Loading...
Plans (81) I I I I MECHANICAL CRITERIA MECHANICAL CRITERIA(CONT.) 5 REVISIONS BY I. BEFORE SUBMITTING A PROPOSAL,THE MECHANICAL CONTRACTOR SHALL VISIT THE 14.FABRICATE AND INSTALL GALVANIZED SHEET METAL DUCTWORK FOR VELOCITIES LESS MECHANICAL SYMBOL LIST O 30 5 SITE OF WORK AND FAMILIARIZE HIMSELF WITH ALL SITE CONDITIONS.MECHANICAL THAN 2000 FEET PER MINUTE AND STATIC PRESSURES LESS THAN Ti WATER GAUGE IN ® SUPPLY AIR DUCT UP 'C C4 Yo p CONTRACTOR SHALL CAREFULLY EXAMINE ALL CIVIL,ARCHITECTURAL,STRUCTURAL. ACCORDANCE WITH THE LATEST EDITION OF THE'LOW VELOCITY DUCT CONSTRUCTION ® SUPPLY AIR DUCT DOWN Q C Z p PLUMBING,MECHANICAL AND ELECTRICAL CONSTRUCTION DOCUMENTS.SUBMISSION STANDARDS-AS PUBLISHED BY THE SMACNA.PROVIDE ELBOWS,BRANCHES AND TEES OF A BID WILL ACKNOWLEDGE THE MECHANICAL CONTRACTOR HAS VISITED THE SITE IN SUPPLY AND RETURN DUCTS WITH TURNING VANES PER SMACNA STANDARDS. Z C0 V AND EXAMINED ALL CONSTRUCTION DOCUMENTS AND BID INSTRUCTIONS.THE INSULATED FLEXIBLE DUCT SHALL BE THERMAFLEX"TYPE MK-E.DUCT SIZES SHOWN RETURN AIR DUCT UP x A ;A. MECHANICAL CONTRACTOR'S BID SHALL INCLUDE ALL MECHANICAL WORK IN THE ON THE DRAWINGS ARE SHEET METAL SIZE AND INCLUDE DUCT LINER AS SCHEDULED Q Z CONSTRUCTION DOCUMENTS,INCLUDING MECHANICAL WORK RELATED TO EQUIPMENT ON THE DRAWINGS.DUCTWORK WITHOUT AN INSULATION TAG IS NOT LINED OR RETURN AIR DUCT DOWN U 1n NZ Lj /1 PROVIDED BY OTHERS. EXTERNALLY INSULATED.THE MECHANICAL CONTRACTOR SHALL PROTECT ALL DUCT ® • S w SZ SYSTEMS AND MECHANICAL EQUIPMENT OPENINGS FROM CONSTRUCTION DUST AND EXHAUST AIR DUCT UP U 2. MECHANICAL CONTRACTOR SHALL REQUEST CLARIFICATION ON ANY ITEMS)OF THE DIRT.FOR MECHANICAL EQUIPMENT OPERATED DURING CONSTRUCTION.PROTECT Z 'y'0 as O O Y EXHAUST AIR DUCT DOWN CONTRACT DOCUMENTS THAT ARE NOT UNDERSTOOD OR WHERE COMPACTS MAY EACH RETURN AIR DUCT OPENING WITH MERVB ALTERSTIAND INSTALL MERVB A H Q O EXIST.CLARIFICATIONS MUST BE PRESENTED AS A-REQUEST FOR INFORMATION"(RFI) FILTER(S)IN EQUIPMENT FILTER RACK.UPON COMPLETION OF CONSTRUCTION, CHANGE IN DUCT SIZE ` UOyyy�j ■r IN WRITING PRIOR TO SUBMITTING A BID.RFI SHALL BE PRESENTED A MINIMUM OF FIVE REMOVE CONSTRUCTION FILTERS AND REPLACE EQUIPMENT FILTERS WITH NEW r^ Z �C o (5)WORKING PAYS BEFORE THE BID DATE.OBTAIN THE RFI FORMAT FILTERS. TURNING VANES V Z L) m m I. �C p WWI.GANDWENGINEERING.COMI000UMEMS.SUBMISSION OF ABIO WILL `+J ACKNOWLEDGE THE MECHANICAL CONTRACTOR UNDERSTANDS THE SCOPE OF WORK. 15.ALL JOINTS AND SEAMS OF NEW DUCT AND DUCT BEING RE-USED SHALL BE CLEANED FLEXIBLE DUCT CONNECTION LV C Q �<Rm 6 MEANS AND METHODS OF INSTALLATION,EQUIPMENT AND MATERIALS TO BE USED.RFI AND SEALED.SEAL NEW DUCTS TO THE FOLLOWING SEAL CLASSES ACCORDING TO ') VV THAT HAVE NOT BEEN CLARIFIED PRIOR TOED,WILL BE PROVIDED BY THE SMACNA"HVAC DUCT CONSTRUCTION STANDARDS-METAL AND FLEXIBLE':SEAL Y 3c 2 •ys= m MECHANICAL CONTRACTOR.AS DIRECTED BY THE ENGINEER OF RECORD,AND THE DUCTS WITH"FOSTER'32-14 SEALANT PER MANUFACTURES INSTALLATION -- HORIZONTAL LIFE SAFETY DAMPER ❑ ^_ MOST STRINGENT MATERIALS,EQUIPMENT,AND SCOPE OF WORK PPLY.NO INSTRUCTIONS FORMIC JOINTS IN LOW AND MEDIUM VELOCITY DUCT. -- VERTICAL LIFE SAFETY DAMPER y 0 Q F ADDITIONAL COMPENSATION WILL BE MADE FOR THE FAILURE OF THE CONTRACTOR TO OUTDOOR,SUPPLYAIR DUCTS:SEAL CLASS A V.�m^ OBTAIN CLARIFICATIONS PRIOR TO BID. OUTDOOR,EXHAUST DUCTS:SEAL CLASS C. -- MOTORIZED AUTOMATIC DAMPER(MAD) V. C OUTDOOR RETURN-AIR DUCTS:SEAL CLASS C. N-- MECHANICAL ABBREVIATIONS di sa g 3. THE MECHANICAL CONTRACTOR'S BID SHALL BE BASED ON THE SCHEDULED UNCONDITIONED SPACE,SUPPLY-A6R DUCTS IN PRESSURE CLASS 2-INCH W.G.AND L__ J MANUAL DAMPER EQUIPMENT.MATERIALS,AND MANUFACTURERS WHICH FORM THE"BASIS OF DESIGN'. LOWER:SEAL CLASS B. ALL OTHER EQUIPMENT,MATERIALS,AND MANUFACTURERS,ARECDNSIDEREO UNCONDITIONED SPACE.EXHAUST DUCTS:SEAL CLASS C. ©c0 CARBON DIOXIDE DETECTOR AFF ABOVE FINISHED FLOOR /'� _� SUBSTITUTIONS.CONTRACTOR PROPOSED SUBSTITUTIONS MUST BE SUBMITTED TO UNCONDITIONED SPACE.RETURNAIR DUCTS:SEAL CLASS B. Al, AUTHORITY HAVING JURISDICTION ` 2 /� THE ENGINEER OF RECORD FOR REVIEW AND WITHUCOMPLETED SUBSTITUTION CONDITIONED SPACE,SUPPLY-AIR DUCTS IN PRESSURE CLASS 2-INCH W.G.AND AHU AIR HANDLING UNIT OFFICE Q P CARBON MONOXIDE DETECTOR AI P ABANDON IN PLACE t OFFICE ■M- THE ENGINEER OF FOR FORME IE W AND WITH A COMPLEEDSUOTITUTI MEATS. CONDITIONED CLASS C. AL ALUMINUM APPROVALS OF SUBSTITUTIONS ARE CONTINGENT UPON ENGINEERS REVIEW.THE CONDITIONED SPACE,EXHAUST DUCTS:SEAL CLASS B. 0 HUMID5TAT ALT ALTERNATE MECHANICAL CONTRACTOR SHALL MAKE NO PRIOR ASSUMPTIONS ON SUBSTITUTIONS LCONDITIONED SPACE,RETURN-AR DUCTS:SEAL CLASS C. AP ACCESS PANEL NOT APPROVED BY THE ENGINEER.IF THE ENGINEER APPROVESASUBSTITUTION 0 MANOMETER AS AIR PANEL REQUEST,THE MECHANICAL CONTRACTOR WILL BE HELD RESPONSIBLE FOR 16. TEST AND ADJUST ALL AIR HANDLING EQUIPMENT,TERMINALS,AND AIR DEVICES TO ATC AUTOMATIC TEMPERATURE CONTROL VALVE ENGINEERING REVISIONS PHYSICAL SIZE,CAPACITIES,COORDINATION, PROVIDE THE REQUIRED AIR VOLUME AGAINST THE AVAILABLE SYSTEM STATIC 0 PRESSURE SWITCH ATR ALL THREAD ROD SUPPLEMENTAL DRAWINGS AND INFORMING OTHER TRADE CONTRACTORS RELATED PRESSURE.TEST AND SET ALL DAMPERS,SUPPLY,RETURN,OUTDOOR AIR AND TO THE INSTALLATION.AS TO ANY SPECIFIED ITEM CHANGES.THE MECHANICAL EXHAUST DEVICES TO THE CFM SHOWN ON THE DRAWINGS.PROVIDE ALL REQUIREDATU AIR TERMINAL UNIT CONTRACTOR SHALL BEAR AS PART OF HIS CONTRACT,ANY ADDITIONAL COSTS SHEAVE AND BELT