Report (161) cepal)
mLA'(2_C 1oc-
COMcheck Software Version 4.0.7.1
Envelo a Com Dance Certificate
p p
RECEIVED
MAY 72018
Section 1: Project Information
CITY Oh 11GARO
Energy Code:2014 Oregon Energy Efficiency Specialty Code 3UIi_DING OiMMStON
Project Title:TTSD Templeton Elementary School
Project Type: New Construction
Envelope Compliance Method: Prescriptive David Moore Rebecca Grant
Tigard-Tualitin School District DOWA-IBI Group Architects
Construction Site: Owner/Agent: 6969 Sandburg St. Designer/Contractor: 907 SW Stark St
9500 S.W.Murdock St Tigard,OR 97223 Portland,OR 97205
Tigard,OR 97224
Building Location(for weather data): Tigard,Oregon
Climate Zone: 4c
Vertical Glazing/Wall Area Pct.: 24%
Building Type Area T e Floor Area
1-School/University:Nonresidential 74525
Educational Group E:Type V-B
Section 2: Envelope Assemblies and Requirements Checklist
Envelope PASSES
Envelope Assemblies:
R-Value Proposed Max.Allowed
Component Name/Description Cavity Cont. U-Factor SHGC U-Factor SHGC
Roof 1:Insulation Entirely Above Deck,[Bldg.Use 1 - --- 20.0 0.048 --- 0.048
School/University]
Exterior Wall 1:Wood-Framed,16"o.c.,[Bldg.Use 1 - 13.0 3.8 0.064 --- 0.064
School/University]
Window 1:Metal Frame with Thermal Break,Clear,[Bldg.Use 1 - --- --- 0.450 0.400 0.460 0.400
School/University]
Exterior Wall 2:Solid Concrete:8"Thickness,Light Density, --- 7.5 0.098 --- 0.150
Furring:None,[Bldg.Use 1 -School/University]
(a)Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
In the following requirements,blank checkboxes identify requirements that the applicant has not acknowledged as being met.Checkmarks
identify requirements that the applicant acknowledges are met or excepted from compliance. 'Plans reference page/section'identifies where in
the plans/specs the requirement can be verified as being satisfied.
Fenestration Product Rating:
yr 1. U-factors of fenestration products(windows,doors and skylights)are determined in accordance with NFRC 100 by an accredited,
independent laboratory,and labeled and certified by the manufacturer or are determined using the commercial size category values
listed in Chapter 15 of the 2009 ASHRAE Handbook of Fundamentals,Table No.4 and shall include the effects of the window frame.
The temporary label afixed to the fenestration products must not be removed prior to inspection.
Exception(s):
Site-built fenestration products shall have a single certificate specifying glazing type,special coatings,spacers,gas fills,
center-of-glass and overall U-factor,and center-of-glass SHGC for every type of site built glass used.These certificates shall be
maintained on the jobsite and made available to the inspector.
Plans reference page/section: Specification Section 08 80 00
g 2. Solar heat gain coefficient(SHGC)of glazed fenestration products(windows,glazed doors and skylights)shall be determined in
accordance with NFRC 200 by an accredited,independent laboratory,and labeled and certified by the manufacturer or be determined
using the Solar Heat Gain Coefficients(SHGC)in Chapter 15 of the 2009 ASHRAE Handbook of Fundamentals,Table No.10.The
overall values must consider type of frame material and operator for the SHGC at normal incidence.
Exception(s):
Project Title:TTSD Templeton Elementary School Report date:01/30/18
Data filename: Untitled.cck Page 1 of 3
U Site-built fenestration products shall have a single certificate specifying glazing type,special coatings,spacers,gas fills,
center-of-glass and overall U-factor,and center-of-glass SHGC for every type of site built glass used.These certificates shall be
maintained on the jobsite and made available to the inspector.
•
Specification Section 08 43 13
Plans reference page/section:
Air Leakage, Insulation, and Component Certification:
Li 3. Sealing of the building envelope.Openings and penetrations in the building envelope are sealed with caulking materials or closed with
gasketing systems compatible with the construction materials and location.Joints and seams are sealed in the same manner or taped
or covered with a moisture vapor-permeable wrapping material.Sealing materials spanning joints between construction materials allow
for expansion and contraction of the construction materials.
Plans reference page/section: Specification Section 07 25 00
g4. Window and door assemblies.The air leakage of window and sliding or swinging door assemblies that are part of the building envelope
are determined in accordance with AAMA/WDMA/CSA 101/I.S.2/A440,or NFRC 400 by an accredited,independent laboratory,and
labeled and certified by the manufacturer.
Exception(s):
p Site-constructed windows and doors that are weatherstripped or sealed in accordance with Section 502.4.3.
Plans reference page/section: Specification Section 08 43 13
3,5. Curtain wall,storefront glazing and commercial entrance doors.Curtain wall,storefront glazing and commercial-glazed swinging
entrance doors and revolving doors are tested for air leakage in accordance with ASTM E 283.For curtain walls and storefront glazing,
the maximum air leakage rate is 0.3 cubic foot per minute per square foot of fenestration area. For commercial glazed swinging
entrance doors and revolving doors,the maximum air leakage rate is 1.00 cfm/ft2 of door area.
Exception(s):
❑ Requirement is not applicable.
Plans reference page/section: Specification Section 08 43 13
6. Buildingthermal envelope insulation.An R-value identification mark is applied(bymanufacturer)to each piece of insulation 12
l� P PP
inches or greater in width.Alternately,the insulation installers have provided a signed,dated and posted certification listing the type,
manufacturer and R-value of insulation installed.Refer to code section for blown or sprayed insulation installation/settling depths and
marker requirements.
g7. Insulation mark installation. Insulating materials are installed such that the manufacturer's R-value mark is readily observable upon
inspection.
g8. Insulation product rating.The thermal resistance(R-value)of insulation has been determined in accordance with the U.S.FTC R-value
rule.
g9. Installation.All material,systems and equipment are installed in accordance with the manufacturer's installation instructions and the
International Building Code.
