FIRE ALARM SUBMITTAL
Washington Square
Lucky Brand
Submittal Version Date Siemens Job Number
44op-246074
Issued for Review 09.06.2018
Siemens Project Manager
Moses Frangopolous
Siemens Project Engineer
Garrick Youngberg,SET
Proprietary document for approval only
TABLE OF CONTENTS SIEMENS
BILL OF MATERIALS &
COMPONENT SPECIFICATIONS
FIRE ALARM POWER SUPPLY
BATTERY AND
VOLTAGE DROP CALCULATIONS
:;)
�w«
!0:41 (
��\
�
6\
> *,
��\
� . .
BILL OF MATERIALS SIEMENS
FIRE ALARM SUBMITTAL
Washington Square
Lucky Brand
Fire Alarm System
Panel Components
Item Model# Siemens Part# Quantity Color Mfg Description
1 E60H-24MCC-FW 7 White Wheelock Multi-Candela Speaker/Strobe-White,Ceiling Mount-High Fideli
2 STW 2 White Wheelock Exceder Multi-Candela Strobe-White,Wall Mount
3 TRI-R 500-896224 1 Siemens MXL Control Relay Module w/Monitor Point
4 FP-11 500-095112 1 White Siemens MXL Smoke Detector-Photo
5 FDBZ492 554319-B22-A1 1 Grey Siemens Air Duct Housing
* Catalog Cut Sheets not available
PROPRIETARY DOCUMENT FOR APPROVAL ONLY 9/6/2018
Effective January 2016
Technical Data TD450017EN Supersedes January 2015
Wheelock E5OH & E6OH High Fidelity
Speakers & Speaker Strobes
Description
:rt The Wheelock E50H Wall and E60H Ceiling Speakers and Speaker
q# f Strobes are designed for high fidelity sound output for indoor
applications. With the widest frequency response range(300
to 8000 Hz)in the industry,the EH product line features leading
r intelligibility with crisp,clear voice messages and tone signaling,
ideal for emergency communications, mass notification,and voice
{ evacuation.
Providing a sleek aesthetic appearance,the wall and ceiling
appliances feature dual voltage(25/70 VRMS)capability and
• "" • field-selectable taps from 1/8 to 2 watts. For faster and easier
installation,the low profile design incorporates a speaker mounting
plate,and each model has a built-in level adjustment feature and
snap-on cover with no visible mounting screws.
•::
::::•• ; For visible signaling to meet the hearing impaired,the Series EH
• •:• ;�;;:; Speaker Strobe models incorporate the low current draw of the RSS
••••.:•'.•.;% �' Strobes.
:,. ;•• Strobe options for wall mount models include Wheelock patented
• 2 MCW multi-candela strobe with field selectable candela settings
of 15/30/75/110cd or the high intensity MCWH strobe with field
„ ice selectable 135/185cd.
Ceiling mount models are available in Wheelock patented MCC
multi-candela ceiling strobe with field selectable intensities of
15/30/75/95cd or the high intensity MCCH strobe with field
selectable 115/177cd.
The strobe portion of all Series EH Speaker Strobes may be
synchronized when used in conjunction with the Wheelock DSM
._ Sync Modules,Wheelock Power Supplies or other manufacturers
panels incorporating the Wheelock Patented Sync Protocol.
Wheelock synchronized strobes offer an easy way to comply with
ADA recommendations concerning photosensitive epilepsy.
Series EH Speaker Strobes are UL Listed for indoor use under
t Standard 1971 (Signaling Devices for the Hearing-Impaired)and
Standard 1480(Speaker Appliances),and ULC listed under CAN/
ULC-S526(Usual-audible Signal Appliances,Fire Alarm)and under
CAN/ULC-S541 (Speakers, Fire Alarm). All inputs employ IN/OUT
wiring terminals for fast installation using#12 to#18 AWG wiring.
Color options for the Series EH Speakers and Speaker Strobes are
red and white.
F:T•
Powering Business Worldwide
Technical Data TD450017EN Wheelock E5OH & E6OH High Fidelity
Effective January 2016 Speakers&Speaker Strobes
Features Drawings
• High Fidelity Sound Output
5.00 1-{-1.46--
• Efficient design for high intelligibility at minimum wattager.
across a frequency range of 300 to 8000 HZ
• 6 Field Selectable Settings in 1 Device 04111ggo <<;�'�
• Wall mount models are available with Field Selectable Candela SA0 i��
Settings of 15/30/75/110cd or 135/185cd(Multi-Candela models) �I' '
or 1575cd(Single Candela model) 14� -
• Ceiling mount models are available with field selectable candela °ggig ii.
settings of 15/30/75/95cd or 115/177cd(Multi-candela models)
• Field Selectable Taps
• 1/8 watt up to 2 watts
• 25 or 70 VRMS operation 2338 •___
• Easy-to-Install
• Low profile design incorporates speaker mounting plate for
faster and easier installation -,......„,,„„,,,
j
ai l'1
• Snap on grille cover with no visible mounting screws
• Quick installation with IN/OUT screw terminals using#12 to Ii'l
#18 AWG wires taiHregtO
lip.
„ga°°
• 4"square backbox prevents wire damage
• Series E50H-No extension ring required
• Series E60H-Optional Extender(E60 Ext)is available for
mounting to 4" square backboxes
• Strobe Synchronization Components Figure 1.E5OH(top)and E6OH(bottom)Speakers-Front&Side Views
• Meet synchronizing standards with Wheelock's DSM Sync
Modules, PS Power Supplies or SAFEPATH products
• Compliance
• UL 1971, UL 1480, ULC-S526, ULC-S541 ( ¢ i I
• Low frequency requirements of UL 464(520 Hz)to meet l
NFPAs 520 Hz tone requirements for sleeping areas
• California State Fire Marshal(CSFM) . , `tit,
• ADA/NFPA/ANSI/OSHA li000.000.00.000.0.0
t
• FCC Part 15, ICES Blv
Note: All CAUTIONS and WARNINGS are identified by the symbol A.All
' warnings are printed in bold capital letters. L.J
3.020
A WARNING ,.— 229 2.223--
PLEASE
.2�PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION
INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING
THIS PRODUCT.VISIT WWW.EATON.COM/MASSNOTIFICATION OR
CONTACT EATON FOR THE CURRENT INSTALLATION INSTRUCTIONS. i.T�'�g
FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR 1.01::::::°'::::::i::::),;°':::-. i �•I�i'
WARNINGS COULD RESULT IN IMPROPER APPLICATION,INSTALLATION I 1 may■
AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, oo OO�o�o,00 oo 111110
I(
WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR \
DEATH TO YOU AND/OR OTHERS. '
Figure 2.E6OH(top)and E6OH(bottom)Speaker Strobes-Front&Side Views
General Notes
• Strobes are designed to flash at 1 flash per second minimum over
their"Regulated Voltage Range:' Note that NFPA-72 specifies a
flash rate of 1 to 2 flashes per second and ADA Guidelines specify
a flash rate of 1 to 3 flashes per second.
• All candela ratings represent minimum effective Strobe intensity
based on UL 1971.
2 EATON wwv.eaton.com
Wheelock E5OH & E6OH High Fidelity Technical Data TD450017EN
Speakers&Speaker Strobes Effective January 2016
Table 1. Maximum RMS Current
UL/ULC Max Current a
24MCW/24MCC 24MCWH/24MCCH
241575W
Regulated Voltage
Model Range VDC 15 30 75 95 110 115 135 177 185
E501-1 16.0-33.0 0.060 0.092 0.165 0.220 0.300 0.420
E6OH 16.0-33.0 0.060 0.105 0.189 0.249 0.300 0.420
Table 2. UL Listed Models and Ratings
UL Reverberant dBA at 10 Feet b
Model 1/8 watts c 1/4 watts 1/2 watts 1 watts 2 watts
E5OH Speaker Strobe 73 76 79 82 84
E6OH Speaker 74 77 80 83 85
E6OH Speaker Strobe 74 77 80 82 85
Table 3. Specification&Ordering Information
Mounting Sync w/DSM or
Model Order# Strobe Candela Red White Lettering Wall Ceiling Options Wheelock Power Supplies
Speakers
E5OH-R 9863 X No Lettering X E,AA
E50H-W 9864 X No Lettering X E,AA
E50H-ALW 3577 X ALERT X E,AA
E60H-R 9867 X No Lettering X E
E60H-W 9874 X No Lettering X E
E60H-ALW 3554 X ALERT X E
Speaker Strobes
E50H-24MCW-FR 0092 15/30/75/110 X FIRE X E,BB X
E50H-24MCW-FW 0093 15/30/75/110 X FIRE X E,BB X
E50H-24MCW-ALR 3559 15/30/75/110 X ALERT X E,BB X
E50H-24MCW-ALW 3560 15/30/75/110 X ALERT X E,BB X
E50H-24MCW-NW 3575 15/30/75/110 X No Lettering X E,BB X
E50H-24MCWH-FR 0094 135/1 85 X FIRE X E,BB X
E50H-24MCWH-FW 0097 135/185 X FIRE X E,BB X
E50H-24MCWH-ALW 3561 135/185 X ALERT X E,BB X
E60H-24MCC-FR 0187 15/30/75/95 X FIRE X E x
E60H-24MCC-FW 0188 15/30/75/95 X FIRE X E X
E6OH-24MCC-NW 0950 15/30/75/95 X No Lettering X E X
E60H-24MCC-ALW 3555 15/30/75/95 X ALERT X E x
E60H-24MCCH-FR 0189 115/177 X FIRE X E x
E60H-24MCCH-FW 0190 115/177 X FIRE X E x
Extender Ring
E60EXT-R' 3578 X
E60EXT-W' 3757 X
Table 4. Specifications
Physical
Material/Lens(Material type) Red or white textured UV stabilized,colored impregnated engineered plastic.Exceeds 94V-0 UL flammability rating./
GE LEXAN 943A
Weight E5OH Speaker:1.5 lbs(0.68 kg);E5OH Speaker Strobe 1.6 lbs(0.73 kg);E6OH Speaker:1.6 lbs(0.73 kg);E6OH Speaker
Strobe 1.7 lbs(0.77 kg);
Dimensions E5OH Speaker: 5"W x 5"H x 1.47"D;E5OH Speaker Strobe: 5"W x 6.74"H x 2.58"D;E6OH Speaker:7.38"Diameter x
.83"D;E6OH Speaker Strobe:7.38"Diameter x 3.02"D
Operating Temperature Indoor:33.8°F to 120.2°F(0°C to 49°C)and maximum humidity of 93%
Mounting&Wire Connections
Mounting(indoor only) 4"square backbox prevents wire damage;Series E5OH-No extension ring required;Series E6OH-Optional Extender
(E60 Ext)is available for mounting to 4"square backboxes,E50 SSB,E50 SB for surface mount of E5OH
Wire Connections #12 through#18 AWG
Power&General
Operating voltage 25/70 VRMS
Strobe Output Rating UL 1971,ULC S526
Strobe Flash Rate Strobes are designed to flash at 1 flash per second
Synchronization Models Strobes can be synchronized with Wheelock's DSM Sync Modules,PS Power Supplies or SAFEPATH products,using
Wheelock patented sync protocol
Frequency Range 300 Hz to 8000 Hz
a RMS current ratings are per UL maximum RMS method.UL max current rating is the maximum RMS current within the listed voltage range(16-33v for 24v units). For
strobes the UL max current is usually at the minimum listed voltage.(l6v for 24v units). For audibles the max current is usually at the maximum listed voltage(33v for
24v units). For unfiltered FWR ratings,see installation instructions.