MODIFICATIONS REQUIRED TO OBTAIN CFM QUANTITIES SHOWN ON 0-- RETURN AIR SMOKE DETECTOR BR MANUAL AIR VENT INCURRED IN HIS WORK OR BY THE OTHER CONTRACTORS AS A RESULT OF THE DRAWINGS.TESTING AND BALANCING SHALL BE IN ACCORDANCE WITH BB BASEBOARD HEATER ® REFRIGERANT(Roo()DETECTOR BD BACK DRAFT DAMPER INSTALLATION FOR OTHER THAN'BASIS OF DESIGN"MATERIALS AND EQUIPMENT. PROCEDURES OUTLINED IN TESTING AND BALANCING MANUAL AS PUBLISHED BY BEES BANKING EQUIPMENT SUPPLIER SMACNA PROVIDE A TEST AND BALANCE REPORT PERFORMED AND PREPARED BY AN DI REFRIGERANT LEAK HORNSTROBE BFF BELOW FINISHED FLOOR 4. MECHANICAL CONTRACTOR SHALL PERFORM WORK INASAFE MANNER.COMPLY WITH INDEPENDENT TESTING AND BALANCING CONTRACTOR CERTIFIED AABC OR NEBB. BMS BUILDING MANAGEMENT SYSTEM APPLICABLE OSHA SAFETY GUIDELINES DURING THE COURSE OF COMPLETES THE PROVIDE AN ELECTRONIC COPY OF THE TESTING AND BLANACING REPORT,INCLUDING 0 THERMOSTAT BOO BOTTOM OF DUCT WORK DESCRIBED ON THESE CONSTRUCTION DOCUMENTS, AMARKED UP PLAN,FOR REVIEW BY THE ENGINEER TESTING AND BALANCING REPORT BOE BOTTOM OF EQUIPMENT CITY OP TIGARD SHALL BE COMPLETED AND PROVIDED TO THE ENGINEER PRIOR TO TENANT MOVE IN. APE/DUCT IN ATTIC BOP BOTTOM OF PIPE 5. SHOP DRAWINGS SHALL BE SUBMITTED ELECTRONICALLY AS PDF FILES.SHOP BS BRANCH SELECTOR-MAN DRAWINGS SHALL INCLUDE TRANSMITTAL PAGES)INDICATING THE NAME OF THE 17.MECHANICAL CONTRACTOR SHALL PROVIDE TEMPERATURE CONTROL WIRING THIS ® PIPE/DUCT BELOW FLOOR OR GRADE CH CHILLER FOR CODE COMPLIANCE PROJECT,AND THE NAME.ADDRESS,AND PHONE NUMBER OF THE GENERAL AND WORK.NO EXCEPTIONS OR EXCLUSIONS.ALL EGUN EQUIPMENT, BE COMPLETE CLG CEILING MECHANICAL CONTRACTORS.GENERAL CONTRACTOR AND MECHANICAL INCLUDING,BUT NOT LIMITED TO:EXPERTISE,DESIGN EQUIPMENT,CABINETS BOXES © PIPEDUCT ABOVE CEILING CO CARBON MONOXIDE O CONTRACTOR SHALL REVIEW SHOP DRAWING SUBMITTALS FOR COMPLIANCE, WATER METERS ES,CONCTRICA CONTACTORS.TRANSFORMERS,CURRENT TRANSFORMERS, CO2 CARBON DIOXIDE , <I CONTENT AND COMPLETENESS AND PROVIDE A STAMP WITH THE DATE OF REVIEW AND WATER AND ELECTRICAL ACCESSORIES.THE EXPANSION OF THE EXISTING EXPOSED DUCT,W/MILL PHOSPHATIZED FINISH CR CONDENSER WATER RETURN OC 1 SIGNATURE OF THE REVIEWER.TRANSMITTAL PAGE SHALL HAVE INDEX WITH BAS INTO THIS TENANT FINISH SHALL INCLUDE ALL REQUIRED COMPONENTS TO CRAC COMPUTER ROOM AIR CONDITIONER Z„ /N Approved: / 1 C ITEMS.NO EXCEPTIONS WILL ESPECIFICATION SEcnoN AND KENSHOPDRAWINGSC PETS O EDBNTH9OORMATWIL BE REJECTED T. EECTMONITRCALUG AS EQUR AND CONTROL HEDBYPROPER E NEW HVAC EQUIPMENT MANAGER WIRING WEXPOSED NATER AND IRETURN ® PIPE DUCT ON ROOF CRCU COMPUTER ROOM CONDENSING UNIT 2Y ( Il �� ]( CS CONDENSER WATER SUPPLY `Ally ` J AND WILL NOT CAUSE REASON FOR AIR PLENUM SHALL BE PLENUM RATED CABLE PROVIDE SHOPORAWINGSFORREVIEW NEWCONNECTIONTO EXISTING IELDPRIORTOERIFYSIZE W, OTC: t 3 . ORDERED UNTIL ENGINEER OF RECORD HAS PROCESSED APPLICABLE SHOP AND PROCESSING THE SHOP DRAWINGS SHALL CONTAINACONTROL SEQUENCE AND LOCATION IN FIELD PRIOR TO BID) CSST CORRUGATED STAINLESS STEEL TUBING �1 CT COOLING TOWER DRAWINGS.AMINIMUM OF SEVEN WORKING DAYS WILL BE ALLOWED FOR SUBMITTAL STATEMENT AND WIRING DIAGRAM WITH ALL PARTS INDICATED ORABILL OF MATERIAL. aN NEW BRANCH DUCT TAP BCONNECTION CU CONDENSING UNIT PROCESSING BY THE ENGINEER.SUBMITTALS SHALL INCLUDE BUT NOT BE LIMITED TO: ALL CONTROLS SHALL BE SUPPLIED IN ACCORDANCE WITH THE BUILDING STANDARDS. TO EXISTING CUH CABINET UNIT HEATER ...1 s ALL NEW SCHEDULED EQUIPMENT AND ACCESSORIES,REGISTERS AND DIFFUSERS, ALL NEW EQUIPMENT AND PROGRAMMING SHALL COMPLY WITH BUILDING STANDARD DDC DIRECT DIGITAL CONTROL Pc in-ru}t 11 �el /, AND TEST AND BALANCE REPORT MONITOR AND CONTROL POINTS ALL COSTS ASSOCIAED WITH HARDWARE, ® DUCT INSULATION(BEESCHEDULE) DIFF DIFFUSER ILI CO d r SOFTWARE AND TIME TO FULLY INTEGRATE THIS NEW EQUIPMENT INTO THE BUILDING PLAN NOTE SYMBOL DISC DISCONNECT DUCTLESS DLSS DUCTLE fi. SUBMIT AND PAY FORMAI REQUIRED WORK PERMITS.PROVIDE ALL REQUIRED STANDARD BAS SHALL BE INCLUDED IN THIS GID. ®®® SS SPLIT SYSTEM ���••• �( INSPECTIONS AND RE-INSPECTIONS.PROVIDE A SIGNED CERTIFICATE OF INSPECTION REVISION SYMBOL DN DOWN 111��� Address$ „,: aa.) y DI c AT THE PROJECT COMPLETION. 18. THE LANDLORDS CONSTRUCTION CRITERIA,LEASE AGREEMENT.AND CONSTRUCTION OPS DIFFERENTIA PRESSURE SWITCH 1 l` ` U ��/ STANDARDS ARE HERE-IN MADE PART OF THIS CONTRACT ALL REQUIREMENTS IN THE e EQUIPMENTCALLOU(SEE SCHEDULE) E) EXISTING Z. ALL EQUIPMENT AND MATERIA LS SHALL BE SPECIFICALLY PROVIDED PER WRITTEN WJDLORDS CONSTRUCTION CRITERIA.LEASE AGREEMENT,DIY CONSTRUCTION Eq EXHAUST AIR Suite,j�� ®s INSTALLATION INSTRUCTIONS AS PUBLISHED BY THE MANUFACTURER OF THE STANDARDS REFERRED TO AS TENANT WORK IS DEFINED AS DIVISION IS MECHANICAL e GRILLE/DIFFUSER CAI-LOUT(SEE SCHEDULE) EBB ELECTRIC BASEBOARD Suite �jq EQUIPMENT OR MATERIAL PROVIDER.MEANSANDTOR METHODS OF INSTALLATION ARE TO WORK ANDNI OBE PROVIDED BY THE CONTRACTOR IT IS THE SEDOCUMENTSNSIBILI OF EC ELECTRICALWORK CONTRACTOR i�� L)`J BE PROVIDED BY THE MECHANICAL CONTRACTOR.MECHANICAL CONTRACTOR SHALL THE MECHANICAL CONTRACTOR TO OBTAIN COPIES OF THESE AND EF EXHAUST FAN GRILLE UNDERSTAND THE PRODUCT,MEANS AND METHODS OF INSTALLATION.THE COMPLETELY FAMILIARIZE HIMSELF WITH THESE DOCUMENTS PRIOR TO BIDDING THIS ® LIFE SAFETY DAMPER CALLOUT(SEE SCHEDULE) EG EXHAUST GRI s ---i}�' Data ik-� . /U MECHANICAL CONTRACTOR SHALL OBTAIN THE INSTALLATION I NSTRUCTIONS AND PROJECT.SUBMI881ON OFA BIO ACKNOWLEDGES