Loading...
Report (167) \U-V3 \W\ "stud . Honeywell ®SILENT E � • � KNIGHT AUG 13 2018 6820CITY G $y.‘ �TM BUILDING DIA;°; a1 1' Addressable Fire Alarm Control Panel The 6820 is an addressable fire alarm control panel(FACP)that can be configured to achieve an overall point capacity of up to 1,110 points and connect up to 17 panels in a single communications link. It has one built-in signaling tine circuit(SLC),which can support 159 (SK)System Sensor®sensors and 159 SK modules or 127(SD)Hochiki® devices per loop.To increase point capabilities,additional SLC loops can be added using the 6815 SLC expander for SK devices or the 5815XL expander for SD devices,increasing the point capacity to a maximum of 1,110 points for SK devices and 635 points for SD devices. 6820 Three additional SLCs are needed to reach 1,110 points(SK devices). Four additional SLCs are needed to reach 635 points(SD devices). The 6820 also has Form C trouble relay,and A common communications and annunciation link allows up to 17 two programmable Form C relays,along with panels to be connected via copper or fiber optic cable.A designated powerful features such as drift compensation, panel is configured as the communicator for all panels in the link for pre-trouble maintenance alert,a built-in sensor convenient single-point communications.It also has a built-in,dual- test to comply with NFPA 72 calibration testing line POTs and IP communicator and optional cellular side-cars. requirements,and calibration trouble alert. The 6820 system can be enhanced by adding modules such as the It supports a variety of devices,including the 6860 remote annunciator which also has four programmable function 6860,5860,and 6855 remote annunciators, buttons to help automate tasks and reduce time spent at the panel. 5824 serial parallel printer interface module(for printing system reports),the 5496 NAC expander, SWIFT®wireless compatibility provides options for wireless detection 5895XL power module,and SK or SD devices. through a Class A mesh network.It is ideal for hard-to-wire locations, buildings where new wiring is not allowed,or to provide an easy install fire system for new construction projects.SWIFT devices can be combined with other hard-wired 6820 compatible devices. FEATURES & BENEFITS • Capable of providing • Connect up to 17 • Integrated dual path • Programmable date • Ftexput'"circuits can up to 1,110 points for panels on one site with IP and POTs setting for automatic be individually enhanced design convenient single- communications and and convenient programmed to flexibility.Additional point access using the optional cellular Daylight Saving Time function as Signal Line Circuits SK-NIC Network side-cars for reliable changes notification circuits, can be added until Interface Card. backup auxiliary power • Built-in dual phone maximum point levels Connected panels can outputs,or initiating • 6860 annunciator with tine and digital alarm are reached. have mixed compatible a 4 x 40 large display, communicator/ circuits that support • Built-in USB interface FACP models. and 4 programmable transmitter(DACT)for both 2 and 4-wire for convenient and • Convenient function buttons. additional smoke detectors quick programming field-upgradeable Free-up time spent at communication firmware. the panel.Program options them for simple or complex tasks. i 1 6820 Product Information SIGNAL LINE CIRCUIT(SLC) alarm,supervisory,system trouble, recommended.The 6820 also has The 6815 signal line circuit(SLC) system silenced and system power. 13 preset notification cadence supports multiple device types of SK System operations include silencing patterns(including ANSI 3.41). protocol,while the 5815XL signal line alarms and troubles,resetting alarms AGENCY LISTINGS AND APPROVALS circuit(SLC)supports multiple device and the display of alarm troubles and NFPA 13,NFPA 15,NFPA 16,NFPA types of SD protocol.You cannot mix memory.The system's non-volatile SD and SK SLC devices on a FACP. 70,NFPA 72:Central station;remote event history buffer stores 1,000 Signaling;Local Protective Signaling The 6820 has one built-in signaling events for viewing from the built- Systems;Auxiliary Protected Premises line circuit(SLC)which supports in or remote annunciator.System Unit;Water Deluge releasing service. multiple devices.Additional points operations can be initiated with a Suitable for automatic,manual, can be added using the 6815 SLC mechanical firefighter's key or a waterflow,sprinkler supervisory(DACT expanders to increase overall capacity valid 4-to 7-digit operator's code. non-coded)signaling services. to 1,110 maximum points(SK devices) • or by adding up to four 5815XL SLC ° °moo UL Listed; expanders to reach 635 maximum "°"a • CSFM 7165-0559:0500; points(SD devices).The number of 4 4 4, • FDNY COA#6249; SLCs which can be used within one •5� DRILL Y system is limited by point count.(See 71 m , • FM approved; the Manual for additional information.) 71^-0-191 44®, • Seismic(CA)(pending) The 6820 SLC loops support multiple 6820 KEYPAD ORDERING INFORMATION device types,maintenance alerts,and a 6820:Addressable Fire Alarm built-in sensor test to comply with NFPA PROGRAMMING Control Panel.(Red cabinet). 72 calibration testing requirements. The 6820 system offers several options to simplify and speed-up programming. COMPATIBLE ANNUNCIATORS INDICATOR LIGHTS JumpStart®AutoProgramming 6860:4x40 LCD remote fire • General Alarm(Red): Flashes if in minimizes programming required to annunciator(4 lines and up to alarm;solid when alarm is silenced start a news stem.The built-in keypad,Y Yp 160 characters)per system;four • Supervisory(Yellow):Flashes if a or the 6860,5860 or 6855 remote programmable buttons supervisory condition exists;solid annunciators give you on-site access 5860:4x20 LCD remote fire when supervisory is silenced to current system programming.You annunciator.5860 is gray;5860R is red • System Troubles(Yellow):Flashes can also program the system using 6855:4x20 LCD remote fire if a trouble condition exists; the Honeywell Fire Software Suite annunciator solid when trouble is silenced (HFSS),which is Windows®based. 5865-3 or 5865-4:LED annunciators • System Silenced(Yellow): SOFTWARE TOOLS can display up to 30 LEDs(15 red and On when an alarm,trouble or SKST:Silent Knight Selection Tool 15 yellow).The 5865-4 has key switches supervisory condition has been provides the installer or design architect for silence and reset,and a system silenced but not yet cleared with a Windows®software system trouble LED. • System Power(Green):Flashes configuration tool to create a detailed 5880:The 5880 LED/10 module for AC failure;solid when Bill of Material(BOM)and battery has 40 programmable LED outputs power systems are normal calculations. and eight supervised dry contact HFSS:Honeywell Fire Software Suite inputs which are useful for custom USER INTERFACE applications.You can use up to eight provides communication and panel The 6820 built-in 4 x 20 annunciator programming,detector status,event 5880 modules on one control panel for with 80 character LCD display history and additional data. Requires a maximum flexibility.Its compact size and large easy-to-use tactile Windows-based computer. allows mounting inside the annunciator, touchpad can be used for system or in an accessory cabinet. operation,programming and ADDITIONAL INFORMATION maintenance.It has five LEDs for Twisted-unshielded pair wire is T ) 6820 COMPATIBLE DEVICES AND B200S-LF:Low-frequency intelligent WSK-PHOTO-T:Wireless Multi-criteria ACCESSORIES sounder base photoelectric smoke detectorwith thermal See the data sheets listed below for a B224RB: Relay base detection(135°F fixed temperture)and complete listing of the SK,SD or SWIFT B224BI: Isolator base B510W 4"base devices. WSK-HEAT:Wireless Heat,(135°F fixed 53623:SK Devices Data Sheet SD COMPATIBLE ADDRESSABLE temperture)and B510W 4"base 53624:SD Devices Data Sheet DEVICES WSK-HEAT-ROR:Wireless heat,ROR 350614,350616&350618:SWIFT SD505-6AB:Addressable 6"base (135°F fixed temperture)and B510W 4" wireless devices SD505-6IB:Addressable 6"short circuit base For a complete and current listing of isolator base WSK-MONITOR:Wireless monitor module compatible devices and accessories go to SD505-6RB:Addressable 6"relay base WSK-RELAY:Wireless relay module www.silentknight.com SD505-6SB:Addressable 6"sounder base W-USB:SWIFT Tools USB transceiver used Important:You cannot mix SK and SD SD500-AIM:Addressable input module for communication with SWIFT devices devices in the same fire alarm system. (switch input) SK COMPATIBLE ADDRESSABLE SD500-AN M:Addressable notification SBUS ACCESSORIES DEVICES module 6815:Each Single Line Circuit allows for SD500-ARM:Addressable relay module an additional 159 SK modules and 159 SK SK-ACCLIMATE:Multi criteria SD505-DTS-K:Remote test switch and photoelectric smoke detector with thermal sensors to be added to the system up to 135°F fixed temperture LED indicator for the SD505-DUCTR SK devi10 otal points.Supports System Sensor SD505-DUCT:Addressable Duct Smoke SK devices only. SK-BEAM:Reflected beam smoke detector 5815XL:Each Single Line Circuit provides without test feature Detector, SD505-DUCTR:Addressable Duct an additional 127 SD devices to be added to SK-BEAM-T:Reflected beam smoke Detector housing with relay base. the system-for a maximum of 635 points. detector with test feature Supports SD devices only. SD505-HEAT:Absolute temperature SK-CONTROL:Supervised control module 5496:A 6 amp notification power expander heat detector.Trip point range from with four ower limited notification SK-CONTROL-6:Six circuit supervised 135°F-150°F(0°C-37°C). power-limited module appliance circuit outputs. SK-DUCT:Photoelectric duct smoke SD500-LIM:Addressable Line isolator 5883:Relay Interface.Provides 10 Form C module detectorwith extended air speed range relays. SD500-MIM:Addressable Mini input SK-FIRE-CO:Four criteria fire and carbon 5824:Serial/Parallel Printer Interface monitor module(switch input) monoxide detector Module for printer connection. SK-HEAT:Fixed thermal detector(135°F) SD505-PHOTO:Photoelectric smoke 5895XL:Power Supply with six Flexput'" detector circuits,and two Form C relays.Max.16 per SK-HEAT-ROR:Fixed rate of rise detector SD500-PS/-PSDA:Addressable Single or system. y (135°F) dual action pull station y SK-HEAT-HT:Fixed high temperature 5815RMK:Remote mounting kit. thermal EAT-HT: detecFred ) SD500-SDM:Addressable smoke detector Dimensions 10 3/8"W x 10-3/16"H x 3"D module SK-ISO:Fault isolator module COMMUNICATION OPTIONS SK-MINIMON:Mini monitor module AUDIBLE/VISIBLE DEVICES CELL-CAB-SK:Cellular communicator, SK-MONITOR:Monitor module These AV devices are all 2-wire.Color:"R" metal enclosure with tock/key* SK-MONITOR-2:Dual input monitor indicates red;"W"denotes white.Fora CELL MOD:Cellular communicator,plastic module complete listing of Silent Knight AV devices enclosure* SK-MON-10:10 input monitor module go to www.silentknight.com. SK-PHOTO:Photoelectric smoke detector CHSRL/CHSWL:Wall chime/strobe Sole path,powered by panel. SK-PHOTO-T:Photoelectric smoke CHSCRL/CHSCWL:Ceiling chime/strobe IPGSM-4G:Dual path fire alarm detector with thermal(135°F fixed CHRL/CHWL:Wail chime or ,backup, sele tabcelle) and/or IP(primary or backup,selectable) temperture) HRL/HWL:Wall horn SK-IP-2:Remote reporting via the Internet. SK-PHOTOR:Photoelectric detector with P2RL/P2WL:Wall horn/strobe Requires a VisorAlarme receiver at the remote test capability PC2RL/PC2WL:Ceiling horn/strobe central station SK-PULL-SA:Addressable single action SRL/SWL:Wall strobe pull station SCRL/SCWL:Ceiling strobe MISC.ACCESSORIES SK-PULL-DA:Addressable dual action pull SPSCRL/SPSCWL:Ceiling speaker/strobe SK-NIC:Network Interface Card.Provides a station common communications link for the 6820. SPSRL/SPSWL:Wall speaker/strobe SK-RELAY:Addressable relay module SK-N IC-KIT:Installation Accessory Kit SK-RELAY-6:Addressable Six relay control SPRL/SPWL:Wall speaker SK-FML:Fiber-Optic Multi Mode, module SPCRL/SPCWL:Ceiling speaker transmitter and receiver SK RELAYMON 2:Addressable Dual relay/ SWIFT WIRELESS DEVICES SK-FSL:Fiber-Optic Single Mode monitor module RBB:Remote battery box accessory cabinet SWIFT is only compatible with SK-ZONE:Addressable zone interface for batteries that are too large to fit in the module System Sensor(SK)devices.It is not FACP cabinet.Dimensions:16"W x 10"H x SK-ZONE-6:Six zone interface module compatible with Hochiki(SD)devices. 