Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Report (89)
Submittal Review 'Q PA- RECEIVED July 18, 2018 SEP 12 2018 Rebecca Grant CITY OF TIGARD DOWA IBI Group BUILDING DIVISION 907 SW Stark Street Portland, Oregon 97205 Project: TTSD Templeton Elementary Project Number: 16-1920 Dear Rebecca: Fire Alarm submittal number 283000-005 data received July 13, 2018 has been reviewed by this office with the following disposition: Item Manufacturer Action 283000 Fire Detection and Alarm Speaker Strobes System Sensor Make Corrections Noted 1. Outdoor Notification Device shall be speaker strobe. The above submittal data has been reviewed only for conformance with the design concept and for compliance with information given in the Contract Documents, and this review does not extend to means, methods, techniques, sequence of construction, dimensions, quantities, or safety precautions thereto. Review does not relieve the Contractor from responsibility for variations from the requirements of the Contract Documents. Sincerely, dp, Michael Lopez OFFIC COPY MRL/kes Submittal Stamp Page Triplett Wellman CONTRACTORS General Contractor Stamp: Project Name Triplett Templeton Elementary School Wellman D REVIEWED 0 REJECTED 0 MAKE CORRECTIONS 0 NOT REVIEWED BY May Nguyen DATE 6/27/2018 SUBMITTAL# 283000 SPEC 283000-00: This review is only for general conformance of the project and general compliance. Corrections or comments made on these drawings during this review do not relieve Contractor/Subcontractor from compliance with the requirements of the plans and specifications. Contractor is responsible for all dimensions and fabrication to be confirmed and correlated at the job site Architect Stamp: Consultant Stamp: PcCi PORTLAND ELECTRICAL CONSTRUCTION INC. 1019 7TH STREET OREGON CITY,OR 97045 PHONE: 503-655-2281 FAX: 503-655-5033 OR CCB#51764 WA EC PORTLECO23PE DIVISION 28 - ELECTRONIC SAFETY & SECURITY PE IFI A S C C T ON SECTION: 28 30 00 FIRE DETECTION & ALARM (MAIN BUILDING) 2.02 CONTROL PANEL 2.03 FIRE COMMUNICATIONS CONTROL PANEL 2.04 CENTRAL STATION REPORTING 2.06 SOFTWARE 2.07 REMOTE EQUIPMENT 2.08 DETECTION DEVICES 2.09 MANUAL PULL STATIONS 2.10 ANNUNCIATION DEVICES PRODUCTS MODIFIED PER SUBMITTAL REVIEW 2.11 ELECTROMAGNETIC DOOR HOLDERS 2.12 ADDRESSABLE ACCESSORIES 2.13 CONTROLLED DEVICES mit Submittal Review ` `""PAE June 20, 2018 Rebecca Grant DOWA IBI Group 907 SW Stark Street Portland, Oregon 97205 Project: TTSD Templeton Elementary Project Number: 16-1920 Dear Rebecca: Fire Alarm submittal number 283000-004 data received June 12, 2018 has been reviewed by this office with the following disposition: Item Manufacturer Action 283000 Fire Detection and Alarm Control Panel Silent Knight No Exceptions Taken Remote Test Station System Sensor No Exceptions Taken Batteries Simplex No Exceptions Taken Fire Alarm Document Enclosure Space Age Electronics No Exceptions Taken Amplifier Silent Knight No Exceptions Taken Fire Alarm Communicator DSC No Exceptions Taken Remote Annunciator Silent Knight No Exceptions Taken 1. Annunciator to be flush mount as indicated on sheet E3.10. Smoke Sensor Silent Knight No Exceptions Taken Heat Sensor Silent Knight No Exceptions Taken Air Duct Smoke Detector Silent Knight No Exceptions Taken Pull Station Silent Knight No Exceptions Taken Horn Strobes System Sensor Amend and Resubmit 1. No Horn Strobes accepted for this project. School will be a Voice Evacuation Sytem 2. Wall Strobes are to be of type SRL as called out in SPEC 283000 2.10(E). 3. Ceiling Strobes are to be of type SCRL as called out in SPEC 283000 2.10(E) June 20, 2018 .«sem Speaker Strobes System Sensor Amend and Resubmit 1. Wall Strobes to be SPSWL-CLR-ALERT as called out in SPEC 283000 2.10(E) 2. Ceiling Strobes to be SPSCWL-CLR-ALERT as called out in SPEC 283000 2.10(E) 3. Outdoor Notification Device shall be speaker strobe. Please submit documentation for review. Electromagnetic Fire Door Holders GE No Exceptions Taken Monitor Module Silent Knight No Exceptions Taken Relay Module Silent Knight No Exceptions Taken The above submittal data has been reviewed only for conformance with the design concept and for compliance with information given in the Contract Documents, and this review does not extend to means, methods, techniques, sequence of construction, dimensions, quantities, or safety precautions thereto. Review does not relieve the Contractor from responsibility for variations from the requirements of the Contract Documents. Sincerely, . Michael Lopez MRL/kes gid,. 2 SILENT IntelliKnight° Model 5820XL-EVS 101 KNIGHT Addressable Fire Alarm Control Panel with Emergency Voice System by Honeywell The IntelliKnight System is the easy way to make the most of fire alarm technology. IntelliKnight 5820XL-EVS offers an Emergency Voice System integrated with the fire alarm functions of the control panel. The 5820XL-EVS offers built-in digital communication, distributed intelligent power, a modular design and an expanded, easy to use interface. Powerful features such as drift compensation and maintenance alert are delivered in this powerful FACP from Silent Knight. For more information about the 5820XL-EVS system, or to locate your nearest source, please call 800-328-0103. Description 5820XL-EVS is an intelligent addressable fire alarm control panel combined with an Emergency Voice System (EVS). When the EVS features are enabled, they are integrated with the fire alarm and voice evacuation functions of the control •• panel. The 5820XL-EVS panel and accessories provide .r features to meet the requirements for Mass Notificationmak XIII 01111 Systems as described in UL 2572. �:NM : _ -1 The basic 5820XL-EVS system can be expanded by adding _ - 0.0,— =I ■", modules such as 5860 remote annunciator, 5815XL signalling line circuit expander, 5824 serial/parallel printer interface module (for printing system reports), and 5895XL intelligent *f 4.11$40,011 aaa0 aa> power module. 5820XL-EVS supports SD or SK devices. Features • Built in support for 99 SK detectors and 99 SK modules, Model 5820XL-EVS expandable to 396 SK detectors and 396 SK modules using • Programmable date setting for Daylight System Sensor protocol Saving Time • Built-in support for 127 SD devices, expandable to 508 SD • Two built-in Form C programmable relays devices using the SD protocol rated at 2.5 amps at 27.4 VDC • Support of up to four EVS-50W, EVS-100W or EVS-125W • 6 amp power supply and maximum charging amplifiers for a maximum of 500 watts capacity of 35 amp hours (An additional • Each amplifier has four built-in speaker circuits expandable cabinet enclosure is required for batteries in to eight excess of 18 amp hours) • 15 Recordable one minute messages that can be mapped to • Improvements in SKSS software deliver five eight EVS buttons times faster uploads/downloads • Can select EVS message as priority over fire • 16 built-in speaker group switches • Support of up to four EVS-RCU's. The EVS-RCU meets the expandable to 32 requirements for a LOC • Built-in RS-232 and USB interface for • Six FlexputTM I/O circuits programming via PC • Central station reporting by point or by zone Compatibility • Built-in synchronization for appliances from AMSECO®, Gentex®, Faraday, System Sensor, and Wheelock® The 5820XL-EVS is compatible with the • Supports Class B (Style 4) and Class A(Style 6) configu- following EVS components: ration for SLC, SBUS, and Flexput circuits • EVS-50W - 50 watt amplifier • 13 pre-programmed output cadences (including ANSI-3.41) • EVS-125W - 125 watt amplifier and 4 programmable outputs • EVS-100W - 50/100 watt amplifier • Built-in annunciator with 80-character LCD display • EVS-100WBU - External backup amplifier • RS-485 bus provides communication to system accessories • EVS-INT50W- 50 watt internal amplifier • UL listed for Continuous or ANSI 520Hz speaker tones that • EVS-SW24 - 24 switch expander meet NFPA 72 Low Frequency Signal Requirements for • EVS-VCM -Voice control module Sleeping Areas when used with the EVS-INT50W or EVS- • EVS-RCU - Supervised remote control unit 100W amplifiers and compatible speakers. P/N 351562 Rev G ©2016 Honeywell International Inc. ParVe TIit SH-Menton SK Net Input Papeete Smoke. Detector . ;:,1 Al ' 2 I i I 1 2''B Nottecetion %mato Pettey Isolator 7ntertace Module Module Modote Modals EVS,ACU EVS.125W SBUS 582DXL EVS M°dU* skPnll'©n . k I, aeo w. $yv PrAl Slxiion I I t. ! I I I c " ,a y e:) k rte....:, vaus +. 1 I ` ,,,„ '.. mf;✓ 7- $c.Photo SK ton Ste Heat CO Smoke Sconce, Relay (sago(51,/3 Det Base Base Base ttt a E SBUS 1 It nuwarn moo. 4--iA ...____1sa $era Pem $324 Gr:ix eeHavc ft�v-'e 59%81 �'582 A'+rte tsedu ,fit, Notification/Aux to 0 ._.. ;"..., ...� On �orasnP#hc: w+sCe [lr rcb oP 4 is / t.. fo." / 38413 Command input on IMonac 1---. VCM or RW 1Syste ,:. _ ktHay i uHay¢ '+ea0 59% a 4,8551 'Yac.e. L=_crEcs lxer la.ertoo,ctcr EVS 588°orInput K. i&SN5 d Sroxn; „mea e Physical Meets the requirements for NFPA 72 Local Protective Flush Mount Dimensions: Signaling Systems& Emergency Communication Systems. 20.25"W x 26.75"H x 2.5"—3"D Other Listings: (51.4 W x 68 H x 6.4-7.6 D cm) CSFM; OSHPD (CA) OSP-0065-10 Overall Dimensions: 20"W x 26.5"H x 4.6"D Compatible Devices (50.75 W x 67.3 H x 11.8 D cm) See the specification sheets listed below for a complete Color: Red listing of the SD and SK devices. Environmental 53624 SD Devices Data Sheet Operating Temperature: 32°F— 120°F (0°C—49°C) 53623 SK Devices Data Sheet Humidity: 10%—93% non-condensing Ordering Information Electrical 5820XL-EVS FACP with Emergency Voice System Primary AC: 120 VAC @ 60 Hz, 2.5A EVS Accessories Total Accessory Load: 6A© 27.4 VC power-limited EVS-50W 50 Watt Amplifier Standby Current: 275 mA EVS-125W 125 Watt Amplifier Alarm Current: 440 mA EVS-100W 50/100 Watt Amplifier Battery Charging Capacity: 7 to 35 AH EVS-100WBU External Backup Amplifier Battery Size: 18 AH max. allowed in control panel cabinet. EVS-INT5OW 50 Watt Internal Amplifier Larger capacity batteries can be housed in RBB accessory EVS-CE4 4 Circuit Audio Expander cabinet EVS-SW24 24 Switch Expander Six Conductor Wiring:Two voice bus &four SBUS EVS-VCM Voice Control Module Listings VIP-TR Panel Trim Ring to flush mount NFPA 13, NFPA 15, NFPA16, NFPA 72: Central station; SK-SCK Seismic Compliance Kit remote Signaling; Local Protective Signaling Systems; EVS-RCU Supervised Remote Command Unit Auxiliary Protected Premises Unit; &Water Deluge releasing service. Suitable for automatic, manual,waterfow, sprinkler- supervisory(DACT non-coded)signaling services. - UL 864 and UL 2572 t SILENT This document is not intended to be used for installation purposes.We try to keep our product information up-to- KNIGHT date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information,contact Silent Knight 12 Clintonville Road, Northford, CrT 06472 Phone: (203)484-7161, Fax: (203)484-7118. For Technical Support, by Honeywell Please call 800-446-6444.www.silentknight.com. INSTALLATION AND MAINTENANCE INSTRUCTIONS f� SYSTEM IJI _' SENSOR® RTS151KEY(A) 3825 Ohio Avenue,St.Charles,Illinois 60174 Remote Test Station 1.800.SENSOR2;Fax:630.377.6495 www.systemsensor.com SPECIFICATIONS Dimensions: 4.6"H x 2.75"W x 1.8"D Weight: 0.24 Lbs. Power Requirements Power LED(Green): 14-35 VDC,12 mA maximum Alarm LED (Red): 2.8-32 VDC,12 mA maximum Alarm Response Time: 40 seconds maximum Temperature: -10°C to 60°C(14°F to 140°F) Humidity: 95%relative humidity,noncondensing Max Listing: UL,FM,CE NOTE:RTS151KEY(A)replaces RTS451KEY. FIGURE 1.RTS151KEY(A) NOTICE:This manual shall be left with the owner/user of this equipment. k 0 \ NOTE:A test coil is required only for use with D2/DNR/DH400/DH500 mod- els. For D2 models order part#DCOIL.For DH400/500 models order part#Coil. i I I ALax�t 11 GENERAL INFORMATION The System Sensor RTS151KEY(A) is an automatic fire detector accessory de- hP _ signed to test remotely located duct and beam detectors. For 4-wire detec- tors,the RTS151KEY(A) features a multi-colored LED that alternates between steady green and red. Green indicates power and that the detector board is 0 in place.Red indicates alarm.For 2-wire detectors,the LED will show red for �__ alarm. Consult the detector installation instructions for additional informa- tion. i The National Fire Protection Association has published codes,standards,and 00 NOT PAW H0195-01 FRE ALARM DEVICE recommended practices for the installation and use of this product. It is rec- _ _ ommended that the installer be familiar with these requirements,with local codes,and any special requirements of the local authority having jurisdiction. FIGURE 2:WIRING DIAGRAM FOR RTS151KEY(A)TO 04120 4-WIRE DUCT SMOKE DETECTOR: RTS151 CONTENTS 1 RTS151KEY(A) remote test station RTS451KEY(A) D4120 1 screw pack(2 mounting screws) 0 AUX OUT+ 2 Keys FIELD © ®i AUXOUT- INSTALLED OPERATION JUMPER O Test Function Insert the key and turn clockwise to the"TEST"position. (RED LED)0 ® ALARM ALARM© R TEST 119. SUP,NO Alarm Indication 0 0 R RESET © SUP,C With the key in the"TEST"position,some time will elapse(40 seconds maxi- mum) depending on the detector type, before the alarm indicating LED will (GREEN LED) turn red. _ POWER Q 'Sup.contacts cannot be used if they are wired to control panel. Reset Function H0582-21 Turn the key counterclockwise to the "RESET" position and hold. The LED FIGURE 3:WIRING DIAGRAM FOR RTS151KEY(A)TO DNR 2-WIRE DUCT should turn off.Then,turn the key back to the"NORMAL"position and re- SMOKE DETECTOR WITH REMOTE TEST CAPABLE HEAD: move.The RTS151KEY(A)is capable of resetting only certain models of detec- tors.Refer to the detector installation instructions for additional information. TEST COIL+ Wiring InstructionsRTS451/RTS451KEY TEST COIL- ® RTS151/RTS151KEY Consult the appropriate detector installation instructions for the applicable wiring diagram.The RTS151KEY(A)mounts to a single gang box(2 i/2"mini- COMM+ _ 1 mum depth),or directly to the wall or ceiling. OUT(CONV ONLY)+ In Canadian applications,the RTS151KEY(A) is intended to be located in the COMM- ® pa same room as the smoke detector and within 60 feet of the unit. JUMPER RA/RTS- RA+ el 4 RTS+ ® 5 Fl T3-00 1 I56-0758-016 06-10 FIGURE 4:WIRING DIAGRAM FOR RTS151KEY(A)TO D2 2-WIRE DUCT SMOKE DETECTOR: MAGNET it 4® +TEST COIL " +TEST COIL TEST 24 VDC 24 VDC 4 SWITCH TEST COIL AUX POWER AUX POWER MAGNET —0_TEST COIL SUPPLIED SUPPLIED TEST 5® ( ) BY USER SWITCH (+).