THE MECHANICAL CONTRACTOR HAS � EXISTING DUCT TO REMAIN EMS ENERGY MANAGEMENT SYSTEM T® 1 REQUIREMENTS PRIOR TOED.ALL RFI AND CLARIFICATIONS OF SCOPE DURING COMPLIED WITH THIS REQUIREMENT OF THE CONTRACT. __- EQPT EQUIPMENT CONSTRUCTION WHERE THE PURPOSESCONTF.0HAS NOT PREVIOUSLY OBTAINED THIS - EXISTING TO BE DEMOLISHED ER EXHAUST REGISTER INFORMATION FOR BIDDING WILL NOT BE CAUSE FOR ADDITIONAL COSTS 19. THE MECHANICAL CONTRACTOR SHALL DISCONNECT AND REMOVE ALL INDICATED MECHANICAL PIPING ERV ENERGY RECOVERY VENTILATOR OR CONSTRUCTION DELAY. EXISTING MECHANICAL EQUIPMENT OCCURRING IN DEMOLISHED WALLS,FLOORS, ET EXPANSION TANK - ATTICS AND CEILING AREAS.REFER TO THE ARCHITECTURAL DRAWINGS FDR THE EUH ELECTRIC UNIT HEATER 8. THE AL SCOPE OF WORK SHALL BE PROVIDED TO COMPLY WITH THE 2014 GENERAL SCOPE OF DEMOLITION.DISCONNECT AND REMOVE MECHANICAL -A- COMPRESSED AIR LINE EWC ELECTRIC WATER COOLER OREGONONMECHANICAL SPECIALTY CODE,LOCAL ORDINANCES,STATE LAW.AND EQUIPMENT,DUCTS,AIR DEVICES,AND PIPING OCCURRING IN THESE AREAS. EWH ELECTRIC WATER HEATER ITY FEDERAL LAW.REFER TO THE ARCHITECTURAL CODE BLOCK OR THE MUNICIPALMECHANICAL COMPONENTS INCLUDING MOTORS TEMPERATURE CONTROL DEVICES. -CD- CONDENSATE DRAIN EXH EXHAUST n WEBSITE FOR THE APPLICABLE CODES AND ADOPTED ORDINANCES PRIOR TO BID. GRILLES,DIFFUSERS,AIR TERMINALS,HANGERS,MOUNTING HARDWARE,ETC.,MUST BE ---CD--- CONDENSATE DRAIN BELOW FLOOR OR GRADE FA FIRE ALARM p SUBMISSION OF A BID ACKNOWLEDGES THE MECHANICAL CONTRACTOR HAS REMOVED FROM THE PREMISES.TO BE LEGALLY DISPOSED OF BY THE MECHANICAL --CR--- CONDENSER WATER RETURN FAAP FIRE ALARM ANNUNCIATOR PANEL Q PERFORMED THIS REQUIREMENT AND THE BID INCLUDES LABOR ANC MATERIAL TO CONTRACTOR.ALL LOOSE ENDS OF SYSTEMS WHERE SUCH ABANDONMENT HAS FACP FIRE ALARM CONTROL PANEL PROVIDE CODE COMPLIANCE.SEISMIC RESTRAINTS AND ANCHORAGE SHALL BE TERMINATED SHALL BE TRIMMED CLEAR AND APPROPRIATELY CAPPED OR SEALED IN A -CS- CONDENSER WATER SUPPLY FC FLEX CONNECTION PROVIDED TO COMPLY WITH THE 2014 OREGON BUILDING SPECIALTY CODE. SAFE AND SECURE MANNER BEHIND NEW FINISHES.MAINTAIN SYSTEM CONTINUITY TO --CHR-- CHILLED SHOT WATER RETURN FCU FAN COIL UNIT ADJOINING AREAS AS NEEDED,THIS INCLUDES BUT IS NOT LIMITED TO REMOVAL, FD FIRE DAMPER 111 9. MECHANICAL CONTRACTOR SHALL PROVIDE FIELD COORDINATION WITH OTHER MODIFICATION AND REINSTALLATION OF EQUIPMENT AS NEEDED TO SUSTAIN THE -CHS- CHILLED B HOT WATER SUPPLY FPC FIRE PROTECTION CONTRACTOR C TRADES:SYSTEMS AS SHOWN ARE DIAGRAMMATIC AND GIVE THE GENERAL EXISTING WORKING CONDITION OF ALL MECHANICAL EQUIPMENT AND TO RETURN --GWR-- CHILLED WATER RETURN FRT FIRE-RETARDANT-TREATED ARRANGEMENT AND LOCAHONS ONLY.MECHANICAL CONTRACTOR SHALL THESE AREAS TO FULL WORKING ORDER AT PROJECT COMPLETION. FSC FOOD SERVICE CONSULTANT v �M COMPLETELY REVIEW ARCHITECTURAL DRAWINGS,STRUCTURAL DRAWINGS,CEILING -CWS- CHILLED WATER SUPPLY FSD FIRE/SMOKE DAMPER W: OPC la ELEVATIONS AND SYSTEM DRAWINGS OF OTHER TRADES FOR DETAILS OF 20,THE MECHANICAL CONTRACTOR SHALL CONFINE HIS ACTIVITIES TO THE AREA SET -D- DRAIN LINE FSEC FOOD SERVICE EQPT.CONTRACTOR Z0/ f0^ CONSTRUCTION ROUGH 4N OF MECHANICAL DEVICES,AIR TERMINALS,EQUIPMENT, ASIDE FOR HIM TO DO HIS VVOK AND SHALL NOT INTERFERE WITH ANY OF THE OWNER FTU FAN TERMINAL UNIT �VVy[O PIPING,ATTACHMENTS,AND HANGERS SHALL BE BASED ON THIS REVIEW.EXACT OR TENANT ACTIVITIES.THE MECHANICAL CONTRACTOR WILL NOT BE PERMITTED TO -G- GAS LINE FV FIELD VERIFY W��' le 15 LOCATIONS AND FINAL LAYOUT SHALL BE DETERMINED IN THE FIELD.PROVIDE ALL STORE MATERIAL EXCEPT WITHIN THE AREAS AS DIRECTED BY THE G.C.SHOULD ANY -HG- HOT GAS LINE GC GENERAL WORK CONTRACTOR ■ NECESSARY EQUIPMENT.DUCT TRANSITIONS,FITTINGS,HANGERS,SUPPORTS,AND DISTURBANCE OF EXISTING INSTALLATION BE NECESSARY,THE CONTRACTOR SHALL SF GAS FURNACE OFFSETS REQUIRED FORA COMPLETE INSTALLATION IN ALL RESPECTS.THE --HPWR-- HEAT PUMP WATER RETURN SO INFORM THE OWNER OR TENANT WELL IN ADVANCE OF THE TIME CONTEMPLATED GWH GAS WATER HEATER MECHANICAL CONTRACTOR MEANS AND METHODS OF INSTALLATION SHALL PROVIDE FOR THE DISTURBANCE.AFTER A PLAN ACCEPTABLE TO THE OWNER OR TENANT HAS -HAWS- HEAT PUMP WATER SUPPLY HP HEAT PUMP FOR OPERATING EFFICIENCY,NEATNESS OF APPEARANCE,AND EASE OF BEEN FORMULATED,THE G.C.SHALL KEEP IN CLOSE PERSONAL CONTACT WITH THE HP HORSEPOWER MAINTENANCE.THE1111 MECHANICAL CONTRACTOR WILL PREPARE DIMENSIONED FIELD WORK TO SEE THAT IT IS EXECUTED IN ACCORDANCE WITH THE AGREED PROCEDURE. --HPC-- HIGH PRESSURE CONDENSATE HRCU HEAT RECOVERY CONDENSING UNIT Y WHERE ERECTION DRAWINGS WHERE REQUIRED FOR USE BY THE INSTALLERS,TO INSURE --HRR-- HOT WATER RETURN HWCP HOT WATER CIRC.PUMP • PROPER INSTALLATION AND COORDINATION.THE MECHANICAL CONI KACTOR SHALL 21,CONTINUITY OF ALL BUILDING SERVICES AND UTILITIES SERVING FACILITIES IN THEHX HEAT EXCHANGER -HAS- HIGH PRESSURE STEAM TAKE THEIR OWN MEASUREMENTS AT THE BUILDING.AND BE RESPONSIBLE FOR THE BUILDING SHALL BE MAINTAINED WITHOUT INTERRUPTION,EXCEPT FOR SUCH APERIOO MAH INAIR HOOD i CORRECT LAYOUT,INTERPRETATION.AND USE OF ALL SIZES AND DIMENSIONS.THE OF TIME DESIGNATED BY THE G.C.THE MECHANICAL CONTRACTOR SHALL SO -HWS- HOT WATER SUPPLY IOM INSTALLATION 8 OPERATION MANUAL CONTRACTOR SHALL KEEP'AS-BUILT'INFORMATION DURING CONSTRUCTION AND ARRANGE AND EXECUTE HIS WORK THAT ANY CONNECTIONS,EITHER TEMPORARY OR -CPS- LOW PRESSURE STEAM ID INSIDEDEMETER d FURNISH TO THE OWNER OR TENANT A RECORD SET OF LEGIBLE BLACK LINE PRINTS PERMANENT,OR