Report (166) �-\ 9 x ,. k, . RECEIVED i*q� AUG 9 2018 ' ', i6Z.s *'''.?K#1: ****:****.' y yr r� �+y�i r + i ; Vit frAu 1" r r x %;- - r FIRE PROTECTION, INC. 9095 S.W. Burnham Tigard, OR 97223 LUCKY BRAND WASH SQ 9716 SW WASHINGTON SQ RD #F03 TIGARD, OR 97223 a pl Co 0o,.e. FIRE PROTECTION EQUIPMENT SUBMITTAL tqco Worldwide Contacts www.tyco-fire.com Series RFII — 5.6 K-factor "Royal Flush II" Concealed Pendent Sprinklers Quick & Standard Response, Standard Coverage General stallation or finish. The tip of the Pro- tective Cap can be used to mark the Description center of the ceiling hole into plaster p board or ceiling tiles by gently push- the ceilingproduct against the Pro- r "� The TYCO Series RFII 5.6 K factor, ing 9 , tective Ca When ceilinginstallation "Royal Flush II" Concealed Pendent p Sprinklers Quick Response (3 mm is complete, the Protective Cap is re- ° bulb) and Standard Response (5 mm moved and the Cover Plate/Retainer Assembly is installed. $ bulb), are decorative sprinklers featur- y ing a flat cover plate designed to con- As an option,the Series RFII Standard ceal the sprinkler.These sprinklers are Response(5-mm bulb)"Royal Flush II" optimal for architecturally sensitive ar- Concealed Pendent Sprinklers can be eas such as hotel lobbies, office build- fitted with a silicone Air and Dust Seal. ings,churches,and restaurants. (Refer to Figure 5.) The Air and Dust • TY3531 (3 mm Bulb) is UL Listed, Seal is intended for sensitive areas CUL Listed, Approved (Certif Each sprinkler includes a Cover Plate/ icate No. G4090007), and NYC Ap- Retainer Assembly and a Sprinkler/ where it is desirable to prevent air and proved (MEA 353-01-E) as Quick Support Cup Assembly. The separa- dust from the area above the ceiling to Response. ble, two-piece assembly design pro- pass through the cover plate. • TY3531 (3-mm Bulb) i vides the following benefits: s FM and NOTICE LPCB Approved (Ref. No. 094a/10) • Allows installation of the sprinklers The Series RFII Concealed Pendent Approved as Standard Response. and pressure testing of the fire pro- FactoryMutual and LPCB do not tection system prior to installation Sprinklers described herein must be of a suspended ceiling or applica- installed and maintained in compli approve any concealed sprinklers tion of the finish coating to a fixed ance with this document and with the for quick response. ceilin applicable standards of the National • TY3551 (5-mm Bulb) is UL Listed, g• Fire Protection Association, in addi- C-UL Listed, FM Approved, LPCB • Permits the removal of suspended tion to the standards of any authori- Approved (Ref. No. 094a/9), and ceiling panels for access to building ties having jurisdiction. Failure to do so NYC Approved (MEA 353-01-E) as service equipment without having may impair the performance of these Standard Response. to first shut down the fire protection devices. system and remove sprinklers. The owner is responsible for maintain- Approvals for Air and Dust Seal • Provides for 1/2 inch (12,7 mm) of ing their fire protection system and de UL and C UL Listed for use with the vertical adjustment to allow a mea- vices in proper operating condition. RFII Standard Response Concealed sure of flexibility in determining the The installing contractor or sprinkler Sprinkler(TY3551). length of fixed piping to cut for the manufacturer should be contacted Maximum Working Pressure sprinkler drops. with any questions. Maximum 250 psi (17,3 bar) by UL, The Series RFII Sprinklers are shipped C-UL, and NYC with a Disposable Protective Cap.The Sprinkler Protective Cap is temporarily removed p Maximum 175 psi (12,1 bar) by FM, during installation and replaced to help Identification VdS, and LPCB protect the sprinkler during ceiling in- Temperature Rating Number (SIN) 155°F(68°C)Sprinkler with IMPORTANT TY3531 — 3 mm bulb 139°F(59°C) Plate Always refer to Technical Data Sheet TFP700 for the "INSTALLER TY3551 — 5 mm bulb 200°F(93°C)Sprinkler with WARNING" that provides cautions 165°F(74°C) Plate with respect to handling and instal- Technical Discharge Coefficient lation of sprinkler systems and corn- K=5.6 GPM/ sit/2 80,6 LPM/bars 2 ponents. Improper handling and in- Data p ( ) stallation can permanently damage Adjustment a sprinkler system or its components Sprinkler Approvals 1/2 inch(12,7 mm) and cause the sprinkler to fail to Approvals apply only to the service operate in a fire situation or cause it conditions indicated in the Design Cri- Finishes to operate prematurely teria section. See the Ordering Procedure section. Page 1 of 4 MARCH 2013 TFP181 TFP181 Page 2 of 4 Physical Characteristics 1/2" NPT 7 / SEALING Frame Bronze ' ASSEMBLY Support Cup Chrome Plated Steel ` Guide Pins Stainless Steel FRAME 1'0 �\ '! Deflector Bronze Compression Screw Brass , ` , CAP • Bulb Glass / •-'/ Cap Bronze or Copper SUPPORT Sealing Assembly Beryllium Nickel w/TEFLON CUP WITH FORMED I BULB Cover Plate Brass Retainer Brass THREADS Ejection Spring Stainless Steel O Desi n I I COMPRE SCREW ION Criteria PINS(2)GUIDE ' �/ AThe TYCO Series RFII 5.6 K-factor, DEFLECTOR "Royal Flush II" Concealed Pendent ' L `_ (DROPPED Sprinklers are intended for fire protec- DEFLECTOR i iti_s ,_________/ POSITION) tion systems designed in accordance E_ _.- = with the standard installation rules rec- ognized by the applicable Listing or SPRINKLER/SUPPORT CUP Approval agency;for example, UL List- ASSEMBLY ing is based on NFPA 13 and VdS Ap- proval is based on the CEA 4001. THREAD INTO I RETAINER For more information on LPCB and SUPPORT I WITH THREAD CUP UNTIL t O O DIMPLES VdS Approvals, contact Tyco Fire Pro- MOUNTING J tection Products at the following office: SURFACE IS EJECTION Enschede, Netherlands FLUSH WITH SPRING Telephone:31-53-428-4444 CEILING Fax:31-53-428-3377 The Series RFII Concealed Pendent _—SJ ,.