-) BY USER {100mA 4/ 5� 0+IN 2 +IN (100mA SUPPLY) (_) SUPPLY) - +OUT 2 0+OUT ALARM 24 VAC(+10%,-15%) 24 VAC(+10%,-15%) (-) LED(RED) r 1® (+) FULL WAVE RECTIFIED, UNFILTERED POWER FULL WAVE RECTIFIED, UNFILTERED POWER ALARM MAY BE USED MAY BE USED LED(RED) *„ 10 (+) -RA RA RTS151KEY(A) +RA RTS151KEY(A) (OPTIONAL) REMOTE RA (OPTIONAL) REMOTE TEST STATION TEST STATION +RTS 0+RTS D2 D2 METHOD#1 -AUX POWER LOCATED METHOD#2-AUX POWER LOCATED AT DUCT DETECTOR AT TEST STATION NOTE:THE USE OF THE RTS151KEY(A) REQUIRES THE INSTALLATION OF AN ACCESSORY COIL,DCOIL,SOLD SEPARATELY. H0612-12 FIGURE 5.WIRING DIAGRAM FOR RTS151KEY(A)TO DH100ACDC FIGURE 6.WIRING DIAGRAM FOR RTS151KEY(A)TO DH100 2-WIRE 4-WIRE DUCT SMOKE DETECTOR: DUCT SMOKE DETECTOR: DH100ACDCLP RTS151KEY(A) NOTE:Terminal 6 of the RTS151KEY(A)is not used when wired to a 2-wire detector. Alarm Signal 15 0 (Red LED)Alarm * DH100 RTS151KEY(A) Aux.Power+ 19 I O O I *Sup.contacts cannot I Test+ 1 S I be used if they are 1 Test I Sup.N.0. 14 wired to control panel. O I/ Test/Reset- O2 q I Sup.COM 0 0 (Green LED) I I Power I Reset+ 03 O Aux.Power" 20 2 O RA+ °4 - 1O LEDIarm Reset Reset O2 O 0 RA_ O O JI Test 11 0 V Out+ 0 O No Connection H0156-08 H0193-05 FIGURE 7.WIRING DIAGRAM FOR RTS151KEY(A)TO DH400ACDC DUCT FIGURE 8.WIRING DIAGRAM FOR RTS151KEY(A)TO BEAM1224/ SMOKE DETECTOR: BEAM1224T SMOKE DETECTOR: DH400ACDC RTS151KEY(A) BEAM1224/BEAM1224T RTS151KEY(A) Alarm Signal 00 (Red LED)Alarm 1 * REMOTE ALARM OUT 0 T2-1 ®(RED LED)ALARM 1 Aux.Power+ 0— *sup.contacts I I cannot be used if I AUX(—)0T2-2 _O f I Sup.N.0. 11 they are wired to I 1 control panel. I r RESET IO RESET INPUT 3O T2-4 - I Sup.COM Ci O6 (Green LED) 1 3 I Power I REMOTE TROUBLE OUTPUT O,T3-3 N O Aux.Power- O O OPTIONAL eLLcw neo TEST TEST INPUT O T2-3 O t Reset 00 0 Test O O5 NOTE:RTS151KEY(A)CAN BE USED WITH INTELLIGENT BEAM DETECTOR PRODUCTS. CONSULT INTELLIGENT BEAM DETECTOR MANUAL FOR ADDITIONAL INSTRUCTIONS H0156-09 H0585-04 THREE-YEAR LIMITED WARRANTY System Sensor warrants its enclosed product to be free from defects in materials and send detective units postage prepaid to:Honeywell,12220 Rojas Drive,Suite 700,El Paso workmanship under normal use and service for a period of three years from date of TX 79936,USA. Please include a note describing the malfunction and suspected cause manufacture.System Sensor makes no other express warranty for the enclosed product. of failure.The Company shall not be obligated to replace units which are found to be No agent, representative, dealer, or employee of the Company has the authority to in- defective because of damage,unreasonable use,modifications, or alterations occurring crease or alter the obligations or limitations of this Warranty.The Company's obligation after the date of manufacture.In no case shall the Company be liable for any consequen- of this Warranty shall be limited to the replacement of any part of the product which is tial or incidental damages for breach of this or any other Warranty,expressed or implied found to be defective in materials or workmanship under normal use and service during whatsoever,even if the loss or damage is caused by the Company's negligence or fault. the three year period commencing with the date of manufacture.After phoning System Some states do not allow the exclusion or limitation of incidental or consequential dam- Sensor's toll free number 800-SENSOR2 (736-7672)for a Return Authorization number, ages,so the above limitation or exclusion may not apply to you.This Warranty gives you specific legal rights,and you may also have other rights which vary from state to state. 2 I56-0758-016 ©2016 System Sensor.06-10 ®SimplEx Fire Alarm Control Panel Accessories Listings* System Batteries, Sealed Lead-Acid; with Applications Reference for Battery Cabinets, and Battery Cabinets with Charger Features Rechargeable,sealed lead-acid batteries: • Lead-calcium grid structure with immobilized electrolyte in absorbent separator —1: rer • Low maintenance with no need to add water • Low self-discharge characteristics 'x. • One-piece,high impact polystyrene cell cover with high 5' ; reliability dual seal construction • UL 924 recognized pressure relief valves << Available in a variety of capacities: • Batteries for internal mounting range from 6.2 Ah up to 50 Ah,depending on control panel cabinet size • Larger batteries,up to 110 Ah,mount in external battery cabinets with models available with internal chargers . . ... .. Battery cabinets with chargers: • Battery cabinets with charger communicate with their connected fire alarm control panel and are available for 4100ES/4010ES/4100U Series and 4010 Series panels Descri•tion Compatible Sealed Lead-Acid Batteries can be Installed Inside Fire Alarm Control Panel Cabinets Simplex®rechargeable sealed-lead acid batteries provide reliable and repeatable discharge and recharge characteristics for use in fire alarm and other systems ["" applications.They are designed with immobilized electrolyte in an absorbent separator,allowing them to E provide rated capacity on the first cycle. y Because of their sealed construction,packaging is allowed within the system electronics enclosure(see illustration on page 2).When this is applicable,the quantity of system cabinets and the battery wiring distances are both minimized.Where required,external battery cabinets can Remote Battery Cabinets are Available for be close-nippled to the control panel to house larger Larger Battery Requirements batteries with battery chargers available in some battery cabinet sizes. Batter Details (Continued) Batte Details Shipping. Sealed lead-acid batteries are shipped via ground or sea transportation only.They are not shipped Charging.These batteries are intended to be used with compatible Simplex battery chargers. via air. Series Connections.These batteries are required to be Disposal.Battery chemicals and materials can be recycled.Refer to information shipped with the battery or connected in series to produce 24 V system voltage. Battery sets must be of identical voltage,model number, on its case.Return to the battery manufacturer or to a appearance,and approximately the same date of similarly qualified battery processing facility for proper manufacture for proper operation. disposal. Testing.Battery capacity testing is recommended to be Seismic Activity Applications.Battery brackets are available for systems tested for compliance with specific performed by using a sealed lead-acid battery tester designed to withdraw a minimum of battery charge.The batteries.Please refer to data sheet 52081-0019 for preferred tester applies a variety of amplitude and details. duration controlled test pulses that compares terminal * Refer to details on page 4 and to the referenced individual product data sheets for agency voltage against those predicted for the specific battery listing status of battery cabinets and chargers.The batteries detailed in this document size.(Testing is available through your local Simplex meet the requirements of UL,ULC,and Factory Mutual for use with respective equipment battery chargers as listed on page 3.Contact your local Simplex product supplier for product supplier.) proper battery selection per system requirements.Listings and approvals under Simplex Time Recorder Co.are the property of Tyco Fire Protection Products. S2081-0006-22 10/2016 Batte Construction Reference Actual appearance will vary with battery size. Sealed outer cover Quick connect or post type terminal Vent hole (type varies with battery size)�/ Potting material,black for negative,red for positive IO IO (polarity is also clearly �sJ� marked with+and-) -4. - AINIA Pressure relief valve Inner cover ,,.._,.... . ...„. rc-Bi- !It Absorbent separator used to immobilize electrolyte lapp ISemi-permeable Lead-calcium grids / membrane separator Cell group /• Cell case(high impact polystyrene) Batte Size S•ecifications Capacity @ 20 Hour Height with Approximate Battery Model Width* Depth* Discharge Rate Terminals Weight* 2081-9272 6.2 Ah 6-1/8"(156 mm) 2-5/8"(67 mm) 4"(102 mm) 5.75 lbs(2.6 kg) 2081-9274 10 Ah 6"(153 mm) 4-1/16"(103 mm) 4"(102 mm) 9.2 lbs(4.2 kg) 2081-9288 12.7 Ah 6"(153 mm) 4"(102 mm) 4"(102 mm) 9 lbs(4.1 kg) 2081-9275 18 Ah 7-1/4"(184 mm) 3-3/8"(86 mm) 6-5/8"(168 mm) 14.3 lbs(6.5 kg) 2081-9287 25 Ah 6-5/8"(168 mm) 5"(127 mm) 7"(178 mm) 19.4 lbs(8.8 kg) 2081-9271 (rectangular case, 33 Ah 12-1/2"(318 mm) 3-3/8"(86 mm) 7-1/16"(179 mm) 26.6 lbs(12.1 kg) typically for service) 2081-9276 ("square"case, 33 Ah 7-3/4"(197 mm) 5-1/4"(133 mm) 6-3/4"(171 mm) 26.5 lbs(12 kg) use for new) 2081-9296 50 Ah 9"(229 mm) 5-1/2"(140 mm) 8-7/8"(225 mm) 41.8 lbs(19 kg) 2081-9279 110 Ah 11-3/16"(284 mm) 10-1/2"(267 mm) 9"(230 mm) 82 Lbs(37 kg) * Dimensions and weight are per battery and are for reference only. Exact size may vary. Refer to the tables on page 3 for mounting compatibility.These batteries are 12 V each and series connected for 24 V system use. NOTE: When wired in series for 24 V output,these batteries are to be of identical voltage,appearance, model number,and approximately the same date of manufacture. General Batte S•ecifications Nominal Voltage Rating 12 Volts per battery Discharge Rating 20 Hour Rate Typical Charge/Discharge Cycles 100 to 150 Preferred Charge Temperature Range 60° F to 90° F(15.6°C to 32.2°C) 2 S2081-0006-22 10/2016 Battery Compatibility for Fire Alarm Control Panel Mounting NOTE: Refer to individual fire alarm control panel product data sheets for additional battery application information Simplex Control Panel Model Series(see legend and notes below) Battery Capacity Model 4007ES& 4006& 4009 4010 4010ES 4100ES/ 4100&4120 4003EC 4004R 4005 4008 (all models) 4100U (2,4 or 6-Unit) 2081-9272 6.2 Ah I I I I I I I I I 2081-9274 10 Ah I 1 ✓ 1 1 1 1 1 ✓ 2081-9288 12.7 Ah I I ✓ I I I I J I 2081-9275 18 Ah Ext Note 3 ✓ Ext Ext Note 2 1 1 1 2081-9287 25 Ah Ext Note 3 Ext Ext NA I I I I 2081-9271 33 Ah Ext Note 3 Ext NA NA Note 3 1 1 Ext rectangular 2081-9276 33 Ah Ext Note 3 NA NA NA Note 3 1 1 1 "square" 2081-9296 50 Ah NA Note 3 NA NA NA Note 3 Note 6 2 or 3 bay Ext 2081-9279 110 Ah Requires external battery cabinet,compatible with 4100ES,4010ES,4100,and 4120 Series only I =Can be placed in the respective equipment cabinet Ext=External battery cabinet is required, refer to selection chart on page 4 NA=Not applicable/not compatible NOTES: 1. These batteries meet the requirements of UL, ULC, and Factory Mutual for use with respective equipment battery chargers listed above. Contact your local Simplex product supplier for proper battery selection per system requirements. 2. 4010 Cabinets will accommodate 2081-9275, 18 Ah batteries, but will not allow bottom entry conduit. 3. Use 4081 series companion cabinet and charger, refer to page 4. 