb is by Thybar. 08-23-2018
No installation shall take place until the anchorage and supporting
JOHN A.
& ASSOCIAT S. I structure are approved by the appropriate jurisdiction.
Structural Engineers
This document contains proprietary information from Thybar Corporation. Its contents may not be used for any other
project or location other than the project or location for which it was created without the prior written permission of
Thybar Corporation.
8/22/2018
Unit: Aaon RQ Cabinet RQ-006 (920AHU05)
Location: Tigard OR 97224
Curb: Insulated VibroCurblll
Governing Code: 2014OSSC / IBC2012
SDC: D
Design Wind Speed: 130 MPH
CWS Durham 0 and M Building Remodel
These calculations begin with the assumption that the Thybar curb is
supported around its full perimeter by building structure. Design of building
structure is not the responsibility of Thybar Corporation.
A 29 inch high Thybar Insulated VibroCurblll of minimum 14 gage galvanized
side wall construction will meet the 2014OSSC / IBC2012 requirements for
installing an Aaon RQ Cabinet RQ-006 (920AHU05) unit in Tigard OR 97224
when manufactured with bulkheads under each isolator and installed according
to the attached drawings.
The unit must be attached to the Thybar Insulated VibroCurbill using 12 gage
restraint brackets. Bracket quantity is determined in the calculations and is
summarized as follows:
Minimum 12 gage bracket quantity: 4
The Thybar Insulated VibroCurblll must be attached to the building structure
using welds or bolts at the curb base flanges. Flange connection minimum bolt
quantity is determined in the calculations and is summarized as follows:
Total connection minimum quantity: 18
As curb manufacturers, Thybar Corporation cannot be expected to provide
appropriate attachment hardware for every possible type of roof structure.
Thybar provides seismic/windload calculations that are based on the material
provided; typically sheet metal curbs. It is the responsibility of others (project
engineer, architect, SEOR, etc) to know enough about the load carrying
capability of the building structure to design a method of attachment to that
structure. Thybar does not design the structure and therefore should not
recommend an attachment method that may create difficulties with existing
field conditions outside of the curb manufacturer's control.
Summary 1
Thybar Corporation 8/22/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
Location Tigard OR 97224
General
Applicable Building Code 2014OSSC/
IBC2012
Seismic Design Category(SDC) D
Unit Manufacturer Aeon
Unit Model RQ Cabinet RO-006
(920AHU05)
Length(in) 100.13
Equip Width(in) 44.25
Height(in) 50.5
Weight(lb) 1,007
CO,,(in) 44.00
CG,.,(in) 19.60
Curb Type Insulated
VibroCurblll
Curb Length(in) 77.50
Curb Width(in) 39.25
Curb Height(in) 29.00
Minimum Pedestal Thickness(ga) 14
Bulkhead max OC spacing(in) 42
F..(psi) 30,000
E(psi) 30,000,000
Thickness(in) 0.0670
u 0.3
Curb I(in) 29.0
hit 433
b/t 627
k, 4.0
k, 1.0
F.(psi) 276
Snow Importance,I 1.2
Snow Load,pf(lb) 824
Curb Design Load,0.75'max(Wind, 1 469
.7'Seismic)+0.755,(Ib)=
0.4*F„=F„(psi) 12,000
0.6"F,=F,(psi) 18,000
Wind Load(130mph)Fw(Ib)= 1,091
Exposure Category= B
Rooftop height(ft)= 20
Velocity Pressure coefficient Kz= 0.70
Topography factor Kzt= 1.00
Wind Directionality factor Kd= 0.90
Wind Speed V= 130
Importance factor Iw= N/A
qz= 27.26
GCr 1.90
FE= 1,620
FE Ma.= 1,728
Fmk,= 324
SDs= 0.715
SDI= 0.442
ap= 2.50
Ip= 1.50
Seismic Rr= 2.00
z/h= 1.0
Ss(%ofg)= 96.10
Si(%of g)= 41.90
Site Coefficient F.= 1.12
Site Coefficient F,= 1.58
Site Soil Classification= D
Seismic Upward Force(Ib),F up= 143.99
ex(in) 6.0625
ey(in) 2.525
Curb Load ax+
Distribution 1.363
Factors ax- 0.637
ay+ 0.557
ay- 0.443
C,,,,(lb/in) 17.9
Curb Loads (lb/in) 3.66
Shear Wall Factor a, 0.682
R Unit shear,v(lb/in) 25.508
S e Curb Lona Unit Overturning,Cu(lb/in) 12.9
u a Dimension Unit Uplift,T(Ib) 624
p c Curb Overturning,Cc(Ib/in) 113.1
p t
o i Curb Corner Uplift,Tc(lb/in) 6.23
▪ o Shear Wall Factor as 0.557
t n Unit shear,v(lb/in) 10.557
s Curb Short Unit Overturning,Cu(Ib/in) 4.663
Dimension Unit Uplift,T(Ib) 528.454
Curb Overturning,Cc(lb/in) 23.703
Curb Corner Uplift,Tc(lb/in) 13.464
Max Shear(lb/in) 19.1
Shear 1,(psi) P88
0.02 <1.0,OK
Curb Verification
Max Axial Reaction(Ib/in) 17.9
Axial f,(psi) 268
1,/F, 0.97 <1.0,OK
Load Calcs 2
Thybar Corporation 8/22/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
General
Location Tigard OR 97224
Applicable Building Code 2014OSSC/IBC2012
Unit Model RQ Cabinet RQ-006(920AHU05)
Curb Type Insulated VibroCurblll
Bracket Dimensions
Length (in) 16
Max bending arm(in) 2.2
Max torsion arm(in) 0.001
Minimum Material thickness(ga) 12
Material thickness(in) 0.0970
Fy(psi) 30,000
Area(in2) 1.552
Screws
Screw size/type(#) 10
Quantity of screws 7
Hole size(in) 1/4
Allowable pullout(lb/screw) 1146
Max pullout(lb/bracket) 8,019
Allowable shear(lb/screw) 1,206
Max shear(lb/bracket) 8,445
Torsion on Bracket
Fv=0.4*Fy(psi) 12,000
Max shear(Ib) 602,176
Flexure on Bracket
Fb=0.6*Fy(psi) 18,000
Max shear(Ib) 33,862
Shear on Bracket Attachment Holes
Distance-hole edge to bracket edge 0.375
Max shear(Ib) 3,056
Tension on Bracket
FT=0.4"Fy(psi) 12,000
TMaX(Ib) 16,587
Bracket Capacity
Allowable Load(lb) 3,056
Bracket Verification
Horizontal Design Load (Ib) 1,469 1,469
Curb Length/Width(in) 77.50 39.25
Shear Wall Factor 0.68 0.56
Design Shear(Ib) 1,001 818
Unit Design Uplift,Tc(Ib) 623.50 528.45
Unit Uplift,Tc(Ib) 425 294
R=(V2+122)1/2 1,088 870
#per side 0.36 0.28
Clip Safety Factor 2
Total Clips Required 4
Unit To Curb 3
Thybar Corporation 8/22/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
General
Location Tigard OR 97224
Applicable Building Code 20140SSC/IBC2012
Unit Model RQ Cabinet RQ-006 (920AHU05)
Curb Type Insulated VibroCurblll
Material Properties
Fy(psi) 30,000
Material Allowable Stress, Fa 12,000
(psi)
Base Attachment Dimensions
Hole Size (in) 0.625
Number of Holes per 1
attachment
Min. Material thickness (ga) 14
Min. Material thickness (in) 0.1340
Cut out area (in2) 0.307
Base flange width (in) 2.0
Edge distance (in) 11/16
Base shear area (in2) 0.09
Base Attachment Forces
Length Width
Horizontal Design Load (Ib) 1468.78 1468.78
Length (in) 77.50 39.25
Shear(lb) 1,001 818
Unit Uplift, Tc(Ib) 425 294
R= (V2 +122)1/2
1,088 870
Length Width
Base Attachment Stresses -fa 984 1,573
(psi)
Base Safety Factor 2 2
fa/Fa 0.16 0.26
Base Attachment Minimum 12 6
Quantity
Minimum Base Attachments- 18
Perimeter Distributed
Base Attachment Holes 4
Thybar Corporation 8/22/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
Support Reactions
Unit: RQ Cabinet RQ-006(920AHU05)
Gravity Load Isolators
C9„,ax=W(p)*ax+*ay+/L, Cg W(p) F(p) N(ns) N L1(in) H1
=9.9 lb/in X Y 1,007 1,469 4 4 77.50 50.50
Co,.=W(p)*ax_*ayJL1 44.00 19.60
=3.7 lb/in
Seismic North-South F(p) Le h1 L2 B2
Unit Overturning Cu=F(p)*Hi/2*ax+/L2/B2 1468.78 41 8/16 7.25 77.5 39.25
=16.6 lb/in I ax+ I ax- I ay+ I ay- I
1.363 0.63670412 0.557 0.443
Unit Uplift Tu=max(0,C,;W(p)*ax+*ay-/L2)
=8.8 lb/in
Seismic East-West hi:Isolator Height(in) Lx(in)=Max Isolator spacing
Unit Overturning C„=F(p)*Hi/2*ay+/L2/B2 29 41.50 Calculation Summary
=6.8 lb/in Ly(in)=Channel Max Lateral Support Spacing OK
Unit Uplift Tu=max(0,C,;W(p)*ay+*ax-/L2) 41.50
=2.2 lb/in
Curb Verification
Transverse Load on Structural Channel Stabilizer Bolt Vertical Channels Isolator Stresses
Channel Height Bolts per isolator,n channels per isolator,n Isolator height:h
=6 in =2 =2 71/4 in
Channel Type Eccentricity Allowance(e): M.=Y..*hi/n Isolator width:W
F,6in.saga 0.02 in =1,815 in lb =4.0 in
Vb=max(V0,,Vew)/n Me„,=Vey,*h1/n Isolator length:L
wx(lb/in)=Ce+Cu(ns) =250 lb =1,195 in lb =10.0 in
=26.5 lb/in M=Vb*e fbx=M„x/Sx Isolator Sx BL*tb2/6
wy(lb/in)=F(p)*[N(ns)/N]/2/L1*(ax+) =5 in lb =822 psi =87.6 in3
=12.9186 lb/in Tb=max(T,,,,Te,„)/n f„x=V„,/(d*t) Isolator S,Bw*tb2/6
Mx=wx*Lx2/8 =182.09 lb =501 psi =35.042 in3
=5,703 in lb fb=M/S fby=McM/Sy fby=Me„/Sy
My=wy*Ly2/8 =121 psi =3,103 psi =34 psi
=2,781 in lb f„=V/A fy,=Ve„,/(2*b*t) fbx=M../Sx
fbx=MA. =567 psi =377 psi =21 psi
=5,030 psi ft=T/A fbx/Fbx+f„x/F„ fb)Fby
fby=My/Sy =412.17 psi =.07<1.7,OK 0.00<1.0,OK
=5,820 psi fb/Fb+f,/F„+ft/Ft fby/Fby+fh/F„ fbx/Fbx
fbx/Fbx =.08<1.7,OK =.14<1.7,OK 0.00<1.0,OK
=.23<1.0,OK Isolator Check Channel Loading
fbx/Fbx+fby/Fby T,,,=T„*Lc Curb Perimeter,P
=.50<1.7,OK =364.19 lb =233.50 in
V„x=F(p)/N*ax+ w=W(p)/P
=501 lb =4.31 lb/in
Tow=T„*L0 M„,ax=w*Lx2/8
=90.61 lb =928.38 in*Ib
yew=F(p)/N*ay+*2 e=M„,ax/Sx
=330 lb =819 psi
fx/Fa
=.02<1.0,OK
Vibro Calcs 5
8/22/2011
Mon RQ Cabinet Unit 111
t hybar Tigard OR
■ CORP ONAI,ON SEISMIC/WINDLOAD RESTRAINT BRACKET
ThyU,,makes It right the fh zt time e.
eves}•tunINSTALLATION DETAILS FOR VIBROCURBS
INSTALLATION INSTRUCTIONS:
PLACE RESTRAINTS IN APPROXIMATE LOCATIONS AS SHOWN. --- �......
EQUALLY DISTRIBUTE RESTRAINT AS MUCH AS POSSIBLE WHILE AVOIDING INTERFERENCES WITH .- "�
LIFTING LUGS,CONDENSATE DRAIN LINES,UNIT BASE SCREWS,ETC. III`
GASKET TOP PERIMETER OF CURB AND RESTRAINTS BEFORE SETTING UNIT.
