Loading...
Plans (16) NW PHOTON ENERGY �� n DIVED 560 FIRST ST, SUITE . TRIANGLE CORPORATE PARK I 126 . 63 JUL 6 2016 104 CITY OF TIGARD 503-703-4046 13010 SW 68T1-IPKWY BUILDING DIVISION KIRK@NWPHOTONENERGY.COM 188056 STAMP: PORTLAND , OR 97223 APlelv011 PROP;c:;,, SCOPE OF WORK GENERAL NOTES SYMBOL KEY SHEET INDEX 78 THE PROJECT SCOPE INCLUDES THE INSTALLATION OF 108,000 WAC RATED GRID-TIED SOLAR ALL ELECTRICAL WORK TO BE INSTALLED BY A QUALIFIED AND LICENSED ELECTRICAL CONTRACTOR. OREGON PHOTOVOLTAIC SYSTEM AT THE PACIFIC NORTHWEST PROPERTIES LP OCCUPIED COMMERCIAL VIEW NUMBER 01 KEYED NOTE it----'4, ELECTRICAL DISCONNECT SWITCH PV1 TITLE PAGE 4,� ,�" BUILDING IN PORTLAND, OR. ALL SOLAR MODULES SHALL BE UL LISTED 1703 & CEC APPROVED. ALL INVERTERS SHALL BE UL LISTED 1741 ' s, ' - SECTION CALLOUT �9 ELECTRICAL FUSE PV2 SITE PLAN R AL CERTIFIED & CEC APPROVED. ALL ELECTRICAL COMPONENTS AND MATERIALS SHALL BE LISTED FOR IT'S PURPOSE111, SHEET NUMBER 0REFERENCE NOTE THE INSTALLATION CONSISTS OF A ROOFTOP MOUNT SOLAR ARRAY, 3 INVERTERS, AND RELATED AND AND INSTALLED IN A WORKMAN LIKE MANNER, ALL OUTDOOR EQUIPMENT SHALL MEET APPROPRIATE NEMA ELECTRICAL BREAKER SYMBOL PV3 ROOF PLAN i EXPIRES12/31/2017 17 ELECTRICAL METERING AND SAFETY EQUIPMENT. ALL EQUIPMENT WILL BE INSTALLED AS REQUIRED BY STANDARDS. DC — DC SIDE OF INVERTER PV4 STRUCTURAL LAYOUT STRUCTURAL ONLY APPLICABLE CODES AND THE LOCAL UTILITY COMPANY, DURING DAYLIGHT HOURS THIS PHOTOVOLTAIC VIEW NUMBER el REVISION BUBBLE PV5 STRUCTURAL DESIGN JUL 05 2016 SYSTEM (SOLAR ELECTRIC) WILL PROVIDE ELECTRICITY IN PARALLEL WITH THE LOCAL UTILITY SERVICE THE ELECTRICAL CONTRACTOR IS ADVISED THAT ALL DRAWINGS AND COMPONENT MANUALS ARE TO BE gh DETAIL CALLOUT AC % AC SIDE OF INVERTER PROVIDER. UNDERSTOOD PRIOR TO INSTALLATION. THE CONTRACTOR IS ADVISED TO HAVE ALL SWITCHES IN THE "OFF" VPE CURRENT TRANSFORMER PV6 LINE DIAGRAM POSITION AND FUSES REMOVED PRIOR TO INSTALLATION OF FUSE-BEARING COMPONENTS. SHEET NUMBER L REVISION NUMBER PV7 ELECTRICAL NOTES ?,, ., D PRpfi SYSTEM DESCRIPTION _ GROUNDING ELECT RODE CONDUCTOR -c, s THIS SYSTEM IS INTENDED TO BE OPERATED IN PARALLEL WITH THE UTILITY SERVICE PROVIDER. ANTI-ISLANDING VIEW NUMBER PV8 SPEC SHEETS c. N i PROTECTION ISA REQUIREMENT OF UL 1741 AND IS INTENDED TO PREVENT THE OPERATION OF THE PV SYSTEM gikTITLE NORTH ARROW © EQUIPMENT GROUNDING LOCATION q w 129 >r ' 1."-- (378) (378) AUO SUNVIVO PM72MWO 335 335WDC MULTICRYSTALLINE MODULE, CEC PTC RATING 307.1WDC VIEW TITLE o WHEN THE UTILITY GRID IS NOT OPERATIONAL. 411, Scale: SCALE - (3) CPS SCA36KTL-DO/US-480 36,000WAC STRING-INVERTER(S), 480V, CEC EFFICIENCY: 98.0% 31) SHEET NUMBERfro rA Q � , PERMISSION TO OPERATE THE SYSTEM IS NOT AUTHORIZED UNTIL FINAL INSPECTIONS AND APPROVALS ARE u'' S �- y `�� 126,630 WATTS DC `� i , 108,000 WATTS AC OBTAINED FROM THE LOCAL AUTHORITY HAVING JURISDICTION AND THE LOCAL UTILITY SERVICE PROVIDER. # /p RUSE ABBREVIATIONS at - _ EXsPr: C%D .T : 6130/17 THE METHOD OF ATTACHMENT CREATES A UNIFIED STRUCTURE TO MEET DEAD LOAD, WIND LOAD, AND SEISMIC TYP. TYPICAL PCC POINT OF COMMON COUPLING OSISC OREGON SOLAR INSTALLATIONLi REQUIREMENTS. SOLAR MODULES WILL BE SECURED TO THE EXISTING ROOF AS SPECIFIED ON THE STRUCTURAL PV PHOTOVOLTAIC AWG AMERICAN WIRE GAUGE SPECIALTY CODE W " SHEETS. EXISTING ROOF EQUIPMENT WILL NOT BE EFFECTED BY THE PV SYSTEM. ALL STRUCTURAL DESIGN AND , TSRF TOTAL SOLAR RESOURCE FACTOR VD% VOLTAGE DROP PERCENT OESC OREGON ELECTRICAL SPECIALTY CODE a INSTALLATION COMPONENTS ARE THE RESPONSIBILITY OF OTHERS AND OUTSIDE THE SCOPE OF THIS DOCUMENT. TOF TILT AND ORIENTATION FACTOR ASHRAE AMERICAN SOCIETY OF HEATING, OSSC OREGON STRUCTURAL SPECIALTYaRI r DC DIRECT CURRENT REFRIGERATING AND AIR CONDITIONING CODE rn ALL FASTENERS SHALL BE CORROSION RESISTANT APPROPRIATE FOR SITE CONDITIONS. CONNECTORS SHALL BE AC ALTERNATING CURRENT ENGINEERS U APPLICABLE CODES TORQUED PER DEVICE LISTING OR ENGINEERING RECOMMENDATIONS. A AMPS UL UNDERWRITERS LABORATORIESI— ALL ROOFING REPAIR MUST MAINTAIN EXISTING CLASS AND TYPE OF ROOF AND ALL WORK SHALL BE IN V VOLTS IEEE INSTITUTE OF ELECTRICAL AND INTERNATIONAL BUILDING CODE, 2009W WATTS ELECTRONICS ENGINEERS CO D 0) OREGON SOLAR INSTALLATION SPECIALTY CODE, 2014 ACCORDANCE WITH THE ROOFING MANUFACTURER'S INSTALLATION REQUIREMENTS. WDC WATTS OF DIRECT CURRENT IBC INTERNATIONAL BUILDING CODE 0 < >- co ' OREGON ELECTRICAL SPECIALTY CODE, 2014 WAC WATTS OF ALTERNATING CURRENT W CNJ r OREGON STRUCTURAL SPECIALTY CODE, 2010 CU COPPER CONDUCTOR U Q r--s p . AL ALUMINUM CONDUCTOR W IY = ct W = PROPOSED LOCATION W � � 0 � VICINITY MAP OF SOLAR ELECTRIC SYSTEM PROJECT TEAM CC fy — Q 0 z z / - © ° CD Q 0 PROJECT DEVELOPER cf, W o 1 w - NW PHOTON ENERGY z CO 0 CZ • � 560 FIRST ST, SUITE 104 < 0_ 503-703-4046 c� w J KIRK@NWPHOTONENERGY.COM cfl ~ �' �, 188056 ciS — CONTRACTOR �' NW PHOTON ENERGY 560 FIRST ST, SUITE 104 SCALE P O e 1301a SW GH*.Pkwy q, J 503-703-4046 AS SHOWN KIRK@ NWPHOTONENERGY.COM E 24" X 36" .A 188056 ORIGINAL SIZ SHEET SIZE ARCH "D" SITE CONTACT ©Copyright 2016 c;..; . ;t,,,z TBT NW PHOTON ENERGY 0 .' The drawings,specifications and other documents related to this Q ,, project are protected under law and contract. Reproduction of �J these documents is authorized for the purpose of constructing, V •, (: ) SYSTEM DESIGNER maintaining and using this project Use of these documents for CI) - any other purpose is not permitted without written authorization. a b s, , CITY OF TIGARD RENEWABLE ENERGY ASSOCIATES, LLC REVIEWED FOR ODE COM LIANCE PO BOX 208 E ., -I:.. 1 Approved: r j f C c+eltery CORVALLIS, OR 97339 li OTC: ( 1 541.754.2001 i Permit#: -G,C 242.1 It - COS b INFO@RENEWABLEASSOCIATES.COM L FOR OFFICIAL USE ONLY Address: ( a o �,, suite STRUCTURAL ENGINEER cu Date: 2h1A7 VECTOR STRUCTURAL ENGINEERING, LLC 9138 S. STATE ST., SUITE 101 03 SANDY, UT 84070 VECTOR@VECTORSE.COM Z ELECTRICAL ENGINEER 0 1- PHIL HANNA CO IX HANNA EmnramacrIGARD o a ' . ,AOR con COMPLIANCE n Approved: OTC: I ] �A � ICI �r z Permit#: l�r/_ —Gc, o �W r Address: i. 4.1 i g% - u) CV Suite •• ILI BY: SHEET NO.&NAME: M B3; �Qi+�±k.. Date: �f CC co 0 cNi co OFFICE COPY PV1 L_, TITLE PAGE E GENERAL NOTES: NW PHOTON 1. PLEASE CHECK WITH CITY/COUNTY OR LAND SURVEYOR FOR ACCURATE PROPERTY LOCATE. ENERGY PV AC COMBINER PANEL 560 FIRST ST, SUITE PV AC DISCONNECT (24/7 PGE ACCESS) 104 UTILITY METER 503-703-4046 KIRK@NWPHOTONENERGY.COM MAIN DISTRIBUTION PANEL AND PCC 188056 IN GROUND FLOOR ELECTRICAL ROOM CPS INVERTERS MOUNTED ON F--- ----------, ROOFTOP RACKS WITH SHADE COVERS x 7/— ' / -1 STAMP I ' _ -14r1 11 } --- a - - a1 a s — a m RIo a •$ w . • - 6 a ® Q W I— w SOLAR ARRAY ON ROOFTOP R I — - II `D ~ CC (378) UL LISTED PV MODULES = ui U) w w AZIMUTH 180°, SLOPE 10° �1� ��_ a . .