4. Some control panel models are listed for battery replacement reference only. 5. For 2 bay international applications only, 50 Ah batteries will fit in the cabinet. External Batte Cabinet Corn•atibili Reference Battery Cabinets without Chargers (connects to charger in panel) Battery Cabinet Panel Compatibility 2081-9275 2081-9287 2081-9271 2081-9276 2081-9296 2081-9279 18 Ah* 25 Ah Rectangular 33 Ah Square 33 Ah 50 Ah 110 Ah 2081-9280 4100ES,4010ES, NA NA NA NA NA 1 41000, and 4100+ 2081-9281 multiple ✓ 1 1 ✓ 1 NA 2081-9282 4009-9801 multiple ✓ ✓** NA NA NA NA 4009-9802 multiple ✓ NA J NA NA NA Battery Cabinets with Chargers 2081-9275 2081-9287 2081-9271 2081-9276 2081-9296 2081-9279 Cabinet Panel Compatibility 18 Ah* 25 Ah Rectangular 33 Ah Square 33 Ah 50 Ah 110 Ah 4081-9301 4004R and 4010 I I J 1 ✓ NA 4081-9302 4081-9306 4100ES,4010ES, NA NA NA NA I I 4081-9308 and 4100U *Batteries smaller than those listed are normally mounted in the product cabinet **25 Ah capacity was effective as of 7/2005. ✓=Can be placed in the respective equipment cabinet NA= Not applicable/not compatible 3 S2081-0006-22 10/2016 External Batte Cabinet S•ecification Reference Battery Cabinets Without Chargers; Shallow Design with Front Door Model Color Listings Description Dimensions 2081-9281 Beige UL and 2-Unit,4100 style cabinet without charger;with locking 25-3/4"W x 20-3/4" H x 6-3/4"D FM solid door and battery shelf,primarily for use with 50 Ah 2081-9282 Red batteries (654 mm x 527 mm x 171 mm) 4003-9860 Beige Multiple Intended for use with 4003EC systems,for up to 33 Ah 9-1/2"H x 24"W x 9"D batteries(refer to 4003EC data sheet S4003-0002) (241 mm x 610 mm x 229 mm) 4009-9801` Beige UL and For up to 25 Ah External battery cabinet without charger, 16-1/4"W x 13-1/2"H x 5-3/4"D FM batteries* with locking solid door and battery (413 mm x 343 mm x 146 mm)* For up to 33 Ah harness;for close-nippled mounting to 25-3/4"W x 20-3/4"H x 4-1/8"D 4009-9802 Beige UL batteries fire alarm control panel cabinet (654 mm x 527 mm x 105 mm) *Depth increased for 25 Ah batteries effective 7/2005. Chargers for use with 4010 Fire Alarm Control Panels and 4004R Suppression Release Systems (refer to data sheet S4081-0001) Model Color Input Voltage Description Dimensions 4081 9301 Beige Battery cabinet with charger for the 4010 and 4004R fire alarm control panel;for up to 50 Ah 120 VAC batteries;with front door 22-1/2"W x16-3/4"H x 8-3/8"D 4081-9302 Red Listings include:UL, ULC, FM, CSFM, and MEA (572 mm x 425 mm x 213 mm) (NYC), see data sheet for details Battery Cabinet Without Charger for 110 Ah Batteries; for use with compatible panel mounted chargers (refer to data sheet S2081-0012) Model& Color Cabinet Description Compatible Charger Description Dimensions Listings Chargers 4010-9xxx 4010ES Main System Supply Series (MSS) 4100-9xxx 4100ES/4100U System Power Series Supplies(SPS) Battery cabinet for 4100-5111 2081-9279, 110 Ah 4100-5112 4100ES/41000 Additional SPS 2081-9280 batteries; includes 4100-5113 Listings Red 80 A battery fuse, 4100-5125 26-1/2"W x 12" H x 12"D include:UL terminals and 4100-5126 4100ES/41000 Remote Power (673 mm x 305 mm x 305 mm) and CSFM battery connection 4100-5127 Supply(RPS) cables;see data 4100-5120 sheet for details 4100-5121 4100ES/4100U TrueAlert 4100-5122 Addressable Power Supply(TPS) 4100-0104 4100-0114 4100 Legacy power supplies 4100-0124 4100ES/4010ES/41000 Compatible Battery Cabinet With Charger for 110 Ah Batteries (for ULC listed systems and for other applications unable to use panel mounted power supply charger; refer to data sheet S4081-0002) Model Color Input Voltage Description Dimensions Battery cabinet with charger for up to 110 Ah 4081-9306 Red 120 VAC batteries; NOTE: Required for ULC listed charging of 27-7/8"W x 13-1/2"H x 14-5/8"D 220/230/240 VAC, 110 Ah batteries;Listings include:UL, ULC, FM, (708 mm x 343 mm x 371 mm) 4081-9308 Red multi-tapped CSFM,and MEA (NYC), see data sheet for details 4100-9837 Green LED Power-on Indicator Kit, required for ULC listing,mounts above access panel using knockout provided TYCO,SIMPLEX and the product names listed in this material are marks and/or registered marks.Unauthorized use is strictly prohibited. aSi m p I EX Tyco Fire Protection Products• Westminster, MA•01441-0001•USA S2081-0006-22 10/2016 www.simplex-fire.com 2014 Tyco Fire Protection Products.All rights reserved.All specifications and other information shown were current as ofdocument revision date and are subject to change without notice. t5\ ,, • tibt SIGNALING U` r �`t LISTED ACE-11 "H FIRE ALARM DOCUMENTS The FAD is the perfect fit to meet the demanding code requirements today. SAE's number one goal is FIRE ALARM DOCUMENTS to manufacture code compliant solutions and this Records / Programs 1 Software product allows you to do just that. NFPA 72 2007 section 6.2.2.1 states, "A record of installed software and firmware version numbers shall be maintained at the location of the fire alarm control unit." This durable 16 gauge steel enclosure with a solid piano hinge and key lock will keep all of your code required documents in one safe place. With a 4GB USB flash drive it stores your fire alarm software safe and secure eliminating the occurrences of the soft- ware not being on site when technicians arrive to service the system. Along with your fire alarm soft- Standard Features: ware you can store your test & inspection docu- ments, service records, manuals &AS built drawings • Installed with a 4 gig digital flash drive for the system. Using a standard USB B connector it with USB B connector allows you to plug in with any standard SB printer • 2 Key ring hooks to hold system keys cable to upload or download information. • Business card holder for key contacts • Overall Dimensions are 12" x 13" tall and 2 '/4 deep The FDB is designed to hold critical manuals and • 16 gauge steel box and cover for security documents with a durable steel retainer. It has • Durable powercoat baked on finish designated hooks to organize key rings and hold other colors available important business cards for easy access and • Standard%"cat 30 key lock other lock as- reference. Inside the cover it has a organized note semblies available table that allows for documentation for passwords • Solid stainless steel piano hinge and other critical system information. • Permanently screened white ink 1" high "Fire Alarm Documents" • Legend sheet for passwords and system information BOX ISO 9001 Space Age Electronics, Inc. FIRE �1��A® �� REGISTEREIJ www.tsae.com NFPA COMPANY 800.486.1723 Toll Free MEMBER Made In \U.S.A. 508.485.0966 Local 508.485.4740 Fax Space Age Electronics, Inc. 2009 No Excuses, Just Solutions! ED0549 LT10559 Rev.D 1/2 SPACE AGE ELECTRONICS, INC. Specifications: The fire alarm documents box (FAD) shall be UL Listed, constructed of 18 gauge cold rolled steel. It shall have a red powder coat epoxy finish. The cover shall be permanently screened with 1" high lettering "FIRE ALARM DOCUMENTS " with white indelible ink. The access door shall be locked with a 3/4" barrel lock and the hinge shall be a solid width 12" stainless steel piano hinge. The enclosure will supply 4 mounting holes. Inside the enclosure will accommodate standard 8 1/2 x 11 manuals and loose document records that will be protected within the enclosure. A legend sheet will be permanently attached to the door for system required documentation, key contacts and system information. The FAD will have securely mounted inside a minimum of 4 Gigabyte digital flash memory drive with a standard USB B connector for uploading and downloading information. The drive shall not be accessible without tools to any person whom gains access to the records. The enclosure shall also provide 2 key ring holders with a location to mount standard business type cards for key contact personnel. USB Storage Interface % 3 Requires Standard USB-B Connector ii P par1Y Informationtion Mn R q Doto ntaGaxn 4 51 G-FL/N)Key Ring Hooks • s'' S.'�'•';tl °' ' C rtfl t dApp I �a.a w 5 ' 19 1 SY t t II t C to t u ,o®.un NA a Enc.,.Or PH Lxsacia na Business Card Holder 95 A to tYH ad« nuaaarcarace wit ts ads TO 4.34,r&u a,A M Vcalage rain.ernal /1% ; ' T ea,A acp %j�jX� K A�' Eqo peeent lnformanon , Sara = Dale t ..+" we q ^eve, a 56 CI 44en Roan 6441 p 4441 64 aoea6174 .w+ LT 0644 Re,.1 Legend sheet for storing system information including contacts,sign-off maintenance & test information,and alternate locations of additional records. Ordering Information: Part # Description SSU00685 Fire Alarmr 9 Sto a e Cabinet RED BOX Space Age Electronics, Inc. SSU00686 Custom screening with your Logo www.lsae.com 800.486.1723 Toll Free Check out our Infinity line eFAD single gang 2 Gig digital storage 508.485.0966 Local solutions (IAMEFAD) 508.485.4740 Fax This document is subject to change without notice,see doc#ED0479 for legal disclaimer No Excuses, Just Solutions! ED0549 LT10559 Rev.D 2/2 SILENT KNIGHT IntelliKnight® Model EVS-100W Intelligent 50/100 Watt Amplifier with by Honeywell optional Backup Amplifier The EVS-100W is an intelligent 50/100 watt amplifier for use with Version 14.0 or newer 5820XL-EVS. The EVS- 100W is used to amplify audio message for distribution throughout a facility. The EVS-100W is capable of producing up to 100 watts of audio power and has the ability to provide an option for 50 watts of backup power. For more information about the EVS-100W, or to locate your nearest source, please call 800-328-0103. Description , The EVS-100W has its own power supply with battery backup and eight speaker circuits. The EVS-100W is fully supervised by the main panel for trouble conditions. Features • Amplifier Configurations: • 50 watts with 50 watts as backup. • 100 watt single channel. • 100 watt single channel with 50 watts backup using EVS-100WBU. • Built in backup amplifier test feature allows you to physically test that the backup amplifier is operating properly. E S-InllW • Up to four amplifiers per 5820XL-EVS distributed between up to 32 audio circuits. • Six-wire connection to EVS system: Two-wires for the voice Model EVS-100W bus and four-wires for the SBUS connections. • Amplifier Bandwidth 400 Hz to 4000 Hz. Installation The EVS-100W can be surface or flush • Can be mounted up to 6000 feet away from 5820XL-EVS mounted. control panel. • 120 VAC or 240 VAC operation. Compatibility • UL 864 and UL 2572 The EVS-100W is compatible with the • UL listed for Continuous or ANSI 520Hz speaker tones that following voice evacuation components: meet NFPA 72 Low Frequency Signal Requirements for Sleeping Areas. See the 5820XL-EVS installation manual • Version 14.0 or newer 5820XL-EVS Voice LS10061-001SK-E for a list of compatible speakers. Integration Panel with Fire Alarm Control P/N 350961 Rev C Copyright©2016 Honeywell International Inc. SK-Msmmon SK-°uct Input Module Smoke Detector .}k ` Z .1 A.1:7'.., • Rf Cf t t t '- 2 Mrs Notlff cation Ilonilor Relay Isolator Intotace Module Modu0 Modue Module EVS.RCU EVS-100W SBU$ 552OXL-EVS Module SK-Pull-0A Addressahie 'Pull Stollen Loop "a;>..i \.,:: °4e YBVS SKPhoto SK SK Heat CO Smoke Sounder Relay Psutator i< = Det Bass Base Base ; — SBUS NO 1010 5821 karoct•Anrra+`O So IParalld Pmx 4 k,leffaGe McSa"9 4 9800XL Notification/Aux F int.s,501.,,,y4.1.40te rt -- — — R, Ftexrs P 4'— E j Cs-venuonal SWItc ec P 1 1•— Bab Stinnes her^y and NACo yrpke Ge[ec'Or r SW..., .,l✓ S Cser'o'm•rpV,t on rnc.;ucu i a VCM or HAM ,sxm . t fl 5883 !'Soy.,,are 3880 S8ti5-1[r 6305. ktawee r.srei:->erool LED,rnuncp to, S:.t:e'.7 niut t:drle (La:,,,Shtr r Or moot Specifications • Circuit 5-8: 50 W max. Physical Main EVS Panel SBUS Standby&Alarm: 10 mA Flush Mount Dimensions: Battery Charging Capacity: 7—35 AH 14.5"W x 24.75"H x 3.4"D (36.8 W x 62.9 H x 8.7 D cm) Battery Size: 18 AH max allowed in cabinet. Use RBB accessory cabinet for larger batteries up to 35 AH per Overall Dimensions: system. 16.1"W x 261/2"H x 4 1/8"D (40.6 W x 66.7 H x 10.5 D cm) Voice Integration Wiring: Six conductor Color: Red Two voice bus Four SBUS Environmental Operating Temperature: 32°F— 120°F (0°C—49°C) Listings NFPA 13, NFPA 70, NFPA 72, UL 2572, UL 1711 & UL 864 & Humidity: 10%—93% non-condensing UL2572 Electrical CSFM (pending); MEA(pending) Primary AC: 120 VAC @ 60 Hz; 240 VAC @ 50 Hz Standby Current: Ordering Information EVS 100W 25V 110 mA EVS-100W Intelligent 50/100 Watt Amplifier EVS-100W 70.7V 110 mA Accessories Alarm Current: EVS-100WBU External Backup Amplifier EVS-100W 25V, 1.2 A RBB Remote Battery Box Accessory Cabinet. EVS 100W 70.7V, 1.4 A Use for backup batteries up to 35 AH. Total Power: 100 W @ 25 VRMS or 70.7 VRMS • Circuit 1-4: 50 W max. SILENT This document is not intended to be used for installation purposes.We try to keep our product information up- to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications KNIGHT are subject to change without notice. For more information,contact Silent Knight 12 Clintonville Road, Northford, CT 06472 Phone: (203)484-7161, Fax: (203)484-7118. For Technical Support, Please call 800-446-6444.www.silentknight.com. by Honeywell 0 0 G 9I LTE Universal Wireless CommercialFire Alarm 7.,,,,, Tii,,,,,,, , ,, lame_ ,, , LE4010CF Features That Make a Difference: • Uses LTE network for high- speed, reliable and low-cost communications to an IP Ensure your installations are receiver Automatically switches to 3G future-ready, with LTE • (HSPA/HSPA+) if LTE service is Due to rapidly-evolving cellular or 1 hour(NFPA72 2013/2016) not available technologies, 2G/3G network sunsets of the failure, or it can be used as are already on the horizon—with part of a multiple communications • Compatible with control panels some having already been completed. technologies(for example in that communicate using Contact Now's the time to adopt and adapt. conjunction with a DACT). When ID or SIA(300 baud)formats Switch to LTE today,to offer used as a back-up provision shall • Full event reporting customers long-lasting