SEE MATRIX BELOW FOR QUANTITIES REQUIRED PER UNIT. I 711:1 - - I✓
I;
0
tl
F[
i
i ? 1 TLI _;:i LV'1'
i i
II
1/-I' crFrP, I
!
I _- :I
eL T ;Hi
(PACK:ET
r---1
NOTE: _,. _ _
DRAWINGS ARE CONCEPTUAL,NOT TO SCALE
INNER RESTRAINTS MUST BE FIELD INSTALLED TO ROOF CURB AFTER SETTING UNIT. RESTRAINT DETAIL
THYCURB MODEL RESTRAINT BRACKET QTY. „
Aaon MATERIAL yL.44 iiZED ATE L P I.I F I 4-i d Olv
SEISMIC RESTRAINTS PER UNIT
HA:. 41/`,PE ( 14 n IG I" TEI �_:FE v' i E . PE3TPL.If IT
Aaon RQ Cabinet RQ-006(920AHU05) ACSWRANB0009RC-01 4
SEISMIC&WINDLOAD BRACKETS ARE DESIGNED&CALCULATED FOR USE IN SEISMIC/WINDLOAD APPLICATIONS WHEN PROVIDED
AS PART OF A SEISMIC/WINDLOAD RATED CURB.
ATTACHMENT OF CALCULATED BRACKETS TO ANY OTHER CURB DOES NOT CONSTITUTE A SEISMIC/WINDLOAD RATED ASSEMBLY.
REVISION DATE 8/22/2018
testraint Bracket Detail
■ thybar
Structural Steel Mounting
CONPPO,jai rON
1117hy6ar makes h right the fist time,
ev 1yti" SEISMIC / WIND LOAD VC3 CURB
INSTALLATION OPTIONS
The equipment support should be anchored to structural steel as follows:
* The width of the supporting structural steel shall be at least as wide as the base plate
of the equipment support.
* Bolts, nuts and washers are to be ASTM A307 grade.
* Bolts should be placed in every hole provided in the base plate of the equipment support;
pass through the base plate of the curb and the structural steel; and tightened according
to manufacturers torque specifications. (Figure 1-1)
* Alternatively, the curb may be welded to the structural steel. (Figure 1-2)
Al BOLT WITH WASHER
110
(" DIAMETER MINIMUM)
i %��
NUT WITH WASHER iL
STRUCTURAL
itSTEEL
Figure 1-1
CENTERED ON lb" 4
EACH BOLT HOLE V
41111111)
1 iniv dr A
Mill r STEEL
STRUCTURAL
I 4 I I I I I I I I I I I 11 1114"4111117')
Figure 1-2
Consult Local Building Codes Sc FEMA Manual. 412/December 2002 VC3 Structural Installation.dw,q
PRINTED:3/26/14
0 thybar Concrete Slab Mounting
CORPONA I:0 1
■ Thybar makes it right the first time,
every time
SEISMIC / WIND LOAD VC3 CURB
INSTALLATION OPTIONS
The equipment support should be anchored to concrete as follows:
* Anchor system must comply with applicable building code (Local building code,
International Building Code, Uniform Building Code, etc.).
* Anchor to be Hilti Kwik Bolt TZ, Simpson Strong—Tie or equivalent.
* Anchors are to be placed in every hole provided in the base plate of the curb.
* Anchors are to pass through the base plate Sc be embedded into the concrete.
* Follow anchor manufacturers instructions for drilling holes, installation anchor and
tightening nut.
L 411
ANCHOR WITH NUT & WASHER
(i" DIAMETER MINIMUM,
_______,.., . ...„..........
EMBEDMENT DEPTH AND
EDGE DISTANCE AS REQUIRED
BY FIELD CONDITIONS AND
HARDWARE SELECTION.)
lin
CONCRETE
•
a ;
a °
a d ° ••
• •A, a..
• a .
Figure 1-1 °:I
4 ILl I"I°...I . . .
•
•
..
IZ)
OO
I°. . 4 4 ' .
•••
d
•
O O
O
d
O d •
.
. d• . O
A
. A .
•
•
SEISMIC & WINDLOAD BRACKETS ARE DESIGNED & CALCULATED FOR USE IN SEISMIC/WINDLOAD APPLICATIONS WHEN PROVIDED
AS PART OF A SEISMIC/WINDLOAD RATED CURB.
ATTACHMENT OF CALCULATED BRACKETS TO ANY OTHER CURB DOES NOT CONSTITUTE A SEISMIC /WINDLOAD RATED ASSEMBLY.
Consult Local Building Codes & FEMA Manual. 412/December 2002 VC3 Concrete Installation.dwq
PRINTER•3/9RH4.
ig t hyba r Wood Beam Mounting
ill
COPIORA Or!
Thybar makes i(right the first time, V I B RO C U RB ON
every Or,e
WOODEN STRUCTURAL BEAM
INSTALLATION OPTIONS
The curbs can be installed on a wood—beam type roof providing there is adequate
support around entire curb perimeter. The beam load carrying capability is to be
determined by others and the following provisions are acceptable:
* Curb base is the be through—bolted to wood joists of roof support.
* Through bolts are to be manufactured according to ASTM A307.
* Bolts are to be 4" diameter minimum and length as required to positively attach
to building structure.
* Bolts are to be installed in every hole in the roof curb base flange and
tightened according to bolt manufacturer's recommendations.
INSTALL (1) "0
ASTM A307 ALL-THREAD BOLT,
LENGTH AS NECESSARY
IN EACH CURB FLANGE
CURB
)OLE AT CURB BASE
1111WOOD BEAM - SIZED
BY OTHERS TO PROVIDE
�� .1,-..-
SUPPORT UNDER ENTIRE
CURB LENGTH AND WIDTH.H.
V
...V
V�
‘ 1.144
11
P
i
�
THROUGH BOLTED ON BEAM UNDERSIDE
WITH NUT, BOLT AND WASHER I THYBAR CURB SECTION
AS NECESSARY TO ATTACH
CURB TO BUILDING ROOF
SUPPORT STRUCTURE. 4,11L WOOD BEAM
II
SIZED BY OTHERS
141%
VC3 Wood Beam Mounting.dwg
Print Date:6/12/2012
THYBAR CORPORATION
III 913 S. Kay Avenue
Addison, IL 60101
800-666-CURB(2872)
Fax:630-543-5309
III www.thybar.com
Member of
VISCIA
Seismic /130 MPH Wind Load Calculations for a
Aaon B Cabinet RN-009 (920AHU06) on a
Thybar Insulated TC-3 Roofcurb
in Tigard OR 97224
CWS Durham 0 and M Building Remodel
Thybar Order#: 184599
August 17, 2018
,3jCTUr,9
� OPROFS.
S
c,4�ca GIN ,4S/o2
�' 19695 9 9r
•REGON
'6141,1,190'
sftVEN C.8th-- 8.23.18
[RENEWAL DATE: 12.31.19
Digitally signed by Steven C Ball,SE
�+C.DN:C=US,E=sball@johnmartin.com,
Steven C Ball, S E O.John A Martin&Associates,Inc",
CN=Steven C Ball,SE"
Date:2018.08.23 13:11:05-07'00'
2 co
m This analysis considers the wind and seismic force
I— t2 calculations and anchorage of the curb to the structure only. Reviewed by:
Q0 The supporting structure shall be reviewed and approved by others. Hossain Ghaffari
io The curb design and unit anchorage to the curb is by Thybar. 08-21-2018
No installation shall take place until the anchorage and supporting
JOHN
H N A.A SR NC. IN structure are approved by the appropriate jurisdiction.
Structural Engineers
This document contains proprietary information from Thybar Corporation. Its contents may not be used for any other
project or location other than the project or location for which it was created without the prior written permission of
Thybar Corporation.
8/17/2018
Unit: Aaon B Cabinet RN-009 (920AHU06)
Location: Tigard OR 97224
Curb: Insulated TC-3
Governing Code: 2014OSSC / IBC2012
SDC: D
Design Wind Speed: 130 MPH
CWS Durham 0 and M Building Remodel
These calculations begin with the assumption that the Thybar curb is
supported around its full perimeter by building structure. Design of building
structure is not the responsibility of Thybar Corporation.
A 19 inch high Thybar Insulated TC-3 of minimum 14 gage galvanized side wall
construction will meet the 2014OSSC / IBC2012 requirements for installing an
Aaon B Cabinet RN-009 (920AHU06) unit in Tigard OR 97224 when
manufactured with stiffeners installed 25 inches max OC and installed
according to the attached drawings.
The unit must be attached to the Thybar Insulated TC-3 using 12 gage
restraint brackets. Bracket quantity is determined in the calculations and is
summarized as follows:
Minimum 12 gage bracket quantity: 4
The Thybar Insulated TC-3 must be attached to the building structure using
welds or bolts at the curb base flanges. Flange connection minimum bolt
quantity is determined in the calculations and is summarized as follows:
Total connection minimum quantity: 8
As curb manufacturers, Thybar Corporation cannot be expected to provide
appropriate attachment hardware for every possible type of roof structure.
Thybar provides seismic/windload calculations that are based on the material
provided; typically sheet metal curbs. It is the responsibility of others (project
engineer, architect, SEOR, etc) to know enough about the load carrying
capability of the building structure to design a method of attachment to that
structure. Thybar does not design the structure and therefore should not
recommend an attachment method that may create difficulties with existing
field conditions outside of the curb manufacturer's control.
