Report (102) . . C 2ol& A CoS63 IX ACCURATE 1 v�, \� C' � ih S .L. -`' . BALANCING . AGENCY INC AIR AND WATER BALANCING • DUCT LEAKAGE TESTING CERTIFIED TEST • ADJUST • BALANCE REPORT Project: Pink Victoria's Secret Location: 9585 SW Washington Square Rd- Tigard, OR. Engineer: M-Engineering HVAC Contractor: Grey Wolf HVAC 14/1\rE 4: i - NEBB# 3177 • CCB# 6475 • ESB# 3866 PO Box 653 • BEAvEProni, OR 97075 • (503) 297-6594 • ABA@ABAINC.US • FAX (503) 292-4825 iikAccuRATE Table of Contents BALANCING AGENCY INC Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR. Page# Table of Contents 1 Certification 2 Terms and Abbreviations 3 Instrument Calibration 4 General Remarks and Summaries 5 FPVAV Terminal Unit Test Report 6 VAV Terminal Unit Test Report 7 Terminal Unit Air Outlet Test Reports 8 Exhaust Fan Test Report 12 Indexed Floor Plan Accurate Balancing Agency, Inc. Page 1 of 12 iikACCURATE Certification BALANCING , AGENCY INC Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR. The data presented in this report is a record of system measurements and final adjustments that have been obtained in accordance with the current edition of the NEBB Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems. Any variances from design quantities, which exceed NEBB tolerances, are noted in the Test-Adjust-Balance Report Project Summary. Significant or noteworthy remarks are noted on the General Remarks or on individual test reports. Noted deficiencies are not the TAB firms responsibility to repair. Prior to issuance of this report, Deficiency Reports are forwarded to our contracted agent. Warranty is limited to one year from date of this report. Within that time, any descrepancies, ambiguities, or omissions found in this report will be retested, adjusted, or balanced as needed. A written notification will be required. Submitted and Certified by NEBB TAB Firm: Accurate Balancing Agency, Inc. Certification: 3177 Expiration Date: March 31,2019 Certification Date: May 26,2017 Signed and Sealed by NEBB Supervisor: Edward M. May Jr. 7,44, f x, fr Accurate Balancing Agency, Inc. Page 2 of 12 )11ACCURATE Terms and Abbreviations BALANCING . AGENCY INC Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR. AC Air Conditioning Unit AH Air Handler AHU Air Handling Unit AK Area Factor or Flowhood Backpressure Compensation Factor BHP Brake Horsepower BMS Building Management System BTUH British Thermal Units per Hour CEF Ceiling Exhaust Fan CFM Cubic Feet per Minute CRU Computer Room Unit DB Dry Bulb DDC Direct Digital Control EAT Entering Air Temperature EWT Entering Water Temperature EF Exhaust Fan EG Exhaust Grille (Shown as Triangled number on indexed plans) ERU Energy Recovery Unit FPB Fan Powered Box (Terminal Unit which incorporates a fan) FSD Fire/Smoke Damper GPM Gallons per Minute Head Pressure Difference across the entering and leaving side of a pump HRU Heat Recovery Unit HVAC Heating Ventilation and Air Conditioning HZ Hertz Inches(") Inches of water gauge K Correction factor to the free area needed to calculate CFM LAT Leaving Air Temperature LWT Leaving Water Temperature N/A Not Applicable N/L Not Listed OBD Opposed Blade Damper OAD Outside Air Damper OD Outside Diameter OSA Outside Air Damper PSI Pounds per Square Inch RA Return Air RG Return Grille (Shown as a Circled number on indexed plans) RPM Revolutions Per Minute RTU Roof Top Unit SA Supply Air SG Supply Grille (Shown as a Standard number on indexed plans) SFA Service Factor Amperage TAB Test;Adjust; and Balance VAV Variable Air Volume (Terminal Unit which regulates airflow) VEL Velocity WB Web Bulb Accurate Balancing Agency, Inc. Page 3 of 12 AACCURATE Instrument Calibration Report BALANCING . AGENCY INC Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space 1407-Tigard,OR. Instrument Manufacturer ! Model# ! Serial# I Calibrated I Cal. Due =I TVPe Tachometer AGPtech 6234766 1546447 8/5/2016 8/5/2017 Rotation Thermometer Evergreen PR-T-1 1600269 12/23/2016 12/23/2017 Immersion Thermometer Evergreen PR-T-1 1600269 12/23/2016 12/23/2017 Air Temp Electrical UEI DL389 160102883 7/26/2016 7/26/2017 Multimeter Manometer Evergreen S-PVF-1 