REARRANGEMENT OF PRESENT EQUIPMENT.DUCTWORK AND PIPING IR INFRA-RED TUBE HEATER(GAS) AND AN ELECTRONIC COPY OF THESE DOCUMENTS AT THE PROJECT COMPLETION. SHALL BE IN SUCH A MANNER AS TO ASSURE FULL RESUMPTION OF SERVICE AT THE --MPC-- MEDIUM PRESSURE CONDENSATE IV INTAKE VENTILATOR TIME DESIGNATED BY THE G.C.PROVIDETEMPORARY CROSS CONNECTIONS,DUCTS, -MPS- MEDIUM PRESSURE STEAM KEF ETCHES EXHAUST FAN 1,REVIEW ARCHITECTURAL DRAWINGS AND EXISTING SITE CONDITIONS FOR ALL FIRE PIPING,HANGERS AND VALVES NECESSARY TO ASSURE THIS CONTINUITY OF THE LLSV LIQUID LINE SOLENOID VALVE RATINGS AND FIRE RATED ASSEMBLIES PRIOR TO BIDDING THE PROJECT.PROVIDE FIRE BUILDING MECHANICAL SYSTEM AT NO ADDITIONAL COST TO THE OWNER OR TENANT. -MUW- MAKE-UP WATER LV LOUVER STOP AT EACH RATEDWALL,FLOOR,CEILING-ROOF ASSEMBLY PENETRATION.FIRE MAINTAIN IS DEFINED TO INCLUDE,BUT IS NOT UMITED TO,REMOVAL,MODIFICATION -RL- REFRIGERANT LIQUID LINE LPG LIQUIFIED PETROLEUM GAS(PROPANE) STOP SYSTEMS SHALL BE MANUFACTURED BY.3M".PROVIDE IN STRICT COMPLIANCE AND REINSTALLATION OF EQUIPMENT AND PIPING AS NEEDED TO SUSTAIN THE -RS- REFRIGERANT SUCTION LINE WITH THE MANUFACTURERS APPLICATION DETAILS RNVIDESHOPDA PROVIDE CONTING RACTOR SHALLCONDITIONURTHE MECHANICAL OR ARESTTO RILL MECHANICAL MC MECMUMCACUITAMCONTRACTOR TAGGED CERTIFICATIONS AT EACH PENETRATION.PROVIDE SHOP DRAWINGS FOR CONTRACTOR SHALL RETURN THESE SYSTEMS OR AREAS TO FULL WORKING ORDER //T�YPE-K/iF EXISTING PIPE TO BE REMOVED MCA MINIMUM CIRCUIT AMPERES REVIEW WITH THE U.L.USIING AND TEST CRITERIA.PROVIDE FIRE STOPPING WHERE AT PROJECT COMPLETION. Ira/T EXISTING PIPE TO BE REMOVED MCC MOTOR CONTROL CENTER REQUIRED BY THE AUTHORITY HAVING JURISDICTION.EQUAL SYSTEMS AS MD MANUAL DAMPER MANUFACTURED BY'SPEC SEAL-OR"HILTI"WILL BE ACCEPTABLE -TYPE(E)- EXISTING PIPING MIN MINIMUM MECHANICAL PIPING SYMBOLS MH MOUNTING VEICT 11.PROVIDE DUCT.PIPING.AND HANGER PENETRATIONS OF NON-RATED ASSEMBLIES MOCP MAXIMUM OVER CURRENT PROTECTOR WITH DRAFT STOPPING OR SMOKE BARRIER SEALANT SYSTEMS.THROUGH MTD MOUNTED PENETRATION SEALANT SYSTEMS SHALL BE MANUFACTURED BY SAPPLY IN STRICT 0 AUTOMATIC AIR VENT(AAV) MUA MAKE-UP AIR COMPUANCE WITH THE MANUFACTURER'S APPLICATION DETAILS ANDND INSTRUCTIONS. m AUTOMATIC FLOW CONTROL VALVE MUW MAKE UP WATER PROVIDDE DRAFT STOPPING OR SMOKE BARRIER SEALANTS TO MEET APPROVAL OF THE NC NORMALLY CLOSED AUTHORITY HAVING JURISDICTION.EQUAL SYSTEMS AS MANUFACTURED BY'SPEC AUTOMATIC TEMPERATURE CONTROL NIC NOT IN CONTRACT SEAL"OR TILT'WILL BE ACCEPTABLE GENERAL NOTES:MECHANICAL VALVE(3-WAY) NO NORMALLY OPEN O AU VE(2-C rliATURE CONTROL OA OUTDOOR AIR 12. THE MECHANICAL CONTRACTOR SHALL GUARANTEE ALL LABOR,EQUIPMENT AND A. CONTRACTOR SHALL CAREFULLY COORDINATE ANY FLOOR PENETRATIONS WITH W yMVE(2-WAV) OD OUTSIDE DIAMETER MATERIAL INSTALLED UNDER THIS CONTRACT TO BE FREE FROM DEFECTS FOR A GENERAL CONTRACTOR,TENANTS CONSTRUCTION COORDINATOR.BUILDING OWNERS 6 mu_VALVE(BA) OX OXYGEN W PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE AND SHALL REPAIR OR REPRESENTATIVE AND TENANT BELOW.POST TENSIONED FLOOR SLAB CONSTRUCTION PC PLUMBING WORK CONTRACTOR REPLACE WITHOUT COST TO THE OWNER ANY EQUIPMENT WHICH IS DEFECTIVE OR SHALL BE X-RAYED AND ALL STRUCTURAL SYSTEMS PERMANENTLY MARKED ON THE nl CHECK VALVE(CV) PCF POUNDS/CUBIC FOOT IMPROPERLY INSTALLED.IN ADDITION,THIS CONTRACTOR SHALL ASSUME FULL FLOOR STRUCTURE AND IDENTIFIED PRIOR TO ANY PENETRATION BEING PERFORMED. 0 CIRCUIT SETTER(CS) PSG PUMP SUCTION GUIDE U}J RESPONSIBILITY FOR ANY DAMAGE TO THE BUILDING AND ITS CONTENTS OR OTHER PT PRESSURE TREATED EQUIPMENT CAUSED BY DEFECTS OR IMPROPER INSTALLATION OF EQUIPMENT OR B. LONG LEAD TIME ITEMS THAT MAY IMPACT THE PROJECT SCHEDULE MUST BE A COMPRESSED AIR QUICK-CONNECT PVC POLYVINYL CHLORIDE MATERIALS INSTALLED UNDER THIS SECTION OF THE WORK. IDENTIFIED ALONG WITH THE SCHEDULE IMPACT VET TDNIC OF BIO.FAILURE TO RA RETURN AIR COMMUNICATE LEAD TIME ISSUES WILL RESULT IN THE CONTRACTOR,AT HIS EXPENSE, -D- CONCENTRIC PIPE REDUCER RAH RELIEF AIRILLE 13.MECHANICAL CONTRACTOR SHALL CUT ANDPATCHREQUIRED PATCH AFTER DEMOLITION) PROVIDING TEMPORARY FIXTURES OR EQUIPMENT TO ALLOW FOR SCHEDULED TENANT _N- ECCENTRIC PIPE REDUCER RF RETURN FAN ROOF,FLOORS,WALLS,AND CEILINGS WHERE REQUIRED TO INSTALL NEW OCCUPANCY.THE TENANT/DESIGN TEAM WILL CONSIDER ALTERNATE PRODUCT RG RETURN GRILLE MECHANICAL EQUIPMENT,DUCT,AND/OR PIPING SYSTEMS AND/OR DEMOLITION OF SUGGESTIONS BY THE CONTRACTOR(IF SUBMITTED PRIOR TO BID)TO MAINTAIN THE I EMERGENCY GAS SHUTOFF VALVE RL EXISTING DEVICE RELOCATED SUCH.SURFACES SHALL BE PATCHED AND LEFT READY FOR FINAL SCHEDULED FINISH. SCHEDULE. RR RETURN REGISTER ROOFING REPAIRS SHALL BE PERFORMED BY A QUALIFIED ROOFING CONTRACTOR LAT FLEXIBLE PIPE CONNECTION RTD RESISTANCE TEMPERATURE DETECTOR THAT MAINTAINS THE ROOF WARRANTY AT THE MECHANICAL CONTRACTOR'S EXPENSE, C. CONTRACTOR SHALL PROVIDE TEMPORARY/PORTABLE EQUIPMENT FOR COOLING RTU ROOF TOP UNIT ALL ROOFING WORK SHALL BE INCLUDED IN THE MECHANICAL CONTRACTORS BID. AND/OR HUMIDITY CONTROL IF REQUIRED FOR CONSTRUCTION AND APPLICATION OF 0 GAS SHUT-OFF VALVE(SOV) RV RELIEF VENTILATOR — FINISHES. SA SUPPLY AIR 041 GATE VALVE(GT.Al SO SPLITTER DAMPER Z Irl- GEAR OPERATED BUTTERFLY VALVE SF SUPPLY FAN Q SG SUPPLY GRILLE T W GLOBE VALVE(GL.V.) SMS SHEET METAL SCREW U HOSE END VALVE SS STAINLESS STEEL SSF SIDE STREAM FILTER (-0MANUAL AIR VENT(MAV) TA TRANSFER AIR TEMP TEMPORARY M • PETE'S PLUG TOT TOP OF