Loading...
Report RECEIVED SEP 18 2018 CITY OF TIARD BUILDING DIVISION * � .. WYATT FIRE PROTECTION, INC. 9095 S.W. Burnham Tigard, OR 97223 CEDARS MEDITERREAN COOLER 16770 SW 72ND AVE TIGARD, OREGON 97224 FIRE PROTECTION EQUIPMENT SUBMITTAL tqco Worldwide www.tyco-fire.com Fire Protection Contacts Products Series DS-C Dry Type Sprinklers 5.6K Concealed Pendent Standard and Quick Response, Standard Coverage General plaster board and ceiling tiles by gently pushing the ceiling product against the t Descri �On Protective Cap.When the ceiling instal jp lation is complete the Protective Cap is TYCO Series DS-C Dry Type Sprinklers, removed and the Cover Plate Assembly 5.6K Concealed Pendent, Standard (5 installed. mm Bulb) and Quick Response (3 mm Bulb)and Standard Coverage,are dec- NOTICE i i orative sprinklers featuring a flat cover Series DS-C Dry Type Concealed plate designed to conceal the sprinkler. Pendent Sprinklers described herein This type of sprinkler is typically used must be installed and maintained in to provide a sprinkler drop from an compliance with this document and the .'_, ,. unheated attic into an area where aes- applicable standards of the National .,. ,4 thetics is a concern, such as nursing Fire Protection Association, in addi- homes, restaurants, and schools. tion to the standards of any authorities Each unit includes a Cover Plate having jurisdiction. Failure to do so Assembly that conceals the sprinkler may impair the performance of these devices. Discharge Coefficient operating components above the K=5.6 GPM/psis/2(80,6 LPM/barli2) ceiling.The separable two-piece design The owner is responsible for main- of the Cover Plate and Support Cup taining their fire protection system Temperature Ratings Assemblies allows installation of the and devices in proper operating con- 155°F(68°C)Sprinkler with sprinklers and pressure testing of dition. Contact the installing contrac- 139°F(59°C)Cover Plate the fire protection system prior to tor or product manufacturer with any 200°F(93°C)Sprinkler with installation of a suspended ceiling or questions. application of the finish coating to a 165°F(74°C)Cover Plate fixed ceiling.They also permit removal Series DS-C Dry Type Concealed Adjustment of suspended ceiling panels for access Pendent Sprinklers must only be 1/2 inch(12,7 mm) to building service equipment without installed in fittings that meet the Finishes having to first shut down the fire pro- requirements of the Design Criteria Refer to Ordering Procedure section tection system and remove sprinklers. section. Also,the separable two-piece design of Physical Characteristics the Sprinkler provides for 1/2 inch(12,7 Sprinkler Inlet Plug Copper Copper mm)of vertical adjustment. Identification Yoke Stainleon Steel are shipped with casing Galvanized CarbB Steel Series DS-C Sprinklers PP Insert Bronze I a Disposable Protective Cap.The Pro- Numbers (SINS) Bulb Seat Stainless Steel tective Cap is temporarily removed for Bulb Glass installation,and then it can be replaced TY3535-3 mm Bulb Deflector Bronze to help protect the sprinkler while the Frame Bronze ceilingis installed or finished.The tipof TY3555 5 mm Bulb Wade Tube Stainless Steel Water Tube Stainless Steel the Protective Cap can also be used to Spring Stainless Steel Gasketed Spring mark the center of the ceiling hole into Technical Plate Seal Beryllium Nickel w/TEFLON Data Support Cup Chrome Plated Steel Guide Pins Stainless Steel Compression Screw Brass IMPORTANT Approvals Cover Retainer Brass Brass Brass UL and C-UL Listed Always refer to Technical Data NYC Approved under MEA 352-01-E-2 Ejection Spring Stainless Steel 1 Sheet TFP700 for the "INSTALLER WARNING" that provides cautions Maximum Working Pressure with respect to handling and instal 175 psi(12,1 bar) lation of sprinkler systems and com- Inlet Thread Connections ponents. Improper handling and 1 inch NPT(Standard Order) installation can permanently damage ISO 7-R1 a sprinkler system or its compo- - nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 8 MAY 2017 TFP515 TFP515 Page 2 of 8 Operation INLETPLUG WITH 'I GASKETED When TYCO Series DS-C Dry Type i, �, SPRING Concealed Pendent Sprinklers is in j j PLATE SEAL service, water is prevented from enter- YOKE - i ing the assembly by the Plug with Gas- keted Spring Plate Seal (Ref. Figure 1) in the Inlet of the Sprinkler. WATER 17 TUBE When exposed to heat from a fire, the INLET BAND E! Cover Plate,which is normallysoldered ; - to the Retainer at three points, falls E1r' .1 away to expose the Sprinkler Assembly. 1 At this point the Deflector supported by SPRING 1 INSERT the Guide Pins drops down to its opera- tional position. i The glass bulb contains a fluid that CASING i BULB expands when exposed to heat. Whenthe rated temperature is reached, the I� 1111 SEAT fluid expands sufficiently to shatter I'. i the glass bulb, and the Bulb Seat is GUIDE TUBE Ii— released. 1The compressed Spring is then able to i , FRAME expand and push the Water Tube as well as the Guide Tube outward. This VENT HOLE i � action simultaneously pulls inward on IIF the Yoke, withdrawing the Plug withGasketed Spring Plate Seal, from the SUPPORT ( 1 BULB Inlet, allowing the sprinkler to activate and flow water. CUP WITH ROLL FORMEDTHREADS - COMPRESSION SCREW GUIDE PIN DEFLECTOR (DROPPED DEFLECTOR POSITION) SPRINKLER SUPPORT CUP THREAD INTO ASSEMBLY 1 RETAINER SUPPORT WITH THREAD CUP UNTIL DIMPLES MOUNTING SURFACE IS FLUSH WITH ' o o CEILING EJECTION SPRING J SOLDER COVER TAB PLATE COVER PLATE - RETAINER ASSEMBLY FIGURE 1 SERIES DS-C STANDARD COVERAGE DRY-TYPE CONCEALED PENDENT SPRINKLER ASSEMBLY TFP515 Page 3 of 8 SPRINKLER FITTING (REFER TO DESIGN ( ------ , ' CRITERIA SECTION) I i L --� --------------------- FACE OF SPRINKLER FITTING ORDER SPRINKLER Ill _ LENGTHS: SUPPORT CUP 2-1/2" DIA. 5"(127,0 mm) ASSEMBLY (63,5 mm) to 48" mm) IN 1/4" (6,4 mm) 1/2"(12,7 mm) (6,4 INCREMENTS TDHUSAMEN =� ADJUSTMENT i� I FACE OF CEILING, mm)RETAINING RING MOUNTING I ,-_ SUpr RFACE �� rJ 11 3/16" G- _' -r-, (4,8 mm) 3/16"to 11/16" FACTORY DEFLECTOR COVER PLATE (4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER REFERENCE 3/32" (2,4 mm) POSITION ASSEMBLY 3-1/4" DIA. (82,6 mm) FIGURE 2 SERIES DS-C STANDARD COVERAGE DRY-TYPE CONCEALED PENDENT SPRINKLER INSTALLATION DIMENSIONS 2-1/2" DIA. 411111111 /lain (63,5 mm) ------ 11111 CLEARANCE HOLE ; FRAME 1�- ' ARM - SUPPORT �/ _ _ �� � A ME CUP )�I A i ON _ISI__ ,,,_, - MI 7/8"(23 mm) 0 -- - -- SQUARE • ••. FIGURE 3 ALIGN DISPOSABLE ARROWS WITH PROTECTIVE CAP FRAME ARMS ■ ai ACCEPTS ,' 0 1/2"SOCKET DRIVE FIGURE 4 RFII SPRINKLER WRENCH TFP515 Page 4 of 8 Desin For wet pipe system installations of 1 For protected area temperatures ginch NPT Series DS-C Dry Type Sprin- between those given above, the Criteria klers connected to CPVC piping, use minimum recommended length from only the following TYCO CPVC fittings: the face of the fitting to the outside of TYCO Series DS-C 3 mm bulb-type • 1"x 1"NPT Female Adapter the protected area may be determined Dry Type Concealed Pendent Sprin- (P/N 80145) by interpolating between the indicated klers(TY3535)are UL and C-UL Listed values. • 1"x 1"x 1" NPT Sprinkler Head as quick response, standard spray Adapter Tee(P/N 80249) Do not attempt to add additional insula- sprinklers for use in accordance with tion around the barrel in the heated area the current NFPA standard. For dry pipe system installations, use as a method to minimize condensation. Series DSC 5 mm bulb-type T e only the side outlet of maximum 2-1/2 This will reduce the calculated "Expo- Dry Type inch reducing tee when locating Series sure Length". Concealed Pendent Sprinklers(TY3555) DS-C Dry Type Sprinklers directly are UL and C-UL Listed as standard below the branch line. Otherwise, use Clearance Space response, standard spray sprinklers the configuration shown in Figure 6 to In accordance with Section 8.4.9.2 of for use in accordance with the current assure complete water drainage from the 2010 edition of NFPA 13,where dry NFPA standard. above Series DS-C Dry Type Sprinklers sprinklers are connected to wet pipe Series DS-C Dry Type Sprinklers are and the branch line. Failure to do so sprinkler systems protecting insulated only listed when installed with Series may result in pipe freezing and water freezer structures,the clearance space RFII Concealed Cover Plates having damage. around the sprinkler barrel of Dry Type a factory-applied painted or metallic Sprinklers must be sealed.Due to tem- finish. NOTICE perature differences between two areas, con- Series DS-C DryType Sprinklers must the potential for the formation of yP P Do not install Series DS-C Dry Type densation in the sprinkler and subse- not be used in applications where the Sprinklers into any other type fitting quent ice build-up is increased. If this air pressure above the ceiling is greater without first consulting the Technical condensation is not controlled, ice than that below. Down drafts through Services Department.Failure to use the build-up can occur that might damage the Support Cup could delay sprinkler appropriate fitting may result in one of the dry type sprinkler and/or prevent operation in a fire situation. the following: proper operation in a fire situation. Sprinkler Fittings • failure of the sprinkler to operate Use of the Model DSB-2 Dry Sprinkler Install 1 inch NPT Series DS-C Dry Type properly due to formation of ice over Boot,described in technical data sheet Concealed Pendent Sprinklers in the 1 the Inlet Plug or binding of the Inlet TFP591 and shown in Figure 8, will inch NPT outlet or run of the following Plug provide the recommended seal. fittings: • insufficient engagement of the • malleable or ductile iron threaded Inlet pipe-threads with consequent NOTICE tee fittings that meet the dimensional leakage For applications where a bore greater requirements of ANSI 316.3 (Class than 1-3/4 inches in diameter has been 150) Drainage cut through the entire height of an insu- In accordance with the minimum lated freezer ceilingcreatinga • cast iron threaded tee fittings that requirements of the National Fire Pro- cavity meet the dimensional requirements tection Association for dry pipe sprinkler above the sprinkler support cup (Ref. of ANSI 316.4(Class 125) systems, branch,cross,and feed-main Figure 8),the cavity must not be filled. Do not install Series DS-C Dry Type piping connected to Dry Sprinklers and Concealed Pendent Sprinklers into subject to freezing temperatures must elbow fittings.The Inlet of the sprinkler be pitched for proper drainage. can contact the interior of the elbow. Exposure Length The unused outlet of the threaded tee When using Dry Type Sprinklers in is plugged as shown in Figures 5 and 6. wet pipe sprinkler systems to protect Install Series DS-C Dry-Type Sprinklers areas subject to freezing temperatures, in the tee run or branch outlet. use Table A to determine a sprinkler's appropriate exposed barrel length to The configuration shown in Figure 5 is prevent water from freezing in the con- only applicable for wet pipe systems necting pipes due to conduction. The where the sprinkler fitting and water- exposed barrel length measurement filled pipe above the sprinkler fitting are must be taken from the face of the not subject to freezing and where the sprinkler fitting to the surface of the length of the Dry Type Sprinkler has the structure or insulation that is exposed minimum exposure length depicted in to the heated area. Refer to Figure 7 for Figure 7. Refer to the Exposure Length an example. section. TFP515 Page 5 of 8 Temperatures for Heated Areaa Ambient Temperature Exposed to Discharge End of 40°F(4°C) 50°F(10°C) 60°F(16°C) Sprinkler Minimum Exposed Barrel Length,Inches(mm)b 40°F(4°C) 0 0 0 30°F(-1°C) 0 0 0 20°F(-7°C) 4(100) 0 0 10°F(-12°C) 8(200) 1 (25) 0 0°F(-18°C) 12(305) 3(75) 0 -10°F(-23°C) 14(355) 4(100) 1 (25) -20°F(-29°C) 14(355) 6(150) 3(75) -30°F(-34°C) 16(405) 8(200) 4(100) -40°F(-40°C) 18(455) 8(200) 4(100) -50°F(-46°C) 