TEST • ADJUST • BALANCE REPORT
Project: Pink Victoria's Secret
Location: 9585 SW Washington Square Rd- Tigard, OR.
Engineer: M-Engineering
HVAC Contractor: Grey Wolf HVAC
14/1\rE 4:
i -
NEBB# 3177 • CCB# 6475 • ESB# 3866
PO Box 653 • BEAvEProni, OR 97075 • (503) 297-6594 • ABA@ABAINC.US • FAX (503) 292-4825
iikAccuRATE Table of Contents
BALANCING
AGENCY INC
Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR.
Page#
Table of Contents 1
Certification 2
Terms and Abbreviations 3
Instrument Calibration 4
General Remarks and Summaries 5
FPVAV Terminal Unit Test Report 6
VAV Terminal Unit Test Report 7
Terminal Unit Air Outlet Test Reports 8
Exhaust Fan Test Report 12
Indexed Floor Plan
Accurate Balancing Agency, Inc. Page 1 of 12
iikACCURATE Certification
BALANCING
, AGENCY INC
Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR.
The data presented in this report is a record of system measurements and final
adjustments that have been obtained in accordance with the current edition of the NEBB
Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems.
Any variances from design quantities, which exceed NEBB tolerances, are noted in the
Test-Adjust-Balance Report Project Summary.
Significant or noteworthy remarks are noted on the General Remarks or on individual
test reports.
Noted deficiencies are not the TAB firms responsibility to repair. Prior to issuance of this
report, Deficiency Reports are forwarded to our contracted agent.
Warranty is limited to one year from date of this report. Within that time, any
descrepancies, ambiguities, or omissions found in this report will be retested, adjusted,
or balanced as needed. A written notification will be required.
Submitted and Certified by
NEBB TAB Firm: Accurate Balancing Agency, Inc.
Certification: 3177
Expiration Date: March 31,2019
Certification Date: May 26,2017
Signed and Sealed by
NEBB Supervisor: Edward M. May Jr.
7,44, f x,
fr
Accurate Balancing Agency, Inc. Page 2 of 12
)11ACCURATE
Terms and Abbreviations
BALANCING
. AGENCY INC
Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR.
AC Air Conditioning Unit
AH Air Handler
AHU Air Handling Unit
AK Area Factor or Flowhood Backpressure Compensation Factor
BHP Brake Horsepower
BMS Building Management System
BTUH British Thermal Units per Hour
CEF Ceiling Exhaust Fan
CFM Cubic Feet per Minute
CRU Computer Room Unit
DB Dry Bulb
DDC Direct Digital Control
EAT Entering Air Temperature
EWT Entering Water Temperature
EF Exhaust Fan
EG Exhaust Grille (Shown as Triangled number on indexed plans)
ERU Energy Recovery Unit
FPB Fan Powered Box (Terminal Unit which incorporates a fan)
FSD Fire/Smoke Damper
GPM Gallons per Minute
Head Pressure Difference across the entering and leaving side of a pump
HRU Heat Recovery Unit
HVAC Heating Ventilation and Air Conditioning
HZ Hertz
Inches(") Inches of water gauge
K Correction factor to the free area needed to calculate CFM
LAT Leaving Air Temperature
LWT Leaving Water Temperature
N/A Not Applicable
N/L Not Listed
OBD Opposed Blade Damper
OAD Outside Air Damper
OD Outside Diameter
OSA Outside Air Damper
PSI Pounds per Square Inch
RA Return Air
RG Return Grille (Shown as a Circled number on indexed plans)
RPM Revolutions Per Minute
RTU Roof Top Unit
SA Supply Air
SG Supply Grille (Shown as a Standard number on indexed plans)
SFA Service Factor Amperage
TAB Test;Adjust; and Balance
VAV Variable Air Volume (Terminal Unit which regulates airflow)
VEL Velocity
WB Web Bulb
Accurate Balancing Agency, Inc. Page 3 of 12
AACCURATE Instrument Calibration Report
BALANCING
. AGENCY INC
Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space 1407-Tigard,OR.
Instrument Manufacturer ! Model# ! Serial# I Calibrated I Cal. Due =I
TVPe
Tachometer AGPtech 6234766 1546447 8/5/2016 8/5/2017
Rotation
Thermometer Evergreen PR-T-1 1600269 12/23/2016 12/23/2017
Immersion
Thermometer Evergreen PR-T-1 1600269 12/23/2016 12/23/2017
Air Temp
Electrical UEI DL389 160102883 7/26/2016 7/26/2017
Multimeter
Manometer Evergreen S-PVF-1 1600225 12/13/2016 12/13/2017
Air Pressure
Hygro-Thermometer Evergreen S-H-3-5" 1600307 9/13/2016 9/13/2017
Humidity
Anemometer Extech AN300 1004100 7/30/2016 7/30/2017
Air Velocity
Flowhood Evergreen CH-15D 1700232 4/16/2017 4/16/2018
Air Volume
Thermometer UEI ATT47 probe N/A 10/9/2016 10/9/2017
Contact
Hydrometer Alnor/TSI HM680 70552165 1/31/2017 1/31/2018
Differential Pressure
Accurate Balancing Agency, Inc. Page 4 of 12
AACCURATE General Remarks and Summary
BALANCING
AGENCY INC
Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR.