Summary 1
Thybar Corporation 8/17/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
Location Tigard OR 97224
General
Applicable Building Code 2014OSSC/
IBC2012
Seismic Design Category(SDC) D
Unit Manufacturer Aeon
Unit Model B Cabinet RN-009
(920AHU06)
Length(in) 110.63
Equip Width(in) 95.75
Height(in) 50.1
Weight(Ib) 1,997
CG,,(in) 44.90
CGr,(in) 3$.90
Curb Type Insulated TC-3
Curb Length(in) 75.88
Curb Width(in) 54.00
Curb Height(in) 19.00
Minimum Thickness(ga) 14
Stiffener max OC spacing(in) 25
F,(psi) 30,000
E(psi) 30,000,000
Thickness(in) 0.0670
u 0.3
I(in) 19.0
Curb h/t 284
b/t 373
kp 4.0
kn 1.0
F.(psi) 779
Snow Importance,I 1.2
Snow Load,pf(lb) 1,971
Curb Design Load,0.75`max(Wind,
.7"Seismic)+0.75S,(lb)= 2376
0.4•Fr=F,(psi) 12,000
0.6•F5=Fr(psi) 18,000
Wind Load(130mph)Fw(Ib)= 1,197
Exposure Category= B
Rooftop height(ft)= 20
Velocity Pressure coefficient Kz= 0.70
Topography factor Kzt= 1.00
Wind Directionality factor Kd= 0.90
Wind Speed V= 130
Importance factor lw= N/A
qz= 27.26
GCr 1.90
FE= 643
FE u = 3,427
FE nun= 643
SDs= 0.715
Sm= 0.442
ao= 1.00
a= 1.50
Seismic Rp= 6.00
z/h= 1.0
Ss(%ofg)= 96.10
S,(%ofg)= 41.90
Site Coefficient F.= 1.12
Site Coefficient F,= 1.58
Site Soil Classification= D
Seismic Upward Force(lb),F up= 285.58
ex(in) 10.4125
ey(in) 11.975
Curb Load ax., 1.565
Distribution
Factors ax 0.435
ay+ 0.625
ay- 0.375
C,,,,,(Ib/in) 51.2
Curb Loads (Ib/in)
4.30
Shear Wall Factor a, 0.782
R Unit shear,v(lb/in) 34.420
S e Unit Overturning,Cu
Curb Long 9, (lb/in
) 15.6
u a Dimension Unit Uplift,T(Ib) 874
p c
p t Curb Overturning,Cc(lb/in) 72.7
o i Curb Corner Uplift,Tc(lb/in) 6.09
✓ o Shear Wall Factor a, 0.625
t n Unit shear,v(lb/in) 19.571
s Curb Short Unit Overturning,Cu(lb/in) 3.514
Dimension Unit Uplift,T(Ib) 340.596
Curb Overturning,Cc(lb/in) 29.405
Curb Corner Uplift,Tc(lb/in) 6.307
Max Shear(lb/in) 25.8
Shear f,(psi) 385
Curb Verification fes" 0.03 <1.0,OK
Max Axial Reaction(lb/in) 51.2
Axial f,(psi) 763
f,/F, 0.98 <1.0,OK
Load Calcs 2
Thybar Corporation 8/17/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
General
Location Tigard OR 97224
Applicable Building Code 20140SSC/IBC2012
Unit Model B Cabinet RN-009(920AHU06)
Curb Type Insulated TC-3
Bracket Dimensions
Length(in) 16
Max bending arm(in) 2.2
Max torsion arm(in) 0.001
Minimum Material thickness(ga) 12
Material thickness(in) 0.0970
Fy(psi) 30,000
Area(in2) 1.552
Screws
Screw size/type(#) 10
Quantity of screws 7
Hole size(in) 1/4
Allowable pullout(lb/screw) 1146
Max pullout(lb/bracket) 8,019
Allowable shear(lb/screw) 1,206
Max shear(lb/bracket) 8,445
Torsion on Bracket
Fv=0.4*Fy(psi) 12,000
Max shear(Ib) 602,176
Flexure on Bracket
Fb=0.6*Fy(psi) 18,000
Max shear(Ib) 33,862
Shear on Bracket Attachment Holes
Distance-hole edge to bracket edge 0.375
Max shear(Ib) 3,056
Tension on Bracket
FT=0.4*Fy(psi) 12,000
TMax(Ib) 16,587
Bracket Capacity
knowable Load(Ib) 3,0561
Bracket Verification
Horizontal Design Load(Ib) 2,376 2,376
Curb Length/Width(in) 75.88 54.00
Shear Wall Factor 0.78 0.63
Design Shear(Ib) 1,859 1,485
Unit Design Uplift,Tc(Ib) 673.96 340.60
Unit Uplift,Tc(lb) 527 213
R=(V2+122)1/2 1,932 1,500
#per side 0.63 0.49
Clip Safety Factor 2
Total Clips Required 4
Unit To Curb 3
Thybar Corporation 8/17/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
General
Location Tigard OR 97224
Applicable Building Code 2014OSSC/ IBC2012
Unit Model B Cabinet RN-009 (920AHU06)
Curb Type Insulated TC-3
Material Properties
Fy(psi) 30,000
Material Allowable Stress, Fa 12,000
(psi)
Base Attachment Dimensions
Hole Size (in) 0.625
Number of Holes per 1
attachment
Min. Material thickness(ga) 14
Min. Material thickness (in) 0.1340
Cut out area (in2) 0.307
Base flange width (in) 2.0
Edge distance (in) 11/16
Base shear area (in2) 0.09
Base Attachment Forces
Length Width
Horizontal Design Load (Ib) 2375.68 2375.68
Length (in) 75.88 54.00
Shear(lb) 1,859 1,485
Unit Uplift, Tc(Ib) 527 213
R= (V2 +T22)112 1,932 1,500
Length Width
Base Attachment Stresses -fa
(psi) 5,243 4,071
Base Safety Factor 2 2
fa/Fa 0.87 0.68
Base Attachment Minimum 4 4
Quantity
Minimum Base Attachments - 8
Perimeter Distributed
Base Attachment Holes 4
8/17/2011
1111 Aaon B Cabinet Unit
t hybar Tigard OR
. CORro ON SEISMIC/WINDLOAD RESTRAINT BRACKET
T31yba„ ,iakesitright,hefnstt,n,e, INSTALLATION DETAILS FOR INSULATED CURBS
INSTALLATION INSTRUCTIONS: --- _._
PLACE RESTRAINTS IN APPROXIMATE LOCATIONS AS SHOWN. '.
EQUALLY DISTRIBUTE RESTRAINT AS MUCH AS POSSIBLE WHILE AVOIDING INTERFERENCES WITH
LIFTING LUGS,CONDENSATE DRAIN LINES,UNIT BASE SCREWS,ETC.
GASKET TOP PERIMETER OF CURB AND RESTRAINTS BEFORE SETTING UNIT. ,tt...t llt'=
SEE MATRIX BELOW FOR QUANTITIES REQUIRED PER UNIT.
t1
r� ;1
f J
� iyy ,1
I
\ .
I
l> I
I '1
NOTE: L
DRAWINGS ARE CONCEPTUAL,NOT TO SCALE
INNER RESTRAINTS MUST BE FIELD INSTALLED TO ROOF CURB BEFORE SETTING UNIT. RESTRAINT DETAIL
Aaon THYCURB MODEL RESTRAINT BRACKET QTY.
MATERIAL �_,_ TAL/AN 'ED STEEL t_O{I TF!It..TIC:N
SEISMIC RESTRAINTS PER UNIT HA _,WAR: 1 7) fj 10.1” i EI ,F ES^`_ PEF RE 'PAH!
Aaon B Cabinet RN-009(920AHU06) ACSWRANBOO1ORC-01 4 1') # "� T { I-F_WS REF RE`,,TF:AP ANT
SEISMIC&WINDLOAD BRACKETS ARE DESIGNED&CALCULATED FOR USE IN SEISMIC/WINDLOAD APPLICATIONS WHEN PROVIDED
AS PART OF A SEISMIC/WINDLOAD RATED CURB.
ATTACHMENT OF CALCULATED BRACKETS TO ANY OTHER CURB DOES NOT CONSTITUTE A SEISMIC/WINDLOAD RATED ASSEMBLY.
REVISION DATE: 8/17/2018
testraint Bracket Detail
thybar Structural Steel Mounting
COR'C)R.A i t
1111Thybar makes a right the hist time,
evary tine
SEISMIC/WIND LOAD INSULATED CURB
INSTALLATION OPTIONS
The curbs should be anchored to structural steel as follows:
* The width of the supporting structural steel shall be at least as wide as the base plate
of the curb.
* Bolts should be ASTM A307 grade min strength, with nuts and washers.
* Bolts should be placed in every hole provided in the base plate of the curb; pass through
the base plate of the curb and the structural steel; and tightened according
to manufacturers torque specifications. (Figure 1-1)
* Alternatively, the curb may be welded to the structural steel. (Figure 1-2)
CO) OLT WITH WASHER
:!r0'.rWOOD NAILER
�;•7r:::�•:.1 (LENGTH TO BE DETERMINED IN FIELD)
CURB ;:�r.iVil
ittri�:r��!r�� �N� VISCMA APPROVED
i". r%:*L SEISMIC/WINDLOAD
i �/ , j// RATED OF
VARIOUS HEIGHTS
MI
STRUCTURAL /
STEEL
NUT WITH WASHER W
Figure 1-1
No
CENTERED ON A" L ire
EACH
EACH BOLT HOLE
v Ovr���.
CURB IP; , ,
.rr��rl��!i•0:
rr��ri•�r0:
STRUCTURAL
STEEL Nill
O
Figure 1-2 .
Consult Local Building Codes & FEMA Manual. 412/December 2002
PRINTED:11/12/15
111 thybar Concrete Slab Mounting
wRwrearON
II Thybat makes it right rite hat ume,
SEISMIC/WIND LOAD INSULATED CURB
INSTALLATION OPTIONS
The equipment support should be anchored to concrete as follows:
* Anchor system must comply with applicable building code (Local building code,
International Building Code, Uniform Building Code, etc.).
* Anchor to be Hilti Kwik Bolt TZ, Simpson Strong—Tie or equivalent.
* Anchors are to be placed in every hole provided in the base plate of the curb.
* Anchors are to pass through the base plate & be embedded into the concrete.
* Follow anchor manufacturers instructions for drilling holes, installation anchor and
tightening nut.
...4:0:S' ANCHOR WITH NUT 8c WASHER
��Al
i'���'�, (4" DIAMETER MINIMUM,
:./.&:�♦`��r TH AND
EDGEEMBEDDISTANCEMENT PAS REQUIRED
'��i Oji�,
BY FIELD CONDITIONS AND
!r%0 ri HARDWARE SELECTION.)
. - •
•
• • a ; •
° CONCRETE
•. •• . THYBAR CURB SECTION
a a
•
•
• ad . . a •
a da .
a Q'
•
a
Figure 1-1
70.
a
\ . a
•;4 d
ad .
a
A. , . •
ad .a •
a a d
�d a a
.
a• • a • a
Q
. .
A
a •
• •
Consult Local Building Codes & FEMA Manual. 412/December 2002 TC3 Concrete Installation.dwg
PRINTPfI•11/17/1 ti
® t hyba r1III Wood Beam Mounting
'''Y"a'.,,axe5"'`g'"' e"' me, INSULATED ROOF CURB ON
WOODEN STRUCTURAL BEAM
INSTALLATION OPTIONS
The curbs can be installed on a wood—beam type roof providing there is adequate
support around entire curb perimeter. The beam load carrying capability is to be
determined by others and the following provisions are acceptable:
* Curb base is the be through—bolted to wood joists of roof support.
* Through bolts are to be manufactured according to ASTM A307.
* Bolts are to be 4" diameter minimum and length as required to positively attach
to building structure.
* Bolts are to be installed in every hole in the roof curb base flange and
tightened according to bolt manufacturer's recommendations.
INSTALL (1) 1 0
• :`Z * ASTM A307 ALL-THREAD BOLT,
LENGTH AS NECESSARY
IN EACH CURB FLANGE
CURB4,,,,,,:re:,:,,..;.,;,,,:::,,,
/S �.%�. HOLE AT CURB BASE
tit::?e,:,.t,:.: WOOD BEAM - SIZED
' `"' ► BY OTHERS TO PROVIDE
70.1SUPPORT UNDER ENTIRE
— �p� CURB LENGTH AND WIDTH.
V
`w V��
V�
V�
\ V�
n
V�
' V�
V�
V�
�V�
THROUGH BOLTED ON BEAM UNDERSIDE
WITH NUT, BOLT AND WASHER TFIYBAR CURB SECTION
AS NECESSARY TO ATTACH
CURB TO BUILDING ROOF
SUPPORT STRUCTURE. WOOD BEAM
SIZED BY OTHERS
r
k
Dl
•
►`
i
TC3 Wood Beam Mounting.dwg
Print Date:11/12/2015
THYBAR CORPORATION
913 S. Kay Avenue
111 Addison, IL 60101
800-666-CURB(2872)
Fax:630-543-5309
www.thybar.com
Member of
VISCIA
Seismic /130 MPH Wind Load Calculations for a
Aaon B Cabinet RN-011 (920AHU07) on a
Thybar Insulated TC-3 Roofcurb
in Tigard OR 97224
CWS Durham 0 and M Building Remodel
Thybar Order#: 184599
August 17, 2018
PROF S l
(5? 19695 9r-
Jr Rik
•REGON
4 4V1,l9'
s'?FEN C.V.\' 8.23.18
RENEWAL DATE: 12.31.19
Digitally signed bya Steven C Bail,SE
Steven C Ball, SE DN JoIin A E=shall Associ aes,In m,
Oa"JChn A Martin&Associates,Inc",
CN="Steven C Ball,SE"
Date:2018.08.23 13:11:18-07'00'
Z w
2; This analysis considers the wind and seismic force Reviewed b
F- calculations and anchorage of the curb to the structure only. y'
QN The supporting structure shall be reviewed and approved by others. Hossain Ghaffari
m The curb design and unit anchorage to the curb is by Thybar. 08-21-2018
No installation shall take place until the anchorage and supporting
JOHN A. MARTIN structure are approved by the appropriate jurisdiction.
& ASSOCIATES, INC.
Structural Engineers
This document contains proprietary information from Thybar Corporation. Its contents may not be used for any other
project or location other than the project or location for which it was created without the prior written permission of
Thybar Corporation.
8/17/2018
Unit: Aaon B Cabinet RN-011 (920AHU07)
Location: Tigard OR 97224
Curb: Insulated TC-3
Governing Code: 2014OSSC / IBC2012
SDC: D
Design Wind Speed: 130 MPH
CWS Durham 0 and M Building Remodel
These calculations begin with the assumption that the Thybar curb is
supported around its full perimeter by building structure. Design of building
structure is not the responsibility of Thybar Corporation.
An 18 inch high Thybar Insulated TC-3 of minimum 14 gage galvanized side
wall construction will meet the 2014OSSC / IBC2012 requirements for installing
an Aaon B Cabinet RN-011 (920AHU07) unit in Tigard OR 97224 when
manufactured with stiffeners installed 25 inches max OC and installed
according to the attached drawings.