DUCT (TEMPERATURE S PRESSURE PORT) TOP TOP OF PIPE IFA PLUG VALVE TXV THERMAL EXPANSION VALVE TYP TYPICAL 0 PRESSURE GAUGE UH UNIT HEATER WE 05/23/2018 LION UNLESS OTHERWISE NOTED ft PRESSURE REDUCING VALVE(PRV) UNV UNIVERSAL SC. AS NOTED STRAINER(STIR) (ITR UP THROUGH ROOF NO IV VAV VARIABLE AIR VOLUME R JNA V' STRAINER WITH SLOWDOWN V. VARIABLE FREQUENCY DRIVE 8 VRF VARIABLE REFRIGERANT FLOW J® ■ THERMOMETER VRV VARIABLE REFRIGERANT VOLUME 0E14014 VSO VARIABLE SPEED DRIVE RN TRIPLE DUTY VALVE(IDV) W/ WEATHERPROOF ITH 5112a1-- VALVE IN RISER WP ATER SO R CE M 100 WSHP WATERSOURCEHEAT PUMP La WATER METER )(FMR TRANSFORMER I 6 9Ef]S ILL O WI NOEB/1MPRERY MM.IIS CANON LM CWTOOR Mm 850 PRCPFRIY MOILS N TNM RN6 TESE NMC Mm ORNNZ I E I P TO E M'RWNICEO.OWI=OR COPED N NNY RM01 C9 MNN.NW9I4FR Om OUT 09T0IMC SE P 01181 141OE190X OF LEL CE900N NOR AM REV 10 E MO.10 MCI T W POET 11011OR FPR WIHM 051F9 P1A109011 Mm COMDR. REVISIONS BY MAIN DUCT WITH("3PCF DENSITY LINER GRILLE,REGISTER,AND DIFFUSER SCHEDULE "TITUS o = s 1"3 PCF DENSITY LINER o n SPIN IN WITH MANUAL VOLUME DAMPER Q �Q O n SPIN IN WITH DAMPER PLAN MODEL NO.' NECK SIZE FACE SIZE MAX PD. BORDER PATTERN FINISH NOTES =z Z v MARK INSULATED FLEXIBLE DUCT(8'MAX.LENGTH) INSULATED FLEXIBLE DUCT(B'MAX.LENGTH) EX-S EXISTING SUPPLY DIFFUSER;BALANCE TO INDICATED CFM 7,3 O 6 Y ,;; `) 90 ADJUSTABLE ELBOW PULL FLEXSA PAS 60 24"x24" 110 0.1 TYPE 3 4-WAY 026 1,2,3 Z INSULATION OVER ELBOW TO GRILLE \ - g U 0 SB PAS 80 24"x24" 235 0.7 TYPE 4-WAY #26 1,2,3 IZ CONNECTION,SEAL WITH TIE WRAP. L7 ♦ Y j PULL FLEX INSULATION OVER \ SC PAS 100 24"x24" 400 0.1 TYPE 3 4-WAY2 CONNECT WITH SHEET METAL SCREWS 4 , ( I�ME I \. 026 2,4,3 Z Z1 i- 3 LOCATIONS AT COLLAR. 1 COLLARS SEAL WITH TIE WRAP. _ N O CONNECT WITH SHEET METAL 0 SD TBD(-80 100 48"x(2)1"SLOTS 300 0.1 TYPE 3 2-WAY #26 2,4 'c < O STANDARD CEILING SCREWS 4 LOCATIONS AT \ i e (V 2 Etj GRID SUPPORT PATTERN COLLAR. / C g 1,3 U O i,� 3 m L •r 7 2 EX-R EXISTING RETURN GRILLE Z c 3 M in SECURE DIFFUSER TO CEILING DIFFUSER PLENUM FULL SIZE- I I ttZ1M 3 U _I�<a N o OF DIFFUSER NECK,INSULATE NOTES: 1. SECURE GRILLE/DIFFUSER TO CEILING GRID WITH q MINIMUM OF(4)810 TECH SCREWS. Z ? f "� Y S S GRID WITH A MINIMUM OF(4) () L n 6 WITH 1/2"-2#DENSITY LINER 2. MECHANICAL CONTRACTOR TO VERIFY CEILING CONSTRUCTION WITH ARCHITECT AND EXISTING CONDITIONS AND ENSURE THAT S�C #10 TEK SCREWS. ® q a_ 3 I 1 } IT IS COMPATIBLE WITH GRILLE,REGISTER,AND DIFFUSER FRAMING,INCLUDING BORDER TYPES,T-BARS,AND CROSS NOTCHES, V 0 \1N 48 £ 3. FRAME TO FIT LAY-IN CEILING NO SCREW HOLES. Q V 6j- $ LAY-IN DIFFUSER I SPIN IN COLLAR 4. PROVIDE WITH MISC.CEILING GRID TEES. .7 PER SCHEDULE J t 1°i.� k III \\ \ (I f $ 0 LAY-IN CEILING DIFFUSER AND BRANCH DUCT _I VENTILATION AIR SCHEDULE - 8 NIEFLAY-IN SLOT DIFFUSER PER SCHEDULE 2014 OREGON MECHANICAL SPECAILTY CODE NO SCALE (2014 OMSC)MINIMUM VENTILATION RATES 0 LAY-IN CEILING DIFFUSER AND BRANCH DUCT ROOM NAME ROOM NUMBER ZONE FLOOR ZONE TABLE 403.3 MINIMUM TABLE 403.3 MINIMUM TABLE 403.3.1.2 OUTSIDE AIR SUPPLY RETURN AREA SQ.FT. POPULATION VENTILATION RATE VENTILATION RATE ZONE AIR DISTRIBUTION BASED ON NO SCALE (Ai) (Pi) (CFM/PERSON) (CFM/SO.FT.) EFFECTIVENESS(D) 2014 OMSC AIR AIR OPEN OFFICE REFER TO PLAN 6595 33 5 D.06 0.8 751 8650 PRIVATE OFFICES REFER TO PLAN 575 4 5 0.06 0.8 68 1000 CONFERENCE ROOMS 501,502,535,536,537 965 30 5 0.06 0.8 260 1550 BREAK ROOM 522 1195 6 5 0.06 0.8 127 1875 TRAINING ROOM 523 1240 62 5 5.06 0.8 481 2675 MOTHER'S ROOM 540 115 1 5 0.06 0.8 12 75 RECTANGULAR DUCT HANGER SCHEDULE BAR JOIST OR PRINT 534 220 1 5 0.06 0.8 23 300 PAIR SPACING: 10 FT. BFT. 5FT 4FT. OTHER CORRIDOR REFER TO PLAN 1280 0 - 0.06 0.8 96 250 LOW PRESSURE /RIGID ROUND DUCT PER DUCT PERIMETER. STRUCTURAL STORAGE 538,541 375 0 - D12 0.8 56 125 E (MAXIMUMTED FLEX VINM MIME MIS DRAWINGS MAYJMUM HALF WIRE/ WIRE/ WIRE( WIRE/ COMPONENT $_�C 6 STRAP STRAP STRAP STRAP W-,-' ROD ROD ROD ROD - IN.xGA IN.xGA IN.xGA IN.xGA 1111. • TOTAL FIFTH FLOOR 1812 16500 14688 . SII II� Pn=30' , PROPERTY MANAGER TO ADJUST OUTDOOR AIR SYSTEM TO COMPLY WITH OUTDOOR AIR REQUIREMENTS. LW (x22 10 GA 1x22 10 G4 1x22 1z GA 1x22 12 GA ' .13s) 4135•) I.t06^) (.toe-) PI2=1Y x16 3/6" 1x20 1/41 1x22 1/7 1x22 1/41 DIFFUSER SPIN-IN WITH LOCKING Fa=266• 1 x 16 3/7 1 x 18 &B• 1 x20 3/6• 1 x 22 1/4• ALVANIZED QUADRANT DAMPER P SHEET METAL (SEE GRILLE,REGISTER 8© )TY ) Pa=,2°' sx,e IIU 7x76 air 1z18 air 1020 //2 II, STRAP TERMINAL UNIT SCHEDULE W DIFFUSER SCHEDULE) P/2=166• 1.5x18 1/7 1.5x16 1/2• 1x16 3/9- 1x18 3'6- "TRANE -I P/2=152• NONE 1n" 1.5116 1/2• 1116 57 1416 NT /, P/2=193'. SPECIAL ANALYSIS REQUIRED "MODEL SIZE CFM STATIC PRESSURE NC LEVELS FAN ELECTRIC HEAT COIL NOTES v INSULATED SHEETMETAL DISCHARGE VARIABLE VOLUME BOX dik PLAN MARK SINGLE HANGER MAXIMUM ALLOWABLE LAP JOINED STRAPS, LOAD RATED PLENUM(MINIMUM 5'-0"LONG) / (SEE SCHEDULE) UNIT OUTLET MAX A'71N. INLET DOWN MIN. RAD. DISCH. CFM ESP HP CFM KW V/PH. STEPS EAT. LAT. I LOAD FASTENERS(PLACE FASTENERS IN I, SHEET METAL W / RUBBER VIBRATION ISOLATORS 8 SERIES,NOT SIDE BY SIDE): 'I� SCREW FP5-1 EXISTING 100 850 230 8.0 90 3/8"ALL THREAD ROD(TYP.OF 4) STRAP WEIGHT WIRFJ WEIGHT STRAP FASTENERS W/WASHER FP 5-2 EXISTING 80 - 750 150 - - - _ _ _ _ - q,5 - - - 90 VAV AIR INLET ROD IN.xGA (QTY)-SIZE FP5-3EXISTING 80 - 750 150 4.5 - - - 90 STRAIGHT RIGID ROUND IN.xGA LBS. 0(IN.) LBS. 1522 260 0.106 80 'x16,2°'22 (2)-#10SMS O (t)-1/4.0 BOLT FP 5-0 EXISTING 80 - 600 150 5.0 - - - 90 - FP 5-5 EXISTING 80 - 900 150 - DUCT MIN.3 DIAMETERS 1 x 20 320 0.135 120 1 x 16 (2)-I/ER BOLT FP 5-9 EXISTING 100 - 1025 2308.0 - - - 90 III1818 420 0.162 160 1.5x16 (2)-3/6"0 - - - - - - _ - - 6.0 - - - 90 TRANSITION TO VAV FP 5-10 EXISTING 100 - 1275 230 - - - - - _ 4 INLET SIZE 878 100 v4 270 STRUCTURE FP 5-11 EXISTING 80 - - _ _ _ _ _ _ STAINLESS STEEL BANDING tsx t6 1100 306 680 NOT REQUIRED FOR FP S-12 EXISTING 80 - - - _ _ _ _ _ - _ 4 1/2 1 DUCTWORK WITH - - - - q-0 - 90 1 .