6"D(406mm W x 254mm H x 152mm D). B210LP:6"mounting base WSK-WGI:Wireless Gateway SK-SCK:Seismic Compliance Kit used to 8501:4"Flangeless mounting base securely fasten batteries to the fire panel. WSK-PHOTO:Wireless Photoelectric B200S:Intelligent sounder base smoke detector • 6820 Technical Specifications PHYSICAL FLEXPUT CIRCUITS For a complete listing of all Overall Dimensions:16.36"W x 26.37"H x 3.91"D Six programmable circuits which can be compliance approvals and ShippingWeight:32 lbs programmed individually as: certifications,please visit www.sitentknight.com. Color:Red Notification Appliance Circuits:3A @ 27.4VDC per circuit,power-limited(with a panel maximum Microsoft,Windows,and ENVIRONMENTAL current of 6A) the Windows Logo are 0 0 o Auxiliary power circuits:3A®27.4VDCper circuit, registered trademarks Operating Temperature:32 F to 120 F (0 C to Y or trademarks of 49°C) power-limited Microsoft Corporation. Humidity:0 to 93%relative humidity(non- Initiating Circuits(Circuits 5 and 6 Only):100mA condensing) ®27.4VDC per circuit,power limited Silent Knight®,Honeywell® and SWIFT®are registered trademarks ELECTRICAL Supports Class B(Style 4)and Class A(Style 6) and Flexputr'is a 6820 Primary AC:120AC @ 60Hz,3.3A Total configuration for SLC,SBUS,and Flexput circuits trademark of Honeywell Accessory Load:6A @ 27.4VDC power-limited International,Inc Standby Current:190mA WIRING:See the product manual for wiring details This document is not Alarm Current:250mA intended to be used for Battery Charging Capacity:7 to 35AH installation purposes.We try to keep our product Battery Size:18AH max.allowed in control panel information up-to cabinet.Larger capacity batteries can be housed in date and accurate.We RBB accessory cabinet. cannot cover all specific applications or anticipate all requirements.All specifications are subject to change without notice. For Technical Support, call 800-446-6444. For more information Learn more about Honeywell Silent Knight and other products by visiting www.sitentknight.com Honeywell Silent Knight 12 Clintonville Road Northford,CT 06472 3516101 A111/17 Honeywell 800-328-0103 ©2017 Honeywell International Inc. --411111111111111 T � Honeyw 7�e�7�ll y KNIGHT 6855 Remote Annunciator The 6855 remote annunciator,can be used to operate and program Honeywell Silent Knight fire alarm control panels(FACPs)from anywhere within the system.It provides a convenient way to view system status indicators. The 6855 comes in a locked,key controlled cabinet-combining security with easy access.It does not require a code or firefighter's key to silence or reset the panel.It also has convenient separate scroll buttons for alarm, w supervisory,and trouble conditions. The remote annunciator communicates with the main fire alarm control panel through an RS-485 connection.When the system is in normal operation and has AC power,the Power LED is lit and all other LEDs are off. N„r; ,.,n The other LEDs turn on as alarms,supervisories,troubles,system silenced, and AC power losses occur. 6855 COMPATIBILITY The 6855 is compatible with the following Honeywell Silent Knight FACPs: • 6820:Addressable fire alarm control panel with up to 1,110 addressable points • 6820EVS:Addressable fire alarm control panel with an emergency voice system,up to 1,110 addressable points • 6808:Addressable fire alarm control panel with up to 198 addressable points • 6700:Addressable fire alarm control panel with up to 100 addressable points FEATURES & BENEFITS • 80-character backlit • Larger keypad buttons • On-board piezo • Accommodates wiring • Can be flush or LCD display(4 lines makes it easier to sounder audibly lengths up to 6000 ft. surface mounted with 20 characters per maneuver for system indicates alarms, from the control panel depending upon line)provides ample reset and silencing troubles,and for added design and design and installation space for messaging . Initiate and end fire supervisories install flexibility needs and is easy to read drills with a single key • Five status LEDs make • System access is • Trim ring available for • Comfortable tactical press it easier to monitor gained either through surface mounting. feel and clear audible . Easily view current and respond to status a user code or confirmation supports status by alarms, changes.They include: firefighter's key accurate supervisories,or Alarm,Supervisory, • Support for programming and troubles Silence and AC Power simultaneous use of easy operation indicators. multiple 6855s t , 6855 Technical Specifications Large Buttons for For a complete listing of all System Silence,Reset, compliance approvals and Event Acknowledge, LED Status and Fire Drill 80 Character certifications,please visit Indicators Display www.silentknight.com. Microsoft,Windows,and the Windows Logo are registered trademarks or trademarks of Microsoft Corporation. / Review Events A / Individually by Alarms, Silent Knight and Supervisories,or Troubles Honeywell®are registered trademarks of Honeywell International,Inc. qui w r r This document is not AL intended to be used for 4 installation purposes.We v.\ try to keep our product information up-to date and accurate.We cannot cover all specific applications or anticipate all requirements.Alt Ergonomic specifications are subject Numeric Keypad Designed Keypad to change without notice. (Hidden when door is closed) (Hidden when door is closed) For Technical Support, 6855 Features call 800 446 6444. PHYSICAL INSTALLATION Flush Mount: The 6855 can be surface or flush mounted.When flush mounting an electrical box is optional.The Outside wall:12.25"W x 11.5"H x 7/8"D(31.1W x RA-100TR trim ring can be used for surface mounts. 29.2H x 2.2D cm) If using an electrical box,use a 4S,single-gang,or Inside wall:9-3/8"W x 8-3/8"H x 2"D(23.8W x double-gang box. 21.3H x 5.1D cm) Surface Mount:(Including Trim Ring)12.25"W x ORDERING INFORMATION 11.5"Hx 3"D(31.1W x 29.2H x 2.2D cm) 6855:Remote Annunciator.Four line(4x20)LCD annunciator.Red. ENVIRONMENTAL Operating Temperature:32°Fto 120°F (0°C to ACCESSORIES 49°C) RA-100TR:Red.Surface Mount Trim Ring Humidity:10°/0-93%non-condensing) AGENCY LISTINGS AND APPROVALS ELECTRICAL UL listed Operating Voltage:24VDC CSFM#7165-0559:0500 Standby Current:20mA NFPA 72 Alarm Current:25mA FM approved FDNY COA approved For more information Learn more about Silent Knight's 6860 and other products available by visiting www.SilentKnight.com Honeywell Silent Knight 12 Clintonville Road Northford,CT 06472-1610 Honeywell 800.328.0103 35161314111/17 www.honeywell.com ©2017 Honeywell International Inc. ®SIL KNIGHT z a Honeywell ®SILENT' KNIGHT CELL-CAB-SK / CELL-MOD Cellular Fire Alarm Communicators The CELL-CAB-SK and CELL-MOD are cellular communicator options for Honeywell Silent Knight 6000 Series addressable fire alarm control panels (FACPs). These GSM communicators interface with the POTS and IP features of the FACPs.They provide dual path cellular and IP reporting capability,while eliminating the need and cost of separate dialer capture modules and special programming.Battery backup from the control panel maximizes overall system efficiency. Small size,easy to install,and programmable supervision time of 1-60 minutes.Both models can be positioned remotely from the fire alarm control panel via 4-wire serial bus for optimum reception.UL 864 and NFPA 72 fire code compliant for sole,primary,or backup communications. CELL-CAB-SK The CELL-CAB-SK and CELL-MOD work with AlarmNet®to provide a UL listed connection to the central station. The CELL-CAB-SK includes a GSM communicator within a metal cabinet enclosure with lock and key and includes an external antenna.The CELL- MOD houses the GSM communicator in a plastic enclosure,(optional external antenna). CELL-MOD FEATURES & BENEFITS • Integrates directly • Communicators • Accounts can be easily • Quality of Service • Programmable with Silent Knight provide dual path managed through (QOS)diagnostics via supervision time from Series 6000 panels. cellular and IP on-line management AlarmNet which 1 to 60 minutes Installation is easy as reporting capability tools conveys vital • Provides full data there is no need for when combined with . Remote mount up to communicator reporting using special programming 6000 series panels 6000 feet to ensure information,including Contact ID format or a separate dialer UL 864 and NFPA 72 best reception when messages are capture module code compliant for received,signal • Battery backup sole,primary,or strength,and message provided by the fire backup path used alarm control panel for communications enhance efficiencies and cost savings tit St CELL-CAB-SK / CELL-MOD Technical Specifications PHYSICAL ORDERING INFORMATION For a complete listing of all Overall Dimensions: CELL-CAB-SK:Cellular module housed in metal compliance approvals and cabinet with lock and key. Includes external certifications,please visit CELL-CAB-SK:10.38"W x 10.165"H x 3.176"D www.silentknight.com. CELL-MOD:7.809"W x 5.982"H x 1.5"D antenna Shipping Weight:1.3lbs(CELL MOD) CELL-MOD:Cellular module housed in plastic Microsoft,Windows,and 5.2lbs(CELL-CAB-SK) enclosure.(External antenna sold separately) the Windows Logo are GSM-ANT3DB:3dB gain external/remote antenna registered trademarks Color:Red or trademarks of 7626-50HC:50 ft.antenna cable,low loss Microsoft Corporation. ENVIRONMENTAL Operating Tem erature:32°F to 120°F (0°C to APPROVALS Silent Knight°and p 9 p Honeywelr are registered 49°C) UL 864,NFPA 72 trademarks of Honeywell Humidity:l0 to 930/0 relative humidity(non- FCC ID:CFS8DLPHS8-US International,Inc condensing) This document is not intended to be used for ELECTRICAL installation purposes.We Standby Current:55mA try to keep our product Alarm Current:100mA information up-to date and accurate.We RADIO TRANSCEIVER cannot cover all specific applications or anticipate 3G Cellular Radio all requirements.All UMTS WCDMA FDD 850/1900MHz specifications are subject FCC part 15,22,24,and 68 compliant to change without notice. For Technical COMMUNICATION PROTOCOLS Support,Please call HSPA+(4G)and HSPA(HSDPA&HSUPA)(3G) 800-446-6444. COMPATIBILITY The CELL-CAB-SK and CELL-MOD are compatible with the following Honeywell Silent Knight FACPs: • 6820:Addressable fire alarm control panel with up to 1,110 addressable points • 6820EVS:Addressable fire alarm control panel with an emergency mass notification system, up to 1,110 addressable points • 6808:Addressable fire alarm control panel with up to 198 addressable points • 6700:Addressable fire alarm control panel with up to 100 addressable points For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Northford,CT 06472 Honeywell 800-328-0103 ri SILENT' 3516271A101/18 KNIGHT www.Honeywell.com 0 2017 Honeywell International Inc. INTELLIKNIGHT ACCESSORY SILENT SK-Mon-10 la KNIGHT by Honeywell Intelligent Ten Input Monitor Module The SK-Mon-10 acts as an interface to contact devices, such as waterflow switches and pull stations. The multiple input design allows for easy and efficient installation. For more information about the IntelliKnight system, or to locate you nearest source, please call 1-800-328-0103. Description The SK-Mon-10 is a ten point addressable monitor „ ice° vt 4 module for use with Silent Knight IntelliKnight series fire ,,- alarm control panels (FACPs). Each monitor module is ' • n•= intended to interface between a control panel and a $ ` , $ (` • 1 normally open contact device.A common SLC input is :a ® e Ft used for all modules, and the initiating device loops share m • _{ • :' 4} a common supervisory supply and ground. Otherwise, •`" each monitor operates independently from the others. , —• • Each module has its own address. ,: 'P The SK-Mon-10 supports ten Class B supervised contact inputs or five Class A supervised contact inputs. Conventional 4-wire smoke detectors can be monitored _ a z, q k • t j 416 a . for alarm and trouble conditions. t t 416. ® ® 4 Y "'P•'PX' 9' mn4�.^WPb•@ w.'@'•� Y � 8 SS]eaoY�• SSITYMri A •• Features � � ' I" � �_ t4a ( • 10 contact monitor • Support for Class A and Class B wiring • Fully supervised • LED indicator for each input SK-Mon-10 • Disable unused addresses Compatibility • Mount up to two modules in one accessory cabinet (PN The S.K-Mon-10 is compatible with the following IDP-ACB) IntelliKnight FACP's: • Rotary address switches for fast installation 5700 • Removable 12 to 18 AWG plug in terminal blocks for 5808 easy wiring and troubleshooting 5820XL 5820XL-EVS • Mounting hardware included • UL Listed Installation You can install one or two SK-Mon-10 modules in an accessorycabinet (PN IDP-ACB). The accessory cabinet has a built-in mounting plate that positions the module boards so that all of the status indicators are visible. P/N 350132 Rev E ©2016 Honeywell International Inc. INTELLIKNIGHT ACCESSORY SK-Mon-10 Ten Input Monitor Module Class B s.sE.o�E. iE O n 10 Class B Devices IS6 10. Q 0 1 4, 1: Q D h6. To Compatible FACP Ii�� Q 0 11, i O Qn x ClaMA. ssA(Typical) ..... *-6 + C.) 1;C:) • a Qn 1 Q 0- 5 Class A Devices I Qn xi Q n c ClassAWiring: w o O O D Class B Wiring: e X Wiring SK-Mon-10 Monitoring Modules Specifications Environmental Physical Operating Temperature: 32°F— 120°F (0°C—49°C) Height: 6.8" (17.3 cm) Humidity: 10% —93% non-condensing Width: 5.8" (14.7 cm) Depth: 1.25" (3 cm) Ordering Information Shipping Weight: 6.3 oz (196 g) SK-Mon-10 10 Input Monitoring Module Electrical Accessories Wire Gauge: 12-18 IDP-ACB SK Module Cabinet Operating Voltage: 15— 32 VDC Standby Current: 3.5 mA max Initiating Device Circuit Wiring Resistance: 150052 max Initiating Device Circuit Voltage: 10.2 VDC max Initiating Device Circuit Current: 240 SIA max SILENT This document is not intended to be used for installation purposes. We try to keep our product it information up-to-date and accurate. We cannot cover all specific applications or anticipate all KNIGHT requirements.All specifications are subject to change without notice. For more information, contact Silent Knight 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800)328-0103, by Honeywell Fax: (203)484-7118. For Technical Support, Please Call 800-446-6444. www.silentknight.com INTELLIKNIGHT ACCESSORY SILENT SK-Monitor KNIGHT by Honeywell Intelligent Monitor Module The SK-Monitor module provides an interface to contact devices, such as security contacts, waterflow switches, or pull stations. For more information about the IntelliKnight system, or to locate you nearest source, please call 1-800-328-0103. Description The SK-Monitor is an addressable monitor module for use with Silent Knight IntelliKnight series fire alarm control panels (FACPs). The SK-Monitor is intended for use in intelligent, two-wire systems, where individual address of each module is selected using the built-in rotaryswitches The SK Monitor supports Class A supervised or Class B " supervised wiring to the load device. Conventional 4-wire xk, smoke detectors can be monitored for alarm and trouble conditions. Features • Single contact monitor • Support for Class A and Class B wiring • Fully supervised • Panel controlled status LED that flashes green in SK-Monitor normal state and is solid red in alarm • Attractive ivory cover plate Specifications • Rotary address switches for fast installation Physical • SEMS screws for easy wiring Height: 4.5" (11.4 cm) • UL Listed Width: 4" (10.2 cm) Installation Depth: 1.25" (3 cm) Shipping Weight: 6.3 oz (196 g) The SK-Monitor mounts directly into a 4" square electrical box. The box must have a minimum depth of 2-1/8".A Electrical surface mount electrical box (System Sensor® PN Operating Voltage: 15— 32 VDC SMB500) is available from Silent Knight. Current Draw (LED on): 5.0 mA max Compatibility Operating Current (LED flashing): 375 pA The SK-Monitor is compatible with the following IntelliKnight FACP's: 5700 5808 5820XL 5820XL-EVS P/N 350131 Rev F ©2016 Honeywell International Inc. INTELLIKNIGHT ACCESSORY Model SK-Monitor Intelligent Monitor Module 44 TO NEXT FROM FA NEL OR Celia. t t.47)- '� mac � PREVIOUS QEWCE MONITOR ANY NUMBER CF LL LISTED CONTACT n MULE f--1k CLOSURE maims MAY BE USED.DO NOT MIX $ fb t DDNNECT MODULES TO LISTED DEMR ABLE FRE ALAFFA INTIATFIQ,SUPERYIEORY,OR 0 CONT RAWLS OILLY SRCES I * ® ...1 '� r I To RESISTOR . _ EIA-41K _ I I - �. NRrr LATNQDEVICEcRCU1Dc)-NFPAETYLE.8 ' IRCNR3i LIMTED:4SEVA MAX.0 11 VDC:WAX INSTALL T L�DEUI1E DEMDES PER PLLWRINO EI-KJHINI IS SLFEF MMES)AM)POWER MUTED WAN MOTU FEET'S INSTALLATION NSTFI.JCTI COI 2-Wire Initiating Circuit Configuration, NFPA Style B TO NEXT FROM PANEL OR DEVICE 'I"41'41"41'f a a.