20(510) 10(255) 6(150) -60°F(-51°C) 20(510) 10(255) 6(150) NOTES: a. For protected area temperatures that occur between values listed above,use the next cooler temperature b. These lengths are inclusive of wind velocities up to 30 mph(18,6 kph) TABLE A EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS MINIMUM RECOMMENDED LENGTHS Installation Step 1. Install the sprinkler in the of the ceiling. It may also be used to pendent position with the centerline locate the center of the clearance hole TYCO Series DSC Dry Concealed of the sprinkler perpendicular to the by gently pushing the ceiling material Pendent Sprinklers must be installed in mounting surface. up against the center point of the Pro- accordance with this section. Step 2. With a non-hardening pipe- tective Cap. Series DSC Dry Type Concealed thread sealant such as TEFLON pipe- As long as the Protective Cap remains Pendent Sprinklers must only be thread sealant applied to the Inlet in place,the system is considered to be installed in fittings that meet the threads,hand-tighten the sprinkler into "Out of Service". requirements of the Design Criteria the sprinkler fitting. Step 4.After installing the ceiling and section. Refer to the Design Criteria Step 3. Wrench-tighten the sprinkler applying a ceiling finish,with the 2-1/2 section for other important require- using either: inch (63,5 mm) diameter hole and in ments regarding piping design and • a pipe wrench on the Inlet Band or preparation for installing the Cover sealing of the clearance space around the Casing(Ref. Figure 1). Plate Assembly, remove and discard the Sprinkler Casing. the Protective Cap, and verify that the Do not install any bulb type sprinkler if • the RFII Sprinkler Wrench on the Deflector moves up and down freely. If the bulb is cracked or there is a loss wrench flat(Ref. Figure 4). the Sprinkler has been damaged and of liquid from the bulb. With the sprin- Apply the wrench recess of the RFII the Deflector does not move up and kler held horizontally,a small air bubble Sprinkler Wrench to the wrench flat. down freely,replace the entire Sprinkler should be present.The diameter of the assembly. Do not attempt to modify or air bubble is approximately 1/16 inch Note: If sprinkler removal becomes repair a damaged sprinkler. (1,6 mm). necessary, remove the sprinkler using Step 5. Screw on the Cover Plate/ the same wrenching method noted Retainer Assembly until the Retainer A leak-tight 1 inch NPT sprinkler joint above.Sprinkler removal is easier when (Ref. Figure 2)contacts the ceiling. Do should be obtained by applying a min- a non-hardening sealant was used not continue to screw on the Cover imum-to-maximum torque of 20 to 30 and torque guidelines were followed. Plate/Retainer Assembly such that it ft. lbs. (26,8 to 40,2 Nm). Higher levels After removal, inspect the sprinkler for lifts a ceiling panel out of its normal of torque may distort the sprinkler Inlet damage. position. If the Cover Plate/Retainer with consequent leakage or impairment When using the RFII Sprinkler Assembly cannot be engaged with of the sprinkler. Wrench, temporarily remove the the Support Cup or the Cover Plate/ Do not attempt to compensate for Protective Cap. Replace the Protec- Retainer Assembly cannot be engaged insufficient adjustment in the Sprinkler tive Cap (Ref. Figure 4) by pushing it sufficiently to contact the ceiling,repo- Assembly by under or over-tightening upwards until it bottoms out against the sition the Sprinkler Fitting. the Sprinkler/Support Cup Assembly. Support Cup.The Protective Cap helps Re-adjust the position of the sprinkler prevent damage to the Deflector and fitting to suit. Arms during ceiling installation and/or during application of the finish coating TFP515 Page 6 of 8 • RUN TO WET SIDE _OUTLETFACE OF SYSTEM OUTLETj -] PLUGGED SPRINKLER • PLUGGED [SPRINKLER FITTING FITTING HEATEDTO DRY (SEE DESIGN HEATED EXPOSURE AREA ill SYSTEM CRITERIA AREA LENGTH SECTION) (SEE DESIGN DSB-2 SPRINKLER AREA DSB-2 CRITERIA FITTING DSB-2 INTENDED (SEE DESIGN SUBJECT INTENDED INTENDED SECTION) FOR FREEZER TO FOR FREEZER STRUCTURES CRITERIA FREEZINGAFOR FREEZER STRUCTURES SECTION) STRUCTURES ii r r ...... __. ,i 41 • lk 41. IL �� ... FIGURE 5 FIGURE 6 SPRINKLER FITTING SPRINKLER FITTING FIGURE 7 HEATED AREA UNHEATED AREA EXPOSURE LENGTH STRAP TIES Care and Sprinklers which are found to be leaking • (ENDS ON or exhibiting visible signs of corrosion OPPOSING Maintenance must be replaced. SIDES OF Automatic sprinklers must never be BOOT) TYCO Series DS-C Dry Type Concealed painted, plated, coated, or other- DSB-2 BOOT Pendent Sprinklers must be maintained wise altered after leaving the factory. and serviced in accordance with this Modified sprinklers must be replaced. ADHESIVE section. Sprinklers that have been exposed to Before closing a fire protection system corrosive products of combustion, but I (63,5 "mmDIA.) main control valve for maintenance have not operated,should be replaced F� CLEARANCE work on the fire protection system if they cannot be completely cleaned HOLE that it controls, obtain permission to by wiping the sprinkler with a cloth or shut down the affected fire protection by brushing it with a soft bristle brush. INSULATED systems from the proper authorities Care must be exercised to avoid FREEZER and notify all personnel who may be damage to the sprinklers - before, ,_____1---- ___ STRUCTURE affected by this action. during, and after installation. Sprin- DS-C Absence of the Cover Plate Assembly klers damaged by dropping, striking, DRY PENDENT may delay sprinkler operation in a fire wrench twist/slippage,or the like,must - CONCEALED situation. be replaced. Also, replace any sprin- SPRINKLER kler that has a cracked bulb or that has FIGURE 8 A Vent Hole is provided in the Bulb lost liquid from its bulb. (Ref. Installa- MODEL DSB-2 Seat (Ref. Figure 1) to indicate if the tion Section.) DRY SPRINKLER BOOT Dry Sprinkler is remaining dry. Evi If a sprinkler must be removed, do not WITH DRY-TYPE