� STRAP(TYPICAL) &6 ' I/ FP S73 EXISTING 8ID - 900 150 - - - _ _ _ - - - - 2000 LESS THANS.SE B SQ.FT. MEDIUM PRESSURE CONICAL FITTING MAX. HANGER STRAPS CROSSSECTIONAL FP 5-17 EXISTING 80 - 875 150 - _ _ _ _ _ _ _ 3.5 - - - 90 1 Si -- &9 3000 (SEE CHART) AREA INSULATED FLEX MAFP 5-18 EXISTING 80 - - - - (MAXIMUM 3'-0"LONG) NOTE:TABLE ALLOWS FOR DUCT WEIGHT.1 LB./SQ.FT.INSULATION WEIGHT,AND NORMAL 4 REINFORCEMENT AND TRAPEZE WEIGHT. 60 in.MAX UNLESS FOOT OF FP 5-21 EXISTING 80 600 150 - - - _ 3.0 - - - 90 1 STRAP IS PLACED FP 5-23 EXISTING 80 4 § UNDERABOTTOM REINFORCEMENT MAIN SPIRAL SUPPLY DUCT -I I W 5-1 EXISTING 80 - 800 150 - - - _ _ _ _ _ _ - - - - (MEDIUM PRESSURE) - W 5-2 EXISTING 80 - 550 150 - _ _ _ - - - - 257 _ 2.5 - 1 �� L. .J VV 5-6 EXISTING 80 - 800 150 - - - - _ _ _ _ 2.0 - - - 1 z`p © VAV BOX INSTALLATION DETAIL SCREWS VV 5-7 EXISTING 80 800 150 2,p - a J¢ VV S8 EXISTING 80 - 550 150 - - - - _ _ _ _ - - - - �W(� LL O lap 2.01 �" NO SCALE / MIN. VV S9 DEMO 80 5 F) . " HANGER VV5-11 EXISTING 60 - 300 100 - - - - _ _ _ _ _ 1.0 - , Z �QI VV Sit EXISTING 60 - 250 0 - - - - - _ _ _ - 1.0 - _ , }y 1111 STRAP LOAD RATED W S13 DEMO 60 = - - - - - - - W FYFY WASHER WASHER FASTENERS 5 -` VV 5-14 EXISTING 80 q V NUT BAND OF SAME SIZE AS HANGER STRAP VV 5-15 VCEF 100 14612 1000 230 1.0 0.25 0.14 24 28 675 7.5 480/3 2 55.0 90.1 3 NOTE. EQ EQ.ON COLUMN OR 1'-0" VV 5-16 VCEF 80 11810 605 150 1.0 0.25 0.03 23 29 - - - 400 4.5 480/3 2 55.0 90,6 3 0- PROVIDE INTERMEDIATE BLOCKING FROM EDGE OF WALL VV 5-17 VCEF 120 17814 1400 325 1.0 0.25 0.13 24 27 - - - 700 7.5 480/3 2 55.0 88.9 3 FOR DEVICES AS REQUIRED FOR / / r___ / WASHERS MAYBE OMITTED VV 5-18 VCEF 80 11010 775 150 1.0 0.25 0.05 25 28 500 5.5 480/3 2 55.0 89.8 3 6" 1'-0" FA VISUAL SIGNAL PLACEMENTL DIMENSIONED BLE / / WITH 100LBMA%LOAD ON 36.0 MAX - - - \ MJJ/ 2z Gn STRAP wHEN FOLDED 24.0 MAX. NOTES. 1. EXISTING UNIT,BALANCE AS SHOWN.UNIT HAS ELECTRIC HEAT,SET HEATING PRIMARY CFM TO PROVIDE 90 DEGREE DISCHARGE TEMPERATURE. F.A.VISUAL SIGNAL WHERE APPLICABLE \ } 2. EXISTING UNIT,BALANCE AS SHOWN. EDGE OF COLUMN OR WALL 1 THERMOSTAT WALL-MOUNTED \ 3. PROVIDE WITH ELECTRIC HEATING COIL,FIBRE FREE LINER,DISCONNECT SWITCH(DOOR INTERLOCK TYPE),PRESSURE INDEPENDENT BUILDING STANDARD TELEPHONE,OR AN DEVICE © DUCT HANGER DETAILS DIGITAL(DOC)CONTROLS,AND BUILDING STANDARD THERMOSTAT.DOC HARDWARE,INSTALLATION AND PROGRAMMING SHALL BE IN ACCORDANCE WITH /g; PROPERTY MANAGEMENT REQUIREMENTS, NO SCALE ADDITIONAL DEVICES 4. EXISTING UNIT NOT IN SCOPE OF WORK.SHOWN FOR REFERENCE ONLY.NO CHANGE. \ / A I THERMOSTAT(TYP.) 5. DEMO EXISTING UNIT. WHERE MULTIPLE SWITCHES OCCUR, / j GANG WITH SINGLE COVER PLATE -`�n \ A THEN LOCATE THE OTHER DEVICES -LIGHT SWITCH(TYP.) co CENTERED OFF FURTHEST LIGHT SWITCH /�/ tO SWITCH OR DIMMER H iL a ' MAINTAIN MINIMUM 12"CLEARANCE IN FRONT OF DUCT INSULATION SCHEDULE DUPLEX RECEPTACLE,r:jFLOOR/ROOF DUCT OPENING AND 8.CLEARANCE ABOVE. im ¢ - \ COMMUNICATION OUTLET,ETC. CONSTRUCTION COORDINATE WITH ALL OTHER TRADES TO ENSURE MATERIAL THICK- FIELD VAPOR DOOR OR SIDE LITE FRAME ` >/ v a. (TYP) ABOVE THIS CLEARANCE IS MAINTAINED. ID TAG K 9H oFrF TRF./0 I I I N REVISIONS BY Z P o-3 ; .'- cC O„ n 4 w �- u0 R ' a p i � z W - Z' F ' o V �'NZ6 o LL W 3 tiki z ; 'O o 0 GENERAL NOTES-MECHANICAL DEMOLITION l] PLAN NOTES-MECHANICAL DEMOLITION w o y 0 c 3 • gA. UNLESS OTHERWISE NOTED,EXISTING DUCT,SUPPLY DIFFUSERS,RETURN AIR GRILLES, 1. CAREFULLY REMOVE AND RELOCATE EXISTING THERMOSTAT.EXTEND CONTROL WIRING TO (J - m Y TRANSFER AIR GRILLES,TERMINAL UNITS AND HVAC CONTROLS SHALL REMAIN AND BE NEW LOCATION. Z m 3 p a REUSED.PROTECT FROM DUST AND DAMAGE. - Q d m_ g 2. CAREFULLY REMOVE AND RELOCATE EXISTING SUPPLY AIR DIFFUSER.REMOVE FLEX DUCT. > e .tn C 5^m 6 B. TURN OVER TO PROPERTY MANAGER/OWNER OR PROPERLY DISPOSE OF ANY REMAINING CAP AND SEAL MAIN DUCT IF BRANCH DUCT IS NOT REUSED. O M- 0 N REMOVED AIR DEVICES AFTER RELOCATED DEVICES ARE ACCOUNTED FOR. O Q L 3. CAREFULLY REMOVE AND RELOCATE EXISTING RETURN AIR GRILLE. erre 4. TEMPORARILY SUPPORT DIFFUSER(S)FOR GRID REMOVAL AND REINSTALL IN NEW GRID. J y$i"" 5. REMOVE EXISTING RETURN AIR TRANSFER. f42'- I 6. REMOVE EXISTING RETURN AIR TRANSFER WITH FIRE DAMPER = • 3 7. REMOVE EXISTING VAV BOX ABOVE CEILING.REMOVE ASSOCIATED CONTROLS,DUCTWORK, DIFFUSERS,AND THERMOSTAT. B. REMOVE EXISTING SPLIT SYSTEM FANCOIL ABOVE CEILING.REMOVE ASSOCIATED THERMOSTAT,DUCTWORK,GRILLES,DIFFUSERS,CONDENSATE AND REFRIGERANT PIPING AND CONDENSING UNIT ON ROOF.PATCH AND SEAL ROOF RAIN TIGHT. 9. REMOVE ALL EXISTING DUCTWORK AND DIFFUSERS DOWNSTREAM OF EXISTING VAV BOX. 10. NO HVAC WORK IN THIS AREA. O 0 0 O ©/,.., p O 0 O iiiE �� .,� :., " ` 'IIE= `, �� Vii• Iii ...1 ilmJ11NJPPlii Am1�)/mlAAl•ii �'i� ii'�' �'i }i ^ 0 I� O -re,E) 4 /0„,,,,,,,,,„ + .2 4 ,re1E) 4/ ,anre) m.(E) ... 1.(E) 0 -,,; 4❑ II O 11�'///�� R ///f ........„7„.____,.....,......0j - 'uiiisJo.