� if s .11104*f s 41111b, PREVIOUS DEVICE MONITOR 4 ANY NUMBER OF Lk LISTED CONTACT MODULE I I n r7 CLOSURE DEVICES MAY BE USER DO NOT MIX ((( • + CONNECT MODULES TO LISTED 00MFATIBLE ARE ALARM INTIATING,SUPERVISORY,OR (2 () 0 $ I NOTIFIER CONTROL PANELS ONLY SECURITY DEVICES ON THE SAME MODULE v ._ 1 li a nim (d + - I Of Iw lA EOL RESISTOR IS I - 70/#o WM — I INTERNAL AT , % IJP TERMINALS 9&9 D 0 INSTALL CONTACT CLOSURE DEVICES PER ALL WRING SHOWN IS SUPERVMED AND POWER LIMITED MANUFACTURER'S INSTALLATION INSTRUCTIONS. 4-Wire Initiating Circuit Configuration, NFPA Style D Standby Current: Environmental 400 pA max @ 24 VDC (one communication every 5 Operating Temperature: 32°F- 120°F (0°C-49°C) sec with 47K EOL) Humidity: 10% -93% non-condensing 550 pA max @ 24 VDC (one communication every 5 sec with EOL <1K) Ordering Information 5.5 mA(with LED latched on) SK-Monitor Monitoring Module LED Current: 5.5 mA(with LED latched on)End-of-Line Resistance: 47K S2 Accessories Initiating Device Circuit Wiring Resistance: 1,500 S2 max SMB500 4" Square Surface Mount Electrical SLC Loop Resistance: 40 S2 max. Box SILENT This document is not intended to be used for installation purposes. We try to keep our product 41 KNIGHT information up-to-date and accurate. We cannot cover all specific applications or anticipate all 4 requirements.All specifications are subject to change without notice. For more information, contact Silent Knight 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800)328-0103, Fax: (203) by Honeywell 484-7118. For Technical Support, Please call 8200-446-6444. www.silentknight.com INTELLIKNIGHT ACCESSORY SILENT SK-Photo, SK-Photo-T El®KNIGHT and SK-PhotoR by Honeywell Intelligent Photoelectric Smoke Sensors The SK-Photo is a photoelectric smoke detector, the SK-Photo-T is a photoelectric smoke detector with thermal and SK-PhotoR is a photoelectric detector with remote test capability. These plug in smoke detectors, with integral communication, provide features that surpass conventional detectors and are for use with Silent Knight IntelliKnight Fire Alarm Control Panels (FACPs). For more information about the IntelliKnight system, or to locate your nearest source, please call 800-328-0103. Description • Optional remote LED annunciator (System Sensor®PN RA100Z) . ; tC` SK-Photo and SK-Photo-T arelu in ' p g- Plug-in mounting provides ease of type smoke sensors that combine a installation photoelectric sensing chamber with • Tamper-proof feature available on addressable analog communications. mounting bases Point ID capability allows each detector's address to be set with rotary • Listed for use in duct applications .k . address switches, providing exact • Rotary address switches for fast ,,,,,,,,„ ,,.:*7 detector locations for selective installation £ maintenance when chamber • UL Listed .. µ. contamination reaches unacceptable • FM Approved `' levels. �' SK Photo and SK Photo T have a Specifications "6 .ift unique optical sensing chamber that is Physical engineered to sense smoke produced Height: 2.0" (5.0 cm) SK-Photo (Base included) by a wide range of combustion Diameter: 4.1" (10.4 cm) installed in sources. In the SK-Photo-T, dual B501 base electronic thermistors add 135°F (57°C) thermal technology to maximize Electrical Compatibility detection. Operating Voltage: 15-32 VDC Standby Current: SK-Photo, and SK-Photo-T are The SK-PhotoR is a remote test compatible with the following detector capable detector for use with the 300 pA @ 24 VDC Maximum bases: DNR/DNRW duct smoke detector. (not Alarm Current: 6.5 mA @ 24 VDC max B210LP 6" base (included) included) (with LED on) B501 2 wire base Environmental B224RB Relay base Operating Temperature B224B1 Isolator base Features SK-Photo: 32°— 120°F (0°C—49°C) B200SR Sounder base • Sleek, low-profile design SK-Photo-T: 32°— 100°F (0°C—38°C) The SK-Photo, SK-Photo-T, and SK- • Base included Humidity: 10%—93% non-condensing PhotoR are compatible with the • Reliable analogcommunications for Other Ratings following IntelliKnight FACPs: 5820XL trouble-free operation SK-Photo-T Thermal: Fixed 5820XL-EVS • Age resistant polymer housing temperature set point 135°F (57°C) 5808 • Dual electronic thermistor design on Velocity: 0—4000 fpm (0—20 m/sec) 5700 the SK-Photo-T Installation 5600 (Rev 2.0 or higher) • Superior EMI resistance for reliability • Simple field cleaning for code The SK-Photo and SK-Photo-T plug compliance into a compatible IntelliKnight-series • Variety of mounting options to meet detector base. The SK Photon is a any application remote test capable detector head included within the DNR(W)duct • Dual LED indicators for 360°visibility smoke detector. P/N 350118 Rev F • Detector transmits signal to indicate ©2016 Honeywell International Inc. maintenance is required INTELLIKNIGHT ACCESSORY Model SK-Photo, SK-Photo-T and SK-PhotoR Intelligent Photoelectric Smoke Sensors Engineering Specifications The contractor shall furnish and install where indicated on the plans, Intelligent photoelectric smoke sensors Silent Knight SK-Photo or SK-Photo-T with thermal. The combination detector head, and twist-lock base, shall be UL listed and compatible with Silent Knight's IntelliKnight fire control panels. The base shall permit direct interchange with SK-Photo or SK-Photo-T. Base shall be the appropriate twist-lock base part number B210LP (included). The PhotoR is a remote test capable detector for use with DNR(W) duct smoke detectors. (not included). The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady. The detector may be reset by actuating the control panel reset switch. The calibration of the detector shall be capable of being selected and measured by the control panel without the need for external test apparatus. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field selectable as required. The SK-Photo shall automatically perform a functional test of the detector. The test method shall simulate effects of products of combustion in the chamber to ensure testing of detector circuits. SLC IN OUT if Ej C' a Compatible FACP Ini tm + - I- RA100Z(Optional) Lie.MI al Kif ::dit\I K." ....411 (00 law ‘IiiLii,rfliir ‘kiilVF 11110 II / ..K, ,..011... \lir Class A Optional Wiring , Wiring SK-Series Detector Mounting Bases SILENTNI This document is not intended to be used for installation purposes. We try to keep our KNIGHT product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information, contact Silent Knight 12 Clintonville Road, Northford, CT 06472-1610 Phone: by Honeywell (800) 328-0103, Fax: (203)484-7118. For Technical Support, Please call 800-446-6444. www.silentknight.com Honeywell SILENT KNIGHT SK-FIRE-CO Advanced Combination Fire and CO Detector The SK-FIRE-CO is a plug-in,addressable device that provides both fire and carbon monoxide(CO)detection.For fire,the detector combines four separate sensing elements in one unit(smoke,CO,tight/flame,and heat) ., to sense multiple components of a fire.This approach enables enhanced sensitivity to real fire with heightened immunity to nuisance particulate. For CO,the detector's electrochemical sensing cell creates a separate signal for life safety CO detection. Released through the incomplete burning of various fuels,CO is a colorless, odorless and deadly gas that is virtually impossible to detect with the human senses.Because the potential exists for dangerous levels of CO to accumulate in almost any building,legislation mandating the use of CO detection in commercial spaces continues to increase across the U.S.and SK-FIRE-CO Canada.The SK-FIRE-CO is listed to the UL 2075 standard for system- connected life safety carbon monoxide monitoring. The SK-FIRE-CO should be used in conjunction with the B200S/B200S-LF intelligent sounder base(sold separately),which can generate either a Temp 3 pattern for fire or a Temp 4 pattern for CO alarm indication.With each sounder base carrying a unique address,the FACP can then command an individual sounder,or a group of sounders,to activate.The command set from the panel can be tailored to the specific event,allowing selection of tone,and group. SK-FIRE-00 can also be used with the B210LP 6"standard FEATURES & BENEFITS • Unique ability to • Automatic drift • Separates audible detect all four major compensation of signal for fire or CO elements of a fire, smoke sensor and CO alarm when used with smoke,carbon cell B200S/B200S-LF monoxide(CO),tight/ . Uses only one address base flame,heat on the SLC • CO cell end-of-life • Separate CO detection • RealTest CO testing warning and fault signal capability • CSFM listed • Highest nuisance • UL 268 and UL 2075 alarm immunity listed SK-FIRE-CO Technical Specifications PHYSICAL CO Monitoring UL Standard Reference-Alarm For a complete listing of all Diameter:6.875"(17.46 cm)installed in a B200S Thresholds are as follows: compliance approvals and base certifications,please visit Parts Per Million Detector Response Time www.sitentknight.com. Height:3.46"(8.79 cm)installed in B200S base Shipping Weight:4.6 oz 70±5 ppm 60-240 min Microsoft,Windows,and Color:Ivory 150±5 ppm 10-50 min the Windows Logo are registered trademarks 400±10 ppm 4-15 min or trademarks of OPERATING Note:Per UL Standard 2075,the SK-FIRE-CO has Microsoft Corporation. Temperature Range:32°F to 100°F(0°C to 38° been tested to the sensitivity limits defined in UL Silent Knight®,System C) Standard 2034, Sensor°and Honeywell® Humidity:15 to 90%relative humidity(non- are registered condensing) ORDERING INFORMATION trademarks of Honeywell Air Velocity:0 to 4,000 ft/min(0 to 20 m/sec) SK-FIRE-CO:Combination Fire and CO Detector International,Inc. (base not included). This document is not ELECTRICAL intended to be used for Operating Voltage:15 to 32VDC OPTIONAL ACCESSORIES installation purposes.We SLC Standby and Alarm Current:300pA B200S:Intelligent sounder base try to keep our product B200S-LF:Low Frequency Intelligent sounder informationdateand unto e SENSITIVITY SETTINGS base cannotc accurate. ci cover all specific Sensitivity settings are programmable through B210LP:6"mounting base applications or anticipate zone programming. B200SR:Sounder base all requirements.Alt t Low:4°/o per foot(30.48 cm)of smoke.Used in B224RB:Relaybase to specificationsgewithoutare notice. to change notice. equipment rooms,kitchens,paint shop. MO2-04-01:Detector test magnet Medium:3°/o per foot(30.48 cm)of smoke. M02-09-01:Telescoping test magnet For Technical Support, Moderately clean environments:Used in hotel call 800-446-6444. rooms,dorm rooms. COMPATIBILITY High:2°/o per foot(30.48 cm)of smoke.Clean The SK-FIRE-CO is compatible with the following environments:Used in offices. Honeywell Silent Knight fire alarm control panels: Warning:After the CO cell has reached the 6820:Addressable fire alarm control panel end-of-life,the CO sensor no longer provides life 6820EVS:Addressable fire alarm control panel safety protection.However,when the fire detector with an emergency voice system. enters Photo,Thermal,Infrared(PTIR)mode,the 6808:Addressable fire alarm control panel following sensitivities apply: Level 1:1%per foot(30.48 cm)of smoke.Very 6700:Addressable fire alarm control panel clean environments Used in laboratories. 5700:Addressable fire alarm control panel Level 2:2°/o per foot(30.48 cm)of smoke.Clean 5808:Addressable fire alarm control panel environments-Ued in offices. 5820XL:Addressable fire alarm control panel Levels:3°/o per foot(30.48 cm)of smoke. 