The unit must be attached to the Thybar Insulated TC-3 using 12 gage
restraint brackets. Bracket quantity is determined in the calculations and is
summarized as follows:
Minimum 12 gage bracket quantity: 4
The Thybar Insulated TC-3 must be attached to the building structure using
welds or bolts at the curb base flanges. Flange connection minimum bolt
quantity is determined in the calculations and is summarized as follows:
Total connection minimum quantity: 8
As curb manufacturers, Thybar Corporation cannot be expected to provide
appropriate attachment hardware for every possible type of roof structure.
Thybar provides seismic/windload calculations that are based on the material
provided; typically sheet metal curbs. It is the responsibility of others (project
engineer, architect, SEOR, etc) to know enough about the load carrying
capability of the building structure to design a method of attachment to that
structure. Thybar does not design the structure and therefore should not
recommend an attachment method that may create difficulties with existing
field conditions outside of the curb manufacturer's control.
Summary 1
Thybar Corporation 8/17/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
Location Tigard OR 97224
General
Applicable Building Code 2014OSSC/
IBC2012
Seismic Design Category(SDC) D
Unit Manufacturer Aeon
Unit Model B Cabinet RN-011
(920AHU07)
Length(in) 110.63
Equip Width(in) 95.75
Height(in) 50.1
Weight(Ib) 2,007
CG,,(in) 44.80
CG,,,(in) 35.80
Curb Type Insulated TC-3
Curb Length(in) 75.88
Curb Width(in) 54.00
Curb Height(in) 18.00
Minimum Thickness(ga) 14
Stiffener max OC spacing(in) 25
F,(psi) 30,000
E(psi) 30,000,000
Thickness(in) 0.0670
u 0.3
I(in) 18.0
Curb h/t 269
b/t 373
k, 4.0
kn 1.0
F.(psi) 779
Snow Importance,I 1.2
Snow Load,pf(lb) 1,971
Curb Design Load,0.75`max(Wind, 2,376
.7`Seismic)+0.755,(Ib)=
0.4°F,=F,(psi) 12,000
0.6`Fy=F,(psi) 18,000
Wind Load(130mph)Fw(lb)= 1,197
Exposure Category= B
Rooftop height(ft)= 20
Velocity Pressure coefficient Kz= 0.70
Topography factor Kzt= 1.00
Wind Directionality factor Kd= 0.90
Wind Speed V= 130
Importance factor Iw= N/A
qz= 27.26
GCr 1.90
Fr= 646
FE Max= 3,443
FE Min= 646
Sss= 0.715
Sm= 0.442
as= 1.00
I,= 1.50
Seismic
Rv= 6.00
z/h= 1.0
Ss(%ofg)= 96.10
Sr(%of g)= 41.90
Site Coefficient F,= 1.12
Site Coefficient F,= 1.58
Site Soil Classification= D
Seismic Upward Force(Ib),F up= 286.93
ex(in) 10.5125
ey(in) 12.075
Curb Load ax*
Distribution 1.570
Factors ax-
0.430
ay+ 0.626
ay- 0.374
(lb/in) 51.5
Curb Loads C,,(lb/in) 4.25
Shear Wall Factor a, 0.785
R Unit shear,v(lb/in) 34.539
S e Curb Long Unit Overturning,Cu(Ib/n) 15.6
u a Dimension Unit Uplift,T(Ib) 671
p c
p t Curb Overturning,Cc(lb/in) 69.1
o i Curb Corner Uplift,Tc(lb/in) 6.06
r o Shear Wall Factor a, 0.626
t n Unit shear,v(lb/in) 19.604
s Curb Short Unit Overturning,Cu(lb/in) 3.519
Dimension Unit Uplift,T(Ib) 307.013
Curb Overturning,Cc(lb/in) 27.904
Curb Corner Uplift,Tc(lb/in) 5.685
Max Shear(lb/in) 25.9
Shear f,(psi) 387
Curb Verification f,/F, 0.03 <1.0,OK
Max Axial Reaction(lb/in) 51.5
Axial f,(psi) 769
f,/F, 0.99 <1.0,OK
Load Calcs 2
Thybar Corporation 8/17/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
General
Location Tigard OR 97224
Applicable Building Code 2014OSSC/IBC2012
Unit Model B Cabinet RN-011 (920AHU07)
Curb Type Insulated TC-3
Bracket Dimensions
Length(in) 16
Max bending arm(in) 2.2
Max torsion arm(in) 0.001
Minimum Material thickness(ga) 12
Material thickness(in) 0.0970
Fy(psi) 30,000
Area(in2) 1.552
Screws
Screw size/type(#) 10
Quantity of screws 7
Hole size(in) 1/4
Allowable pullout(lb/screw) 1146
Max pullout(lb/bracket) 8,019
Allowable shear(lb/screw) 1,206
Max shear(lb/bracket) 8,445
Torsion on Bracket
Fv=0.4*Fy(psi) 12,000
Max shear(lb) 602,176
Flexure on Bracket
Fb=0.6*Fy(psi) 18,000
Max shear(Ib) 33,862
Shear on Bracket Attachment Holes
Distance-hole edge to bracket edge 0.375
Max shear(Ib) 3,056
Tension on Bracket
FT=0.4*Fy(psi) 12,000
TMaX(Ib) 16,587
Bracket Capacity
Allowable Load (Ib) 3,056
Bracket Verification
Horizontal Design Load(lb) 2,376 2,376
Curb Length/Width(in) 75.88 54.00
Shear Wall Factor 0.79 0.63
Design Shear(Ib) 1,865 1,487
Unit Design Uplift,Tc(lb) 670.63 307.01
Unit Uplift,Ta(Ib) 526 192
R=(V2+T22)112 1,938 1,500
#per side 0.63 0.49
Clip Safety Factor 2
Total Clips Required 4
Unit To Curb 3
Thybar Corporation 8/17/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
General
Location Tigard OR 97224
Applicable Building Code 2014OSSC/ IBC2012
Unit Model B Cabinet RN-011 (920AHU07)
Curb Type Insulated TC-3
Material Properties
Fy(psi) 30,000
Material Allowable Stress, Fa 12,000
(psi)
Base Attachment Dimensions
Hole Size (in) 0.625
Number of Holes per 1
attachment
Min. Material thickness (ga) 14
Min. Material thickness (in) 0.1340
Cut out area (in2) 0.307
Base flange width (in) 2.0
Edge distance (in) 11/16
Base shear area (in2) 0.09
Base Attachment Forces
Length Width
Horizontal Design Load (Ib) 2375.68 2375.68
Length (in) 75.88 54.00
Shear(Ib) 1,865 1,487
Unit Uplift, Tc(Ib) 526 192
R= (V2 +T22)112 1,938 1,500
Length Width
Base Attachment Stresses-fa 5,259 4,070
(psi)
Base Safety Factor 2 2
fa/Fa 0.88 0.68
Base Attachment Minimum 4 4
Quantity
Minimum Base Attachments- 8
Perimeter Distributed
Base Attachment Holes 4
8/17/2011
I
Aaon B Cabinet Unit 1111
thybar
Tigard OR
IIICO1�I° '' N SEISMIC/WINDLOAD RESTRAINT BRACKET
T,''-aa rakes:/right the hot Dre
every rime INSTALLATION DETAILS FOR INSULATED CURBS
INSTALLATION INSTRUCTIONS: — _____
PLACE RESTRAINTS IN APPROXIMATE LOCATIONS AS SHOWN. -
EQUALLY DISTRIBUTE RESTRAINT AS MUCH AS POSSIBLE WHILE AVOIDING INTERFERENCES WITH
LIFTING LUGS,CONDENSATE DRAIN LINES,UNIT BASE SCREWS,ETC.
GASKET TOP PERIMETER OF CURB AND RESTRAINTS BEFORE SETTING UNIT. I:AEr:LTlfd,.'
SEE MATRIX BELOW FOR QUANTITIES REQUIRED PER UNIT.
PD 1.--
1
5 I� 'i
/
/
/
f
NOTE: - 1
DRAWINGS ARE CONCEPTUAL,NOT TO SCALE
INNER RESTRAINTS MUST BE FIELD INSTALLED TO ROOF CURB BEFORE SETTING UNIT. RESTRAINT DETAIL
THYCURBMODEL RESTRAINT BRACKET QTY. `/`-TEaIAL �{ / A -.AL`,<A('aZED „'•TEFL ,:'rJI:`RUC-TI��Pd.
SOD SEISMIC RESTRAINTS PER UNIT Hr- /WARE f 7j #I i; I" 'E I
�l�R W`, F'Lk �'E1,fRAI°1i
Aaon B Cabinet RN-011(920AHU07) ACSWRANB0010RC-01 4 (,7) # ,/ 2 1 E f' HER V,I2 PER RE'_11,41,,IT
SEISMIC&WINDLOAD BRACKETS ARE DESIGNED&CALCULATED FOR USE IN SEISMIC/WINDLOAD APPLICATIONS WHEN PROVIDED
AS PART OF A SEISMIC/WINDLOAD RATED CURB.
ATTACHMENT OF CALCULATED BRACKETS TO ANY OTHER CURB DOES NOT CONSTITUTE A SEISMIC/WINDLOAD RATED ASSEMBLY.
REVISION DATE 8/17/2018
testraint Bracket Detail
in thybar Structural Steel Mounting
Thybar makes;t right the first t r,e,
evey t;r,e
SEISMIC/WIND LOAD INSULATED CURB
INSTALLATION OPTIONS
The curbs should be anchored to structural steel as follows:
* The width of the supporting structural steel shall be at least as wide as the base plate
of the curb.
* Bolts should be ASTM A307 grade min strength, with nuts and washers.
* Bolts should be placed in every hole provided in the base plate of the curb; pass through
the base plate of the curb and the structural steel; and tightened according
to manufacturers torque specifications. (Figure 1-1)
* Alternatively, the curb may be welded to the structural steel. (Figure 1 -2)
i::4_':W) i" MIN 0 BOLT WITH WASHER
�•���'iWi WOOD NAILER
�;r�i:: Q (LENGTH TO BE DETERMINED IN FIELD)
iiiAAM
CURB g i:: ::`�•:::Q
41
iiiii��!i��00 � VISCMA APPROVED
s%'���%�*, nSEISMIC/WINDLOAD
�ZA Z RATED OF
VARIOUS HEIGHTS
OM
STRUCTURAL 0
STEEL
NUT WITH WASHER ;
Figure 1-1 y
lio
CENTERED ON 1r k 1r '
EACH BOLT HOLE
CURB ''`' '
;b`!i bt:
IktitiO
STRUCTURAL
STEEL NI
Figure 1-2 .
Consult Local Building Codes & FEMA Manual. 412/December 2002
PRINTED:11/12/15
. thybar Concrete Slab Mounting
IIIThytmi makes ii right the&,-t time.
SEISMIC/WIND LOAD INSULATED CURB
INSTALLATION OPTIONS
The equipment support should be anchored to concrete as follows:
* Anchor system must comply with applicable building code (Local building code,
International Building Code, Uniform Building Code, etc.).
* Anchor to be Hilti Kwik Bolt TZ, Simpson Strong—Tie or equivalent.
* Anchors are to be placed in every hole provided in the base plate of the curb.
* Anchors are to pass through the base plate & be embedded into the concrete.
* Follow anchor manufacturers instructions for drilling holes, installation anchor and
tightening nut.
,•:f\s4)
�.; ,AI
ANCHOR WITH NUT & WASHER
,��i/��i��� (i" DIAMETER MINIMUM,
`i'��iii���/; EMBEDMENT DEPTH AND
•Z:::,'!, EDGE DISTANCE AS REQUIRED
i��00..00 BY FIELD CONDITIONS AND
;.!ekiV:,i HARDWARE SELECTION.)
v � � Ing%kii� �
'"--
• ° CONCRETE
° ° d THYBAR CURB SECTION
•
•
•
• d° • ° •
Q• Q d
4/.//
° •
•
Figure 1-1 k
a.
a
•
0,\ d V
® 41d
d da :a
• o G d Q
•
d C • .
. • Q Q
•
o '
a •
•
Consult Local Building Codes & FEMA Manual. 412/December 2002 TC3 Concrete Installation.dwg
PRINTPl•11/19/1g
lim t hyba r Wood Beam Mounting
C OI 2r rybar aka,a right e fin
1111 Amthe a,
<,,.t,r:.r INSULATED ROOF CURB ON
WOODEN STRUCTURAL BEAM
INSTALLATION OPTIONS
The curbs can be installed on a wood—beam type roof providing there is adequate
support around entire curb perimeter. The beam load carrying capability is to be
determined by others and the following provisions are acceptable:
* Curb base is the be through—bolted to wood joists of roof support.
