April 2, 1990
Dennis Woods
Mackenzie/Saito & Associates
P.O. Box 69039
Portland, Oregon 97201-0039
Re: Tenant Modification
Oregon Business Park - Bldg. 15
15800 S.W. Upper Boones Ferry Rd.
Dear Dennis:
This is a Fire and Life Safety Plan Review and is based on the 1988
editions of the Fire and Life Safety Code (UBC) , Mechanical Fire and Life
Safety Code (UMC) , Uniform Fire Code (UFC) , and other local ordinances and
regulations.
Plans are conditionally approved subject to the following items:
1. Automatic Sprinkler Plans: Plans referred to and examined by this
office contain no provisions for the alteration or installation of
automatic sprinkler system. Not less than three sets of plans for
the installation shall be submitted to this office for approval
prior to installation. UBC 302(b)
2. Firestopping: In all wood framed walls and partitions,
firestopping consisting of 2-inch nominally-sized lumber or other
approved materials must be installed at all floor and ceiling
levels. Penetrations in this prescribed firestopping to
accommodate wiring, plumbing, and other similar utility runs must
be packed with noncombustible materials in an approved manner so
as to prevent the passage of flame. UBC Sec. 2516
3 . Approved Plans on Job Site: One set of approved plans bearing the
stamps of the building department issuing the construction permit
and this office must be maintained on the project site throughout
all phases of construction and must be made available to building
and fire inspectors for reference during required construction
inspections. UBC Sec. 303
"Working"Smoke Detectors Save Lives
Dennis Woods
April 2, 1990
Page 2
4. Required Occupancy Certificate: Prior to the use and occupancy of
the project (space) , a certificate of occupancy or other written
instrument of approval must be obtained from the building
department issuing the construction permit. UBC Sec. 307
If I can be of any further assistance to you, please feel free to contact
me at 526-2502.
Sincerely,
-1 ' \
Gene Birchill
Deputy Fire Marshal
GB:kw
/f
cc: Tigard Building Department ✓