investment be made to monitor the integrity of 4 on board inputs with NC, NO protection, and reduce your future each communication path and failure • truck rolls. of any communications path shall or SEOL supervision be annunciated at the supervising • 4 on-board outputs(open The LE4010CF connects the alarm station and at the protected premises collector) control panel to the Cellular network within not more than 24 hours of the and reports alarm signals directly to failure. • Activation and initialization a monitoring station receiver via website or mobile (Sur-Gard System I-IP/ll/IIVIV/5).The How it Works interface provided by C24 LE4010CF uses the Cellular network Communications to ensure low-cost, high-speed and The LE4010CF can be used as • View communicator statusreliable alarm communications and is either a Sole Communicator or as a directly from your mobile phone compatible with control panels that Backup Communicator.When being communicate using the Contact ID or used as a Sole Communicator the to support on-site or remote SIA(300 baud)format. LE4010CF will replace the phone troubleshooting line connection on the panel and • Compatible with Sur-Gard® The LE4010CF is compliant as soon as it detects that an alarm System l-IP/II/Ill/lV/5 monitoring with the latest requirements for needs to be transmitted it will send station receivers Communications Methods as per the alarm across the Cellular network UL864 and NFPA72 2010, 2013, immediately.When being used as a • Includes UL listed power and 2016 editions. It can be used backup the communicator assesses supply, transformer and 7 Ah in Fire Monitoring applications as a the connection to the PSTN phone rechargeable battery single communications technology, line, and only in the event of a phone • UL 864 listed in which case any failure of the line failure will it send all alarm traffic communications path shall be across the Cellular network to the • CSFM listed annunciated at the supervising station monitoring station. within 5 minutes(NFPA72 2010) contact your DSC distdtor ww r;ds .ccrr 1 1-888" 8 -7 3 Dap From Tyco Security Products In instances where the control panel does not support CSFM Listing Contact ID or SIA(300 baud),the LE4010CF has inputs pre The LE4010CF has been approved by the California State Fire set to transmit fire alarm,fire supervisory or system trouble. Marshal(CSFM)pursuant to Section 13144.1 of the California Alarm signals are transmitted directly without the need of Health and Safety Code. a clearinghouse to the IP linecard of the monitoring station receiver(Sur-Gar&System I-IP/II/III/IV/5). Ordering Information: Activating & Initializing the Unit LE4010CF AT Universal Wireless Commercial Fire Alarm Communicator Activating and initializing the LE4010CF can be done using the website interface provided by C24 Communications. Rate Plan No special tools are required. Cost-effective rate plans have been negotiated and are Mobile Site for Easy Installation and available through authorized master resellers. Contact your Comprehensive Maintenance monitoring station or visit www.connect24.com to find a master reseller. When used as a sole communicator,the C24 Communications mobile site(m.connect24.com) LE4010CF requires use of the 4MB(NFPA72 2010)or 500kB makes the installation a simple process and offers intuitive (NFPA72 2013/2016) rate plans to support the supervision trouble-shooting features, cutting down on time and cost requirements. allocated to maintenance. Specifications Dimensions 11-1/2"x 10"x 3" (290 mm x 254 mm x 75 mm) .. Input Voltage 120 VAC all „„., t Current Draw 200 mA(standby) 400 mA(transmitting) . a 11111111M1111111111111111\ �� Operating Environment 32°to 120° F(0°to 49°C) Weight 12.8 lbs(5.8 kg) UL Listing Optional Acessories The LE4010CF is UL listed under File S4019, Listing guide UOXX, as a sole or backup communicator for Commercial Fire Model Description monitoring installations.When used as a sole communicator LTE-15ANT 15 ft extension antenna under NFPA72 2010 guidelines the LE4010CF will send its heartbeat once every 97 seconds ensuring that three LTE-25ANT 25 ft extension antenna heartbeats will be received at the supervising station within LTE-50ANT 50 ft extension antenna the 300 second window.When used as a sole communicator under NFPA72 2013/2016 guidelines the LE4010CF will send its heartbeat once every 5 minutes to monitor connectivity with the supervising station within the 1 hour window.When used as a backup communicator the LE4010CF will monitor the other communication method (DACT)and send a daily test transmission to the supervising station. oQN V m 1 r 'r" ✓ S,, \ - f - yyr �� ate$ &ad Honervell rs SILENT Sia KNIGHT 5860 Remote Annunciator The 5860 remote annunciator,can be used to operate and program Honeywell Silent Knight fire alarm control panels(FACPs)from anywhere -.. • within the system. I The 5860 features include an 80-character backlit LCD providing easy-to ,,. understand system messages.The annunciator is ergonomically designed with over-sized buttons for the most frequently used features,like Reset and Silence. In addition to status messages displayed on the LCD,there are five LEDs for alarm,supervisory,trouble,silence,and AC power status. The 5860 annunciator is available in gray to match virtually any decor and 5860/5860R red for applications where the annunciator must stand out.The annunciator enclosure can be surface or flush mounted.A trim ring kit is available for surface mounting. COMPATIBILITY The 5860 is compatible with the following Honeywell Silent Knight FACPs: 6820:Addressable fire alarm control panel with up to 1,110 addressable points 6820EVS:Addressable fire alarm control panel with an emergency communication systems and up to 1,110 addressable points 6808:Addressable fire alarm control panelwith up to 198 addressable points 6700:Addressable fire alarm control panel with up to 100 addressable points 5820XL:Addressable fire alarm control panel 5820XL-EVS:Addressable fire alarm control panel with an emergency communication systems 5808:Addressable fire alarm control panel 5700:Addressable fire alarm control panel • 80-character backlit • Support for • Five Status LEDs • Accommodates wiring • Accepts user codes or LCD display;4 lines simultaneous use oflengths up to 6000 ft, fire fighter's key • Available in red or light with 20 characters per multiple 5860s from the control panel . keypad buttonsgray color Largeryl for added design and Easily view current 'ine) makes it easier to install fl.exit>i="tY maneuver for system • ..lac�ti€e!a:�d<b'e status by alarms, feedback when a key is supervisor es,or reset and silencing pressed on the troubles annunciator • Uses the RS-485 SBUS to interface with the panel 5860 Technical Specifications For a complete listing of all compliance approvals and certifications,please visit www.sitentknight.com. Microsoft,Windows,and the Windows Logo are registered trademarks or trademarks of Microsoft Corporation. Wire Runs Up to 6000 Feet From FACP Silent Knight"and • Honeywell'are registered trademarks of Isko •-"4111• IWO.. International.Incney ell SBUS AN — { ra 1E g This document is not '' •• € intended to be used for 6860 0860 6860 installation purposes.We try to keep our product *Up to Eight 5860s Per 5700 or 6700 System information up-to •Up to 12 5860s Per 5808,8808,5820XL,or 5820XL-EVS System date and accurate.We Up to 16 5860.s per 6820 or 6820EVS System cannot cover all specific Compatible Silent Knight FACP applications or anticipate all requirements.All specifications are subject to change without notice. For Technical Support, 5860 Features call 800 446 6444. PHYSICAL ORDERING INFORMATION Dimensions:9.1"W x 7.4"H x 1.5"D(23.1W x 18.8H x 5860:Remote Annunciator,four line(4x20)LCD 3.8D cm) annunciator with 20 characters per line.Gray Shipping Weight:2.8 lbs(1.3 kg) 5860R:Remote Annunciator,four tine(4x20)LCD Color:5860R:Red;5860:Gray annunciator with 20 characters per line.Red ENVIRONMENTAL ACCESSORIES Operating Temperature:32°F to 120°F(0°C to 5860TR:Red Trim Ring for surface mounting 49°C) 5860TG:Gray Trim Ring for surface mounting Humidity:10°/a-93°/a non-condensing) AGENCY LISTINGS AND APPROVALS ELECTRICAL UL listed Operating Voltage:24VDC CSFM approved Standby Current:20mA Meets NFPA 72 requirements Alarm Current:25mA FM approved MEA approved For more information Learn more about Honeywell.Silent Knight and other products by visiting www.sitentknight.com Honeywell Silent Knight 12 Clintonville Road Honeywell Northford,CT 06472 Doc 3502241 RevJ 112/17 ri SILENT' 800-328-0103 ©2017 Honeywell International Inc. 56;4 KNIGH't INTELLIKNIGHT ACCESSORY 10 SILENT SK-Photo, SK-Photo-T KNIGHT and SK-PhotoR by Honeywell Intelligent Photoelectric Smoke Sensors The SK-Photo is a photoelectric smoke detector, the SK-Photo-T is a photoelectric smoke detector with thermal and SK-PhotoR is a photoelectric detector with remote test capability. These plug in smoke detectors, with integral communication, provide features that surpass conventional detectors and are for use with Silent Knight IntelliKnight Fire Alarm Control Panels (FACPs). For more information about the IntelliKnight system, or to locate your nearest source, please call 800-328-0103. 1 • Optional remote LED annunciator Description ��� �� (System Sensor®PN RA100Z 'A , / ,v SK Photo and SK Photo T are plug-in Plug-in mounting provides ease of ; ' , type smoke sensors that combine a installation z ; photoelectric sensing chamber with • Tamper-proof feature available on r addressable analog communications. mounting bases Point ID capability allows each detector's address to be set with rotary Listed for use in duct applications �� • Rotaryaddress switches for fast gg address switches, providing exact d detector locations for selective installation s maintenance when chamber • UL Listed contamination reaches unacceptable • FM Approved ,; gs levels. SK Photo and SK Photo T have a Specifications 'A 1g unique optical sensing chamber that is Physical engineered to sense smoke produced Height: 2.0" (5.0 cm) SK-Photo (Base included) by a wide range of combustion Diameter:4.1" (10.4 cm) installed in sources. In the SK-Photo-T, dual B501 base Installation electronic thermistors add 135°F (57°C) thermal technology to maximize Electrical Operating Voltage: 15-32 VDC The SK-Photo and SK-Photo-T plug detection. into a compatible IntelliKnight-series The SK-PhotoR is a remote test Standby Current: detector base.The SK-PhotoR is a capable detector for use with the 300 pA @ 24 VDC Maximum remote test capable detector head DNR/DNRW duct smoke detector. (not Alarm Current: 6.5 mA @ 24 VDC max included within the DNR(W)duct included) (with LED on) smoke detector. Environmental Compatibility Operating Temperature Features SK-Photo: 32°— 120°F (0°C—49°C) SK-Photo, and SK-Photo-T are • Sleek, low-profile design SK-Photo-T: 32°— 100°F (0°C—38°C) compatible with the following detector • Base included Humidity: 10%—93% non-condensing bases: B210LP 6" base (included) • Reliable analog communications for Other Ratings B501 2 wire base trouble-free operation SK-Photo-T Thermal: Fixed B224RB Relay base • Age resistant polymer housing temperature set point 135°F (57°C) B224B1 Isolator base • Dual electronic thermistor design on Velocity: 0—4000 fpm (0—20 m/sec) B200SR Sounder base the SK-Photo-T The SK-Photo, SK-Photo-T, and SK- • Superior EMI resistance for reliability PhotoR are compatible with the • Simple field cleaning for code following IntelliKnight FACPs: compliance 5820XL 5820XL-EVS • Variety of mounting options to meet 5808 any application 5700 • Dual LED indicators for 360°visibility 5600 (Rev 2.0 or higher) • Detector transmits signal to indicate maintenance is required Model SK-Photo, SK-Photo-T and SK-PhotoR Intelligent Photoelectric Smoke Sensors Engineering Specifications The contractor shall furnish and install where indicated on the plans, Intelligent photoelectric smoke sensors Silent Knight SK-Photo or SK-Photo-T with thermal. The combination detector head, and twist-lock base, shall be UL listed and compatible with Silent Knight's IntelliKnight fire control panels. The base shall permit direct interchange with SK-Photo or SK-Photo-T. Base shall be the appropriate twist-lock base part number B210LP (included). The PhotoR is a remote test capable detector for use with DNR(W) duct smoke detectors. (not included). The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady. The detector may be reset by actuating the control panel reset switch. The calibration of the detector shall be capable of being selected and measured by the control panel without the need for external test apparatus. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field selectable as required. The SK-Photo shall automatically perform a functional test of the detector. The test method shall simulate effects of products of combustion in the chamber to ensure testing of detector circuits. _ sic IN OUT 1 Compatible FACP 'vizi alt, i i f RA100Z(Optional) ilite- -_11"11111 ;184/1- a- '44\ 111.441":711111Alle\s\ (1-117 V-111911111111411114 I Vali ' fir 1 wig la iv .... I \\. Foy 1%."