� . ._ . r - a i Z z i LO j / au 11 E ® a I SUNEYE LOCATION l _............_....._.-_._.�... I j r - I, li Ii ___t_ I / 1I 11 SUNEYE LOCATION �..� � / �::�_� � i` II MIMI MINIM= :I j 11111•11 MEIN. i LU OM i SW IRVING ST 1 1 x Z II SUNEYE LOCATION I1 I I 1 II I Lll U) Ct v CL CL � L1J N .V. . .00co co U Q 07 can cin LLI w O O m co co Q O z Z _............ ____ -- .._........ _ — --1 0 U J I— c) COJ C) W 1 O o o o z co 0_ / 0 Q 0_ z " r O CO CO N— _ I CL I COa) O 0 I SCALE 0Custom .� j ORIGINAL SIZE 24" X 36" 1— o 1 SHEET SIZE ARCH "D" Yt „ 1" cu a 1 ©Copyright 2016 NW PHOTON ENERGY T. • • The drawings,specifications and other documents related to this 0_ j project are protected under law and contract. Reproduction of p 11 I these documents is authorized for the purpose of constructing, U maintaining and using this project. Use of these documents for any other purpose is not permitted without written authorization. a, ADJACENT ' I ` I PROPERTY F— rn I j j w . CL z o I N U N O 1 i 1 c6 ! t 1 Q w ctz o 1- z i= w o a- u) U .—_—�- ._ -__-- o w , w J a 1 0 m Z 0 co lf) N LLJ Q � MSW 68TH PKWY SHEET NO.&NAME: coN PV2 ti w H Q SITE PLAN z NW PHOTON ENERGY 560 FIRST ST, SUITE 104 503-703-4046 KIRK@NWPHOTONENERGY.COM 188056 PV AC COMBINER PANEL STAMP: PV AC DISCONNECT (24/7 PGE ACCESS) UTILITY METER ,// MAIN DISTRIBUTION PANEL AND PCC IN GROUND FLOOR ELECTRICAL ROOM ROOFTOP JUNCTION BOX, TYP. FI ROOFTOP CONDUIT FROM INVERTERS TO PV AC COMBINER ON GROUND LEVEL I I • — — —,' BC-5, INV-3 I I I I BC-6, INV-3 BC-4, INV-3 ' I I 1 I I I BC-1, INV-1 CPS INVERTERS MOUNTED ON ROOFTOP RACKS WITH SHADE COVERS I I • BC-3, INV-3 I _ , I I BC-7, INV-3 I I r I BC-2, INV-1 I W I i BC-2, INV-3 I— I C/) — cn (Y CD • ! U �- CO C6 ._ I I- JP N N— I I H ,BC-1, INV-3 I i_ ti WQ CL rn W J m BC-3, INV-1 - - BC-6, INV-1 W OO r r Ct CD O co CO I I Q O Z Z BC-4, INV-1 - • - 0 0 Cr) Q I-- orCD LL.I CD I CD ct 111 ooo BC-5, INV-1 - „ z o� CL r2 O I I 0 Q N z BC-7, INV-1 -a I I I O co ` � I I I I BC-1, INV-2 BC-4, INV-2 ct o_ I I 1 I U I I Q - BC-2, INV-2 ... o SCALE 0 1/8" _ 11.0" BC-3, INV-2 i ORIGINAL SIZE 24" X 36" r 1— - BC-7, INV-2 SHEET SIZE ARCH "D" _s I I 0 /„ 1" Cli5a ROOFTOP CONDUIT BETWEEN ©Copyright 2016 NW PHOTON ENERGY ARRAYS AS NECESSARY I The drawings,specifications and other documents related to this Qproject are protected under law and contract. Reproduction of these documents is authorized for the purpose of constructing, jmaintaining and using this project. Use of these documents for any other purpose is not permitted without written authorization. = CU .g c0 W uy Z f C7). EMI11.1. N -- N U CD CO CO QEMI CL Z O I—^^ WI lal I= Lll H- O I I W W 121 o BC-5, INV-2 - °- I I - 0 I I m z - BC-6, INV-2 - - - -- — 0 co w Q fn N C/)Ct 11j W M O-> SHEET NO.&NAME: c_o 0 NPV3 csp N--. j W I— Q I- i ROOF PLAN z I ': NOTES: 1. ALL CONDUIT RUNS ON ROOF UNLESS OTHERWISE SPECIFIED. NW PHOTON 2. CONDUIT SUPPORTED BY PROPERLY SEALED AND GLUED PT WOOD BLOCKING OR UNISTRUT WITH SEALANT PER ROOFING MANUFACTURERS SPECIFICATIONS ENERGY 560 FIRST ST, SUITE PV AC COMBINER PANEL 104 PV AC DISCONNECT 503-703-4046 K1RK@NWPHOTONENERGY.COM UTILITY METER 188056 1 7— r I— E n 'I I j I - m STA�4P EMT CONDUIT ON ROOF CONDUIT BRIDGE TO BE 7'-51" (4' MIN.) 1 ��� Q ` � � I _ t I UNIRAC BALLAST TRAY 3.5" ABOVE ROOF MIN INSTALLED IN ACCESS PATHWAY 4 1 '-2-" (4' tv ,;, r "�. " L , - 1 11'-71.. :_..._... ( ) 6 2 , MIN.) 2 I D .� ` 1 — — , — G °' o r P PV4 � ; NP M — = AUO SOLAR MODULE — --------- I-- W I III OREGON , , 4' CPS STRING-INVERTER = =� �;=� � = .� � �-=�<=� � �=� �.=� �= I 3 , ,,,,z:,/ ' ROOFTOP AIR --- 411111107 7.4=11114 �. _ toid o LITRES 12731/2017 0 E E M CONDITIONING UNIT - -- -- -----_�---- 41111MM -*MIEN -:-4M1114 g=11,4 STRUCTURAL ONLY FiNiir, 1,114 Iiiim = 68.7661�- JUL 052016 /." t.:1'' MM.T., : '-'1=14 — 7g.4600 — ..=---...' — — .-- ' ...7-- Till= 2. 631.1800 65-10�" CONDUIT BRIDGE TO BE 4 INSTALLED IN ACCESS PATHWAY j R R R 0 R R 0 I R 0 R R R M R R R R R R I R R R (-- , I ' I M M @ M E 0 E M E E E E E E E M 0 / 236.3800 M M / M M - til: E M 0 ras. .mss -., = r . DDD ! § = __ = ..- = .- = _ ..;;;–., ....., .= =.–c.'.4 ....... --_-_,.., — -..„„ .. .._,.,, — .— — M 118'-10" I I W NEMA 4 ROOF MOUNTED j j I— — C JUNCTION BOX, TYP. >- - E PV4 B U) rn PV4 ROOFTOP AIR I : 0 Q co , R R R R R R i R CONDITIONING UNIT ? , W N 253.5769 — — — ' I— I— r2 , K/7 I— O = 5._43.. (4' MIN.) — cc'4 co 134.6029 Q� Z Z @ / 118'-44" / j O O J I— co 293.5936 ? U 0 •r— o a �. Q U —w 97.7947 ' Q lit I w�� �mil i CL ice'.. ~J 1 z II �._ = 102.6967' -�= CO I— W _ : -- � 5,_31„ -- fzu as o -- _='. E SCALE U °' ' I AS SHOWN = I 7'-9co= 2", (4' MIN.) I ,✓ / ORIGINAL SIZE 24" X 36" RI \ I SHEET SIZE ARCH "D" ozs ' 0 y2i, 1" iffs0 ©Copyright 2016 NW PHOTON ENERGY A ROOF PLAN ROOFTOP VENT, TYP. The drawings,specifications and other documents related to this project are protected under law and contract. Reproduction of O £ [ these documents is authorized for the purpose of constructing, o PV4 Scale: 3/32 = 1I-0 1 maintaining and using this project. Use of these documents for a) / 59I-24 / ' £ any other purpose is not permitted without written authorization. CV SYSTEM MECHANICAL INFORMATION (FOR REFERENCE ONLY) / 19'_81„ / 32 lbs. BALLAST BLOCK, TYP. ch 2 SHADE COVER SOLAR MODULE WEIGHT: 49.6 lbs. c- MOUNTING RAIL WEIGHT: 36 lbs max/If 41I-9"71e-- 4", TYP. //— z f-z SOLAR ARRAY WEIGHT: 55,266 lbs `..i _ r CPS INVERTER NEMA 4 JUNCTION F_-c-, SOLAR MODULE DIMENSIONS: 77" X 39.05" X 1.57" -- mom — AUO SOLAR MODULE r — AUO SOLAR MODULE BOX, TYP. CONDUIT BODY CN TOTAL ROOF AREA (MEASURED IN PLAN VIEW): 28,006 ft2 �- / 31-3H / 11-7" / - ((1.3 SOLAR ARRAY AREA: 12,524 ft22y --, MEASURED IN PLAN VIEW: 12,225 ft 11.1 ROOFTOP o ARRAY AREA PERCENT OF ROOF (MEASURED IN PLAN VIEW): 43.6 CONDUIT ROOF PIPE JACK SOLAR ARRAY DEAD LOAD: 4.52 lbs/ft2 �� ° ,_ ��) 4 ■. MOW FLASHING TYP. 03 -= SOLAR ARRAY ATTACHMENT TYPE: UNIRAC RM ' 1111w 7 CO 11-7" 10° ° itim //�� ii 11 I a Q ATTACHMENT QUANTITY: 497 @ 78" MAX. SPACING 3 r I �� — oo aA., a r SOLAR ARRAY MOUNTING RAIL TYPE: UNIRAC RM or.,.....11,1kIri 15 - 30 , TYP. .o. o �o� o o� z z3._3.. iiiaaiiiiaiaiiiiiiiiiiiiiaaiaiaaaii�iiaiiiiiiiiiiiii4v A,iiiiaaaaioaiiiiiiiiiiaiai4 wo 0 0� 0000 0 0 0WATER TIGHTCQ • ROOFTOP CONDUIT FITTINGS v CO 12 of I UNIRAC RM VOI w w V1 ' n 0 ' fl 1 I c. BALLAST TRAY 32 lbs. BALLAST CLAMPS TYP. 4 CONTRACTOR INSTRALLED BLOCKS, TYP. ROOF FRAMING >- z ROOFING PAD CONDUIT SLEEPER ATTIC CONDUIT o co r r J OR EQUIVALENT p ,2, 30" MAX. DEPTH ENGINEERED K-JOIST c`nn M -/ 6 5 / 6' O.C., W142'-6" MAX, SPAN, TYP. „ @ ADJUSTABLE ROOFTOP ,,, 6-3 ROLLED ASPHALT INVERTER MOUNTING RACK SHEET No.