b dBA ratings are based on testing under UL Standard 1480.
c 1/8 watt tap is for private mode only.
d E60 EXT is an attractive extender ring that mounts behind the speaker to permit mounting to a 4"square x 2 1/8"deep electrical box without need for an extension
ring on the box.
EATON www.eaton.com 3
Technical Data TD450017EN Wheelock E5OH &E6OH High Fidelity Speakers&Speaker Strobes
Effective December 2015
Architects and Engineers Specifications
Wheelock E50H-The speaker appliances shall be Wheelock E5OH Wheelock E6OH-The speaker appliances shall be Wheelock
High Fidelity Speakers,and the High Fidelity Speaker Strobe appli- E6OH High Fidelity Speakers,and the High Fidelity Speaker Strobe
ances shall be Wheelock E5OH Speaker Strobes or approved equals. appliances shall be Wheelock Series E6OH Speaker Strobes or
The speakers shall be UL Listed under UL 1480 for Fire Protective approved equals.The speakers shall be UL Listed under UL 1480
Service and speakers equipped with strobes shall be listed under UL for Fire Protective Service and speakers equipped with strobes shall
1971 for Emergency Devices for the Hearing-Impaired.In addition, be listed under UL 1971 for Emergency Devices for the Hearing-
the strobes shall be certified to meet the requirements of FCC Part Impaired. In addition,the strobes shall be certified to meet the
15,Class A. requirements of FCC Part 15,Class A.
Bakers shall be designed for a field selectable input of either 25 All speakers shall be designed for a field selectable input of either
All speakers 9 p 25 or 70 VRMS,with selectable power taps from 1/8 watt to 2
or 70 VRMS,with selectable power taps from 1/8 watt to 2 watts. watts.All models shall have listed sound output of up to 87 dB at
All models shall have listed sound output of up to 87 dBA at 10 feet 10 feet and a listed frequency response of 300 to 8000 Hz.The
and a listed frequency response of 300 to 8000 Hz.The speaker speaker shall also incorporate a sealed back construction.All inputs
shall incorporate a sealed back construction.All inputs shall employ shall employ terminals that accept#12 to#18 AWG wire sizes. The
terminals that accept#12 to#18 AWG wire sizes. The strobe portion strobe portion of the appliance shall produce a flash rate of one(1)
of the appliance shall produce a flash rate of one(1)flash per second flash per second over the Regulated Voltage Range.The strobe shall
over the Regulated Voltage Range and shall be of low current design. be of low current design.Where Multi-Candela Speaker Strobes are
Where Multi-Candela Speaker Strobes are specified,the strobe specified,the strobe intensity shall have field selectable settings
intensity shall have field selectable settings and shall be rated per and shall be rated per UL 1971 15/30/75/95cd or 115/177cd for
UL 1971 at 15/30/75/110cd or 135/185cd for wall mounting. The ceiling mount. The selector switch for selecting the candela shall
selector switch for selecting the candela shall be tamper resistant. be tamper resistant. When synchronization is required,the strobe
portion of the appliance shall be compatible with Wheelock DSM
When synchronization is required,the strobe portion of the sync modules or the Wheelock Power Supplies with built-in Patented
appliance shall be compatible with the Wheelock's DSM sync Sync Protocol.The strobes shall not drift out of synchronization at
modules or Wheelock Power Supplies with built-in Patented Sync any time during operation. If the sync module or Power Supply fails
Protocol.The strobes shall not drift out of synchronization at any to operate,(i.e.,contacts remain closed),the strobe shall revert to a
time during operation. If the sync module or Power Supply fails to non-synchronized flash rate.
operate, (i.e.,contacts remain closed),the strobe shall revert to a The speaker and speaker strobe appliances shall be designed
non-synchronized flash rate. for indoor flush mounting.The speaker and speaker strobe shall
The speaker and speaker strobe appliances shall be designed for incorporate a speaker mounting plate with a snap-on grille cover
indoor flush mounting to 4"x 2-1/8"electrical boxes without need with no visible screws for a level,aesthetic finish and shall mount to
for an extension ring or surface mounting to Wheelock's E5OSB standard electrical hardware. The finish of the Series E6OH Speakers
or E5OSSB surface boxes.The speaker and speaker strobe shall and Speaker Strobes shall be white or red. All speaker and speaker
incorporate a speaker mounting plate with a snap-on grille cover.The strobe appliances shall be backward compatible.
finish of the Series E5OH speakers and speakers strobes shall be The speaker shall be listed to the low frequency requirements of UL
white or red. 464(520 Hz)to meet NFPAs 520 Hz tone requirements for sleeping
The speaker shall be listed to the low frequency requirements of UL 464 areas.
(520 Hz)to meet NFPAs 520 Hz tone requirements for sleeping areas. UL 1971, UL 1480, ULC-S526, ULC-S541,CSFM, FCC.
UL 1971, UL 1480, ULC-5526, ULC-S541,CSFM, FCC.
Note:Due to continuous development of our products,specifications and offerings are subject to change without notice in accordance with Cooper
Wheelock Inc.,dba Eaton standard terms and conditions.
re CMAn
ISM 11111110111
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Eaton
1000 Eaton Boulevard
Cleveland,OH 44122
United States
Eaton.com
Eaton
Life safety&mass notification solutions
273 Branchport Ave.
Long Branch,NJ 07740
www.eaton.com/massnotification
®2016 Eaton
All Flights Reserved Eaton is a registered trademark.
E Printed in USA
Publication No.TD450017EN All other trademarks are property
Powering Business Worldwide January 2016 of their respective owners.
HN Series
Effective October 2014 HS Series
Technical Data TDOO1O17EN Supersedes May 2013 ST Series
Exceder Strobe, Horn Strobe, and
Horn Notification Appliances
Description
The Wheelock Exceder Series of notification appliances
feature a sleek modern design that will please building owners
with reduced total cost of ownership. Installers will benefit from
its comprehensive feature list,including the most candela options
in one appliance, low current draw,no tools needed for setting
changes,voltage test points, 12/24VDC operation, universal
$ mounting base and multiple mounting options for both new and
retrofit construction.
The Wheelock Exceder Series incorporates high reliability and high
FIRE efficiency optics to minimize current draw allowing for a greater
number of appliances on the notification appliance circuit.All strobe
/
models feature an industry first of 8 candela settings on a single
1 appliance. Models with an audible feature 3 sound settings(90,95,
. � *77 99 dB).All switches to change settings,can be set without the use
�j of a tool and are located behind the appliance to prevent tampering.
cj -K / Wall models feature voltage test points to take readings with a
NA" /77 / voltage meter for troubleshooting and AHJ inspection.
The Wheelock Exceder Series of wall and ceiling notification
f I appliances feature a Universal Mounting Base(UMB)designed
to simplify the installation and testing of horns,strobes,and
combination horn strobes.The separate universal mounting base
can be pre-wired to allow full testing of circuit wiring before the
appliance is installed and the surface is finished. It comes complete
with a Contact Cover for protection against dirt,dust, paint and
damage to the contacts.The Contact Cover also acts as a
shunting device to allow pre-wire testing for common wiring issues.