5820XL-EVS:Addressable fire alarm control panel Moderately clean environments-Used in hotel with an emergency voice system. rooms,dorm rooms. Level 6:Thermal alarm at 135°F(57°C). For more information Learn more about Honeywell Silent Knight and other products byvisitingwww.sitentknight.com Honeywell Silent Knight 12 Clintonville Road /fig, Northford,CT 06472 t °:LENT' Doc 351181 I Rev G 101/18 800-328-0103 ©2018 Honeywell International Inc. 1''" `` G` ' INTELLIKNIGHT ACCESSORY SILENT B200SR/B200SR-LF KNIGHT by Honeywell Sounder Bases The B200SR series sounder bases sets a new standard for performance, installation ease, and aesthetics. They offer maximum flexibility in installation,configuration, and operation to meet or exceed UL 268 and UL 464 requirements. For more information about the IntelliKnight system, or to locate you nearest source, please call 1-800-328-0103. Description The B200SR sounder base series is designed for new and existing dwelling unit applications. It offers maximum , flexibility in installation, configuration, and operation to meet7 or exceed UL 268 and UL 464 requirements. The B200SR series is fully compatible with existing B501 BH- . Series sounder base installations. The device enables users • p • . to select one of two B501-supported tones (ANSI Temporal 3 or Continuous) by removing a jumper. -ter With its attractive aesthetics, the B200SR series is ideal for — � applications where appearance is critical. For example, the sounder base employs a separate mounting plate that B200SR-LF B200SR installs on various junction box sizes to eliminate unsightly surface-mount boxes. In addition, the mounting plate enables pre-wiring of all connections to speed and simplify installation. The housing then mates with the mounting plate Compatibility and is locked in position with two retaining screws, which are The B200SR/B200SR-LF are compatible with covered by the installed sensor head for added tamper the following SK-series detectors: resistance. • SK-Photo Photoelectric Smoke Detector and The B200SR-LF low frequency sounder base is designed to SK--Photo-T Photoelectric Smoke Detector meet the NFPA 72 sleeping space requirement to produce a with Thermal fundamental frequency of 520 Hz +1– 10% with a square • SK-Acclimate Multicriteria Photoelectric wave or its equivalent. Studies show that a lower frequency, Smoke Detector centered around 520 Hz, is the most ideal to awaken • sleeping occupants, even those with mild to severe hearing SK Ion Ionization Smoke Detector loss. • SK-Heat Fixed Temperature Thermal Detector, Features: SK -Heat-ROR Rate-of-Rise Detector with • Tone selection via an onboard jumper Thermal, and SK-Heat-HT Fixed High Temperature Thermal Detector • UL 268 and UL 464 compliant • Pre-wire mounting plate fits various junction box sizes • Fully compatible with existing B501 BH-Series sounder base The B200SR/B200SR-LF are compatible with installations the following IntelliKnight FACP's: • Mechanical locking feature prevents the removal of the 5700 attached sensor head 5808 • 520 Hz +1– 10% square wave tone (B200S-LF) 5820XL 5820XL-EVS Installation The B200SR/B200SR-LF can be mounted directly into a 4" square by at least 1.5"–2.1" deep electrical box, using the supplied mounting kit. INTELLIKNIGHT ACCESSORY Model B200SR/B200SR-LF Sounder Bases INTELLIGENT + -/ MONITOR MONITOR MODULE CUSS AOPTIONAL WIRING SLC / _ -III(+)sic ■(-i51c OPTIONALL-SOUNDER INTERCONNECT' CoIA 1 �asa.FncP / / At1STEG ECL rl *IF 1 4 1,1P "- a ,r1 �' r C.R � Mr' END OF LINE RELAY 6q K... rs i1 • K '' . R IA f f , (EOLR-T OR EQUIVALENT) (+Y POWER i FIRST SECOND / LAST MIN SOUNDERSOUNDER SOUNDER RASE RASE BASE / (-)POWER Lit USTED2RV POSVIA SUPPLY *GROUPING OF MODEL B2IOSR SOUNDER BASES Specifications Physical Height: 2.0" (5.08 cm) less sensor Width: 6.875" (17.46 cm) Shipping Weight: B200SR 0.50 lb. (227 gm); B200SR-LF: 0.60 lb. (272 gm) Electrical External Supply Voltage 16 to 33 VDC (VFWR) External Supply Standby 1 mA maximum Alarm Current (B200SR) 35 mA maximum Alarm Current (B200SR-LF) 125 mA maximum SLC Operating Voltage 15 to 32 VDC SLC Standby Current 300 pA maximum Environmental Operating Temperature: Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com Humidity: 10% —93% non-condensing Sound Output Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone) Ordering Information B200SR Sounder Base B200SR-LF Low Frequency Sounder Base SILENT This document is not intended to be used for installation purposes.We try to Assembled In USA /t keep our product information up-to-date and accurate.We cannot cover all KNIGHT specific applications or anticipate all requirements.All specifications are FORM#350267 Rev C subject to change without notice. For more information, contact Silent Knight ©2015 Honeywell International Inc. by Honeywell 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800)328-0103, Fax: (203)484-7118. For Technical Support, Please Call 800-446-6444. www.silentknight.com INTELLIKNIGHT ACCESSORY ElSILENT SK-Pull-SA and SK-Pull-DA KNIGHT by Honeywell Intelligent Pull Stations The SK-Pull-SA and SK-Pull-DA are a single action or dual action addressable fire alarm pull station for use with Silent Knight's IntelliKnight fire control panel. Extremely easy to operate, the SK-Pull-DA and SK-Pull-SA provide a fast and practical means of manually initiating a fire alarm signal. The IntelliKnight panel recognizes each manual pull station by its specific address saving precious seconds in determining the location of an alarm. For more information about the IntelliKnight system, or to locate you nearest source, please call 1-800-328-0103. Description The SK-Pull-SA is a single action pull station requiring only one motion to activate the station. The SK-Pull-DA is a dual action pull station requiring two motions to active the station. Both pull stations are designed to work with Silent Knight PULL I DOWN i Intelliknight series fire alarm control panels (FACPs). Features • Installer can open station without causing an alarm I. condition ®sitENr KNIGHT t t waor.roa G • Dual-color LED is visible through handle of station blinks green to indicate normal operation and remains steady red SK-Pull-SA in an alarm condition • Key operated test and reset lock using lock plate actuator • Key matches compatible FACP locks • Meets the Americans with Disabilities Act Accessibility t PUSH IN Guidelines (ADAAG) controls and operating mechanisms PUt�l.C�C2WN� guidelines (Section 4.1.3[13]) • Meets ADA requirement for 5 lbs maximum pull force to active NT ®KNIGHT - Z • Shell, door, and handle molded from durable LEXAN® _w' ) Ci • Reliable analog communications for trouble-free operation SK-Pull-DA • Braille text on station handle Compatibility • Handle latches in down position and the word Activated The SK-Pull-SA and SK-Pull-DA are compatible appears, clearly indicating the station has been pulled with the following IntelliKnight FACP's: 5600 • Rotary address switches for fast installation 5700 5808 • UL Listed, including UL 38, Standard of Manually Actuated 5820XL Signaling System 5820XL-EVS P/N 350135 Rev D ©2016 Honeywell International Inc. INTELLIKNIGHT ACCESSORY Model SK-Pull-DA and SK-Pull-SA Intelligent Pull Stations Engineering Specifications The contractor shall furnish and install where indicated on the plans, Addressable Pull Stations, Silent Knight model SK-Pull-SA single action pull station or SK-Pull-DA, dual action pull station. SK-Pull-DA or SK-Pull-SA meet the ADAAG controls and operating mechanisms guidelines, and the ADA requirements for a 5 lb. maximum pull force to activate the pull station. { Class A our t 't:4,- clam;e Cotter FAG'? I:'' q. i t e ®Pi �'. /� 1, 1 'Y 1'IV i ,, j ... .„,,,,,„,,,...44"j, S' Class A Wilma: — Y4.17,0, Gass B Ming: Wiring SK-Pull-SA&SK-Pull-DA Pull Stations Specifications Electrical Physical Operating Voltage: 15-32 VDC Height: 5.5" (14 cm) Average Operating Current(LED flashing): 300 pA Width: 4" (10.2 cm) Wire Gauge: Up to 12 AWG (3.1 mm2) Depth: 1.45" (3.7 cm) Environmental Housing Material: LEXAN polycarbonate resin Operating Temperature 32°— 120°F (0°C—49°C) Bi-Colored LED: Humidity: 10%—93% non-condensing Blinking Green: Normal Steady Red:Alarm Accessories Switch: Single pole, single throw(SPST) normally open (N/O) BG-TR Optional trim ring. switch which closes upon activation of the pull station SB-I/O Surface backbox SILENT This document is not intended to be used for installation purposes. We try to keep our product KNIGHT requirements. up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information, contact Silent Knight 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800)328-0103, by Honeywell Fax: (203)484-7118. For Technical Support, Please call 800-446-6444. www.silentknight.com • FIRE PRODUCTS • STI STOPPER Il ® I- SIRE -LIFT rOV rp L FIR ALARM KEY FEATURES »� a General Information •Proven effective for more than 35 years in helping stop false fire alarms without restricting legitimate alarms. PULL. • Can be used as a guard against „ ' physical damage to a manual pull station,with or without the optional warning horn. •Three year guarantee against IN CASE OF breakage of polycarbonate in normal use(one year on electro U mechanical and electronic t F coos components). ADA Design Compliant 1 BSA •Larger sizes and surface mounted• SEE REVERSE pull stations accommodated with FOR DETAILS STI-3100 conduit spacer. ... TTr •Weather models have closed cell LIFT RE gaskets. ® •The Stopper ii design is a registered trademark of Safety Technology Sri-1100 International, Inc. PRODUCT OVERVIEW Construction •UL Listed to U.S.and Canadian This protective cover has been helping to stop false fire alarms around the world for safety standards(also for custom more than 35 years, without restricting legitimate alarms. All models offer excellent labeling). protection against physical damage(both accidental and intentional)and several Installation •When covering a pull station against severe environments both inside and out. It is ideal for schools, colleges, outside, UL requires stations to be hospitals, nursing homes, stores, hotels and public buildings of almost every kind listed for outdoor use. where there is a threat of false alarms. .Typical working properties of polycarbonate are-40°to 250°F HOW IT WORKS (-40°to 121°C). Electronics Stopper II consists of a clear, tamperproof, tough polycarbonate shield and frame, but • Power source is a 9V DC alkaline the line includes models with the option of a piezo horn, spacer, Form "C"dry relay battery included on standard contact and gaskets.The cover accommodates most manual pull stations.When the Stopper II(remote powered unit available). Stopper II with horn is lifted to gain access to the protected alarm, a piercing self- Options contained 95 or 105 dB warning horn (at one foot)sounds. Immediate attention is • Optional horn has a choice of 95 or drawn to the area and a prankster will either run or be caught. The cover is connected 105 dB at one foot. to the frame by a cable.When the cover is lifted, it drops off of the frame and a horn • Standard red units have"In Case will sound (models with horn) until the cover is snappedofn label unless specified with back onto the frame or for the �no label"or"custom label"(extra life of the battery. charge for custom label). For more information,call 1-800-888-4784(4STI)or visit www.sti-usa.com C� D) Safety Technology International • r STI Stopper II® Dimensions and Technical Information MODELS AVAILABLE APPROVALS & WARRANTY Stopper Il®Models Indoor Use TESTING STI-1100* With horn for flush mount It has been tested and approved or listed by: STI-1130" With horn and spacer •UL/cUL Listed No.S2466 STI-1200" Without horn flush mount •For fire alarm applications,UL38 requires outdoor listed stations for STI-1230* Without horn with spacer outdoor use Weather Stopper®with gaskets(Indoor/Outdoor rated) •State of California(obtain local fire marshal approval) STI-1150* Stopper II with horn flush mount • MEA 49-00-E(STI 1200) STI-1155* Stopper II with horn and spacer •Flush models ADA Compliant.Surface models ADA Compliant for STI-1250" STI-1200 flush mount and gasket operation(UL Certified No.S2466) STI-3150* STI 1200 with spacer and gaskets •Weather Stopper®versions designed to meet the requirements of IP54. Accessories •The indoor/outdoor rated station covers,when mounted on a KIT-316 Louvers for STI-3100 smooth surface,provide a rain tight seal similar to a 3R enclosure KIT-H19015 Two 3/16"Allen wrenches rating. STI-1102 Replacement horn for cover with alarm WARRANTY STI-1280 Backplate Three year guarantee against breakage of polycarbonate in normal STI-3002 Weather gasket STI-3003 Conduit gasket use(one year on electro mechanical and electronic components). STI-3004 Rigid conduit gasket STI-3100 2"conduit spacer with 1/2"or 3/4"conduit entry IMPORTANT NOTICE STI-3104 2"conduit spacer with 1/2"or 3/4"conduit entry Stopper II"FIRE"models are intended to be used in areas where (includes one 3/4"conduit entry gasket) the incidence of false fire alarms from manual pull stations is high or *Add-NR for no label on horn housing has proven to be a serious problem.Any disadvantage of this device Add-CR for custom label on horn housing is more than balanced when one considers the consequences of Add-FR for French labeling false fire alarms,especially if fire service personnel and equipment Add-ES for Spanish labeling are responding to a false fire alarm when they are needed for a real fire somewhere else.Add to this the disruption to the facility when COVER false alarms occur. If you have,or may have,a problem with false � �, fidevicesre alarm, sthe orStopper physical/IIweathercould damage prove toinvaluable. your fire alarm activation l; 5.37 in. • /, ', 3.175 in. HORN HOUSINGS (137mm) (81mm) gr i' 1in. (25mm) *WARNING:QFor RC models:UL Listing does not permit relay 011 _,_____ 6 in. °,�/ F-1 (152mm) !'7 contacts to connect to the fire alarm or a life safety function. + ,, The power supply for horns,according to UL Listing,cannot SPACER 1 2 in. be connected to a UL Listed fire alarm system.For electrical ( (51mm) specifications see install book. RC models contain one set of Form s-__ "C"dry contacts.Contacts rated 30 VAC/VDC 1 amp. SIDE VIEW MODELS WITH HORN(STI-1100 Series) COVER �-- • _ _ ll; [, 5.34 in. •�'• 3.179 in. 136mm 3 in. vim• ( ) �', (81mm) '� -76mm� 3.18 in. ii .• .5 in. ••••F 4 in.( ) f 2.73 in.(81mm) II ' (13mm) ,/ (102mm) 5 in. \ 2.32 in. (70mm) !, 7.4 in. �i_ % • \ 1.61 in.