--- Sprinklers are only listed and approved -7 with the Series RFII Concealed Cover Plates having a factory applied finish. SOLDER COVER TABS(3) COVER PLATE/RETAINER PLATE NOTICE ASSEMBLY Do not use the Series RFII in applica- FIGURE 1 tions where the air pressure above MODEL RFII CONCEALED SPRINKLER the ceiling is greater than that be- ASSEMBLY low. Down drafts through the Sprin- kler/Support Cup Assembly can delay Installation Do not attempt to compensate for in- sprinkler operation in a fire situation, sufficient adjustment in the Sprinkler The TYCO Series RFII 5.6 K-factor, by under-or over-tightening the Sprin- Operation "Royal Flush II" Concealed Pendent kler/Support Cup Assembly. Re-adjust Sprinklers must be installed in accor- the position of the sprinkler fitting to When exposed to heat from a fire, the dance with this section. suit. Cover Plate, normally soldered to the General Instructions Step 1. Install the sprinkler only in the Retainer at three points, falls away to Do not install any bulb type sprinkler if expose the Sprinkler/Support Cup pendent position with the center line of the sprinkler perpendicular to the Assembly. the bulb is cracked or there is a loss mounting surface. of liquid from the bulb. With the sprin- Step 2. Remove the Protective Cap. The Deflector — supported by the kler held horizontally, a small air bub- Guide Pins — then drops down to its ble should be present. The diameter Step 3. With pipe thread sealant ap- operational position. of the air bubble is approximately 1/16 plied to the pipe threads, hand-tighten The glass bulb contains a fluid that ex- inch (1,6 mm)for the 155°F (68°C) and the sprinkler into the sprinkler fitting. pands when exposed to heat. When 3/32 inch(2,4 mm)for the 200°F(93°C) Step 4. Wrench-tighten the sprinkler the rated temperature is reached, the temperature ratings. using only the RFII Sprinkler Wrench. fluid expands sufficiently to shatter the A leak tight 1/2 inch NPT sprinkler joint (Refer to Figure 3.) Apply the RFII glass bulb, activating the sprinkler and should be obtained byapplying a min- kler Wrench to the Sprinkler as shown in Figure 3. allowing water to flow. imum to maximum torque of 7 to 14 Step 5. Replace the Protective Cap ft. lbs. (9,5 to 19,0 Nm). Higher levels by pushing it upwards until it bottoms of torque can distort the sprinkler In- out against the Support Cup. (Refer let with consequent leakage or impair- to Figure 4.) The Protective Cap helps ment of the sprinkler. prevent damage to the Deflector and TFP181 Page 3 of 4 FACE OF CLEARANCE HOLE CLEARANCE SPRINKLER DIAMETER HOLE FITTING DIMENSION C SPRINKLER j 'i��� SUPPORT CUP ASSEMBLY I ft ( 1/2"(12,7 mm) 1 11111/11 THREADED .DADJUSTMENT �) ��r ����� �� FACE l — ���__. OF CEILING, RETAINING RING I I /•_ • i MOUNTING l • SURFACE �4 1 \ / Q I • j FIGURE 4 DISPOSABLE PROTECTIVE CAP i ‘..\ _ _ I � Arms during ceiling installation and/or -z r_� finish. You can also use the Protective -r T Cap to locate the center of the clear- 3/16"to 11/16" MANUFACTURER DEFLECTOR COVER PLATE ance hole by gently pushing the ceiling (4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER material up against the center point of REFERENCE 3/32" (2,4 mm) POSITION ASSEMBLY the Protective Cap. COVER PLATE COVER PLATE NOTICE -PROFILE DEPTH DIAMETER As long as the Protective Cap remains DIMENSION B DIMENSION A in place, the system is considered A:3-1/4 inches(82,6 mm) C:2-3/8 to 2-5/8 inches(60,3 to 66,7 mm) "Out of Service". Step 6.After the ceiling has been com- B:3/16 inches(4,8 mm) D:1-3/4 to 2-1/4 inches(44,5 to 57,2 mm) pleted with the 2-1/2 inch(63,5 mm)di- ameter clearance hole and in prepa- FIGURE2 ration for installing the Cover Plate/ SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS Retainer Assembly, remove and dis- card the Protective Cap.Verify that the Deflector moves up and down freely. If the Sprinkler is damaged and the Ij�l, , FRAME (j��� Deflector does not move up and down loll — r, freely, replace the entire Sprinkler. / ARM Do not attempt to modify or repair a \ �� damaged sprinkler. �� pSUPPORT OA ' _ Ste 7. When installing an Air and CUP ' , Dust Seal, refer to Figure 5; otherwise, , proceed to Step 8. To attach the Air � , ■'. / ' and Dust Seal, verify the angle of the I■I ��� outside edge of the seal is oriented y ac- cording to Figure 5. Start the edge of -'— ---- the Retainer in the grooved slot of the 7/8"(23 mm) 0 Air and Dust Seal and continue around SQUARE the retainer until the entire Air and Dust Seal is engaged. -` Step 8. Screw on the Cover Plate/ ALIGN /� Retainer Assembly until the Retainer ARROWS WITH / 1 I \ (shown in Figure 2)or the Air and Dust FRAME ARMS \_ Seal (shown in Figure 5) contacts the la� ceiling. Do not continue to screw on l 1 i the Cover Plate/Retainer Assembly ACCEPTS so that it lifts a ceiling panel out of its , 0 1/2"SOCKET normal position. If you cannot engage DRIVE the Cover Plate/Retainer Assembly FIGURE 3 with the Support Cup or you cannot SPRINKLER WRENCH engage the Cover Plate/Retainer As- RFIIsembly sufficiently to contact the ceil- ing, you must reposition the Sprinkler Fitting. TFP181 Page 4 of 4 Care and SUPPORT SPRINKLER FACE OF ORIENT CUP CEILING SEAL Maintenance BEVEL AS ML.--- SHOWN The TYCO Series RFII 5.6 K-fac i -_ 1 , COVER PLATE �� tor, "Royal Flush II" Concealed Pen- ; i RETAINER - dent Sprinklers must be maintained ; and serviced in accordance with this �jaill (; ASSEMBLY _ _ :\ section. ;� .' Before closing a fire protection system �( I - I main control valve for maintenance i EMI lin- . / AIR work on the fire protection system that /` !I�/I�. �� AND DUST it controls, obtainpermission to shutT�_�in �__. " SEAL �� LIP OF COVER down the affected fire protection sys- RETAINER PLATE tem from the proper authorities and FIGURE 5 notify all personnel who may be affect OPTIONAL AIR AND DUST SEAL FOR SERIES RFII(TY3551) ed by this action. Absence of the Cover Plate/Retainer If you must remove a sprinkler, do not Ordering Assembly can delay sprinkler opera- reinstall it or a replacement without re- tion in a fire situation. installing the Cover Plate/Retainer As- Procedure When properly installed, there is a sembly. If a Cover Plate/Retainer As- nominal 3/32 inch (2,4 mm) air gap be- sembly becomes dislodged during Contact your local distributor for tween the lipof the Cover Plate and the service, replace it immediately. availability. When placing an order, ceiling, as shown in Figure 2. The owner is responsible for the in- indicate the