-..-\\ i1/4............./ ....... i, f .... .. . . ... ... ,.. .. .... Class A Optional Wiring Wiring SK-Series Detector Mounting Bases SILENT This document is not intended to be used for installation purposes.We try toNI it MADE IN AMERICA KNIGHT, keep our product information up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are FORM#350118 Rev E subject to change without notice. For more information,contact Silent Knight ©2013 Honeywell International Inc. by Honeywell 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800)328-0103, Fax: (203)484-7118. For Technical Support, Please call 800-446-6444. www.silentknight.com INTELLIKNIGHT ACCESSORY Itiik SILENTSK-Heat, SK-Heat-HT Iii KNIGHT and SK-Heat-ROR by Honeywell Addressable Thermal Heat and Rate-of-Rise Detectors The SK-Heat, SK-Heat-HT, and SK-Heat-ROR are plug in thermal detectors, with integral communication, that provide features that surpass conventional detectors. These thermal detectors are for use with Silent Knight IntelliKnight series Fire Alarm Control Panels (FACPs). IntelliKnight heat detectors are an essential component in virtually any IntelliKnight installation. The IntelliKnight panel recognizes each detector by its specific address, so precious seconds are not wasted in determining location of an alarm. Description visibility SK-Heat, SK-Heat-HT and SK- • Detector transmits signal to . Heat-ROR are intelligent sensors indicate maintenance is required fi that utilize astate-of-the art Plug-in mounting provides ease a�`. 4. thermistor sensing circuit for fast of installation response. Sensitivity is • Optional remote LED annunciator - continuously monitored and Sensor° PN RA100Z) reported to the FACP. Point ID capability allows each detector's • Tamper-proof feature available on address to be set with rotary mounting bases address switches, providing exact • Rotary address switches for fast SK-Heat (base included) detector locations for selective installation SK-Heat-HT: High temperature heat maintenance when chamber • UL Listed sensor 135°F - 190°F (57°C - 88°C) contamination reaches unacceptable levels. Specifications SK-Heat-ROR: Rate-of-rise p Physical detection 15°F/min (8.3°C/min) SK-Heat is a fixed temperature Y sensor that uses a thermistor Height: 2.0" (51 mm) Compatibility sensing circuit to produce 135°F Diameter: 6.1" (155 mm) installed (57°C)fixed temperature alarm. in B210LP base The SK-Heat-HT and SK-Heat- Shipping Weight: 4.8 oz (137 g) ROR are compatible with the SK-Heat-HT is a variable high following IntelliKnight FACP's: temperature detector that provides Electrical high temperature detection at Operating Voltage: 5820XL 135°F - 190°F. (57°C - 88°C) 15 to 32 Volts DC Peak 5808 5700 SK-Heat-ROR is a rate-of-rise Standby Current: temperature sensor with 135°F 300pA @ 24 VDC The SK-Heat is compatible with the (57°C)fixed temperature alarm. LED Current: 6.5 mA@ 24 VDC following IntelliKnight FACP's: Features Environmental 5820XL 5808 • Reliable analog communications Operating Temperature 5700 for trouble-free operation SK-Heat & SK-Heat-ROR: 5600 (Rev 2.0 or higher) -4°- 100°F (-20°C- 38°C) • Age resistant polymer housing The SK-Heat, SK-Heat-HT and SK- • Innovative thermistor sensing SK-Heat-HT:: -4°- 150°F Heat-ROR are compatible with the circuit (-20°C- 66°C) following detector bases: • Superior EMI resistance for Humidity: 10% -93% B210LP 6" base (included) reliability noncondensing B501 2 wire base B224B1 Isolator base • Variety of mounting options to Thermal Ratings B224RB Relay base meet any application SK-Heat: Fixed temperature alarm g200SR Sounder base • Dual LED indicators for 360° 135°F (57°C) INTELLIKNIGHT ACCESSORY Model SK-Heat, SK-Heat-HT, SK-Heat ROR Addressable Thermal and Rate-of-Rise Thermal Detectors Engineering Specifications The contractor shall furnish and install where indicated on the plans, Intelligent Thermal Sensor Silent Knight Model SK-Heat, SK-Heat-HT or SK-Heat-ROR. The base included shall be B210LP. The Heat detector shall have a flashing status LED for visual supervision. When the detector is activated, the flashing LED will latch on steady at full brilliance. The detector may be reset by actuating the control panel reset switch. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field removable when not required.Voltage and RF/transient suppression techniques shall be employed to minimize false alarm potential. `- IN OUT I Compatible FACP € ' RA'I40Z(Optional) . IIILNo 1111 iii (116,, ,I'' 11,1110\11. Ira 0 IV 111" rill 1011 V i %le ' '11." NNE OF 011111111, VilliiiiH\ PliF • I j Ar•:, ::i7-1:. „ilit\i\I Class A Optional wrong / Wiring SK-Series Detector Mounting Bases Accessories M02-09-00-Test Magnet with Telescoping Handle. RA100Z-Remote LED Annunciator. XP-4-Extension Pole for XR2B. Extends from 5—15 ft. RMK400-Recessed Mounting Kit. Provides low profile for use with T55-127-000-Detector Removal Head. 6501. XR2B-Detector Removal Tool.A removal and re-placement tool BCK-200B-Black Detector Kit. For SK-series detectors. for SK plug-in detectors. Includes the T55-127-000. *Unless otherwise noted,specifications apply to all SK thermal M02-04-01 -Replacement Test Magnet. detectors. SILENT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA illkeep our product information up-to-date and accurate.We cannot cover all �j KNIGHT specific applications or anticipate all requirements.All specifications are subject FORM#350120 Rev. D1 to change without notice. For more information,contact Silent Knight 12 ©2013 Honeywell International Inc. by Honeywell Clintonville Road Northford, CT 06472-1610 Phone: (800)328-0103, Fax: (203)484-7118. For Technical Support call 800-446-6444. www.silentknight.com - . •_. 13 SILENTSK-DUCT ,._ KNIGHT Intelligent Air Duct Smoke Detector by Honeywell Detect smoke in air handling systems and air handling equipment with Silent Knight's addressable duct smoke detector The SK-Duct Intelligent air duct smoke detector is used with SK-PhotoR (included)for detecting smoke and products of combustion present in air moving through an HVAC air handling system. When smoke is detected in a duct, the unit communicates the condition to the IntelliKnight control panel. The panel, in turn, depending on programming and wiring, turns off fans, blowers, and other devices. The duct housing allows for mounting of SK-Relay addressable relay module. Now there's even more power and flexibility available to the IntelliKnight family of products! Description , The Model SK-Duct Air Duct Smoke Detector utilizes -;' -V` photoelectric technology for the detection of smoke. It provides early detection of smoke and products of combustion present in air moving through HVAC ducts in ; Commercial and Industrial applications. , 1 The SK-Duct is in a heavy duty gray steel backbox with a clear cover. It features a pivoting housing that fits both ' square and rectangular footprints capable of mounting to a round or rectangular duct. It installs quickly and easily. SK DUCT The unit senses smoke in the most challenging conditions, operating in airflow speeds of 100 to 4000 feet per minute, Specifications temperatures of-4°F to 158°F, and a humidity range of 0 to 95 percent (non-condensing). Physical (Rectangular): 14.38 in (37 cm) Length; Features 5in (12.7 cm)Width; 2.5 in (6.6 cm) Depth (Square): 7.75 in (19.7cm) Length; • Versatile mounting options: square or rectangular gin (22.9cm)Width; 2.5 in (6.35cm) Depth configuration • New Cover tamper signal Weight: 1.6lb (0.73kg) • LED alarm indication and communication on sensor Environmental head Operating Temperature: -4°F— 158°F • Detects and limits the spread of smoke (-20°C— 70°C) • Rugged steel back box with clear plastic cover Humidity: 0% —95% (non-condensing) • Easy to clean Air Velocity • Large terminal connection screws 100 to 4000 ft/min (0.5—20.3 m/sec.) • Transparent cover for convenient visual inspection • Patented sampling tube installs from front or back of the Electrical (using SK-Photo or SK-Photon) detector with no tools required Operating Voltage: 15-32 VDC • Available space within housing to accommodate Standby Current: 300 pA @ 24 VDC max. mounting of relay module Alarm Current: 6.5 mA @ 24 VDC max • UL listed (with LED on) Model SK-DUCT Air Duct Smoke Detector Engineering Specifications The air duct smoke detector shall be a SK-Duct photoelectric duct smoke detector. The detector housing shall be UL listed per UL 268A specifically for use in air handling systems. The flexible housing of the duct smoke detector fits both square and rectangular footprints. The detector shall operate at air velocities of 100 ft/min to 4000 ft/min (0.5 m/sec to 20.32 m/sec). The unit shall be capable of providing a trouble signal in the event that the sensor cover is removed or improperly installed. It shall be capable of local testing via magnetic switch or remote testing using the RTS151KEY remote test station. Terminal connections shall be of the strip and clamp method suitable for 12-18AWG wiring. The unit housing shall be capable of mounting a relay module. Ordering Information SK-Duct Intelligent non-relay duct smoke detector M02-04-00 Test Magnet SK-Photo Addressable Photo Detector P48-21-00 Replacement End Cap for Metal SK-PhotoR Addressable Photo Detector with remote test Sampling Tube capability(included with SK-Duct) APA151 Remote annunciator with piezo alarm SK-Relay Addressable Relay Module, must be added if relay function is required, (fits in housing) Important Notes: Accessoriest •The use of either RTS151 or RTS151 KEY requires the DST1 Metal Sampling Tube Duct Width up to 1' installation of an accessory coil, DCOIL, sold separately. DST1.5 Metal Sampling Tube Duct Widths 1'-2' Please refer to the SK-Duct installation instructions for DST3 Metal Sampling Tube Duct Widths 2'—4' more information > DST5 Metal Sampling Tube Duct Widths 4'—8' •The RTS151/RTS151 KEY test coil circuit requires an DST10 Metal Sampling Tube Duct Widths 8'— 12' external 24VDC power supply which must be UL listed. DH4000E-1 Weatherproof Enclosure ETX Metal Exhaust Tube Duct width 1' RA100Z Remote LED Annunciator Accessory Current Loads at 24 VDC DCOIL Duct accessory coil, required if using with Device Standby Alarm SK-Photo and not SK-PhotoR (included)with RA100Z OmA 12mA Max. SK-Duct RTS151 Magnetic Remote Test station RTS151 OmA 12mA Max. RTS151KEY Key-Activated Remote Test station RTS151KEY 12mA 12mA Max. O. SILENT This document is not intended to be used for installation purposes.We try MADE IN AMERICA to keep our product information up-to-date and accurate.We cannot cover KNIGHT all specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information, contact Silent FORM#350122 Rev D Knight 12 Clintonville Road, Northford, CT 06472-1610 ©2010 Honeywell International Inc. by Honeywell Phone: (800)328-0103, Fax: (203)484-7118. www.silentknight.com - .- 110 SILENTSK-Pull-SA and SK-Pull-DA KNIGHT Intelligent Pull Stations by Honeywell The SK-Pull-SA and SK-Pull-DA are a single action or dual action addressable fire alarm pull station for use with Silent Knights IntelliKnight fire control panel. Extremely easy to operate, the SK-Pull-DA and SK-Pull-SA provide a fast and practical means of manually initiating a fire alarm signal. The IntelliKnight panel recognizes each manual pull station by its specific address saving precious seconds in determining the location of an alarm. For more information about the IntelliKnight system, or to locate you nearest source, please call 1-800-328-0103. Description The SK-Pull-SA is a single action pull station requiring only E one motion to activate the station. The SK-Pull-DA is a dual action pull station requiring two motions to active the station. Both pull stations are designed to work with Silent Knight 4. DO, N , Intelliknight series fire alarm control panels (FACPs). l Features • Installer can open station without causing an alarm condition 0 • Dual-color LED is visible through handle of station blinks green to indicate normal operation and remains steady red SK-Pull-SA in an alarm condition • Key operated test and reset lock using lock plate actuator FIRE • Key matches compatible FACP locks • Meets the Americans with Disabilities Act Accessibility I PUSH IN I PULL DOWNS Guidelines (ADAAG) controls and operating mechanisms guidelines (Section 4.1.3[13]) • Meets ADA requirement for 5 lbs maximum pull force to active FaKNIGHT - • Shell, door, and handle molded from durable LEXAN® • Reliable analog communications for trouble-free operation SK-Pull-DA • Braille text on station handle Compatibility • Handle latches in down position and the word Activated The SK-Pull-SA and SK-Pull-DA are compatible appears, clearly indicating the station has been pulled with the following IntelliKnight FACP's: 5600 • Rotary address switches for fast installation 5700 5808 • UL Listed, including UL 38, Standard of Manually Actuated 5820XL Signaling System 5820XL EVS P/N 350135 Rev D ©2016 Honeywell International Inc. 1 'N . aR Model SK-Pull-DA and SK-Pull-SA Intelligent Pull Stations Engineering Specifications The contractor shall furnish and install where indicated on the plans, Addressable Pull Stations, Silent Knight model SK-Pull-SA single action pull station or SK-Pull-DA, dual action pull station. SK-Pull-DA or SK-Pull-SA meet the ADAAG controls and operating mechanisms guidelines, and the ADA requirements for a 5 lb. maximum pull force to activate the pull station. g II ._ cess IBJ ik - Class a 7 Qonvetitie rc v7 I , , ,„till ..k. 1 , I Liii. , , , 1' 1 t i i „.. ,,, i 1 SRI'41 , p . p i .Ir c:ass ek uAr g:= Class B Wcing. .. Oa 4,i Wiring SK-Pull-SA& SK-Puil-DA Pull Stations Specifications Electrical Operating Voltage: 15-32 VDC Physical Height: 5.5" (14 cm) Average Operating Current(LED flashing): 300 pA Width: 4"(10.2 cm) Wire Gauge: Up to 12 AWG (3.1 mm2) Depth: 1.45" (3.7 cm) Environmental Housing Material: LEXAN polycarbonate resin Operating Temperature 32°— 120°F (0°C—49°C) Bi-Colored LED: Humidity: 10%—93% non-condensing Blinking Green: Normal Steady Red:Alarm Accessories Switch: Single pole, single throw(SPST) normally open (N/O) BG-TR Optional trim ring. switch which closes upon activation of the pull station SB-I/O Surface backbox sn ENr This document is not intended to be used for installation purposes. We try to keep our product G� information up-to-date and accurate. We cannot cover all specific applications or anticipate all KINIrequirements.All specifications are subject to change without notice. For more information, contact Silent Knight 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800) 328-0103, by Honeywell Fax: (203)484-7118. For Technical Support, Please call 800-446-6444. www.silentknight.com 11 : it‘Th SYSTEM -\7%-‘,,..,, 4 SENSOR rR a Ili";,,‘ie' ;:::::.....::::42-::::: � _-_-_:::::::::::::.,,..,T,,,,,,.