* Through bolts are to be manufactured according to ASTM A307.
* Bolts are to be 3" diameter minimum and length as required to positively attach
to building structure.
* Bolts are to be installed in every hole in the roof curb base flange and
tightened according to bolt manufacturer's recommendations.
z:<v-
\S;\'S;j��y; INSTALL (1) }"0
;<\Z>'�: , ASTM A307 ALL-THREAD BOLT,
'S;''�` '�?, LENGTH AS NECESSARY
``''"''^" IN EACH CURB FLANGE
CURB yt �1
5,.%.% HOLE AT CURB BASE
''` ",O1
a,
° WOOD BEAM - SIZED
1,,,,.....,z. __ 1 BY OTHERS TO PROVIDE
j/�� SUPPORT UNDER ENTIRE
- / ---.--,-.',-:' CURB LENGTH AND WIDTH.
t'�
THROUGH BOLTED ON BEAM UNDERSIDE
WITH NUT, BOLT AND WASHER THYBAR CURB SECTION
AS NECESSARY TO ATTACH
CURB TO BUILDING ROOF
SUPPORT STRUCTURE. WOOD BEAM
SIZED BY OTHERS
S
TC3 Wood Beam Mounting.dwg
Print Date:11/12/2015
THYBAR CORPORATION
913 S. Kay Avenue
Addison, IL 60101
1111
800-666-CURB(2872)
Fax:630-543-5309
www.thybar.com
Member of
VISCIA
Seismic /130 MPH Wind Load Calculations for a
Aaon RQ Cabinet RQ-003 (920AHU08) on a
Thybar Insulated TC-3 Roofcurb
in Tigard OR 97224
CWS Durham 0 and M Building Remodel
Thybar Order#: 184599
August 17, 2018
jCT�R�
¢EO PROP
ss/0
cr 19695 9r
i RECON
kar 1,1
Sr6VEN C.OP1\, 8.23.18
!RENEWAL DATE: 12.31.19
Digitally signed by Steven C Ball,SE
DN:
E=shall@johnmartin.com,O_"John A
Steven C Ball, SE Martel&Associates,Inc",
CN="Steven C Ball,SE"
Date:2018.08.23 13:11:32-0700'
Zw
This analysis considers the wind and seismic force Reviewed h
n) calculations and anchorage of the curb to the structure only. y:
oThe supporting structure shall be reviewed and approved by others. Hossain Ghaffari
The curb design and unit anchorage to the curb is by Thybar. 08-21-2018
2 03
No installation shall take place until the anchorage and supporting
JOHN A. MARTIN structure are approved by the appropriate jurisdiction.
& ASSOCIATES, INC.
Structural Engineers
This document contains proprietary information from Thybar Corporation. Its contents may not be used for any other
project or location other than the project or location for which it was created without the prior written permission of
Thybar Corporation.
8/17/2018
Unit: Aaon RQ Cabinet RQ-003 (920AHU08)
Location: Tigard OR 97224
Curb: Insulated TC-3
Governing Code: 2014OSSC / IBC2012
SDC: D
Design Wind Speed: 130 MPH
CWS Durham 0 and M Building Remodel
These calculations begin with the assumption that the Thybar curb is
supported around its full perimeter by building structure. Design of building
structure is not the responsibility of Thybar Corporation.
A 19 inch high Thybar Insulated TC-3 of minimum 14 gage galvanized side wall
construction will meet the 2014OSSC / IBC2012 requirements for installing an
Aaon RQ Cabinet RQ-003 (920AHU08) unit in Tigard OR 97224 when
manufactured with stiffeners installed 46 inches max OC and installed
according to the attached drawings.
The unit must be attached to the Thybar Insulated TC-3 using 12 gage
restraint brackets. Bracket quantity is determined in the calculations and is
summarized as follows:
Minimum 12 gage bracket quantity: 4
The Thybar Insulated TC-3 must be attached to the building structure using
welds or bolts at the curb base flanges. Flange connection minimum bolt
quantity is determined in the calculations and is summarized as follows:
Total connection minimum quantity: 8
As curb manufacturers, Thybar Corporation cannot be expected to provide
appropriate attachment hardware for every possible type of roof structure.
Thybar provides seismic/windload calculations that are based on the material
provided; typically sheet metal curbs. It is the responsibility of others (project
engineer, architect, SEOR, etc) to know enough about the load carrying
capability of the building structure to design a method of attachment to that
structure. Thybar does not design the structure and therefore should not
recommend an attachment method that may create difficulties with existing
field conditions outside of the curb manufacturer's control.
Summary 1
Thybar Corporation 8/17/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
Location Tigard OR 97224
General
Applicable Building Code 2014OSSC/
IBC2012
Seismic Design Category(SDC) D
Unit Manufacturer Aaon
Unit Model RQ Cabinet RQ-003
(920AHU08)
Length(in) 116.00
Equip Width(in) 61.88
Height(in) 50.5
Weight(lb) 1,192
CG,,(in) 57.90
CGc(in) 20.20
Curb Type Insulated TC-3
Curb Length(in) 111.50
Curb Width(in) 39.25
Curb Height(in) 19.00
Minimum Thickness(ga) 14
Stiffener max OC spacing(in) 46
Fs(psi) 30,000
E(psi) 30,000,000
Thickness(in) 0.0670
u 0.3
I(in) 19.0
Curb h/t 284
b/t 687
k, 4.0
k, 1.0
F.(psi) 230
Snow Importance,I 1.2
Snow Load,pf(lb) 1,336
Curb Design Load,0.75`max(Wind,
.7`Seismic)+0.755,(Ib)= 1,950
0.4=F,=F,(psi) 12,000
0.6`Fy=F,(psi) 18,000
Wind Load(130mph)Fw(lb)= 1,264
Exposure Category= B
Rooftop height(ft)= 20
Velocity Pressure coefficient Kz= 0.70
Topography factor Kzt= 1.00
Wind Directionality factor Kd= 0.90
Wind Speed V= 130
Importance factor Iw= N/A
qz= 27.26
GCr 1.90
FE= 383
FE nm.= 2,045
FEµa= 383
Sos= 0.715
Sof= 0.442
av= 1.00
lv= 1.50
Seismic Rv= 6.00
z/h= 1.0
Ss(%of g)= 96.10
S,(%of g)= 41.90
Site Coefficient F.= 1.12
Site Coefficient F,= 1.58
Site Soil Classification= D
Seismic Upward Force(Ib),F up= 170.42
ex(in) 0.1
ey(in) 10.7375
Curb Load ax*
Distribution 1.005
Factors ax- 0.995
ay* 0.674
ay- 0.326
• (lb/in) 15.3
Curb Loads • (lb/in) 3.47
Shear Wall Factor a, 0.503
R Unit shear,v(lb/in) 24.966
S e Curb Lone Unit Overtuming,Cu(Ib/in) 10.9
u a Dimension Unit Uplift,T(Ib) 965
p c
p t Curb Overturning,Cc(lb/in) 72.5
o i Curb Comer Uplift,Tc(lb/in) 8.S2
✓ o Shear Wall Factor as 0.674
t n Unit shear,v(lb/in) 11.778
s Curb Short Unit Overturning,Cu(Ib/in) 4.620
Dimension Unit Uplift,T(Ib) 240.127
Curb Overtuming,Cc(lb/in) 12.042
Curb Corner Uplift,Tc(lb/in) 6.118
Max Shear(lb/in) 18.7
Shear f,(psi) 279
Curb Verification f,IF, 0.02 <1.0,OK
Max Axial Reaction(lb/in) 15.3
Axial f,(psi) 229
f,/F, 1.00 <1.0,OK
Load Calcs 2
Thybar Corporation 8/17/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
General
Location Tigard OR 97224
Applicable Building Code 2014OSSC/IBC2012
Unit Model RQ Cabinet RQ-003(920AHU08)
Curb Type Insulated TC-3
Bracket Dimensions
Length(in) 16
Max bending arm(in) 2.2
Max torsion arm(in) 0.001
Minimum Material thickness(ga) 12
Material thickness(in) 0.0970
Fy(psi) 30,000
Area(in2) 1.552
Screws
Screw size/type(#) 10
Quantity of screws 7
Hole size(in) 1/4
Allowable pullout(lb/screw) 1146
Max pullout(lb/bracket) 8,019
Allowable shear(lb/screw) 1,206
Max shear(lb/bracket) 8,445
Torsion on Bracket
Fv=0.4*Fy(psi) 12,000
Max shear(Ib) 602,176
Flexure on Bracket
Fb=0.6*Fy(psi) 18,000
Max shear(Ib) 33,862
Shear on Bracket Attachment Holes
Distance-hole edge to bracket edge 0.375
Max shear(lb) 3,056
Tension on Bracket
FT=0.4*Fy(psi) 12,000
TMax(Ib) 16,587
Bracket Capacity
(Allowable Load(Ib) 3,0561
Bracket Verification
Horizontal Design Load(Ib) 1,950 1,950
Curb Length/Width(in) 111.50 39.25
Shear Wall Factor 0.50 0.67
Design Shear(Ib) 980 1,313
Unit Design Uplift,Tc(Ib) 964.88 240.13
Unit Uplift,Tc(Ib) 485 162
R=(V2+T22)112 1,093 1,323
#per side 0.36 0.43
Clip Safety Factor 2
Total Clips Required 4
Unit To Curb 3
Thybar Corporation 8/17/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
General
Location Tigard OR 97224
Applicable Building Code 2014OSSC/ IBC2012
Unit Model RQ Cabinet RQ-003 (920AHU08)
Curb Type Insulated TC-3
Material Properties
Fy(psi) 30,000
Material Allowable Stress, Fa 12,000
(psi)
Base Attachment Dimensions
Hole Size (in) 0.625
Number of Holes per 1
attachment
Min. Material thickness(ga) 14
Min. Material thickness(in) 0.1340
Cut out area (in2) 0.307
Base flange width (in) 2.0
Edge distance (in) 11/16
Base shear area (in2) 0.09
Base Attachment Forces
Length Width
Horizontal Design Load (Ib) 1949.74 1949.74
Length (in) 111.50 39.25
Shear(Ib) 980 1,313
Unit Uplift, Tc(Ib) 485 162
R= (V2+122)1'2 1,093 1,323
Length Width
Base Attachment Stresses -fa 2,967 3,591
(psi)
Base Safety Factor 2 2
fa/Fa 0.49 0.60
Base Attachment Minimum 4 4
Quantity
Minimum Base Attachments- 8
Perimeter Distributed
Base Attachment Holes 4
8/17/2011
Mon RQ Cabinet Unit 011
t hybar Tigard OR
IIICO"° A ON SEISMIC/WINDLOAD RESTRAINT BRACKET
Thyva,,rakes it right the ft,sr tire,
wary irr.':e INSTALLATION DETAILS FOR INSULATED CURBS
INSTALLATION INSTRUCTIONS: —— — ._...
PLACE RESTRAINTS IN APPROXIMATE LOCATIONS AS SHOWN.
EQUALLY DISTRIBUTE RESTRAINT AS MUCH AS POSSIBLE WHILE AVOIDING INTERFERENCES WITH '
LIFTING LUGS,CONDENSATE DRAIN LINES,UNIT BASE SCREWS,ETC.
GASKET TOP PERIMETER OF CURB AND RESTRAINTS BEFORE SETTING UNIT. GAS!,CRT": y---
SEE MATRIX BELOW FOR QUANTITIES REQUIRED PER UNIT.
/
L / \`
f
I
�/
.
NOTE: 7:
DRAWINGS ARE CONCEPTUAL,NOT TO SCALE
INNER RESTRAINTS MUST BE FIELD INSTALLED TO ROOF CURB BEFORE SETTING UNIT. RESTRAINT DETAIL
THYCURB MODEL RESTRAINT BRACKET QTY, MATERIAL: 12 LA. GALdAN7 D STEEL 'COI,13TR,JCTION
Aaon SEISMIC RESTRAINTS PER UNIT HARI2WARE: (/) #l iFr 1., T I• EC FEW':: PER RE_:1 PAIN i
Aaon RQ Cabinet RQ-003(920AHU08) ACSWRANB0009RC-01 4 (7) # ,24. TEP. SLREWE REF RESTFAINT
SEISMIC&WINDLOAD BRACKETS ARE DESIGNED&CALCULATED FOR USE IN SEISMIC/WINDLOAD APPLICATIONS WHEN PROVIDED
AS PART OF A SEISMIC/WINDLOAD RATED CURB.