full product name. This air gap is necessary for proper spection, testing, and maintenance of Sprinkler/Support operation of the sprinkler. If the ceil- their fire protection system and devic p pport Cup Assembly ing requires repainting after sprinkler es in compliance with this document, Specify: Series RFII (specify SIN), installation, the new paint as well as with the applicable stan- K=5.6, "Royal Flush II" Pendent Sprin- does not seal ensure any thatof the air gap. dards of the National Fire Protection klers (specify) temperature rating and Association(e.g., NFPA 25), in addition (specify)finish, P/N (specify). Do not pull the Cover Plate relative to to the standards of any other authori- the Enclosure.Separation may result. ties having jurisdiction. Contact the in- 155°F(68°C) 200°F(93°C) Sprinklers which are found to be leak stalling contractor or sprinkler manu- TY3531 51-792-1-155 51-792-1-200 ing or exhibiting visible signs of corro facturer regarding any questions. TY3551 51-790-1-155 51-790-1-200 sion must be replaced. Automatic sprinkler systems should be Separately Ordered Cover Plate/ Automatic sprinklers must never be inspected,tested,and maintained by a Retainer Assembly: plated, coated, or other- qualifiedncInspectionoal Service in accor- painted, /oSpecify: (temperature with local requirements and/or P y: rating from be- wise altered after leaving the factory. national code. low) Series RFII Concealed Cover Modified sprinklers must be replaced. Plate with(finish), P/N (specify). Sprinklers that have been exposed to 139°F(ss°c)(a) 165°F(74°c)(b) corrosive products of combustion, but Grey White have not operated,should be replaced (RAL9002) 56-792-0-135 56-792-0-165 if they cannot be completely cleaned Brass 56-792-1-135 56-792-1-165 by wiping the sprinkler with a cloth or Pure White(c) by brushing it with a soft bristle brush. (RAL9010) 56-792-3-135 56-792-3-165 Care must be exercised to avoid dam- Signal White (RAL9003) 56-792-4-135 56-792-4-165 age to the sprinklers - before, during, Jet Black and after installation. Sprinklers dam- (RAL9005) 56-792-6-135 59-792-6-165 aged by dropping, striking, wrench Brushed twist/slippage, or the like, must be re- chrome 56-792-8-135 56-792-8-165placed.Also, replace any sprinkler that Chrome 56-792-9-135 56-792-9-165 has a cracked bulb or that has lost Custom 56-792-X-135 56-792-x-165 liquid from its bulb. (Ref. Installation (a) For use with 155°F(68°C)sprinklers. Section.) (b) For use with 200°F(93°C)sprinklers. (c) Eastern Hemisphere sales only. Exercise care to avoid damage to sprinklers before, during, and after in- Sprinkler Wrench stallation.Replace sprinklers damaged by dropping, striking, wrench twisting, Specify: RFII Sprinkler Wrench, wrench slipping, or the like. Also, P/N 56-000-1-075. re- place any sprinkler that has a cracked Air and Dust Seal bulb or that has lost liquid from its Specify:Air and Dust Seal, bulb.(Refer to the Installation section.) P/N 56-908-1-001. GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2013 Tyco Fire Products,LP. All rights reserved. Vico TEFLON is trademark of The DuPont Corporation. L ti,ii Worldwide www.tyco-fire.com Fire Protection Contacts Products Series TY-FRB — 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Quick Response, Standard Coverage General tained when exposed to corrosive at- mospheres. Although corrosion resis- Description tent coated sprinklers have passed the standard corrosion tests of the appli- The Series TY-FRB, 5.6 K-factor, Hor- cable approval agencies,the testing is izontal and Vertical Sidewall Sprin not representative of all possible cor- rosive atmospheres. Consequently, it d' -iii.f. klers described in this data sheet is recommended that the end user be ..,,:IIIITI: c,,0* ) are quick response standard cover- consulted with respect to the serbil I #a, age, decorative 3 mm glass bulb type ity of these coatings for any given cor- spray sprinklers designed for use in rosive environment.The effects of am- light and ordinary hazard, commer- cial occupancies such as banks, ho- chemicals, temperature, concentration of tels, shopping malls, etc.They are de chemicals, and gas/chemical velocity, signed for installation along a wall or should be considered, as a minimum, the side of a beam and just beneath a along with the corrosive nature of the smooth ceiling. Sidewall sprinklers are chemical to which the sprinklers will commonly used instead of pendent or be exposed. upright sprinklers due to aesthetics or building construction considerations, NOTICE where piping across the ceiling is not The Series TY-FRB Sprinklers de desirable. scribed herein must be installed and compliance maintained in with this The recessed version of the Series TY-FRB Horizontal Sidewall Sprin- document, as well as with the appli kler is intended for use in areas with cable standards of the National Fire a finished wall. It uses a two-piece Protection Association, in addition to Style 10 Recessed Escutcheon with the standards of any other authorities 1/2 inch(12,7 mm)of recessed adjust having jurisdiction. Failure to do so ment or up to 3/4 inch(19,1 mm)of to- may impair the performance of these tal adjustment from the flush sidewall devices. position, or a two-piece Style 20 Re- The owner is responsible for main- cessed Escutcheon with 1/4 inch (6,4 taining their fire protection system mm) of recessed adjustment or up to and devices in proper operating con- : "TM 1/2 inch (12,7 mm) of total adjustment dition. Contact the installing contrac- from the flush sidewall position. The tor or sprinkler manufacturer with any adjustment provided by the Recessed questions. Technical Escutcheon reduces the accuracy to which the fixed pipe nipples to the Sprinkler Data sprinklers must be cut. Corrosion resistant coatings, where Identification Approvals applicable, are utilized to extend the UL and C-UL Listed. life of copper alloy sprinklers beyond Numbers FM, LPCB, and NYC Approved. that which would otherwise be ob- (Refer to Table A for complete approv- TY3331 Horizontal al information including corrosion re- TY3431 Vertical sistant status.) IMPORTANT Always refer to Technical Data Maximum Working Pressure Sheet TFP700 for the "INSTALLER Refer to Table B. WARNING" that provides cau- Discharge Coefficient tions with respect to handling K=5.6 GPM/psi1/2(80,6 LPM/bar1/2) and installation of sprinkler sys- tems and components. Improp- Temperature Ratings er handling and installation can Refer to Table A. permanently damage a sprin- Finishes kler system or its components Sprinkler: Refer to Table C. and cause the sprinkler to fail Recessed Escutcheon:Signal or Pure to operate in a fire situation or cause White,Jet Black, Chrome Plated, or it to operate prematurely. Brass Plated. Page 1 of 6 FEBRUARY 2014 TFP176 TFP176 Page 2 of 6 DEFLECTOR Installation 1 - Frame 2 Button HAT _____) 5 frAga o to The Series TY-FRB, 5.6 K-factor, Hori- 3 - Sealing R, zontal and Vertical Sidewall Sprinklers Assembly I 41 must be installed in accordance with 4 Bulb Sy, tiger,, 0 this section. 