SPRINKLER dence of leakage from the Vent Hole reinstall it or a replacement without indicate potential leakage past the Inlet seal and the need to remove the sprin reinstalling the Cover Plate Assembly. kler to determine the cause of leakage; If a Cover Plate Assembly becomes for example,an improper installation or dislodged during service, replace it an ice plug. Close the fire protection immediately. system control valve and the system The owner is responsible for the drain before removing the sprinkler. inspection,testing,and maintenance of When properly installed, there is a their fire protection system and devices • nominal 3/16 inch (4,8 mm) air gap in compliance with this document, as between the lip of the Cover Plate and well as with the applicable standards of the ceiling, as shown in Figure 2. This the National Fire Protection Association air gap is necessary for proper oper (for example, NFPA 25), in addition to ation of the sprinkler. If the ceiling is the standards of any other authorities to be repainted after the installation of having jurisdiction.Contact the install the Sprinkler, care must be exercised ing contractor or product manufacturer to ensure that the new paint does NOT with any questions. seal off any of the air gap. Automatic sprinkler systems are rec- Do not pull the Cover Plate relative to ommended to be inspected, tested, the Enclosure.Separation may result. and maintained by a qualified Inspec tion Service in accordance with local requirements and/or national codes. TFP515 Page 7 of 8 P/N" 60 - XXX - 1 - XXX SIN TEMPERATURE ORDER RATING LENGTH** 46 Quick Response TY3535 1 155°F(68°C) 055 5.50" (3 mm Bulb) 86 Standard Response TY3555 3 200°F(93°C) 082 8.25" (5 mm Bulb) Note 180 18.00" * Use Prefix"I"for ISO 7-R1 Connection (for example,I-60-461-1-180). ** Dry-Type Sprinklers are furnished based upon"Order Length"as 187 18.75" measured per Figure 2,for each individual sprinkler where it is to be installed.After the measurement is taken,round it to the near- est 1/4 inch increment. 372 37.25" 480 48.00" TABLE B SERIES DS-C STANDARD COVERAGE DRY-TYPE CONCEALED PENDENT SPRINKLER PART NUMBER SELECTION Limited Ordering Separately Ordered Cover Plate 7 Specify: Series RFII Concealed Cover WarraWarrant Procedure Plate with(specify)temperature rating, nty (specify)finish, P/N (specify): For warranty terms and conditions,visit Contact your local distributor for avail- 139°F(59°C)Cover Plate www.tyco-fire.com. ability. When placing an order, indi- for use with 155°F(68°C)Sprinkler cate the full product name, including Grey White(RAL9002) 56-792-0-135 Brass 56-792-1-135 description and Part Number(P/N). Pure White(RAL9010)* 56-792-3-135 Dry Type Sprinkler Assemblies Signal White(RAL9003) 56-792-4-135 When ordering5.6 K-Factor Series Jet Black(RAL9005) 56-792-6-135 Chrome 56-792-9-135 DS-C Standard Coverage Dry Type Custom 56-792-X-135 Concealed Pendent Sprinklers,specify 165°F(74°C)Cover Plate the following information: for use with 200°F(93°C)Sprinkler • SIN Grey White(RAL9002) 56-792-0-165 Quick Response TY3535 or Brass ( ) 56-792-1-165 p Pure White RAL9010* 56-792-3-165 Standard Response TY3555 Signal White(RAL9003) 56-792-4-165 • Temperature Rating Jet Black(RAL9005) 56-792-6-165 Chrome 56-792-9-165 • Order Length Custom 56-792-X-165 Dry Type Sprinklers are furnished *Eastern Hemisphere Sales Only based upon Order Length as Sprinkler Wrench measured from the face of the ceiling Specify: RFII Sprinkler Wrench, to the face of the sprinkler fitting P/N 56-000-1-075 (Ref. Figure 2). After the measure- ment is taken,round it to the nearest Sprinkler Boot 1/4 inch increment. Specify: Model DSB-2 Dry Sprinkler • Inlet Thread Connection Boot, P/N 63-000-0-002 1 inch NPT or ISO 7-R1 This Part Number includes one Boot, • Part Number from Table B two Strap Ties, and 1/3 oz. of Adhe- sive (a sufficient quantity for installing one boot),refer to Technical Data Sheet TFP591 for complete information. TFP515 Page 8 of 8 GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446 Telephone+1-215-362-0700 Copyright©2017 Tyco Fire Products,LP. All rights reserved. tgcc TEFLON is a registered trademark of DuPont '7 Fire Protection Products Eddythread 40 ,,,,,,,,,:,,, ,,,,,,,,,,,, , . A Lightweight Schedule 40 Replacement Pipe That Has a Corrosion Resistance Ratio of 1.0 Bull Moose Tube Company has been making pipe for a long time and is recognized as a producer of quality pipe • products. Eddythread 40 is designed with the same thoroughness as our other fine pipe products and now our customers have an option to buy a carefully designed replacement for Schedule 40 that: • Has a Corrosion Resistance Ratio of 1.0 • Has a Pressure Rating of 300 psi • Is Lighter Weight Than Schedule 40 • Is Approved by Factory Mutual and Listed by Underwriters Laboratories • Is Produced in Accordance to ASTM A-135 and A-795 • Can be Used With Standard Schedule 40 Threaded Fittings, Couplings and Valves • Is Produced From Steel With Excellent Properties of Strength and Threadability • Can be Used in Wet, Dry, Preaction, and Deluge Type Sprinkler Systems" • Offers Lower Freight Costs EDDYTHREAD 40 SPECIFICATIONS 1 1.461 1.083 70 1 1/4 2.070 1.418 51 1 1/2 2.547 1.654 44 2 3.308 2.123 30 CORROSION RESISTANCE RATIOS 1 1.00 1.00 ;o. 1 1/4 1.00 1.00 11/2 1.00 1.00 2 1.00 1.00 Eddythread 40 can be hot dipped galvanized to meet FM's requirement for dry systems 1819 Clarkson Road For additional information, C uL us A (� Chesterfield, MO 63017 contact your salesperson today at j BULL MOOSE TUBE COMPANY (800)325-4467 (800)325-4467 or(636)537-2600 LISTED CJ FAX:(636)537-2645 in the USA,or from Canada IN ww.bullmoosetube.com call(800)882-4666 41> A CUM)company e-mail:salesnbullrnoosetube.com APPROVED . All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation. 8/08 .1,,,..-,..,-,:.-.: :, :.':::::.:„.. • _ ..,.... . >T, _.. ,..... :'- • •, . ,.. Ductile. ... Iran Threaded Fittin s ,, :,..., ..„.____.,,,,,.„,...:::..... ,:;,.....i.: .. . .....