The Contact Cover is polarized to prevent it from being installed
incorrectly and prevents the appliance from being installed while it
is on the UMB. When the Contact Cover is removed the circuit will
show an open until the appliance is installed.The UMB allows for
consistent installation and easy replacement of appliances if
required.Wall models provide an optional locking screw for extra
secure installation,while the ceiling models provide a captivated
screw to prevent the screw from falling during installation.
E:T�N
Powering Business Worldwide
Technical Data TD001017EN HN Series
Effective October 2014 HS Series
ST Series
Features • Environmentally friendly
• Sleek modern aesthetics ii
Low current draw
• Finger slide switches • Up to 9 models now in 1 appliance draw®
• Voltage test points • 12/24VDC on a single appliance
• Multiple voltages • Easy to remember model numbers
• 3 Audible settings O Patented
• 90,95, 99 dB Note:All CAUTIONS and WARNINGS are identified by the symbol A.All
warnings are printed in bold capital letters.
• Industry leading-8 candela settings on 1 device
. Wall: 15/1575/30/75/95/110/135/185 A WARNING
• Ceiling: 15/30/60/75/95/115/150/177 PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION
INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING
'. THIS PRODUCT.VISIT WWW COOPERNOTIFICATION.COM OR CONTACT
' COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS.
FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR
WARNINGS COULD RESULT IN IMPROPER APPLICATION,INSTALLATION
AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,
WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR
DEATH TO YOU AND/OR OTHERS.
General Notes
• Strobes are designed to flash at 1 flash per second minimum over
their"Regulated Voltage Range"
• All candela ratings represent minimum effective strobe intensity
based on UL Standard 1971.
Universal mouting base • Series Exceder Strobe products are Listed under UL Standards
1971 and 464 for indoor use with a temperature range of 32°F to
• Ceiling and wall 120°F (0°C to 49°C)and maximum humidity of 93% (±2%) UL
• Mounts to 5 backbox types: 1 gang,2 gang,4" square, 464(85% UL 1971).
3.5"octal.&4"octal. (100mm for international customers) • Series Exceder horns are under UL Standard 464 for audible
Universal mounting base Contact cover signal appliances(Indoor use only).
s oil ,..'''',.e4'14 i
Compatibility and requirements
tii„ €a P�1 ,a • Synchronize using the Wheelock®Sync Modules or panels with
3 �: built-in Wheelock®Patented Sync Protocol
Compatible with UL"Regulated Voltage" using filtered VDC or
�� '''''''''''',S'4unfiltered VRMS input voltage
.$`-' 1 • Strobes produce 1 flash per second over the "Regulated
Voltage" range
Common base for wall and ceiling with 5 mounting options Compliance
• Voltage test points for quick troubleshooting and easy spot • UL 1971, UL 464, ULC,CSFM, FM
checking(wall models only) • ADA/NFPA/ANSI/OSHA
• RoHS
....- ,, „ ---\\
2 EATON www.eaton.com
HN Series Technical Data TD001017EN
HS Series Effective October 2014
ST Series
Table 1. Strobe Ratings per UL Standard 1971
UL Max Current®
24VDC/24FWR 12VDC
Regulated Voltage
Model Range VDC 15 15!75 30 60 75 95 110 115 135 150 177 185 15 15/75
ST 8.0-33.0 0.057 0.070 0.085 - 0.135 0.163 0.182 - 0.205 - - 0.253 0.110 0.140
STC 8.0-33.0 0.061 - 0.085 0.103 0.135 0.163 - 0.182 - 0.205 0.253 - 0.110 -
Table 2. Horn Strobe Ratings per UL 1971 &Anechoic at 24VDC
UL Max Current®at Anechoic 99 dBA
24 VDC 12 VDC
Regulated Voltage
Model Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
HS 8.0-33.0 0.082 0.095 0.102 - 0.148 0.176 0.197 - 0.242 - - 0.282 0.125 0.159
HSC 8.0-33.0 0.082 - 0.102 0.141 0.148 0.176 - 0.197 - 0.242 0.282 - 0.125 -
UL Max Current®at Anechoic 95 dBA
24 VDC 12 VDC
Regulated Voltage
Model Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
HS 8.0-33.0 0.073 0.083 0.087 - 0.139 0.163 0.186 - 0.230 - - 0.282 0.122 0.153
HSC 8.0-33.0 0.073 - 0.087 0.128 0.139 0.163 - 0.186 - 0.230 0.272 - 0.122 -
UL Max Current®at Anechoic 90 dBA
24 VDC 12 VDC
Regulated Voltage
Model Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
HS 8.0-33.0 0.065 0.075 0.084 - 0.136 0.157 0.184 - 0.226 - - 0.267 0.120 0.148
HSC 8.0-33.0 0.065 - 0.084 0.120 0.136 0.157 - 0.184 - 0.226 0.267 - 0.120 -
®UL max current rating is the maximum RMS current within the listed voltage range 116-33 VDC for 24 VDC unitsl.For strobes the UL max current is usually at the minimum listed voltage 116 VDC for 24 VDC
units).For audibles the max current is usually at the maximum listed voltage 133 VDC for 24 VDC unitsl.For unfiltered ratings,see installation instructions.
Table 3. Horn Ratings per UL Anechoic Model Legend
Regulated Voltage HN = Horn R = Red
Model Range VDC 99 dB 95 dB 80 dB
HN 16-33.0 0.064 0.044 0.022 ST = Strobe A = Agent Lettering(strobes only(
HNC 16-33.0 0.084 0.044 0.022 HS = Horn Strobe AL = Alert Lettering(strobes only)
HN 8.0-17.5 0.047 0.026 0.017 C = Ceiling Mount N = No Lettering(strobes only)
HNC 8.0-17.5 0.047 0.026 0.017 W = White
Example 1:STRC=Strobe,Red,Ceiling Mount
Table 4. Specification&Ordering Information Example 2:HSR=Horn Strobe,Red,Wall Mount
S nc w/DSM or Example 3:HSW=Horn Strobe,White,Wall Mount
Wheelock Power 12/24 Mounting Example 4:STW-AL=Strobe,White,Wall Mount,Alert Lettering
Model Strobe Candela Supplies VDC® Options
Horn Strobes s6 r,
HSR 15/1575/30/75/95/110/135/185 X X UMBO e-
HSW 15/1575/30/75/95/110/135/185 X X UMBO v /T
HSRC 15/30/60/75/95/115/150/177 X X UMBO ' Ay
HSWC 15/30/60/75/95/115/150/177 X X UMBOS �K
Strobes y ,
STR 15/1575/30/75/95/110/135/185 X X UMB®
STW 15/1575/30/75/95/110/135/185 X X UMB®
STRC '15/30/60/75/95/115/150/177 X X UMB® ::: ,
STWC 15/30/60/75/95/115/150/177 X X UMB® I
Horn ?
HNR X X UMB®
HNW°, X X UMBO '•,
L.
HNRC X X UMBO Example:HSR Example:HSWC
HNWC X X UMB®
®12 VDC models feature t5&15/75 settings
OO UMB=Universal Mounting Base
EATON www.eaton.com 3
Technical Data TD001017EN HN Series
Effective October 2014 HS Series
ST Series
Architects and Engineers Specifications
The notification appliances shall be Wheelock Exceder Series HS Audible Strobe appliances,Series ST Visual Strobe appliances and Series
HN Audible appliances or approved equals.The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency Devices for the
Hearing-Impaired)for Indoor Fire Protection Service.The Series HS and HN Audibles shall be UL Listed under Standard 464(Fire Protective
Signaling).All Series shall meet the requirements of FCC Part 15 Class B.All inputs shall be compatible with standard reverse polarity
supervision of circuit wiring by a Fire Alarm Control Panel(FACP)with the ability to operate from 8 to 33 VDC. Indoor wall models shall
incorporate voltage test points for easy voltage inspection.
The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one(1)flash per second over the Regulated Voltage
Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan®lens.The Series shall be of low current design.Where multi-
candela appliances are specified,the strobe intensity shall have 8 field selectable settings at 15, 15/75,30,75,95, 110, 135, 185 candela
for wall mount and 15,30,60,75,95, 115, 150, 177 candela for ceiling mount.The selector switch for selecting the candela shall be tamper
resistant.The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required
(e.g.,ADA compliance).Appliances with candela settings shall show the candela selection in a visible location at all times when installed.
The audible shall have a minimum of three(3)field selectable settings for dBA levels and shall have a choice of continuous or temporal
(Code 3)audible outputs.
The Series HS Audible Strobe,ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow
mounting to a single-gang,double-gang,4-inch square,3.5-inch octal,4-inch octal or 100mm European type back boxes.Two wire appliance
wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to attaching any
notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of an appliance shall
result in a supervision fault condition by the Fire Alarm Control Panel(FACP).The mounting base shall be the same base among all horn,
strobe, horn strobe,wall and ceiling models.All notification appliances shall be backwards compatible.
The Series HS and ST wall models shall have a low profile measuring 5.24" H x 4.58"W x 2.19" D. Series HN wall shall measure 5.24" H x
4.58"W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68" x 2.63" D.Series HNC ceiling
shall have a diameter of 6.68"x 1.50" D.
When synchronization is required,the appliance shall be compatible with Wheelock's DSM Sync Modules,Wheelock Power Supplies or other
manufacturer's panels with built-in Wheelock Patented Sync Protocol.The strobes shall not drift out of synchronization at any time during
operation. If the sync protocol fails to operate,the strobe shall revert to a non-synchronized flash-rate and still maintain(1)flash per second
over its Regulated Voltage Range.The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe
activation when used with Wheelock synchronization protocol.