&NAME: AUO SOLAR MODULE ROOFING CVPV4 ti UNIRAC BALLAST TRAY T Lij B SECTION DETAIL rc� ATTACHMENT DETAIL I-D INVERTER MOUNTING DETAIL E CONDUIT SUPPORT DETAIL �F CONDUIT ENTRY DETAIL o STRUCTURAL PV4 Scale: 1/4" = 1'-0" PV4 Scale: NTS PV4 Scale: NTS PV4 Scale: NTS PV4 Scale: NTS � LAYOUT NOTES: 1. BASED ON 32 lbs. BALLAST BLOCK NW PHOTON ENERGY 1 BALLAST BLOCK PER BASKET 560 FIRST ST, SUITE � `� 104 � 503-703-4046 2 BALLAST BLOCKS PER BASKET • KIRK@NWPHOTONENERGY.COM 188056 n2. a' \ 3 BALLAST BLOCKS PER BASKET r Lai O u v STAMP .,..- 4 BALLAST BLOCKS PER BASKET N ° triyi ta rz, t''''\ l's /c;;S ,k,\G I N4-k-„ii ,N 3 > 78178PE OREGON /7 _.,,,,,,d 2 I , .......w I \ \ < � , \�� I I 3 I I I I I .. 2 � , ' s^p ,} , ,� I. )j ..:,; f ,gyp \\. }.. ""� F .,... , 1:: \ � �c .1:_,"‘ .7,,,,7,..,. , 1 ' i77: 1 _ leI w .•: a2�. a —,,: 3 �.ti..: # % S 1' t € d� T7� <f 2 g 8 P fk p °_ ...:<� � ;: � � � _' .,_ ��,, {{ � � 771"--1 � : ,., __, ®, �. ,_. � � s � �. � I � s > e s .\11 lc qac � irgt� }a • P _,.. , a. .. _....... ..... m� ...._. ,. ' .,„ « p '"`t .>43"3i�Sr 1 e.$?a'SJ 1 iN''' ' § a 9 t d i , • a, € •z \te. € . •1,,,,,,,„' ';�.....-•---........! ..,.,.M.-,..., gil..w...—...� .a.. � �' <. ,., ...� .:; .•;:.. �_-. :.. ‘„,,,,-,--‘,14; . t .. % :5-5 ' [ „.17.t --I I 3 i ,..... s \.: >, 1 �,� x,.\ � � . TP.UCTURAL OP1LY W. -,r,‘2,‘,. s)E 0 <. � c 1, ,,,,,..,, ,,,, i Z _ i i I i 1 ! 1 — JUL052016 -7;:--1 r 1 • Z �. 'I‘' �\\ u.1 Li ��\: . < ', :,; �,, �tib\ \\ , t ''t,.:27,‘,.,,,::,‘„,,,,,,,,,i. ,k,‘,,v,.!,,,f.,,,,72,,,---' ,..7-, -, --- 1 1 ...... .L.,.. 2 i„ I 3 1„___- i 2 .--- 1 1_ lirTii il 1 0 II ! j1 « f [t 1 a -‘ 1 i ,:%';'' ''1:.: ,,''' —"":-A' , ' l' I i ate...,__; 'F-2-71 ii.,, 3 Taair,l1_3_II -121-J '1 11111 '---------:,•1"L'I - ----{-1 .._11-111-----F1*--;, 7----1 i 9 1 .� .a '... . \ �. . .... � FT' .. l',,,,,:t,,,,,,,;:::4,?':_ :tea. ,i i ! Pam____rni21 2 I j I j I i 2 2— t, _1 _2- 'A','N',e-;''''':-.----_,I- L______,, S\O , I j i _3 .- 1'::'''''''''''1'11,,_II-1' t Fm ..—.�.m. � .:o .... � .a: �;<a:, �• +... �..ab.,.m.....�.j � i.:.. ..a .....:... _...� I ., '‘::"..:'''''''\''1, . :. -..,_.. �a��\.,... \ ,'�� Y iI 1 , t d 7 � ii: v�V va v ::. t \ay e `� vA x .,._, ! I,L:.,,� I ,:li ‘,_,, LLJ ¢ :IT-7: ill>x: _ : @ A � : % 1di } -i � F �` i -1,-----'Ll-'-1 �� I t t e I I- -1----I'll I I P I .a I':...,L--1------siL 1-1'17----! p I 1 ,, ii_i_14 ,s1,,,,,,,, 1 2 > e v 1. '7.-: i i �� an- 1\34'''‘ "V '‘' \ H k- , ' '--4--, ' ‘i.:1Titititi . Lksilkitu,,,, t'\ 4 — 1 \\2,,,\,::,•„, Cn � LLJ ti 111111111w: - �g I I ¢ I � .� �a�. A ..�mai�v - - —, ''''--,\:,:7 -— 1--- , .......___11 . 7 A ,,:: l'illill y ra: ''''''''''' ''''''k'''\\\'''' :A:. � I t jg I 1 ' O j --I 4 7,,,,..,„:„.N.,, ,',, V,,, ' . :;,°,,,:i,,„.H.,5'icilli.h.\:,;7.,,,i,,-','':,•-, -'-.-;- -4:::..A. ,a,1 wim...H,i.f:i:',,,', 41-'1 ''''" :‘,:',:t" I i I11-''''''' � 1 j I I1_______H__,I' O r— •a'a\\ V IA ..'::___H. M 1 � � f �.. ! j j sg ��\� • a , ,,,,..„ , , , 0 L__ „,„:‘,„,,,,,,„ , ..4°. ,. ''..."., -, ,,,s,:ic,' j ! I 2 € ,,,,,,,, _,: \,.. ,.tea \ u j £ "� ,...� � [ 2H21 IL-71----:j' �L2 ., 1W,,,',, `,,, .. -.',,Q.;IT:fi'::: ,;'•', ....,$4,e,,,,t‘., , Le mLEL H .re yC.,``t,• i g O ,,, 2 - -,71 1 2 1 I -v CO : _ mF 4 _ — gym, ! N Q L. H .�as- U .._., ....\\ .. H 1 SCALE (13 AS SHOWN cu KIN,,,„, ORIGINAL SIZE 24" X 36" Fi-,,. —li I SHEET SIZE ARCH "D" /z ® a ©Copyright 2010 �R 1 1 11 ! NW PHOTON ENERGY p 1 L®„„ ,.,.., I _ The drawings specifications and other documents related to this 025 _ ! project are protected under law and contract Reproduction of O Fi, — '" —, these documents is authorized for the purpose of constructing, C3� — maintaining and using this psi roject. Use of these documents for U any other purpose is not permitted without written authorization. co N i I , 1:44 I itli .1 : 4 CL O co i co cL .L.,_,,„..J ---1 ,Rm, *,,,'. \ i . I i ,,,, e,cA4',IP.', . ‘.iis,,,'‘,',; ‘ i----- r H ' it • °' I i i I i H� �� � I 65 P 2 _7, En 1 _ _ � e �. i , , ---1 ',,,,,f-- , 2 z z CL ow CL U co U u) fY O W w J o d ct D U) is5 >- fY Co Z 0 co W D C) CV Q 11J M Et rn '( ' PV5 SHEET NO.&NAME: c.O CV co ti W 1— <Q STRUCTURAL Z DESIGN EE SITE SPECIFIC INFORMATION: • SITE LOCATION: PORTLAND, OR 97223 NW PHOTON TEMPERATURE DESIGN LOCATION (IF APPLICABLE): ENERGY PORTLAND/HILLSBORO - FREE AIR 560 FIRST ST, SUITE ASHRAE HIGH TEMPERATURE: 37°C 00 (2) 10 AWG PV WIRE CU 104 AVERAGE HIGH TEMPERATURE: 32°C (1) 6 AWG GND 503-703-4046 ASHRAE LOWEST EXPECTED TEMPERATURE: -8°C -70'W/0.30% VD GROUNDING MID CLAMP KIRK@NWPHOTONENERGY.COM MODULE INFORMATION: AUO SOLAR MODULE 188056 n c6 ADDITIONAL SOURCE MODULE TYPE: AUO, SUNVIVO PM72MWO 335, 335WDC (STC) CIRCUITS OF 18 MODULES . e P o e e o o e o 0 o a a a o 0 a. MULTICRYSTALLINE MODULE ; 0 CEC PTC RATING: 307.1 WDC A a R p 9 a P p a o p A A a a o A POWER TOLERANCE: +3/-OWDC STAMP: Voc: 47.0VDC (52VDC AT-8°C) WEER GROUND LUG „,...,,..,3,,_,_ Vmp: 37.OVDC (30.3VDC AT 37°C) ,: .:, Isc: : 37.0 C UNIRAC MOUNTING RAIL ,,,,r , Imp: 8.82ADC 1/D i\ . *3 Fa �A' \ SERIES FUSE RATING: 15ADC . 1-- <---› Voc CORRECTION (%/°C):-0.32% PV6 m. ti....... Vmp CORRECTION (%/°C): -0.43% "' a MODULE DIMENSIONS: 77" X 39.05" X 1.57" �;7-\ „\ .