„:„. . . ...., ,,..,...„. . ,, . :. ; ,,,.. .:.„,., ,,,..,. .. .,„ . , . .......... : ,. .,,,. .;. . ..... : .„ ,..., , , , , ....,...,, .. , , ..., .....„.., . . ,.. , :‘ , :;.... . . .........__ „ . :„..... ..,:, . .: .. ,.....„.,,, . .. c,...,..... , . ........ .. , . , ,..,, ... ; . , ..„ . , , ..„..,......., . ,, , .... . „ ........ . , ,,,..,., . ..„._„... ,_ „..,..., . . ..,..... . . , . ... ,, . . . , ,- ,, , . . : _ . .,..,,,,, ,.. ....:. .„ , .. .. . „ . ,....„,...:: x, , _ ,. , .„ ..., ...,„ . . .., ..„,,,,,..„....f.,,..., .... .. . ,,..4.,..,., .,...... : i „.:.,., ... „ „. . .„ . . , ,.: ..,,,.,.......,:........„,...,.;:•..,,,„:„.„ .., ..,. ,... ..• ...,... ,:.:._ , ...:„... ...,......,.,„ ,,,... , H .....„.. I -.:„ .• :...:::.„.,,.,,,,„,,,,,„.,,, ..ts,. . . „,, . ; I ,:i.,::„.:.:.:....,:r.' ', , ',': . .;, 4x” rY 'iiP% qk°:',' ,•'':'-'4,,,,,',',•°:''.+:.:'•'•t • .. ..,� i'°.” 'ills M�:til ii gyp'' ,i.;-arn� .j P f'� '14. C ¢a M1 „ '':'' '4 '''' ':11'.illt•''',..i:!;I:'•,.:*4::•'''ii1:,;:ti.;i„.::;'-'''',"$'''-'1;''':6,i''''k'' ,4,‘','''',i':;'i—*('?°:'!';'''':';',',*•#''''''.;,1!...;*;'''°.::::;'•;:','°i:':,....;':;:::;:j2.''' -.*.i'',.:':'°•••:;',.i.'''',-1*.:''T'l:-*:::::;;'',.';''',,,11':.-;,.'1':;':'',,.:': ''' ',;°•:;',';,..*; • iliflii • J t nyj t'(r i tddt i."J',�y • r' 14, „ ,' ,.• +` .:1�9 x + fi, , , .4 + r."` d t,M t y;d a „r P r 7” i 4 P t d tpy . 4i t F ^ tg 1 „ ° f� St**•: `C^ `!. u f a 7 •!tX r s J '� i 6 ,fey € , ,;7 - rtl • 3 nr t...trtV41.:Aktfi-%--.t--•'''-Vt r*.,:i" 4-,:-,-,- S -V,1 I it • C I t t ,..*4 £¢ " I N T E R N A T I O N A L Ductile Iron Threaded Fittings Specifications • branded ductile iron threaded fittings are UL Listed and FM Approved act 500�psi US • Rated to 300 WSP • Ductile iron castings conform to ASTM A536 LISTED 414:).11'' • Fitting dimensions conform to ASME B16.3 • Bushings and plugs conform to ASME B16.14 • Fittings are 100% air tested APPROVED • NPT threads on all fittings conform to ASME B 1.20.1 • Independent lab verification that fittings meet applicable chemical &physical properties • Manufacturing facilities are ISO 9001:2008 and ISO 14001 • Temperature Working 300# PressureClassThreaded, NonshockFittings psiG Degrees F -20 to 100 500 150 -_`a, 500 200 480 250 �. 460 .- 300 440 350 420 ; 400 400 450 380 500 360 550 - 340 Y 600 320 650 I '` 300 r ,. r y, 1: " 1 ucti e ron ittings- ass 1 i 1 v I QUALITY P1.11I. c ® us 41/111 APPROVED Fig. 35E 3-90°Elbow LISTED A Size A Packing Weight 1is,a Part Number in in Inner Master lb + 1/2 35E 3004 1.13 100 200 0.2 I - 3/4 35E 3006 1.31 70 140 0.3 1�i � A 1 35L 3010 1.50 40 80 0.5 1-1(4 35E 3012 1.75 25 50 0.8 1-1/2 35E 3014 1.94 18 36 1.1 2 35E 3020 2.25 10 20 1.8 2-1/2 35E 3024 2.70 4 8 3,2 Fig. 35RE3-90°Reducing Elbow B Size A B Packing Weight . :.,i�' Part Number in in in Inner Master lb " `r 111_,-....„ 3/4 x 1/7 350E3006004 1.20 1.22 80 160 0.3 -i� 1 x 1/2 35RE3010004 1.26 1.36 70 140 0.4 1 x 314 358L3010006 1.38 45 50 100 0.4 A 1-1/4 x 1/2 35RE3012004 1.34 1.53 35 70 0.5 ��qi 1-1/4 x 3/4 3513E3012006 1.45 1.63 35 70 0.6 1-1/4 x 1 35RE3012010 1.58 1.67 30 60 0.7 1-1/2 x 1/2 350E3014004 1.52 1.75 30 60 0.6 1-1/2 x 3/4 35RE3014006 1.52 1.75 25 50 0.7 1-1/2 x 1 358E3014010 1.65 1.80 20 40 0.8 1-1/2 x 1-1/4 35RE3014012 1.82 1.88 18 36 1.0 2 x 1/2 350E3020004 1.60 1.97 18 36 1 0 2 x 3/4 358E3020006 1.60 1.97 18 36 1.0 2 x 1 350E3020010 173 2,02 16 32 1.2 2 x 1-1/4 35RE3020012 1.90 2,10 12 24 1.3 1 2 x 1-1/2 3519E3020014 2.02 2.16 10 20 1.5 2-1/2 x 1-1/2 35RE3024014 2.16 2.51 6 12 2.2 2-112 x 2 358E3024020 2.39 2.60 6 12 2,5 Fig. 35F 3-45°Elbow Size Part Number g g XA Packin Wei ht , in -- in Inner Master ----ib - ,./ 111\\ 1/2 3o 3004 0 88 150 300 0.2 3/4 35F 3006 0.98 80 160 0.3 � 1 3513010 1.13 40 80 0.5 1-1/4 35F3012 1.29 25 50 0.7 �IR �A 1-1/2 35F 3014 1 44 20 40 1.0 2 35F 3920 1.69 10 20 1.6 2-1/2 35F 3024 1 95 4 8 2.7 Fig. 35T3- Tee Size A Packing Weight Part Number -- in in Inner Master lb i��� A 1/2 35T 3004 1.13 80 160 0.3 111113/4 35T 3006 1.31 30 60 0.5 1 35T 3010 50 25 50 0.7 1-1/4 35T 3012 1.75 10 20 1.1 c )It 1 1-1/2 351 3014 1 9.1 10 20 1.5 2 35T 3020 225 6 12 2.4 2-1/2 35T 3024 2 70 4 8 4.3 • 111 SMITH-COOPER INTERNATIONAL' • TOLI. FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com eI 1 uctile Iron ittings- ass I I I QUALM C?LIZ c ® us APPROVED Fig. 35RT3-Reducing Tee LISTED Size Part Number A B C Packing Weight st.JI�■1 in in in in Inner Master lb I LW C 3/4 x 1/2 35813006004 1 20 1.20 1 22 60 120 0.4 1 x 1/2 35813010004 1.26 1.26 1.36 30 60 0.6 -11--_t__ x 1/2x 1 35813010504010 50 1.36 1.50 30 60 0.6 1 x 3/4 35013010006 1.38 1.38 1.45 25 50 0.6 B > > 1 x 3/4 x 3/4 35013010006006 1.38 1 31 1.45 35 70 0.6 A 1 x 3/4 x 1 35013010006010 1.50 1.45 1.50 25 50 0.7 1-1/4x 1/2 35013012004 1.34 1.34 1,53 20 40 08 1-1/4 x 1/2 x 1-1/4 35813012004012 1.75 1.53 1.75 25 50 0.9 1-1/4 x 3/4 35013012006 1 45 1-45 1.62 15 30 0.9 1-114 x 3/4 x 1-1/4 35R13012006012 1.75 1.62 1.75 20 40 1.0 1-1/4x1 35013012010 1.58 1.58 1,67 15 30 1.0 1-1I4 x 1 x 1/2 35RT3012010004 1.34 1.26 1.53 25 50 0.7 1-1/4 x 1 x 3/4 35013012010006 1.45 1.38 1,63 20 40 0.8 1-1/4 x 1 x 1 35R13012010010 1.58 1.50 1.69 20 40 0.9 1-1/4 x 1 x 1-1/4 35813012010012 1.75 1.69 1.75 15 30 1.0 1-1/2x1/2 35813014004 1.41 1.41 1.66 16 32 1.0 1 1/2 x 1/2 x 1 1/4 350T3014004012 1.81 1.56 1.88 24 48 1.1 1-1/2 x 1/2 x 1-1/2 35813014004014 1.94 1.66 1.94 12 24 1.2 1-1/2x3/4 35013014006 1,52 1.52 1.75 16 32 1.1 1-1/2x3/4x1-1/4 35813014006012 1.94 1.66 1.88 20 40 1.1 1-1/2 x 3/4 x 1-1/2 35RT3014006014 1.94 1.75 1_94 18 36 1.2 1-1/2 x 1 35013014010 1.65 1.65 1.80 12 24 1.2 1-1;2 x 1 x 1,2 35013014010004 1.44 1 25 1.69 20 40 0.8 1-1/2 x 1 x 3/4 35013014010006 1.50 1.44 1.75 16 32 0.9 1-1r2 x 1 x 1 35813014010010 1,65 1.50 1,80 16 32 1.0 1-1/2 x 1 x 1-1/4 35R13014010012 1.82 1.67 1.88 12 24 1.2 1-1/2 x 1 y 1 1/2 35013014010014 1 94 1.80 1.91 12 24 1.3 x 1-1/2 x 1-1/4 35813014012 1.82 1.82 1.88 12 24 1.4 1 1/2 x 1-1/4 x 1/2 35013014012004 1.41 1.34 1.66 16 32 