Wall Appliances: UL Standard 1971, UL Standard 464,California State Fire Marshal(CSFM), ULC, FM, RoHS
Ceiling Appliances: UL Standard 1971, UL Standard 464, California State Fire Marshal(CSFM), ULC, FM, RoHS
Note:Due to continuous development of our products,specifications and offerings are subject to change without notice in accordance with Cooper
Wheelock Inc.,dba Cooper Notification standard terms and conditions.
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Eaton
1000 Eaton Boulevard
Cleveland,OH 44122
United States
Eaton.com
Eaton
Cooper Notification
273 Branchport Ave.
Long Branch,NJ 07740
CooperNotification.com
0 2014 Eaton
All Rights Reserved Eaton is a registered trademark.
EA N Printed in USA
Publication No.TD001017EN All other trademarks are property
Powering Business Worldwide October 2014 of their respective owners.
SIEMENS Data Sheet
Fire Safety& Security Products
Intelligent Detection Devices
TRI Series — Intelligent Initiating Interface Modules
[For use with FireFinder® XLS and MXL Panels]
Models TRI-D, TRI-R and TRI-S
ARCHITECT AND ENGINEER SPECIFICATIONS
• Used as an intelligent initiating interface module for the
FireFinder XLS and MXL fire-alarm control panels(FACPs)
• Interfaces and supervises normally open (N.0)contacts
• Integral single-pole,double-throw(SPDT)relay(up to 4 amps),Model TRI-R
• Dual input for Model TRI-D
• Multi-color light-emitting diode(LED)indicates detector status
(green,amber,red)
•
• Simple front-end access to programming port and wiring terminals
• Mounts in a 4"-square,2-1/8"-deep standard or double-gang box e "".1
• Dynamic supervision r. : t �` ""'4
• 5-x-5-inch faceplate included 4,4.1.414
•
• Two-wire operation
• Compatible with Model DPU or FPI-32 field programmer/tester ° t `
• Electronic-address programming is simple and dependable
• ®UL Listed,€ULC Listed;
CSFM and NYC Fire Department Approved
Product Overview
The Model TRI-series of intelligent interface The sole purpose of Model TRI-S is to monitor and
modules from Siemens—Fire Safety is designed to report the status of the contact,while Model TRI-R
provide the means of interfacing direct shorting incorporates an addressable'Form C'relay. The
devices to Model MLC for the FireFinder XLS FACP, relay and contact device input for Model TRI-R are
or to Model ALD for the MXL system, respectively. controlled at the same address. The relay and input
The Model TRI-series of intelligent interface contact can be controlled as a separate function.
modules provides the most advanced method of The relay is typically used where control or shunting
address programming and supervision—combined of external equipment is required.
with sophisticated FACP communication. Each Model TRI-D is a dual-input module that is designed to
Model TRI-series interface module incorporates a supervise and monitor two (2)sets of dry contacts.
microcomputer chip. In turn,the microcomputer- Model TRI-D requires two(2) address settings. Model
chip technology and its sophisticated bi-directional TRI-D is ideal for monitoring a waterflow switch and its
communication capabilities with the FACP,achieve respective valve tamper switch.
the state of an'Intelligent Device.' Model TRI-series has a multi-color LED that flashes
Specifications green when operating normally; -I � if unit is in
The Model TRI series of intelligent interface trouble condition,and red to indicate a change of
modules is available in three (3) models. Models status command. Model TRI-D flashes two(2) times—
TRI Sand TRI-R are designed to monitor a normally once for each address, and the red LED of Model TRI-R
open (N.O.) dry contact. The interface module indicates a change of state in the relay.
reports the contact's status to the FACP.
TRI Series —Intelligent Initiating Interface Modules 61 79
SIEMENS Industry, Inc.
Building Technologies Division
Specifications — (continued) Electrical Ratings
The microcomputer chip for the Model TRI-series of Current Draw: 1.5mA
devices has the capacity of storing—in memory— [Active or Standby]
identification information as well as important Model TRI-R Relay Ratings:
operating status information. 4A,125VAC
Resistive: 4A,30VDC
Siemens—Fire Safety innovative technology allows
all Model TRI-series intelligent interface modules to 3.5A,120VAC[0.6 P.F]
be programmed and tested,via Model DPU or the 73.OA,3OVDC[0.6 P.F]
Inductive: 2.0A,120VAC[0.4 P.F]
FPI-32 Programmer 1 Tester. Each of these 2.OA,120VAC[0.35 P.F]
programmer 1 testers is a compact, portable and 2.0A, 120VAC[0.35 P.F]
menu-driven accessory that makes programming
and testing an interface device faster,easier and
more dependable than previous methods.
Mounting Diagram
Model DPU or the FPI-32 eliminates the need for
MouNTINeSLOTS
mechanical addressing mechanisms(such as:
FOR 4-INCH
program jumpers, DIP switches,or rotary dials), SWI 104130X
since either programmer I tester device
electronically sets the address of the Model TRI- Q
series into the interface's microcomputer chip, non- ° '*
volatile memory. Vibration,corrosion and other TA SJo/R
[ t ., MODULE
conditions that deteriorate mechanical addressing [a1 2
aim
mechanisms are no longer a cause for concern. ? s KM°
LAI 4 MOUNTING
The Model TRI-series of intelligent interface [=I 5 s HOLES FOR
modules is fitted with screw terminals for 7 SWiTCHPLATE
connection to an addressable circuit,and is fully
compatible on the same circuit with all intelligent
Model FP; Model IL and Model ID-60-series o 0
detectors; Model MSI Series addressable manual
stations,or any other addressable intelligent MouraTlNrT
modules,such as Model CZM or Model ICP. FON o0Ui3LL-GANG
STCHBOX
All Model TRI-series intelligent interface modules
arebUL and'ULC Listed.
Details for Ordering
Model Part Shipping Weight
Number Number DescriptlCa
Oz. Kg.
TRI-D 500-896226 Dual Input Intelligent 7 0.2
Interface Module
Single-Input[wl relay]
TRI-R 500-896224 Intelligent Interface 7 0.2
Module
Single-Input
TRI-S 500-896225 Intelligent Interface 7 i 0.2
Module
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information,refer to each product's installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
SIEMENS Industry,Inc. Florham Park,NJ 07932 Brampton,Ontario
Building Technologies Division Tel:(973)593-2600 (su-FS) L6T 5E4/Canada Supersedes
2012 5/06sheet dated
FAX:(908)547-6877 Printed in U.S.A. Tel:(905)799-9937 (Rev 4)
URL:www.usa.Siemens.com/Fire FAX:(905)799-9858
SIEMENS Data Sheet
Fire Safety& Security Products
Intelligent Detection Devices
Intelligent FirePrintrM Detector
[For use with FireFinder® XLS and MXL Panels]
Model FP-11
ARCHITECT AND ENGINEER SPECIFICATIONS
• Most sophisticated'detector intelligence'available in the Fire/Life Safety market
• Multi-criteria fire detection for the price of a photoelectric detector
• Remote-sensitivity-measurement capability
at
•
Easily programmed to match specific hazard profiles
from the fire-alarm control panel(FACP)
• FirePrintTM technology to distinguish between deceptive tf ;
phenomena and an actual fire
• Pre-Alarm reporting based upon fire profile selected �� •
• Field-cleanable chamber with replaceable chamber parts
• System-logic activation based upon any of three(3) inputs
from the detector(smoke,heat or neural network)
• Supports software-based,automatic environmental compensation •
• EnviroLINK ��-
• Compatible with field programmer/tester • Multi color,detector status
• Model DPU/FPI-32 Upgrade Kit
• Backward compatible with older MXL systems light emitting diode(LED)
• Rev.2 and above • Two-wire operation
• Optional fully programmable relay base,audible base • aUL and OULC Listed;
and duct housing FM,CSFM &NYCFD Approved
Product Overview
The Intelligent Fire Detector(Model FP-11)is a The upgrade kit(Models DPU or FPI-32) eliminates the
highly evolved detection system that provides the need for cumbersome, unreliable mechanical
most sophisticated level of fire protection,along programming methods,as well as reduces installation
with superior nuisance-alarm immunity currently and service costs by electronically programming and
available in the Fire/Life Safety industry. testing the detector prior to installation.
Model FP-11 utilizes highly developed detection Specifications
technology that allows the detector to distinguish
non-threatening deceptive phenomena (i.e. — Model FP-11 is a plug-in,two-wire and multi-sensor
cigarette smoke)from actual fire hazards,while detector with photoelectric and thermal inputs that is
optimizing detection for the area of its intended compatible with the FireFinder XLS and MXL family of
zone. Model FP-11 uses state-of-the-art FACPs. Each detector consists of a dust-resistant,field-
microprocessor circuitry with error check, detector cleanable photo chamber;a solid-state, non-
self-diagnostics and supervision programs. mechanical thermal sensor,and microprocessor-based
Model FP-11 is compatible with the Siemens—Fire electronics with a low profile plastic cover and base.
Safety Model FPI-32 upgrade kit or Siemens'field- Model FP-11 utilizes state-of-the-art ASIC and surface-
programmer/tester, Model DPU/FPI-32,which is a mount technology for maximum reliability. Every
compact, portable and menu-driven accessory for Model FP-11 fire detector is shipped with a protective
efficiently programming and testing detectors dust cover. Model FP-11 fire detector utilizes an
electronically. infrared light-emitting diode(IRLED),and light sensing
photodiode.
Intelligent FirePrintTM Detector 61 75
SIEMENS Industry, Inc.