(59mm) .oird' (188mm) ',11 1,0® (140mm)5.5 in. (127mm) ^` (41mm) SPACER 1 2 in. .78 in. v (51mm) 6.81 in. (20mm) SPACER ADDS ` I ' ' (173mm) 2"DEPTH(50mm) i SIDE VIEW MODELS WITHOUT HORN(STI-3150 Series) ALL MODELS END VIEW EXTERNAL DIMENSIONS: •Flush 7.2 W x 10.2 H x 3.3 D in.(183x259x84mm) •Surface 7.2 W x 10.2 H x 5.5 D in.(183x259x140mm) Safety Technology 2306 Airport Road Tel:248-673-9898 Taylor House Tel:+44(0)1527 520 999 Waterford,Michigan Fax:248-673-1246 34 Sherwood Road Fax:+44(0)1527 501 999 International 48327,USA Toll-free:800-888-4784 Bromsgrove,Worcestershire info@sti-emea.com info@sti-usa.com B60 3DR,England www.sti-emea.com www.sti-usa.com Printed in U.S.A.,©1987-2017 Safety Technology International,Inc. Subject to change without notice. 07/18 INTELLIKNIGHT ACCESSORY SILENT SK-Relay KNIGHT by Honeywell Intelligent Relay Module The SK-Relay Module is intended for use in intelligent, two-wire systems where the individual address of each module is selected using the built in rotary switches. For more information about the IntelliKnight system, or to locate you nearest source, please call 800-328-0103. Description The SK-Relay is an addressable relay module for use with Silent Knight IntelliKnight series fire alarm control • panels (FACPs). The SK-Relay allows a Silent Knight FACP to switch discrete contacts by code command. The relay contains � � two isolated sets of Form C contacts, which operate as a DPDT switch. No supervision is provided for the S notification appliance circuit. The SK-Relay contacts can be used for virtually any normally open or normally closed application. Each SK- SK-Relay Relay is programmed with a unique signaling line circuit (SLC) loop address. When an event occurs that controls Installation the SK-Relay, the relay is triggered by the FACP. The SK-Relay mounts directly into a 4" square electrical box. The box must have a minimum Features depth of 2-1/8".A surface mount electrical box • Two sets of Form C contacts (System Sensor® PN SMB500) is available from • Rotary address switches for fast installation Silent Knight • Contacts are rated for a variety of amps (see Specifications) Compatibility The SK-Relay is compatible with the following • Panel controlled status LED that flashes green in IntelliKnight FACP's: normal state and is solid red in alarm 5820XL 5820XL-EVS • Relay programming is completely flexible—can be 5808 mapped to zone conditions 5700 5600 (Rev 2.0 or higher) • Polling LED visible through the cover plate • Attractive ivory cover plate • SEMS screws for easy wiring P/N 350127 Rev F • UL Listed ©2016 Honeywell International Inc. INTELLIKNIGHT ACCESSORY Model SK-Relay Intelligent Relay Module CONNECT MODULES TO LISTED COMPATIBLE (-) CONTROL PANELS ONLY. (-) FROM PANEL TO NEXT DEVICE 1.���1.���1.��` t ORPREVIOUS .iic {+) (-o DEVICE RELAY CONTROL I MODULECil If any wiring to Terminals 4-10 is I Nonpower limited,The CB500 barrier /) O O (�, is required.oThe CB500 includes a (�.J( u l`.1l Nonpower limited label,which _ io e o must be placed over the Power Ili @ Limited terminal information on Relay Common 2 g-no TI ill O the name plate label. Normally Closed 2 lj},T9 T2 it Normally Open 2 1j},T8 T3 Relay Common 1 ij},T7 789 T4 Unused Normally Closed 1 j0-6 3'e Q 40 T5 Normally Open 1 M- los to TeNs 0 OFFS o *NOTE:ANY FAULT IN THE POWER SUPPLY IS LIMITED O (2.0RE:s0 TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN , A SEPARATE ZONE. d O Wiring the SK-Relay Module Specifications Ordering Information Physical SK-Relay Relay Module 4.675" H x 4.275" W x 1.4" D Shipping Weight: 6.3 oz (196 g) Accessories SMB500 4" Square Surface Mount Electrical Box Environmental Operating Temperature: 32°F — 120°F (0°C—49°C) CB500 Module Barrier Humidity: 10% —93% non-condensing Electrical Operating Voltage: 15 —32 VDC Relay Contact Ratings End-of-Line Resistance: Not used 3.0A @ 30 VDC resistive SLC Standby &Alarm Current: .255mA max @ 24 0.9A @ 110 VDC resistive VDC (one communication every 5 sec with LED 0.9A @ 125 VAC resistive enabled) 0.5A @ 125 VAC inductive (PF = .35) 0.7A @ 75 VAC inductive (PF = .35) SILENT1. This document is not intended to be used for installation purposes. We try to keep our product KNIGHT information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information, contact by Honeywell Silent Knight 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800) 328-0103, Fax: (203) 484-7118. For Technical Support, Please Call 800-446-6444. www.silentknight.com ;47-"7„,„ SYSTEM \...._._4•V SENSOR' 1 # ! 1 1 ; ,' oislys 11111.111 Indoor Selectable- T. Output Horns, �k " r Strobes, and 'g u Horn Strobes for Wall Applications A: d. 'fit' :i ? -t System Sensor L-Series audible visible notification x ,,, t, l products are rich with features guaranteed to cut 4 -- ,,- r .4,r rtRiff: i £n j £ it , ., installation times and maximize profits with lower tt!. = ti, ' current draw and modern aesthetics. :.. - . Features • Updated Modern Aesthetics The System Sensor L-Series offers the most versatile and • Small profile devices for Horns and Horn Strobes easy-to-use line of horns,strobes,and horn strobes in the industry • Plug-in design with minimal intrusion into the back box with lower current draws and modern aesthetics.With white and red plastic housings,standard and compact devices,and plain, FIRE, • Tamper-resistant construction and FUEGO-printed devices,System Sensor L-Series can • Automatic selection of 12-or 24-volt operation at 15 and 30 meet virtually any application requirement. candela • Field-selectable candela settings on wall units: The[-Series line of wall-mount horns,strobes,and horn strobes 15,30,75,95, 110, 135,and 185 include a variety of features that increase their application versatility • Horn rated at 88+dBA at 16 volts while simplifying installation.All devices feature plug-in designs • Rotary switch for horn tone and two volume selections with minimal intrusion into the back box,making installations fast and foolproof while virtually eliminating costly and time-consuming • Mounting plate for all standard and all compact wall units ground faults. • Mounting plate shorting spring checks wiring continuity before device installation To further simplify installation and protect devices from construction • Electrically compatible with legacy SpectrAlert and SpectrAlert damage,the L-Series utilizes a universal mounting plate for all Advance devices models with an onboard shorting spring,so installers can test wiring • Compatible with MDL3 sync module continuity before the device is installed. • Strobes and Horn Strobes listed for wall mounting only Installers can also easily adapt devices to a suit a wide range • Horns listed for wall or ceiling use of application requirements using field-selectable candela settings, automatic selection of 12-or 24-volt operation,and a rotary switch for horn tones with two volume selections. Agency Listings SIGNALING UL 4t;* 6 LISTED APPROVED Ural S5512 FM approved except 7125-1653:0504 54011 for ALERT models 7135-1653:0503 3057383,3057072 AVDS865-05•2/22/2018•Page 1 L-Series Specifications Architect/Engineer Specifications General L-Series standard horns,strobes,and horn strobes shall mount to a standard 2 x 4 x 17/e-inch back box,4 x 4 x 11/2-inch back box,4-inch octagon back box,or double-gang back box.L-Series compact products shall mount to a single-gang 2 x 4 x 17/8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting plate shall be used for mounting wall compact models.The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,L-Series products,when used with the Sync•Circuit'"Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts.Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15,30,75,95, 110, 135,and 185. Strobe The strobe shall be a System Sensor L-Series Model listed to UL 1971 and shall be approved for fire protective service.The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize Strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns on horn strobe models over a single pair of wires.The module shall mount to a 411/16 x 411/16 x 21/8-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC or regulated 24 DC/FWR1 Operating Voltage Rangel 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33 V(24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions(including lens) 5.6"L x 4.7"W x 1.91"D(143 mm L x 119 mm W x 49 mm D) Compact Wall-Mount Dimensions(including lens) 5.26"L x 3.46"W x 1.91"D(133 mm L x 88 mm W x 49 mm D) Horn Dimensions 5.6"L x 4.7"W x 1.25"D(143 mm L x 119 mm W x 32 mm D) Compact Horn Dimensions 5.25"L x 3.45"W x 1.25"D(133 mm L x 88 mm W x 32 mm D) 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.Strobe products will operate at 12 V nominal only for 15 cd and 30 cd. AVDS865-05•2/22/2018•Page 2 UL Current Draw Data UL Max.Strobe Current Draw(mA RMS) UL Max.Horn Current Draw(mA RMS) 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC DC FWR Sound Pattern dB DC DC FWR Candela 15 88 43 60 Temporal High 39 44 54 Range 30 143 63 83 Temporal Low 28 32 54 75 N/A 107 136 Non-Temporal High 43 47 54 / p 9 95 N/A 121 155 Non-Temporal Low 29 32 54 110 N/A 148 179 3.1 KHz Temporal High 39 41 54 135 N/A 172 209 3.1 KHz Temporal Low 29 32 54 185 N/A 222 257 3.1 KHz Non-Temporal High 42 43 54 3.1 KHz Non-Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 UL Max.Current Draw(mA RMS),Wall Horn Strobe,Candela Range(15-185 cd) 8-17.5 Volts 16-33 Volts DC Input 15cd 30cd 15cd 30cd 75cd 95cd 110cd 135cd 185cd Temporal High 98 158 54 74 121 142 162 196 245 Temporal Low 93 154 44 65 111 133 157 184 235 Non-Temporal High 106 166 73 94 139 160 182 211 262 Non-Temportal Low 93 156 51 71 119 139 162 190 239 3.1KTemporal High 93 156 53 73 119 140 164 190 242 3.1K Temporal Low 91 154 45 66 112 133 160 185 235 3.1K Non-Temporal High 99 162 69 90 135 157 175 208 261 3.1K Non-Temporal Low 93 156 52 72 119 138 162 192 242 16-33 Volts FWR Input 15cd 30cd 75cd 95cd 110cd 135cd 185cd Temporal High 83 107 156 177 198 234 287 Temporal Low 68 91 145 165 185 223 271 Non-Temporal High 111 135 185 207 230 264 316 Non-Temportal Low 79 104 157 175 197 235 283 3.1K Temporal High 81 105 155 177 196 234 284 3.1K Temporal Low 68 90 145 166 186 222 276 3.1K Non-Temporal High 104 131 177 204 230 264 326 3.1K Non-Temporal Low 77 102 156 177 199 234 291 Horn Tones and Sound Output Data Horn and Horn Strobe Output(dBA) 8-17.5 16-33 Switch Volts Volts Position Sound Pattern dB DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 9" Coded High 85 90 90 10" 3.1 KHz Coded High 84 89 89 *Settings 9 and 10 are not available on 2-wire horn strobes.Temporal coding must be provided by the NAC.If the NAC voltage is held constant,the horn output remains constantly on. AVDS865-05•2/22/2018•Page 3 L-Series Dimensions _ 3.46" , I 48.5 mm —88 mm \ ' 1.25° 3.57° 1.55' 88 mm ,.25" 32 mm 9.1 cm 32mm ( ) (3.9 cm) T F ��,':�:� I/� �Piga**wl 131 �I o - !..4..Te 1 !!!!!!!!! 0 o �11e1ee1O�eeelle5.2T ,1"1"1e,1"1. i 5.38'133.9 mm �l' 527" (13.7cm)1339 mm 000eouo! 0 II °I°®°1°1®e®®® '..� 1.111.:q.:. I I I IIA \, ,J `111 a. 1 11e11•e11�e1e. @. Vi o_ IL'i ' 0.--- —.4 IN , .‘---_----_--1--7,7,-_-- ..4 ( A0548-00 A0547-00 A0557-00 Compact Strobe,Horn Strobe Compact Horn Compact Wall Surface Mount Back Box SBBGRL,SBBGWL 4.70° I- - 4.7" ` � (12.24 cm) ri 71 1.25 (4.69 cm) .1"8 mm) 1-)31 � � �� � ®-IP - 11111.1.1111 (3 ,;.�;�. C 0!!!!, 5.76' I,Q— I 144 mm !!!°®!°/eo, 14.68 cm) OM PP (14.4 cm) ,.e41AK sees/1111e1, oto��J� L ® _J 0 _ it A0550-00 A0549-00 A0554-01 Strobe,Horn Strobe Horn Wall Surface Mount Back Box SBBRUSBBWL L-Series Ordering Information Model Description Model Description `fA : ''" Wall Horn Strobes Horns* P2RL 2-Wire,Horn Strobe,Red HRL` Horn, Red P2WL 2-Wire,Horn Strobe,White HWL* Horn,White P2GRL 2-Wire,Compact Horn Strobe,Red HGRL* Compact Horn,Red P2GWL 2-Wire,Comp 2 fils act Horn Strobe,White HGWL* Compact Horn,White P2RL-P 2-Wire, Horn Strobe, Red,Plain Accessories P2WL-P 2-Wire, Horn Strobe,White,Plain TR-2 Universal Wall Trim Ring Red P2RL-SP 2-Wire, Horn Strobe,Red,FUEGO TR-2W Universal Wall Trim Ring White P2WL-SP 2-Wire,Horn Strobe,White,FUEGO SBBRL Wall Surface Mount Back Box,Red P4RL 4-Wire,Horn Strobe,Red SBBWL Wall Surface Mount Back Box,White P4WL 4-Wire,Horn Strobe,White SBBGRL Compact Wall Surface Mount Back Box,Red Wall Strobes SBBGWL Compact Wall Surface Mount Back Box,White SRL Strobe,Red SWL Strobe,White SGRL Compact Strobe,Red SGWL Compact Strobe,White SRL-P Strobe,Red,Plain SWL-P Strobe,White,Plain SRL-SP Strobe,Red,FUEGO SWL-CLR-ALERT Strobe,White,ALERT Notes: All-P models have a plain housing(no"FIRE"marking on cover). All-SP models have"FUEGO"marking on cover. All-ALERT models have"ALERT"marking on cover. `Horn-only models are listed for wall or ceiling use. *� STEM 3825 Ohio Avenue•St.Charles, IL 60174 02018 System Sensor. SENSOR® Phone:800 SENSOR2•Fax:630 377-6495 Pforcurre tyro product sumatioochangngtheltestivesion sthisdatasheet for current product information,including the latest version of this data sheet www.systemse n sor.com AVDS865-05.2/22/2018 Sr--Th 6. s .