„1, --22-'\;„",\W INVERTER INFORMATION: �\ ,°"" - CPS STRING-INVERTER, SCA36KTL-DO/US-480, 480V, 34 (1) 1-1/2" EMT I EXPIRATION DATE. 630in I CEC WEIGHTED EFFICIENCY: 98.0% (14) 10 AWG PV WIRE CU 10 , START VOLTAGE: 330VDC (1) 12 AWG GND MPPT MINIMUM VOLTAGE: 540VDC '"260' W/ 1.0% VD() MPPT MAXIMUM VOLTAGE: 800VDC MAXIMUM SYSTEM VOLTAGE: 1000VDC MAXIMUM POWER INPUT: 54000WDC MAXIMUM POWER OUTPUT: 36000WAC MAXIMUM CURRENT OUTPUT: 43.50AAC AC NOMINAL VOLTAGE OUTPUT: 480VAC AC OVERCURRENT PROTECTION: 60AAC MAX (PER MANUFACTURER REQUIREMENTS) ARRAY ELECTRICAL SPECS 0 ARRAY ELECTRICAL SPECS MODULES: 378 (4) °c- 2/D INVERTERS: 3 PV6 (21) SOURCE CIRCUITS OF 18 MODULES (7) SOURCE CIRCUITS � i � 5 i OF (18) MODULES 1 w MAX. SYSTEM VOLTAGE: 935.3VDC W/ 18 MODULES @ -8°C ; - I- MAX. POWER POINT VOLTAGE: 666.0VDC W/ 18 MODULES 116 8 MIN. ADJ. VMP (ASHRAE HIGH TEMP): 545.7VDC W/ 18 MODULES C1) Et rn MIN. ADJ. VMP (AVG. HIGH TEMP): 560.0VDC W/ 18 MODULES 00 U < >- co MAX. RATED ISC OF ARRAY: 39.0ADC W/4 STRINGS ® RI CD W MAX. SHORT CIRCUIT CURRENT: 48.75ADC W/4 STRINGS U I- W rn a MAX. POWER POINT CURRENT: 36.4ADC W/4 STRINGS 4 -J LC _ m w O I- 0 VOLTAGE CALCULATIONS: NEC 690.7 -� �.. (2) 3/4" EMT CC Cl- coo 0 D co LOW TEMPERATURE FOR DESIGN (ASHRAE LOW TEMP) = -8°C (7) SOURCE CIRCUITS UTILITY CT METER CC (3) 6 AWG THWN-2 CU EACH MAIN SERVICE 15 0 Z Z c) ARRAY Voc AT STC: 47.0VDC X 18 MODULES IN SERIES = 846.0VDC OF (18) MODULES 7 •5 � r (1) 10 AWG GND EACH 0 0 0 Cn J U �.. DISCONNECT o TEMPERATURE ADJUSTED Voc: -40 W/0.30% VD (1) 1-1/2" EMT UTILITY w w o F- o [846.0VDC X( 1 + ( ( -8°C - 25°C ) X ( -0.32% ) ) ) I = 935.3VDC ��--- - - AC�� e J W E-, MAX. Voc PER INVERTER MANUFACTURER REQ. = 1000VDC (3) 2/0 AWG THWN-2 CU �O® (1) 6 AWG GND U0 z o a. v 935.3VDC <_ 1000VDC (OK) 00 -25' W/0.10% VD 1) \�/ 12 c8) r cl 0 a) ® O l -.��. ® O z 1600A,,t,, Tr F- 4) 3P _ O co 3P 3/D -,-- -- �, pc. coW H W n_ 1-e-\, II 3P 7 a) �v ~ 5 ��� 60A f. - r5ti lti L its�� 1 3P 3P 11 e ij-----arr G SCALE v L ,�� _ Ac 4,- -e `� �� EXISTING GROUNDING °'a, CONDUCTOR AS SHOWN 00 (1) 3/4" EMT (1) 1-1/2" EMT EGC BONDED TO ALL EQUIPMENT 1 ORIGINAL SIZE 24" X 36" (3) 6 AWG THWN-2 CU (3) 2/0 AWG THWN-2 CU SIZED ACCORDING TO NEC 690.45(A)AND NEC 250.122 SHEET SIZE ARCH "D" °o (1) 10 AWG GND (1) 6 AWG GND L -40'W/0.30% VD -10'W/0.05% VD 0 %2" 1" co cL a) SYSTEM SPECIFICATIONS LINE DIAGRAM A B ©Copyright 2016 NW PHOTON ENERGY CO The drawings,specifications and other documents related to this 0 Scale: NTS Scale: NTS PV6 PV6 project are protected under law and contract. Reproduction of 0 _ these documents is authorized for the purpose of constructing, U maintaining and using this project. Use of these documents for a) any other purpose is not permitted without written authorization. C? 0 (378) AUO, SUNVIVO PM72MWO 335, 335WDC MULTICRYSTALLINE MODULE, CEC PTC RATING: n LOCKABLE UNFUSED EXTERIOR PV DISCONNECT SWITCH TO BE LOCATED WITHIN SITE OF EXISTING co 307.1 WDC. INCLUDES OUTDOOR RATED QUICK CONNECTS WITH MULTI CONTACT CONNECTORS FOR UTILITY METER PER UTILITY REQUIREMENTS. 200AAC, 600VAC, NEMA 3R. CONDUCTOR, CONDUIT & OCPD __ - _._ KEY 1 KEY3 KEY4 I ' MODULE INTERCONNECTION. DO NOT REMOVE THE QUICK CONNECTS, OTHERWISE THE MODULE QTY SIZE TYPE QTY SIZE TYPE QTY SIZE TYPE WARRANTY AND THE UL LISTING MAY BE INVALIDATED. ® PCC MADE IN EXISTING INTERIOR 480VAC, 1600AAC 3 PHASE MAIN DISTRIBUTION PANEL WITH (1) RACEWAY 1 1-1/2" EMT 1 3/4" EMT 1 1-1/2" EMT Earl_ 175AAC 3 POLE SOLAR BREAKER RATED FOR BACKFEED. THIS CONNECTION SHALL BE MADE IN CURRENT CARRYING CONDUCTORS: 14 #10 PV WIRE CU 3 #6 . THWN-2 CU 32/0 THWN-2 CU z O FREE AIR EQUIPMENT GROUNDING CONDUCTOR ACCOMPLISHED VIA CONTINUOUS#6 CU GROUND CONFORMANCE WITH NEC 705.12(D). SEE D/PV6 FOR BREAKER SIZING CALCULATIONS. NEUTRAL: NOT APPLICABLE NOT REQUIRED NOT REQUIRED WIRE. GROUND WIRE SHALL BE INSTALLED TO ALLOW FOR PANEL REMOVAL WITHOUT DISRUPTING EGC/GEC: 1 #12 PV WIRE CU 1 #10 THWN-2 CU 1 #6 THWN-2 CU O CONTINUITY. ALL MODULE GROUND CONNECTIONS SHALL BE MADE IN ACCORDANCE WITH NEC (-9-) ALL CONDUIT TO BE EMT, SCHD 40 PVC OR RIGID METAL. MIN. 3.5" OFF OF ROOF SURFACE. OVER-CURRENT PROTECTION DEVICE (OCPD): 14 20A FUSE 1 60A BREAKER 1 175A BREAKER 690.31(J). EXTERIOR FITTINGS TO BE WATER TIGHT. ESTIMATED MAX. LENGTH & MAX. VOLTAGE DROP %: 260ft 1.0% 40ft 0.30% 10ft 0.05% •o NEC CODE & CONDUCTOR SIZING CALCULATIONS CIRCUIT INFO CIRCUIT INFO CIRCUIT INFO TRANSITION FROM FREE AIR PV WIRE TO CONDUIT BETWEEN ARRAYS AS NEEDED. 0 ALL DC CONDUCTORS TO BE 1000VDC RATED COPPER (CU) UNLESS NOTED OTHERWISE. QUANTITY OF PARALLELED CIRCUITS 1 1 3 SEE D/PV6 FOR CONDUCTOR SIZING CALCULATIONS. 690.8(A); MAXIMUM CURRENT: Isc X 1.25 X 1 = 12.0A INV. OUTPUT = 43.5A INV. COMBINED = 130.5A w n TOTAL DC VOLTAGE DROP PERCENT (578.2VDC, 8.82ADC): 1.30%VDC 690.8(B)(1)(a); CONTINUOUS CIRCUIT CURRENT: Isc X 1.25 X 1.25 X 1 = 15.0A INV. OUTPUT X 1.25 = 54.4A _ INV. COMBINED X 1.25 = 163.1A ® INVERTER INTEGRATED DC DISCONNECT. 15ADC FUSES EACH INPUT. ° 690.8(B)(1)(b); TERMINAL TEMPERATURE REQUIREMENTS: _ 75°C:310.15(B)(16) = 35A >_ 15.0A 60°C:310.15(B)(16) = 55A >_ 54.4A 75°C:310.15(B)(16) = 175A >_ 163.1A z z 12 TOTAL AC VOLTAGE DROP (480VAC, 43.5AAC MAX PER INVERTER, 132AAC COMBINED): 0.45 VAC 690.8(B)(2)(a); CONDUCTOR AMPACITY WITHOUT CONDITIONS OF USE: ' 90°C:310.15(B)(16) = 40A >_ 15.0A 90°C:310.15(B)(16) = 75A >_ 54.4A 90°C:310.15(B)(16) = 195A _ 163.1A z 1- O o n (3) CPS, SCA36KTL-DO/US-480 36,000WAC STRING-INVERTER, 480VAC, CEC WEIGHTED EFFICIENCY 310.15(B)(2)(A); AMBIENT TEMPERATURE: 32°C 32°C 32°C "' F- 98.0% . UL1741 LISTED WITH INTEGRAL ANTI-ISLANDING PROTECTION FEATURES. NEMA 4X, UL1741 0 EQUIPMENT LABEL CALLOUT. SEE C/PV7 FOR DETAILS. 310.15(B)(3)(c); TEMPERATURE ADDER FOR CONDUIT HEIGHT: + 17°C - 3-1/2" - 12" ABOVE ROOF + 0°C - NOT ON ROOF OR 36"+ + 0°C - NOT ON ROOF OR 36"+ o o LISTING INCLUDES COMPLIANCE WITH IEEE519 FOR POWER QUALITY, IEEE929 FOR 310.15(B)(2)(A); TEMPERATURE & THE DERATE: i 32°C + 17°C = 49°C = 82% 32°C + 0°C = 32°C = 96% 32°C + 0°C = 32°C = 96% w w INTERCONNECTION SAFETY AND THE NATIONAL ELECTRICAL CODE. TIED TO EXISTING FACILITY 310.15(B)(3)(a); ° ° w CONDUCTORS IN RACEWAY/BUNDLED & THE DERATE: 14 CURRENT CARRYING = 50/0 3 CURRENT CARRYING = 100/0 3 CURRENT CARRYING = 100/o o GROUND. INVERTER IS TRANSFORMERLESS, UNGROUNDED AND UL LISTED AS A UNIT. INVERTER HAS TOTAL CONDUCTOR DERATE: 82% X 50% = 41.0% 96% X 100% = 96.0% 96% X 100% = 96.0% UL1741 APPROVED GROUND FAULT DETECTION DEVICES THAT MEET NEC 250.122 REQUIREMENTS 690.8(B)(2)(b); CONDUCTOR DERATED AMPACITY: 40A X 41.0% = 16.4A >_ 12.0A75A X 96.0% = 72.0A >_ 43.5A 195A X 96.0% = 187.2A >_ 130.5A m z FOR EQUIPMENT GROUNDING. •690.8(B)(1)(a), 250.122 &/or 250.166; OCPD SIZE IF REQ. &ASSO. EGC/GEC: 20A OCPD <_#12 EGC/GEC 60A OCPD <_#10 EGC/GEC 175A OCPD _<#6 EGC/GEC o CO�690.8(B)(2)(c); CONDUCTOR DERATED AMPACITY & OCPD AMPACITY: 16.4A IS OK ON A 20A OCPD 72.OA IS OK ON A 60A OCPD 187.2A IS OK ON A 175A OCPD N \6/ DEDICATED 480VAC, 200AAC, 3 PHASE, INVERTER COMBINER PANEL TO PLACE INVERTER OUTPUT w ( . Q CIRCUITS IN PARALLEL. (3) 60AAC 3 POLE SOLAR BREAKERS RATED FOR BACKFEED. TOTAL RATING w I (, OF ALL OVERCURRENT DEVICES, EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE, SHALL NOTcL 6' EXCEED AMPACITY OF BUSBAR. SEE D/PV6 FOR BREAKER SIZING CALCULATIONS. SHEET NO.