Building Technologies Division
Specifications — (continued)
Under normal conditions, light transmitted by the LED The FirePrint technology for Model FP-11 monitors
is directed away from the photodiode and scattered input from the photo chamber and the thermal sensor,
through the smoke chamber in a controlled pattern. evaluating this information with sophisticated
The smoke chamber is designed to manage light mathematical formulas or algorithms,and compares
dissipation and extraneous reflections from dust data transfer to this input to the characteristics of both
particles or other non-smoke airborne contaminants in threatening fires and deceptive phenomena that would
such a way as to maintain stable,consistent detector deceive any ordinary detector.
operation. When smoke enters the detector chamber, This technology was developed over years of research
light emitted from the IRLED is scattered by the smoke and reviewing the results of over 20 years of fire-test
particles,and is received by the photodiode. data in one of the world's most advanced fire research
Model FP-11 also utilizes a modern,accurate and centers. The results of this research are the
shock-resistant thermistor to sense temperature mathematical models that form the algorithms used in
changes. The'on-board'FirePrint technology FirePrint. No other fire detector has this level of
allows the detector to gather smoke and thermal data, intelligence or,this amount of research and
analyzing this data in the detector's'neural network.' development supporting its design.
By comparing data received with the common The software of the microprocessor can identify and
characteristics of fires,or fire fingerprints, Model FP-11 disregard false input caused by radio frequency(RFI)
can compare these'fire prints'to those of deceptive and electromagnetic(EMI) interference,and validates
phenomena that cause other detectors to go into Alarm all Trouble conditions before annunciating or reporting
mode, to the control panel. The microprocessor for Model FP-
This advanced FirePrint technology allows Model FP-11 11 uses an integral electronically erasable
to accurately determine a true fire hazard from non- programmable read-only memory(EEPROM)to store
threatening,deceptive phenomena—without the need the detector's address and other critical operating
to use alarm-delaying verification and confirmation parameters,which include the assigned program
techniques;thus decreasing the probability of losses in values for Alarm and Trouble—command thresholds.
infrastructure from an actual fire. Communications within the detector;between Model
Model FP-11 provides the highest level of detector FP-11 and the FACP,or with the field programmer 1
intelligence available today with a detector 1 control- tester(Model DRU 1 FPI 32),are supervised and
panel link that allows the user to program the detector safeguarded against disruption by reliable,
for the specific hazard profile. microprocessor-based error checking routines.
Detectors are optimized by selecting one(1)of Additionally,the microprocessor supervises all EEPROM
memory locations and provides a high degree of
the following applications: EEPROM failure fault tolerance.
• Office 1 Retail Model FP-11 determines its operating status(Normal,
• Lobby
• Computer room Alarm,or Trouble modes)based upon the difference
• Dormitory between the alarm-threshold values stored in the
• Healthcare facility detector's memory and the detector's latest analog
• Parking garage measurement. The detector then communicates
• Utility/transformer room changes in its status to the FACP.
• Hostile environment In addition,the FACP will sample the value of the
• Precious storage analog signal for Model FP-11 over a period of time,in
•Air duct
•Warehouse 1 light manufacturing order to determine if those values indicate excessive
buildup in the photo chamber. In the event of
Once programmed,the software does the rest— excessive buildup,the FACP will accurately indicate
no guessing on detector sensitivities or alarm which detector shall require maintenance.
verification—the FACP programs Model FP-11 for the Model FP 11 is listed as a self testing device. The LED
protected area without any confirmation delays. for Model FP-11 flashes green every four(4)seconds,
Once optimized for the hazards in the protected area, indicating communication with the FACP,and that it
Model FP-11 provides the utmost means in detection. has passed its self-test. Should the detector sense a
Should the operator or installer forget fault or failure within its systems,the LED will flash
to program the detector, Model FP-11 will revert amber,and the detector will transmit that data to the
to a default setting that, in turn,allows operation FACP. A quick visual inspection is sufficient to indicate
as a standard photoelectric or photothermal detector. the condition of the detector at any time.
SIEMENS Industry, Inc.
Building Technologies Division
Specifications — (continued)
If more detailed information is required,a printed Model FP-11 uses the low-profile,surface-mounting
report can be provided from the FACP,indicating the base, Model DB-11. This base mounts on a 4-inch
status and settings assigned to each individual octagon,square,or a single-gang electrical box. The
detector. base utilizes screw-clamp contacts for electrical
When Model FP-1 lactivates into Alarm mode,the connections and self-wiping contacts for increased
detector will flash amber,and will transmit that data to reliability.
the FACP. When the FACP confirms the condition of The base can be used with the optional Model LK-11
the detector,the FACP will instruct Model FP-11 to detector locking kit,which contains 50 detector locks,
flash red—and continue to flash red—until the system as well as an installation tool,thus preventing
is reset manually at the FACP. At that same time,any unauthorized removal of the detector head. Model DB-
user-defined system alarm functions programmed into 11 has integral,decorative plugs to cover the outer
the system are activated. Each Model FP-11 detector mounting screw holes.
can operate one(1) remote alarm indicator;one(1) Model FP-11 is electrically compatible with existing
auxiliary relay,or one(1)audible base. MXL-detector accessories,including relays, remote
Detector sensitivity,calibration and identification are lamps,duct housings and audible bases. With duct
dynamically supervised by the FACP. Detector housings,a base adapter and new detector housing
sensitivity and pre-Alarm levels are a function of the cover are required (order AD-11 UK upgrade kit). To use
application chosen at the FACP,and are controlled by existing Model DB-3S base or audible base, Model FP-
the panel. If an alternate, non-FirePrint mode is 11 requires a base adapter(Model DB-ADPT).
selected,then the sensitivity can be changed from the
FACP. Temperature and Humidity Range
The Program/Test unit(Model DPU or FPI-32) upgrade All Model FP 11 detectors are t9UL 864 9th Edition
kit is used to program and verify the detector's address. Listed for indoor dry locations within a temperature
The technician selects the accessory's program mode to range of 120+/-3°F(49+1-2°C)to 32+/-3°F(0+/-2°C)and
enter the desired address. In turn,the programmer a relative-humidity range of 93+1-2%at a temperature
unit(Model DPU or FPI-32)automatically sets/verifies of 90+/-3°F(32+/-2°C).
the address,and tests the detector. Model DPU 1 FPI-32 Application Data
also allows the user to change the device ID from that Installation of the Model FP-11 series of fire detectors
of a Model FP-11 detector to an older detector ID(such requires a (2)two-wire circuit of 18 American Wire
as: ILP-1,ILPT-1,ILP-2,ID-60P or ID-60PT)to allow for Gauge(AWG),minimum,thermoplastic fixture wire
easy replacement of older detectors without the need enclosed in conduit,or 18 AWG(American Wire Gauge)
of reprogramming the FACP. limited-energy,shielded-cable without conduit,if
The FPI-32 upgrade kit operates on AC power or permitted by local codes. Field wiring should conform
rechargeable batteries, providing flexibility and to local and national electric codes and the control
convenience in programming and testing equipment panel wiring specifications.
from almost any location. When in'test'mode, Model 'T-tapping'is permitted only for Style 4(Class B)wiring.
DPU or FPI-32 upgrade kit will perform a series of
diagnostic tests without altering the address or other Model FP 11 fire detectors can be applied within the
stored data,allowing technicians to determine if the maximum 30-foot center spacing (900 sq.ft.areas),as
detector is operating properly. referenced in NFPA 72. This applications guideline is
based upon ideal conditions—specifically—smooth
Model FP-11 may be installed on the same initiating ceiling surfaces, minimal air movement,and no
circuit with Models IL or ID series detectors physical obstructions between potential fire sources
(Photoelectric,thermal,or ionization);Model MSI- and the detector. Do not mount detectors in close
series manual stations;Model TRI-series interfaces; proximity to ventilation or heating and air-conditioning
Model ICP output-control devices,or Model CZM series outlets.
of addressable,conventional zone modules. Exposed joints or beamed ceilings may also affect safe
All Model FP-11 detectors can be cleaned in the field— spacing limitations for detectors.Should questions
when required—by simply removing the detector cover arise regarding detector placement,observe National
and unsnapping the photo chamber. There is also the Fire Protection Association (NFPA)72 guidelines.
option of cleaning the interior of the detector with a
clean,soft cloth or brush,or replacing the labyrinth and
bug screen included in the detector maintenance kit,
Model DMK-11.
SIEMENS Industry,Inc.
