Report (86) c )-z S � vim: ,.:,, 1 vcX S-1. iLlL 1 6 Imewell System dower RequirementsOF Ufl q DING GFPS-9 Power Supply Protected Premises: Tempelton Elementary School Date: 7/11/2018 Address: 9500 SW Murdock St City: Tigard State: OR Zip: 97224 Prepared By: Scott Sullivan Advanced Alarm Systems Inc Phone: 503-550-0999 Address: 12017 NE Sumner St Email: City: Portland State: OR Zip: 97220 Primary Standby Load 0.08 Amps Current load on the primary power supply during non-alarm conditions. Primary Alarm Load 3.54 Amps Current load on the primary power supply during alarm conditions. Secondary Load Requirements 2.52 Amp Hours Total Secondary Load from the calculation table below. Current Draw Time (hours) I Total (AH) Seconday Standby Load x Required Standby Time 0.075 A 24 hours 1.80 Secondary Alarm Load Required Alarm Time (hours) 3.539 A 0.084 hours 0.30 Total Secondary Load 2.10 Derating factor x 1.2 Secondary Load Requirements 2.52 AH Battery Selection 7 Amp Hours Select batteries from the list below. 7.0 AH BAT-1270 Battery(12 volt) Two Four(two 12VDC sets in parallel) Page 1 of 2 Battery Distribution Chart Shows amp-hour distribution of your selections. t Spare Battery Capacity Secondary Alarm Load Seo Secondary Standby Load 040 x Secondary Alarm Load Secondary Standby Load 31% x 5 -Spare Battery Capacity 4`'3 * r a ,:` 64% Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3.The selected batteries (7AH)are within the charger range of this power supply(7-26AH). Spare Battery Capacity 4.48 Battery Selection(AH)-Secondary Load Requirements(AH) Secondary Standby Load 2.16 Secondary Standby Load(AH)*Derating Factor Secondary Alarm Load 0.36 Secondary Alarm Load(AH)*Derating Factor Page 2 of 2 -(0-41HarmA t atlCi System Current Draw - GFPS-9 li jamaii Total Current Standby 0.075 A Alarm 3.539 A Cl -Standby Current C2-Alarm Current DeviceQty Draw Standby Qty Draw Alarm 1.Power Supply GFPS-9 Distributed Power Module 1 x 0.07500 0.07500 1 x 0.20500 0.20500 2.NAC#1 NAC 1 1 x 0.00000 0.00000 1 x 0.84700 0.84700 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 _ 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC#1 Totals(Max 3.0 Amps): _ 0.00000 0.84700 3. NAC#2 NAC 2 1 x 0.00000 0.00000 1 x 0.84700 0.84700 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 _ 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC#2 Totals(Max 3.0 Amps). 0.00000 0.84700 4. NAC#3 NAC 3 1 x 0.00000 0.00000 1 x 0.84700 0.84700 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC#3 Totals(Max 3.0 Amps): 0.00000 0.84700 5. NAC#4 NAC 4 1 x 0.00000 0.00000 1 x 0.79300 0.79300 0 x 0.00000 0 x 0.00000 0 x 0.00000 _ 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 _ 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC#4 Totals(Max 3 0 Amps). _ 0.00000 0.79300 6.Auxiliary Devices Auxiliary Device 1 0 x 0.00000 0 x 0.00000 Auxiliary Device 2 0 x 0.00000 _ 0 x 0.00000 Auxiliary Device 3 0 x 0.00000 0 x 0.00000 Auxiliary Device 4 0 x 0.00000 0 x 0.00000 Auxiliary Device 5 0 x 0.00000 0 x 0.00000 Total Standby Load: 0.075 Total Alarm Load: 3.539 I This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Project Name Tempelton Elementary Portables CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS Date 7/11/2018 Circuit Number 1 Totals Voltage Totals Voltage Totals Voltage Area Covered Portables 7,8,9 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.847 215 0.61 0.847 215 1.118 0.847 215 0.559 Minimum Device Voltage 16 End of Line Voltage 19.79 End of Line Voltage 19.28 End of Line Voltage 19.84 Total Circuit Current 0.847 Wire Ohm's Percent Drop 2.99% Percent Drop 5.48% Percent Drop 2.74% Gauge Per 1000 End of Line and Load Centering Methods use only the wire guage for the first device to source Distance from source to 1st devic 40 14 3.07 Standard Wire Resistance in Ohms per 1000 feet. Wire Gauge for balance of circuit 14 3.07 18=7.77 16=4.89 14=3.07 12=1.98 10=1.24 Enter current in amps. Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors .150= 150 ma from Voltage Device Device previous At Drop from Percent Device Manufacturer System Sensor _ Device Manufacturer System Sensor Number Current device Device source Drop Current Current Device 1 0.121 40 20.19 0.208 1.02% Horn Strobe @Rated Strobe Only @Rated Device 2 0.121 20 20.10 0.297 1.46% Model# Candela Voltage Model# Candela Voltage Device 3 0.121 20 20.03 0.371 1.82% P2WL Wall 15 0.054 SWL Wall 15 0.043 Device 4 0.121 25 19.95 0.446 2.19% P2WL Wall 30 0.074 SWL Wall 30 0.063 Device 5 0.121 35 19.88 0.524 2.57% P2WL Wall 75 0.121 SWL Wall 75 0.107 Device 6 0.121 40 19.82 0.583 2.86% P2WL Wall 95 0.142 SWL Wall 95 0.121 Device 7 0.121 35 19.79 0.609 2.99% P2WL Wall 110 0.162 SWL Wall 110 0.148 END 19.79 0.609 2.99% P2WL Wall 135 0.196 SWL Wall 135 0.172 END 19.79 0.609 2.99% P2WL Wall 185 0.245 SWL Wall 185 0.222 END 19.79 0.609 2.99% PC2WL Ceiling 15 0.071 SCWL Ceiling 15 0.041 END 19.79 0.609 2.99% PC2WL Ceiling 30 0.090 SCWL Ceiling 30 0.063 END 19.79 0.609 2.99% PC2WL Ceiling 75 0.143 SCWL Ceiling 75 0.111 END 19.79 0.609 2.99% PC2WL Ceiling 95 0.165 SCWL Ceiling 95 0.134 END 19.79 0.609 2.99% PC2WL Ceiling 110 0.187 SCWL Ceiling 110 0.158 END 19.79 0.609 2.99% PC2WL Ceiling 135 0.217 SCWL Ceiling 138 0.189 END 19.79 0.609 2.99% PC2WL Ceiling 185 0.254 SCWL Ceiling 185 0.226 END 19.79 0.609 2.99% END 19.79 0.609 2.99% P2WH-LF 135 0.352 END 19.79 0.609 2.99% P2WH-LF 185 0.344 END 19.79 0.609 2.99% HW-LF N/A 0.138 Totals 0.847 215 End of Line Voltage 19.79 This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Project Name Tempelton Elementary Portables CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS Date 7/11/2018 Circuit Number 2 Totals Voltage Totals ' Voltage Totals Voltage Area Covered Portables 4,5,6 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.847 475 2.03 0.847 475 2.470 0.847 475 1.235 Minimum Device Voltage 16 End of Line Voltage 18.37 End of Line Voltage 17.93 End of Line Voltage 19.16 Total Circuit Current 0.847 Wire Ohm's Percent Drop 9.96% Percent Drop 12.11% Percent Drop 6.05% Gauge Per 1000 End of Line and Load Centering Methods use only the wire guage for the first device to source Distance from source to 1st devic 300 14 3.07 Standard Wire Resistance in Ohms per 1000 feet. Wire Gauge for balance of circuit 14 3.07 18=7.77 16=4.89 14=3.07 12=1.98 10=1.24 Enter current in amps. Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors .150= 150 ma from Voltage Device Device previous At Drop from Percent Device Manufacturer System Sensor Device Manufacturer System Sensor Number Current device Device source Drop Current Current Device 1 0.121 300 18.84 1.560 7.65% Horn Strobe @Rated Strobe Only @Rated Device 2 0.121 35 18.68 1.716 8.41% Model# Candela Voltage Model# Candela Voltage Device 3 0.121 40 18.54 1.865 9.14% P2WL Wall 15 0.054 SWL Wall 15 0.043 Device 4 0.121 20 18.48 1.924 9.43% P2WL Wall 30 0.074 SWL Wall 30 0.063 Device 5 0.121 20 18.43 1.969 9.65% P2WL Wall 75 0.121 SWL Wall 75 0.107 Device 6 0.121 25 18.39 2.006 9.83% P2WL Wall 95 0.142 SWL Wall 95 0.121 Device 7 0.121 35 18.37 2.032 9.96% P2WL Wall 110 0.162 SWL Wall 110 0.148 END 18.37 2.032 9.96% P2WL Wall 135 0.196 SWL Wall 135 0.172 END 18.37 2.032 9.96% P2WL Wall 185 0.245 SWL Wall 185 0.222 END 18.37 2.032 9.96% PC2WL Ceiling 15 0.071 SCWL Ceiling 15 0.041 END 18.37 2.032 9.96% PC2WL Ceiling 30 0.090 SCWL Ceiling 30 0.063 END 18.37 2.032 9.96% PC2WL Ceiling 75 0.143 SCWL Ceiling 75 0.111 END 18.37 2.032 9.96% PC2WL Ceiling 95 0.165 SCWL Ceiling 95 0.134 END 18.37 2.032 9.96% PC2WL Ceiling 110 0.187 SCWL Ceiling 110 0.158 END 18.37 2.032 9.96% PC2WL Ceiling 135 0.217 SCWL Ceiling 138 0.189 END 18.37 2.032 9.96% PC2WL Ceiling 185 0.254 SCWL Ceiling 185 0.226 END 18.37 2.032 9.96% END 18.37 2.032 9.96% P2WH-LF 135 0.352 END 18.37 2.032 9.96% P2WH-LF 185 0.344 END 18.37 2.032 9.96% HW-LF N/A 0.138 Totals 0.847 475 End of Line Voltage 18.37 This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Project Name Tempelton Elementary Portables CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS Date 7/11/2018 Circuit Number 3 Totals Voltage Totals Voltage Totals Voltage Area Covered Portables 1,2,3 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.847 575 2.55 0.847 575 2.990 0.847 575 1.495 Minimum Device Voltage 16 End of Line Voltage 17.85 End of Line Voltage 17.41 End of Line Voltage 18.90 Total Circuit Current 0.847 Wire Ohm's Percent Drop 12.51% Percent Drop 14.66% Percent Drop 7.33% Gauge Per 1000 End of Line and Load Centering Methods use only the wire guage for the first device to source Distance from source to 1st devic 400 14 3.07 Standard Wire Resistance in Ohms per 1000 feet. Wire Gauge for balance of circuit 14 3.07 18=7.77 16=4.89 14=3.07 12=1.98 10=1.24 Enter current in amps. Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors .150= 150 ma from Voltage Device Device previous At Drop from Percent Device Manufacturer System Sensor Device Manufacturer System Sensor Number Current device Device source Drop Current Current Device 1 0.121 400 18.32 2.080 10.20% Horn Strobe @Rated Strobe Only @Rated Device 2 0.121 35 18.16 2.236 10.96% Model# Candela Voltage Model# Candela Voltage Device 3 0.121 40 18.02 2.385 11.69% P2WL Wall 15 0.054 SWL Wall 15 0.043 Device 4 0.121 20 17.96 2.444 11.98% P2WL Wall 30 0.074 SWL Wall 30 0.063 Device 5 0.121 20 17.91 2.489 12.20% P2WL Wall 75 0.121 SWL Wall 75 0.107 Device 6 0.121 25 17.87 2.526 12.38% P2WL Wall 95 0.142 SWL Wall 95 0.121 Device 7 0.121 35 17.85 2.552 12.51% P2WL Wall 110 0.162 SWL Wall 110 0.148 END 17.85 2.552 12.51% P2WL Wall 135 0.196 SWL Wall 135 0.172 END 17.85 2.552 12.51% P2WL Wall 185 0.245 SWL Wall 185 0.222 END 17.85 2.552 12.51% PC2WL Ceiling 15 0.071 SCWL Ceiling 15 0.041 END 17.85 2.552 12.51% PC2WL Ceiling 30 0.090 SCWL Ceiling 30 0.063 END 17.85 2.552 12.51% PC2WL Ceiling 75 0.143 SCWL Ceiling 75 0.111 END 17.85 2.552 12.51% PC2WL Ceiling 95 0.165 SCWL Ceiling 95 0.134 END 17.85 2.552 12.51% PC2WL Ceiling 110 0.187 SCWL Ceiling 110 0.158 END 17.85 2.552 12.51% PC2WL Ceiling 135 0.217 SCWL Ceiling 138 0.189 END 17.85 2.552 12.51% PC2WL Ceiling 185 0.254 SCWL Ceiling 185 0.226 END 17.85 2.552 12.51% END 17.85 2.552 12.51% P2WH-LF 135 0.352 END 17.85 2.552 12.51% P2WH-LF 185 0.344 END 17.85 2.552 12.51% HW-LF N/A 0.138 Totals 0.847 575 End of Line Voltage 17.85 This calculator provided voltage drop calculations in three formats(Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Project Name Tempelton Elementary Portables CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS Date 7/11/2018 Circuit Number 4 Totals Voltage Totals Voltage Totals Voltage Area Covered Restrooms Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.793 430 1.48 0.793 430 2.094 0.793 430 1.047 Minimum Device Voltage 16 End of Line Voltage 18.92 End of Line Voltage 18.31 End of Line Voltage 19.35 Total Circuit Current 0.793 Wire Ohm's Percent Drop 7.24% Percent Drop 10.26% Percent Drop 5.13% Gauge Per 1000 End of Line and Load Centering Methods use only the wire guage for the first device to source Distance from source to 1st devic 180 14 3.07 Standard Wire Resistance in Ohms per 1000 feet. Wire Gauge for balance of circuit 14 3.07 18=7.77 16=4.89 14=3.07 12=1.98 10=1.24 Enter current in amps. Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors .150= 150 ma from Voltage Device Device previous At Drop from Percent Device Manufacturer [ystem Sensor Device Manufacturer System Sensor Number Current device Device source Drop Current Current Device 1 0.043 180 19.52 0.876 4.30% Horn Strobe @Rated Strobe Only @Rated Device 2 0.121 10 19.48 0.922 4.52% Model# Candela Voltage Model# Candela Voltage Device 3 0.043 10 19.44 0.961 4.71% P2WL Wall 15 0.054 SWL Wall 15 0.043 Device 4 0.043 70 19.19 1.213 5.95% P2WL Wall 30 0.074 SWL Wall 30 0.063 Device 5 0.121 10 19.15 1.246 6.11% P2WL Wall 75 0.121 SWL Wall 75 0.107 Device 6 0.043 10 19.13 1.272 6.24% P2WL Wall 95 0.142 SWL Wall 95 0.121 Device 7 0.043 20 19.08 1.319 6.46% P2WL Wall 110 0.162 SWL Wall 110 0.148 Device 8 0.043 15 19.05 1.350 6.62% P2WL Wall 135 0.196 SWL Wall 135 0.172 Device 9 0.043 50 18.96 1.440 7.06% P2WL Wall 185 0.245 SWL Wall 185 0.222 I Device 10 0.121 10 18.95 1.455 7.13% PC2WL Ceiling 15 0.071 SCWL Ceiling 15 0.041 Device 11 0:043 10 18.94 1.463 7.17% PC2WL Ceiling 30 0:090 SCWL Ceiling 30 0.063 Device 12 0.043 20 18.93 1.473 7.22% PC2WL Ceiling 75 0.143 SCWL Ceiling 75 0.111 Device 13 0.043 15 18.92 1.477 7.24% PC2WL Ceiling 95 0.165 SCWL Ceiling 95 0.134 END 18.92 1.477 7.24% PC2WL Ceiling 110 0.187 SCWL Ceiling 110 0.158 END 18.92 1.477 7.24% PC2WL Ceiling 135 0.217 SCWL Ceiling 138 0.189 END 18.92 1.477 7.24% PC2WL Ceiling 185 0.254 SCWL Ceiling 185 0.226 END 18.92 1.477 7.24% END 18.92 1.477 7.24% P2WH-LF 135 0.352 END 18.92 1.477 7.24% P2WH-LF 185 0.344 END 18.92 1.477 7.24% HW-LF N/A 0.138 Totals 0.793 430 End of Line Voltage 18.92 Gamer/ell Velociti® Series FCi NSSrRUUMENTS ASD-PL2F, ASD-PTL2F by Honeywell and ASD-PL2FR Description Analog, Addressable Photoelectronic Smoke Sensor The Gamewell-FCI Velociti® Series, analog address pO ",\` able plug-in smoke sensors with integral communica- �� \; tion provide features that surpass conventional