ATTACHMENT OF CALCULATED BRACKETS TO ANY OTHER CURB DOES NOT CONSTITUTE A SEISMIC/WINDLOAD RATED ASSEMBLY.
REVISION DATE: 8/17/2018
testraint Bracket Detail
thybar Structural Steel Mounting
t:o (JA _'1
III Thyhai makes it right the first t r,
every tire
SEISMIC/WIND LOAD INSULATED CURB
INSTALLATION OPTIONS
The curbs should be anchored to structural steel as follows:
* The width of the supporting structural steel shall be at least as wide as the base plate
of the curb.
* Bolts should be ASTM A307 grade min strength, with nuts and washers.
* Bolts should be placed in every hole provided in the base plate of the curb; pass through
the base plate of the curb and the structural steel; and tightened according
to manufacturers torque specifications. (Figure 1 -1)
* Alternatively, the curb may be welded to the structural steel. (Figure 1 -2)
�..:( ::- i" MIN 0 BOLT WITH WASHER
�� i)i:/\ (LENGTH TO BE DETERMINED IN FIELD) WOOD NAILER
����!i Y�i O:
CURB441 gii:V,*ii:,
ilis!i;���G�� N� VISCMA APPROVED
:;:',S�i;, SEISMIC/WINDLOAD
z /---'7%, RATED OF
onoVARIOUS HEIGHTS
STRUCTURAL j
STEEL
NUT WITH WASHER I
Figure 1-1
0 a
GD
CENTERED ON t " 1i" '� a
EACH BOLT HOLE S
AAP
CURB g,1:4:'• ",
kIA.moi
STRUCTURAL /
STEEL NI
Figure 1-2 .
Consult Local Building Codes & FEMA Manual. 412/December 2002
PRINTED:11/12/15
Nth barN Concrete Slab Mounting
7hyba,,ykeK,i right the 6 st z,,'E.
SEISMIC/WIND LOAD INSULATED CURB
INSTALLATION OPTIONS
The equipment support should be anchored to concrete as follows:
* Anchor system must comply with applicable building code (Local building code,
International Building Code, Uniform Building Code, etc.).
* Anchor to be Hilti Kwik Bolt TZ, Simpson Strong—Tie or equivalent.
* Anchors are to be placed in every hole provided in the base plate of the curb.
* Anchors are to pass through the base plate & be embedded into the concrete.
* Follow anchor manufacturers instructions for drilling holes, installation anchor and
tightening nut.
��`�si�.`p�` ANCHOR WITH NUT & WASHER
AI�� ��•�, ( " DIAMETER MINIMUM,
;i���.i•�.d EMBEDMENT DEPTH AND
i �', EDGE DISTANCE AS REQUIRED
���������� BY FIELD CONDITIONS AND
!,:w.:..-; HARDWARE SELECTION.)
Z,``�`�1 Normal Weight
�ttH� Concrete
° CONCRETE
° a • a
° .
° d THYBAR CURB SECTION
A
da • ; •.
Figure 1-1
C -t . - .4
° • d :a •
° •d
° a
a e • •
a Q
a
v ° • a• a d
d .
Consult Local Building Codes & FEMA Manual. 412/December 2002 TC3 Concrete Installation.dwg
PRIMTP11•11/19/1S
ill■ t hyba r Wood Beam Mounting
iii T,,YU"`:'�k�s,c.,9nc rer""``:. INSULATED ROOF CURB ON
WOODEN STRUCTURAL BEAM
INSTALLATION OPTIONS
The curbs can be installed on a wood—beam type roof providing there is adequate
support around entire curb perimeter. The beam load carrying capability is to be
determined by others and the following provisions are acceptable:
* Curb base is the be through—bolted to wood joists of roof support.
* Through bolts are to be manufactured according to ASTM A307.
* Bolts are to be 4" diameter minimum and length as required to positively attach
to building structure.
* Bolts are to be installed in every hole in the roof curb base flange and
tightened according to bolt manufacturer's recommendations.
.;:-
:'S�'�:�°�°i INSTALL (1) 4"0
! °.� ASTM A307 ALL-THREAD BOLT,
\s��.:\�. LENGTH AS NECESSARY
. :#.;%. IN EACH CURB FLANGE
CURB .*.*:!% HOLE AT CURB BASE
.... WOOD BEAM - SIZED
s'''�'''�`'' BY OTHERS TO PROVIDE
meal,„:„,,,,,,::/„:.
-V pPIP/ SUPPORT UNDER ENTIRE
CURB LENGTH AND WIDTH.
an
3
:: 0
'145 0
THROUGH BOLTED ON BEAM UNDERSIDE
WITH NUT, BOLT AND WASHER THYBAR CURB SECTION
AS NECESSARY TO ATTACH
CURB TO BUILDING ROOF
SUPPORT STRUCTURE. WOOD BEAM
SIZED BY OTHERS
0I
1
�
s
TC3 Wood Beam Mounting.dwg
Print Date:11/12/2015
THYBAR CORPORATION
913 S. Kay Avenue
Addison, IL 60101
800-666-CURB(2872)
Fax:630-543-5309
www.thybar.com
Member of
VISCIA
Seismic /130 MPH Wind Load Calculations for a
Aaon C Cabinet RN-020 (920AHU09) on a
Thybar Insulated TC-3 Roofcurb
in Tigard OR 97224
CWS Durham 0 and M Building Remodel
Thybar Order#: 184599
August 17, 2018
.g,1iCTUk
PRO Fssl
ct 19695 9r
41 Rik
•REGON
'star 1.1
SikEN C.aP' 8.23.18
!RENEWAL DATE: 12.31.19
Digltaky signed by Steven C Ball,SE
Steven C Ball, SE DN:ohn A E=shall Associ arts,Inc",O�"John A Martin&Associates,Inc",
CN='Steven C Ball,SE"
Date:2018.08.23 13:11:44-0700'
Z W
2; This analysis considers the wind and seismic force Reviewed b
•tD calculations and anchorage of the curb to the structure only. y"
Q Hossain Ghaffari
o The supporting structure shall be reviewed and approved by others.
o
The curb design and unit anchorage to the curb is by Thybar. 08-21-2018
No installation shall take place until the anchorage and supporting
JOHN A. MARTIN structure are approved by the appropriate jurisdiction.
& ASSOCIATES, INC.
Structural Engineers
This document contains proprietary information from Thybar Corporation. Its contents may not be used for any other
project or location other than the project or location for which it was created without the prior written permission of
Thybar Corporation.
8/17/2018
Unit: Aaon C Cabinet RN-020 (920AHU09)
Location: Tigard OR 97224
Curb: Insulated TC-3
Governing Code: 2014OSSC / IBC2012
SDC: D
Design Wind Speed: 130 MPH
CWS Durham 0 and M Building Remodel
These calculations begin with the assumption that the Thybar curb is
supported around its full perimeter by building structure. Design of building
structure is not the responsibility of Thybar Corporation.
A 19 inch high Thybar Insulated TC-3 of minimum 14 gage galvanized side wall
construction will meet the 2014OSSC / IBC2012 requirements for installing an
Aaon C Cabinet RN-020 (920AHU09) unit in Tigard OR 97224 when
manufactured with stiffeners installed 22 inches max OC and installed
according to the attached drawings.
The unit must be attached to the Thybar Insulated TC-3 using 12 gage
restraint brackets. Bracket quantity is determined in the calculations and is
summarized as follows:
Minimum 12 gage bracket quantity: 4
The Thybar Insulated TC-3 must be attached to the building structure using
welds or bolts at the curb base flanges. Flange connection minimum bolt
quantity is determined in the calculations and is summarized as follows:
Total connection minimum quantity: 10
As curb manufacturers, Thybar Corporation cannot be expected to provide
appropriate attachment hardware for every possible type of roof structure.
Thybar provides seismic/windload calculations that are based on the material
provided; typically sheet metal curbs. It is the responsibility of others (project
engineer, architect, SEOR, etc) to know enough about the load carrying
capability of the building structure to design a method of attachment to that
structure. Thybar does not design the structure and therefore should not
recommend an attachment method that may create difficulties with existing
field conditions outside of the curb manufacturer's control.
Summary 1
Thybar Corporation 8/17/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
Location Tigard OR 97224
General
Applicable Building Code 2014085C/
IBC2012
Seismic Design Category(SDC) D
Unit Manufacturer Aaon
Unit Model C Cabinet RN-020
(920AHU09)
Length(in) 138.00
Equip Width(in) 100.88
Height(in) 59.3
Weight(Ib) 3,093
CG„(in) 52.90
CG,,(in) 34.60
Curb Type Insulated TC-3
Curb Length fin) 96.88
Curb Width(in) 54.00
Curb Height(in) 19.00
Minimum Thickness(ga) 14
Stiffener max OC spacing(in) 22
Fy(psi) 30,000
E(psi) 30,000,000
Thickness(in) 0.0670
u 0.3
Curb I(in) 10.0
h/t 284
b/t 328
kp 4.0
k 1.0
Fe(psi) 1,006
Snow Importance,I 1.2
Snow Load,pf(lb) 2,590
Curb Design Load,0.75`max(Wind, 3266
.7`Seismic)+0.755,(lb)_
0.4.F,=F„(psi) 12,000
0.6`Fy=F,(psi) 18,000
Wind Load(130mph)Fw(Ib)= 1,764
Exposure Category= B
Rooftop height(ft)= 20
Velocity Pressure coefficient Kz= 0.70
Topography factor Kzt= 1.00
Wind Directionality factor Kd= 0.90
Wind Speed V= 130
Importance factor Iw= N/A
gz= 27.26
GCr 1.90
FE= 995
FE Mex= 5,308
FE MI„= 995
SDs= 0.715
SD,= 0.442
ap= 1.00
Ip= 1.50
Seismic Ftp 6.00
z/h= 1.0
Ss(%ofg)= 96.10
S,(%of g)= 41.90
Site Coefficient F.= 1.12
Site Coefficient F,.= 1.58
Site Soil Classification= D
Seismic Upward Force(Ib),F up= 442.33
ex(in) 16.1
ey(in) 15.8375
Curb Load ax+ 1.700
Distribution
Factors ax- 0.300
ay+ 0.657
ay- 0.343
C,,„„(lb/in) 65.5
Curb Loads
C,,,, (Ib/in) 3.29
Shear Wall Factor a, 0.850
R Unit shear,v(Ib/in) 51.410
S e Curb Long Unit Overturning,Cu(Ib/in) 22.1
U a Dimension Unit Uplift,T(Ib) 903
p c
p t Curb Overturning,Cc(Ibfin) 108.5
o I Curb Corner Uplift,Tc(lb/in) 6.55
✓ o Shear Wall Factor az 0.657
t n Unit shear,v(lb/in) 22.150
s Curb Short Unit Overturning,Cu(Ib/in) 4.567
Dimension Unit Uplift,T(Ib) 171.373
Curb Overturning,Cc(lb/in) 26.066
Curb Corner Uplift,Tc(lb/in) 3.174
Max Shear(lb/in) 38.6
Shear f„(psi) 575
Curb Verification 0.05 <1.0,OK
Max Axial Reaction(lb/in) 65.5
Axial f,(psi) 978
fa/Fa 0.97 <1.0,OK
Load Calcs
2
Thybar Corporation 8/17/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
General
Location Tigard OR 97224
Applicable Building Code 2014OSSC/IBC2012
Unit Model C Cabinet RN-020(920AHU09)
Curb Type Insulated TC-3
Bracket Dimensions
Length(in) 16
Max bending arm(in) 2.2
Max torsion arm(in) 0.001
Minimum Material thickness(ga) 12
Material thickness(in) 0.0970
Fy(psi) 30,000
Area(in2) 1.552
Screws
Screw size/type(#) 10
Quantity of screws 7
Hole size(in) 1/4
Allowable pullout(lb/screw) 1146
Max pullout(lb/bracket) 8,019
Allowable shear(lb/screw) 1,206
Max shear(lb/bracket) 8,445
Torsion on Bracket
Fv=0.4*Fy(psi) 12,000
Max shear(Ib) 602,176
Flexure on Bracket
Fb=0.6*Fy(psi) 18,000
Max shear(lb) 33,862
Shear on Bracket Attachment Holes
Distance-hole edge to bracket edge 0.375
Max shear(Ib) 3,056
Tension on Bracket
FT=0.4*Fy(psi) 12,000
TMax(Ib) 16,587
Bracket Capacity
'Allowable Load(Ib) 3,0561
Bracket Verification
Horizontal Design Load(Ib) 3,266 3,266
Curb Length/Width(in) 96.88 54.00
Shear Wall Factor 0.85 0.66
Design Shear(Ib) 2,776 2,146
Unit Design Uplift,Tc(Ib) 903.41 171.37
Unit Uplift,Tc(Ib) 768 113
R=(V2+T22)112 2,880 2,149
#per side 0.94 0.70
Clip Safety Factor 2
Total Clips Required 4
Unit To Curb 3
Thybar Corporation 8/17/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
General
Location Tigard OR 97224
Applicable Building Code 20140SSC/ IBC2012
Unit Model C Cabinet RN-020 (920AHU09)
Curb Type Insulated TC-3
Material Properties
Fy(psi) 30,000
Material Allowable Stress, Fa 12,000
(psi)
Base Attachment Dimensions
Hole Size (in) 0.625
Number of Holes per
attachment 1
Min. Material thickness (ga) 14
Min. Material thickness (in) 0.1340
Cut out area (in2) 0.307
Base flange width (in) 2.0
Edge distance (in) 11/16
Base shear area (in2) 0.09
Base Attachment Forces
Length Width
Horizontal Design Load (Ib) 3266.05 3266.05
Length (in) 96.88 54.00
Shear(lb) 2,776 2,146
Unit Uplift, Tc(Ib) 768 113
R= (V2+T22)1/2 2,880 2,149
Length Width
Base Attachment Stresses-fa 5,211 5,831
(psi)
Base Safety Factor 2 2
fa/Fa 0.87 0.97
Base Attachment Minimum 6 4
Quantity
Minimum Base Attachments- 10
Perimeter Distributed
Base Attachment Holes 4
8/17/2011
Aaon C Cabinet Unit
t hyba r Tigard OR
■ COI
tOA ON SEISMIC/WINDLOAD RESTRAINT BRACKET
Th ba, ekes rt right the hi st
�-e:Fy fiq'+� INSTALLATION DETAILS FOR INSULATED CURBS
INSTALLATION INSTRUCTIONS: . —_
PLACE RESTRAINTS IN APPROXIMATE LOCATIONS AS SHOWN.