>,,, t ii Field-Selectable tt,0� ;�, t; ; ;, Emergency ;;;, ,,1:11r' ,- '�- itS ., Communications . Devices System Sensor L-Series emergency communications devices and accessories combine application versatility with all the time-and money-saving benefits of the L-Series line. . Emergency Communications Features: H U • Plain or ALERT-printed white housings System Sensor L-Series,the broadest and most versatile line • Clear or Amber lens strobes and speaker strobes of notification devices available,includes a wide range of devices to • Color lens attachments for use with clear lens meet emergency communications application requirements. wall or ceiling strobes • Meets DoD specification requirements ALERT-printed on white housings amber lens strobes and speaker strobes provide visual signaling for emergency communications in L-Series Features: compliance with ANSI/UL 1638—Standard for General Signaling Visible Appliances.Other Plain or ALERT-printed models provide clear • Plug-in design for simplified installation and troubleshooting lenses for use with color lens strobe attachments(amber,blue,green, • Mounting plate shorting spring easily tests wiring continuity and red)that easily attach to strobe and speaker strobe devices • Automatic selection of 12-or 24-volt operation without a candela derating. at 15 and 30 candela In addition,L-Series emergency communications devices include • Field-selectable candela settings of: plain(non-printed}strobes,horn strobes,and speaker strobes. -Wall: 15,30,75,95, 110, 135, 185 These devices,along with ALERT-printed devices and L-Series -Ceiling: 15,30.75,95, 115, 150, 177 accessories,can meet a wide range of requirements for indoor • Rated from 32°F to 120°F(indoor devices) applications,including emergency communications,general • Optional tamper-resistant Torx head screw signaling,severe weather,and emergency response. • Compatible with System Sensor synchronization protocol All L Series emergency communications and general signaling devices are compatible with the entire L-Series Eine and include all tme time-amoney-siaFoe, inhe design simplifiesnd installation andaving reducesnnovtions.costlyr groundexamplfaultsplug, eal mounting plates with ting springs test wiring continuity univrsto speed installation and onboard protectshordevices from damage, Agency Listings and field selectable settings provide versatility and enable installers SIGNALING to quickly set each device to meet application requirements. �� iAs`I LISTED APPROVED Karn nNobes: fM apm•.red except for Strobes:7125-1653 0564 455':2.5401? ALEFT rnodets and colored recall. Homs/Ho;o S rabes:7135-16530503 Speaker S!ob,^s. Horn Strobes-1667382.3tb57072 Speaker Strobes.7320-1653:0505 04048 Speaker Strome:31657433 L-Series Specifications General System Sensor L-Series strobes and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box,4-inch octagon back box,or double-gang back box.L-Series compact devices shall mount to a single-gang 2 x 4 x 17/8-inch back box.L-Series speaker strobes shall mount to a 4 x 4 x 21/8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit wiring and amplifier wiring shall terminate at the universal mounting plate.Also, L-Series products,when used with the Sync•Circuif°Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module,12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts.Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.Strobes,horn strobes,and speaker strobes shall have field-selectable candela settings,including 15,30,75,95, 110,115,135,150,177,and 185. Strobe The clear strobe shall be a System Sensor L-Series Model listed to UL 1971 and shall be approved for fire protective service.Colored lens strobes shall be listed to ANSI/UL 1638 and shall be approved for Private Mode Emergency.The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch between a temporal three-pattern and a non-temporal(continuous)pattern.These options shall be set by a multiple position switch.The horn and horn strobe models shall operate on a coded or non-coded power supply. Speaker Strobe Combination The speaker strobe shall be a System Sensor L-Series Model listed to UL 1480 and UL 1971 and be approved for fire protective signaling systems.Speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms selected via rotary switch,and shall have a frequency range of 400 to 4,000 Hz.Speaker shall have power taps that are selected by rotary switch.The strobe shall comply with the NFPA 72 requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize L-Series strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns on horn strobe models over a single pair of wires.The module shall mount to a 411/16 x 411/16 x 21/8-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Color Lens Strobe Attachment The System Sensor L-Series color lens attachments shall be approved for fire protective service as listed in UL 1638.The lens attachments shall only be used with (plain non-fire-printed)System Sensor strobe devices,They shall mount to any wall or ceiling strobe and be rated from minus 35 degrees to 151 degrees Fahrenheit.The effective light loss for wall units shall be as follows Amber=0%,Blue=-40%,Green=-65%,Red=-85% Physio pert n �iyz.: • :_ Standard Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Dimensions Wall-Mount 5.6"L x 4.7"W x 1.91"D(143 mm L x 119 mm W x 49 mm D) Strobe and Horn Strobe(including lens) SPS Speaker Strobe(including lens) 6.5"L x 5.0"W x 2.3"D(165 mm L x 127 mm W x 58 mm D) Dimensions Ceiling-Mount Strobe(including lens) 6.8"diameter x 2.8"D ElecttieaKVeratingSpecifitatiorrs Nominal Voltage(strobes and horn strobes) Regulated 12 VDC or regulated 24 DC/FWR Nominal Voltage(speakers) 25 V or 70.7 V(nominal) Maximum Supervisory Voltage(speakers) 50 VDC Operating Voltage Range 8 to 17.5 V(12 V nominal)or 17 to 33 V(24 V nominal) Operating Voltage Range with MDL3 8.5 to 17.5(12V nominal)or 16.5 to 33V(24V nominal) Strobe Flash Rate 1 flash per second Speaker Frequency Range 400 to 4,000 Hz Speaker Power 1/4,1/2, 1,2 watts und Ouput di.Reverberant(dBA @ 10 ft,) 2 W 1 W /z VV 1/4 W Wall-Mount SPS Series 88 85 82 79 Ceiling-Mount SPC Series 88 85 82 79 AVDS871C2 UL Current Draw Data UL Max Stn:lbe Currant Draw(rnA RMS) 8-17.5 Volts 16-33 Volts Candela DC DC FWR 15 87 41 60 30 153 63 86 75 N/A 111 142 95 N/A 134 164 110 N/A 148 179 115 N/A 158 191 135 N/A 172 209 150 N/A 189 228 177 N/A 226 264 185 N/A 222 257 Wall Candela Settings: 15,30.75,95, 110, 135, 185 Ceiling Candela Settings: 15,30,75,95, 115. 150, 177 UL Mu.Current Draw OA RMA},2-Wire Horn Strobe 8VDC 16VDC DC Input 15 30 15 30 75 95 110 115 135 150 175 185 Temporal High 98 158 54 74 121 142 162 187 196 217 254 245 Temporal Low 93 154 44 65 111 133 157 185 184 211 249 235 Non-Temporal High 106 166 73 94 139 160 182 187 211 230 273 262 Non-Temportal Low 93 156 51 71 119 139 162 170 190 216 258 239 3.1K Temporal High 93 156 53 73 119 140 164 184 190 229 257 242 3.1K Temporal Low 91 154 45 66 112 133 160 185 185 212 252 235 3.1K Non-Temporal High 99 162 69 90 135 157 175 202 208 229 271 261 3.1K Non-Temporal Low 93 156 52 72 119 138 162 187 192 217 259 242 16VFWR FWR Input 15 30 75 95 110 115 135 150 175 185 Temporal High 83 107 156 177 198 223 234 254 286 287 Temporal Low 68 91 145 165 185 199 223 229 262 271 Non-Temporal High 108 135 181 207 230 223 264 254 286 315 Non-Temportal Low 79 104 157 175 197 199 235 229 262 281 3.1K Temporal High 81 105 155 177 196 225 234 255 289 284 3.1K Temporal Low 68 90 145 166 186 196 222 229 260 276 3.1K Non-Temporal High 101 131 176 204 230 225 264 255 289 326 3.1K Non-Temporal Low 77 102 156 177 199 196 234 229 260 291 Wall Candela Settings: 15,30,75,95, 110, 135, 185 Ceiling Candela Settings: 15,30,75,95, 115, 150. 177 Horn Tones and Sound Output Data Horn and Horn Strobe Output(dBA) 8-17.5 16-33 Switch Volts Volts Position Sound Pattern dB DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 9* Coded High 85 90 90 10* 3.1 KHz Coded High 84 89 89 *Settings 9 and 10 are not available on the 2-wire horn strobes. AVDS87102 L-Series Ordering Information Part N �,:. ��� Ili P '; art No. .. < <_ Alert Devices Colored Lenses SWL-CLR-ALERT Strobe,White,Wall,Clear Lens,Alert LENS-A2 Wall-Mount Lens Attachment,Amber SWL-ALERT Strobe,White,Wall,Amber Lens,Alert LENS-B2 Wall-Mount Lens Attachment,Blue SCWL-CLR-ALERT Strobe,White,Ceiling,Clear Lens,Alert LENS-G2 Wall-Mount Lens Attachment,Green SPSWL-ALERT Speaker Strobe,White,Wall,Amber Lens, LENS-R2 Wall-Mount Lens Attachment,Red Alert LENS-AC2 Ceiling-Mount Lens Attachment,Amber SPSWL-CLR-ALERT Speaker Strobe,White,Wall,Clear Lens,Alert LENS-BC2 Ceiling-Mount Lens Attachment,Blue SPSCWL-CLR-ALERT Speaker Strobe,White,Ceiling,Clear Lens, LENS-GC2 Ceiling-Mount Lens Attachment,Green Alert LENS-RC2 Ceiling-Mount Lens Attachment,Red Plain Wail Strobes Bezel Kits* SRL-P Strobe,Red,Wall,Plain BZR Wall Red Bezel Kit SWL-P Strobe,White,Wall,Plain BZW Wall White Bezel Kit Plain Wall Horn Strobes BZGR Compact Wall Red Bezel Kit P2RL-P Horn Strobe,Red,Wall,Plain BZGW Compact Wall White Bezel Kit P2WL-P Horn Strobe,White,Wall,Plain BZRC Horn/Strobe Ceiling Red Bezel Kit Plain Wall Speaker Strobes BZWC Horn/Strobe Ceiling White Bezel Kit SPSRL-P Speaker Strobe,Red,Wall, Plain BZSPR Speaker Wall Red Bezel Kit SPSWL-P Speaker Strobe,White,Wall,Plain BZSPW Speaker Wall White Bezel Kit Plain Ceiling Speaker Strobes BZSPRC Speaker Ceiling Red Bezel Kit SPSCWL-P Speaker Strobe,White,Ceiling,Plain BZSPWC Speaker Ceiling White Bezel Kit Notes: 'Each bezel pack ships in a package of 5.For bezel option All-P models have a plain housing(no"FIRE"marking on cover). add-F(FIRE),-AL(ALERT),-EV(EVAC).-AG(AGENT),-P(Plain), -SP(FUEGO),-PG(FOGO)for desired printing. SYSTEM 3825 Ohio Avenue•St.Charles, IL 60174 02017 System Sensor. SE AisORPhone:800-SENSOR2•Fax:630-377-6495 Product specifications subject to change witnoutnotice.Visit systemsensorcom for current product information,including the latest version of this data sheet. www.systemsensor.com AVDS87102.03/17 1 IIfI�li1t1i1111111ii1 1,..' � _f111`1 1.1 1.1.1,1 # 11111 SYSTEM SENSOR # 1 !11 1i1i111!