&NAME: 0 PV6 CV (0 N-- di C� KEYED NOTES D CONDUCTOR AMPACITY CALCULATIONS a \ P6.. / Scale: NTS \PV6 Scale: NTS LINE DIAGRAM z E ELECTRICAL NOTES FOR NEW PHOTOVOLTAIC SYSTEM: NW PHOTON 1. THIS PROPOSED SOLAR ELECTRIC SYSTEM IS INTENDED TO OPERATE IN PARALLEL WITH POWER RECEIVED FROM THE UTILITY SERVICE PROVIDER. 2. EQUIPMENT GROUNDING CONDUCTORS AND SYSTEM GROUNDING CONDUCTORS WILL HAVE AS SHORT A DISTANCE TO GROUND AS POSSIBLE AND ENERGY A MINIMUM NUMBER OF TURNS 2. THE INVERTER FOR THE PROPOSED SOLAR ELECTRIC SYSTEM SHALL BE IDENTIFIED AND LISTED AS A UTILITY INTERACTIVE INVERTER FOR USE IN 560 FIRST ST, SUITE SOLAR PHOTOVOLTAIC SYSTEMS. 3. NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING; NOTING THAT TERMINAL LUGS BOLTED ON AN 104 ENCLOSURE'S FINISHED SURFACE MAY BE INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY 503-703-4046 3. THIS SYSTEM IS INTENDED TO CONNECT TO THE EXISTING FACILITY POWER SYSTEM AT ONE POINT, POINT OF COMMON COUPLING (POCC). THIS REMOVED. KIRK@NWPHOTONENERGY.COM CONNECTION SHALL BE IN COMPLIANCE WITH THE NEC ARTICLE 705.12 "POINT OF CONNECTION". 188056 5. MODULES SHALL BE GROUNDED WITH EQUIPMENT GROUNDING CONDUCTORS BONDED TO A LOCATION APPROVED BY THE MANUFACTURER WITH 4. ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION FOR TESTING AND ISOLATION. A MEANS OF BONDING LISTED FOR THIS PURPOSE. 5. ALL DISCONNECTS AND COMBINERS SHALL BE SECURED FROM UNAUTHORIZED/UNQUALIFIED PERSONNEL BY LOCK OR LOCATION 6. THE CONNECTION TO THE MODULE OF THIS PROPOSED SOLAR ELECTRIC SYSTEM SHALL BE SO ARRANGED THAT REMOVAL OF A MODULE FROM THE PHOTOVOLTAIC SOURCE CIRCUIT DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER PHOTOVOLTAIC SOURCE CIRCUIT. SETS OF STAMP: 6. ALL DISCONNECTS, COMBINERS, PULL/SPLICE BOXES, AND ENCLOSURES SHALL BE LISTED FOR IT'S PURPOSE. MODULES INTERCONNECTED AS SYSTEMS RATED AT 50 VOLTS OR LESS WITH OR WITHOUT BLOCKING DIODES, AND HAVING A SINGLE OVER CURRENT DEVICE SHALL BE CONSIDERED AS A SINGLE SOURCE CIRCUIT. -.--::-:7;7'..::-,\ �� '.. 7. EQUIPMENT SHALL BE INSTALLED IN A SECURE AREA. INVERTER PERFORMANCE MAY BE AFFECTED IF INSTALLED IN DIRECT SUNLIGHT. , ,312;\\ „ J 7. GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, INCLUDING BUT NOT LIMITED TO GROUND RODS, GROUNDING LUGS, ' <^ .. WIRING METHODS: GROUNDING CLAMPS, ETC. �... ALL WIRING METHODS AND INSTALLATION PRACTICES SHALL CONFORM TO THE NATIONAL ELECTRICAL CODE (NEC), LOCAL STATE CODES, AND - OTHER APPLICABLE LOCAL CODES 8. WHERE GROUND FAULT PROTECTION IS NOT PROVIDED, EACH GROUNDING CONDUCTOR SHALL BE SIZED TO TWICE THE NORMAL CALCULATED r_� •.• �:xt:N , __, `z, AMPACITY PER NEC 690.45(B). +F `` ` 1. EXPOSED PV SOLAR PANEL WIRING WILL BE PV WIRE, 90 DEGREE C, WET RATED AND UV RESISTANT. ALL EXPOSED CABLES, SUCH AS MODULE ,/ RUSVA w; LEADS SHALL BE SECURED WITH MECHANICAL OR OTHER SUNLIGHT RESISTANT MEANS. GROUND FAULT PROTECTION: `�" " 1. PHOTOVOLTAIC INVERTERS SHALL BE EQUIPPED WITH DC GROUND FAULT PROTECTION TO REDUCE FIRE HAZARDS. li (.sem "„ ,,,,,,,,",,,,,,,,,,,,,,,,," 2. ALL GROUNDED CONDUCTORS SHALL BE WHITE OR GRAY AND EQUIPMENT GROUNDING CONDUCTORS GREEN OR BARE. (NEC 200.6). DISCONNECTING MEANS: 3. DC SOURCE CIRCUITS SHALL BE BLACK PV WIRE WITH LABELS ON BOTH ENDS INDICATING INVERTER NUMBER AND SOURCE CIRCUIT NUMBER. 1. MEANS SHALL BE PROVIDED TO DISCONNECT ALL CURRENT CARRYING CONDUCTORS OF THE PHOTOVOLTAIC POWER SOURCE FROM ALL OTHER SOURCE CIRCUITS WILL BE IDENTIFIED AT ALL POINTS OF TERMINATION, CONNECTION, AND SPLICES WITH RED MARKING FOR POSITIVE CONDUCTORS IN THE BUILDING. CONDUCTORS AND BLACK FOR NEGATIVE CONDUCTORS OR A COLOR OTHER THAN GREEN, WHITE, GRAY, OR RED. 2. THE DISCONNECTING MEANS SHALL NOT BE REQUIRED TO BE SUITABLE AS SERVICE EQUIPMENT AND SHALL BE RATED IN ACCORDANCE WITH 4. CONDUIT TYPES USED IN THE PV INSTALLATION SHALL BE APPROVED FOR THEIR SPECIFIC APPLICATION AND SUPPORTED PROPERLY PER NEC. SECTION 690.17. 5. LONG STRAIGHT CONDUIT RUNS, 100 FEET OR MORE, SHALL HAVE EXPANSION FITTINGS, IF EXPOSED TO WEATHER. 3. A SINGLE DISCONNECTING MEANS SHALL BE PERMITTED FOR THE COMBINED A.C. OUTPUT OF ONE OR MORE INVERTERS IN AN INTERACTIVE SYSTEM. 6. IF USED, ALL WIRENUTS ARE TO BE INSTALLED PER LOCATION REQUIREMENTS AND MANUFACTURERS SPECIFICATIONS BY A QUALIFIED/CERTIFIED PERSON. WIRENUTS SHALL NOT BE USED ON DC CONDUCTORS. REQUIRED SAFETY SIGNS AND LABELS: 1. REQUIRED SAFETY SIGNS AND LABELS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE, OR OTHER MECHANICAL MEANS. LABELS SHALL COMPLY 7. FUSES AND WIRES SUBJECT TO TRANSFORMER INRUSH CURRENT SHALL BE SIZED ACCORDINGLY. WITH ARTICLE 690 VI OF THE NEC OR OTHER APPLICABLE STATE AND LOCAL CODES. SEE LABELS AND MARKING PAGE FOR MORE INFORMATION. 8. ALL DC MATERIALS SHALL BE LISTED FOR 1000V DC GENERAL NOTES GRID TIE PHOTOVOLTAIC INVERTERS: 1. SYSTEM GROUNDING MEANS: THIS INVERTER IS INTENDED TO BE INSTALLED AS PART OF A PERMANENTLY GROUNDED ELECTRICAL SYSTEM PER 9. CONDUITS AND CONDUCTORS: ALL INTERCONNECT WIRING AND POWER CONDUCTORS INTERFACING THE UNIT MUST BE IN ACCORDANCE WITH THE NEC ANSI/NFPA 70. THE AC AND DC GROUND BUS BARS ARE CONNECTED TO THE MAIN INVERTER ENCLOSURE. A GROUND FAULT INTERRUPTION w THE NEC ANSI/NFPA 70 AND ANY APPLICABLE LOCAL CODES. LARGE GAUGE WIRE MUST CONFORM TO THE MINIMUM BEND RADIUS SPECIFIED IN THE DEVICE IS PROVIDED INSIDE THE INVERTER. GROUND FAULTS ARE MONITORED BY THE INVERTER AND THE INVERTER IS DISCONNECTED FROM THE I- H NEC, ARTICLE 300.34. KEEP ALL WIRE BUNDLES AWAY FROM ANY SHARP EDGES TO AVOID DAMAGE TO WIRE INSULATION. ALL CONDUCTORS SHOULD GRID IN THE EVENT OF A GROUND FAULT. CD - BE MADE OF COPPER AND RATED FOR 90 DEGREE C MINIMUM. FOR OUTDOOR INSTALLATIONS, ALL INTERCONNECT CONDUITS AND FITTINGS MUST BE COC 6)NEMA-4 RATED AS REQUIRED BY THE NEC. 2. INVERTER ENCLOSURE: INVERTERS ARE INDOOR/OUTDOOR RATED, IEC GRADE, NEMA 3R OR EQUIVALENT. ALUMINUM CONSTRUCTION WITH U Q >_ co ENAMEL COATED PAINT ON ALL SURFACES. ALL REMOVABLE INTERNAL PANELS ARE COVERED WITH ENAMEL COATED PAINT ON ALL SURFACES. ALL EE w 10. CONNECTORS TO BE TORQUED PER DEVICE LISTING, OR MANUFACTURERS RECOMMENDATIONS. SURFACES ARE TREATED WITH A ZINC-RICH PRIMER AND THEN POWDER COATED TO INHIBIT CORROSION. I- 1 rn 11. ALL AC WIRING SHALL BE COPPER WIRE, TYPE THWN-2 RATED AT 90 DEGREE C, AND RATED FOR 600V, OR APPROVED EQUAL. 