„,..,...._4 ' ENSOR '� � liliill ., , �1 hill Selectable Output Chimes and l i l i t Chime/Strobes 1:1:1:1:1 System Sensor L-Series selectable-output chimes and chime/strobes are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. Features The System Sensor L-Series product line of wall and ceiling- Updated modern aesthetics mount chimes and chime strobes include a variety of features that • increase their application versatility while simplifying the installation. • Plug-in design with minimal intrusion into the back box With white and red plastic housings,System Sensor[-Series can • Mounting plate shorting spring feature checks wiring continuity meet virtually any application requirement. before device installation Selectable-output chimes and chime/strobes are private mode • Captive mounting screw notification appliances used to alert trained personnel to investigate • Tamper-resistant construction possible emergency situations and to take appropriate action. • Field-selectable candela settings: Security guard and nurse workstations are ideal locations for —Wall: 15,30,75,95, 110, 135, 185 chime products. —Ceiling: 15,30,75,95, 115, 150, 177 All devices feature plug-in design with minimal intrusion into the • Automatic selection of 12-or 24-volt operation at 15 and 30 candela back box,making the installation fast and foolproof while virtually eliminating costly and time-consuming ground faults. • Rotary switch for tone and volume selections • Five selectable tones with high and low volume settings Installers can easily adapt devices to a wide range of application requirements using field-selectable candela settings,automatic • Electrically compatible with legacy SpectrAlert and SpectrAlert Advance devices selection of 12-or-24 volt operation,and a rotary switch for chime tones and two volume selections. • Wall models listed for wall mounting only,ceiling models listed for ceiling mounting only Agency Listings SIGNALING C4 114* LISTED APPROVED I0""I S4;,,1 3057383,3057072 7135-1653:0503 AVDS86902•11/02/2017•Page 1 L-Series Specifications Architect/Engineer Specifications �x> General System Sensor L-Series chimes and chime strobes shall mount to a standard 4 x 4 x 11/2-inch back box,4-inch octagon back box,single- gang 2 x 4 x 17/a-inch back box,or double-gang back box.A universal mounting plate shall be used for mounting products.The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,System Sensor[-Series products,when used with the Sync•Circuit Module accessory,shall be powered from a non coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync.Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC,or full-wave rectified,unfiltered power supply.Chime strobes shall have field-selectable candela settings of 15,30,75,95, 110, 135,and 185 for wall units and 15,30,75,95, 115, 150,and 177 for ceiling units. Chime Strobe Combination The chime strobe shall be a System Sensor L-Series Model listed to UL 1638 and UL 464.The chime strobe shall comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The chime shall have two audibility options and an option to switch between temporal three pattern,non-temporal(continuous)pattern, 1 second chime pattern, 1/4 second chime pattern,5 second whoop chime pattern.These options are set by a multiple position switch. Synchronization Module The module shall be a System Sensor Sync•Circuit listed to UL 464 and shall be approved for fire protective service.The module shall synchronize strobes at 1 Hz and all available chime tones.Also,while operating the strobes,the module shall silence the chimes on chime/strobe models over a single pair of wires.The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12VDC or regulated 24DC/FWR1 Operating Voltage Rangel 8 to 17.5V(12V nominal)or 16 to 33V(24V nominal) Operating Voltage Range with MLD3 8.5 to 17.5V(12V nominal)or 16.5 to 33V(24V nominal) Input terminal wire gauge 12 to 18 AWG Chime strobe dimensions(including lens) 5.6 in L x 4.7 in W x 1.91 in D(143 mm L x 119 mm W x 49 mm D) Chime dimensions 5.6 in Lx 4.7 inWx 1.25 inD(143mmLx 119mmWx32mmD) Ceiling Chime strobe dimensions(including lens) 6.8"Dia.x 2.47"D(173.5mm Dia.x 62.7mm D) SBBRL(red wall surface mount back box) 5.6 in L x 4.7 in W x 4.3 in D(142 mm L x 119 mm W x 109 mm D) SBBWL(white wall surface mount back box) 5.6 in L x 4.7 in W x 4.3 in D(142 mm L x 119 mm W x 109 mm D) SBBCRL(red ceiling surface mount back box) 6.9"Dia.x 2.5"D(175.8mm Dia.x 63.5mm) SBBCWL(white ceiling surface mount back box) 6.9"Dia.x 2.5"D(175.8mm Dia.x 63.5mm) Notes: 1.Full Wave Rectified(FWR)voltage is a non filtered,time varying power source that is used on some power supply and panel outputs. 2.CHS products will operate at 12 V nominal only for 15 and 30 cd. UL Current Draw Data UL Max.Chime Current Draw(mA RMS) 8-17.5 Volts 16-33 Volts Sound Pattern dB DC DC FWR 1 Second Chime High 5 8 9 1 Second Chime Low 5 8 9 1/4 Second Chime High 6 10 10 1/4 Second Chime Low 5 9 9 Temporal Chime High 7 10 10 Temporal Chime Low 6 9 9 5 Second Whoop High 12 15 16 5 Second Whoop Low 7 10 11 Coded High 12 15 16 °This data represents coding at 3 chimes per second.Actual current draw will vary depending upon coding selected. AVDS86902•11/02/2017•Page 2 UL Max.Chime/Strobe Current Draw(mA RMS)Wall 8-17.5 Volts 16-33 Volts DC Input 15 30 15 30 75 95 110 135 185 1 Second Chime 90 154 51 71 115 136 161 202 238 1 Second Chime 89 154 50 70 116 136 154 199 242 1/4 Second Chime 90 154 52 72 117 137 168 201 242 1/4 Second Chime 89 153 49 70 115 136 165 199 241 Temporal Chime 88 153 49 69 112 137 168 201 246 Temporal Chime 88 152 47 68 111 136 167 196 241 5 Second Whoop 91 154 52 70 113 132 176 206 243 5 Second Whoop 87 149 46 66 108 130 170 202 240 16-33 Volts FWR Input 15 30 75 95 110 135 185 1 Second Chime 70 90 160 176 197 233 275 1 Second Chime 67 88 158 175 191 232 271 1/4 Second Chime 69 93 159 175 198 233 272 14 Second Chime 68 93 154 169 196 232 270 Temporal Chime 65 90 145 170 189 228 283 Temporal Chime 64 89 142 170 188 219 282 5 Second Whoop 70 93 145 168 187 223 278 5 Second Whoop 62 84 137 159 180 216 272 UL Max.Chime/Strobe Current Draw(mA RMS)Ceiling 8-17.5 Volts 16-33 Volts DC Input 15 30 15 30 75 95 115 150 177 1 Second Chime 95.5 165 47 69 117 137 165 202 238 1 Second Chime 93 162 47 68 116 137 165 200 238 1/4 Second Chime 94 161 48 70 117 138 166 202 237 1/4 Second Chime 93 157 48 69 116 137 164 199 236 Temporal Chime 93 163 48 69.5 116 138 165 199 238 Temporal Chime 92 160 47 68.5 116 136 164 198 237 5 Second Whoop 98 169 54 77 124 146 173 206 245 5 Second Whoop 95 166 49 71 117 144 168 202 239 16-33 Volts FWR Input 15 30 75 95 115 150 177 1 Second Chime 63 90 147 169 184 212 245 1 Second Chime 63 88 147 169 183 212 244 1/4 Second Chime 65 90 149 170 184 213 246 1/4 Second Chime 64 89 148 168 184 213 244 Temporal Chime 64 89 148 169 184 212 245 Temporal Chime 63 88 147 169 183 212 245 5 Second Whoop 75 100 155 178 193 221 255 5 Second Whoop 68 91 148 170 186 217 248 Tone Selection Chime tone selection is accomplished by using the rotary switch on the back of the product. The current draw and sound measurements for various chime tone settings are listed below. Chime and Chime/Strobe Output(dBA) Setting Repetition Rate dB Level Switch 8-17.5 Volts 16-33 Volts 1 1 Second Chime High Position Sound Pattern dB DC DC FWR 2 1 Second Chime Low 1 1 Second Chime High 61 62 62 3 1/4 Second Chime High 2 1 Second Chime Low 56 55 55 4 1/4 Second Chime Low 3 1/4 Second Chime High 67 70 70 5 Temporal Chime High 4 1/4 Second Chime Low 61 61 61 6 Temporal Chime Low 5 Temporal Chime High 64 66 66 7 5 Second Whoop High 6 Temporal Chime Low 59 60 60 8 5 Second Whoop Low 7 5 Second Whoop High 76 78 78 9 Coded** High 8 5 Second Whoop Low 62 64 64 **For chime only. 9 Coded** High 57 51 57 AVDS86902•11/02/2017•Page 3 L-Series Dimensions = 4.T 119 mm —_ = 1.91" SYSTEM SENSOR Audible Visible A A � Accessories ,..044600 System Sensor L-Series offers a wide range of Audible 117 Visible (AV)accessories to enable you to meet a variety of application requirements. Features The MP120KL Mounting Plate is designed to use 120 VAC to power MP120KL Mounting Plate SpectrAlert Advance horns,strobes, horn strobes,chimes,and chime strobes. • Designed for both indoor and outdoor use • Plug-in design eliminates ground faults Color Lens Attachments install easily on any L-Series strobe • Power supply that converts 120 VAC to nominal 24 V FWR devices to provide distinctive visual signaling. • Compatible with all two-wire L-Series devices Bezel Kits enable installers to easily turn any L-Series Fire or Plain Color Lens Attachments device into a device that meets ECN/MNS requirements.Bezel kits are available for all varieties and footprints of L-Series products and • Easily turns any device into a strobe for ECS/MNS events: come in FIRE,ALERT, EVAC,AGENT, FUEGO,FOGO,and Plain severe weather,toxic gases,sprinkler activation and more options making customization easy. • Outdoor rated from—35°F to 151°F • Wall or ceiling mount lenses available Universal Trim Rings for wall and ceiling mount devices allow for additional space within the backbox. • UL 1638 listed Bezel Kits L-Series Surface Mount Back Boxes are the best solution in locations where you have a hard surface to mount to. • Easily turn a Fire or Plain device into a device to meet ECS/MNS requirements The Sync•Circuit Module synchronizes L-Series strobes at 1 Hz and • Bezel kits available for strobes,horns,chimes,horn strobes, horns and chimes at temporal 3 over a single pair of wires. Patented chime strobes and speaker strobes module technology also allows the silencing of horns or chimes on • Bezels options with FIRE,ALERT, EVAC,AGENT, PLAIN,FUEGO, horn strobe and chime strobe models over a pair of wires.See the FOGO printing Sync•Circuit Datasheet for more information. • For use with L-Series devices only • Operating temperature-40°F to 151°F Agency Listings Cr11) 4140*. LISTED APPROVED IW'I 55512 FM approved: 7125-1653:0504 54011 Sync modules and MP120KL. 7135-1653:0503 S4048 3057383,3057072,3057493 Does not include color lenses. Specifications MP120KL 120 VAC mounting plate model MP120KL shall be listed to UL 464 for fire protective signaling systems.The mounting plate shall power a two- wire L-Series horn,strobe,horn strobe,chime or chime strobe from a 120 VAC supply converted to nominal 24 V FWR.For indoor applications, the mounting plate shall be installed in a 4x4x21/e-inch junction box. Compatibility MP120KL may be used with any of the following products at all horn and strobe settings:P2RL,P2WL,P2RL-P,P2WL-P,P2RL-SP,P2WL-SP, PC2RL, PC2WL,SRL,SWL,SRL-P,SWL-P,SRL-SP,SWL-CLR-ALERT,SWL-ALERT,SCRL,SCWL,SCWL-CLR-ALERT,HRL,HWL,CHRL, CHWL,CHSRL,CHSWL,CHSCRL,CHSCWL. Physical/Operating Specifications - • "` ,. > .. • ,.» 1• 41;c+,P'. Standard Operating Temperature -40°F to 151°F(-40°C to 66°C) Humidity Range 10 to 93%non-condensing(indoor products) Nominal Voltage Regulated 120 VAC Operating Voltage Range 96-132 VAC Current Draw From AC Line 150 mA max. L-Series Bezels The System Sensor L-Series bezels are for installation with strobes,horns,chimes,horn strobes,chime strobes,and speaker strobes. Bezels are offered in red and white for both wall and ceiling devices.Available in FIRE,ALERT,EVAC,AGENT,Plain(no marking),FUEGO, and FOGO. Operating temperature shall be-40°F to 151°F. , i, 1 di 0 �'�'p00Opoo 0J ,°00000 / 0, ij„otel U1 0�� i CP II QL E NEE ,J� i ouoI% O0 i! goN ,OoO 11 I. SSiiOl/DO p0000$, 0000 1 W oo0009�4 Specifications Colored Lens Attachments The System Sensor L-Series colored lens attachments shall be approved for fire protective service as listed in UL 1638.The lens attachments shall only be used with plain(no"FIRE"print)System Sensor strobe devices or in conjunction with a non-fire printed bezel.The lens shall mount to any wall-or ceiling-mount strobes and shall be rated from—35°F to 151°F. Compatibility Colored lens attachments may be used with the following System Sensor L-Series plain(non-FIRE-printed)strobe models:P2RL-P,P2WL-P, SRL-P,SWL-P,SPSRL-P,SPSWL-P,SPSCWL-P,or any device used with a non-FIRE printed bezel. Colored Lens Installation Installation to Wall-Mount Strobe Installation to Ceiling-Mount Strobe ioetalm 000000 0000000000000 liii, i titir ;., 1r %��ljtiv ,' fizO • �ODoo �Oeo ♦ t, Ordering Information Part No. Description Part No. Description yy Surface Mount Back Box Colored Lenses SBBRL Red,wall-mount,compatible with standard LENS-B2 Wall-mount,blue horns,strobes,horn strobes,chimes and chime LENS-R2 Wall-mount,red strobes LENS-G2 Wall-mount,green SBBWL White,wall-mount,compatible with standard horns,strobes,horn strobes,chimes and chime LENS A2 Wall mount,amber strobes LENS-BC2 Ceiling-mount,blue SBBSPRL Red,wall-mount,compatible with speakers and LENS-RC2 Ceiling-mount,red speaker strobes LENS-GC2 Ceiling-mount,green SBBSPWL White,wall-mount,compatible with speakers LENS-AC2 Ceiling-mount,amber and speaker strobes SBBCRL Red,ceiling-mount compatible with horns, Retrofit Plates strobe,horn strobes,chimes,chime strobes, (For use with horn strobe&speaker strobe devices) speakers and speaker strobes RFPW 9.5"x 7"white SBBCWL White,ceiling-mount,compatible with horns, RFP 9.5"x 7"red strobe,horn strobes,chimes,chime strobes, Mounting Plate speakers and speaker strobes MP120KL 120 VAC Adapter Mounting Plate SBBGRL Red,wall-mount,compatible with compact horns,strobes,horn strobes Sync Modules SBBGWL White,wall-mount,compatible with MDL3W White, 12/24 volt Sync-Circuit module compact horns,strobes,horn strobes MDL3R Red, 12/24 volt Sync-Circuit module Bezels* Trim Rings BZR Wall Red Bezel Kit TR-2 Universal wall trim ring,red,6.3"x 8.2" BZW Wall White Bezel Kit TRC-2 Universal ceiling trim ring,red,diameter 8.5" BZGR Compact Wall Red Bezel Kit TR-2W Universal wall trim ring,white,6.3"x 8.2" BZGW Compact Wall White Bezel Kit TRC-2W Universal ceiling trim ring,white,diameter 8.5" BZRC Horn Strobe Ceiling Red Bezel Kit BZWC Horn Strobe Ceiling White Bezel Kit BZSPR Speaker Wall Red Bezel Kit BZSPW Speaker Wall White Bezel Kit BZSPRC Speaker Ceiling Red Bezel Kit BZSPWC Speaker Ceiling White Bezel Kit "Each bezel pack ships in a package of 5.For desired bezel option add-F(FIRE),-AL(ALERT),-EV(EVAC),-AG(AGENT),-P(Plain), -SP(FUEGO),-PG(FOGO)for desired printing. �' SYSTEM 3825 Ohio Avenue•St.Charles, IL 60174 ©2017 System Sensor. SYSTEM Phone:800-SENSOR2•Fax:630-377-6495 