##IIj1�1� 11 :II 111# ;', 11 .11 1 # 11 ##11 ' 111{ Indoor Selectable- I#'' 1111 1111#:1; 111 € 1It1 11 � Output Speaker Strobes and Dual Voltage Evacuation I Speakers for Wall 44:14 R Applications System Sensor L-Series selectable output speaker strobes and dual-voltage evacuation speakers can reduce ground faults and enable faster installation with lower current draw and modern aesthetics. The System Sensor L-Series of speakers and speaker strobes reduce costly ground faults using a plug-in design and universal Features mounting plate that allow the installer to pre-wire mounting plates, • Plug-in design and protective cover reduce ground faults dress the wires,and confirm wiring continuity before plugging in the speakers. In addition,a protective plastic cover prevents nicked • Universal mounting plate with an onboard shorting spring tests wires by covering exposed speaker components. wiring continuity before installation • No extension ring required These devices also enable faster installations by providing instant • Field selectable candela settings on wall units: feedback to ensure that wiring is properly connected,rotary switches 15,30,75,95, 110, 135, 185 to select voltage and power settings,and 7 field-selectable candela settings for wall speaker strobes. • Automatic selection of 12-or 24-volt operation at 15 and 30 candela The low total harmonic distortion of the speaker offers high fidelity • Rotary switch simplifies field selection of speaker voltage sound output while still offering high volume sound output for use (25 and 70.7 Vrms)and power settings(1/4,'/, 1 and 2 watts) in high ambient noise applications. • Seakers offer high fidelity and high volume sound output System Sensor L-Series makes installation easy • Compatible with System Sensor synchronization protocol •Attach a universal mounting plate to a 4 x 4 x 21/8 inch back box. • Electrical compatibility with existing SpectrAlert and SpectrAlert Flush-mount applications do not require an extension ring. Advance products •Connect the notification appliance circuit or speaker wiring to the • Tamper-resistant construction terminals on the mounting plate. •Attach the speaker or speaker strobe to the mounting plate by • Updated modern aesthetics inserting the product tabs into the mounting plate grooves.Hinge the device into position to lock the product pins into the mounting plate terminals.The device will temporarily hold in place with a Agency Listings catch until it is secured with a captured mounting screw. S1/c'Ma�uxc <1; X17 LISTEDAPPROVED S40'18 FM approved except 7320..1653 0505 for ALERT models 3057493 L-Series Speaker and Speaker Strobe Specifications Arttfta aura cif't � � : ... .. General L-Series speaker and speaker strobes shall mount to a 4 x 4 x 21/8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate.Also,L-Series speaker strobes,when used with the Sync•CircuitTM Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32°F and 120°F from a regulated DC,or full-wave rectified,unfiltered power supply.Wall- mount speaker strobes shall have field-selectable candela settings including 15,30,75,95, 110, 135, 185. Speaker The speaker shall be a System Sensor L-Series model dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms. It should be listed to UL 1480 and shall be approved for fire protective service.The speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F.The speaker shall have power taps and voltage that are selected by rotary switches. Speaker Strobe combination The speaker strobe shall be a System Sensor L-Series model listed to UL1480 and UL 1971 and be approved for fire protective signaling systems.The speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms selected via rotary switch,and shall have a frequency range of 400 to 4,000 Hz.The speaker shall have power taps that are selected by rotary switch.The strobe shall comply with the NFPA 72 requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz.The module shall mount to a 411/16 x 411/16 x 21/8-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical Specifications,s Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Dimensions,Wall-Mount Length Width Depth SPL Speaker 6.5 in, 165 mm 5 in, 127 mm .97 in,23 mm With Surface Mount Back Box 6.6 in, 168 mm 5.1 in, 130 mm 3.2 in,82 mm SPSL Speaker/Strobe 6.5 in, 165 mm 5.0 in, 127 mm 2.3 in,58 mm (including lens and speaker) With Surface Mount Back Box 6.6 in, 168 mm 5.1 in, 130 mm 4.5 in, 116 mm Electrical/Operating Specifications,• .... • _ E ..,r. +W ; Nominal Voltage(speakers) 25 Volts or 70.7 Volts(nominal) Maximum Supervisory Voltage(speakers) 50 VDC Strobe Flash Rate 1 flash per second Nominal Voltage(strobes) Regulated 12 VDC or regulated 24 DC/FWR1,2 Operating Voltage Range(includes fire 8 to 17.5 V(12 V nominal)or 16 to 33V(24 V nominal) alarm panels with built in sync) Operating Voltage with MDL3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33V(24 V nominal) Frequency Range 400 to 4000 Hz Power 1/4,1/2, 1,2 watts 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.Strobe products will operate at 12 V nominal only for 15 and 30 cd UL Current Draw Data UL Max Strobe Current Draw intA FIRM) 8 to 17,5 Volts 16 to 33 Volts Candela DC DC FWR 15 88 43 60 30 143 63 83 75 N/A 107 136 95 N/A 121 155 110 N/A 148 179 135 N/A 172 209 185 N/A 222 257 SOUnd OUtpUt Speaker Strobe ¼W ½W 1W 2W UL Reverberant(dBA @10 ft) 77 80 83 86 UL Anechoic(dBA @10 ft) 77 80 83 86 Sound Output Speaker ¼W ½W 1W 2W UL Reverberant(dBA @10 ft) 79 82 85 88 UL Anechoic(dBA @10 ft) 79 82 85 88 L-Series Dimensions = 5.00 = .97 = - = = 1.63 63 5.00 1.63 1.39 = - r(7.2-7-11-7-7- "L'I..`t. ,_ 1---- 1 --4-7.1- .]:']-:'''''-- : _5_11 I _immeirnommelimer__ iill k_.--..-.L----,-.--------7---77.--IL tor-;•• . - 711 ' .- (1:''il.",*:':','.'1,'!:::1: :4 -': 'i .--, 011," 11111:1-12111 6.50 -,', ' ',...: .. '-:f-.i..f-]:,- = di 6.50 ...:..:1, ,I_-. .1111111 L j1111 ---iii IMILIP} 14101::: 0 ::,,,Iztllil474"..47y,,v.:1,7,Y,!,:.,i k I 10 ,:i_ ..4 ii , , ....----..,....... ._. ---- ,.-±.----7----- -- .4%, 1 Wall-Mount Speaker Wall-Mount Speaker Strobe Surface Mounting • 7 1 k III ^ B°A°ApAAAAAA4AUABB ® ( (✓ pAA 9ApgA9AgAA9BAAA9AOAOABApI OA A AA°A°A^A° . AA! A 9e Bf, @ DOODA aAA,A°pi98a, \..�- I. ®09®D gB9°90AOA989BA9A9� A„ �1 ®DB 'A90AAA9AAAOA090A° AB' \ � ;� ®®BD Opoo aaaam°°v O9A9 n � BA iL lg't5'. Alf' �+1 JL _ r B° 000° .f°1 o°a° °1i Wall-Mount Speaker Strobe with SBBSPL Surface Mount Back Box L-Series Ordering Information Walt mount White Red Description SPWL SPRL Speaker only SPSWL SPSRL Speaker Strobe SPSWL-P SPSRL-P Plain Speaker Strobe SPSWL-ALERT — Speaker Strobe,Amber Lens SPSWL-CLR-ALERT — Speaker Strobe Clear Lens — SPSRL-SP Speaker Strobe,Fuego AcceSsories 5 i White Red Description RFPW RFP 7 in x 9.5 in Retrofit Plate SBBSPWL SBBSPRL Surface Mount Back Box for Speakers and Speaker Strobes TR-2W TR-2 Wall Mount Trim Ring Notes: All-P models have a plain housing(no"FIRE"marking on the cover) 3825 Ohio Avenue•St. Charles, IL 60174 , U2 1' stem Sznsc. Phone:800-SENSOR2•Fax:630-377-6495 Product specificaton s bec s change trout notice.Jisit sys'temsensor.com for cucent product information ine uding he latest er ion of this data sheet, www.systemsensor.com n o e o,•03i17 SYSTEM SENSOR' Indoor Selectable � i Output Speaker Strobes and Dual Voltage Evacuation Speakers for Ceiling Applications System Sensor L-Series selectable-output speaker strobes and dual-voltage evacuation speakers can reduce ground faults and enable faster installation with lower current draw and modern aesthetics. System Sensor L-Series of speakers and speaker strobes reduce costly ground faults using a plug-in design and universal Features mounting plate that allow the installer to pre-wire mounting plates, • Plug-in design and protective cover reduce ground faults dress the wires,and confirm wiring continuity before plugging in the speakers.In addition,a protective plastic cover prevents nicked • Universal mounting plate with an onboard shorting spring tests wires by covering exposed speaker components. wiring continuity before installation • No extension ring required These devices also enable faster installations by providing instant • Field selectable candela settings on ceiling units: feedback to ensure that wiring is properly connected,rotary switches 15,30,75,95, 115, 150,and 177 to select voltage and power settings,and 7 field-selectable candela settings for both wall and ceiling speaker strobes. • Automatic selection of 12-or 24-volt operation at 15 and 30 candela The low total harmonic'distortion of the SP speaker offers high fidelity • Rotary switch simplifies field selection of speaker voltage(25 sound output while still offering high volume sound output for use in and 70.7 Vrms)and power settings(1/4,Y2, 1 and 2 watts) high ambient noise applications. • Speakers offer high fidelity and high volume sound output L-Series makes installation easy • 520 Hz+1-10%square wave tone capable with compatible FACP •Attach a universal mounting plate to a 4 x 4 x 21/8 inch back box. • Compatible with System Sensor synchronization protocol Flush-mount applications do not require an extension ring. • Electrical compatibility with existing SpectrAlert and SpectrAlert •Connect the notification appliance circuit or speaker wiring to the Advance products terminals on the mounting plate. •Attach the speaker or speaker strobe to the mounting plate by • Tamper-resistant construction inserting the product tabs into the mounting plate grooves.Hinge • Updated modern aesthetics the device into position to lock the product pins into the mounting plate terminals.The device will temporarily hold in place with a Agency Listings catch until it is secured with a captured mounting screw. SIGNALING 414> LISTEDAPPROVED 94048 FM approved except 7320-15530535 for ALERT models 3057493 AVDS666-03.03/23,12018•Page L-Series Speaker and Speaker Strobe Specifications Archi ng s EF General L-Series speaker and speaker strobes shall mount to a 4 x 4 x 21/8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate.Also,L-Series speaker strobes,when used with the Sync•CircuitTM Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32°F and 120°F from a regulated DC,or full-wave rectified,unfiltered power supply.Speaker strobes shall have field-selectable candela settings including 15,30,75,95, 115, 150, 177. Speaker The speaker shall be a System Sensor L-Series model dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms. It should be listed to UL 1480 and shall be approved for fire protective service.The speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F.The speaker shall have power taps and voltage that are selected by rotary switches. Speaker Strobe combination The speaker strobe shall be a System Sensor L-Series model listed to UL1480 and UL 1971 and be approved for fire protective signaling systems.The speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms selected via rotary switch,and shall have a frequency range of 400 to 4,000 Hz.The speaker shall have power taps that are selected by rotary switch.The strobe shall comply with the NFPA 72 requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz.The module shall mount to a 411/16 x 411/16 x 21/8-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. physical specifics, dans , . Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Dimensions,Ceiling-Mount Diameter Depth SPC Speaker 6.8 in, 173 mm 1.0 in,25 mm With Surface Mount Back Box 6.9 in, 176 mm 3.5 in,89 mm SPSC Speaker Strobe 6.8 in, 173 mm 2.8 in,73 mm With Surface Mount Back Box 6.9 in, 176 mm 5.37 in, 136 mm *When using 12AWG, 14 AWG,or adding extra wires in the box,a deeper box or extension ring is recommended. BechicatiOperaiing Specifications ; Nominal Voltage(speakers) 25 Volts or 70.7 Volts(nominal) Maximum Supervisory Voltage(speakers) 50 VDC Strobe Flash Rate 1 flash per second Nominal Voltage(strobes) Regulated 12 VDC or regulated 24 VDC/FWR 1.2 Operating Voltage Range(includes fire 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) alarm panels with built in sync) Operating Voltage with MDL3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33 V(24 V nominal) Frequency Range 400 to 4,000 Hz3 Power 1/4,1/2, 1,2 watts 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.Strobe products will operate at 12 V nominal only for 15 and 30 cd. 3.520 Hz+/-10%square wave tone capable with compatible FACP. AVDS866-03•03/23/2018•Page 2 UL Current Draw Data IX Max.Strobe Cunent Draw OM MS) 8 to 175 Volts 16 to 33 Volts Candela DC DC FWR 15 87 41 60 30 153 63 86 75 NA 111 142 95 NA 134 164 115 NA 158 191 150 NA 189 228 177 NA 226 264 Ceiling-Mount Speaker Sound Output Setting UL Reverberant(dBA @10 ft) UL Anechoic(dBA @10 ft) 1/4W 79 79 1/2 W 82 82 1W 85 85 2W 88 88 Ceiling-Mount Speaker Strobe Sound Output Setting UL Reverberant(dBA @10 ft) UL Anechoic(dBA @10 ft) 1/4W 77 77 1/2W 80 80 1W 83 83 2W 86 86 L-Series Dimensions 1.6" 1.63 8-1 6.8"dia. -"----‘ / \ *'\'':,•, \ i II I ,.,\,.•;.. ::.' -, ,-,2..,-,.,-,-__-_-:,,i,f';'';';`:%/.%/1//-7 s :•;..\w,,,--,.-4,--''''"--,5%%ii.V//...' A0543 00 Ceiling Speaker 2 V' 66 dia 72.9 mm)—1-'-(4116663;.) 1 76" 130180TPAINr ,,,;;::/:Wf;- - '..,'s,.•‘'. 4*.\*\ r- : ii., ,.., ,,,,,„, II: ,, ,,%,.:4...cf.fi•ri.siv,z , „...... .41.1.1.4... . A0544 00 Ceiling Speaker Strobe A DSB66 03•/3/23 206•Page 3 Surface Mounting r4; LT t-tt\.. 44,-; 48- , _. , 1 ---,, um zani,,,, b„. ��� a II ,:,„,„„,,,,,,,,, ,,,,,t, ,,.....,4,...,„.„ ‘'4.::4','"'°a°;---,',7 713,--:11 , ,, A050401 la°a� �11 1 neo", „..44,4.,..7:!/ A0520-01 Ceiling Speaker with Surface Mount Back Box Ceiling Speaker Strobe with Surface Mount Back Box .r 11° ice_ C1 i y:, ,..