• 10.Outdoor air intakes and exhaust openings.Stair and elevator shaft vents and other outdoor air intakes and exhaust openings integral
to the building envelope shall be equipped with not less than a Class I motorized,leakage-rated damper with a maximum leakage rate
of 4 cfm per square foot at 1.0 inch water gauge when tested in accordance with AMCA 500D.Stair and shaft vent dampers shall be
capable of being automatically closed during normal building operation and interlocked to open as required by fire and smoke detection
systems.
Exception(s):
0 Requirement is not applicable.
Plans reference page/section: N//4
• 11.Loading dock weatherseals.Cargo doors and loading dock doors are equipped with weather seals to restrict infiltration when vehicles
are parked in the doorway.
Exception(s):
0 Requirement is not applicable.
Plans reference page/section: N/A
• 12.Recessed lighting. Recessed luminaires installed in the building thermal envelope are sealed to limit air leakage between conditioned
and unconditioned spaces.All recessed luminaires are IC-rated and labeled as meeting ASTM E 283.All recessed luminaires are
sealed with a gasket or caulk between the housing and interior wall or ceiling covering.
Exception(s):
Li Requirement is not applicable.
Plans reference page/section: N/A
13.Vestibules.Doors that separate conditioned space from the exterior are protected with an enclosed vestibule,with all doors of the
vestibule equipped with self-closing devices.Vestibules are designed so interior and exterior doors to not operate simultaneously.
Project Title:TTSD Templeton Elementary School Report date: 01/30/18
Data filename: Untitled.cck Page 2 of 3
Exception(s):
U Doors not intended to be used as a building entrance door,such as doors to mechanical or electrical equipment rooms.
Doors opening directly from a sleeping unit or dwelling unit.
p Doors that open directly from a space less than 3000 sq.ft.in area.
Revolving doors.
0 Doors used primarily to facilitate vehicular movement or material handling and adjacent personnel doors.
:I Requirement is not applicable.
Plans reference page/section: Drawings A2.10, A2.13
14.0ther components have supporting documentation for proposed U-Factors.
Exception(s):
p Requirement is not applicable.
Plans reference page/section:
Section 3: Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans,specifications and
other calculations submitted with this permit application.The proposed envelope system has been designed to meet the 2014 Oregon Energy
Efficiency Specialty Code requirements in COMcheck Version 4.0.7.1 and to comply with the mandatory requirements in the Requirements
Checklist.
1ij r��
Rebecca Grant, Principal 02.09.18
Name-Title Signature Date
Project Title:TTSD Templeton Elementary School Report date:01/30/18
Data filename: Untitled.cck Page 3 of 3
COM check Software Version 4.0.7.1
Envelope Compliance Certificate
RECEIVED
Section 1: Project Information MAY 7 2018
Energy Code:2014 Oregon Energy Efficiency Specialty Code CITY OF TI GARD
Project Title:TTSD Templeton Elementary School BUILDING DIVISION
Project Type: New Construction
Envelope Compliance Method: Prescriptive David Moore Rebecca Grant
Tigard-Tualitin School District DOWA-IBI Group Architects
Construction Site: Owner/Agent: 6969 Sandburg St. Designer/Contractor: 907 SW Stark St
9500 S.W. Murdock St Tigard,OR 97223 Portland,OR 97205
Tigard,OR 97224
Building Location(for weather data): Tigard,Oregon
Climate Zone: 4c
Vertical Glazing/Wall Area Pct.: 24%
Building Use:Area Type Floor Area
1-School/University:Nonresidential 74525
Educational Group E:Type V-B
Section 2: Envelope Assemblies and Requirements Checklist
Envelope PASSES
Envelope Assemblies:
R-Value Proposed Max.Allowed
Component Name/Description Cavity Cont. U-Factor SHGC U-Factor SHGC
Roof 1:Insulation Entirely Above Deck,[Bldg. Use 1 - --- 20.0 0.048 --- 0.048
School/University]
Exterior Wall 1:Wood-Framed,16"o.c.,[Bldg.Use 1 - 13.0 3.8 0.064 --- 0.064
School/University]
Window 1:Metal Frame with Thermal Break,Clear,[Bldg.Use 1 - --- --- 0.450 0.400 0.460 0.400
School/University]
Exterior Wall 2:Solid Concrete:8"Thickness,Light Density, --- 7.5 0.098 --- 0.150
Furring:None,[Bldg.Use 1 -School/University]
(a)Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
In the following requirements,blank checkboxes identify requirements that the applicant has not acknowledged as being met. Checkmarks
identify requirements that the applicant acknowledges are met or excepted from compliance. 'Plans reference page/section'identifies where in
the plans/specs the requirement can be verified as being satisfied.
Fenestration Product Rating:
Nr 1. U-factors of fenestration products(windows,doors and skylights)are determined in accordance with NFRC 100 by an accredited,
independent laboratory,and labeled and certified by the manufacturer or are determined using the commercial size category values
listed in Chapter 15 of the 2009 ASHRAE Handbook of Fundamentals,Table No.4 and shall include the effects of the window frame.
The temporary label afixed to the fenestration products must not be removed prior to inspection.
Exception(s):
5d Site-built fenestration products shall have a single certificate specifying glazing type,special coatings,spacers,gas fills,
center-of-glass and overall U-factor,and center-of-glass SHGC for every type of site built glass used.These certificates shall be
maintained on the jobsite and made available to the inspector.
Plans reference page/section: Specification Section 08 80 00
2. Solar heat gain coefficient(SHGC)of glazed fenestration products(windows,glazed doors and skylights)shall be determined in
accordance with NFRC 200 by an accredited,independent laboratory,and labeled and certified by the manufacturer or be determined
using the Solar Heat Gain Coefficients(SHGC)in Chapter 15 of the 2009 ASHRAE Handbook of Fundamentals,Table No.10.The
overall values must consider type of frame material and operator for the SHGC at normal incidence.
Exception(s):
Project Title:TTSD Templeton Elementary School Report date:01/30/18
Data filename: Untitled.cck Page 1 of 3
1
❑ Site-built fenestration products shall have a single certificate specifying glazing type,special coatings,spacers,gas fills,
center-of-glass and overall U-factor,and center-of-glass SHGC for every type of site built glass used.These certificates shall be
maintained on the jobsite and made available to the inspector.