�s Fi�sir�iii ii..'r7iK Y si / . !f/ffJf�l ffft %f //l/I'//fv: --7 A' 1100(El � II T cli ITA ®LI7A ® Piii. ii.1 T I I _ v4. o /111[o1 ® 4. IIIIE•o, 14 irk (I� 1II� �' 1 i VW or 1E1 i I et 0 Ala 0 I. ® =1,0Ifili 1 MI % ❑ 'kYem is❑1 — �', !s3 . � ! Or •moi,., %'/r ___ r� i /' ��1�. -_Y�.II i I / § /iii r f�Ersi�e�l I ���/ ��I ��/ /.i /.l / p 5 e, .,i aR1E) a ��% I % Wegir l/ " � ;5��, 'y/ (%%// � rr: o% 1,�py ❑ iii --- — ri�fi�( i � / ' . _4,,e. �� r2 I0 r e / E ITT,`/ �� �¢ /❑ II I .-� - p � ,. - `r:'6 1,� - — � w 7/ / /` rilyr L — i / _ �E %, ��/ / '� � / ,+r� � 3 ,, ISI "74'4 iI �� r01;" i i:' /0' 7� ml 7Yi� � I": II r�S 41 I,i100; ❑ , 610 _L._ [ u / % s � B � ! I!�y9�/ % /f// ` s / z I I _ �y�? g�i�G/7? 'r���i,r— + - i ., p r. f r: . ;r � /�7//�yl� ►�� r SIE11 /,'/.�EGG��dG� ri S , S El �� / �/ r. � 0 1 ® lflffffff� /<BIE) 'C-_-. 11 -�:+. --_'" , / ,""—' 16,x/ $z i lis f n / ��%��//.� % +i � z 1 / 1 .046 120 `© / p o ❑ � ❑ 1...= �',p m U II Imr4r/////////h%/Al—-�//%�1w T: M$4\J © In �_rwer / /J 3 / © -- - ---- f — �' II I ►'BT Iq sett �•' ae, em lD 3 L. E• _ I /;;%' " /7,-J / Imo'/ `, © �/ W V — /.,/ /.�i1I/�.� 4(p / 0 I i T = + 7 P.-- HI-IP, 4e/ 1--Tei--- of /�SJIY11YJfl/�JfHI % ❑z %% /•/ �' ' / / Q :,0„,e) , 1 rr--Irl /��` ❑ - --- eelE) ( _ 3 III re E) ❑`rs j=i_° 11 °LI r—I /ie // / ///'/ �j Q or i .0,., . . ,,,/z,,. .0., za, / ' © 3 I 0 3 0`/ sr iii I �i rY r'.• 100(E ® ' iij Lu Irk •-- r i fj //// i / // Ce 2 MY �fff�fl/ riA I' zump f: , /, is 1rf FA,007 // %%�/ _—_— -T— - ---- ---- h ��J 'ter, /" , z 6,-. p Oj : i �e f/ f1/ . ��'�! :. /� �/A /. . r6 ea/ •JU !I/�'���Als� �0 '�_� . ' ! f' //,.//,//F�IYYYIIIIII�! 7//ffl%/ I 7ffldI /flflfffN/// / _ • . I F .,m # 017 � 'Mk ee fE) '31 f ^ /•!f- I'�� I�f/llH/a.// :ylffflll/ N fffH : I/iHfl/fiflf/! Yfff/ U "..1 2-1 Li g IP :, o I o f, v i� a_ ou 0 O © war o5/23/24318 SOLE AS WED �1� 1=11,7 0 0 0 - 3R„ 0A cowl. ® PARTIAL FIFTH FLOOR CEILING PLAN - MECHANICAL DEMOLITION ! 1_ 01 NA =1,0I IR R9CI IE1 4OPIF44Y .. IrsCOMMONON COPTII MO ORFR PROPERIT MEM MTICE PV114 TICKNIH!ND 0100ME I1TTO E REPNP%ED.OWYE♦CP COM SNIY FOAM OR 110)0MN104NA 111111 0 1 8 OBIM*C TE! VW.P17145104 OFR00ME4 TO E TET TO BEAMMO10MTII=PARTY WIllldrt TOT OHM ICSPIT.PI NO MAW. SIMS I I I I a 8 N REVISIONS BY p g .5-8 n F dix O vi Z pJ Z GENERAL NOTES-MECHANICAL ® PLAN NOTES-MECHANICAL o `: c w ; Z m ,53 z A EXISTING DUCT SIZES,DUCT LOCATIONS,EQUIPMENT SIZES,EQUIPMENT LOCATIONS,AND H. ADEQUATE SPACE SHALL BE PROVIDED FOR THE FIRE SUPPRESSION SPRINKLER PIPING. 1. NEW LOCATION FOR EXISTING THERMOSTAT.EXTEND CONTROL WIRING TO NEW LOCATION. ��/{ r,,..- =y O AIR DEVICE SIZES WERE OBTAINED FROM EXISTING PLANS OR LIMITED SITE COORDINATE DUCT ELEVATIONS WITH FIRE SPRINKLER CONTRACTOR PRIOR TO START OF CUT AND PATCH AS REQUIRED.MOUNT AT 48"AFF. -�/ U r r, a Z OBSERVATIONS AND SHALL BE CONSIDERED APPROXIMATE.SITE VERIFY EXISTING CONSTRUCTION. Z(.2 ri` V m .' DIMENSIONS AND LOCATIONS DURING BIDDING PROCESS AND IDENTIFY ANY 2. NEW LOCATION FOR EXISTING SUPPLY DIFFUSER.CONNECT TO EXISTING BRANCH DUCT DISCREPANCIES PREVENTING THE NEW SCOPE OF WORK AS SHOWN. I. COORDINATE DUCT OPENINGS IN THE WALL FRAMING WITH THE FRAMING CONTRACTOR WITH NEW FLEX DUCT.RIGID ROUND METAL DUCT OR PROVIDE NEW TAP TO EXISTING MAIN Z M DUCT. u: A^ 3 J'C P o PRIOR TO START OF CONSTRUCTION. O 3 F *(7) � Y`n O B. WHERE WALLS ARE EXTENDED UP TO DECK REPLACE FLEX DUCTS WITH SHEETMETAL 2 V � L DUCT THROUGH WALL. J. OFFSETS AND TRANSITIONS ARE TO BE PROVIDED FOR COORDINATION WITH OTHER 3. NEW LOCATION FOR EXISTING SUPPLY DIFFUSER.REMOVE TEMPORARY SUPPORT AND - O ,L� c 9a SYSTEMS AND THE BUILDING STRUCTURE. REROUTE EXISTING FLEX DUCT TO DIFFUSER LOCATION.REPLACE FLEX DUCT AS REQUIRED. 0 \1k'� PP Z C. WIPE CLEAN FACE OF EXISTING SUPPLY DIFFUSERS AND RETURN GRILLES. K. PROVIDE ACCESS PANEL WHERE REQUIRED FOR HVAC DAMPERS AND COMPONENT 4. NEW LOCATION FOR EXISTING RETURN AIR GRILLE. CI�'• D. PROVIDE INSULATED BASE FOR THERMOSTATS OR SENSORS LOCATED ON EXTERIOR ACCESS WHEN INSTALLED ABOVE NON-ACCESSIBLE CEILINGS. J a.. �`m WALL OR COLUMN FURRING THAT IS INTEGRAL WITH EXTERIOR WALL. 5. PROVIDE VARIABLE AIR VOLUME(VAV)BOX AS SCHEDULED AND SPECIFIED.EXTEND - L. COORDINATE ACTUAL ROUTE OF SUPPLY,RETURN,EXHAUST DUCT,AND MECHANICAL INSULATED SUPPLY AIR DUCT FULL SIZE FROM UNIT CONNECTIONS AND TRANSITION TO DUCT Z VII'S.. E. WHERE DUCTS PENETRATE THE ASSEMBLY,FIRE STOP CAULK SHALL BE APPLIED IN PIPING ROUTES IN THE FIELD.COORDINATE WITH ARCHITECTURAL,ELECTRICAL, SIZED AS SHOWN.INTERLOCK WITH WALL MOUNTED THERMOSTAT. - ACCORDANCE WITH MANUFACTURES INSTALLATION GUIDELINES AND U.L.LISTED TESTING PLUMBING,FIRE PROTECTION,AND STRUCTURAL CONDITIONS. — ■' 6M APPROVALS. 6. PROVIDE TRANSFER AIR SLEEVE HIGH ABOVE CEILING SIZED AS SHOWN.REFER TO DETAIL M. COORDINATE DUCTWORK DROPS WITH STRUCTURAL COMPONENTS. 6/M-101. F. THE MECHANICAL CONTRACTOR SHALL PROTECT ALL OPEN DUCT,PIPING,AND MECHANICAL EQUIPMENT,NEW AND EXISTING FROM CONSTRUCTION DUST AND DIRT. N. EQUIVALENT AREA DUCTS AND MODIFICATIONS TO LAYOUT ARE ACCEPTABLE BASED ON T. NO HVAC WORK IN THIS AREA. MECHANICAL SYSTEMS SHALL NOT BE OPERATED DURING CONSTRUCTION EXCEPT FIELD CONDITIONS AND COORDINATION. WHERE WRITTEN APPROVAL IS OBTAINED FROM THE ENGINEER AND OWNER.WHEN APPROVAL IS ISSUED,PROTECT EACH RETURN AIR DUCT OPENING WITH MERV 8 FILTERS O. PRIOR TO THE START OF CONSTRUCTION,THE MECHANICAL CONTRACTOR SHALL AND INSTALL MERV 8 FILTER(S)IN EQUIPMENT FILTER RACK.PRIOR TO TESTING AND COMPLETELY REVIEW AND CONFIRM THE INTENDED RETURN AIR PATH TO MECHANICAL BALANCING,REMOVE FILTERS AND INSTALL NEW MERV 8 FILTERS.AT COMPLETION OF EQUIPMENT IS OPEN AND WILL BE FUNCTIONAL.CONFIRM AGAIN,PRIOR TO THE AIR CONSTRUCTION,REMOVE CONSTRUCTION FILTERS AND REPLACE EQUIPMENT FILTERS BALANCE OF THE MECHANICAL SYSTEM. WITH NEW FILTERS. P. COORDINATE LOCATION AND SUPPORTS OF MECHANICAL UNITS WITH OTHER TRADES. G. ELBOWS IN MECHANICAL SYSTEMS DUCTS SHALL BE HELD TO A MINIMUM.COORDINATE LOCATION OF DUCTS WITH OTHER TRADE CONTRACTORS PRIOR TO STARTING WORK. C ® m v v ask --_. �„ ___ — ,• --- .,, i n■■ ■1 ■n■■ ,R fAV4'A/.1 //i�9' ..,_ .. _, /w,1 --- ■ii rnIi■■I■w ■■w■. ■■,i I•• ■w .A� .