3. ENVIRONMENTAL CONDITIONS: INVERTERS ARE DESIGNED TO BE INSTALLED IN EITHER AN INDOOR OR OUTDOOR LOCATION. THE UNIT MUST BE J o _ 0 m 0 = ANCHORED TO A LEVEL CONCRETE FLOOR OR STEEL PLATFORM, OR OTHER NON-FLAMMABLE STRUCTURE CAPABLE OF SUPPORTING THE W a Co0 co 12. Pct ROPERLY SUPPORT ALL EXPOSED PV SOURCE CIRCUITS TO MAINTAIN THE INTEGRITY OF THE CONDUCTOR'S INSULATION. EQUIPMENT. ALLOWABLE OPERATING TEMPERATURE RANGE FOR THE UNITS ARE SPECIFIED BY THE MANUFACTURER. ._<51 O z z 0 13. ALL FIELD MADE QUICK CONNECTS USED FOR PV MODULE WIRING MUST BE OF THE SAME MAKE AND MODEL AS THOSE ON THE PV MODULES. USE ELECTRICAL SAFETY FEATURES: Oo w Cr) I- U o LISTED CRIMPERS FOR FILED MADE CONNECTIONS. THE UNIT HAS ONLY ONE MODE OF OPERATION, LINE LINKAGE MODE (GRID EXPORT MODE). THE OUTPUT VOLTAGES AND CURRENTS ARE SINUSOIDAL U _1 p o O o WITH LOW TOTAL HARMONIC DISTORTION MEETING IEEE 519-1992 HARMONIC STANDARDS. D z Q GROUNDING: < U c, SEE ELECTRICAL DIAGRAM AND ELECTRICAL DETAILS FOR MORE GROUNDING INFORMATION. THE ANTI-ISLANDING TRIP TIME IS LESS THAN (2) SECONDS AS PER UL 1741 STANDARDS. THE INVERTER UNIT WILL AUTOMATICALLY SHUT DOWNM E z WHEN THE LOSS OF GRID POWER IS DETECTED. co ~ 1. DC SYSTEM IS UNGROUNDED AND DOES NOT HAVE A DIRECT CONNECTION TO A GROUNDING ELECTRODE CONDUCTOR. cd. N2 N (a r co a_ a, 1 A� GENERAL ELECTRICAL NOTES L �- �PVy Scale: NTS 0 SCALE 0 O AS SHOWN cp GENERAL NOTES: NEC 2014 705.12(D)(2)(3)(C) NEC 2014 690.13(B), 690.54 NEC 2014 690.15(A)(4), 690.56(B), 705.10, 705.12(D)(3) NEC 2014 690.13(B), 690.54, 705.12(D)(2)(3)(B) ORIGINAL SIZE 24" X 36" L1 L2 NOT USED L3 L4 L5 SHEET SIZE ARCH "D" 1. THE MARKING SHALL ADEQUATELY WARN OF THE HAZARD USING EFFECTIVE O OIVO OWARNING OTICE WARNING \1\J1.\RNING „ • WORDS AND/OR COLORS AND/OR SYMBOLS. NEC 110.21 0 %2 1" a THIS EQUIPMENT FED BY MULTIPLE SOURCES DUAL POWER SOURCE PHOTOVOLTAIC SYSTEM DISCONNECT ©Copyright 2016 2. THE LABEL SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING PHOTOVOLTAIC SYSTEM AC SECOND SOURCE IS PV SYSTEM INVERTER OUTPUT CONNECTION NW PHOTON ENERGY o TOTAL RATING OF ALL OVERCURRENT DEVICES, DISCONNECT AND POWER SOURCE The drawings,ectespecdundersandother contract. Reproductints related on of- METHOD AND SHALL NOT BE HAND WRITTEN. NEC 110.21 project are protected under law and Reproduction of SYSTEM DISCONNECT LOCATED: DO NOT RELOCATE THIS DEVICE these documents is authorized for the purpose of constructing, 0o EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE, RATED OUTPUT CURRENT:130.5AAC LOCATION maintaining and using this project. Use of these documents for t3. THE LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE SHALL NOT EXCEED AMPACITY OF BUSBAR. any other purpose is not permitted without written authorization. ENVIRONMENT INVOLVED. NEC 110.21 NOMINAL OPERATING VOLTAGE:480VAC LABEL TO BE APPLIED AT SERVICE EQUIPMENT RATED OUTPUT CURRENT:43.5AAC co LABEL TO BE LOCATED ON COVER OF INVERTER AC LABEL TO BE LOCATED ON THE PV SYSTEM AC LOCATION OR ON ALL POWER PRODUCTION SOURCES NOM. OPERATING VOLTAGE:480VAC 4. LABELS AND MARKINGS SHALL BE APPLIED TO THE APPROPRIATE COMPONENTS COMBINER PANEL. (1) TOTAL DISCONNECT. (1) TOTAL CAPABLE OF BEING INTERCONNECTED. (2) TOTAL LABEL TO BE LOCATED ADJACENT TO THE 11, IN ACCORDANCE WITH THE NEC. PV BREAKER AT THE POINT OF COMMON a. COUPLING AND AT INVERTER AC z 5. SOLAR MODULES AND INVERTERS ARE SUPPLIED FROM THE MANUFACTURER DISCONNECT. (6) TOTAL o WITH MARKINGS PRE-APPLIED TO MEET THE REQUIREMENTS OF NEC 690.5(C) & NEC 2014 690.31(G)(3) NEC 2014 690.35(F) NEC 2014 690.15, 690.17(E) & 690.53 690.51. L6 L7 L8 WARNING O 3. OSHA 1910.145 AND ANSI 2535 SPECIFICATIONS ARE RECOMMENDED BUT NOT 3/8" MIN. WARNING WARNING : PHOTOVOLTAIC POWER S ELECTRIC SHOCK HAZARD - REQUIRED. -F PHOTOVOLTAIC DC DISCONNECT a. LABELS SHALL HAVE ROUNDED CORNERS. THE DC CONDUCTORS OF THIS PHOTOVOLTAIC ELECTRIC SHOCK HAZARD w b. LABELS SHALL BE VISIBLE AT A MINIMUM OF 5ft. LABEL SHALL BE LOCATED ON ALL EXPOSED RACEWAYS, CABLE TRAYS, OTHER WIRING METHODS, COVERS OR ENCLOSURES OF PULL SYSTEM ARE UNGROUNDED AND MAY BE 5- c. "WARNING" LABEL BACKGROUND SHALL BE IN ORANGE. BOXES AND JUNCTION BOXES AND ON CONDUIT BODIES IN WHICH ANY OF THE AVAILABLE CONDUIT OPENINGS ARE UNUSED. LABEL SHALL ENERGIZED DO NOT TOUCH TERMINALS z Z d. "NOTICE" LABEL SHALL BE IN BLUE. BE REFLECTIVE, AND ALL LETTERS CAPITALIZED AND SHALL BE MINIMUM HEIGHT OF 3/8" IN WHITE ON A RED BACKGROUND. SPACING LABEL TO BE LOCATED ON EACH JUNCTION BOX0 , J o 1- TERMINALS ON BOTH THE LINE AND LOAD SIDE MAY o 1 a▪ e. ALL TEXT SHALL BE BLACK. BETWEEN LABELS OR MARKINGS, OR BETWEEN A LABEL AND MARKING, SHALL NOT BE MORE THEN 10FT. COMBINER BOX, DISCONNECT, AND DEVICE WHERE BE ENERGIZED IN THE OPEN POSITION E o ENERGIZED, UNGROUNDED CIRCUITS MAY BE Cf) Q o EXPOSED DURING SERVICE. (10) TOTAL RATED MAX. POWER-POINT CURRENT:35.3ADC o a CD RATED MAX. POWER-POINT VOLTAGE:666.OVDC � MAXIMUM SYSTEM VOLTAGE:935.3VDC MAXIMUM CIRCUIT CURRENT:48.1ADC m z o co w LABEL TO BE LOCATED ON COVER OF DC DISCONNECTING D N MEANS. (3) TOTAL w , Q i w I rnSHEET NO.&NAME: co 0 PV7 c: ,_ ,_ C LABELS AND MARKINGS 0 KPV7) Scale: AS SHOWN ELECTRICAL NOTES zE NW PHOTON ENERGY � s.„:.ao� CI Technical Dat.: 560 FIRST ST, SUITE Model Name CICS SCA36KTL-DONS-480 61( 1000 ` r Eiji nee r* for North Am rica DClnput ua iWC 104 503-703-4046 Max.PV Power 54kW(27kW/MPP1) KIRK@NWPHOTONENERGY.COM Nominal DC Input Power 37kw. 188056 Max.DC Input Voltage l 000Vdc , Operating DC Input Voltage Range 240-950Vdc Start-up DC Input Voltage/Power 330V/300W #e Number of MPP Trackers 2 - O MPPT Voltage Range 540-SOOVdc The medium power series of grid-tied,transformerless inverters ,A help to accelerate the use of 1000Vdc and three phase stringSTAMP: architecture for commercial and small ground mount utility Max.In put Current(imp) 70A(35A perMPPT) \ applications. A NAIL approved,cost effective alternative Max Short Circuit Current(lsc) : 7 1\' P, „ 0,-) \ \ al ,11 to central inverters enabling BoS cost savings, high harvest =' Number of DC Inputs 8 inputs,4perMPPT t ,.,, performance and modular design building blocks. These models DC Disconnection Type Load rated DC switch provide up to 98,4%conversionefficiency and wide operating %� - window of 240-950Vdc and dual MPPT"s for maximum energy $ AC Output '1 harvest. Rated AC Output Power 36kW t10- i-Cine Photovoltaic Module Max.AC Output Power 36kW Rated Output Voltage 480Vac ` , Output Voltage Range* 422-528Vac _ Power Range Efficiency Curve Grid Connection Type 3m/PE/N(Neutral Optional) \ -. --3 5 Grp CPS SCA36KTL DO/US 480 Maximum AC Output Current @480Vac 43.5A I ( t A 99.00% CPS SCA36KTL-DONS-480 Rated Output Frequency \ 60FIz \, ,N4Al\=a �� •••• PoweIM YFa tarencyRange* ,0.99(±OSadjustable) ,�� `' ModdeS,n �theiclydDii 97.00% I .,- iced Icath DC INPUT VOLTAGE a to meet.1 Fal oathn�,re guxeri e rm- 3 9500% -_ _._..