Plans reference page/section: Specification Section 08 43 13
Air Leakage, Insulation, and Component Certification:
❑ 3. Sealing of the building envelope.Openings and penetrations in the building envelope are sealed with caulking materials or closed with
gasketing systems compatible with the construction materials and location.Joints and seams are sealed in the same manner or taped
or covered with a moisture vapor-permeable wrapping material.Sealing materials spanning joints between construction materials allow
for expansion and contraction of the construction materials.
Plans reference page/section: Specification Section 07 25 00
g4. Window and door assemblies.The air leakage of window and sliding or swinging door assemblies that are part of the building envelope
are determined in accordance with AAMA/WDMA/CSA 101/I.S.2/A440,or NFRC 400 by an accredited,independent laboratory,and
labeled and certified by the manufacturer.
Exception(s):
❑ Site-constructed windows and doors that are weatherstripped or sealed in accordance with Section 502.4.3.
Plans reference page/section: Specification Section 08 43 13
Y5. Curtain wall,storefront glazing and commercial entrance doors.Curtain wall,storefront glazing and commercial-glazed swinging
entrance doors and revolving doors are tested for air leakage in accordance with ASTM E 283. For curtain walls and storefront glazing,
the maximum air leakage rate is 0.3 cubic foot per minute per square foot of fenestration area.For commercial glazed swinging
entrance doors and revolving doors,the maximum air leakage rate is 1.00 cfm/ft2 of door area.
Exception(s):
❑ Requirement is not applicable.
Plans reference page/section: Specification Section 08 43 13
g 6. Building thermal envelope insulation.An R-value identification mark is applied(by manufacturer)to each piece of insulation 12
inches or greater in width.Alternately,the insulation installers have provided a signed,dated and posted certification listing the type,
manufacturer and R-value of insulation installed.Refer to code section for blown or sprayed insulation installation/settling depths and
marker requirements.
g7. Insulation mark installation. Insulating materials are installed such that the manufacturer's R-value mark is readily observable upon
inspection.
[t8. Insulation product rating.The thermal resistance(R-value)of insulation has been determined in accordance with the U.S.FTC R-value
rule.
[$9. Installation.All material,systems and equipment are installed in accordance with the manufacturer's installation instructions and the
International Building Code.
❑ 10.Outdoor air intakes and exhaust openings.Stair and elevator shaft vents and other outdoor air intakes and exhaust openings integral
to the building envelope shall be equipped with not less than a Class I motorized,leakage-rated damper with a maximum leakage rate
of 4 cfm per square foot at 1.0 inch water gauge when tested in accordance with AMCA 500D.Stair and shaft vent dampers shall be
capable of being automatically closed during normal building operation and interlocked to open as required by fire and smoke detection
systems.
Exception(s):
❑ Requirement is not applicable.
Plans reference page/section: NSA
❑ 11.Loading dock weatherseals.Cargo doors and loading dock doors are equipped with weather seals to restrict infiltration when vehicles
are parked in the doorway.
Exception(s):
❑ Requirement is not applicable.
Plans reference page/section: N/A
❑ 12.Recessed lighting. Recessed luminaires installed in the building thermal envelope are sealed to limit air leakage between conditioned
and unconditioned spaces.All recessed luminaires are IC-rated and labeled as meeting ASTM E 283.All recessed luminaires are
sealed with a gasket or caulk between the housing and interior wall or ceiling covering.
Exception(s):
❑ Requirement is not applicable.
Plans reference page/section: N/A
13.Vestibules.Doors that separate conditioned space from the exterior are protected with an enclosed vestibule,with all doors of the
vestibule equipped with self-closing devices.Vestibules are designed so interior and exterior doors to not operate simultaneously.
Project Title:TTSD Templeton Elementary School Report date:01/30/18
Data filename: Untitled.cck Page 2 of 3
Exception(s):
I] Doors not intended to be used as a building entrance door,such as doors to mechanical or electrical equipment rooms.
• Doors opening directly from a sleeping unit or dwelling unit.
U Doors that open directly from a space less than 3000 sq.ft.in area.
1J Revolving doors.
O Doors used primarily to facilitate vehicular movement or material handling and adjacent personnel doors.
• Requirement is not applicable.
Plans reference page/section: Drawings A2.10, A2.13
14.'Other'components have supporting documentation for proposed U-Factors.
Exception(s):
J Requirement is not applicable.
Plans reference page/section:
Section 3: Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans,specifications and
other calculations submitted with this permit application.The proposed envelope system has been designed to meet the 2014 Oregon Energy
Efficiency Specialty Code requirements in COMcheck Version 4.0.7.1 and to comply with the mandatory requirements in the Requirements
Checklist.
11 r�i
Rebecca Grant, Principal 02.09.18
Name-Title Signature Date
Project Title:TTSD Templeton Elementary School Report date:01/30/18
Data filename: Untitled.cck Page 3 of 3
I .
, ,Lei
COMcheck Software Version 4.0.8.1
Interior Lighting Compliance
Certificate
Section 1: Project Information
Energy Code:2014 Oregon Energy Efficiency Specialty Code
Project Title:TTSD Templeton Elementary School
Project Type: New Construction
Construction Site: Owner/Agent: Designer/Contractor:
9500 S.W.Murdock St
Tigard,OR 97224
Section 2: Interior Lighting and Power Calculation
A B C D
Floor Area Allowed Allowed Watts
Watts/ft2
School/University 81280 1.01 82093
Total Allowed Watts= 82093
Section 3: Interior Lighting Fixture Schedule
A B C D E
Fixture ID: Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
School/University(81280 sq.ft.)