Product specifications subject to change without notice.Visit systemsensor.com SENSOR® for current product information,including the latest version of this data sheet. www.systemsensor.com AVDS87001•03-17 6-, M, SYSTEM SENcOR *144 Outdoor Selectable- ` tg Sirla Output Horns, Strobes, and Horn Strobes for Wall Applications SPECTFlclert SpectrAlert®Advance outdoor audible visible products ®wEiraj A "I are rich with features that cut installation times and maximize profits. Features SpectrAlert Advance offers the broadest line of outdoor horns, • Weatherproof per NEMA 4X, IP56 strobes,and horn strobes in the industry.With white or red plastic housings,wall or ceiling mounting options,and plain or FIRE-printed • Listed to UL 1638(strobe)and UL 464(horn) devices,SpectrAlert Advance can meet virtually any application • Compatible with System Sensor synchronization protocol and requirement,including indoor,outdoor,wet,and dry applications in legacy SpectrAlert products temperatures from—40°F to 151°F. • Field selectable candela settings: 15, 15/75,30,75,95, 110, 115, Like the entire SpectrAlert Advance line,outdoor horns,strobes, 135, 150, 177,and 185 and horn strobes for wall applications include a variety of features • Automatic selection of 12-or 24-volt operation at 15 and that increase application flexibility and simplify installation. First, 15/75 candela field-selectable settings,including candela,automatic selection of • Rotary switch for horn tone and three volume selections 12-or 24-volt operation, horn tones,and three volume options enable installers to easily adapt devices to meet requirements. • Horn rated at 88+dBA at 16 volts • Rated from—40°F to 151°F Next,SpectrAlert Advance devices use a universal mounting plate • Universal mounting plate with an onboard shorting spring that for both wall and ceiling applications.This mounting plate includes tests wiring continuity before devices are installed an onboard shorting spring that ensures wiring continuity before Plug-in design with minimal intrusion into the back box devices are installed,so installers can verify proper wiring without • mounting the devices and exposing them to potential construction • Tamper-resistant construction damage.Once the plates are mounted,all SpectrAlert Advance • Listed for ceiling or wall mounting devices utilize a plug-in design with a single captured screw to speed installation and virtually eliminate costly ground faults. Outdoor devices ship with weatherproof plastic back boxes(metal back boxes are available separately)that accommodate in-and- Agency Listings out wiring for daisy chaining devices. Plastic back boxes feature removable side flanges and improved resistance to saltwater SIGNALING (5— corrosion. Knock-outs located on the back eliminate the need to drill holes for screw-in mounting. Plastic and metal weatherproof back MEA 1 1 boxes come with 3/4-inch top and bottom conduit entries and 3/4-inch LISTED ® 7300-1653:187(outdoor strobes) 54011(chimes,horn strobes,horns) APPROVED approved 7125-1653:188(horn strobes, knock-outs at the back.A screw-in NPT plug with an 0-ring gasket S3593(outdoor and alert strobes) 3023572 MEA452-05-E 7135-1653:189(horns,chimes) for a watertight seal is included with each back box. • SpectrAlert Advance Outdoor Horn, Strobe, and Horn Strobe Specifications Architect/Engineer Specifications General SpectrAlert Advance outdoor horns,strobes,and horn strobes shall mount to a weatherproof back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate. Also,SpectrAlert Advance products,when used with the Sync•CircuiL°Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 9 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts.Outdoor SpectrAlert Advance products shall operate between—40 and 151 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75,30,75,95, 110, 115, 135, 150, 177,and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL.The strobe shall be suitable for use in wet environments. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal(continuous)pattern.These options shall be set by a multiple position switch. On four-wire products,the strobe shall be powered independently of the sounder.The horn or horn strobe models shall operate on a coded or non-coded power supply.The horn strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The horn strobe shall be suitable for use in wet environments. I le • s Operating Temperature —40°F to 151°F(-40°C to 66°C) Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1 Operating Voltage Rangel 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions(including lens) 5.6"L x 4.7"W x 2.5"D(142 mm L x 119 mm W x 64 mm D) Horn Dimensions 5.6"Lx4.7"Wx1.3"D(142mmLx119mmWx33mmD) Wall-Mount Weatherproof Back Box Dimensions(SA-WBB) 5.7"L x 5.1"W x 2.0"D(145 mm L x 130 mm W x 51 mm D) Notes: 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.P,5,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd. AVDS01201 UL Current Draw Data KLMax.'Strobe Current Draw(mA RMS) UL Max.Horn Current Draw(mA RMS) 8-1Z5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR Standard 15 123 128 66 71 Temporal High 57 55 69 75 Candela 15/75 142 148 77 81 Temporal Medium 44 49 58 69 Range 30 NA NA 94 96 Temporal Low 38 44 44 48 75 NA NA 158 153 Non-Temporal High 57 56 69 75 95 NA NA 181 176 Non-Temporal Medium 42 50 60 69 110 NA NA 202 195 Non-Temporal Low 41 44 50 50 115 NA NA 210 205 Coded High 57 55 69 75 High 135 NA NA 228 207 Coded Medium 44 51 56 69 Candela 150 NA NA 246 220 Coded Low 40 46 52 50 Range 177 NA NA 281 251 185 NA NA 286 258 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,Standard Candela Range(15-115 cd) 8-17.5 Volts 16-33 Volts DC Input 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,High Candela Range(135-185 cd) 16-33 Volts 16-33 Volts DC Input 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 Candela Derating Horn Tones and Sound Output Data For K series products used at low temperatures,listed Horn and Horn Strobe Output(dBA) candela ratings must be reduced in accordance with 8-17.5 16-33 24-Volt Nominal this table. Switch Sound Volts Volts Reverberant Anechoic Strobe Output(cd) Position Pattern dB DC FWR DC FWR DC FWR DC FWR Listed Candela Candela rating at 40°F 1 Temporal High 78 78 84 84 88 88 99 98 15 2 Temporal Medium 74 74 80 80 86 86 96 96 15/75 Do not use below 32°F 3 Temporal Low 71 73 76 76 83 80 94 89 30 4 Non- High 75 44 Temporal 82 82 88 88 93 92 100 100 95 70 5 Non- Medium 110 110 Temporal 78 78 85 85 90 90 98 98 115 115 6 Non- Low 75 75 81 81 88 84 96 92 135 135 Temporal 150 150 71- Coded High 82 82 88 88 93 92 101 101 177 177 8t Coded Medium 78 78 85 85 90 90 97 98 185 185 9t Coded Low 75 75 81 81 88 85 96 92 Settings 7,8,and 9 are not available on 2-wire horn strobe. AVDSO1201 SpectrAlert Advance Diagrams r4.7" 2.5'=► 1 CO Mr MC 5.6" 1.0) 0 ." 1 1111, Wall-Mount Horn Strobes < � Wall Plastic Weatherproof Back Box UP S ®J) � ® m �ll Wall-Mount Horn Strobe with Plastic Weatherproof Back Box SpectrAlert Advance Ordering Information Model Description Wall Horn Strobes P2RK"t 2-Wire Horn Strobe,Standard cd, Red,Outdoor(includes plastic weatherproof back box) P2RHK"t 2-Wire Horn Strobe,High cd, Red,Outdoor(includes plastic weatherproof back box) P2WK"t 2-Wire Horn Strobe,Standard cd,White,Outdoor(includes plastic weatherproof back box) P2WHK"t 2-Wire Horn Strobe,High cd,White,Outdoor(includes plastic weatherproof back box) P4RKt 4-Wire Horn Strobe,Standard cd,Red,Outdoor(includes plastic weatherproof back box) P4WK 4-Wire Horn Strobe,Standard cd,White,Outdoor(includes plastic weatherproof back box) P2RHK-120 2-Wire Horn Strobe,High cd, Red,Outdoor, 120 V(includes plastic weatherproof back box) Wall Strobes SRK*t Strobe,Standard cd,Red,Outdoor(includes plastic weatherproof back box) SRHK*t Strobe,High cd,Red,Outdoor(includes plastic weatherproof back box) SWK"t Strobe,Standard cd,White,Outdoor(includes plastic weatherproof back box) SWHK"t Strobe,High cd,White,Outdoor(includes plastic weatherproof back box) Horns HRKt Horn,Red,Outdoor(includes plastic weatherproof back box) Accessories SA-WBB Red,Metal Weatherproof Back Box SA-WBBW White,Metal Weatherproof Back Box Notes: "Add"-P"to model number for plain housing(no"FIRE"marking on cover),e.g.,P2RK-P. t Add"-R"to model number for weatherproof replacement device(no back box included),only for use with weatherproof outdoor flush mounting plate,WTP and WTPW. "Standard cd"refers to strobes that include 15,15/75,30,75,95,110,and 115 candela settings."High cd"refers to strobes that include 135,150,177,and 185 candela settings.When replacing standard outdoor units both the device and back box must be replaced. SYSTEM ©2012 System Sensor. / 3825 Ohio Avenue•St.Charles, IL 60174 Product specifications subject to change without notice.Visit systemsensorcom SENSOR' Phone:800-SENSOR2•Fax:630-377-6495 for current product information,including the latest version of this data sheet. AVDS01201•3/12 ACE AC :Ft OX ACCESSORY CABINET ENCLOSURE - _ Economical enclosures ideally suited for field troubleshooting and easy maintenance of system wiring, these surface mountable cabinets are available in a variety of sizes to meet your demands. Every durable box is fabricated from 16 gauge steel with a powder coat finish and features a formed liftaway hinged door CAT 30 key locked for security. Standard units are available in red, but can be easily customized to any color or size /4°"4 FEATURES with the additional option of screened labelling 000° • Custom sizes, colors, on the door. Also included is an interior galvanized tit and lettering available back plate with a hole matrix configuration raised +9. 0,5" to provide ample room for mounting • 16 gauge steel construction optional components. 020 • Liftaway hinge with a CAT 30 keyed door lock LISTED • EMT and rigid 0.5", 0.75", 1" and 1.5" cluster knockouts CUSTOM OPTIONS • Removable, 0.5" raised 18 gauge galvanized back plate with mounting hole matrix • Internal threaded grounding lug 41111 screw in back box •Grounding stud screw on cover • UL listed TERMINALA1-1NFt-ME-T • ISO 9001 quality controlled Size Color Lettering J. SPACE AGE ELECTRONICS www.lsae.com I toll free 1.800.486.1723 I fax 508.485.4740 Da NEM Ir6;11a Copyright 2007 Space Age Electronics,Inc.'This document is subject to change without notice I LT10065 I Rev.G NFPIC Pg.1/2 C IR ACCESSORY CABINET ENCLOSURE SPECIFICATIONS Constructed of 16 gauge(.059"thick)cold rolled steel and finished with a durable, heat-resistant baked-on enamel. Front cover features a removable formed liftaway hinge and a high security CAT 30 keyed door lock. Custom sizes, finishes, and labeling available. EMT and rigid 0.5", 0.75", 1" and 1.5" knockout clusters embedded in cabinet. 18 gauge galvanized removable back plate is mounted on studs to the back box, Plate clears the back box by 0.5"to accommodate mounted hardware. Custom equipment mounting can be accomplished with standard hole matrix or self tapping drill screws. Cover and back box include a threaded grounding stud and lug. ØyRemovable Formed BOX SIZES �� Liftaway Hinge Part# Width Height Depth SSU00655 23.5" 13" 5.5" SSU00656 13.75" 13.75" 3.25" 00"..... 4111111111.11111Mi\ SSU00657 23.5" 23,5" 5.5" RemovableSBack Plate Drill I WALL MOUNTING PATTERN SIZES Back Plate .1'1;MINIIIIIIIMMIRM } Part# Width Height f 0.5" SSU00655 20.25" 9.75" SSU00656 11.5" 11.85" SSU00657 20.25" 20.5" AGENCY APPROVALS ORDERING INFORMATION UOXX.S2580 UL Listed Control Unit Accessories Part# Description SSU00655 ACE A Accessory Cabinet Enclosure, Red SSU00656 AC2 Accessory Cabinet Enclosure, Red SSU00657 ACE D Accessory Cabinet Enclosure, Red wirS PACE AGE ELECTRONICS www.lsae.com I toll free 1.800.486.17231 fax 508.485.4740 MAUkF�filSIERED ©Copyright 2007 Space Age Electronics,Inc.'This document is subject to change without notice I LT10065 I Rev.G N CO1` ' {` Pg.2/2 • 01 *1/4'5\ s tibt) 2 "Multi I/O" Module Bracket he 2MB Multi-Module Assembly Bracket is designed to hold up to two System Sensor style Multiple Input and Output Addressable Modules. Ideally suited for Gamewell-FCI, Notifier, Firelite, and other addressable • module installations. Each Multiple 10 module is installed independently with the field wiring connections easily accessible. The 2MB is supplied with all of the hardware required to mount it to any of the Space Age ACE Cabinets for a profes- sional installation. _ Space Age's ACE Cabinet size "A" (SSU00655) or"D" (SS000657) and AC2 Cabinet (SS000656) are instock and features key access and a lift away removable 1111 104ftftr door to access the address modules and field wiring thus allowing you time saving maintenance and trouble shooting of the system. AC2 Cabinet Enclosure (PN: SSU00656) Holds 2 2MB brackets 13.75" H x 13.75" W x A 3MB Bracket is available. It allows for the mounting 3.25"D of 3 System Sensor Multi I/O Addressable Modules per ACE Cabinet Enclosure: bracket. This unit only fits the ACE "A" and "D" Cabi- •A size holds 4 2MB brackets 23 1/2" x 13" nets, not the AC2. (PN SSU00655) • D size holds 8 2MB brackets 23 1/2" x 23 1/2" (PN SSU00657) Standard Features: Secures 2 System Sensor I/O Modules per 2MB. Matches ACE and AC2 cabinet mounting holes. 2, 2MBs mount in the AC2 Cabinet (4 Multi I/O Mods) 4, 2MBs mount in the ACE A Cab (8 Multi I/O Mods) 8, 2MBs mount in the ACE D Cab (16 Multi I/O Mods) • 20 gauge steel construction B01 Space Age Electronics, inc. I S 0 9 0 0 1 www.1SAE.com NFPA Made In U.S.A. REGISTERED 800.486.1723 Toll Free 508.485.0966 Local 508.485.4740 Fax Space Age Electronics, Inc. 2007 No Excuses, Just Solutions! ED0438 LT10448 Rev.A 1/2 ESPACE AGE ELECTRONICS, INC. Specifications: The 2MB Bracket is made of 20 gauge cold rolled steel (CRS) and is galvanized to protect the metal from cor- rosion. Each bracket can support two of System Sensor's multi I/O modules. The 2MB can be purchased separately or through Space Age's Custom Assembly and be mounted in any number of our cabinets (below are just a few), Call For pricing. System Sensor part numbers are: CR-6, SC-6, CZ-6 and the IM-10. These can be purchased separately and mounted in the brackets for you as well. - 1375" 1"sm jrl 1111111 .