0.9 1 1-1/2 x 1-1/4 x 3/4 35013014012006 1.52 1.45 1.75 16 32 1.0 ' 1-1/2 x 1-1/4 x 1 35813014012010 1.65 1.58 1 80 16 32 1.1 1-1/2 x 1-1/4 x 1-1/4 35013014012012 1.82 1.75 1.88 14 28 1.3 1-1/2 x 1-1/4 x 1-1/2 35813014012014 1,94 1.88 1.94 14 28 1.4 2 x 1/2 35813020004 1.49 1.49 1.88 10 20 1.5 2 x 3/4 35813020006 1.60 1.60 1.97 10 20 1,6 ' 2 x 1 35813020010 1.73 1.73 2.02 8 16 1.7 2 x 1x'2 35813020010020 2.25 2.02 225 8 16 1.9 2 x 1-1/4 35R13020012 1.90 1.90 2.10 8 16 1.9 2 x 1 1 4 x 2 35813020012020 2.25 2.10 2.25 8 16 2.0 2x 1-1/2 35813020014 2.02 2.02 2.16 8 16 2.1 2 x 1 1/2 x 1/2 35113520014004 1.49 1,41 1.88 10 20 1.3 2 x 1-1/2 x 3/4 35413020014006 1.60 1.52 1.97 10 20 1.4 2 x 1-1/2 x 1 35173020014010 1.73 1.65 2,02 8 16 i.5 2 x 1-1/2 x 1-1/4 35RT3020014012 1.90 1.82 2.10 8 16 1.7 2 x 1-1/2 x 1-1/2 35R13020014014 2.02 1.94 2.16 8 16 1.8 Fig. 35RT3-Bull Head Tee ;' Size Part Number A B C Packing Weight �' i..r in in in in Inner Master lb C 3;4 x 1 35813006010 1.45 1.45 1.37 30 60 0.6 MillinI 1 x 1-1/4 35813010012 1.67 1.67 1.58 20 40 0.9 1 x 1-1/2 35813010014 1.80 1.80 1 65 15 30 1.0 t F A >( B > 1-114 x 1 x 1-1/2 35BT3012010014 1.88 1.80 1.82 15 30 1.2 1-1/4 x 1-1/2 35813012014 1.88 1.88 1 82 15 30 1_3 1-114 x 2 35B13012020 2.10 2.10 1.90 10 20 1.6 1-12 x 1-1/4 x 2 35813014012020 2.16 2.10 2.02 10 20 1.8 1-1/2 x 2 35813014020 2.16 2.16 2.02 8 16 1.8 SMITH-COOPER INTERNAFIONAL® • TOLL FREE 1-800-766-0876 • FAX(323)880-445() • NAwvx.srninccooper.com 112 -- '' I �" I ucti e ron ittings- ass I I I T 1. (AWN,PLt13 C ® US APPROVED A Fig. 35CP3 -Straight Coupling with Ribs LISTED Size 0 III Part Number A Packing Weight in in Inner Master lb - 2 35C83004 1,38 200 400 0.1 3/4 35CP3006 1.63 100 200 0.2 1 35CP3010 1.75 60 120 0.4 1-1;4 35C83012 2.00 35 70 0.5 1-1/2 35CP3014 2.19 25 50 0.7 2 35CP3020 2.62 15 30 1.2 2-1/2 35CP3024 3.00 9 18 2.2 • Fig. 35RC3 -Hex Reducing Coupling Size A Packing Weight Part Number WW1 - in in Inner Master lb ® x 1/2 358C3010004 1.69 80 60 0.3 ' A 1 x 3/4 35RC3010006 1.669 60 120 0.4 1-1/4x314 35RC3012006 2.06 40 80 0.6 ;' ; 11 2 x 1 (not hex) 35RC3020010 2.81 20 40_ 1.0 Fig. 35HB3 -Hex Bushing Size A Packing Weight B in Part Number in Inner Master lb t ' 1 x 1(2 35HB3010004 1 06 180 360 0.2 ¶ H! A 1 x3/4 35HB3010006 1.06 180 360 0.1 1-1/4x 1 35HB3012010 1.19 90 180 0. 1-1/2 x 1 35HB3014010 1,25 75 150 0.4 1-1/2 x 1-1/4 35HB3014012 1.25 75 150 0 3 1t. 2 x 1 35HB3020010 1.38 40 80 0.6 2 x 1-1(4 35HB3020012 1.38 40 80 0.6 2 x 1-1/2 35HB3020014 1.38 40 80 0.6 Fig. 35SP3 -Square Head Plug Size A Packing Weight in Part Number in Inner Master lb 1/2 35SP3004 0,94 600 1200 0.07 A 3/4 35SP3006 112 350 700 0.1 TrAilli 1 35SP3010 1.25 200 4000.1 1-1/4 35SP3012 1.37 100 200 0.3 1-1/2 35S83014 1.44 80 160 0.4 I i 2 35S83020 1.50 45 90 0.6 Fig. 35U 3-Union with Brass Seat < A Size Part Number A Packing Weight €; °� ,--- in` in Inner Master lb , ��' 350 3010 2.19 20 40 1.0 In' 1-1/4 35U 3012 250 15 30 1.2 1-1/2 35U 301,4 2 62 10 20 1.7 �`a 2 35U 3020 3.12 6 12 2.4 113 SMITH-COOPER 1\TER\rVT IO\.'\.L/ • TOLI, FREE 1-800-766-0076 • FAX.(323)890-4456 • ww,wsmithcooper.com `"�E> 4 c®� FM 'yds) LPCB �P � ��1' LISTED 491a/27 SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 922 The Style 922 Outlet-T provides a convenient method of incorporating' ,3/4,and 1"/15,20 and 25mm outlets for directly connecting sprinklers,drop nipples,sprigs,gauges,drains and other outlet products.Available for 11/4 through 76.1 mm/32 to 76.1 mm piping systems,Style 922 outlets are UL/ULC Listed, LPCB and FM Approved for branch connections and VdS f Approved for direct sprinkler connection only on wet and dry systems. The locating collar engages into the hole prepared in the pipe.When tightened,the assembly compresses the gasket onto the OD of the pipe.The Style 922 Outlet-T is UL/FM rated up to 300 psi/2068 kPa and VdS rated up to 16 bar at the ambient temperatures typical for fire protection systems. Style 922 is suitable for use on standard,lightwall,Schedule 5 and other specialty pipes." Contact Victaulic for other optional coatings. "Consult Section 10.01 for specific listings/approvals. MATERIAL SPECIFICATIONS Housing:Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. Gasket: • Grade"E"EPDM-Type A (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc.and Approved by Factory Mutual Research for wet and dry(oil free air)sprinkler services up to the rated working pressure using the Grade"E"Type A Gasket System. Bolts/Nuts:Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. Housing Coating: • Orange enamel(North America, Latin America,Asia Pacific) • Red enamel(Europe) JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date • www.victaulic.com ictaul.C° VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. v- REV G 5<'. IPS CARBON STEEL PIPE.. HOLE CUT PRODUCTS 10.52 T4 �let- STYLE 922 DIMENSIONS Nominal Size Hole Approx. inches/mm Diameter Dimensions-inches/millimeters Weight Each Y1.:.......... -1 I,a k - sii 183 1.10 3.87 256 1.0 • V ��� 3 �C 2 3s.0 46 5 27.9 98 3 65 0 0.45 T 3/16 1.28 1.83 1.10 3 87 2.56 1.1 .AM_�■ t 2r 30.2 32.5 46.5 27.9 98.3 65.0 0.50 •Mir • w iti '3/16 1.52 2.18 1.10 3.87 2.56 1.2 �� I I 11 25 30.2 38.6 55.4 27.9 98.3 65.0 0.54 1 1 02 1 3/16 1.42 1.95 1.22 4.08 2.56 12 40 X 15 30.2 36.1 49.5 31.0 103.6 65.0 0.54 3/a 13/16 1.40 1.95 1.22 4.08 2.56 1.2 20 30.2 35.6 49.5 31.0 103.6 65.0 0.54 1 13/16 1.64 2.30 1.22 408 2.56 1.3 25 30.2 41.7 58.4 31.0 103.6 65.0 0.59 2 / 1 3/16 1.66 219 1.46 4.60 2.56 1.3 50 X 15 30.2 42.2 55.6 37.1 116.8 65.0 0.59 3/ '.. 1 3/16 1.64 2.19 1.46 4.60 2.56 1.4 20 30.2 41.7 55.6 37.1 116.8 65.0 0.64 1 1 3/16 1.88 2 54 1.46 4.60 - 2.56 1.5 25 30.2 47.8 64.5 37.1 116.8 65.0 0.68 2'/z V. 13/16 1.91 2.44 1.71 5.40 256 1.6 65 X 15 30.2 48.5 62.0 43.4 137.2 65.0 0.73 / 1 3/16 1.89 2.44 1.71 5.40 2.56 1.6 20 30.2 48.0 62.0 43.4 137.2 65.0 G_'3 1... 13/16 2.13 2.79 1.71 5.40 2.56 1.6 25 30.2 54.1 70.9 43.4 137.2 65.0 0.73 76.1 mm X %2 13/16 1.91 244 171 5.50 2.56 1.6 15 30.2 48.5 62.0 43.4 139.7 65.0 0.73 Va 13/16 1.89 2.44 1.71 5.50 '. 