LED 1:L1:LED Linear 17W: 1 734 16 11744
LED 2:L2:LED Linear 8W: 1 908 5 4540
LED 3:L3:LED Other Fixture Unit 36W: 1 85 40 3400
LED 4:L4:Other: 1 18 49 882
LED 5:L5:LED Other Fixture Unit 28W: 1 24 26 624
LED 6:L6:LED Other Fixture Unit 36W: 1 15 35 525
LED 7:L6A:LED Other Fixture Unit 25W: 1 61 18 1098
LED 8:L7:LED Other Fixture Unit 36W: 1 75 30 2250
LED 9:L8:Other: 1 12 158 1896
LED 10:L9:LED Other Fixture Unit 16W: 1 115 15 1725
LED 11:L10:LED Linear 8W: 1 24 5 120
LED 12:L11:LED Other Fixture Unit 36W: 1 10 29 290
LED 13:L11 A:LED Other Fixture Unit 50W: 1 9 49 441
LED 14:L12:LED Other Fixture Unit 60W: 1 17 59 1003
LED 15:L12A:LED Other Fixture Unit 103W: 1 11 90 990
LED 16:L13:LED Other Fixture Unit 36W: 1 20 29 580
LED 17:L14:LED Other Fixture Unit 13W: 1 3 10 30
LED 18:L15:LED Other Fixture Unit 36W: 1 4 30 120
LED 19:T1:LED Other Fixture Unit 25W: 1 11 23 253
LED 20:T2:LED Other Fixture Unit 25W: 1 10 23 230
Total Proposed Watts= 32741
Section 4: Requirements Checklist
In the following requirements,blank checkboxes identify requirements that the applicant has not acknowledged as being met. Checkmarks
identify requirements that the applicant acknowledges are met or excepted from compliance. 'Plans reference page/section'identifies where in
the plans/specs the requirement can be verified as being satisfied.
Lighting Wattage:
v 1. Total proposed watts must be less than or equal to total allowed watts.
Project Title:TTSD Templeton Elementary School Report date: 02/06/18
Data filename:P:\2016\16-1920-TTSD Templeton Elementary\12 Codes and Stnds\Compliance Forms\Templeton Lighting
Compliance.cck Page 1 of 5
Allowed Wattage:82093 Proposed Wattage:32741
Complies:YES
Mandatory Requirements:
✓ 2. Exit signs.Internally illuminated exit signs shall not exceed 5 watts per side.
Plans reference page/section: E0.02.
`/ 3. Daylight zone control.All daylight zones are provided with individual controls that control the lights independent of general area lighting
in the non-daylight zone.In all individual daylight zones larger than 350 sq.ft.,automatic daylight controls is provided.Automatic
daylight sensing controls reduce the light output of the controlled luminaires at least 50 percent,and provide an automatic OFF control,
while maintaining a uniform level of illumination.Contiguous daylight zones adjacent to vertical fenestration may be controlled by a
single controlling device provided that they do not include zones facing more than two adjacent cardinal orientations(i.e.,north,east,
south,west).Daylight zones under skylights shall be controlled separately from daylight zones adjacent to vertical fenestration.
• Exception applies:Spaces required to have occupancy sensors.
Plans reference page/section: E2.10-E2.21.
v 4. Interior lighting controls.At least one local shutoff lighting control has been provided for every 2,000 square feet of lit floor area and
each area enclosed by walls or floor-to-ceiling partitions.The required controls are located within the area served by the controls or are
a remote switch that identifies the lights served and indicates their status.
Plans reference page/section: E2.10-E2.21.
✓ 5. Sleeping unit controls.Master switch at entry to hotel/motel guest room.
Plans reference page/section: N/A -No sleeping units.
✓ 6. Egress lighting.Egress illumination is controlled by a combination of listed emergency relay and occupancy sensors to shut off during
periods that the building space served by the means of egress is unoccupied.
Plans reference page/section: E2.10-E2.21. Specifications.
✓ 7. Additional controls.Each area that is required to have a manual control shall have additional controls that meet the requirements of
Sections 505.2.2.1 and 505.2.2.2.
Plans reference page/section: E2.10-E2.21.
✓ 8. Light reduction controls.Each space required to have a manual control also allows for reducing the connected lighting load by at least
50 percent by either
1)controlling(dimming or multi-level switching)all luminaires;or
2)dual switching of alternate rows of luminaires,alternate luminaires,or alternate lamps;or
3)switching the middle lamp luminaires independently of other lamps;or
4)switching each luminaire or each lamp.
• Exception applies: Electrical and mechanical room.
Plans reference page/section: E2.10-E2.21
✓ 9. Buildings larger than 2,000 square feet are equipped with an automatic control device to shut off lighting in those areas.This automatic
control device shall function on either:
1)a scheduled basis,using time-of-day,with an independent program schedule that controls the interior lighting in areas that do not
exceed 10,000 square feet and are not more than one floor;or
2)an occupant sensor that shall turn lighting off within 30 minutes of an occupant leaving a space;or
3)a signal from another control or alarm system that indicates the area is unoccupied.
• Exception applies:Sleeping units,patient care areas;and spaces where automatic shutoff would endanger safety or security.
Plans reference page/section: E2.10-E2.21.
✓ 10.Occupancy sensors in rooms that include daylight zones are required to have Manual ON activation.
Plans reference page/section: E2.10-E2.21.
`/ 11.An occupant sensor control device is installed that automatically turns lighting off within 30 minutes of all occupants leaving a space.
Plans reference page/section: E2.10-E2.21. Specifications.
`/ 12.Additional controls.An occupant sensor control device that automatically turns lighting off within 30 minutes of all occupants leaving a
space or a locally activated switch that automatically turns lighting off within 30 minutes of being activated is installed in all storage and
supply rooms up to 1000 square feet.
Plans reference page/section: E2.10-E2.21.
✓ 13.Occupant override.Automatic lighting shutoff operating on a time-of-day scheduled basis incorporates an override switching device
that:1)is readily accessible,2)is located so that a person using the device can see the lights or the area controlled by that switch,or
so that the area being lit is annunciated,3)is manually operated,4)allows the lighting to remain on for no more than 2 hours when an
override is initiated,and 5)controls an area not exceeding 2,000 square feet.
Project Title: TTSD Templeton Elementary School Report date: 02/06/18
Data filename:P:\2016\16-1920-TTSD Templeton Elementary\12 Codes and Stnds\Compliance Forms\Templeton Lighting
Compliance.cck Page 2 of 5
Plans reference page/section: E2.10-E2.21. Specifications.