sensors. Sensitivity can be programmed in the con- trol panel software, and is continuously monitored and reported to the panel. Point ID capability allows 410111111k ig • each sensor's address to be set, providing exact locations for selective maintenance when the cham- ber ham • ber contamination reaches an unacceptable level. ASD-PL2F/ASD-PTL2F ASD-PL2FR The ASD-PL2F photoelectric sensor's unique optical sensing chamber is engineered to sense smoke pro- Features duced by a wide range of combustion sources. Dual electronic thermistors add 135°F (57°C) fixed-tem- • Sleek, low-profile design. perature thermal sensing on the ASD-PTL2F model. • Visual rotary, decimal switch addressing(01-159). • Built-in functional test switch activated by an external The Velociti® Series use a communication protocol magnet. that substantially increases the speed of communica- • Bicolor LEDs flash green whenever the sensor is tion between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These addressed, and light steady red on alarm.* devices operate in a grouped fashion. If one of the • Optional relay, isolator, or sounder bases. devices in the group has a status change, the panel's • Low standby current. microprocessor stops the group poll and concen- • Analog addressable communication. trates on the single device. The net effect is a • Stable communication technique with noise immunity. response speed up to five times greater than earlier • Optional remote, single-gang LED Indicator(RA100Z). designs. • Compatible with Gamewell-FCI analog addressable Ordering Information panels. Note:*Only the red LED is operative in panels that do not operate in Velociti mode. Part Number Description ASD-PL2F Analog, addressable photoelectronic smoke sensor ASD-PTL2F Analog, addressable photoelectronic smoke sensor with thermal sensing ASD-PL2FR Analog,addressable photoelectronic smoke sensor used with the DNR duct base when the remote test is required. SIGNALING ® ® MA ��r Approved s'� z, Velociti®is a registered trademark of Honeywell International Inc. LISTED APPROVED FDNY l UL®is a registered trademark of Underwriters Laboratories Inc. S1913 3023594 COA#:219.02-E 7272-1703:0121 Vol.VI /ISO 900 GAMEWELL-FCI te""" """`"°"""" 12 Clintonville Road,Northford,CT 06472-1653 USA•Tel:(203)484-7161 •Fax:(203)484-7118 Specifications are for information only,are not intended for installation purposes,and are subject to change without notice.No responsibility is assumed by Gamewell-FCI for their use. ©2013 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0617 Rev.J page 1 of 2 Installation Specifications ASD-PL2F plug-in sensors use a separate base to ASD-PL2F,ASD-PTL2F,ASD-PL2FR: simplify installation, service, and maintenance. A Dimensions: 2.1"(5.1 cm)height special tool allows maintenance personnel to plug-in Diameter: 4.1"(10.4 cm)installed in the B501 base and remove sensors without using a ladder. 6.1"(15.5 cm)installed in the B210LP base Shipping Weight:5.2 oz. (147 g) Mount the base on a box which is at least 1.5"(3.8 cm) Operating ASD-PL2F: deep. Suitable mounting base boxes include: Temperature: 32° F to 120° F(0°C to 49°C) ASD-PTL2F: • 4.0"(10.2 cm)square box. 32° F to 100° F(0°C to 38°C) • 3.5"(8.9 cm)or 4.0"(10.2 cm)octagonal box. UL®-Listed 0-4000 ft./min. (1,219.2 m/min.), • Single-gang box(except relay or isolator bases). Velocity Range: suitable for installation in ducts. • With B200S or B200SR base, mounted on a 4.0" Relative (10.2 cm)octagonal or square box. Humidity: 10-93%(non-condensing) • With B224RB or 622461 base, mounted on a 3.5" Thermal Ratings: Fixed-temperature setpoint 135° F(57°C) (8.9 cm)octagonal box, or a 4.0"(10.2 cm)octagonal or square box. Electrical Specifications NOTE: Because of the inherent supervision provided Voltage Range: 15-32 volts DC peak by the SLC, end-of-line resistors are not required. Standby Current: (max. avg.): .0003 A @ 24 VDC Wiring "T-taps" or branches are permitted for Style 4 (One communication every 5 (Class"B")wiring. seconds with LED blink enabled). Maximum Alarm- Current: .0065 A @ 24 VDC(LED)lit). Sensor Spacing Gamewell-FCI recommends that the spacing sensors Bases and Options be used in compliance with NFPA 72. B501 Plug-in sensor base without flange Dimensions: 4.1"(10.4 cm)diameter B210LP Flanged mounting base Dimensions: 6.1"(15.5 cm)diameter B210LPBP Flanged mounting base bulk pack Dimensions: 6.1"(15.5 cm)diameter