5 Compression General Instructions Screw 6 - Deflector* /AI 4 2 3 1 Do not install any bulb type sprin kler if the bulb is cracked or there is • a loss of liquid from the bulb. With the 9/16" WRENCH 1/2"** sprinkler held horizontally, a small air (14,3 mm) FLATS NPT bubble should be present. The diam- eter of the air bubble is approximately —�I / 1/16 inch(1,6 mm)for the 135°F(57°C) �� ~� ��� to 3/32 inch (2,4 mm) for the 286°F ��� / tillW (141°C)temperature ratings. ��'ei. A leak tight 1/2 inch NPT sprinkler joint • should be obtained with a torque of 7 1-13/16" 7/16�� to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher (46 mm) (11,1 mm) levels of torque may distort the sprin- NOMINAL - kler and cause leakage or impairment CENTERLINE MAKE IN of the sprinkler. OF SPRINKLER WATERWAY Do not attempt to make-up for insuf- 1-1/2" ficient adjustment in the escutcheon x(38,1 mm) plate by under-or over-tightening the *Temperature rating sprinkler. Readjust the position of the is indicated on 2-3/16" sprinkler fitting to suit. Deflector. (55,6 mm) STYLE ESCUTCHEON Series TY-FRB Horizontal and ** Pipe thread 10 or 20 — PLATE SEATING Vertical Sidewall Sprinkler connections per RECESSED SURFACE Installation ISO 7-1 can be ESCUTCHEON I The Series TY-FRB Horizontal and provspecial ded on ' 1� ins Vertical in cll Sprinklers must bol- special request. � installed in accordance with the fol- -^� lowing instructions. (73,0 mm lifigallin Step 1. Horizontal sidewall sprinklers . are to be installed in the horizontal po sition with their centerline of waterway perpendicular to the back wall and parallel to the ceiling.The word "TOP" on the Deflector is to face towards the ceiling. Vertical sidewall sprinklers are to be FIGURE 1 installed in the pendent or upright po- 5.6 K-FACTOR QUICK RESPONSE sition with the arrow on the Deflector SERIES TY-FRB HORIZONTAL SIDEWALL(TY3331)SPRINKLERS pointing away from the wall. Characteristics Step 2. With pipe thread sealant ap- PhysicalDesign plied to the pipe threads, hand tighten Frame Bronze the sprinkler into the sprinkler fitting. Button Brass/Copper Criteria Sealing Assembly Beryllium Nickel w/ Step 3. Tighten the sprinkler into the . TEFLON The Series TY FRB5.6 K ftHi sprinkler fitting using only the W-Type , acor, or, Bulb Glass6 Sprinkler Wrench (Ref. Figure 5), Compression Screw Bronze zontal and Vertical Sidewall Sprinklers With reference to Figure 1 or 2, the W- HSW Deflector Bronze are intended for fire protection sys- Type 6 Sprinkler Wrench is to be ap- VSW Deflector copper tems designed in accordance with the standard installation rules recognized plied to the wrench flats. Operation by the applicable Listing or Approval agency (e.g., UL Listing is based on The glass bulb contains a fluid which the requirements of NFPA 13, and FM expands when exposed to heat.When Approval is based on the requirements the rated temperature is reached, the of FM's Loss Prevention Data Sheets). fluid expands sufficiently to shatter Only the Style 10 or 20 Recessed Es- the glass bulb, allowing the sprinkler cutcheon, as applicable, is to be used to activate and water to flow. for recessed horizontal installations. TFP176 Page 3 of 6 Series TY-FRB Recessed Horizontal Sidewall Sprinkler *Temperature ** Pipe thread 1 - Frame 4 - Bulb 7 - Ejection Installation rating is connections 2 - Button 5 - Compression Spring indicated on per ISO 7-1 can 3 - Sealing Screw The Series TY-FRB Recessed Hori- Deflector. be provided on Assembly 6 - Deflector* zontal Sidewall Sprinklers must be special request. installed in accordance with this A section. ARROW MUST Step A. Recessed horizontal sidewall POINT AWAY ,----<sprinklers are to be installed in the 7/1m FROMPFAND BE V ESCUTCHEON (11,1 mm) PERPENDICULAR V O horizontal position with their center- PLATE SEATING NOMINAL TO THE BACK line of waterway perpendicular to the SURFACE 1/2"** MAKE-IN WALL SURFACE4 back wall and parallel to the ceiling. NPT The word "TOP" on the Deflector is to face towards the ceiling. I 11 f����—� ,, .._7lIS� Step B.After installing the Style 10 or �O� FLOW��` \�5 20 Mounting Plate over the sprinkler } threads,hand tighten the sprinkler into 2-3/16" Am 2-3/16" I 4 the sprinkler fitting. (55,6 mm) f rx (55,6 mm)Step C. Tighten the sprinkler into the 1-1/2" —� QrR * 2 sprinkler fitting using only the W-Type (38,1 mm) WRENCH/ mm V 7 Recessed Sprinkler Wrench (Ref. FLATS 7 i 3 Figure 6). With reference to Figure .