✓ 14.Holiday scheduling.Automatic lighting shutoff operating on a time-of-day scheduled basis has an automatic holiday scheduling feature
that turns off all loads for at least 24 hours,then resumes the normally scheduled operation.
Plans reference page/section: N/A
✓ 15.Exterior lighting controls.Lighting not designated for dusk-to-dawn operation shall be controlled by either a combination of a
photosensor and a time switch,or an astronomical time switch.Lighting designated for dusk-to-dawn operation shall be controlled by
an astronomical time switch or photosensor.
Plans reference page/section: E2.10-E2.21.
✓ 16.Tandem wiring.The following luminaires located within the same area shall be tandem wired:
1.Fluorescent luminaires equipped with one,three or odd-numbered lamp configurations,that are recess-mounted within 10 feet
center-to-center of each other.
2.Fluorescent luminaires equipped with one,three or any odd-numbered lamp configuration,that are pendant-or surface-mounted
within 1 foot edge-to-edge of each other.
Plans reference page/section: N/A
`/ 17.Medical task lighting or art/history display lighting claimed to be exempt from compliance has a control device independent of the control
of the nonexempt lighting.
Plans reference page/section: N/A
`/ 18.Each dwelling unit in a building is metered separately.
Plans reference page/section: N/A
Interior Lighting PASSES:Design 60%better than code.
Section 5: Compliance Statement
Compliance Statement: The proposed lighting design represented in this document is consistent with the building plans,specifications and
other calculations submitted with this permit application.The proposed lighting system has been designed to meet the 2014 Oregon Energy
Efficiency Specialty Code requirements in COMcheck Version 4.0.8.1 and to comply with the .ndatory requirements in the Requirements
Checklist. II
EWMichael Lopez, PE, Lead Engineer. 2/8/2018
Name-Title Signature Date
Project Title:TTSD Templeton Elementary School Report date: 02/06/18
Data filename:P:\2016\16-1920-TTSD Templeton Elementary\12 Codes and Stnds\Compliance Forms\Templeton Lighting
Compliance.cck Page 3 of 5
COMcheck Software Version 4.0.8.1
Exterior Lighting Compliance
Certificate
Section 1: Project Information
Energy Code:2014 Oregon Energy Efficiency Specialty Code
Project Title:TTSD Templeton Elementary School
Project Type: New Construction
Exterior Lighting Zone: 2(Residential mixed use area)
Construction Site: Owner/Agent: Designer/Contractor:
9500 S.W.Murdock St
Tigard,OR 97224
Section 2: Exterior Lighting Area/Surface Power Calculation
A B C D E F
Exterior Area/Surface Quantity Allowed Tradable Allowed Proposed
Watts Wattage Watts Watts
/Unit (B x C)
E2.10 Canopy(Entry canopy) 1200 ft2 0.25 Yes 300 550
E2.13 Canopy(Entry canopy) 1180 ft2 0.25 Yes 295 800
E2.13 Covered Play(Special feature area) 3728 ft2 0.14 Yes 522 576
E2.20 Entry Canopy(Entry canopy) 350 ft2 0.25 Yes 88 192
E0.11 South Building Parking(Parking area) 4836 ft2 0.06 Yes 290 280
E0.11 South/West Driveway(Driveway) 31835 ft2 0.06 Yes 1910 560
E0.11 North/West Parking(Parking area) 39238 ft2 0.06 Yes 2354 700
E0.11 North/East Parking(Parking area) 25030 ft2 0.06 Yes 1502 630
E0.11 North/West Walkways(Walkway<10 feet wide) 1524 ft of walkway length 0.7 Yes 1067 832
E0.11 West Facad/Service Yard(Illuminated length of 385 ft 2.5 No 963 330
facade wall/surface or roof path)
E2.10 Main Entry(Main entry) 13 ft of door width 20 Yes 260 620
E0.11 East Facade(Illuminated length of facade 297 ft 2.5 No 743 186
wall/surface or roof path)
Total Tradable Watts*= 8588 5740
Total Allowed Watts= 10293
Total Allowed Supplemental Watts**= 600
*Wattage tradeoffs are only allowed between tradable areas/surfaces.
**A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Section 3: Exterior Lighting Fixture Schedule
A B C D E
Fixture ID:Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
E2.10 Canopy(Entry canopy 1200 ft2):Tradable Wattage
LED 1:51:LED Linear 8W: 1 110 5 550
E2.10 Main Entry(Main entry 13 ft of door width):Tradable Wattage
LED 13:51:LED Linear 8W: 1 124 5 620
E2.13 Canopy(Entry canopy 1180 ft2):Tradable Wattage
LED 2:51:LED Linear 8W: 1 160 5 800
E2.13 Covered Play(Special feature area 3728 ft2):Tradable Wattage
LED 3:S6:LED Roadway-Parking Unit 54W: 1 12 48 576
E2.20 Entry Canopy(Entry canopy 350 ft2):Tradable Wattage
LED 4:S6:LED Other Fixture Unit 50W: 1 4 48 192
E0.11 South Building Parking(Parking area 4836 ft2):Tradable Wattage
Project Title:TTSD Templeton Elementary School Report date: 02/06/18
Data filename:P:\2016\16-1920-TTSD Templeton Elementary\12 Codes and Stnds\Compliance Forms\Templeton Lighting
Comoliance.cck Page 4 of 5
LED 5:S3:LED Other Fixture Unit 80W: 1 4 70 280
E0.^11 South/West Driveway(Driveway 31835 ft2):Tradable Wattage
LED 6:S3:LED Other Fixture Unit 80W: 1 8 70 560
E0.11 North/West Parking(Parking area 39238 ft2):Tradable Wattage
LED 7:S3:LED Other Fixture Unit 80W: 1 10 70 700
E0.11 North/East Parking(Parking area 25030 ft2):Tradable Wattage
LED 8:S3:LED Other Fixture Unit 60W: 1 9 70 630
E0.11 North/West Walkways(Walkway<10 feet wide 1524 ft of walkway length):Tradable Wattage
LED 9:S3:LED Other Fixture Unit 80W: 1 6 70 420
LED 10:S5:LED Other Fixture Unit 80W: 1 4 70 280
LED 11:S9:LED Other Fixture Unit 60W: 1 2 54 108
LED 12:S2:LED Other Fixture Unit 25W: 1 1 24 24
E0.11 West Facad/Service Yard(Illuminated length of facade wall/surface or roof path 385 ft):Non-tradable Wattage
LED 14:S2:LED Other Fixture Unit 25W: 1 7 24 168
LED 15:S9:LED Other Fixture Unit 60W: 1 3 54 162
E0.11 East Facade(Illuminated length of facade wall/surface or roof path 297 ft):Non-tradable Wattage
LED 16:S2:LED Other Fixture Unit 25W: 1 3 24 72
LED 17:S9:LED Other Fixture Unit 60W: 1 2 54 108
LED 18:S7:LED Other Fixture Unit 6.5W: 1 1 6 6
Total Tradable Proposed Watts= 5740
Section 4: Requirements Checklist
In the following requirements,blank checkboxes identify requirements that the applicant has not acknowledged as being met.Checkmarks
identify requirements that the applicant acknowledges are met or excepted from compliance. 'Plans reference page/section'identifies where in
the plans/specs the requirement can be verified as being satisfied.