Building Technologies Division
Technical Data Details for Ordering
Environmental 'Mel Part `" t ,*
Temperature: 32°F(TO to 100°F(38°C) ., _ er NU ,y, ; Descri `�`= i`
Humidity: Up to 93%RH,non-condensing FP-11 500-095112 Addressable FirePrintm"Detector
Air Pressure: No effect DB-11 500-094151 Detector Mounting Base
Alarm Temperature: 135°F(57°C) For Series 11 Intelligent Detectors
DB-11E 500-094151E Detector Base(Small)
Electrical Air-Duct Housing
Voltage: 16—27 VDC AD2-P 500-649706 (for use with Models FP-11,HFP-11,
HFPO-11 and PE-11 Detectors)
Ripple: 3V,peak-to-peak
Supervisory Current: 11 ONA max ____Air-Duct Housing______
Alarm Current: 33—SomA AD2-XHR 500-649708 (for use with Models FP-11,HFP-11,
HFPO-11 Detectors with Relay)
ADBX-11 500-096181 Audible Base
Dimensions DB-X11 RS 500-096125 Relay Base for Model 11 series
Intelligent Detectors
Diameter Base Remote Alarm Indicator
0 g•' RLI-1 500-390673
i 4"Octagon Box Mount,Red
1 05.3 cm]
RLI-2 500-390674 Remote Alarm Indicator
ir "^ Single-Gang Mount,Red
�,11111"— �- DMK-11 500-695338 Model 11-series Maintenance Kit
�_ "' .� (replacement labyrinth and bug screen)
Height DB-ADPT , 500-094187 Base Adapter to Model DB-3S Base
•3"• _\ j_ ..,. LK-11 500-695350 Base Locking Kit for Series 11 Detectors
[5.8cm] 1/00.r.7171., '
�' In Canada,please order:
; Description
135°F Fixed Temperature,Plug-In
FP-11C 500-095112C Detector Addressable FirePrint'^^
Detector]@ULC Listed]
Detector Mounting Base
DB-11C 500-095687 (for Model 11-series Intelligent Detectors) ,
]@ULC Listed]
AD-11 PC 500-095984 Air-Duct Housing[ ULC Listed]
DB-X11 RSC 500-093125C Relay Base for Model 11-series
Intelligent Detectors[ 'ULC Listed]
ADBX 11 C 500-096181C Audible Base for Model 11-series
Intelligent Detectors(4"AULC Listed]
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information,refer to each product's installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
SIEMENS Industry, Inc. Florham Park,NJ 07932 Brampton,Ontario June 2012
Building Technologies Division Tel:(973)593-2600 SII-FS L6T 5E4/Canada Supersedes sheet dated 8/10
FAX:(908)547-6877 Printed in U.S.A. Tel:(905)799-9937 (Rey.2)
URL:www.usa.Siemens.com/Fire FAX:(905)799-9858
1
!Data Sheet
LSpecialized Devices
is Air-Duct Housings (FDBZ Series)
; Models FDBZ492, FDBZ492-HR, FDBZ492-R and FDBZ492-RP {with FDBZ-WT and FDBZ492-RTL}
' ARCHITECT AND ENGINEER SPECIFICATIONS
__ • Four (4) models available . _
• Addressable and conventional with and without relays ' ,
441
• Compatible with Siemens—Fire Safety conventional 4y -w
'
fiand addressable fire-alarm control panels(FACPs)
:
• Magnet test feature with the Model OP121 FDBZ-series of air-duct housings
r-31 [FDBZ492,FDBZ492-HR,FDBZ492-R&FDBZ492-RP]
tsx conventional detector =,
Remote alarm -
• Design for air-velocity range of 100 indicator
to 4,000 feet-per-minute (fpm) [FDBZ492-RTL]
• Robust,compatible conventional remote indicator test
switch that incorporates tri-color light-emitting diode (LED) -
• Clear housing cover with smoke test port on cover
t for quick identification of detector type -
• Removable via four(4)captive-thumb screws(no tools required)
ht housin
• Includes a smoke/aerosol detector test port Watertight 9
[FDBZ-WT]
,:l; • Optional NEMA 4X-reinforced, stainless-steel and
• Self-contained model available with 'on board'
,, watertight enclosure available, Model FDBZ-WT
power supply for conventional detectors
• No tools required for cover removal, sampling and • Expanded temperature range
4 i' exhaust-tube installations •
Relay models available
• Trouble-event activation upon front-cover removal • ®UL268A Listed,®ULC S529 Listed;
lig ; • Alarm LED visible from front FM (#3010), CSFM (#3240-0067:0265) Approved
Product Overview
The Siemens—Fire Safety Model'FDBZ'-series of air- Notes-(cont.'d): With either the Cerberus PRO series or
duct-detector housings are designed for use with FireFinder XLS series of FACPs,up to 252-addressable
(`;• detectors with relays per circuit may be used.The connection of an
Siemens Model'H'series,Cerberus PRO series and intelligent remote lamp(ICED)and a remote relay is allowed for
Model OP121 detectors. (see: Details for Ordering for each detector simultaneously.
a complete list of compatible devices).
Designed for installation directly to heating,ventilating Specifications ,
' and air-conditioning (HVAC)duct systems,the Model The Model'FDBZ'-series of air-duct housings are uniquely
�:.: 'FDBZ'-series of duct housings complies with National designed to use with the photoelectric detector. Sensitivity
$ Fire Protection Association Standard (NFPA) No.'s 72 of Models PE-11,PE-11C,OP121,and 8854 conventional
and 90A,and is Underwriters'Laboratories Listed. detectors can be verified for calibration via LED visual status
When equipped,the air-duct detector housing will
or a Model RSAW-11, Model RSAC-11 or FDBZ492-RTL multi-
color remote lamp. A green flash indicates the detector has
, signal the presence of smoke being carried through passed its self test. Amber indicates a Trouble condition,and
the duct system. Air-duct detectors are not intended
y red indicates an Alarm event.
to be substituted for open-area detection.
.; Notes: Most conventional time-control equipment guarantee Sensitivity for Models FP 11,HFP 11,SFP 11,H FPO 11,
only one(1)detector per zone when the detector's SFPO 11,OP921,OOH941,OOHC941,8710,and 8713
operated relay function is critical. The connection of a intelligent detectors is verified from the multi-color LED of
remote lamp and a remote relay—per detector— is the respective detector,or its sensitivity reading may be
allowed. Refer to the installation manual of the rented bycommand fromthe corresponding FACP to an
respective conventional FACP. p pong
JR
optional printer.
- Cerberus® PRO 9906
,. -S.',.&11.6':
. ,...i114:44,Ii< Fire Safety Products Model 'FDBZ' Series of Air-Duct Housings and Detectors
Answers for infrastructure SIEMENS
lie
Specifications — (continued) Sampling Tube Selection Table
The remote alarm indicator(Model FDBZ492-RTL)allows for Duct Width Sampling Tube
manual testing via a key-switch for conventional and (Model No.)
addressable detectors,as well as the conventional and For duct widths 6"to 1' ST-10
addressable air-duct housing with relay. Model FDBZ492- For duct widths 1'to 3' ST-25
RTL,which mounts remotely from the conventional and For duct widths 3'to 5' ST-50
addressable air-duct housing,allows for manual relay- (requires support)
output control. The duct-detector remote indicator key- For duct widths 5'to 10'
ST-100
switch also indicates the current state of the detector. (requires support)
The watertight housing (Model FDBZ-WT),which allows the Maintenance of the detector is easily accomplished via the
air-duct detector housing to be installed inside the separate removal of the duct-housing sampling chamber cover. The
NEMA 4X enclosure, is for installations for either an outdoor detector,which plugs into the housing,is easily removed
area or in environments where excessive moisture is for cleaning or replacing by a trained technician.
prevalent. All that is necessary for installation of the air-duct detector
Each detector unit employs a cross-sectional sampling is the cutting of three(3)small holes for the Sampling Tube
principle of operation. Inlet sampling tubes are installation(template included),and the drilling of two(2)
available in four(4) lengths(see: Sampling Tube holes for mounting the air-duct housing. The unit is then
Selection Table). Outlet sampling tubes are one(1) easily mounted in place,and connection made to the
common length and draw. A continuous,cross-sectional existing wires or terminals—if optional accessories are
sample of air moves through the duct. Stratification or skin utilized. No mechanical tools are required for removing the
affect phenomenon that occurs in the duct can prevent cover or connecting the sampling and exhaust tubes to an
smoke(especially in large ducts)from reaching a spot-type air-duct housing.
detector. Models ST-50 and ST-100 require support. However, Model
In addition,the unique design of the sampling chamber ST-100 is shipped in two(2) 5-ft. (152 cm.) pieces with a
insures uniform sensitivity in air velocities, ranging from a coupling for field assembly.
low of 100 fpm to as high as 4,000 fpm. Each air-duct
housing comes with three(3)wiring entry ports: Technical Data
■ Two(2) 3/4"conduit knockouts
Operating
• One(1)1/2"conduit opening
p g
Temperature +32°F (0°C)to 120°F (49°C)
The inlet sampling tube length is determined by the width Ranges:
of the air duct being protected. The inlet tube—greater
than and nearest to the duct width—should be used (see: Sampling Tube Pressure > 0.01 inches;
Sampling Tube Selection Table).The inlet tube can then be Range of Differences: < 1.2 inches of water
trimmed at the job site to the exact width of the duct.The column
outlet sampling tube for all ducts—irrespective of width—
has a fixed length of approximately 5.5 inches(14cm.),and Relative Humidity: 0—95%; non-condensing
is supplied with the air-duct housing. Air Pressure/ No effect/
Note: When the use of a remote relay is required,order Altitude Range: No limitations
Model FDBZ492-R for conventional systems;Model
FDBZ492-HR for addressable systems.When required, Air-Duct Velocity: 100—4,000 ft./min
a separate watertight enclosure(Model FDBZ-WT), (0.51—20m/sec)
which is designed to contain the air-duct housings is
available. Dimensions: {H-x-W-x-D}
(For full details,refer to installation instructions for the •Rectangular: 14.38"-x-5"-x-2.5"
respective air-duct housing.) (37 cm.-x-12.7 cm.-x-6.36 cm.)
Note: When a self-contained duct detector with power ■Square: 7.75"-x-9"-x-2.5"
supply is required,order Model FDBZ492-RP. (19.7 cm.-x-22.9 cm.-x-6.36 cm.)