EQUALLY DISTRIBUTE RESTRAINT AS MUCH AS POSSIBLE WHILE AVOIDING INTERFERENCES WITH
LIFTING LUGS,CONDENSATE DRAIN LINES,UNIT BASE SCREWS,ETC.
GASKET TOP PERIMETER OF CURB AND RESTRAINTS BEFORE SETTING UNIT. a ;E tac y
SEE MATRIX BELOW FOR QUANTITIES REQUIRED PER UNIT.
e 1J t
r r.
NOTE:
DRAWINGS ARE CONCEPTUAL,NOT TO SCALE
INNER RESTRAINTS MUST BE FIELD INSTALLED TO ROOF CURB BEFORE SETTING UNIT. RESTRAINT DETAIL
THYCURB MODEL RESTRAINT BRACKET QTY. MATERIAL CA_ GALVANIZED STEEL C:ONTRJCTION.
Aaon SEISMIC RESTRAINTS PER UNIT
HARDWARE felt},.}„ TEl FEW.`: I`Ef' '?ESTRNI'J1
AaonC Cabinet RN-020(920AHU09) ACSWRANB001IRC-01 4 I:7) I z2 ' T I SC"R;W'w REF RE`'•TFAI'IT,
SEISMIC&WINDLOAD BRACKETS ARE DESIGNED&CALCULATED FOR USE IN SEISMIC/WINDLOAD APPLICATIONS WHEN PROVIDED
AS PART OF A SEISMIC/WINDLOAD RATED CURB.
ATTACHMENT OF CALCULATED BRACKETS TO ANY OTHER CURB DOES NOT CONSTITUTE A SEISMIC/WINDLOAD RATED ASSEMBLY.
REVISION DATE: 8/17/2018
testraint Bracket Detail
■ thybar Structural Steel Mounting
■
co.„!4A, C l
Thybar makes rt right the first time,
eva..:y,tir+e
SEISMIC/WIND LOAD INSULATED CURB
INSTALLATION OPTIONS
The curbs should be anchored to structural steel as follows:
* The width of the supporting structural steel shall be at least as wide as the base plate
of the curb.
* Bolts should be ASTM A307 grade min strength, with nuts and washers.
* Bolts should be placed in every hole provided in the base plate of the curb; pass through
the base plate of the curb and the structural steel; and tightened according
to manufacturers torque specifications. (Figure 1-1)
* Alternatively, the curb may be welded to the structural steel. (Figure 1-2)
.::k'si�'��i` i" MIN 0 BOLT WITH WASHER
Vi:**', (LENGTH TO BE DETERMINED IN FIELD) WOOD NAILER
CURB 41 g �i•:•�:,
��Jl���i���; VISCMA APPROVED
i::f���i::��i', -11,,. SEISMIC/WINDLOAD
/�/�/�����/ ZARWZA RATED OF
MO
VARIOUS HEIGHTS
01.
STRUCTURAL
STEEL '`
NUT WITH WASHER
Figure 1-1 y
0 a
CENTERED ON t " L 1i" f; a
EACH BOLT HOLE
Keg
All CiliViil
CURB '+i'•�'i,
ijJ�!i��Yi��:
r..4)• (1
STRUCTURAL
STEEL NI
Figure 1-2 .
Consult Local Building Codes & FEMA Manual. 412/December 2002
PRINTED:11/12/15
■ t h ba r Concrete Slab Mounting
y c,,,,,„,,.,A
1111 Thebe'makes it right the first.7.
SEISMIC/WIND LOAD INSULATED CURB
INSTALLATION OPTIONS
The equipment support should be anchored to concrete as follows:
* Anchor system must comply with applicable building code (Local building code,
International Building Code, Uniform Building Code, etc.).
* Anchor to be Hilti Kwik Bolt TZ, Simpson Strong—Tie or equivalent.
* Anchors are to be placed in every hole provided in the base plate of the curb.
* Anchors are to pass through the base plate Sc be embedded into the concrete.
* Follow anchor manufacturers instructions for drilling holes, installation anchor and
tightening nut.
':i(;'.�i` ANCHOR WITH NUT & WASHER
AI�� '���i'�, ( ” DIAMETER MINIMUM,
`i;�i.��: EMBEDMENT DEPTH AND
''Z° , EDGE DISTANCE AS REQUIRED
��iO*�iO BY FIELD CONDITIONS AND
�•:W•� ���•.`�i )
�•.i HARDWARE SELECTION.
•
•
° CONCRETE
• • ° ° THYBAR CURB SECTION
. a d
•
4.1/6)
Figure 1-1
.• a
' • a
0 ® • hv
a
Ias .
a a
• a
• . tea a . a. •$•. a .• . . . .. . .
Q • a
• .
a a a
as •
a - a' • a • .
. a
• • ,
Consult Local Building Codes & FEMA Manual. 412/December 2002 TC3 Concrete Installation.dwg
PRINTI fl•11/19/1g
lim t hy bar Wood Beam Mounting
co.,CN
■ Thybarmakes itright the tirsrtme, INSULATED ROOF CURB ON
„t,,,.
WOODEN STRUCTURAL BEAM
INSTALLATION OPTIONS
The curbs can be installed on a wood—beam type roof providing there is adequate
support around entire curb perimeter. The beam load carrying capability is to be
determined by others and the following provisions are acceptable:
* Curb base is the be through—bolted to wood joists of roof support.
* Through bolts are to be manufactured according to ASTM A307.
* Bolts are to be " diameter minimum and length as required to positively attach
to building structure.
* Bolts are to be installed in every hole in the roof curb base flange and
tightened according to bolt manufacturer's recommendations.
:s��:� INSTALL (1) "0
";/....„,/•\./.: ASTM A307 ALL—THREAD BOLT,
'S''�`::'�`> LENGTH AS NECESSARY
C`*::(.i% IN EACH CURB FLANGE
CURB �: ` '��'� HOLE AT CURB BASE
L5::\��`\�� �V�= WOOD BEAM — SIZED
'""' BY OTHERS TO PROVIDE
:!i y SUPPORT UNDER ENTIRE
CURB LENGTH AND WIDTH.
�'��2 V
gEW
THROUGH BOLTED ON BEAM UNDERSIDE
WITH NUT, BOLT AND WASHER � THYBAR CURB SECTION
AS NECESSARY TO ATTACH
CURB TO BUILDING ROOF
SUPPORT STRUCTURE. WOOD BEAM
SIZED BY OTHERS
,.:,
IQ
j0
,
TC3 Wood Beam Mounting.dwg
Print Date:11/12/2015
THYBAR CORPORATION
913 S. Kay Avenue
1111 Addison, IL 60101
800-666-CURB(2872)
Fax:630-543-5309
www.thybar.com
Member of
VISCUA
Seismic /130 MPH Wind Load Calculations for a
Aaon C Cabinet RN-011 (920AHU10) on a
Thybar Insulated TC-3 Roofcurb
in Tigard OR 97224
CWS Durham 0 and M Building Remodel
Thybar Order#: 184599
August 17, 2018
,03 C
O3Cr[J1
0 PROpE ,t
ossi
CO2
5,71 � NFF
19695 9 9�-
•REGON
411'1,190
St,
frEN C.S' 8.23.18
RENEWAL DATE: 12.31.19
Digitally signed by Steven C Ball,SE
Steven C Ball, SE DN:.0stA E=sball@johnmaes,Inc",
�"John A Martin&Associates,Inc",
CN='Steven C Ball,SE"
Date:2018.08.23 13:11:58-0700'
Z w
This analysis considers the wind and seismic force Reviewed b
F— m calculations and anchorage of the curb to the structure only. y'
oThe supporting structure shall be reviewed and approved by others. Hossain Ghaffari
u) The curb design and unit anchorage to the curb is by Thybar. 08-21-2018
2 co
No installation shall take place until the anchorage and supporting
JOHN A. MARTIN structure are approved by the appropriate jurisdiction.
& ASSOCIATES, INC.
Structural Engineers
This document contains proprietary information from Thybar Corporation. Its contents may not be used for any other
project or location other than the project or location for which it was created without the prior written permission of
Thybar Corporation.
8/17/2018
Unit: Aaon C Cabinet RN-011 (920AHU10)
Location: Tigard OR 97224
Curb: Insulated TC-3
Governing Code: 2014OSSC / IBC2012
SDC: D
Design Wind Speed: 130 MPH
CWS Durham 0 and M Building Remodel
These calculations begin with the assumption that the Thybar curb is
supported around its full perimeter by building structure. Design of building
structure is not the responsibility of Thybar Corporation.
A 14 inch high Thybar Insulated TC-3 of minimum 14 gage galvanized side wall
construction will meet the 2014OSSC / IBC2012 requirements for installing an
Aaon C Cabinet RN-011 (920AHU10) unit in Tigard OR 97224 when
manufactured with stiffeners installed 34 inches max OC and installed
according to the attached drawings.
The unit must be attached to the Thybar Insulated TC-3 using 12 gage
restraint brackets. Bracket quantity is determined in the calculations and is
summarized as follows:
Minimum 12 gage bracket quantity: 4
The Thybar Insulated TC-3 must be attached to the building structure using
welds or bolts at the curb base flanges. Flange connection minimum bolt
quantity is determined in the calculations and is summarized as follows:
Total connection minimum quantity: 12
As curb manufacturers, Thybar Corporation cannot be expected to provide
appropriate attachment hardware for every possible type of roof structure.
Thybar provides seismic/windload calculations that are based on the material
provided; typically sheet metal curbs. It is the responsibility of others (project
engineer, architect, SEOR, etc) to know enough about the load carrying
capability of the building structure to design a method of attachment to that
structure. Thybar does not design the structure and therefore should not
recommend an attachment method that may create difficulties with existing
field conditions outside of the curb manufacturer's control.