„....,„...,..::- A0542-00 Ceiling Speaker Strobe with Trim Ring and 4°°Square Electrical Box L-Series Ordering Information Ceding M \" 01 K',K Yy-- ,. \ y�•• ( \sW/l.. e n• , White Red Description SPCWL SPCRL Speaker only SPSCWL SPSCRL Speaker Strobe SPSCWL-P — Plain,Speaker Strobe SPSCWL-SP — Fuego,Speaker Strobe SPSCWL-CLR-ALERT — Alert,Speaker Strobe,Clear Lens White Red Description SBBCWL SBBCRL Universal Ceiling Surface Mount Back Box TRC-2W TRC-2 Universal Ceiling Trim Ring 3825 Ohio Avenue•St.Charles, IL 60174 ©2018 System Sensor. Phone:800-SENSOR2•Fax:630-377-6495 Productspecifloations subject to change without notice.Visitsystemoensorcom for current product information,including the latest version of this data sheet . www.systemsensor.com AVDS866-03.03/23/2018 Security Accessories Overview Standard Features GE Electromagnetic Door Holders are ruggedly constructed and •• Surface mount,semi-flush, flush,and floor mounted models attractively designed.The housings are baked with a durable poly • Chrome or brass finishes blend In with other door hardware ester undercoating and are available in either a chrome or brass finish. • Low power consumption The floor or wall section houses the electromagnet while the • AC/DC models contact plate attaches to the door.The contact plate has a shock • Completely silent operation25 Lbf(111N)nominal holding force absorbing nylon(swivel)ball which allows the plate to adjust to any door angle.Floor units are available in single-door or double-door • Adjustable,swivel contact plate (back to back)versions.Wall units are available in flush or surface mounted versions.GE door holders should be installed wherever doors may be effectively used to confine smoke and fire,or where the release of a self-closing door from a remote location is desirable other reasons.Always consult your local Authority Having Juris- diction with any questions regarding a specific application.Fail-safe operation is an inherent feature of GE Security door holder-releases. s.If power fails,doors are released automatically but may be opened or closed manually at any time.All units are free of moving parts, are self-contained and require no maintenance.These door holder- releases have a holding force of approximately 15 to 25 Lbf(66 to 111N).The device holds a door open while energized. When de-energized by a relay controlled by the fire alarm system or other switch,the door is released to a closed position,checking the spread of smoke and flames.Electromagnetic door holders should be used and installed in accordance with local Building Codes and Standards. E ectromagnetIc Fire Door -lo ders , -„, ,,, -:-.7' : DH series cpt illii. d:.a Data Sheet FX85001-0603 Issue 1 Not to be used for installation purposes.Page 1 of 4 Surface Mount Bac-‹ Box Dimensions Door Magnet ------ci-7 1 6 31, , _ 711 114 7 o84n 17 4 2... . Iim 0 11 4117j 7 0 cm 1 1" 95" Extension Rod Applications Catch Plate Assembly and Accessories , /r.- „,-\., I DHW 7 % 1I I -1- III --i.. ,41) ,.... ,, OH ER1 I '1 I 0" 2 54 cm DH ER3 CO ) k• -1 Data Sheet N85001-0603 Issue 1 Not to be used for installation purposes.Page 2 of 4 Extension Rod Applications Catch Plate Assembly and Accessories Voltage Reference C—Common L—Low s. ..... , �O O H—High Li (C+L)Low F--- Voltage ( t 1 ` .1 Low Voltage i C L H ;, \` ED'EP 11 ..;i I I V; ;' C L H 1 M � ?( (C+H)High ?.'.l_) ,.J''I Voltage A� ( ) ( ) `},''............. ';, I I High Voltage I i` Low Voltage C L H CLH High Voltage - ---.1 4 i C L H C L H Performance Data Model Voltage DC/mA AC/mA Terminals Coil lbs kg.(Nominal) DHX*-1224 12V 30 30 C&L Single 35 15.9 24V 15 15 C&H Single 35 15.9 DHX*-24120 24V 15 15 C&L Single 35 15.9 120V — 15 C&H Single 35 15.9 DHFMt-1224 12V 60 60 C&L Double 35 15.9 24V 60 60 C&H Double 35 15.9 DHFMt-24120 24V - 30 30 C&L Double 35 15.9 120V — 30 C&H Double 35 15.9 *For all models,"X"represents either F(Flush Mount),FM(Floor Mount single-coil),R(Recessed),or S(Surface Mount). f For Floor Mount,double coil models. NOTE:Voltage supplied by a UL listed control panel Data Sheet FX85001-0603 Issue 1 Not to be used for installation purposes.Page 3 of 4 Security �.5. Ordering Information T 888-GESECURITY F 503-691-7566 Model Description Case Qty Canada Wall Mount T 519 376 2430 DHR-1224C 12 or 24 V DC/V AC,recess-mount,chrome,with 3"Extension Rod 20/case F5193767258 DHR-24120C 24 V DC/V AC 120V AC,recess-mount,chrome,with 3"Extension Rod 20/case Asia DHF-1224C 12 or 24 V DC/V AC,semi-flush-mount,chrome 20/case T 852 2907 8108 DHF-12248 12 or 24 V DC/V AC,semi-flush-mount,brass 20/case F 852 2142 5063 DHF-24120C 24 V DC/V AC 120V AC,recess-mount,chrome 20/case Latin America DHF-2410B 24 V DC/V AC 120V AC,semi-flush-mount,brass 20/case T 305 593 4301 DHS-1224C 12 or 24V DC/V AC,surface-mount,chrome 20/case F305 593 4300 DHS-1224B 12 or 24V DC/V AC,surface-mount,brass 20/case www.gesecurity.com/fireworx DHS-24120C 24V DC/V AC 120V AC,surface-mount,chrome 20/case ®2009 General Electric Company DHS-24120B 24V DCN AC 120V AC,surface-mount,brass 20/case All Rights Reserved Floor Mount DHFM1-1224 Single coil,12 or 24VDC/VAC,floor-mount,brushed steel 6/case DHFM1-24120 Single coil,24VDC/VAC 120VAC,floor-mount,brushed steel 6/case DHFM2-1224 Double coil,12 or 24VDCNAC,floor-mount,brushed steel 6/case DHFM2-24120 Double coil,24VDC/VAC 120VAC,floor-mount,brushed steel 6/case Extension Rods DHFM1-1224 Single coil,12 or 24VDC/VAC,floor-mount,brushed steel DH-ER1C 1"chrome DH-ER1B 1"brass DH-ER3C 3"chrome DH-ER3B 3"brass Accessories DHW Extension rod wrenches DH-BP Back Plate(chrome or brass) DH-ARMC Replacement armature,chrome DH-ARMB Replacement armature,brass imagination a Y work • t4 Data Sheet FX85001-0603 Issue 1 Not to be used for installation purposes.Page 4 of 4 - •-- SILENT SK-Monitor 4tvi; KNIGHT by Honeywell Intelligent Monitor Module The SK-Monitor module provides an interface to contact devices, such as security contacts, waterflow switches, or pull stations. For more information about the IntelliKnight system, or to locate you nearest source, please call 1-800-328-0103. Description The SK-Monitor is an addressable monitor module for use with Silent Knight IntelliKnight series fire alarm control \ £° panels (FACPs). The SK-Monitor is intended for use ins intelligent, two-wire systems, where individual address of each module is selected using the built-in rotary switches r• ,s The SK-Monitor supports Class A supervised or Class B • R t4t, supervised wiring to the load device. Conventional 4-wire smoke detectors can be monitored for alarm and trouble ry _ : conditions. Features • Single contact monitor • Support for Class A and Class B wiring ¢, • Fully supervised • Panel controlled status LED that flashes green in normal state and is solid red in alarm • Attractive ivory cover plate SK-Monitor • Rotary address switches for fast installation • SEMS screws for easy wiring Specifications • UL Listed Physical Installation Height: 4.5" (11.4 cm) The SK-Monitor mounts directly into a 4" square electrical Width: 4" (10.2 cm) box. The box must have a minimum depth of 2-1/8". A Depth: 1.25" (3 cm) surface mount electrical box (System Sensor® PN Shipping Weight: 6.3 oz (196 g) SMB500) is available from Silent Knight. Electrical Compatibility Operating Voltage: 15 32 VDC The SK-Monitor is compatible with the following Current Draw (LED on): 5.0 mA max IntelliKnight FACP's: Operating Current (LED flashing): 375 pA 5700 5808 5820XL 5820XL-EVS — . • - Model SK-Monitor Intelligent Monitor Module Deice - h PRE41DLtP DEVICE i ;si ANY NUMBER LL LISTED Qf } WC LILE L 7 + { CLOSURE EIPACES WaY EE USED.CSINOT NIX , - {- �^- 'f CONNECT MCULLEETO LIE1ED QUARRELS r ffirmL F�4$ D E w xt INT Artie,sL�1EFIsr. ' r- ! I E LFITYDEVICE OHTl^EUNE MCgLLE * *• , R a "µ ;' EOL y ° 3 T# SIG 14 LIiaEc19ctrrt3Lq. FTESISTUR �' WIC MAX, y a vara e sat =4 MISTED PAIR INITIATISSDeiceCSCUTiloq-NFFAETYLE`9 FURERUMTED:4 AMX.$iiMCCMAR METALL�'I 4�T LLI}6UFE DEVICES PER Al-3-°A' FlbtC4 4 1-t 3 AND POWER L tt ] MARLRETLIRERE NeTT✓tL;L,RTFC$1 P E.TRJC I , 2-Wire Initiating Circuit Configuration, NFPA Style B TO NEXT +c ,4 '`IC FROM PANEL OR DEV1c.E , 1. !'�� ;'1 +w ern.w' 0a .s.-.C>,"7:),=( {.,.,.. Pr3EVtoos DEVICE MONITOR • I ANYNUMBER OF L LISTED CONTACTMODULE a-OSURE DEVICES MAY BE USED DO NOT MIX # I CONNECT MODULES TO LISTED COMPATIBLE FIRE ALARM I NTI.ATIMG, IPER4CECRY,OR '2 NOTIFIER CONTROL PANELS ONLY SECURITY DEVICES ON THE SAME MOOULE. L_. r64 F . x'k 51 LINE I fROU(USW 32VDC MAX EOL RESISTOR IB - awe a il onSHIELDED-TWISTED Phi INTERNAL AT 114 ( ISRECOMENDED FtTERMINALS B®g NSTALLC NTAt T 'URE-DEVICES PER ALL *RINGa SHOWN IS SUPERVISED AND POWER LIMITED MANUFACTURER'S INSTALLARON INSTRUCTIONS, 4-Wire Initiating Circuit Configuration, NFPA Style D Standby Current: Environmental 400 pA max @ 24 VDC (one communication every 5 Operating Temperature: 32°F- 120°F (0°C-49°C) sec with 47K EOL) Humidity: 10% - 93% non-condensing 550 pA max @ 24 VDC (one communication every 5 sec with EOL <1K) Ordering Information 5.5 mA(with LED latched on) SK-Monitor Monitoring Module LED Current: 5.5 mA(with LED latched on)End-of-Line Resistance: 47K S2 Accessories Initiating Device Circuit Wiring Resistance: 1,500 c max SMB500 4" Square Surface Mount Electrical Box SLC Loop Resistance: 40 c) max. SILENT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA 410 keep our product information up-to-date and accurate.We cannot cover all KNIGHT specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information,contact Silent Knight FORM#350131 Rev D by Honeywell 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800)328-0103, ©2013 Honeywell International Inc. Fax: (203)484-7118. For Technical Support, Please call 8200-446-6444. www.silentknight.com - •-- 10 SILENT SK-Relay KNIGHT Intelligent Relay Module by Honeywell The SK-Relay Module is intended for use in intelligent, two-wire systems where the individual address of each module is selected using the built in rotary switches. For more information about the IntelliKnight system, or to locate you nearest source, please call 800-328-0103. Description The SK-Relay is an addressable relay module for use with Silent Knight IntelliKnight series fire alarm control panels (FACPs). The SK-Relay allows a Silent Knight FACP to switch a • 3 �d discrete contacts by code command. The relay contains414 two isolated sets of Form C contacts, which operate as a DPDT switch. No supervision is provided for the notification appliance circuit. The SK-Relay contacts can be used for virtually any normally open or normally closed application. Each SK- SK-Relay Relay is programmed with a unique signaling line circuit (SLC) loop address. When an event occurs that controls Installation the SK-Relay, the relay is triggered by the FACP. The SK-Relay mounts directly into a 4" square electrical box. The box must have a minimum Features depth of 2-1/8". A surface mount electrical box • Two sets of Form C contacts (System Sensor® PN SMB500) is available from • Rotary address switches for fast installation Silent Knight • Contacts are rated for a variety of amps (see Specifications) Compatibility The SK-Relay is compatible with the following • Panel controlled status LED that flashes green in IntelliKnight FACP's: normal state and is solid red in alarm 5820XL 5820XL-EVS • Relay programming is completely flexible—can be 5808 mapped to zone conditions 5700 5600 (Rev 2.0 or higher) • Polling LED visible through the cover plate • Attractive ivory cover plate • SEMS screws for easy wiring P/N 350127 Rev F • UL Listed ©2016 Honeywell International Inc. . , - . •-- Model SK-Relay Intelligent Relay Module CONNECT MODULES TO LISTED CO MPPTSLE H COM ROLPANELS ONLY (-) FROM PANEL TO NEXT ' OR PREVIOUS DEVICE ' 411.4110 +} (4,b t7!V[CE. RELAY CONTROL , MODULE1111 any wiring to Terminals 4-10 is Nonpower limited,The 08500 barrier _ — is required.The 08500 includes a Nonpower placed limnedaver label,the which 00. . 0er+ ' rrTow 0�� Limited terminal information on It,Til {-' i-i the name plate label. Relay Common 2 (I`t Tio Tt'll PAIIIIMEIPIP Norman Closed 2 s r2' l T9 it Normally Open 2 it:TO T3, Relay Common 1 1 . e . T- Unused Normally Closed 1 1.;T8 + ti 15 Normally Open 1 11 i_.. 10 I HAT LONE ANIN THE r O RESUL N A UNWED l A SEPARATE ZONE, iii Wiring the SK-Relay Module Specifications Ordering Information Physical SK-Relay Relay Module 4.675" H x 4.275" W x 1.4" D Shipping Weight: 6.3 oz (196 g) Accessories SMB500 4" Square Surface Mount Electrical Box Environmental CB500 Module Barrier Operating Temperature: 32°F— 120°F (0°C—49°C) Humidity: 10% — 93% non-condensing Electrical Operating Voltage: 15— 32 VDC Relay Contact Ratings End-of-Line Resistance: Not used 3.0A @ 30 VDC resistive SLC Standby &Alarm Current: .255mA max @ 24 0.9A @ 110 VDC resistive VDC (one communication every 5 sec with LED 0.9A @ 125 VAC resistive enabled) 0.5A @ 125 VAC inductive (PF = .35) 0.7A @ 75 VAC inductive (PF = .35) SILENTlc.it This document is not intended to be used for installation purposes. We try to keep our product KNIGHT information up-to-date and accurate. We cannot cover all specific applications or anticipate all 11,h requirements.All specifications are subject to change without notice. For more information, contact Silent Knight 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800)328-0103, Fax: (203) by Honeywell 484-7118. For Technical Support, Please Call 800-446-6444. www.silentknight.com