1600225 12/13/2016 12/13/2017 Air Pressure Hygro-Thermometer Evergreen S-H-3-5" 1600307 9/13/2016 9/13/2017 Humidity Anemometer Extech AN300 1004100 7/30/2016 7/30/2017 Air Velocity Flowhood Evergreen CH-15D 1700232 4/16/2017 4/16/2018 Air Volume Thermometer UEI ATT47 probe N/A 10/9/2016 10/9/2017 Contact Hydrometer Alnor/TSI HM680 70552165 1/31/2017 1/31/2018 Differential Pressure Accurate Balancing Agency, Inc. Page 4 of 12 AACCURATE General Remarks and Summary BALANCING AGENCY INC Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR. 1) FPVAV-1 is a series fan powered terminal unit which was balanced in full cooling;fan was adjusted to match primary airflow such that the terminal unit filter was neutral in full cooling mode. 2) FPVAV-2 is a series fan powered terminal unit which was balanced in full cooling;fan was adjusted to match primary airflow such that the terminal unit filter was neutral in full cooling mode. 3) FPVAV-3 is a series fan powered terminal unit which was balanced in full cooling;fan was adjusted to match primary airflow such that the terminal unit filter was neutral in full cooling mode. 4) FPVAV-3 primary airflow was listed on the equipment schedule at 690 CFM while its fan was listed at 520 CFM. FPVAV-3 supply grille design airflows have been altered to match the fan quantity. 5) FPVAV-4 is a series fan powered terminal unit which was balanced in full cooling;fan was adjusted to match primary airflow such that the terminal unit filter was neutral in full cooling mode. 6) FPVAV-4 was balanced with VAV-1 in maximum mode. 7) EF-1 is a single speed direct drive fan and is reported as tested. Accurate Balancing Agency, Inc. Page 5 of 12 . . AACCURATE Fan Powered Terminal Test Report BALANCING (Pressure Independent) . AGENCY INC Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR. Technician: TT Test Date: May 2017 Submittal Test Data FPB Terminal Type Size DDC Address Cal. Factor Fan Speed FPVAV-1 Series FPB 14"R FPVAV-1 1.02 Potentiometer FPVAV-2 Series FPB 14"R FPVAV-2 0.89 Potentiometer FPVAV-3 Series FPB 8"R FPVAV-3 1.02 Potentiometer FPVAV-4 Series FPB 12"R FPVAV-4 0.88 Potentiometer Remarks: I See related Air Outlet Test Report for additional air flow data. No Remarks were noted. Accurate Balancing Agency, Inc. Page 6 of 12 ACCURATE Variable Volume Terminal Test Report BALANCING . AGENCY INC (Pressure Independent) Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR. Technician: TT Test Date: May 2017 Submittal Test Data VAV Terminal Type Size DDC Address Cal. Factor VAV-1 Single Duct 10"R VAV-1 1.03 Remarks: ' See related Air Outlet Test Report for additional air flow data. No Remarks were noted. Accurate Balancing Agency,Inc. Page 7 of 12 • ACCURATE Air Outlet Test Report BALANCING . AGENCY INC Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR. Technician: TT Test Date: May 2017 Unit Design Preliminary Final Test SystemArea Served # J Size Type AK VEL CFM VEL CFM VEL CFM % FPVAV-1 Fan Sales Area 1 10"R SG 1.00 315 315 360 360 310 310 98% Sales Area 2 10"R SG 1.00 315 315 260 260 300 300 95% Sales Area 3 10"R SG 1.00 315 315 345 345 295 295 94% Sales Area 4 10"R SG 1.00 315 315 300 300 295 295 94% Sales Area 5 10"R SG 1.00 315 315 400 400 310 310 98% Sales Area 6 10"R SG 1.00 315 315 390 390 305 305 97% Sales Area 7 10"R SG 1.00 315 315 350 350 305 305 97% Sales Area 8 10"R SG 1.00 315 315 410 410 310 310 98% Totals 2520_ 2815 2430 96% FPVAV-1 1 Total Sum 1.00 2520 2520 2504 2504 2504 2504 99% Primary Maximum Totals 2520 2504 2504 99% FPVAV-1 1 Total Sum 1.00 500 500 497 497 497 497 99% Primary Minimum Totals 500 497 497 99% Remarks: FPVAV-1 is a series fan powered terminal unit which was balanced in full cooling;fan was adjusted to match primary airflow such that the terminal unit filter was neutral in full cooling mode. Accurate Balancing Agency, Inc. Page 8 of 12 ACCURATE Air Outlet Test Report BALANCING , AGENCY INC Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR. Technician: TT Test Date: May 2017 System/Unit Design Preliminary Final Test Area Served # Size Type AK VEL CFM VEL CFM VEL CFM % FPVAV-2 Fan Sales Area 1 10"R SG 1.00 260 260 225 