B224RB Plug-in sensor base with auxiliary Relay Base relay, SPDT, rated 2 amps @ 30 VDC (resistive). Screw terminals: Up to 14 AWG(2.0 mm2) 2 coil latching relay 1 Form C contact UL/CSA Rating: 0.9 A @ 125 VAC, inductive 0.9 A @ 110 VDC, inductive 3 A @ 30 VDC, resistive Dimensions: 6.1"(15.5 cm)diameter Maximum:25 devices between isolator bases. B200S Intelligent sensor sounder base Dimensions: 6.875"(17.5 cm)diameter B200SR Standard sounder base, UL 8649th Edition compliant, ULC Listed Dimensions: 6.875"(17.5 cm)diameter RA100Z Remote LED Annunciator BCK-200 Black detector covers(box of 10) DNR Duct smoke housing GAMEWELL-FCI 1i 12 Clintonville Road,Northford,CT 06472-1653 USA•Tel:(203)484-7161 •Fax:(203)484-7118 , 9020-0617 Rev.J page 2 of 2 www.gamewell-fci.com \\\\ ti ,E m MS-7 Series -- nci FIRE CONTROL INSTRUMENTS by Honeywell Description Non-Coded, Manual Fire Alarm Stations The Gamewell-FCI, MS-7 Series manual fire alarm sta- tions are available in a wide variety of configurations. The Stations comply with the Americans with Disabilities Act I (ADA) 5-lb. maximum pull force requirement. Operating instructions and Braille text are engraved in the handle.All stations have a key lock/reset which is keyed alike with PUSH Gamewell-FCI fire alarm control panels and other manual fire alarm stations. PULL;1 ^ ' U yLr MS-7AF Velociti Addressable Station The MS-7AF Velociti®Series addressable station is a dou `.. •""" ble action station designed for installation in the signaling I ,, line circuit of Gamewell-FCI analog addressable control ' I—GAMMON i panels. Activation of the station causes its assigned i t.°", address to register at the control panel. The door contains an LED which flashes green in normal condition and lights MS-7 steady red when the station has been activated.*The sta- tion features screw terminals. Features MS-7ASF„Velociti Addressable Station The MS-7ASF Velociti® Series addressable station is a • Addressable stations compatible with all Gamewell-FCI single action station designed for installation in the signal- analog addressable fire alarm controls ing line circuit of Gamewell-FCI analog addressable con- trol panels. Activation of the station causes its assigned • Conventional stations suitable for use with any UL® address to register at the control panel. The door contains Listed control panel an LED which flashes green in normal condition and lights steady red when the station has been activated.*The sta- • Both single and double action stations available tion features screw terminals. • Tumbler lock for test and reset keyed alike with The Velociti® Series stations use a communication proto- Gamewell-FCI controls col that substantially increases the speed of communica- tion between the sensors and certain Gamewell-FCI • Surface or semi-flush mounting analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the • Shock and vibration resistant group has a status change, the panel's microprocessor stops the group poll and focuses on the single device.The net effect is response speed up to five times greater than • Stations(MS-7LOB) Listed for outdoor applications earlier designs. • Complies with ADA pull force requirements MS-7 Double Action Station "Only the red LED is operative in panels that do not oper- The MS-7 double action station is used with conventional ate in Velociti mode. fire alarm control panels. It features a set of single pole contacts and screw terminals for connection to an initiating circuit. ® An ISO 9001-2000 Company Velociti is a registered trademark of Honeywell International Inc. SIGN,,, NG UL®is a registered trademark of Underwriter's Laboratories Inc. ®<> ,. '' LEXAN®is a registered trademark of GE Plastics,a subsidiary of General MEA Electric Company. LISTED APPROVED Approved - --` S2465 3023594 67-0z-EVol.VIII 07150-0694261 GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 Specifications are for information only,are not intended for installation purposes,and are subject to change without notice.No responsibility is assumed by Gamewell-FCI for their use. ©2010 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0616 Rev.D page 1 of 2 I MS-7S Single Action Station Specifications The MS-7S single action station is used with conventional fire alarm control panels. It features a set of single pole Material: Lexan® contacts and wire leads for connection to an initiating circuit. Contact