� 1, the W-Type 7 Recessed Sprinkler — ����� 1 Wrench is to be applied to the sprin SHOWN SHOWN CROSS kler wrench flats. PENDENT UPRIGHT SECTION Step D. After the ceiling has been in- FIGURE 2 stalled or the finish coat has been ap 5,6 K-FACTOR QUICK RESPONSE plied, slide on the Style 10 or 20 Clo SERIES TY-FRB VERTICAL SIDEWALL(TY3431)SPRINKLERS sure over the Series TY-FRB Sprinkler and push the Closure over the Mount- ing Plate until its flange comes in con- if they cannot be completely cleaned The owner is responsible for the in- tact with the ceiling. by wiping the sprinkler with a cloth or spection, testing, and maintenance by brushing it with a soft bristle brush. of their fire protection system and de- Care and Care must be exercised to avoid dam- vices in compliance with this docu- age to the sprinklers before, during, ment, as well as with the applicable Maintenance and after installation. Sprinklers dam- standards of the National Fire Pro- aged by dropping, striking, wrench addion Association (e.g., NFPA 25), in The Series TY-FRB,5.6 K-factor, Hori- twist/slippage, or the like, must be addition to the standards of any oth- zontal and Vertical Sidewall Sprinklers replaced. Also, replace any sprinkler er authorities having jurisdiction. The must be maintained and serviced in that has a cracked bulb or that has installing contractor or sprinkler man- accordance with this section. lost liquid from its bulb. (Ref. Installa- ufacturer should be contacted relative tion Section to any questions. Before closing a fire protection sys- )• tem main control valve for mainte- The owner must assure that the sprin- It is recommended that automatic nance work on the fire protection sys- klers are not used for hanging any ob- sprinkler systems be inspected, test- tem that it controls,permission to shut jects and that the sprinklers are only ed, and maintained by a qualified In- down the affected fire protection sys- cleaned by means of gently dusting spection Service in accordance with tem must be obtained from the prop- with a feather duster; otherwise, non- local requirements and/or national er authorities and all personnel who operation in the event of a fire or inad- codes. may be affected by this action must vertent operation may result. be notified. Frequent visual inspections are rec- Absence of an escutcheon, which is ommended to be initially performed used to cover a clearance hole, may for corrosion resistant coated sprin- delay the time to sprinkler operation in klers, after the installation has been a fire situation. completed,to verify the integrity of the Sprinklers that are found to be leaking corrosion resistant coating. Thereaf- or exhibiting visible signs of corrosion ter, annual inspections per NFPA 25 must be replaced. should suffice; however, instead of in- specting from the floor level, a random Automatic sprinklers must never be sampling of close-up visual inspec- painted, plated, coated or other- tions should be made, so as to better wise altered after leaving the factory. determine the exact sprinkler condi- Modified sprinklers must be replaced. tion and the long term integrity of the Sprinklers that have been exposed to corrosion resistant coating, as it may corrosive products of combustion, but be affected by the corrosive condi- have not operated,should be replaced tions present. TFP176 Page 4 of 6 5/8±1/4" !� (15,9±6,4 mm) �•' MOUNTING FACE OF WRENCH RECESS SURFACE �- SPRINKLER (END"A"USED FOR FITTING 1/2" NPT MODELS) A - FIGURE 5 CLOSURE W-TYPE 6 • SPRINKLER WRENCH �� 2-7/8" DIA. SERIES (73,0 mm) TY FRB linirAM _�.,illll 2-1/4" DIA. WRENCH !JI (57,2 mm) RECESS MOUNTING `. PLATE IV 1/8" (3,2 mm) 1-1/4"(31,8 mm) 3/4"(19,1 mm) PUSH WRENCH 3/4"(19,1 mm) 1/4"(6,4 mm) IN TO ENSURE ENGAGEMENT FIGURE 3 WITH SPRINKLER SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER WRENCHING AREA WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT FIGURE 6 STYLE 10 RECESSED ESCUTCHEON W-TYPE 7 RECESSED SPRINKLER WRENCH 1/2±1/8" (12,7±3,2 mm) MOUNTING FACE OF SURFACE SPRINKLER FITTING A CLOSURE A - 2-7/8" DIA. SERIES � (73,0 mm) TY-FRB I•_�,11III 2-1/4"(57,2 D) `I MOUNTING PLATE /1 1/8" - (3,2 mm) 1-1/4" (31,8 mm) 1/2"(12,7 mm) 1"(25,4 mm) 1/4"(6,4 mm) FIGURE 4 SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON TFP176 Page 5 of 6 SPRINKLER FINISH(See Note 11) K TYPE TEMP. BULB NATURAL CHROME LIQUID BRASS PLATED POLYESTER*** LEAD COATED 135°F(57°C) Orange HORIZ. 155°F(68°C) Red SIDEWALL 175°F(79°C) Yellow 1,2,3,4,9, 10 1,2,3,9 1,2,3,9 (TY3331) 200°F(93°C) Green 286°F(141°C) Blue 5.6 RECESSED 135°F(57°C) Orange 1/2" HORIZ. 155°F(68°C) Red NPT SIDEWALL 1,2,4,9, 10 1,2,9 N/A (TY3331)* 175°F(79°C) Yellow Figure 3 200°F(93°C) Green RECESSED 135°F(57°C) Orange HORIZ. 155°F(68°C) Red SIDEWALL 1,2,3,4,9 N/A (TY3331)** 175°F(79°C) Yellow Figure 4 200°F(93°C) Green VERTICAL 135°F(57°C) Orange SIDEWALL 155°F(68°C) Red 5.6 (TY3431) 1/2" Installed 175°F(79°C) Yellow 5,6,7,8,9 5,6,7,9 NPT Pendent or 200°F(93°C) Green Upright 286°F(141°C) Blue NOTES: 1. Listed by Underwriters Laboratories,Inc.(UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector to ceiling distance. 2. Listed by Underwriters Laboratories Inc.for use in Canada(C-UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector to ceiling distance. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers for use in Light Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector to ceiling distance. 4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007a/04)at a 4 to 6 inch(100 to 150 mm)top of deflector to ceiling distance.The LPC does riot rate the thermal sensitivity of horizontal sidewall sprinklers. 5. Listed by Underwriters Laboratories,Inc.as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. 6. Listed by Underwriters Laboratories for use in Canada(C-UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. 7. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers for use in Light Hazard Occupancies. 8. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06&007a/04)as Quick Response Sprinklers. 9. Approved by the City of New York under MEA 354-01-E. 10. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)at a 4 to 6 inch(100 to 150 mm)top of deflector to ceiling distance.The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 11. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion Resis- tant Sprinklers.Where Lead Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as Corrosion Resistant Sprinklers. Installed with Style 10(1/2"NPT)3/4"Total Adjustment Recessed Escutcheon. "Installed with Style 20(1/2"NPT)1/2"Total Adjustment Recessed Escutcheon. '.'Frame and deflector only. TABLE A LABORATORY LISTINGS AND APPROVALS TFP176 Page 6 of 6 SPRINKLER FINISH K TYPE NATURAL BRASS CHROME PLATED POLYESTER LEAD COATED HORIZONTAL SIDEWALL 250 PSI(17,2 BAR) (TY3331) or 175PSI(12,1 BAR) 5.6 RECESSED HORIZ. 1/2" SIDEWALL(TY3331) (SEE NOTE 1) NPT VERTICAL SIDEWALL (TY3431) 175 PSI(12,1 BAR) NOTES: 1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories, Inc.