1) FPVAV-1 is a series fan powered terminal unit which was balanced in full cooling;fan was adjusted to match
primary airflow such that the terminal unit filter was neutral in full cooling mode.
2) FPVAV-2 is a series fan powered terminal unit which was balanced in full cooling;fan was adjusted to match
primary airflow such that the terminal unit filter was neutral in full cooling mode.
3) FPVAV-3 is a series fan powered terminal unit which was balanced in full cooling;fan was adjusted to match
primary airflow such that the terminal unit filter was neutral in full cooling mode.
4) FPVAV-3 primary airflow was listed on the equipment schedule at 690 CFM while its fan was listed at 520
CFM. FPVAV-3 supply grille design airflows have been altered to match the fan quantity.
5) FPVAV-4 is a series fan powered terminal unit which was balanced in full cooling;fan was adjusted to match
primary airflow such that the terminal unit filter was neutral in full cooling mode.
6) FPVAV-4 was balanced with VAV-1 in maximum mode.
7) EF-1 is a single speed direct drive fan and is reported as tested.
Accurate Balancing Agency, Inc. Page 5 of 12
. .
AACCURATE Fan Powered Terminal Test Report
BALANCING (Pressure Independent)
. AGENCY INC
Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR.
Technician: TT Test Date: May 2017
Submittal Test Data
FPB Terminal Type Size DDC Address Cal. Factor Fan Speed
FPVAV-1 Series FPB 14"R FPVAV-1 1.02 Potentiometer
FPVAV-2 Series FPB 14"R FPVAV-2 0.89 Potentiometer
FPVAV-3 Series FPB 8"R FPVAV-3 1.02 Potentiometer
FPVAV-4 Series FPB 12"R FPVAV-4 0.88 Potentiometer
Remarks: I See related Air Outlet Test Report for additional air flow data.
No Remarks were noted.
Accurate Balancing Agency, Inc. Page 6 of 12
ACCURATE Variable Volume Terminal Test Report
BALANCING
. AGENCY INC (Pressure Independent)
Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR.
Technician: TT Test Date: May 2017
Submittal Test Data
VAV Terminal Type Size DDC Address Cal. Factor
VAV-1 Single Duct 10"R VAV-1 1.03
Remarks: ' See related Air Outlet Test Report for additional air flow data.
No Remarks were noted.
Accurate Balancing Agency,Inc. Page 7 of 12
•
ACCURATE Air Outlet Test Report
BALANCING
. AGENCY INC
Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR.
Technician: TT Test Date: May 2017
Unit Design Preliminary Final Test
SystemArea Served # J Size Type AK VEL CFM VEL CFM VEL CFM %
FPVAV-1 Fan
Sales Area 1 10"R SG 1.00 315 315 360 360 310 310 98%
Sales Area 2 10"R SG 1.00 315 315 260 260 300 300 95%
Sales Area 3 10"R SG 1.00 315 315 345 345 295 295 94%
Sales Area 4 10"R SG 1.00 315 315 300 300 295 295 94%
Sales Area 5 10"R SG 1.00 315 315 400 400 310 310 98%
Sales Area 6 10"R SG 1.00 315 315 390 390 305 305 97%
Sales Area 7 10"R SG 1.00 315 315 350 350 305 305 97%
Sales Area 8 10"R SG 1.00 315 315 410 410 310 310 98%
Totals 2520_ 2815 2430 96%
FPVAV-1 1 Total Sum 1.00 2520 2520 2504 2504 2504 2504 99%
Primary Maximum Totals 2520 2504 2504 99%
FPVAV-1 1 Total Sum 1.00 500 500 497 497 497 497 99%
Primary Minimum Totals 500 497 497 99%
Remarks:
FPVAV-1 is a series fan powered terminal unit which was balanced in full cooling;fan was adjusted to match
primary airflow such that the terminal unit filter was neutral in full cooling mode.
Accurate Balancing Agency, Inc. Page 8 of 12
ACCURATE Air Outlet Test Report
BALANCING
, AGENCY INC
Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR.