Ratings: 0.25 amps. @ 30 VAC/VDC MS-7SP Double Action Station (resistive) The MS-7SP is a double action station similar to the MS-7 Dimensions: 5 5/8" H x 4 1/4"W x 1 1/4" D station, with the additional feature of both English and (14 x 10.1 x 3.2 cm) Spanish instructions molded into the unit. Operating Temperature MS-7LR Dual-action Agent Release Station (MS-7AF,MS-7ASF): 32°to 120° F(0°to 49°C) The MS-7LR is designed for use with the Gamewell-FCI (MS-7LOB): -30°to 150° F(-35°to 66°C) fire alarm control panels with releasing capabilities and Relative Humidity Flex Series releasing systems. It features a set of single (MS-7AF,MS-7ASF): 10 to 93%(non-condensing) pole contacts and screw terminals for connection to an ini- (MS-7LOB): 85%±5%@ 86°±3.6° tiating circuit. (30°±2°C) Alarm Current: .0030 amp. 0.007 for LED MS-7LRA Agent Release Station with Abort Supervisory Current The MS-7LRA is designed for use with the Gamewell-FCI (MS-7AF,MS-7ASF): .00030 amps. fire alarm control panels with releasing capabilities and Flex Series releasing systems where system abort capabil- ities are required. It consists of an MS-7LR mounted on a Ordering Information plate with an abort switch and LED indicators for system normal, and system activated status. Part Number Description MS-7LOB Double Action Station MS-7 Double action station (Listed for Outdoor Applications) MS-7AF** Velociti addressable double action The MS-7LOB station must be mounted on a Model SB-I/O station backbox. In retrofit applications,the station is UL Listed for MS-7ASF** Velociti addressable single action station use with the WP-10 backbox. It is intended for use with MS-7S Single action station,wire leads conventional control panels and has a set of single pole MS-7SP Double action station, English and contacts and screw terminals. Spanish instructions Mounting MS-7LR Agent release station, dual-action The MS-7 interior stations may be surface mounted or MS-7LRA Agent release station with abort switch, LED indicators, dual-action semi-flush mounted on a standard double-gang, or 4-inch MS-7LOB Double action station, outdoor use (10.2 cm)square electrical box.An optional trim ring (Includes SB-I/O-Indoor/outdoor use (BG12TR)may also be used for semi-flush mounting. backbox) NYC-Plate SB-I/O Indoor/outdoor use backbackbox The NYC-Plate provides the backplate for the manual pull SB-10 Surface backbox station. (See Figure 1). BG12TR Trim ring for semi-flush mount, plastic NY-PLATE NYC backplate for manual pull station . **For use with the Gamewell-FCI analog addressable control panels only. #i P�i S Figure 1 NYC-Plate GAMEWELL-FCI i 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 9020-0616 Rev.D page 2 of 2 www.gamewell-fci.com .cla GameweHVelociti® Series FCIFIRE CONTROL INSTRUMENTS AOM-25F by Honeywell Addressable Output Relay Description Supervised Control Module The Gamewell-FCI Velociti® Series addressable output supervised control module (AOM-2SF) allows a #:::::: 1 Gamewell-FCI analog addressable fire alarm control panel , to switch an external power supply, such as a DC supply or audio amplifier(up to 80 VRMs) to notification appliances. The AOM-2SF notification appliance circuit can be wired either Class A(Style Z)or Class B(Style Y). It also super- ,I PP'-''N-- vises the wiring to the connected loads and reports their status to the panel as NORMAL, OPEN or SHORT .''',.',.i.4- CIRCUIT.The module contains a panel controlled LED. AOM-2SF The Velociti® Series use a communication protocol that Features substantially increases the speed of communication between the SLC devices and certain Gamewell-FCI ana • Listed under UL®Standard 864 and UL2572 for Mass log addressable fire alarm control panels. These devices Notification. • Designed as a compact size to allow easy installation. operate in a grouped fashion. If one of the devices in the • Includes Class A,Style Z,or Class B,Style Y notification group has a status change, the panel's microprocessor appliance circuit. stops the group poll and concentrates on the single device. • Accommodates audio amplifiers up to 80 VRMs. The net result is a superior response speed up to five • FM Listed as suitable for a releasing device service. times greater than the earlier designs. • Includes a bicolor LED that flashes green whenever the module is addressed, and lights steady red upon The AOM-2SF module is designed for installation in the