Controls, Switching, and Wiring:
1. Lighting designated to operate more than 2000 hours per year for Uncovered Parking Areas shall be equipped with motion sensors that
will reduce the luminaire power by thirty-three percent or turn off one-third the luminaires when no activity is detected.
Plans reference page/section: Specifications.
Exterior Lighting Restrictions and Exceptions:
`/ 2. Mercury vapor and incandescent lighting is not permitted for use as exterior lighting.
v 3. Exempt lighting fixtures are equipped with a control device independent of the control of the nonexempt lighting and are identified in
Section 3 table above.
Plans reference page/section: N/A
Section 5: Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,specifications
and other calculations submitted with this permit application.The proposed lighting system has been designed to meet the 2014 Oregon
Energy Efficiency Specialty Code requirements in COMcheck Version 4.0.8.1 and to comply w the mandatory requirements in the
Requirements Checklist.
Michael Lopez, PE, Lead Engineer. 2/8/2018
Name-Title Signature Date
Project Title:TTSD Templeton Elementary School Report date: 02/06/18
Data filename:P:\2016\16-1920-TTSD Templeton Elementary\12 Codes and Stnds\Compliance Forms\Templeton Lighting
Compliance.cck Pape 5 of 5
(1111 COMcheck Software Version 4.0.8.1
Interior Lighting Compliance
Certificate
Section 1: Project Information
Energy Code:2014 Oregon Energy Efficiency Specialty Code
Project Title:TTSD Templeton Elementary School
Project Type: New Construction
Construction Site: Owner/Agent: Designer/Contractor:
9500 S.W.Murdock St
Tigard,OR 97224
Section 2: Interior Lighting and Power Calculation
A B C D
Floor Area Allowed Allowed Watts
Watts/ft2
School/University 81280 1.01 82093
Total Allowed Watts= 82093
Section 3: Interior Lighting Fixture Schedule
A B C D E
Fixture ID:Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
School/University(81280 sq.ft.)
LED 1:L1:LED Linear 17W: 1 734 16 11744
LED 2:L2:LED Linear 8W: 1 908 5 4540
LED 3:L3:LED Other Fixture Unit 36W: 1 85 40 3400
LED 4:L4:Other: 1 18 49 882
LED 5:L5:LED Other Fixture Unit 28W: 1 24 26 624
LED 6:L6:LED Other Fixture Unit 36W: 1 15 35 525
LED 7:L6A:LED Other Fixture Unit 25W: 1 61 18 1098
LED 8:L7:LED Other Fixture Unit 36W: 1 75 30 2250
LED 9:L8:Other: 1 12 158 1896
LED 10:L9:LED Other Fixture Unit 16W: 1 115 15 1725
LED 11:L10:LED Linear 8W: 1 24 5 120
LED 12:L11:LED Other Fixture Unit 36W: 1 10 29 290
LED 13:L11 A:LED Other Fixture Unit 50W: 1 9 49 441
LED 14:L12:LED Other Fixture Unit 60W: 1 17 59 1003
LED 15:L12A:LED Other Fixture Unit 103W: 1 11 90 990
LED 16:L13:LED Other Fixture Unit 36W: 1 20 29 580
LED 17:L14:LED Other Fixture Unit 13W: 1 3 10 30
LED 18:L15:LED Other Fixture Unit 36W: 1 4 30 120
LED 19:T1:LED Other Fixture Unit 25W: 1 11 23 253
LED 20:T2:LED Other Fixture Unit 25W: 1 10 23 230
Total Proposed Watts= 32741
Section 4: Requirements Checklist
In the following requirements,blank checkboxes identify requirements that the applicant has not acknowledged as being met. Checkmarks
identify requirements that the applicant acknowledges are met or excepted from compliance. 'Plans reference page/section'identifies where in
the plans/specs the requirement can be verified as being satisfied.
Lighting Wattage:
v 1. Total proposed watts must be less than or equal to total allowed watts.
Project Title:TTSD Templeton Elementary School Report date: 02/06/18
Data filename:P:\2016\16-1920-TTSD Templeton Elementary\12 Codes and Stnds\Compliance Forms\Templeton Lighting
Compliance.cck Page 1 of 5
Allowed Wattage:82093 Proposed Wattage:32741
Complies:YES
Mandatory Requirements:
v 2. Exit signs.Internally illuminated exit signs shall not exceed 5 watts per side.
Plans reference page/section: E0.02.
v 3. Daylight zone control.All daylight zones are provided with individual controls that control the lights independent of general area lighting
in the non-daylight zone.In all individual daylight zones larger than 350 sq.ft.,automatic daylight controls is provided.Automatic
daylight sensing controls reduce the light output of the controlled luminaires at least 50 percent,and provide an automatic OFF control,
while maintaining a uniform level of illumination.Contiguous daylight zones adjacent to vertical fenestration may be controlled by a
single controlling device provided that they do not include zones facing more than two adjacent cardinal orientations(i.e.,north,east,
south,west).Daylight zones under skylights shall be controlled separately from daylight zones adjacent to vertical fenestration.