(For full details,refer to installation instructions part Detector Weight: 1.8 Lbs.(0.82 Kg.)
number A6V10330327.)
SIEMENS Industry, Inc. Cerberus® PRO
Building Technologies Division
Operation Details for Ordering
Based on the monitoring results,the LED indicator flashes Part
Model Description
the following colors based on the following conditions: Number a,
Flash A two-wire addressable or conventional
FI sh duct detector(without relays)designed for
Cond ition Interval direct use on heating,ventilating and air-
Color conditioning(HVAC)air-duct systems.
(in seconds) When equipped,the air-duct detector
Normal supervisory operation. S5431 9-B22- housing will signal the presence of smoke
FDBZ492 Al being carried through the duct system.
Green*: Smoke sensitivity is within 10
rated limits. For use with the following Models:
- 8710 —8713 —0011941 —OP121
Detector is in Trouble - 8854 —HFPO-11 —00HC941 —PE-11
Yellow: condition, and needs either 4 - FP-11 —HFP-11 —PE-11C —SFP-11
repair or replacement. -srPo-11
A two-wire addressable duct detector(with
Red: Alarm condition. 1 relays)designed for direct use to HVAC air-
duct systems and works with the Remote
No Flash: Detector is not powered. -- Test Switch(FDBZ492-RTL). This part has a
programmable relay base,and when
*LED can be turned OFF. equipped,the addressable air-duct detector
Please follow the corresponding description of the panel used. FDBZ492- 554319-B23- housing will signal the presence of smoke
being carried through the duct system.
HR Al For use with the following Models:
— 8710 — FP-11
— 8713 — HFP-11
Products included with the air-duct housing: - 00H941 — HFPO-11
(1)short-return(outlet)tube — 00HC941 — OP921
- (1)stopper — SFP-11 — SFPO-11
A two-wire conventional duct detector with
- (2)#12+3/4"sheet-metal screws relays designed for direct use on HVAC air-
- (1)mounting template duct systems. This detector has a relay
base,and when equipped with conventional
Note: Detector and sampling tube to be purchased separately. S54319-B24- air-duct housing,will signal the presence of
Minimum hardware required is: one(1)air-duct housing FDBZ492-R Al smoke being carried through the duct
assembly;one(1)sampling tube and one(1)detector. system.
For use with the following Models:
— PE-11 —PE-11C
— OP121 —8854
A four-wire conventional duct detector with
relays and a built-in power supply. Housing
is designed for direct use to HVAC air-duct
systems. It has a relay base with a built-in
power source. When equipped with
FDBZ492- S54319-B25- conventional air-duct housing,this duct
RP Al detector will signal the presence of smoke
being carried through the duct system.
For use with the following Models:
— PE-11 —PE-11C
- OP121
Device is used for manual testing via a key-
switch for duct-housing Models FDBZ492-R,
FDBZ492-RP and FDBZ492-HR. Device
mounts remotely from the conventional and
FDBZ492- 554319-S27- addressable air-duct housing,allowing for
RTL Al manual relay-output control. The duct-
detector remote key-switch also indicates
the current state of the detector.
For use with the following Models:
—FDBZ492-HR •FDBZ492-R •FDBZ492-RP
An optional,separate watertight NEMA 4X
enclosure(Model FDBZ-WT)that provides
added watertight protection for any of the
Model FDBZ492-series duct housings.The
duct housing fits into the separate 4X
enclosure. This part allows the air-duct
FDBZ-WT S54319-B26- detector housing to be installed in the
Al separate enclosure,and can be used in
either an outdoor area or in environments
where excessive moisture is prevalent.
For use with the following Models:
— FDBZ492 — FDBZ492-R
— FDBZ492-HR — FDBZ492-RP
ST-10 500-649710 Sampling tube for Ducts 6"to 1'
ST-25 500-649711 Sampling tube for Ducts over 1'to 3'
ST-50 500-649712 Sampling tube for Ducts 3"to 5'
ST-100 500-649713 Sampling tube for Ducts 5'to 10'
SIEMENS Industry, Inc. Cerberus® PRO
Building Technologies Division
SIEM ENS Cerberus® PRO NOTICE—The information contained in this data-sheet document is intended only as a summary,and
is subject to change without notice. The devices described here have specific instruction sheets that
cover various technical,limitation and liability information.
Siemens Industry, Inc.—Building Technologies Div. Copies of these instruction sheets and the General Product Warning and Limitations document,
8 Fernwood Road • Florham Park, NJ 07932 which also contains important information,are provided with the product and,are available from
Tel: (973) 593-2600 • Fax: (908) 547-6877 the Manufacturer.
Web:www.USA.Siemens.com/Cerberus-PRO Information contained in these documents should be consulted before specifying or using the
product. For further information or assistance concerning particular problems contact the Manufacturer.
Building Technologies Division September 2014—Supersedes sheet dated 8/2013
SII–Fire Safety (Rev.4)
[Printed in U.S.A
« »
•
\22
\
•
or
t �\
•
3«�
VV.;
114-
k-
«.
{\\it
)
3<:
)
��§
t\?
)
�\ \
t< .
��)
IV/
FAPS-F1 SIEMENS
BATTERY&VOLTAGE DROP CALCULATIONS
FIRE ALARM SUBMITTAL
Washington Square
Lucky Brand
FAPS-FI SPECIFICATIONS FAPS-F1 BATTERY CALCULATIONS
FAPS-Ft PANEL 24 Hours(A)Requirement for Standby Charge:
PS-8 MODEL 15 Minutes(B)Requirement for Alarm Charge:
15%Design Voltage Drop(20%Max Voltage Drop) 20%(C)Spare Battery Capacity:
3.00 Amp Max Current Draw Per Output 0.13 Amp(F)Standby Total Current Draw
2.50 Amp Max Current Draw Per AUX Output 3.42 Amp(G)Alarm Total Current Draw
8.00 Amp Max Current Draw Per Panel 3.1 Amp Hr(H)Design Standby Charge=(A x F)
14 AWG Wire Gauge 0.9 Amp Hr(J)Design Alarm Charge=(B x G)I60
20.4 VDC Voltage at First Device' 0.8 Amp Hr(K)Additional Capacity Charge=(C x((A x F)+(B x G)/60))
0.13 Amp Standby Current Draw 4.7 Amp Hr(AH)Battery Amp Hour requirement=(H+J+K)
0.13 Amp Alarm Current Draw 7.0 Amp Hr Battery Size
32.0 Amp Hr Max Battery Charging Capacity
FAPS-F1 VOLTAGE DROP CALCULATION RESULTS
PERCENT STANDBY ALARM PERCENT
OUTPUT VOLTAGE CURRENT CURRENT CURRENT
LABEL Lucky Brand DROP DRAW DRAW DRAW
OUTPUT-1 NF1-1- 2.69 Volt 13.20% 0.00 Amp 1.49 Amp 49.77%
OUTPUT-2 NF1-2- 1.05 Volt 5.14% 0.00 Amp 0.78 Amp 25.90%
OUTPUT-3 NF1-3- 1.62 Volt 7.94% 0.00 Amp 1.02 Amp 34.03%
OUTPUT-4 NF1-4- 0.00 Volt 0.00% 0.00 Amp 0.00 Amp 0.00%
AUX OUTPUT NF1-AX- 0.00 Volt 0.00% 0.00 Amp 0.00 Amp 0.00%
Total Current Draw 0.00 Amp 3.29 Amp 41.14%
FAPS-F1 VOLTAGE DROP CALCULATIONS
LABEL CD MODEL STANDBY ALARM DISTANCE VOLTAGE' Alarm Voltage Drop=VD=R x la
FAPS-Fl PS-8 = - 7,i'.' __20A00 287.25 Ft (L)Total Circuit Length(One Leg)