activation*. signaling line circuit of any Gamewell-FCI analog address- *Note: Only the red LED is operative in panels that do not operate in able fire alarm control panel. The signaling line circuits of Velociti®mode. Gamewell-FCI analog addressable fire alarm control pan- els are designed to accommodate up to 159 modules per Specifications circuit. The AOM-2SF is designed to mount in a 4" (10.16 cm)square junction box 2 1/8"(5.5 cm)deep. Supervisory Current: .000375 amps Table 1 lists the relay contact ratings. Alarm Current: .0065 amps Current Maximum Load I Operating Temperature:32°to 120° F(0°to 49°C) Rating Voltage Description Application Relative Humidity: 10 to 93% relative humidity 3A 30 VDC Resistive Non-Coded (non-condensing) 2A 30 VDC Resistive Coded Dimensions: 4 1/2"H x 4"W x 1 1/4" D 0.9A 110 VDC Resistive Non-Coded (11.4 H x 10.2 W x 3.2 D cm) 0.5A 125 VAC Resistive Non-Coded OrderingInformation 0.5A 30 VDC Inductive(L/R=5ms) Coded 1A 30 VDC Inductive(L/R=2ms) Coded Part Number Description AOM-25F Addressable output supervised 0.5A 125 VAC Inductive(PF=.35) Non-Coded control module 0.7A 75 VAC Inductive Non-Coded SIGNALING Table 1: Relay Contact Ratings U� MEA �°�') Velociti®is a registered trademark of Honeywell International Inc. 1 UL®is a registered trademark of Underwriters Laboratories Inc. LISTED APPRO ED Approved z'tJ S1949 3023594 227-03-E VoLIV 7300-1703:0102 iiso gaol GAMEWELL-FCI M FABIMLSSiQUAITY SYSTEMS 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 Specifications are for information only,are not intended for installation purposes,and are subject to change without notice.No responsibility is assumed by Gamewell-FCI for their use. ©2014 Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0627 Rev.G page 1 of 1 vin :yG riq ameweI G FPS-9 ad FIRE CONTROL INSTRUMENTS FCI Honeywell Description Gamewell-FCI Power Supply 9 The Gamewell-FCI Power Supply 9 (GFPS-9) panel provides two(2)Class A, Style Z, or four(4) Class B, Style Y notification appliance circuits. Each circuit is rated at 3 amperes, with a total capacity of 9 amperes per panel. These circuits may be programmed to activate by groups or , various combinations by connection to one (1) or two (2) existing Class A or B notification appliance circuits with I � / operating voltages ranging from 9 to 30 VDC. Either non- ,, ,, coded or coded operation is possible. In addition, the GFPS-9 can provide a temporal pattern output from a non- coded input. / N A unique feature allows for programmable synchronized- outputs for strobes by three(3)different major GFPS-9 manufacturers,System Sensor, Faraday,or Gentex. Features The GFPS-9 contains its own battery charger capable of maintaining batteries of up to 33 AH. The cabinet provides • UL Listed as a fire alarm accessory for use with any space for a set of 7 A/H batteries. It is supervised for Gamewell-FCI or other UL Listed fire alarm controls. ground fault, over-current, open circuits and low battery • Two(2)Class A(Style Z),or four(4)Class B(Style Y) conditions. These conditions light the appropriate trouble notification appliance circuits. LED and automatically open the notification appliance cir- • Programmable temporal pattern output including cuit used for activation, transmitting a trouble signal to the ANSI S3.41. main fire alarm control panel.The ground fault detection • High current 9 amp.total output. circuit may be disabled. • Integral strobe synchronization feature for strobes by three(3) manufacturers. The unit contains a set of dry, Form "C" trouble actuated • Integral ground fault detection. auxiliary contacts, rated 2.5 amp. @ 24 VDC (resistive). • Form"C"trouble contacts with delayed AC failure Transfer of these contacts for AC power failure is program- indication. mable and can be delayed for a period of six(6)hours.This delay feature may be disabled. A power limited,non-resettable auxiliary power output up to three (3) amperes is also available. The panel can be pro- grammed via DIP switch to disconnect this output from the batteries 30 seconds after AC power failure, in order to avoid running down the batteries from current devices such as door holders,etc. An ISO 9000-2000 Company SIGNALING ® LISTED i GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 Specifications are for information only,are not intended for installation purposes,and are subject to change without notice.No responsibility is assumed