Exception applies:Spaces required to have occupancy sensors.
Plans reference page/section: E2.10-E2.21.
✓ 4. Interior lighting controls.At least one local shutoff lighting control has been provided for every 2,000 square feet of lit floor area and
each area enclosed by walls or floor-to-ceiling partitions.The required controls are located within the area served by the controls or are
a remote switch that identifies the lights served and indicates their status.
Plans reference page/section: E2.10-E2.21.
v 5. Sleeping unit controls.Master switch at entry to hotel/motel guest room.
Plans reference page/section: N/A -No sleeping units.
v 6. Egress lighting.Egress illumination is controlled by a combination of listed emergency relay and occupancy sensors to shut off during
periods that the building space served by the means of egress is unoccupied.
Plans reference page/section: E2.10-E2.21. Specifications.
✓ 7. Additional controls.Each area that is required to have a manual control shall have additional controls that meet the requirements of
Sections 505.2.2.1 and 505.2.2.2.
Plans reference page/section: E2.10-E2.21.
/ 8. Light reduction controls.Each space required to have a manual control also allows for reducing the connected lighting load by at least
50 percent by either
1)controlling(dimming or multi-level switching)all luminaires;or
2)dual switching of alternate rows of luminaires,alternate luminaires,or alternate lamps;or
3)switching the middle lamp luminaires independently of other lamps;or
4)switching each luminaire or each lamp.
• Exception applies:Electrical and mechanical room.
Plans reference page/section: E2.10-E2.21
v 9. Buildings larger than 2,000 square feet are equipped with an automatic control device to shut off lighting in those areas.This automatic
control device shall function on either:
1)a scheduled basis,using time-of-day,with an independent program schedule that controls the interior lighting in areas that do not
exceed 10,000 square feet and are not more than one floor;or
2)an occupant sensor that shall turn lighting off within 30 minutes of an occupant leaving a space;or
3)a signal from another control or alarm system that indicates the area is unoccupied.
• Exception applies:Sleeping units,patient care areas;and spaces where automatic shutoff would endanger safety or security.
Plans reference page/section: E2.10- E2.21.
✓ 10.Occupancy sensors in rooms that include daylight zones are required to have Manual ON activation.
Plans reference page/section: E2.10- E2.21.
`/ 11.An occupant sensor control device is installed that automatically turns lighting off within 30 minutes of all occupants leaving a space.
Plans reference page/section: E2.10-E2.21. Specifications.
✓ 12.Additional controls.An occupant sensor control device that automatically turns lighting off within 30 minutes of all occupants leaving a
space or a locally activated switch that automatically turns lighting off within 30 minutes of being activated is installed in all storage and
supply rooms up to 1000 square feet.
Plans reference page/section: E2.10-E2.21.
✓ 13.Occupant override.Automatic lighting shutoff operating on a time-of-day scheduled basis incorporates an override switching device
that:1)is readily accessible,2)is located so that a person using the device can see the lights or the area controlled by that switch,or
so that the area being lit is annunciated,3)is manually operated,4)allows the lighting to remain on for no more than 2 hours when an
override is initiated,and 5)controls an area not exceeding 2,000 square feet.
Project Title:TTSD Templeton Elementary School Report date: 02/06/18
Data filename:P:\2016\16-1920-TTSD Templeton Elementary\12 Codes and Stnds\Compliance Forms\Templeton Lighting
Compliance.cck Page 2 of 5
` Mans reference page/section: E2.10-E2.21. Specifications.
✓ 14.Holiday scheduling.Automatic lighting shutoff operating on a time-of-day scheduled basis has an automatic holiday scheduling feature
that turns off all loads for at least 24 hours,then resumes the normally scheduled operation.
Plans reference page/section: N/A
`/ 15.Exterior lighting controls.Lighting not designated for dusk-to-dawn operation shall be controlled by either a combination of a
photosensor and a time switch,or an astronomical time switch.Lighting designated for dusk-to-dawn operation shall be controlled by
an astronomical time switch or photosensor.
Plans reference page/section: E2.10-E2.21.
✓ 16.Tandem wiring.The following luminaires located within the same area shall be tandem wired:
1.Fluorescent luminaires equipped with one,three or odd-numbered lamp configurations,that are recess-mounted within 10 feet
center-to-center of each other.
2.Fluorescent luminaires equipped with one,three or any odd-numbered lamp configuration,that are pendant-or surface-mounted
within 1 foot edge-to-edge of each other.
Plans reference page/section: N/A
✓ 17.Medical task lighting or art/history display lighting claimed to be exempt from compliance has a control device independent of the control
of the nonexempt lighting.
Plans reference page/section: N/A
18.Each dwelling unit in a building is metered separately.
Plans reference page/section: N/A
Interior Lighting PASSES:Design 60%better than code.
Section 5: Compliance Statement
Compliance Statement The proposed lighting design represented in this document is consistent with the building plans,specifications and
other calculations submitted with this permit application.The proposed lighting system has been designed to meet the 2014 Oregon Energy
Efficiency Specialty Code requirements in COMcheck Version 4.0.8.1 and to comply with theAif.ndatory requirements in the Requirements
Checklist.