(UL);the Listing by Underwriters Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York. TABLE B MAXIMUM WORKING PRESSURE P/N 57 - XXX - X - XXX I SIN SPRINKLER TEMPERATURE FINISH RATINGS HORIZONTAL SIDEWALL TY3331 1 NATURAL BRASS 135 135°F(57°C) ® VERTICAL SIDEWALL TY3431 3 PURE WHITE(RAL9010)* 155 155°F(68°C) POLYESTER 4 SIGNAL WHITE(RAL9003) 175 175°F(79°C) POLYESTER 5 JET BLACK(RAL9005)** 200 200°F(93°C) POLYESTER 7 LEAD COATED 286 286°F(141°C) 9 CHROME PLATED *Eastern Hemisphere sales only. **Available in 155°F(68°C)or 200°F (93°C)temperature rating only. TABLE C PART NUMBER SELECTION SERIES TY-FRB HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS Ordering Sprinkler Assemblies with NPT Recessed Escutcheon Thread Connections: Specify:Style(10 or 20) Recessed Es- 1 Procedure Specify: Series TY-FRB (specify SIN), cutcheon with (specify*) finish, P/N (specify K-factor), (specify) Horizontal (specify*). Contact your local distributor for avail- Sidewall or Vertical Sidewall Sprinkler, Refer to Technical Data Sheet TFP770 ability. When placing an order, indi- Standard Response, Standard Cov- cate the full product name and Part erage, (specify) temperature rating, Sprinkler Wrench Number(P/N). (specify) finish or coating, P/N (spec- Specify: W-Type 6 Sprinkler Wrench, ify from Table C) P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2013 Tyco Fire Products,LP. All rights reserved. Vico TEFLON is trademark of The DuPont Corporation. " Fire Protection Products Eddythread 40 A Lightweight Schedule 40 Replacement Pipe That Has a Corrosion Resistance Ratio of 1.0 Bull Moose Tube Company has been making pipe for a long time and is recognized as a producer of quality pipe products. Eddythread 40 is designed with the same thoroughness as our other fine pipe products and now our customers have an option to buy a carefully designed replacement for Schedule 40 that: • Has a Corrosion Resistance Ratio of 1.0 • Has a Pressure Rating of 300 psi • Is Lighter Weight Than Schedule 40 • Is Approved by Factory Mutual and Listed by Underwriters Laboratories • Is Produced in Accordance to ASTM A-135 and A-795 • Can be Used With Standard Schedule 40 Threaded Fittings, Couplings and Valves • Is Produced From Steel With Excellent Properties of Strength and Threadability • Can be Used in Wet, Dry, Preaction, and Deluge Type Sprinkler Systems* • Offers Lower Freight Costs EDDYTHREAD 40 SPECIFICATIONS 1 1.461 1.083 70 1 1/4 2.070 1.418 51 1 1/2 2.547 1.654 44 2 3.308 2.123 30 CORROSION RESISTANCE RATIOS 1 1.00 1.00 1 1/4 1.00 1.00 1 1/2 1.00 1.00 2 1.00 1.00 *Eddythread 40 can be hot dipped galvanized to meet FM's requirement for dry systems (�„Nt�t1819 Clarkson Road For additional information, C u� us 4 "� Chesterfield,MO 63017 contact your salesperson today at API 1 f E�uLL Moose TUBE COMPANY (800)325 446 (800)325-4467 or(636)537-2600 LISTED CCCJJJ FAX:(636)537-7 2645 in the USA,or from Canada www.bullmoosetube.com call(800)882-4666 41> A L O company e-mail:salesAbullmoosetube.com APPROVED All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation. 8/08 0 Yy •Pool 11/111. PlICII: k N A '%,.>3.,..,;•...:,.,•,110.,.,.:,h ry 't :�§"m J:Rm "Y r, e' , F„” '"� 4tiCP g� , ," . •5,litfitti,.:„,...„•,.',.„.„,„,:/,:.:::t1;11't'll''''i::::11;1it1:11:1;i,t';:::',.,7„:'••,:!'•.'":•,':'::!';:;;;,::'•:':'!',:•':':'•I••''''!••:'•'''''•'•'l':'':''''':':':''''''''''"". ,( f,a y. (Pliti:$ ry4rp 2^^ q' MW, ,CZ 1, N}iffi4;4 • . .....;'.1.'::.,:!.'1•*i.'..:'.:.'.1:....,.t...,:''•'•i•,.!..,!:....:..:..:..!.':•••:.,•,.:••;..i.l..:',11.,,.!..1':•,.:. .,„:1:4,........" 4 r .,,,,„„°..i.!,:!1,1,1„511111,4,11,1iiiAlivill!i'•:::.;::::::::':':::::::,'•'•,:,•,,,:likkAnli,..,„„:i:ii„il.:•:1!,•,•!0.!,,,,!::::::::',...'•'•:::•:..,:.: ' 1—"""*4—•.' '''I'....:::':''':::'::::'\::':::': ':11:4: t''''''' '14..%:'. .,.•...,......:...., .,..„..,,:.:........„....•••. „,.,.,„..,:„.„..........,. E•imi ...,..,,,,„.„.1,1,•„.. ., • .. , 'kik" lgidijtlillZM:MtEkiii„i,g::;i:.;4,g4tgIMMIZNI,I1N1;3'4 „1;;;:;,;,: ;:!:i,;;;jitijrig::!Siail:ijijpNI!.4 Ai';',...,... ''''''",\„,,,........ .,,,,,e;,,,,‘„,„„,,,,,,,,,,,„,,,,,,.,,,,,,,,,„,,,,,,,,,,,,,a4,44#4,.„,.,:,01.4..„*..'.„:„.,,,,„,,,,,,,,,,,,,,,,,00,,,,,,o,u0,4*04%,,,,001.0,-:-,...,,,, ,,...,,:•...4,,,„:,„,,,„,„„„,,,,,,„,,,„,,,„,„,„,,,,,,,,,,,,„,,,,,,„„,:,,,:„,,,„,,,,„,..,,,.,„:"„:„..,,,,,,,,,,,,,,,,,„„,,,„,,,,,,,,,,,,,,,t,„.„,,o,,;,,..„,„„,„,,,„...„..,.......:..,:,.„.........„.„..:::„..„,,.....,,,,,,,,,,„:„.„,,,,,......;......„:„.• .........„,..:,,,.„,;„,,,„„,„,„„:„,,.„,„,,,,,„:„.„,,,„,„.t.:,.: ..,„:„,..,,.. 1114,4 y h ka`a1`A '4; '@ A SMITH = COOPEI ® INTERNATIONAL Ductile Iron Threaded Fittings Specifications • 4, branded ductile iron threaded fittings are UL Listed and FM Approved at 500 psi • Rated to 300 WSP • Cel US Ductile iron castings conform to ASTM A536 LISTED • Fitting dimensions conform to ASME B16.3 • Bushings and plugs conform to ASME B16.14 • Fittings are 100% air tested APPROVED • NPT threads on all fittings conform to ASME B1.20.1 • Independent lab verification that fittings meet applicable chemical &physical properties • Manufacturing facilities are ISO 9001:2008 and ISO 14001 Temperature Working Pressure, Nonshock psiG Degrees F 300# Class Threaded Fittings -20 to 100 500 150 500 71, 200 480 250 460 300 440 350 420 400 400 450 380 ..y 500 360 550 340 600 320 650 300 r -'4"-;;,i14-4,, ' Ductile Iron Fittings- Class 300 UL/FM :;_i_; F! c ® us APPROVED A Fig. 35E 3-90°Elbow LISTED Size A Packing Weight in Part Number in Inner Master lb ---N 1/2 35E 3004 1.13 100 200 0.2 �� 3/4 35E 3006 1.31 70 140 0.3 i A 1 35L 3010 1.50 40 80 0.5 ✓�; 1-1/4 35E 3012 1.75 25 50 0.8 1-1/2 35L 3014 1.94 18 36 1.1 2 35E 3020 2.25 10 20 1.8 2-1/2 35L 3024 2.70 4 8 3.2 Fig. 35RE3-90°Reducing Elbow BSize A B Packing Weight _ ) in Part Number in in Inner Master lb I 3/4 x 1/2 350E3006004 1.20 1.22 80 160 0.3 1 x 1/2 35RE3010004 1.26 1.36 70 140 0.4 1 x 3/4 350E3010006 1.38 1.45 50 100 0.4 A 1-1/4 x 1/2 35RE3012004 1.34 1.53 35 70 0.5 INS 1-1/4 x 3/4 350E3012006 1.45 1.63 35 70 0.6 1-1/4 x 1 35RE3012010 1.58 1.67 30 60 0.7 1-1/2 x 1/2 