-_-._.. �__ ._ Current THD <..,% , „ 540 V Dimensions AC Disconnection Type Load rated AC switch 93,00% E' ,, saHs710'd .7gOV System I I .€ i. 1 t. its . ElammabilityTest • assvaaav91.00% 1-- J____---�----.-_,i-. €_._ .�_ — -. Topology Transformerless a , , : t 1 r �` e * ka. A:\� Low hitablfrtppnsuringfirQs�feYp 0 6000 12000 18000 24000 30000 36Q00 Max Efficiency 98.4% 1 �, t 4u, \' outputPower(W) . i 't l € o CERicC Efficiency 98.0% i-......1:1-'1.1.:1 "� Stand-by 7Night Consum tion <20W/<2W , •• Anti-Reflection Coated Glass . a, 111 tr1 � i t1 '�Efficientvm Environment 1`f rI I +Anti-refle titresurfdcaenhanc- t n power €• €� erforrn me 101 t 1�1r Protection Degree NEMA 4 . . p a Maximum efficiency of 98.496,CEC efficiency of 9896 I Cooling Variable speed cooling fans . a 3-level technology and enhanced control mechanism ° ° to achieve high efficiency over wide load range �. Operating Temperature Range 13°F to+140°F/-25 C to+60 C(derating from+113°F/+45°C) a2MPPTstoachievehighersystemefficiency 2a.Sln L-e.iin- Storage Temperature Range -49°F to+158°F/-45°C to+70°C "' , Trgnsformerless design Operating Humidity 0-95%,non-condensing Operating Altitude 13123.4ft/4000m(derating from 6561.7ft/2000m) ,, i Vit, Display and Communication E High Reliability Broad Adaptability Display LCD+LED • Communication Standard:RS485(Modbus)Optional:TCP/IP Card t ` a"Electrolyte-free design"for improved long-term reliability a NEM 4(IP65),outdoor application Mechanical ' Standard warranty5 years,extension up to 20 years e Utility interactive controls: Active power derating, reactive power control Dimensions(WxHxD) 600x1000x230mrn $ Advanced thermal design,with variable speed fans" :;i E i : W Separate wiring box design Weight Inverter:121Ibs/55kg; Wirebox:24ibs/1lkg 1- a Ground-fault detection and interruption circuit s I — a�Integrated DC AC disconnects Installation Angle 15-90 degrees from horizontal AFCI Integrated per UL1699B ›- a•Wide MPPT range for flexible string sizing Safety ': € Ct C3) 1000V Max.DC input voltage for flexible configuration Safety EMC Standard UL1741:2010,UL1699B,CSA-C22,2 NO.107,1-01,IEEE1547;FCC PART16 I U Q Cr) tit 15 90 de teeinsiallationan Ie Grid Standard IEEE1547:2003,IEEE1547.1:2006 ( n- CV CO Fe fltl p e rcci :u g g ,..kir rY+rFQP41u - z W ti t: us c Compatible with-Copperand Aluminium wire on AC side *The"Output Voltage Range and"Output Frequency Range may differ according to specific grid standard. - ,� W Q 0_ C3) LUCK eCHINTPOWER 2015/06-MKT (hint Power r,tern A: rice € 2 70.',0 Kcll CenterParkway Suit 1r Pleasanton C0.94.,66 ' �� Tel 855-524-716a !veil Anserlc.asaInt F intpowea corn 91..0 ,ww.ch ntpowersys+eli;;=urn W co co Q O Z Z c O O Cr) Q U) W D F- (Di— CD ..._ .. \\,\ DM !WOL CONNECT GROUNDING8.4% 0 c o ,:, ;r GUIDE I m •a Z , CL ic INSTALLATION PAGE I I Q CL 12 a) S P E C I F I CAT I O N S _ WEEBLUO may be Cr) z 4101\ ,—.,.. used up to5tiimes ® (C *eT j Eie.ctFic.d Data Dimension', trim (inch) CO C g Use C> Sire [ it 1 w• _:i. - �'" i 'p.Nor(nal Pcvwer F1, 320W325W '331V'/ 335W a I tt9 \( \ CNI Q C /''Q(i '�ri ri =1`It tl0dule Efltlenr:` f 5. f 7.Ja T a i7 r I 1 ., 1;117' 4 1 h ( 1, I 0 Torque to Aloft-lbs li e Torque to 51t-its 1 ;t i,,,YR I !ilia t [ti el 373 3't5 ii T U$J3 • r • %� z 1 �t z �` ±}"it t i 'Ffi rill _u. ,",irt l.R.(tt'I 'SS 31:i,, c 76 6°2 � PROTECT CHARACTERISTICS �= _.), ,- Tl3t i:� a G a �" T' .s_ , nCjn alt .'1LiyC1` ''f 1t,.11r. 1t 111 (i 5r, `- rrsarkin - i If/ 1 ,!rain } (3*,klj. I ��'. , -. sl_-hart r,Ilt . _ S,- 9 t f Q- .,,= 3 Allowable Roof Slope: 3 Degrees_...-. _. . ___.__.___..__.,_ t€fel disc e bending lug tan m •- ;int is i e'1 ' -. S be located Ped anywhere along Fergus vela€e d«pends rsn , , '_ tl +"t SCALE O �V _s Unevenness: +/-3.5 Degrees lo£afaoa, Udepends on '� f1...9al�Fii,��,_ldi:- u, "sr �,u the same surface as true Turgue Yalu conductor size, \ ��• ••,aAh\.\�. i• , ... i J conductor - 5R� a7am la rHrci�.tmtuanrorn3zi:�isE:rriTcstCnr nbnsfiT ftnctdzn'!n+ N w Max Building Height: 100 ft ___ „_ -. marking!abet g' See product data sheet it. ; 3 .- ., - <-, - :t . . z ' m e r 'a �S-rf;.lmtnrrlrUU54mapcctrsldssihnFi,Mly,vary;�rx?rri17`f 'C,InurartincrrfihEld6[ftah:, AS SHOWN 0 , 2 w Se product data sheet for torque value. / y. �.� iWind Speed: Up to 120 mph w g 4 •the Ei`•,n rlsrts Tss d rr a8nril raffle r,+trhars m 5r bi9t t rums anrlmiFu trrls}1 Ink nntas Q€f lu tsttit tie C o�� A��,...:, 4_.. .. �.� ..... ,-•-:-,t- - :,'..„....„:„� :' r for tarqut Value. sus pinn of fi Tilt riasl�ilorc sa irhnts d isserdive Px � . - - °liukhuk.siaai t3L1721160:uitindirnon-331}it%ekleeteektheft`r"44OP,PI,44'tbrV5Ud3.39t4 lr � � � , WIn:Exposure. Categories B and C. (D Upon Request) ( t I �: t, 36 ORIGINAL SIZE 24 X - ��---, >.. ,{ PSF on Roof: As low as 3.5 PSF BONDING PATH DIAGRAM:The RM ballast conformance with U 703 was demonstrated without the use of oxide inhibitor material,it is �`=C!l ?1 ttil'� Co1 efficient__ . -_ baysAlthough�o m ce Lz ' - ,,..... . . , . ��.,.. Moaning SHEET SIZE ARCH "D" ot$ Surfaces: EPDM, PVC&TPO Membranes, are bonded to the PV module frames through the recommended by Iosco to provide an optimized bonding solution for their lay-in lug. ,g_ He hs — mounting clip and bolt. This method of bonding '-. T 1r Bitumen &Concrete provides an exceptionally low resistance path along GROUNDING LUG MOUNTING DETAILS AS REQUIRED BY CODE & ENGINEER OF RECORD: Details >_ _. ............... "............,.. 11-la,Tetripf:t*atur€"Coefficient U P. -ll.}_.u' I. 0 /2aa 1" 2 z each row and column of the arrayare provided for both the WEEB and Iosco products.The WEEBLug has a grounding symbol located on the cB Min.Local Contact Area: 38 in per Module(57 in with Roof Pad) 1 i� (bib I Jp lug assembly.The Iosco tug has a green colored set screw for grounding indication purposes.One Lug is TyrTetnpera tire C,0efficient of ,,,,� -f!_2%,1 l: ('fe2`A f,='.JB)�. 0 Copyright 2016 � Module Orientation: Landscape recommended per continuous array,not to exceed 150ft X 150ft - - - - -- _--. :-�.nl �'� CO _______.___._.