Michael Lopez, PE, Lead Engineer. r 2/8/2018
Adi
Name-Title Signature Date
Project Title:TTSD Templeton Elementary School Report date: 02/06/18
Data filename:P:\2016\16-1920-TTSD Templeton Elementary\12 Codes and Stnds\Compliance Forms\Templeton Lighting
Compliance.cck Page 3 of 5
COMcheck Software Version 4.0.8.1
iluld/'
Exterior Lighting Compliance
Certificate
Section 1: Project Information
Energy Code:2014 Oregon Energy Efficiency Specialty Code
Project Title:TTSD Templeton Elementary School
Project Type: New Construction
Exterior Lighting Zone: 2(Residential mixed use area)
Construction Site: Owner/Agent: Designer/Contractor:
9500 S.W.Murdock St
Tigard,OR 97224
Section 2: Exterior Lighting Area/Surface Power Calculation
A B C D E F
Exterior Area/Surface Quantity Allowed Tradable Allowed Proposed
Watts Wattage Watts Watts
/Unit (B x C)
E2.10 Canopy(Entry canopy) 1200 ft2 0.25 Yes 300 550
E2.13 Canopy(Entry canopy) 1180 ft2 0.25 Yes 295 800
E2.13 Covered Play(Special feature area) 3728 ft2 0.14 Yes 522 576
E2.20 Entry Canopy(Entry canopy) 350 ft2 0.25 Yes 88 192
E0.11 South Building Parking(Parking area) 4836 ft2 0.06 Yes 290 280
E0.11 South/West Driveway(Driveway) 31835 ft2 0.06 Yes 1910 560
E0.11 North/West Parking(Parking area) 39238 ft2 0.06 Yes 2354 700
E0.11 North/East Parking(Parking area) 25030 ft2 0.06 Yes 1502 630
E0.11 North/West Walkways(Walkway<10 feet wide) 1524 ft of walkway length 0.7 Yes 1067 832
E0.11 West Facad/Service Yard(Illuminated length of 385 ft 2.5 No 963 330
facade wall/surface or roof path)
E2.10 Main Entry(Main entry) 13 ft of door width 20 Yes 260 620
E0.11 East Facade(Illuminated length of facade 297 ft 2.5 No 743 186
wall/surface or roof path)
Total Tradable Watts*= 8588 5740
Total Allowed Watts= 10293
Total Allowed Supplemental Watts"= 600
Wattage tradeoffs are only allowed between tradable areas/surfaces.
**A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Section 3: Exterior Lighting Fixture Schedule
A B C D E
Fixture ID:Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
E2.10 Canopy(Entry canopy 1200 ft2):Tradable Wattage
LED 1:S1:LED Linear 8W: 1 110 5 550
E2.10 Main Entry(Main entry 13 ft of door width):Tradable Wattage
LED 13:S1:LED Linear 8W: 1 124 5 620
E2.13 Canopy(Entry canopy 1180 ft2):Tradable Wattage
LED 2:S1:LED Linear 8W: 1 160 5 800
E2.13 Covered Play(Special feature area 3728 ft2):Tradable Wattage
LED 3:S6:LED Roadway-Parking Unit 54W: 1 12 48 576
E2.20 Entry Canopy(Entry canopy 350 ft2):Tradable Wattage
LED 4:S6:LED Other Fixture Unit 50W: 1 4 48 192
E0.11 South Building Parking(Parking area 4836 ft2):Tradable Wattage
Project Title:TTSD Templeton Elementary School Report date: 02/06/18
Data filename:P:\2016\16-1920-TTSD Templeton Elementary\12 Codes and Stnds\Compliance Forms\Templeton Lighting
Compliance.cck Page 4 of 5
LED.5:S3:LED Other Fixture Unit 80W: 1 4 70 280
E0.11 South/West Driveway(Driveway 31835 ft2):Tradable Wattage
LED 6:S3:LED Other Fixture Unit 80W: 1 8 70 560
E0.11 North/West Parking(Parking area 39238 ft2):Tradable Wattage
LED 7:S3:LED Other Fixture Unit 80W: 1 10 70 700
E0.11 North/East Parking(Parking area 25030 ft2):Tradable Wattage
LED 8:S3:LED Other Fixture Unit 60W: 1 9 70 630
E0.11 North/West Walkways(Walkway<10 feet wide 1524 ft of walkway length):Tradable Wattage
LED 9:S3:LED Other Fixture Unit 80W: 1 6 70 420
LED 10:S5:LED Other Fixture Unit 80W: 1 4 70 280
LED 11:S9:LED Other Fixture Unit 60W: 1 2 54 108
LED 12:S2:LED Other Fixture Unit 25W: 1 1 24 24
E0.11 West Facad/Service Yard(Illuminated length of facade wall/surface or roof path 385 ft):Non-tradable Wattage
LED 14:S2:LED Other Fixture Unit 25W: 1 7 24 168
LED 15:S9:LED Other Fixture Unit 60W: 1 3 54 162
E0.11 East Facade(Illuminated length of facade wall/surface or roof path 297 ft):Non-tradable Wattage
LED 16:S2:LED Other Fixture Unit 25W: 1 3 24 72
LED 17:S9:LED Other Fixture Unit 60W: 1 2 54 108
LED 18:S7:LED Other Fixture Unit 6.5W: 1 1 6 6
Total Tradable Proposed Watts= 5740
Section 4: Requirements Checklist
In the following requirements,blank checkboxes identify requirements that the applicant has not acknowledged as being met.Checkmarks
identify requirements that the applicant acknowledges are met or excepted from compliance. 'Plans reference page/section'identifies where in
the plans/specs the requirement can be verified as being satisfied.
Controls, Switching, and Wiring:
• 1. Lighting designated to operate more than 2000 hours per year for Uncovered Parking Areas shall be equipped with motion sensors that
will reduce the luminaire power by thirty-three percent or turn off one-third the luminaires when no activity is detected.
Plans reference page/section: Specifications.
Exterior Lighting Restrictions and Exceptions:
✓ 2. Mercury vapor and incandescent lighting is not permitted for use as exterior lighting.
✓ 3. Exempt lighting fixtures are equipped with a control device independent of the control of the nonexempt lighting and are identified in
Section 3 table above.
Plans reference page/section: N/A
Section 5: Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,specifications
and other calculations submitted with this permit application.The proposed lighting system has been designed to meet the 2014 Oregon
Energy Efficiency Specialty Code requirements in COMcheck Version 4.0.8.1 and to comply w the mandatory requirements in the
Requirements Checklist.
Michael Lopez, PE, Lead Engineer. 2/8/2018
Name-Title Signature ` Date
Project Title:TTSD Templeton Elementary School Report date: 02/06/18
Data filename:P:\2016\16-1920-TTSD Templeton Elementary\12 Codes and Stnds\Compliance Forms\Templeton Lighting
Compliance.cck Page 5 of 5