35053014004 1.52 1.75 30 60 0.6 1-1/2 x 3/4 35RE3014006 1.52 1.75 25 50 0.7 1-1/2 x 1 350E3014010 1.65 1.80 20 40 0.8 1-1/2 x 1-1/4 35RE3014012 1.82 1.88 18 36 1,0 2 x 1/2 35RL3020004 1.60 1.97 18 36 1.0 2 x 3/4 35RE3020006 1.60 1.97 18 36 1.0 2 x 1 350E3020010 1.73 2.02 16 32 1.2 2 x 1-1/4 35RE3020012 1.90 2.10 12 24 1.3 I 2 x 1-1/2 358E3020014 2.02 2.16 10 20 1.5 2-1/2 x 1-1/2 35RE3024014 2.16 2.51 6 12 2.2 2-1/2 x 2 350E3024020 2.39 2.60 6 12 2.5 Fig. 35F 3-45°Elbow Size Part Number A Packing Weight A in in Inner Master lb i7 Il 1/2 35F 3004 0.88 150 300 0.2 ,4 ., 3/4 35F 3006 0.98 80 160 0.3 -� 1 35F 3010 1.13 40 80 0.5 1-1/4 35F 3012 1.29 25 50 0.7 1101IA 1-1/2 35F 3014 44 20 40 1.0 2 35F 3020 1.69 10 20 1.6 2-1/2 35E 3024 1.95 4 8 2.7 Fig. 35T3- Tee Size Part Number A Packing Weight i0� . in in Inner I Master lb IA 2 351 3004 13 80 160 0.3 3/4 351 3006 1.31 30 60 0.5 low "IN 111111111b �� 1111 3513010 1 50 25 50 0.7 iiiiiiarsommoreivie 1-1/4 35T 3012 1.75 10 20 1,1 A A 1-1/2 35T 3014 94 0 20 1.5 2 35T 3020 2.25 6 12 2.4 2-1/2 3513024 2.70 4 8 4.3 111 SNII'I'H-COOPER INTERNATIONAL • TOLL, FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com I ucta e ron fittings- ass I I I c ill) us 411> APPROVED Fig. 35RT3-Reducing Tee LISTED Size Part Number A B C Packing Weight Cpl in in in in Inner Master lb s7 C 3/4 x 1/2 35R[3006004 20 1.20 22 60 20 0.4 - I1 x 1(2, 35R13010004 1.26 1.26 1.36 30 60 0.6 (_ I I 1 x 1/2 x 1 35013010004010 50 1.36 50 30 60 0.6 1 x 3/4 35R13010006 1,38 1.38 1.45 25 50 0.6 B >< 1 1 x 3/4 x 3/4 3581.3010006006 1.38 1.31 1.45 35 70 0.6 A 1 x 3/4 x 1 35813010006010 1.50 1.45 1.50 25 50 0.7 1-1/4 x 1/2 35813012004 1.34 1,34 1.53 20 40 0.8 1-1/4x 1/2x 1-1/4 35RT3012004012 1.75 1.53 1.75 25 50 0.9 1-1/4 x 3/4 35013012006 1.45 1.45 1.62 15 30 0.9 1-1/4 x 3/4 x 1-1/4 35RT3012006012 1.75 1.62 1.75 20 40 1.0 1-1/4 x 1 3501-3012010 1.58 1,58 1.67 15 30 1.0 1-1/4x 1 x 1/2 35813012010004 1.34 1.26 1.53 25 50 0.7 1-1/4 x 1 x 3/4 35813012010006 1.45 1.38 1.63 270 40 0.8 1-1/4 x Tx 1 35873012010010 1.58 1.50 1.69 20 40 0.9 1-1/4 x 1 x 1-1/4 35013012010012 1 75 1.69 1.75 15 30 1.0 1-1/2 x 1/2 351313014004 1.41 1.41 1.66 16 32 1.0 1 1/2 x 1/2 x 1 1/4 350[3014004012 1.81 1.56 1.88 24 48 1.1 1-1/2 x 1/2 x 1-1/2 35RT3014004014 1.94 1.66 1.94 12 24 1.2 1-1/2 x 3/4 35873014006 1.52 1.52 1.75 16 32 1.1 1-1/2x3/4x1-1/4 35RT3014006012 1.94 1.66 1.88 20 40 1.1 1-1/2 x 3/4 x 1-1/2 35813014006014 1.94 1,75 1.94 18 36 1.2 1-1(2 x 1 35R13014010 1.65 1.65 1.80 12 24 1.2 1-1/2 x 1 x 1/2 35013014010004 1.44 1.25 1.69 20 40 0.8 1-1/2 x 1 x 3/4 35RT3014010006 1.50 1.44 1.75 16 32 0.9 1-1/2 x 1 x 1 35013014010010 1.65 1.50 1.80 16 32 1.0 1-112 x 1 x 1-1/4 35813014010012 1.82 1.67 1.88 12 24 1.2 1-1/2 x 1 x 1-1/2 35RT3014010014 1 94 1.80 1.94 12 24 1.3 1-1/2 x 1-1/4 35813014012 1.82 1.82 1.88 12 24 1.4 1-1/2 x 1-1/4 x 1/2 35113514012004 1.41 1.34 1.66 16 3? 0.9 1-1/2 x 1-1/4 x 3/4 35813014012006 1.52 1.45 1.75 16 32 1.0 1-1/2 x 1-1/4 x 1 35813014012010 1.65 1.58 1.80 16 32 1.1 1-1/2 x 1-1/4 x 1-1/4 35813014012012 1.82 1.75 1.88 14 28 1.3 1-1/2 x 1 1/4 x 1-1/2 35813014012014 1.94 1.88 1.94 14 28 1.4 2 x 1/2 35RT3020004 1.49 1.49 1.88 10 20 1.5 2 x 3/4 35813020006 1.60 1,60 1.97 10 20 1.6 2 x 1 351313020010 1.73 1.73 2.02 8 16 1.7 2 x 1 x 2 350[3020010020 2.25 2.02 2.25 8 16 1.9 2 x 1-1/4 35RT3020012 1.90 1.90 2.10 8 16 1.9 2 x 1 1/4 x 2 35813020012020 2.25 2.10 2.25 8 16 2.0 2 x 1-1/2 35813020014 2.02 2.02 2.16 8 16 2.1 2x 1-112x 1/2 35813020014004 1,49 1.41 1.88 10 20 1.3 2 x 1-1/2 x 3/4 35R13020014006 1.60 1.52 1.97 10 20 1.4 2 x 1-1/2 x 1 35013020014010 1.73 1.65 202 8 16 1.5 2 x 1-1/2 x 1-1/4 35R13020014012 1.90 1.82 2.10 8 16 1.7 2 x 1-1/2 x 1 1/2 35R13020014014 2.02 1.94 2.16 8 16 1.8 Fig. 35RT3-Bull Head Tee Size Part Number A B C Packing Weight '._ �C in in in in Inner Master lb 3/4 x 1 35B13006010 1.45 1.45 1.37 30 60 0.6 dol. limo 1 x 1-1/4 35873010012 1.67 1.67 1.58 20 40 0.9 1 x 1-1/2 35813010014 1.80 1,80 1.65 15 30 1.0 E A r�B'' 1-1/4 x 1 x 1-1/2 35813012010014 1.88 1.80 1.82 15 30 1.2 1-1/4x 1-1/2 35813012014 1.88 1.88 1.82 15 30 1.3 1-1/4 x 2 35BT3012020 2.10 2.10 1.90 10 20 1.6 1-1/2 x 1-1/4 x 2 35313014012020 2.16 2.10 2 02 10 20 1.8 1-1/2 x 2 35813014020 2.16 2.16 2.02 8 16 1.8 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com 112 4.1. Ductile Iron Fittings- Class 300 UL/FM ' c ® us APPROVED A LISTEDFig. 35CP3 -Straight Coupling with Ribs 0 Size part Number A Packing Weight in in Inner Master lb 1/2 35C63004 1.38 200 400 0.1.2 3/4 35CP3006 1.63 100 200 0 1 35CP3010 75 60 120 0.4 1-1/4 35CP3012 2.00 35 " 70 0.5 1-1/2 35CP3014 2.19 25 50 0.7 2 35CP3020 2,62 15 30 1.2 2-1/2 35CP3024 3.00 9 18 2.2 Fig. 35RC3 -Hex Reducing Coupling Size in part Number A Packing Weight 0.3 in 1.69InnerMasterIblas A 1 x 1/2 35RC3010004 80 60 160 1 x 314 35RC3010006 1.69 120 0.4 1-1/4 x 3/4 35RC3012006 2.06 40 80 0.6 2 x 1(not hex), 35RC3020010 2.81 20 40 1.0 Fig. 35HB3 -Hex Bushing Size Part Number A Packing Weight B in in Inner Master Ib 1 x 1/2 35HB3010004 1.06 180 360 0.2 1�1 Ir, 1 x 3/4 35HB3010006 1.06 180 360 0.1 I 1-1/4 x 1 35HB3012010i 1 1.19 90 180 0.2 1-1/2 x 1 35HB3014010 1,25 75 150 0.4 2 x 1-1/4 35H83014012 1.25 75 150 0.3 2 x 1 35HB3020010 1.38 40 80 0.6 tj- 2 x 1-1/4 35HB3020012 1.38 40 80 0.6 40 2 x 1-1/2 35HB3020014 1.38 40 80 0.6 Fig. 35SP3 -Square Head Plug Size Part Number A Packing Weight in in Inner Master lb 1/2 35SP3004 0,94 600 1200 0.07 ro., , yA3/4 35SP3006 1.12 350 700 0.1 1 35SP3010 1.25 200 400 01 1-1/4 35SP3012 1.37 100 200 0.3 1-1/2 35SP3014 1.44 80 160 0.4 2 35SP3020 1.50 45 90 0.6 Fig. 35U 3- Union with Brass Seat • , A Packing Weight A Size Part Number its in in Inner , Master, lb sia- 1111111 135U 30102.19 20 40 �.0 1-1/4 35U 3012 2.50 15 301.2 1-U2 350 3014 2.62 10 201 7 s'INN '_I ' 2 35U 3020 3.12 6 12 2.4 113 SNIITII-COOPER I_NLERNATIONAL' • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com .',,, Ductile Iron Fittings- Class 300 UL/FM c ® uS APPROVED Fig. 35X 3- Cross LISTED E -- '1�-' Size A Packing Weight in in Inner Master lb till. __ JA Part Number 1 35X 3010 1.50 20 40 0.9 in 11-1/4 35X 3012 1.75 12 24 1.4 �� 2 35X 3014 1,94 8 16 1.8 Era\INI