225 250 250 96% Sales Area 2 10"R SG 1.00 260 260 235 235 260 260 100% Sales Area 3 10"R SG 1.00 260 260 280 280 260 260 100% Sales Area 4 10"R SG 1.00 260 260 245 245 255 255 98% Sales Area 5 8"R SG 1.00 150 150 140 140 145 145 97% Sales Area 6 8"R SG 1.00 150 150 160 160 145 145 97% Sales Area 7 8"R SG 1.00 150 150 145 145 150 150 100% Cash Room 8 8"R SG 1.00 130 130 130 130 130 130 100% Cash Room 9 8"R SG 1.00 130 130 130 130 135 135 104% Cash Room 10 8"R SG 1.00 130 130 175 175 130 130 100% Hallway 11 6"R SG 1.00 75 75 85 85 75 75 100% Totals 1955 1950 1935 99% FPVAV-2 1 Total Sum 1.00 1955 1955 1967 1967 1967 1967 101% Primary Maximum Totals 1955 1967 1967 101% FPVAV-2 1 Total Sum 1.00 400 400 406 406 406 406 102% Primary Minimum Totals 400 406 406 102% Remarks: I FPVAV-2 is a series fan powered terminal unit which was balanced in full cooling;fan was adjusted to match primary airflow such that the terminal unit filter was neutral in full cooling mode. Accurate Balancing Agency, Inc. Page 9 of 12 )1KACCURATE Air Outlet Test Report BALANCING AGENCY INC Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR. Technician: TT Test Date: May 2017 Systern/unit Design Preliminary Final Test Area Served # ` Size Type AK VEL CFM VEL CFM VEL CR4 g FPVAV-3 Fan Fitting Rooms 1 8"R SG 1.00 150 150 240 240 145 145 97% Fitting Rooms 2 8"R SG 1.00 150 150 250 250 155 155 103% Fitting Rooms 3 8"R SG 1.00 75 75 240 240 75 75 100% Fitting Rooms 4 6"R SG 1.00 40 40 250 250 40 40 100% Fitting Rooms 5 8"R SG 1.00 105 105 245 245 105 105 100% Totals 520 1225 520 100% FPVAV-3 1 Total Sum 1.00 520 520 520 520 520 520 100% Primary Maximum Totals 520 520 520 100% FPVAV-3 1 Total Sum 1.00 110 110 106 106 106 106 96% Primary Minimum Totals 110 106 106 96% Remarks: FPVAV-3 is a series fan powered terminal unit which was balanced in full cooling;fan was adjusted to match primary airflow such that the terminal unit filter was neutral in full cooling mode. FPVAV-3 primary airflow was listed on the equipment schedule at 690 CFM while its fan was listed at 520 CFM. FPVAV-3 supply grille design airflows have been altered to match the fan quantity. Accurate Balancing Agency,Inc. Page 10 of 12 • . AACCURATE Air Outlet Test Report BALANCING AGENCY INC Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR. Technician: TT Test Date: May 2017 System/ Unit Design Preliminary Final Test Area Solved Size Type AK VEL CFM VEL CFM VEL CFM Wo FPVAV-4 Max Stock Area 1 10"R SG 1.00 225 225 370 370 225 225 100% Stock Area 2 10"R SG 1.00 225 225 320 320 220 220 98% Stock Area 3 8"R SG 1.00 200 200 160 160 200 200 100% Break Room 4 8"R SG 1.00 200 200 195 195 195 195 98% Hallway 5 8"R SG 1.00 100 100 170 170 105 105 105% VAV-1 6 10"R SG 1.00 250 250 130 130 245 245 98% Totals 1200 1345 1190 99% FPVAV-4 1 Total Sum 1.00 1200 1200 1189 1189 1189 1189 99% Primary Maximum Totals 1200 1189 1189 99% FPVAV-4 1 Total Sum 1.00 240 240 230 230 230 230 96% Primary Minimum Totals 240 230 230 96% VAV-1 Max 1 10"R SG 1.00 250 250 130 130 245 245 98% Manager Totals 250 130 245 98% VAV-1 1 Total SG 1.00 0 0 0 0 0 0 Minimum Totals 0 0 0 Remarks: I FPVAV-4 is a series fan powered terminal unit which was balanced in full cooling;fan was adjusted to match primary airflow such that the terminal unit filter was neutral in full cooling mode. FPVAV-4 was balanced with VAV-1 in maximum mode. Accurate Balancing Agency, Inc. Page 11 of 12 AACCURATE Fan Test Report BALANCING . AGENCY INC (Direct Drive< 1/6HP) Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR. Technician: TT Test Date: May 2017 Submittal Data I Unit Designation EF-1 Service Pink Powder Room Manufacturer Cook Model Number Gemini 140 Test Data I Item Design Actual Total Airflow (CFM Design/Outlet) 120/ 120 140 Submittal Data , Unit Designation Service Manufacturer Model Number Test Data , Item Design Actual Total Airflow (CFM Design/Outlet) Submittal Data I Unit Designation Service Manufacturer Model Number Test Data I Item Design Actual Total Airflow (CFM Design / Outlet) Remarks: EF-1 is a single speed direct drive fan and is reported as tested. Accurate Balancing Agency, Inc. Page 12 of 12