Summary 1
Th bar Corporation 8/17/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
Location Tigard OR 97224
General
Applicable Building Code 20140SSC/
IBC2012
Seismic Design Category(SDC) D
Unit Manufacturer Aaon
Unit Model C Cabinet RN-011
(920AHU10)
Length(in) 185.00
Equip Width(in) 100.88
Height(in) 60.0
Weight(Ib) 3,003
CG„(in) 89.80
CGy,(in) 32.00
Curb Type Insulated TC-3
Curb Length(in) 173.38
Curb Width(in) • 54.00
Curb Height(in) 14.00
Minimum Thickness(ga) 14
Stiffener max OC spacing(in) 34
F5(psi) 30,000
E(psi) 30,000,000
Thickness(in) 0.0670
u 0.3
I(in) 14.0
Curb hit 209
b/t 507
k, 4.0
k, 1.0
F,(psi) 421
Snow Importance,I 1.2
Snow Load,pi(Ib) 3,473
Curb Design Load,0.75`max(Wind, 4401
.7'Seismic)+0.755,(lb)=
0.4•F5=F,(psi) 12,000
0.6'F5=F,(psi) 18,000
Wind Load(130mph)Fw(Ib)= 2,395
Exposure Category= B
Rooftop height(ft)= 20
Velocity Pressure coefficient Kz= 0.70
Topography factor Kzt= 1.00
Wind Directionality factor Kd= 0.90
Wind Speed V= 130
Importance factor Iw= N/A
qz= 27.26
GCr 1.90
Fr= 966
Fe,,,,,,= 5,153
Fe M,= 966
Sxs= 0.715
So,= 0.442
a,= 1.00
= 1.50
Seismic
to
RP= 6.00
z/h= 1.0
Ss(%ofg)= 96.10
S,(%of g)= 41.90
Site Coefficient F,= 1.12
Site Coefficient F,= 1.58
Site Soil Classification= D
Seismic Upward Force(lb),F up= 429.42
ex(in) 2.7
ey(in) 18.4375
Curb Load ax.,. 1.088
Distribution
Factors ax- 0.912
ay+ 0.683
ay- 0.317
C,„„(lb/in) 27.7
Curb Loads C,,,,(lb/in) 5.01
Shear Wall Factor a, 0.544
R Unit shear,v(lb/in) 44.317
S e Curb Long Unit Overturning,Cu(Ibin) 14.4
u a Dimension Unit Uplift,T(lb) 1,626
p c Curb Overturning,Cc(Win) 68.9
p t
o I Curb Corner Uplift,Tc(lb/in) 8.79
✓ o Shear Wall Factors, 0.683
t n Unit shear,v(lb/in) 17.331
s Curb Short Unit Overturning,Cu(Ibfin) 4830
Dimension Unit Uplift,T(Ib) -223.829
Curb Overturning,Cc(lb/in) 8.397
Curb Corner Uplift,Tc(lb/in) -4.145
Max Shear(lb/in) 33.2
Shear f,(psi) 496
f,/F, 0.04 <1.0,OK
Curb Verification
Max Axial Reaction(lb/in) 27.7
Axial f,(psi) 414
fa/Fa 0.98 <1.0,OK
Load Calcs 2
Thybar Corporation 8/17/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
General
Location Tigard OR 97224
Applicable Building Code 20140SSC/IBC2012
Unit Model C Cabinet RN-011 (920AHU10)
Curb Type Insulated TC-3
Bracket Dimensions
Length(in) 16
Max bending arm(in) 2.2
Max torsion arm(in) 0.001
Minimum Material thickness(ga) 12
Material thickness(in) 0.0970
Fy(psi) 30,000
Area(in2) 1.552
Screws
Screw size/type(#) 10
Quantity of screws 7
Hole size(in) 1/4
Allowable pullout(lb/screw) 1146
Max pullout(lb/bracket) 8,019
Allowable shear(lb/screw) 1,206
Max shear(lb/bracket) 8,445
Torsion on Bracket
Fv=0.4*Fy(psi) 12,000
Max shear(Ib) 602,176
Flexure on Bracket
Fb=0.6*Fy(psi) 18,000
Max shear(Ib) 33,862
Shear on Bracket Attachment Holes
Distance-hole edge to bracket edge 0.375
Max shear(Ib) 3,056
Tension on Bracket
FT=0.4*Fy(psi) 12,000
TMaX(Ib) 16,587
Bracket Capacity
Allowable Load(Ib) 3,056
Bracket Verification
Horizontal Design Load(Ib) 4,401 4,401
Curb Length/Width(in) 173.38 54.00
Shear Wall Factor 0.54 0.68
Design Shear(Ib) 2,393 3,005
Unit Design Uplift,Tc(Ib) 1626.43 0.00
Unit Uplift,Tc(Ib) 884 0
R=(V2+122)1/2
2,551 3,005
#per side 0.83 0.98
Clip Safety Factor 2
Total Clips Required 4
Unit To Curb 3
Thybar Corporation 8/17/2018
ThybarTC3-VC3 Aaon Units TigardOR OSSC2014
General
Location Tigard OR 97224
Applicable Building Code 2014OSSC/ IBC2012
Unit Model C Cabinet RN-011 (920AHU10)
Curb Type Insulated TC-3
Material Properties
Fy(psi) 30,000
Material Allowable Stress, Fa 12,000
(psi)
Base Attachment Dimensions
Hole Size (in) 0.625
Number of Holes per 1
attachment
Min. Material thickness (ga) 14
Min. Material thickness (in) 0.1340
Cut out area (in2) 0.307
Base flange width (in) 2.0
Edge distance (in) 11/16
Base shear area (in2) 0.09
Base Attachment Forces
Length Width
Horizontal Design Load (lb) 4400.86 4400.86
Length (in) 173.38 54.00
Shear(Ib) 2,393 3,005
Unit Uplift, Tc(Ib) 884 0
R= (V2+T22)112 2,551 3,005
Length Width
Base Attachment Stresses-fa 4,616 5,436
(psi)
Base Safety Factor 2 2
fa/Fa 0.77 0.91
Base Attachment Minimum 6 6
Quantity
Minimum Base Attachments- 12
Perimeter Distributed
Base Attachment Holes 4
8/17/2011
Aaon C Cabinet Unit
� t hy barTigard OR
COR''°N,I ON
111 SEISMIC/WINDLOAD RESTRAINT BRACKET
rnyba makes fr right the ver',time,
e, INSTALLATION DETAILS FOR INSULATED CURBS
wary tin:e
INSTALLATION INSTRUCTIONS:
,.1
PLACE RESTRAINTS IN APPROXIMATE LOCATIONS AS SHOWN. -
EQUALLY DISTRIBUTE RESTRAINT AS MUCH AS POSSIBLE WHILE AVOIDING INTERFERENCES WITH
LIFTING LUGS,CONDENSATE DRAIN LINES,UNIT BASE SCREWS,ETC.
GASKET TOP PERIMETER OF CURB AND RESTRAINTS BEFORE SETTING UNIT. r.A ?[TING
SEE MATRIX BELOW FOR QUANTITIES REQUIRED PER UNIT.
I
k :T1 I
P
1
r---1 r---1' . ,.,::$
• .$
NOTE:
DRAWINGS ARE CONCEPTUAL,NOT TO SCALE
INNER RESTRAINTS MUST BE FIELD INSTALLED TO ROOF CURB BEFORE SETTING UNIT. RESTRAINT DETAIL
THYCURB MODEL RESTRAINT BRACKET QTY. MATERIAL GAC4,L1/ANI C EEL .l.j1J F-,.,IvTI'��Pl
Aaon SEISMIC RESTRAINTS PER UNIT HARDWARE ( /) #10,1" T I •I.FE W` PER RE 1 PAI1I I
Aaon CCabinet RN-011(920AHU10) ACSWRANB0011RC-01 4 (') # ,2 ID' SOF' Ww PER RE'.JR AI'11
SEISMIC&WINDLOAD BRACKETS ARE DESIGNED&CALCULATED FOR USE IN SEISMIC/WINDLOAD APPLICATIONS WHEN PROVIDED
AS PART OF A SEISMIC/WINDLOAD RATED CURB.
ATTACHMENT OF CALCULATED BRACKETS TO ANY OTHER CURB DOES NOT CONSTITUTE A SEISMIC/WINDLOAD RATED ASSEMBLY.
REVISION DATE: 8/1 712 01 8
testraint Bracket Detail
in thybar Structural Steel Mounting
u,
• thybar rvrake,k right the J,:st tm:e.
every tle e
SEISMIC/WIND LOAD INSULATED CURB
INSTALLATION OPTIONS
The curbs should be anchored to structural steel as follows:
* The width of the supporting structural steel shall be at least as wide as the base plate
of the curb.
* Bolts should be ASTM A307 grade min strength, with nuts and washers.
* Bolts should be placed in every hole provided in the base plate of the curb; pass through
the base plate of the curb and the structural steel; and tightened according
to manufacturers torque specifications. (Figure 1-1)
* Alternatively, the curb may be welded to the structural steel. (Figure 1-2)
�_,.:.: : xi 3" MIN 0 BOLT WITH WASHER
:/0:4*k.:4' WOOD NAILER
�i•�i:;:v.;, (LENGTH TO BE DETERMINED IN FIELD)
CURB ��::Z,•:•iil
/: /".GO:
Vit:*�''`Z
:::4 VISCMA APPROVED
itt•1S•. = SEISMIC WINDLOAD
� RATED OF
%�� '"�/� VARIOUS HEIGHTS
un
Po
le
STRUCTURAL ►,
STEEL ��
NUT WITH WASHER t.
Figure 1-1
CENTERED ON 1 " L1�" f` cip
EACH BOLT HOLE \
CURB •�•:,
(44:::(t:
STRUCTURAL
STEEL NII
Figure 1-2 .
Consult Local Building Codes & FEMA Manual. 412/December 2002
PRINTED:11/12/15
■ thybari III
Concrete Slab Mounting
courx;ttr.r;cw
7hybar makes;t right the 6,,st time,
SEISMIC/WIND LOAD INSULATED CURB
INSTALLATION OPTIONS
The equipment support should be anchored to concrete as follows:
* Anchor system must comply with applicable building code (Local building code,
International Building Code, Uniform Building Code, etc.).
* Anchor to be Hilti Kwik Bolt TZ, Simpson Strong—Tie or equivalent.
* Anchors are to be placed in every hole provided in the base plate of the curb.
* Anchors are to pass through the base plate & be embedded into the concrete.
* Follow anchor manufacturers instructions for drilling holes, installation anchor and
tightening nut.
�iQs��'���`�i' ANCHOR WITH NUT Se WASHER
AI.�Zi'��'�, (i" DIAMETER MINIMUM,•
E•
MBEDMENT TH AND
EDGEDDISTANCEPAS REQUIRED
�•:.�,•.�.; BY FIELD CONDITIONS AND
:4:iV�` - HARDWARE SELECTION.)
to.:74:::i
. �;; Normal Weight
�R� Concrete
• ' .<7.... .... CONCRETE
A G
• . ° "° n THYBAR CURB SECTION
pi • '
• Q a
° •4, d •
Figure 1-1
a
® n e °
a• a ..
a a d
a
4,d . C . . d. •$., e • •
e . •
v •• ' d ' ° •
a da
CI ° a a•
° a
d .
Consult Local Building Codes & FEMA Manual. 412/December 2002 TC3 Concrete Installation.dwg
PRINTFfl•11/19/1c
® t hyba r Wood Beam Mounting
III Thybar rake,a right the fi:thh:- INSULATED ROOF CURB ON
every tr
WOODEN STRUCTURAL BEAM
INSTALLATION OPTIONS
The curbs can be installed on a wood—beam type roof providing there is adequate
support around entire curb perimeter. The beam load carrying capability is to be
determined by others and the following provisions are acceptable:
* Curb base is the be through—bolted to wood joists of roof support.
* Through bolts are to be manufactured according to ASTM A307.
* Bolts are to be 4" diameter minimum and length as required to positively attach
to building structure.
* Bolts are to be installed in every hole in the roof curb base flange and
tightened according to bolt manufacturer's recommendations.
\�.
S. :*. INSTALL (1) }"O
`''�`%;�% ASTM A307 ALL-THREAD BOLT,
*4`• , LENGTH AS NECESSARY
* : ; IN EACH CURB FLANGE
CURB .,.�.o%. HOLE AT CURB BASE
%s'\4 X, ___ WOOD BEAM - SIZED
1 BY OTHERS TO PROVIDE
.....:-2.,/
�/"/ SUPPORT UNDER WIDTH.j\ // CURB LENGTH AND WIDTH.
THROUGH BOLTED ON BEAM UNDERSIDE
WITH NUT, BOLT AND WASHER THYBAR CURB SECTION
AS NECESSARY TO ATTACH
CURB TO BUILDING ROOF
SUPPORT STRUCTURE. oill WOODIZED BEAM
SBY OTHERS
1Q
co
TC3 Wood Beam Mounting.dwg
Print Date:11/12/2015