IA 2 35X 3020 2.25 6 12 28 B B Fig. 35RX3-Reducing Cross (-- )` Size A B Packing Weight . in Part Number � in in Innen 'Master Ib IA 1-1/4 x 1 35RX3012010 1.67 1.58 15 30 1.2 t. 1__ 1-1/2 x 1 35RX3014010 1.80 1.65 12 24 1.4 I 2 x 1 35RX3020010 2.02 1.73 8 16 2.0 !Mil IA Fig. 35C 3- Cap Size A Packing Weight inPartNumher ;nInner Master Ib (pib)k. q1/235C30040.87 300 600 01 3/4 350 3006 0.97 200 400 0.1 �I= _11111 350 3010 1.16 110 220 0.2 I 1-1/4 35C 3012 1.28 70 140 0.4 1-1/2 35C 3014 1.33 50 100 0.5 ky 2 35C 3020 1.45 25 50 0.8 2-1/2 35C 3024 1.70 18 36 1.6 Fig. 35BC3-Beam Clamp r -4111 Size Part Number A Packing Weight q in in Inner Master lb � 3/8 35BC3003 0.75 100 200 0.3 M ■i 1/2 35B03004 0.75 80 160 0.5 -- ._ are in SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com 114 Pipe Hangers Fig.200- "Trimline" Adjustable Band Hanger (B-Line Fig.B317ONF) ®"rol.ct Fig.200F- "Trimline" Adjustable Band Hanger with Felt Lining (B-Line Fig.B317ONFF) DL Fig.200C - "Trimline" Adjustable Band Hanger with Plastic Coated (B-Line Fig.B317ONFC) LISTED Fig.200S - "Trimline" Adjustable Band Hanger with Non-Captured Nut Size Range: Fig. 200 - 1/2" (15mm)thru 8" (200mm) pipe Material: Steel, Pre-Galvanized to G90 specifications s Function: For fire sprinkler and other general piping purposes. Knurled - u swivel nut design permits hanger adjustment after installation. �j Features: ® ,__ • (1/2" (15mm)thru 2" (5omm)) Flared edges ease installation for all pipe types and protect CPVC plastic pipe from abrasion. Captured design r ' keeps adjusting nut from separating with hanger. Hanger is easilyi B installed around pipe. - For hanger with non-captured nut order Fig. 200S. A • (21/2" (65mm)thru 8" (200mm)) Spring tension on nut holds it secure) in p g Y : hanger before installation. Adjusting nut is easily removed. Approvals: Underwriters Laboratories listed (1/2" (15mm)thru 8" 1200mm)) Fig.200-1/2.200-3/4 in the USA(UL) and Canada (cUL)for steel and CPVC plastic pipe and Fig.200-1 to 200-2 Fig.200-2'12 to 200-8 Factory Mutual Engineering Approved (FM) (3/4" (20mm)thru 8" (200mm)). Conforms to Federal Specifications WW-H-171 E &A-A-1192A,Type 10 and Manufacturers Standardization Society ANSI/MSS SP-69&SP-58, Type 10. , . Maximum Temperature: 650°F (343°C) 4 Finish: Pre-Galvanized. Stainless Steel .. k materials will be supplied with (2) hex nuts ` in place of a knurl nut. ?.. Order By: Figure number and pipe size Designed to meet or exceed requirements of ... FM DS 2-0. ' Fig.200 Fig.200C Fig.200E Pipe Size Rod Size A B Approx.Wt./100 r, Part No. in. (mm) in. (mm) in. (mm) lbs. (kg) x 2001/2 1/2" (15) 3/e"-16 31/8" (79.4) 25/8" (66.71 11 (5.01 200-3/4 3/4' (20) 3/8"-16 31/8" (79.4) 21/2" (63.5) 11 (5.0) ST 200-1 1" 125) 3/8°-16 33/8" (85.7) 25/8" (66.71 12 (5.5) Lle 200-11/4 11/4" (32) 3/8"-16 33/4" 194.0) 27/8" (73.01 13 (5.9) ; 200-11/2 11/2" (40) 3/8"-16 37/a" (98.4) 27/8" (73.0) 14 (6.4) 200-2 2" (50) 3/8"-16 41/2" (114.3) 3" (76.3) 15 (6.9) 200-21/2 21/2" 165) 3/8"-16 55/8" (142.9) 41/8" (104.7) 27 112.3) 200-3 3" (75) 3/8"-16 57/8" (149.1) 4" (101.6) 29 (13.3) Fig.200S 200-31/2 31/2" 190) 3/8"-16 73/8" (187.3) 51/4" (133.3) 34 115.6) 200-4 4" 1100) 3/8"-16 73/8" (187.3) 5" (127.0) 35 (16.0) 200-5 5" 1125) 1/2"-13 91/8" (231.8) 61/4" (158.7) 66 (30.2) 200-6 6" (150) 1/2"-13 101/8" (257.2) 63/4" (171.4) 73 (33.4) 200-8 8" (200) 1/2"-13 131/8" (333.4) 83/4" (222.2) 136 (62.3) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. -Line Fire Protection Solutions 21 by E t• Threaded Accessories B3205 - Threaded Rod (right-hand threads - both ends) (TOLCO Fig.103) B3205L - Threaded Rod (right& left hand threads) TLS Size Range: 3/8"-16 thru 3"-4 rod Specify Length llllll�� Material: Steel �, support in hanger Function: Recommended for use as a hanger assemblies.RTL available with left and d is threaded on oth right wand threadss with right haspec specify Fig. B3205L whenand threads of the length hown.ordering.lso .40) A Thread Size Maximum Temperature: 750°F(399°C) Finish: Plain. Contact B-Line for alternative finishes and materials. Order By: Part number, rod size, length and finish Standard Design Load Thread Size Thread Length TL 650°F(343°C) 750°F(399°C) Part No. A in. (mm) Lbs. (kN) Lbs. (kN) B3205-3/a x'L' 3/8"-16 21/2" (63.5) 730 (3.25) 572 (2.54) B3205-1/2 x'L' 1/2"-13 21/2" (63.5) 1350 (6.00) 1057 (4.70) 83205-5/8 x'L' 5/8"-11 21/2" (63.5) 2160 (9.61) 1692 (7.52) B3205-3/4 x'L' 3/4"-10 3" (76.2) 3230 (14.37) 2530 (11.25) 83205-7/e x'L' 7/8"-9 31/2" (88.9) 4480 (19.93) 3508 (15.60) B3205-1 x'L' 1"-8 4" (101.6) 5900 (26.24) 4620 (20.55) 83205-11/ax'L' 11/8"-7 41/2" (114.3) 7450 (33.14) 5830 (25.93) 83205-11/4 x'L' 11/4%7 5" (127.0) 9500 (42.25) 7440 (33.09) 83205-11/2 x'L' 11/2%6 6 6" (152.4) 13800 (61.38) 10807 (48.07) 83205-13/4 x'L' 13/4"-5 7" (177.8) 18600 (82.73) 14566 (64.79) B3205-2 x'L' 2"-41/2 8" (203.2) 24600 (109.42) 19625 (87.29) B3205-21/4 x'L' 21/4"-41/2 9" (228.6) 32300 (143.67) 25295 (112.51) B3205-21/2 x'L' 21/2"-4 10" (254.0) 39800 (177.03) 31169 (138.64) 83205-23/4 x'1' 23/4"-4 11" (279.4) 49400 (219.73) 38687 (172.08) B3205-3 x'L' 3"-4 12" (304.8) 60100 (267.32) 47066 (209.35) ATR - All Threaded Rod 120" (3.05m) Lengths (TOLCO Fig. 100) Fig. 99 - All Threaded Rod Cut To Length l llllllll Size Range: /8"-16 thru 11/2% rod in 120"(3.05m)lengths or cut to length .��""' 011O Material: Steel -%- .a m Maximum Temperature: 750°F(399°C) Is o Finish: Plain. Contact B-Line for alternative finishes and materials. L m - Order By: Part number, rod diameter and finish FQ Part No.-Size x Length Threads Recommended Load Approx.WtJ100 Ft. AIR - Fig.99 Per Inch Lbs. (kN) Lbs. (kg) ATR 1/4"x 120 99-1/4"x length 20 240 (1.07) 12 (5.44) ATR 3/8"x 120 99-3/8"x length 16 730 (3.24) 29 (13.15) ATR 1/2"x 120 99-1/2"x length 13 1350 (6.00) 53 (24.04) ATR 5/8"x 120 99-5/8"x length 11 2160 (9.60) 89 (40.37) ATR 3/4"x 120 99-3/4"x length 10 3230 (14.37) 123 (55.79) ATR 7/8"x 120 99-7/8"x length 9 4480 (19.93) 170 (77.11) ATR 1"x 120 99-1"x length 8 5900 (26.24) 225 (102.06) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. B- Pipe Hangers&Supports 236 Revised 4/28/2014 Li ne by E:'L•N