� ` --1--- . 1.mil 2MMO , • ,. 41■11 ® . • L1111> .• a • ,: 019 • i■ .713.75" 11 tills. 2MMO ' I r �v •i 11111 ` . I J Lel.# . s 1 AC2 Cabinet with two (2) 2MB Brackets. 3 1/4,, Total of 4 System Sensor Multi I/O Modules 1 _ Overall Cabinet Dimensions •• IL ILS • —1 Size:A 2OI'II . 2MMO ]I I « I IN• Iill •Ir C i ■i 1 41■ :i 23 1/2" II I I IN i 0 1 ■i 1111 1 0 i I I It■ 21M0 . III I!■ . 2M400 '� SizeD 0 I T ■7� 1!■ ' 0 J ■!1 l 0 1 i o • '• •- 111 I11 _• • '• 0 23 1/2" ACE "A" Cabinet with Four (4) 3MB Brackets. Total of 12 System Sensor Multi I/O Modules y ACE "D" can hold eight (8) 2MBs or 16 Modules. Ordering Information: Part# Description 3OKSS000456 2MB multi I/O Module Bracket Space Age Electronics, inc. www.1SAE.com 800.486.1723 Toll Free 508.485.0966 Local 508.485.4740 Fax No Excuses, Just Solutions! Space Age Electronics, Inc. 2007 ED00438 LT10448 Rev.A 2/2 y_ a It.LV AP al - TTS .. _ , Tool-Less Terminal Strip The TTS Tool-less Terminal Strip is designed to minimize wiring costs while meeting UL 864 Rev. 9 Sect. 12.4 Field Wiring applications requirements. It allows for quick easy mounting of multiple connection points. The clamp connections can accommodate wire sizes ranging from 20 to 12 AWG, stranded or solid core wire, and I" can be. easily connected by depressing the terminal tab the stripped �� with either a finger or screwdriver, pushing pp a conductor into the connection point and releasing the W Black terminal tab to secure the wire. Up to four conductors can be connected to each terminal point. There are 4 P/N: SS000470 built in test ports for quick circuit trouble shooting. The terminal strip can mount into the Space Age Electronics, Inc. Accessory cabinets or the BB4 Back Box Bracket (purchased separately) or can be surface mounted. : lip ailt eti Standard Features: -w III ► • Each package consists of 1 terminal block , ` l • (2) 4/40 machine screws for --... .., mounting ----... • Accepts 20 to 12 AWG White • • Rated for 25A @ 300V and 5A @ P/N: SSU00471 600V • Measures 2" L X 1-3/8" W X 7/8"H • Built in test ports for troubleshooting Eel • Available in black or white. • NFPA Made In U.S.A. Mithi.°YA (''. *. t:\ BOX ISO 9001Space Age Electronics, inc. ADA REGISTERED www.1SAE.com 11,113- Uses UL Recognized Components COMPANY 508.485.0508.485.0996666 Toll Free Local 508.485.4740 Fax Space Age Electronics, Inc. 2007 ED0409 LT10376 Rev C 1/2 No Excuses, Just Solutions! • i, . SPACE AGE ELECTRONICS, INC. Specifications: The TTS Tool-Less Terminal Strip will be a UL recognized component. There will be four terminal poles with four quick connection points per terminal pole. It shall accommodate connections of solid or stranded and wire sizes ranging from 20 to 12 AWG. There will be four direct test ports for each pole. It will be available in black or white. It will measure 2" L X 1-3/8" W X 7/8"H. It shall be rated for 25A © 300V and 5A @ 600V. The TTS Tool-Less Terminal Strip was designed to improve field termination and installation time while meeting full code compliance and allowing for first round inspection sign off. Built in test ports allow for quick and easy trouble shooting. Available in black or white to help improve circuit identification. Mounting Holes C D �CD Test Port N 81 )3 4wires are _ ' .� 1 all 1 circuit �. .. r,„tr� �A B �� ® ;� A B �I Wires sizes 20-12 AWG �1Ili Stranded or Solid core wire 4 poles / 16 connection points 300V @ 20A 600V @ 5A g---g 1 Terminal Pole IB 4 Connection Points '1%41444'----,/ o i44E%'%\ ® <'^/ ,,•,'off; BB4 4" Sq. Box Bracket dE%%�,,\� (SS000465) \`0 /'�� Versatile and strong enough to hold 20 AWG Stranded wire under 1 point and 12 AWG Solid under the second point. Warning: Do not use Aluminum Conductors with the TTS Terminals per UL 864 Rev. 9 Sect. 12.4. Ordering Information: Part# Description SS000470 TTS Tool-Less Terminal Strip (Black) ;� SS000471 TTS Tool-Less Terminal Strip (White) Be Space Age Electronics, inc. Accessories: ccessories: 800.486.1723 Toll Free SSU00465 BB4 Box Bracket 4" Square 508.485.0966 Local SSU00472 TTP Tool-Less Test Plug Test Probe 508.485.4740 Fax This document is subject to change without notice,see doc#ED0479 for legal disclaimer No Excuses, Just Solutions! ED0409 LT10376 Rev C 2/2 . • '•. MFIaP 4Series ,.mr i War Surge Protection DITEK ® Surge Protection DITEK's DTK-2MHLPB series of signal, data and loop circuit surge protectors provide robust protection in a compact package. This series was designed for ease of 4 _ installation, with convenient field-replaceable modules and a Snap-Track base system, allowing the installer to protectmultiple circuits while utilizing a common ground point. tee. DTK-2MHLP24B Technical Specifications DTK-2MHLP24BWB DTK-2MHLP 5B 12B 24B 36B 48B 75B Product Features Service Voltage: 5V 12V 24V 36V 48V 75V • Protects two pairs per module MCOV: 6V 18V 33V 48V 64V 90V • Multi-stage, SAD technology, hybrid design, Clamping Voltage: 6.8V 21.6V 39V 57V 76V 108V provides the best possible protection Protection Modes: Line Ground (All) • Field replaceable, modular edge card connection design with a single point ground for fast Surge Current 20,000 Amps installation, saves time Rating: • Six voltage levels available to protect all types of Max Continuous 5 Amps voice/data applications Current: • Hard-wired multi-base mounting system allows Data Rate: 200kbps to 2Mbps you to protect up to ten pairs with a common ground. See next page for base part numbers Mechanical Characteristics • Suitable for use on both AC and DC circuits Base Connection Method: 10AWG max screw terminals Applications Module Connection Edge card into mounting base Method: • Fire Alarm Panel NAC, SLC, PIV and IDC Circuits Housing: ABS • Burglar Alarm Panels NAC and IDC Circuits Operating • 70V Speakers and Audio Equipment Temperature: -40°F-158°F (-40°C-70°C) • Low-Voltage Landscape Lighting and Lighting Maximum Humidity: 95%non-condensing Control Circuits • 4-20mA Current Loops Module Module with Base Dimensions: 2.1"Lx1.4Wx1.9"H 3.25L"x1.5"Wx2.6"H (53mm x 36mm x48mm) (83mm x 38mm x 66mm) Weight: 1.2 oz(34g) 2.8 oz(79g) Accessories • To order Module with Base, add "WB"to end of Quality, Standards &Approval part number Agency Approvals: UL497B • Test Module Kit—Part Number DTK-2MHLPTM • DIN Rail Mounting Kit—Part Number DTK-DRK Warranty: Ten Year Limited Warranty Every precaution has been taken to ensure that this literature is accurate and complete.DITEK Corporation assumes no responsEitify and disclaims all liability for damages resulting from the use of this information or for any errors or omissions. One DITEK Center 1720 Starkey Road-Largo,FL 33771 I Doc.Number:SPS-100010-001 Rev 15 04/17rv1ADE IN Phone:1-800-753-2345 Direct:727-812-5000 ©2017 DITEK Corp. Iw t y i o 1411 j, Technical Support:1-888-472-6100 Page 1 of 2 diteksurgeprotection.com NFRA LISTED u S A. Series ion IfilII° . aryl S_ . Protection ..,:. ,, , protect ._, , v ,-„, At ti '..- lar Surge I 9 '' A' Circuit flOCIU ..,,,,,,,,,..) LPB . . .. _ t.t . Surge eiTEK ® Numbers and Dimensions ,...--i ..„, Base Part , Dimensions , . .. #Pairs w (82.5mm x 38.1mm) . Number Protected .., .. .1.50".. N , ' Part 3.25 11 x 2 82.5m , DTK-MB1° 3mill, m x 114. 1 a -•- • 0 4 DTK-2MB 3.25"H x 4-5v" m x 152.4mm) 3.25"H x 3.0n0"WW((82.,,m m x 76.2mm) . ~ ' mia 6 (82.5mm DTK-3-- 3.25.H x 6.00'w (8 8 .7. ,-, W (82.5mm DTK-MB10 DTK-4MB 3.25"H x ' ‘ju 10 DTK- 5MB x 190.5mm) • 49; r ...f. ..?.:,.. , (" 1 . O.- - • ' ' ' —, /;•!•",*..0..1.- 0 # * * . . g * ** , ,t , . rip) i,.., t , . , ' 0 rzi ' _ -0./-7 , 24,! a , , l' , . ...---- 01A. * • . ' '''',.*,..., °#.4.1 ' ,. * ' 1 -i f . -• .- ' ' 1., i DTK-2MB DTK-3MB ., to•0 0, ik,..) ' i a a )". ..ar 0 1 ' r •a '0 I it.41T1I , ••• ' IA . " 1 ... * '4' s/i,'"` .P• vi', r 1 .. ' d 40i) .- •* ' ..*,,r-;:',..r _ ' , ., ., 1.4, 6, 1 ii.t-.)' is •"' '„, • . I ..I). a * - CIP I *• ', ''''''' ' ‘ti, 0 . ;': •.. ..- • •J DTK-5MB 4- ".• . _ .',.. • I .04 4.: g*.** :.; ..e... 57. 1,,.., • -* t e ' DTK-4MB Page 2 of 2 i. .., ',-;c••• m rotection.co .diteksurgeP Si GE Interlogix Product Information wwvv GE-InterlogixSecunty.corn ESL DH Series Electromagnetic Fire Door Holders Overview The DH Series Electromagnetic Fire Door Holders are constructed of the finest materials available.Each wall mount door holder is , made of durable die-cast metal and finished in a high luster . double chrome or brass plating for a high quality appea - -1117 rance. For wall mount units,standard dual voltage AC or DC inputs J' reduce stocking requirements with 12/24V and 24/120V models. The 24/120V model draws a mere 15mA 0 24VAC or DC,helping 1.6 6 keep overall job costs to a minimum. Installation is easy with the ESL DH Series installation - ..� r technique-an adhesive template assures alignment without secondary adjustments.No brackets are required for recessed, flush or surface mounting(the surface mounting box has three conduit ready entries).Plus,the new catch plate features two pivot points and two way adjustability to further ensure perfect �� alignment.Optional extension rods are also available for providing >; the proper gap distance between the door and wall. (Recess mounted door holder includes a 3"extension rod). ESL Door Holders Wall&Floor Mount(insert) The basic units offer superiority reliability with built-in transient protection and low residual magnetism so they release easily Standard Features even on new ADA low pressure door closers. o Extremely low current draw.Only 15mA 0 24V saves on power supplies and backup batteries o New recessed mount for lowest profile look o Dual voltage inputs in each unit reduces stocking requirements o Self-adjusting swivel catch-plate reduces installation time and adjusts to door alignment changes o Optional extension rods make installation even faster 04.a- o Low residual magnetism easily releases even on new ei..!,.--.4'..a,r.".'' ADA low pressure door closers 1 • 0 Built-in transient protection t "' 0 Floor mount units available,both single and double-coil #_f > 213'.**;*? « k s t+, rr.• F u: DH Series Electromagnetic Fire Door Holders Surface Mount Back Box Dimensions Door Magnet o A 6 1 I 4.7" 3.3" 1.1" ��1 4.6" 11.9cm 8.4cm 2.8cm Oi 77. cm `'—� 3.3" o 61m _,• IWI LO7 1.2" Y 3.0cm 2.1" y 2.75" 5.2cm 7.0cm . 2.8" E E 7.1cm 1.1" .95" 2.8cm 2.4cm Extension Rod Applications and Accessories Catch Plate Assembly DHW(Wrench) DH-ERI s7 1)01 ) 201 � I 25" i-b•l F .� 6.4cm III 5..1cm 1.5' 2.54cm DH-ER3 I 2.0" l I`— 5.1cm 3.0" 7.62cm DH Series Electromagnetic Fire Door Holders Dual Voltage Terminal Diagram for Flush Mount, Dual Voltage Terminal Diagram for Floor Mount Recessed or Surface Mount Voltage References C=common O O L=low H=high Low Voltage (C+L) C L H Low Voltage C L H ®® \ J ICS High Voltage I I (C+H) High Voltage Low Voltage Application 1 41 41 C L H C L H High Voltage Application r1 41 C L H CLH Performance Data Model Voltage D :` ^ AC/mATerminals Coil lbs kg.(Nominal) DHX* 1224 12V 30 30 C&L Single 35 15.9 24V 15 15 C&H Single 35 15.9 DHX* 24120 24V 15 15 C&L Single 35 15.9 120V - 15 C&H Single 35 15.9 DHFM'1224 12V 60 60 C&L Double 35 15.9 24V 60 60 C&H Double 35 15,9 DHFM'24120 24V 30 30 C&L Double 35 15.9 120V - 30 C&H Double 35 15.9 *For all models, 'X"represents either F(Flush Mount),FM(Floor Mount single-coil),R(Recessed),or S(Surface Mount). (For Floor Mount,double coil models. NOTE:Voltage supplied by a UL listed control panel 0. DH series :1 *� r LoJ4øIders fi DHS-24120C DHFM1-24120 Door Holder Type of Plating Door Holder #of coils DHS-24120C DHFM1-24120 Type of Mounting Voltage Type of Mounting Voltage LISTED ']j wrrnoveD Ordering Information Model Description Case Qty. Wall Mount DHR-1224C ESL 12 or 24 VDC/VAC,recess-mount,chrome,with 3"Extension Rod 20/case DHR-24120C ESL 24 VDC/VAC 120VAC,recess-mount,chrome,with 3"Extension Rod 20/case DHF-1224C ESL 12 or 24 VDC/VAC,semi-flush-mount,chrome 20/case DHF-1224B ESL 12 or 24 VDC/VAC,semi-flush-mount,brass 20/case DHF-24120C ESL 24 VDC/VAC 120VAC,recess-mount,chrome 20/case DHF-2410B ESL 24 VDC/VAC 120VAC,semi-flush-mount,brass 20/case DHS-1224C ESL 12 or 24VDC/VAC,surface-mount,chrome 20/case OHS-1224B ESL 12 or 24VDC/VAC,surface-mount,brass 20/case DHS-24120C ESL 24VDC/VAC 120VAC,surface-mount,chrome 20/case DHS-24120B ESL 24VDC/VAC 120VAC,surface-mount,brass 20/case Floor Mount DHFM1-1224 Single coil,12 or 24VDC/VAC,floor-mount,brushed steel,UL only,CUL pending 6/case DHFM1-24120 Single coil,24VDC/VAC 120VAC,floor-mount,brushed steel,UL only,CUL pending 6/case DHFM2-1224 Double coil,12 or 24VDC/VAC,floor-mount,brushed steel,UL only,CUL pending 6/case DHFM2-24120 Double coil,24VDC/VAC 120VAC,floor-mount,brushed steel,UL only,CUL pending 6/case Extension Rods DH-ERIC 1"chrome DH-ER1B 1"brass DH-ER3C 3"chrome DH-ER3B 3"brass Accessories DHW Extension rod wrenches DH-BP Back Plate(chrome or brass) DH-ARMC Replacement armature,chrome DH-ARMB Replacement armature,brass OC9 GE Interlogix www.GE-InterlogixSecurity.com 12345 SW Leveton Drive 2266 Second Street North Tualatin,OR 97062 North St.Paul,MN 55109 Phone:503-692-4052 Phone:657-777-2690 USA&Canada:800-547-2556 LISA&Canada:800-777-5485 Technical Service:800-648-7424 Technical Service:800-777-2624 Faxback:800-483-2495 ©2002 GE Interlogix.ANI trademarks are properties of their owners. E-3969-5000KA-0702