�1 if/fiXdre:✓7i'/ii. • A'A 'A ///�i"i. /;rias. : ar.i%O 1 " 0 i 1 / : EIS •®� O I.l' ' ;-`� '°��E�� ! ;- L-�iVl � -.........© {ca I � ` / /t Ei• Y rre r rr rp' %y r r / ♦ 1. . . i■ Zy rre A Te i 4 dwrozd _ � A B 4156:111P1(12111111rlibllirra° m IEJ �1�L /isy''1 1' / // �' r/r . , r�.--��� . '� o■ 1 111_ ■� A■II, `111 I .rF� .r � %// e .�D ,�i,- � i {,moo ►, ' o �fil ;� ,,,�r ,-, /%ry/, /� � "�affli07�. Ei 4,YJ ,4k,4 rm- {` 1.....fi.. {� Il;l YfiAA A •. � 'r,%. Yf!/// /�,, %�rlt/ 0 u J1111111"111.1 '14�_ 1.1bIA iii�iUM i ArAk�i Ii t m N _ o o ■II� ®■N ImEr ��o • amai ■I , r � .� �� F , 1 Atruv �% _ , _ .. , qi: " -f, , - . :. � ! r i' IvAff r tri s .�Aer r 1 ftp i,'� kl © gam: I� I S' 1 A A Is 44::4,-„,,,,l- # - %' ;:�� /--_ - ,-- 1.` �lt \..__ ■► •'.1� — — .•ate r % /1.,,,,,,/.v, r',,,/�.'/a'r r �, r f -" _._— mum! _vim---riiiii� r 1 /... L. /� - �- � l/�/ -1�/-„----;,--,4,,vrr r r� � �i� A r r f l /,,--71.9_14110,-2- eE ogi- //,, /r//.e 7. IIIPtl % c — \D 1' a '►;•31-j �,_�4� '1111 p, t�� 'u �U1� ���. I%/ • / +rrl / %=- q� 9 •fi_ '/"i 1 //�yi Aa:4 I/i%If/ p%y�r . /i;,i% , .0 f • Wr .���� 1■■1 /f/: ./.7r,�. /:Yli. z Vie./l /11i.r ® :�■ .,-►�91111111,10 ,IIL .� � F ��I ►�Y / � /��/ ����% I' , �� /y.//�i� %� , API 4:4,414 � /;r , /� ..�.�.;, � �; e t , e .��_—.me —■Ir "04,4 ht- / /�,� 1I,r ///,/G.%/'iS'/ � / {%�y//7 / //�`/'/� `/SIU%/f/!%%/G r" %f�� I �° ggI irm© - - 11■� 1:5231110.10L/44 p , r / 1140 i ..r 44-04/11A / 's7 /'A.,t 21.4% A U MINNl�iE , 0/� mow' it rr ' F t� / r�� e '/ it/: / ° d ,A.„4.,„?.,,' �i�� o► s tom//� ,r v - /v/ iro r �- / 400- PO-00- 0i 1%%rFla .gg z 1 Kri.. sa, ,, � � , r „,, , , i„."44,, GlUI: ►' 1 vim. ,'�" / : / ' — I 1 ®_lnem■ ! i� 40.1.400141,0EE//��. �I ��s �-�----,0 �' • � 0 I �� / � Gs 11611;0„,0, ■■ / "�1�f Y ��A'�5 l / ��/i'fJ//.y//.Al /+ mum� FSS //Oer4P0 k4Y% / ■ ,, A!i �+/Ii tl+� / � � �� �/r !/� �F/; /� y�./%ryrrr +' qtr r V A 1„„;1 imalieni:.����� GG // i - !�/t© I /�_. I.v•_C �i�!�� '44Alytt#,A'Ar,.�//1II®■■ oradv�./rA it /d I rG/?.e/QE/.r y/, i �1//r m , I iv .�_f , / /�/ter _ /� ,� 12 Iv ,11.; � �■ yI �r ■� u��z� •• — 9l//. fimmorormorz %tom✓�r72 � J ■�r.. �- 0 I I_�rim..em r erru iamitilimmiiii.... Gtr 4 `11 • �. II Lg�� ® ,--Ard.Ez zA%%/.yf%,-rg d//imr r//d/01 q, I/ Gy//O////�///At/ A;A.%f t.if, Jti�� i %✓/ ei%' ''l' e.. P mail_ �.■ R_ yIr r I\ fid' / r �� • -' —' •:E' : _ p --©� A-________ ■ i oA is y � � ;Y� �� , ��2a '��1__1��1111 m - ` _— __ / ryrye�//////// o A A re„uw R'IEr� WI.�r .�q ►1 �I �. , - — R_ 1��■;--., O• r�� ,u , ,.,NR,. ,.� '/.f,.,/ s„ . /� r /r�P%/7/��s 744 + . �� , , " { ..R���� • - - ■VIII ����.�i �i�.,'i�r ' �' ' i r r/ ./ /FEMNAr. /.rerilr r / / " ii �■ o,�arte. ' 1111,0911111M11 p ►� � , pj ` ,► ,�0 .ae ✓/ ,R Ar A / r� j /,01 fl It m Q■sl i ! �\ TI'■'`�s�l tlrt�»�r.-moi i i fl \FE�.I/I JIlv�//%m/.r'eact% .'gym 'i� %� offer a m ry/���/ ///�/�/gor El® 'i --A Ah �_■I i�v ■ , 1111111111111 AF.._aliV • j►n,► ■ 5- Wa.", III .; le11 Ilaill".111 VII if , ;,, ., , � 1 �� a /1 ■ /� IAppI�1 a iffilinillt_ 111 11 I,t r1 /1 /% r r /, r a �i9�Z Q • ►v im I *4 � " =� 0/� ,,/ ,v / %r/ r / / ;/ i _l i of a r _ 31 ir: _ -- _ - o ' �r /' 11 A .o -.. ,' � � y :vr S+. wy"--ry r r � ;. �P,.� ,7ROM - ,iay.::�rr I ■/►� I1o��!' hoed:/ kNlJA■I� ■{�%/�%!�'itr.� �/�'/fJ .4�% r �%�� . �f/L( lL �' //P, /Irry4 / y / / o, rry / L►.�'v\_... g � ,70:89:../ %!ff/.lii:0 ri.•St/w �� .wiliniums, Rig . qw/ i // y/r! r6 `�,� o/ y�/�/ - % 2��'rr y7%� / / r .Y /7072,,,,i0% 1 ( �^.-� E :� �. duly r I y 7. � .r /r r ���j%'?� /���///rl� 7�%/,���// � � ■ i � I ,�•©'�I ` •V/''/.//r�/U�%///�,'�li�' % �//���/ Mat" , a ! ► re".ni't '� / klAJl ,rTA- •4!irdd4 i..4 4_44 ■�■ •���M� ro ( /� IT%,% �/,M,ArA/fe r ,1•T�- Z r rr .-.. I.��.��t AI. �.�. ;1 ,� s, � � /'�E >�yl�/��ry/r'�G•r TRA. I :.. /! / // / //�% i�;,., / 7rG�yS1 =�^ r%S r,/� r /r y/,+r � � ;%i�J!/2!/ �� �z/s /nA I� / �/ r �' !Hoa I vira.6E�•///',i/�% ��,� ..F'4 ...o' ,.s///�r/=Sek r A r,•r m F 7J /1� • /, �// / �. O ��.mium- ♦..x.7.7,.-Y-�-<- _ / t..r-L y� %orf/I/. � %gor---fi. --- . ' �emu 1 '5 � /s...� �/ i/i /./� �! 1. �/:40:.�/ %•�xL.�/��i�� I ����II� �y '// '/1/ GI%' / /./ / iriii Pl//� !! /I/ './/%f.IlJI/ /i ��77 ' tri�y�,r�r�� ' �'/��i�t� ■� — v , MORN•`�:f..ff.msiii� miliiii .� :_..__�oia/i�i ifr_ si C.ii..iffiiiu� ,ii� Z an All Ack ® 0 v r11/��//� :ill, �lyE�4!�y rriL.� d.�\ L�t� '.-___--• Vz z �rlrrr'' �1� iv � n'r 9 .r ' ��:�� 0 ►,/m �� 1► ■I�tMII I® inia Tom rd, '404X-54 Iere$0 -d 4;-id .„ImY. Arjaiii IMEMAIMMili I I ° Ds/za/zD+a Aft SOME AS NOTED 0 0 --® p 00 0 .°k JRA ® ®p ® ..a CEN014 COW' PARTIAL FIFTH FLOOR CEILING PLAN - MECHANICAL NSCALE 1/8• -0" M-301 OF OEM IML Cam IEREMIOPfRlr MOMS DS COMMON LVE NPI5RI1 NO ORM PROPFRIY 5.115 R TCM RNA TOME RNR NO ORMIM ME ItT TO BE 5]%RWSD,0W WAD 54 CORM IN N%1001 BR WHFA MN1OEVE1 M IMI'001.WC TE EOIZSm RIMER PRIMINO1 Cr I0.COM 101 NE THEY 10 5E Kamm 10.WY TIM ENVY 50041 MO COMM WW1.PFAOSON MO CRBFMI.