2.56. 1.6 20 30.2 48.0 62.0 43.4 139.7 65.0 0.73 1 13/16 2.13 2.79 1.71 5.50 2.56 1.7 25 30.2 54.1 70.9 43.4 139.7 65.0 0.80 t Victaulic female threaded products are designed to accommodate standard NPT or BSPT(optional) male pipe threads only.Use of male threaded products with special features,such as probes,dry pen- dent sprinklers,etc.,should be verified as suitable for use with this Victaulic product.Failure to verify suitability in advance may result in assembly problems or leakage. *Center of run to engaged pipe end for NPT threads(dimensions are approximate). www.victaulic.com ictaul.c° VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. - --- 10,52 2 REV IPS CARBON STEEL PIPE HOLE CUT PRODUCTS 10.52 kr eery STYLE 922 PERFORMANCE Equivalent Length of 1 inch Schedule 40 Steel Pipe(per UL Run Size x Outlet Size 213,Section 16)(C=120)*,FT '4 8.5 32 X 25 2.6 /z ___. .X.. 8.5 _...... 40 25 2.6 • 2 X 1 8.5 50 25 2.6 2/z.... .. 8.5 65 X 25 2.6 76.1mm X 1 8.5 25 2.6 *Hazen-Williams coefficient of friction is 120 www.victaulic.com VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICt`au Usc REV C 113.52,_3 t - STYLE 922 INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. • For complete contact information,visit www.victaulic.com 10.52 3355 REV G UPDATED 12/2009 ✓CtauI.C' VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 10,52 Pipe Hangers Fig.200- "Trimline" Adjustable Band Hanger (B-Line Fig.B317ONF) ®TalLccl • Fig.200F- "Trimline" Adjustable Band Hanger with Felt Lining (B-Line Fig.B317ONFF) Fig. 200C- "Trimline" Adjustable Band Hanger with Plastic Coated (B-Line Fig.B317ONFC) LISTED . Fig.200S - "Trimline" Adjustable Band Hanger with Non-Captured Nut Size Range: Fig. 200 - 1/2" (15mm)thru 8" (200mm) pipe Material: Steel, Pre-Galvanized to G90 specifications Function: For fire sprinkler and other general piping purposes. Knurled swivel nut design permits hanger adjustment after installation. '---,..'-.7% Features: , 8 ;__ • • (1/2" (15mm)thru 2" (5omm)) Flared edges ease installation for all pipe (� ,� types and protect CPVC plastic pipe from abrasion. Captured designer i ' keeps adjusting nut from separating with hanger. Hanger is easily a B /' installed around pipe. A !1 For hanger with non-captured nut order Fig. 200S. ;i • (21/2" (65mm)thru 8" (20omm)) Spring tension on nut holds it securely in '__. hanger before installation.Adjusting nut is easily removed. Approvals: Underwriters Laboratories listed (1/2" (15mm)thru 8" (200mm)) Fig.200-1/2.200-3/4 in the USA(UL) and Canada (cUL)for steel and CPVC plastic pipe and Fig.200-1 to 200-2 Fig.200-21/2 to 200-8 Factory Mutual Engineering Approved (FM) (3/4" (20mm)thru 8" (2oomm)). Conforms to Federal Specifications WW-H-171 E &A-A-1192A,Type 10 and Manufacturers Standardization Society ANSI/MSS SP-69& SP-58, Type 10. ,,,iiii Maximum Temperature: 650°F (343°C) •-, avi Finish: Pre-Galvanized. Stainless Steel materials will be supplied with (2) hex nuts4ii ii,1$ in place of a knurl nut. f 1 Order By: Figure number and pipe size Designed to meet or exceed requirements of - FMDS20. �� ; ,..p Fig.200 Fig.200C Fig.200F Pipe Size Rod Size A B Approx.Wt./100 ° Part No. in. (mm) in. (mm) in. (mm) lbs. (kg) ad 200-1/2 1/2 (15) 3/8"-16 31/8' (79.4) 25/8" (66.7) 11 (5.0) le 200-3/4 3/4" (20) 3/8"-16 31/8" 179.4) 21/2" 163.5) 11 (5.0) A 200-1 1" (25) 3/8"-16 33/8" (85.7) 25/8" (66.7) 12 (5.5) 200-11/4 11/4" (32) 3/8"-16 33/4" (94.0) 27/8" (73.0) 13 (5.9) 1:C' 200-11/2 11/2" (40) 3/8"-16 37/8" (98.4) 27/8 (73.0) 14 (6.4) 1 200-2 2" (50) 3/8"-16 41/2" (114.3) 3" 176.31 15 16.9) 200-21/2 21/2" (65) 3/8"-16 56/8" (142.9) 41/e" (104.7) 27 (12.3) 200-3 3" (75) 3/8"-16 57/8" (149.1) 4" (101.6) 29 (13.3) Fig.200S 200-31/2 31/2" (90) 3/8"-16 73/8" (187.3) 51/4" (133.3) 34 115.6) 200-4 4'' (100) 3/8"-16 73/8" (187.3) 5" (127.0) 35 (16.0) 200-5 5" (125) 1/2"-13 91/8" (231.8) 61/4" (158.7) 66 (30.2) 200-6 6' (150) 1/2"-13 101/8" (257.21 63/4" (171.4) 73 (33.4) 200-8 8" (200) 1/2"-13 131/8" (333.4) 83/4" (222.2) 136 (62.3) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. Fire Protection Solutions 21 B-Line bY Ellifi Threaded Accessories B3205 - Threaded Rod (right-hand threads - both ends) (TOLCO Fig. 103) - B3205L - Threaded Rod (right& left hand threads) TL �� Size Range: 3/8"-16 thru 3"-4 rod Specify Length 111�1111 1 Material: Steel Function: Recommended for use as a hanger support in hanger assemblies. TL Rod is threaded on both ends with right hand threads of the length shown.Also available with left and right hand threads-specify Fig. B3205L when ordering. -41)\ A 9 P YThread Size Maximum Temperature: 750°F(399°C) . Finish: Plain. Contact B-Line for alternative finishes and materials. Order By: Part number, rod size, length and finish Standard Design Load Thread Size Thread Length TL 650°F(343°C) 750°F(399°C) Part No. A in. (mm) Lbs. (kN) Lbs. (kN) B3205-3/8 x'L' 3/8"-16 21h" (63.5) 730 (3.25) 572 (2.54) 83205-1/2 x'L' 1/2"-13 21/2" (63.5) 1350 (6.00) 1057 (4.70) B3205-5/8 x'L' 5/8"-11 21/2" (63.5) 2160 (9.61) 1692 (7.52) B3205-3/4 x'L' - 3/4"-10 3" (76.2) 3230 (14.37) 2530 (11.25) B3205-7/8 x'L' 7/8"-9 31/2" (88.9) 4480 (19.93) 3508 (15.60) B3205-1 x'L' 1"-8 4" (101.6) 5900 (26.24) 4620 (20.55) B3205-11/8x'L' 11/8"-7 41/2" (114.3) 7450 (33.14) 5830 (25.93) 83205-11/4 x'L' 11/4"-7 5" (127.0) 9500 (42.25) 7440 (33.09) B3205-11/2 x'L' 11/2"-6 6" (152.4) 13800 (61.38) 10807 (48.07) 83205-13/4 x'L' 13/4"-5 7" (177.8) 18600 (82.73) 14566 (64.79) B3205-2 x'L' 2"-41/2 8" (203.2) 24600 (109.42) 19625 (87.29) B3205-21/4 x'L' 21/4"-41/2 9" (228.6) 32300 (143.67) 25295 (112.51) B3205-21/2 x'L' 21/2"-4 10" (254.0) 39800 (177.03) 31169 (138.64) B3205-23/4 x'L' 23/4"-4 11" (279.4) 49400 (219.73) 38687 (172.08) B3205-3 x'L' 3"-4 12" (304.8) 60100 (267.32) 47066 (209.35) ATR -All Threaded Rod 120" (3.05m) Lengths (TOLCO Fig. 100) Fig. 99 - All Threaded Rod Cut To Length �n���� Size Range: 3/8"-16 thru 11/2"-6 