Loading...
13285 SW PACIFIC HWY (2)• •OREGON* 004 [ — 4 - I_ it [ t : t X44, P.O. BOX 127 • TUALATIN, OREGON 97062 • PHONE 682-2601 • RUSSELL WASHBURN, CHIEF March 15, 1984 Seven Eleven Store (New Const) 8100-1 SW Pacific Hw Tigard, OR 97223 253A-285-000 Dear Sirs , This is a Fire and Life Safety Plan Review and is based on the 1982 edition of the State of Oregon Structural Specialty Code and Fire and Life Safety Code (UBC) and the 1982 edition of the State of Oregon Mechanical Specialty Code and Mechanical Fire and Life Safety Code (UMC) and local ordinances. Hardware for all doors required for egress is required to be of a simple type having no provisions for locking against egress, with obvious method of operation. Flush bolts other than listed automatic are not acceptable. UBC Section 3303 (see exception) Exit signs shall be installed at required exit doorways and where otherwise necessary to clearly indicate the direction of egress when the exit serves an occupant load of 50 or more. UBC Section 3314(a) . Fire stops , blocking or framing members pierced for utility runs require packing to equal fire resistance prior to such piercing. Wood frame construction requires firestopping of both vertical and horizontal draft openings at maximum intervals of 10 feet. UBC Section 2517(f) Surface flame spread rates of walls and ceilings, minimum requirement: stairway 25, corridors - 75, other rooms - 200. UBC Section 4204. All exposed insulation materials , including facings, shall have a maximum flame spread rating of 25 and a smoke density not to exceed 450. UBC Section 1718(c) Conformance with all requirements for the removal of architectural barriers to the handicapped is required in compliance with UBC Chapter 31. Thermal insulation shall not be installed within 3 inches of a recessed light fixture enclosure, or ballast and shall not be installed above the fixture as to trap heat. UBC Section 1718(d) A firefighting water supply is required (prior to any combustible construction) within 250 feet of all portions of the building (UFC Section 10.301(c) . Not less than one approved fire extinguisher with a rating of not less than 2-A: 10-B:C shall be provided for each 3,000 sq. ft. of floor area or fraction thereof. The travel distance to an extinguisher from any portion of the building shall not exceed 75 feet. UFC Standard No. 10-1 03-15-84, Page 2 Seven-Eleven Store One set of approved plans, specifications , and plan review shall be kept on the construction site where the work authorized thereby is in progress. UBC Section 303(b) Approval of submitted plans is not an approval of omissions or oversights by this office or of non-compliance with any applicable regulations of local government. This structure (or tenant space) has not received a final inspection and is NOT approved for occupancy. A member of Fire Prevention staff shall make framing and final inspection(s) of your new construction project. Please call for an appointment 24 hours prior to the time that you think that your project will be ready for one of the above noted inspections. Reinspection of violations written during one of the above inspections also will be required at the discretion of the inspector. Normal office hours for Fire District Inspectors are from 8:00 to 9:00 AM and from 4:30 to 5:00 PM. Inspection requests and questions should be made by phone during these hours only. Whenever possible please ask for the inspector you wish to talk to by name. If you desire a conference regarding this plan review or if you have questions, please contact Darrel Holmes at (503) 682-2601. Sincerely, Darrel Holmes Fire Prevention Bureau • TFFMZ260 OCCUPANCY FILE LIST MAR 19, 1984 11:03:39 TUALATIN R. F. P. D. PAGE 2 :a,FY INFORMATION> Assignment Code : R2258 :CONSTRUCTION INFORMATION> <FIRE PROTECTION INFORMATION) FMZ-Occupancy Number ---,-_- 1 1. Floor Construction : 2,CONCRETE 1. Hazard Class 901 : 512 253A-285-000 2. Floor Covering : 8,OTHER 2. UBC Occ Class 1 : B-2 3. Roof Construction : 2, W00D TRU 3. 2 Bus-Occ Name & Address 4. Roof Covering : 1, CLASSA/B 4. 3 5. Flue Type : NONE 5. 4 : SEVEN-ELEVEN STORE (NEW CONST) 6. Heating System Type : ELECTRIC 6. Heater Room Enclosed : N 2 SW PACIFIC HW TI 7. Interior Finish Type: 8,NONCOMBUST 7. Number of Stairs 0 `BASIC INFORMATION: B. Exterior Finish Type: 2,WOOD 8. Stairway Enclosed : N 9. Structure Columns WOOL 9. Number of Vert Shafts 0 1. Occupancy Phone : - - 10. Construction Type . V-N 10. Exits 2 Manager 's Name & Phone 11. Total square feet : 2700 11. Attic Stops : 0 12. Ground Area Sq Ft : 2700 12. Alarm Shutoff Loc : NONE --- 2. Bedford Properties 13. Basement sq ft : 0 13. Power Shutoff Loc I-NW 3. 503-257-0716 14. Building Height : 18 14. Water Shutoff Loc : NONE 15. Number of Stories : 1 15. Nat Gas Shutoff Loc : NONE Business Mailing Address 16. Building Value 76000 16. Fire Dept Conn Loc : NONE --- 17. Contents Value : 0 - 17. Sprinkler Control Loc : NONE 4. • 18. Other Value : 0 18. Type of Spr System : NONE 5. 6600 N. E. 78TH 19. Ins - Building 0 19. Number of Heads 0 6. Portland, Ore on 20. - Contents : 0 20. Sprinkler Supervised: N 21. Occupancy Square Ft : 2700 21. Hazard Classif : NONE Owner 's Name, Phone, & Address 22. Ceiling Type : SUSPENDED 22. Anti-Freeze System : N 23. Wall Framing 1 5 WOOD 23 Area Covered by Spr : 0 7. Bedford Properties 24. Stand Pipe Size 0 8.503-257-0716 25. Int/Ext Stand Pipe : NONE i 9. 26. Water Available : HYDRANT 10. 6600 N. E. 78th 27 Attic Access Loc : NONE 11. Portland, OR 97218 r •'SECURITY INFORMATION: 12. Property in Use : NO 13. ISO Class : 3 1. Alarm System Type : NONE 14. Census Tract : 319.02 2. Alarm Numb_er ---- NONE - 15. Code Edition Used : 12 3. Alam Comment Code NONE 16 Date Built : 02-28-84 4. Guard -Security Service : NONE 17. Date Remodeled - - 5. phone : NON-E - 18. Insp. Type/Month : INF /12 6. Watchman on Duty : N 19. Property Type : RETAIL STORE 7. phone : NON-E 20. Special Haz Type : NONE 8. Guard Dogs : N 21 Special Hazard Loc: NONE 9. Guard Dog Owner's Name : NONE 22. Misc. Number 1 1. 127 10. phone : NON-E - . _ _ _ . _'_=:<<<<<totai number. of occupancies listed is 2 >rn..,.,=:?.,,rn