NF1-1-01 75cd E60H-24MCC-FW 0.189 35.92 ft 20.383 3.14 Ohm Wire Resistance Per 1000 Feet
NF1-1-02 75cd E60H-24MCC-FW 0.189 31.42 ft 20.252 1.80 Ohm (R)Total Circuit Resistance(Both Legs)
NF1-1-03 75cd E60H-24MCC-FW 0.189 31.25 ft 20.131 0.00 Amp (Is)Total Current Draw(Standby)
NF1-1-04 15cd E60H-24MCC-FW 0.065 28.92 ft 20.055 1.49 Amp (la)Total Current Draw(Alarm)
NF1-1-05 30cd E60H-24MCC-FW 0.105 20.50 ft 20.015 17.71 Volt (20.4-(lax R))Applied Voltage at Last Device'
NF1-1-06 75cd E60H-24MCC-FW 0.189 41.17 ft 19.923 2.69 Volt (VD)Voltage Drop
NF1-1-07 75cd E60H-24MCC-FW 0.189 21.67 ft 19.802 13.20% Percent Voltage Drop
NF1-1-08 75cd E60H-24MCC-FW 0.189 41.42 ft 19.681 49.77% Percent Current Draw Output-1
NF1-1-09 75cd E60H-24MCC-FW 0.189 35.00 ft 19.528
OUTPUT-2
LABEL CD MODEL STANDBY ALARM DISTANCE VOLTAGE' Voltage Drop=VD=L'R'la
FAPS-Fl - 'PS-8 Jr' 20.400 214.83 Ft (L)Total Circuit Length(One Leg)
NF1-2-01 15cd STWC 0.061 42.25 0 20.396 3.14 Ohm Wire Resistance Per 1000 Feet
NF1-2-02 15cd STWC 0.061 7.83 ft 20.358 1.35 Ohm (R)Total Circuit Resistance(Both Legs)
NF1-2-03 15cd E60H-24MCC-FW 0.065 16.42 ft 20.343 0.00 Amp (Is)Total Current Draw(Standby)
NF1-2-04 15cd STWC 0.061 10.17 ft 20.327 0.78 Amp (la)Total Current Draw(Alarm)
NF1-2-05 30cd E601-1-24MCC-FW 0.105 29.00 ft 20.292 19.35 Volt (20.4-(la x R))Applied Voltage at Last Device'
NF1-2-06 30cd E60H-24MCC-FW 0.105 27.92 ft 20.233 1.05 Volt (VD)Voltage Drop
NF1-2-07 75cd E60H-24MCC-FW 0.189 30.58 ft 20.147 5.14% Percent Voltage Drop
NF1-2-08 15cd E60H-24MCC-FW 0.065 27.25 ft 20.074 25.90% Percent Current Draw Output-2
NF1-2-09 15cd E60H-24MCC-FW 0.065 23.42 ft 20.043
PROPRIETARY DOCUMENT FOR APPROVAL ONLY 91612018
FAPS-FI VOLTAGE DROP CALCULATIONS CONTINUED
Mink MIGIESSIZIESI=
OUTPUT-3
LABEL CD MODEL STANDBY ALARM DISTANCE VOLTAGE' Voltage Drop=VD=L'R'la
FAPS-F1 PS-8 o g -T 20.400 252.67 Ft (1)Total Circuit Length(One Leg)
NF1-3-01 15cd E60H-24MCC-FW 0.065 27.50 ft 20.397 3.14 Ohm Wire Resistance Per 1000 Feet
NF1-3-02 30cd E60H-24MCC-FW 0.105 35.83 ft 20.342 1.59 Ohm (R)Total Circuit Resistance(Both Legs)
NF1-3-03 30cd E60H-24MCC-FW 0.105 32.92 ft 20.268 0.00 Amp (Is)Total Current Draw(Standby)
NF1-3-04 75cd E60H-24MCC-FW 0.189 42.25 ft 20.151 1.02 Amp (la)Total Current Draw(Alarm)
NF1-3-05 75cd E60H-24MCC-FW 0.189 33.92 ft 19.999 18.78 Volt (20.4-(lax R))Applied Voltage at Last Device'
NF1-3-06 15cd E60H-24MCC-FW 0.065 28.33 ft 19.918 1.62 Volt (VD)Voltage Drop
NF1-3-07 15cd STW 0.057 13.58 ft 19.895 7.94% Percent Voltage Drop
NF1-3-08 15cd STW 0.057 19.58 5 19.880 34.03% Percent Current Draw Output-3
NF1-3-09 75cd E60H-24MCC-FW 0.189 18.75 5 19.840
OUTPUT-4
LABEL CD MODEL STANDBY ALARM DISTANCE VOLTAGE' Voltage Drop=VD=L'R'la
FAPS-F1 „PS-8 b4[ 1 20.400 0.00 Ft (L)Total Circuit Length(One Leg)
3.14 Ohm Wire Resistance Per 1000 Feet
0.00 Ohm (R)Total Circuit Resistance(Both Legs)
0.00 Amp (Is)Total Current Draw(Standby)
0.00 Amp (la)Total Current Draw(Alarm)
20.40 Volt (20.4-(la x R))Applied Voltage at Last Device'
0.00 Volt (VD)Voltage Drop
0.00% Percent Voltage Drop
0.00% Percent Current Draw Output-4
AUX OUTPUT
LABEL CD MODEL STANDBY ALARM DISTANCE VOLTAGE' Voltage Drop=VO=L'R'la
FAPS-FI 5-i PS-8 _ = t 4/7 L 20.400 0.00 Ft (L)Total Circuit Length(One Leg)
3.14 Ohm Wire Resistance Per 1000 Feet
0.00 Ohm (R)Total Circuit Resistance(Both Legs)
0.00 Amp (Is)Total Current Draw(Standby)
0.00 Amp (la)Total Current Draw(Alarm)
20.40 Volt (20.4-(la x R))Applied Voltage at Last Device'
0.00 Volt (VD)Voltage Drop
0.00% Percent Voltage Drop
0.00% Percent Current Draw Aux Output
Note-1;24 Volt derated by 15%to 20.4 Volts.
Note-2;Point to Point Voltage Drop Calculation. Note-3;Line Voltage Drop Calculation
PROPRIETARY DOCUMENT FOR APPROVAL ONLY 9/6/2018
db LOSS CALCULATIONS SIEMENS
FIRE ALARM SUBMITTAL
Washington Square
Lucky Brand
FAAB-F7 PANEL
EBA2001 AMP MODEL
0.50 dB Mao dB Loss
50 Watt Max Wattage Per Output
100 Watt Max Wattage Per Card
14AWG Wire Gauge
70 VRMS (V)Audio Voltage
db LOSS CALCULATION RESULTS
OUTPUT TOTAL PERCENT
LABEL db LOSS WATTS OUTPUT
LOAD
OUTPUT 1 SF1-1- -0.04 dB 7.00 Watts 14.00%
OUTPUT 2 571-2- -0.01 dB 3.50 Watts 7.00%
OUTPUT3 SPARE #DIV/01 0.00 Watts 0.00%
OUTPUT 4 SPARE #DIV/OI 0.00 Watts 0.00%
Total Watts 10.50 Watts 10.50%
OUTPUT 1 db LOSS CALCULATIONS
LABEL WATT MODEL db LOSS db Loss=20log10(RL/(RL+RW()
FAAB-Fl EDA2001112PV' _„�-� �Al2
SF1-1-01 1/4W E60H-24MCC-FW .000 dB 70 VRMS (V)Audio Voltage
SF1-1-02 1/2W E60H-24MCC-FW .001 dB 0.0031 Ohm (R)Wire Resistance Per Foot
SF1-1-03 1W E60H-W .002 dB 561.17 Ft (L)Total Circuit Length(One Leg)
SF1-1-04 1/2W E600-24MCC-FW 003 dB 700.00 (RL(Load Resistance=1/"2AN
SF1-1-05 1/2W 44op-246074 005 dB 3.48 Ohm (RW)Circuit Resistance=R*L'2(Both Legs)
SF1-1-06 1W E60H-24MCC-FW .007 dB 7.00 Watt (W)Total Circuit Wattage
SF1-1-07 12W E6019-24MCC-FW .009 dB -0.04 dB Total Circuit Signal Loss
SF1-1-08 1/4W E60H-24MCC-FW .011 dB dB Loss=20log10(RLgRL+RW()
SF1-1-09 1/4W E60H-24MCC-FW .013 dB 14.00% Percent Output Load
SF1-1-10 114W E60H-24MCC-FW .015 dB
5F1-1-11 1/4W E60H-24MCC-FW .017 dB
SF1-1-12 1/4W E60H-24MCC-FW .020 dB
SF1-1-13 1/4W E60H-W .022 dB
SF1-1-14 1/4W E60H-W .025 dB
5F1-1-15 1/4W E605-24MCC-FW .028 dB
SF1-1-16 1/4W E60H-24MCC-FW .031 dB
SF1-1-17 1/4W E60H-24MCC-FW .034 dB
SF1-1-18 1/4W E60H-24MCC-FW .037 dB
PROPRIETARY DOCUMENT FOR APPROVAL ONLY 9/6/2018
OUTPUT 2 db LOSS CALCULATIONS
LABEL WATT MODEL db LOSS db Loss=20Iog10(RL/(RL+RW))
FAAB-Fl a EhA2001 :MOVE' _ ,, ,, z
SF1-2-01 1/2W E60H-24MCC-FW .000 dB 70 VR MS (V)Audio Voltage
SF1-2-02 1/2W E60H-24MCC-FW .001 dB 0.0031 Ohm (R)Wire Resistance Per Foot
SF1-2-03 1/2W E60H-24MCC-FW 001 dB 236.17 Ft (L)Total Circuit Length(One Leg)
SF1-2-04 1/2W E60H-24MCC-FW 003 dB 1400.00 (RL)Load Resistance=V"2AN
SF7-2.05 1/2W E601-1-24MCC-FW .004 dB 1.46 Ohm (RW)Circuit Resistance=R*L*2(Both Legs)
SF7-2-06 1/2W E60H-24MCC-FW 005 dB 3.50 Watt (W)Total Circuit Wattage
SF1-2-07 1/2W E60H-24MCC-FW 007 dB -0.01 dB Total Circuit Signal Loss
dB Loss=20Iog10(RL/(RL+RW))
7.00% Percent Output Load
OUTPUT 3 db LOSS CALCULATIONS
LABEL WATT MODEL db LOSS db Loss=20Iog10(RL/(RL+RW))
FAAB-F1 ^EBA2001
SPARE01 70 VR MS (V)Audio Voltage
0.0031 Ohm (R)Wire Resistance Per Foot
0.00 Ft (LI Total Circuit Length(One Leg)
#DIV/0! (RL)Load Resistance=V"2AN
0.00 Ohm (RW)Circuit Resistance=R'L*2(Both Legs)
0.00 Watt (W)Total Circuit Wattage
#DIV/01 Total Circuit Signal Loss
d8 Loss=201og10(RL/(RL+RW))
0.90% Percent Output Load
PROPRIETARY DOCUMENT FOR APPROVAL ONLY 9/6/2018