rod in 120" (3.05m)lengths or cut to lengthy ����� Material: Steel Maximum Temperature: 750°F(399°C) Finish: Plain. Contact B-Line for alternative finishes and materials. a • Order By: Part number, rod diameter and finish Part No. Size x Length Threads Recommended Load Approx.Wt./100 Ft. ATR Fig.99 Per Inch Lbs. (kN) Lbs. (kg) ATR 1/4"X 120 99-1/4"x length 20 240 (1.07) 12 (5.44) ATR 3/8"x 120 99-3/8"x length 16 730 (3.24) 29 (13.15) ATR 1/2"X 120 99-1/2"x length 13 1350 (6.00) 53 (24.04) AIR 5/8"x 120 99-5/8"x length 11 2160 (9.60) 89 (40.37) ATR 3/4"x 120 99-3/4"x length 10 3230 (14.37) 123 (55.79) ATR 718"x 120 99-7/8"x length 9 4480 (19.93) 170 (77.11) ATR 1"x 120 99-1"x length 8 5900 (26.24) 225 (102.06) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. B-Line Pipe Hangers&Supports 236 Revised 4/28/2014 by :"f'• VERTICAL MOUNT SAMMYS SAMMYS° for Wood y Not less than Wood Flooringj„ . :. 2"nominal vndth Product Features (1-1/2") 4 a •No pre-drilling required. Not less than •Quick to install using the Sammy a"n°mina) thickness(2-1/2") (depth or side Wood Joist Nut Driver with an 18V cordless drill/driver. of vertical member) .-._, a •Saves time from traditional Double ck Ceiling ding methods. iift •Reduces installation cost. m*Ailltr , •Made in the U.S.A. ratannisodetboilompart T i 1 rest " Gam. tea.. 210(7/16"OSB) 1/4" 8002957 GST 100 1/4 x 1" 25 125 670(3/4"Ply) 1/4" 8003957 GST 200 1/4 x 2" 1760 (Fir) 25 125 1/4" 8004957 GST 300 1/4 x 3' 2060(Fir) E, ', 25 125 3/8" 8006957 GST.75 1/4 x 3/4' 564 (3/4"Ply) 25 125 CL 3/8" 8007957 GST 10 1/4 x 1° 210(7/16 OSB) 300 ti 25 125 670(3/4"Ply) "„ _ 3/8" 8008957 GST 20 1/4 x 2' 1760 (Fir) 850 1475 25 125 3/8" 8068925 GST 20-SS 1/4 x 2' 1760(Fir) z $50. 25 125 0- 3/8" 8009925 GST 25-380 3/8x2-1/2" 2113 (Fir) 1500 25 125 #14 Black 3/8" 8010957 GST 30 1/4 x 3" 2060(Fir) r1 15( ?�� " ,� 25 125 Nut Driver 3/8" 8069925 GST 30-SS 114 x 3" 2060 (Fir) 25 125 Part#8113910 3/8" 8011925 GST 40 114 x 4" 2180(Fir) . ";t ,#` = 25 125 ° 3/8" 8012925 GST 60 1/4 x 6 2230 (Fir) 25 125 1/2" 8013925 GST 2 1/4 x 2" 1760(Fir) ""'' `°'i°" 25 125 " 1/2 8014925 GST 2.5-380 3/8 x 2 1/2 2113 (Fir) 25 125 1/2" 8015925 GST 3 1/4 x 3" 2275(Fir) At 25 125 1/2" 8016925 GST 4 1/4 x 4" 2180 (Fir) 25 125 1/2" 8017925 GST 6 1/4 x 6" 2230(Fir) rx "" 25 125 #14 SW Red Nut Driver Part#8114910 SAMMY Swivel Head' for Wood Product Features •Eliminates distortion of threaded rod. •Saves time from traditional methods. •Accommodates up to 3'/2'x 12 pitch roof. •Reduces installation cost. •Allows 17°deflection from vertical. •Made in the U.S.A. -Rod Part Screw Ukterale UL Test Fit Tat lara Eloa- Case 1 Qty • 3/8".. 8139957 SH-GST 20 1/4 x 2" 1257(Fir) 1050 1475 25 125 125 I 3/8" 8141957 SH GST 30 1/4 x 3" 1720(Fir) 1500 1475 25 125 #14 Black Nut Driver SPECIAL NiJ1 S{STl#1:The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time.When the face of the driver comes into Part#8113910 contact with the material you are installing into,continue drilling until nut driver spins free.Installation is then complete.Warranty requires the use of the appropriate nut driver for installations. rThsFor the most up to date information,visit www.sammysuperscrew.com 4 v toot wus* *: mow`• SAMMYSHORIZONTAL MOUNT 0 -- SIDEWINDERS° for Wood j v ii.:.--_- Not less than 2"nominal width Product Features tti (1-1/2")up to 3-1/2"pipe;not less than ,,, ". 3"(2-t/2")nominal width 4"&5"pipe •No pre-drilling required. 1-----? Floor Joist •quick to install using the Sammy Minimum 2-112"from bottom for Nut Driver with an 18V cordless ' branch lines.Minimum 3"from i : bottom for main lines.Exce tion:This "; p drill/driver. requirement shall not apply to 2"or ' \ _ thicker nailing strips resting on top of steel teams. •Savesmethods.time from traditional r I •Reduces installation cost. •Made in the U.S.A. 4 ----;;''0? ' ite/Trus gg ---manufacturer .. , +1` d 'installation "Prbe required for k S available on pg 10) -,01-.7'-'; vals Model Resew mate UL7est aee :.:-.. , 0 _ {Iii Load abs) . 0 114" 8018957 SWG 100 1/4 x l" 622(Fir) -` ,,, " 25 125 114" 8019957 SWG 200 1/4 x 2' 1725 (Fir) n 25 125 318" 8020957 SWG 10 114 x 1" 622(Fir) + 25 125 * ��,, 3/8" 8021957 SWG 20 1/4 x 2" 1725 (Fir) 1050 25 125 3i8" 8073925 SWG 20-SS 1/4 x 2" 1725 (Fir) 4 "_i 25 125 #14 SW Red 1 Q" 3/8" 8022925 SWG 25-380 3/8 x 2-1/2" 2249 (Fir) 1500 25 125 ` Nut Driver °_ 318" 8023925 SWG 30 1/4 x 3" 1884 (Fir) 25 125 Part#8114910 1.Insert the appropriate nut driver into a 3/8"or 1/2";:rtabledrill. 1.Insert the appropriate nut driver into a 3/8"or 1/2"portable drill. 0 2.Insert the SAMMYS into the#14(black)nut driver(p/n 8113910).Drill 2.Insert the SAMMYS into the#14SW(red)nut driver(p/n 8114910).With drill - o should be in a vertical position. unit in a horizontal position and at a right angle to the structural member, begin installation. at 3.Push the face of the nut driver tight to the member.When the nut driver spins freely on the SAMMYS,stop drill and remove. 3.When the nut driver spins free on the SAMMYS,stop the drill and • remove. 4.The SAMMYS is now ready to receive 1/4",3/8",1/2"or metric all thread rod,bolt stock.(The 1/2"requires the#14SW red nut driver) 4.The unit is.now ready to receive 1/4",3/8"or metric all thread rod or bolt stock. . Note:When installing DSTR,follow the above instructions, then add retainer nut and torque to 20 foot lbs.for maximum Note:When installing SWDR,follow the above instructions,then add retainer nut 8... ,, pullout in purlin steel. and torque to 20 foot lbs.for maximum pullout in purlin steel. =" • ':-,t. Y: Ikj •.LRN.if •-,2, 701 , , , , f o .. .. ...-1...__ .• • SPEC AL NUT DRIVER SYSTEM:The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time.When the face of the driver comes into contact with the material you are installing into,continue drilling until nut driver spins free.Installation is then complete.Wa rarity requires the use of the appropriate nut driver for installations 5 To find a distributor near you,call 800-BUILDEX