___. Ten"I teratur2(.0eff(i etit 9t k, 0.07�a,+ NW PHOTON ENERGY o Nominal Module Tilt Angle: 10 Degrees Nominal i Unirac Roof Mount is intended to be used with PV arrays that have a system voltage less than or equal to t Graundis3 _y .• g g (Nominal) ( ,( ! The drawings,specifications and other documents related to this 1000VDC.A min.10 AWG,105 degrees Celsius copper grounding conductor should be used to ground a 1000 .,:i.OCTkaumila7priirm CsI'3i€aptriarr,rrsu[rr;7rcnd�n::,ka rti r Cthfa4a2•A,t1 i,5 riin -s,tn 33.'C,vwdgas d I ink Ho E= project are protected under law and contract. Reproduction of 'THE POWER Row Spacing: 19 in(Nominal) 4 VDC system,according to the (NEC) National Electric Code and the authority having jurisdicition.It is the these p `I installers responsibility to check codes,which ma vathese documents is authorized for the purpose of constructing, U -�-� p ty y n gChlrt}C3J t 17 �cr�F t ticc maintaining and using this project. Use of these documents for Of SIMPLICITYany NOTE:The installation must be conducted'€n accordance with tine National Electric Ct de ANSI NITA70. I other purpose is not permitted without written authorization. a 1 1- I irfitnsions- r15b < Q?y { h� �c CD COMPONENTS MATERIALS �" - �1 xw.gti) 1, � eta-: li_ t_I�J_ .. I i in� � !-�''' � ....---"'~' �,1T Ground Lug � Bolt Size Drill Size Torque Value H _„ _ i . �� \1u etpht 225kt(49.1 Masi ROOF MOUNT introduces the Power Ballast Bay Aluminum 6063-T5 P iia., WEEBLug I 1/a=3o 17/64' 10ftdbs CA `j IlseoLug #10-32 I 7/32' Sft-lbs • Front• IeS, i-1f,h transp,..rent,oldr,lid5�[ttnipert3,I,:1 firYl]fi.la jn,i of Si mplicityto the ballasted flat roof Module Clamp Aluminum 6005AT61 � % solar industry. The system consists Locking 3/8"Hex Bolt Stainless Steel 300 Series rli i2 rnLliti:r ct3lli lc filar wells • W �a(}:Sheet r�0nr{€af4te'II rn- n- of ono two ma or com onents, Roof Pad TPE 7o ShoreA ._-- -----_---- -_- ---- -.. Y 1 p Frame Anodized al'Iltnininnttrile z minimizing preparation work and lunation Box:: 1P-67 rated'CI h 3 bypass diodes installation time.Seamlessly design CunnecrorTyp.e 1 i i / •.-uric BALLAST BAY GEOMETRY , t",c4,.,ompTIttie: 1 f:4trial, Lenett each 17 fi-r (47.241n I-V r�,ei'.tdiltirradiart cV around roof obstacles, supportw. .w,. .. .,. , ,,.:', , , - , . . �� ,\�. ,atlO GROUNDING & BONDING PROCEDUREa Width. 21 in � � s �� V2o p, t ip00lah/w] most framed modules and bondr Irl t; ndll�n a? Length: 17 in ,a` INSTALLATION 11R �� ....._-.- s .._—__-:__.-___-_-___ __ . \ r,Ou � GUIDE i PAGE �35 C P00 W/rn __ . _ , CL the system with just the turn Ofd Height: 13 in 0pvrattnl,Ternperature 1 4-8 ; wrench. Weight: 3.5 lbs TEMPORARY GROUNDING & BONDING ArobaentTernperata re R?ars s - 1 45 . fi '5C$C 7iii l - �- 1- ., � . Lru"�1 m�-I �. � - - -------- PROCEDURE: Periodic inspections should be • �, f't,.�.S�.ster:Z�,+c-�t�+eLlL (?lliQ"',,' � j i = Roof Pad: 3 in x 10 in conducted on the PV array to ensure there are not �v' i , w`, enf--1- i j j.,•-•-.-,- loose components, loose fasteners or corrosion. \` t P \ _ Serial Fu"e Ratnt Q If any of the above items are found,the affected ,. - - i -.'.. Li] ®, s r ' lt" tins' I - - Pimmediately replaced. t`it,ntuml€arrarlLea., rdialto1_111703 _ 1 " components are to be If a dC.alxut,' Te ted u i toS0 Pa at @ f Ct MODULE COMPATIBILITY :.4:.. a i ' swims ra£> ..a.at,atest, orar a_.. l z y Z liorsdi ay jumper must be used to ensure safety of �� L. 14' S un 57 0!�?: arrantie`�- and r er`trf31 3tisun4 the goy sonnet end PV system. , TMw O Standard 60 and 72 Cell Framed Modules A� Prod,i , ,f• ° (v5 • CL CO NOTE:Removing a PV module.from a system is not WErrPLoc, !Isco Lay-an Lug .^ I ouu ct VYar ry rite Ma: min i0 ,ars for rnat»nal aitd M,orkrnan.ship a�.itrentAt:ltar cItTzterttio; ;tilt:depnrd*rr:e On inadance and tnoJtiv.temperature, ~ www.unirac corn Module Clamp w/Integrated Bonding to UL2703 runsfdt:rsr,to be routine maintenance.This type of — Q i_.t,f.=r3r,_li.o- 'ataranttee uuarasteeaiin+'ar, 7 * O (pactivity shatud early b performed by traia,ed ani APPROVED LUGS ATTACH LUGS: Use approved Lug(s) to install on �e ra(3ti on t+kiU for..53 r r; ! Cable Management Compatible w/Strut Accessories t adjacent bays where the module is beingremoved. ,,,- ,, �, r morn e to IE/E`d 61215.IEC1131 1 g=Ia and UL 1703 tuidelitt *s O qualified a=arta Le WEEBLug UNIRAC PN 008002S a h LU �' NOTE In order is prevent cor;asici's induced by S•' _ .R'r rix,:, r 0 CL O dssussitar metals.it is important to verify that the Ilsco lay-in Lug Iosco PN GBL-4DBT •z Huss rs fir is rarrmyIsitrrhideeui .dear w i e', a not come into cs r t ct with See product date.'laect: ,.Nue t enirm aOW El rirrtalrin:cif ii%Id risdir. 0 WARRANTY &CERTIFICATIONS it i,.thew i",.'.€ -Is must be kept separate,_.__._ Par)'41tY* Cnrrfi i.3r3ttor'! 20 Year Manufacturingm Z _�ntairier 20'6 P 40' fin UL 2703 Certification _ hetes per llet 52 xi, 0 co M ;1,,,,,iiiii‘:: L1.1 N- • Pallet perE:c'ntaiser 5 s11 p r 1� 624C u7 so :'�' Q 3 .s 1 .e >,.:_ Iaetes e oita(ter 3t0 CO LU Copyright 02013.2014/UniranInc. ;s ,,:.v:=.,., 10 witra(,.10.,ch),S,,.tr�:.Bui1., g,.r>- - ,0f..,i-r,..:,. . :. ,ilii,c t About A11 C5 mrorv_- i7 rssa.d.: -A11461•1141111i �, All rights reserved Pub140425 4 V,,,,, y ,.. ,,.WireM t C tn_r:rc r U.: :s a l�tdnl? !coal naaraut.cbar at TFT-LCD ct�nrrittet= rh htdin ireerl. 1uti:,rice ih>v,t,rld *de :u_.t nt r in rrcnr: r tat O� g #6 AWG Bare Copper r s P I, 1 8 f g SHEET NO.&NAME: co su;tair:able and frisrity to the errviressnint.Its addition-to it,sstrerritfi=its pr,.d+lit arid techndw• ,ical _� innovatiort MO s�- es its c orrra-sirnee.d to going groan C3 I . j a slid10utiliANIrmmuetturilPxeilencetao+de\slopwit.,et:let:ysolar-...oludortstt-residential,commercial,and urllit,•1_eg7rwnts. C•1 INSERT COPPER WIRE:Insert bare copper(#6 AWG) REMOVE MODULE & REVERSE THE OPERATION ' PV8 wire into each lug, providing a bonding jumper AFTER MAINTENANCE IS COMPLETE s tkIt:s��, „Li ripns 0 y u rr'arp Jmiai 011 I's- across the missing module location. ,: , ,.r ,, a system is not ® i�\\ \ ��: N I Li-I-him fid 'S Hsinchu Science Part:,Horrhu 30078,TaiM:ars considered to be astatine maintenance.This type of E3 ■ i ;:� ,-\� TeL 4886-3.500-2899 -dar$41.10.cori LJJ t3P am ` ■ \ ` .. \N. t Gagit-12M:Ap:ernbtr2015.4LI Liptr*:wi:CawF.MIrlghsnesesled.blortragi rr,aychay. wit,outno.ixt.This m:de:-at is iretdr,4i ,:ylik I- activity should only be perrerrned by trained end CIqualified installers. • 1— . SPEC SHEETS z . E