Technician: TT Test Date: May 2017
System/Unit Design Preliminary Final Test
Area Served # Size Type AK VEL CFM VEL CFM VEL CFM %
FPVAV-2 Fan
Sales Area 1 10"R SG 1.00 260 260 225 225 250 250 96%
Sales Area 2 10"R SG 1.00 260 260 235 235 260 260 100%
Sales Area 3 10"R SG 1.00 260 260 280 280 260 260 100%
Sales Area 4 10"R SG 1.00 260 260 245 245 255 255 98%
Sales Area 5 8"R SG 1.00 150 150 140 140 145 145 97%
Sales Area 6 8"R SG 1.00 150 150 160 160 145 145 97%
Sales Area 7 8"R SG 1.00 150 150 145 145 150 150 100%
Cash Room 8 8"R SG 1.00 130 130 130 130 130 130 100%
Cash Room 9 8"R SG 1.00 130 130 130 130 135 135 104%
Cash Room 10 8"R SG 1.00 130 130 175 175 130 130 100%
Hallway 11 6"R SG 1.00 75 75 85 85 75 75 100%
Totals 1955 1950 1935 99%
FPVAV-2 1 Total Sum 1.00 1955 1955 1967 1967 1967 1967 101%
Primary Maximum Totals 1955 1967 1967 101%
FPVAV-2 1 Total Sum 1.00 400 400 406 406 406 406 102%
Primary Minimum Totals 400 406 406 102%
Remarks: I
FPVAV-2 is a series fan powered terminal unit which was balanced in full cooling;fan was adjusted to match
primary airflow such that the terminal unit filter was neutral in full cooling mode.
Accurate Balancing Agency, Inc. Page 9 of 12
)1KACCURATE Air Outlet Test Report
BALANCING
AGENCY INC
Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR.
Technician: TT Test Date: May 2017
Systern/unit Design Preliminary Final Test
Area Served # ` Size Type AK VEL CFM VEL CFM VEL CR4 g
FPVAV-3 Fan
Fitting Rooms 1 8"R SG 1.00 150 150 240 240 145 145 97%
Fitting Rooms 2 8"R SG 1.00 150 150 250 250 155 155 103%
Fitting Rooms 3 8"R SG 1.00 75 75 240 240 75 75 100%
Fitting Rooms 4 6"R SG 1.00 40 40 250 250 40 40 100%
Fitting Rooms 5 8"R SG 1.00 105 105 245 245 105 105 100%
Totals 520 1225 520 100%
FPVAV-3 1 Total Sum 1.00 520 520 520 520 520 520 100%
Primary Maximum Totals 520 520 520 100%
FPVAV-3 1 Total Sum 1.00 110 110 106 106 106 106 96%
Primary Minimum Totals 110 106 106 96%
Remarks:
FPVAV-3 is a series fan powered terminal unit which was balanced in full cooling;fan was adjusted to match
primary airflow such that the terminal unit filter was neutral in full cooling mode.
FPVAV-3 primary airflow was listed on the equipment schedule at 690 CFM while its fan was listed at 520 CFM.
FPVAV-3 supply grille design airflows have been altered to match the fan quantity.
Accurate Balancing Agency,Inc. Page 10 of 12
• .
AACCURATE Air Outlet Test Report
BALANCING
AGENCY INC
Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR.
Technician: TT Test Date: May 2017
System/ Unit Design Preliminary Final Test
Area Solved Size Type AK VEL CFM VEL CFM VEL CFM Wo
FPVAV-4 Max
Stock Area 1 10"R SG 1.00 225 225 370 370 225 225 100%
Stock Area 2 10"R SG 1.00 225 225 320 320 220 220 98%
Stock Area 3 8"R SG 1.00 200 200 160 160 200 200 100%
Break Room 4 8"R SG 1.00 200 200 195 195 195 195 98%
Hallway 5 8"R SG 1.00 100 100 170 170 105 105 105%
VAV-1 6 10"R SG 1.00 250 250 130 130 245 245 98%
Totals 1200 1345 1190 99%
FPVAV-4 1 Total Sum 1.00 1200 1200 1189 1189 1189 1189 99%
Primary Maximum Totals 1200 1189 1189 99%
FPVAV-4 1 Total Sum 1.00 240 240 230 230 230 230 96%
Primary Minimum Totals 240 230 230 96%
VAV-1 Max 1 10"R SG 1.00 250 250 130 130 245 245 98%
Manager Totals 250 130 245 98%
VAV-1 1 Total SG 1.00 0 0 0 0 0 0
Minimum Totals 0 0 0
Remarks: I
FPVAV-4 is a series fan powered terminal unit which was balanced in full cooling;fan was adjusted to match
primary airflow such that the terminal unit filter was neutral in full cooling mode.
FPVAV-4 was balanced with VAV-1 in maximum mode.
Accurate Balancing Agency, Inc. Page 11 of 12
AACCURATE Fan Test Report
BALANCING
. AGENCY INC (Direct Drive< 1/6HP)
Project-Location: Pink Victoria's Secret-9585 SW Washington Square Road-Space H07-Tigard,OR.
Technician: TT Test Date: May 2017
Submittal Data I
Unit Designation EF-1
Service Pink Powder Room
Manufacturer Cook
Model Number Gemini 140
Test Data I
Item Design Actual
Total Airflow (CFM Design/Outlet) 120/ 120 140
Submittal Data ,
Unit Designation
Service
Manufacturer
Model Number
Test Data ,
Item Design Actual
Total Airflow (CFM Design/Outlet)
Submittal Data I
Unit Designation
Service
Manufacturer
Model Number
Test Data I
Item Design Actual
Total Airflow (CFM Design / Outlet)
Remarks:
EF-1 is a single speed direct drive fan and is reported as tested.
Accurate Balancing Agency, Inc. Page 12 of 12