by Gamewell-FCI for their use. K,©2007 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-60236 Rev.A page 1 of 2 / Specifications Ordering Information Operating Power: 120 VAC, 3.6 amp. 60 Hz Model Description Standby Battery GFPS-9 Gamewell-FCI Power Supply-9 Circuit: 24 VDC(nominal) 7 ampere/ hours, max. Supervisory Current: 0.075 amp. Alarm Current: 0.175 amp. (excluding notification appliances) Alarm Output: 9.0 amp. max. @ 24 VDC (nominal) Dimensions: 16"H x 12.25"W x 3" D (40.64 x 30.88 x 7.62 cm) Operating Temperature: 32°to 120° F(0°to 49°C) Relative Humidity: 10 to 85% @ 86°F (non-condensing) GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel: (203)484-7161 •Fax: (203)484-7118 9020-60236 Rev.A page 2 of 2 www.gamewell-fci.com ..‘ ..,...,.. :,, mil G II ,.„, arnewe I-Series 2,--1.-- ciRUE Indoor Strobes .. . by Honeywell and Norn Strobes Description Indoor Selectable-Output Strobes The L-Series audible visible notification products offer the and Horn Strobes for Ceiling Applications most versatile and easy-to-use product line of horns, strobes, and horn strobes in the industry. This product includes lower current draws and a modern aesthetic design which reduce installation times and maximize prof- its. In addition, the L-Series offers white and red plastic housings and wall and ceiling mounting options. Similar to the entire L-Series product line, the ceiling mount strobes and horn strobes include a variety of fea v. tures tures that increase their application versatility while simpli- ,,, fying the installation. All devices offer a plug-in design so that there is minimal intrusion into the backbox.These fea- tures make installations fast and foolproof while eliminating costly and time-consuming ground faults. i To simplify the installation, the L-Series uses a universal mounting plate allowing you to mount the devices to a wide array of backboxes. With an on-board shorting spring, Ceiling Horn Strobes Installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to suit a wide Features range of application requirements using the following: • Field-selectable candela settings. • Listed for ceiling mounting only. • Automatic selection of 12-or 24-volt operation. • Features a plug-in design so that there is minimal • Rotary switch for horn tones with two volume selections. intrusion into the backbox. L-Series Specifications • Designed with a tamper-resistant construction. Architect/Engineer Specifications • Provides an automatic selection of 12-or 24-volt General operation at 15 and 30 candela. • The L-Series ceiling-mount strobes and horn strobes shall Uses field selectable candela settings on the following mount to any of the following: ceiling units: -• double-gang backbox • 4-inch octagon backbox 15 30 75 95 • a standard 4 x 4 x 1 1/2-inch backbox -115 150 177 Two-wire products shall also mount to a single-gang corn- • Produces horn rated at 88+dBA at 16 volts. pact 2 x 4 x 17/8-inch backbox.A universal mounting plate • Offers a rotary switch for horn tone and two volume shall be used for mounting ceiling and wall products. The selections. notification appliance circuit wiring shall terminate at the • Includes a universal mounting plate for ceiling units. universal mounting plate. Also, the L-Series products, when used with the Sync•Cir • Contains a mounting plate with a shorting spring feature cuit Module accessory,shall be powered from a non-coded that checks the wiring continuity before device installa- notification appliance circuit output and shall operate on a tion. nominal 12 or 24 volts. When it is used with the Sync•Cir- • Compatible with System Sensor synchronization protocol. cuit Module,the following occur: • Supports electrical compatibility with the legacy • 12-volt-rated notification appliance circuit outputs shall SpectrAlert and the SpectrAlert Advance devices. operate between 8.5 and 17.5 volts. • 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. The Indoor L-Series products shall operate between 32 SIGNALING and 120 degrees Fahrenheit from a regulated DC or full- ® � wave rectified unfiltered power supply. =`t" ', 11PPROVED '1yn4;.: LISTED G PENDING _$_900 GAMEWELL-FCI 0 0L4`Y MITI 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 Specifications are for information only,are not intended for installation purposes,and are subject to change without notice.No responsibility is assumed by Gamewell-FCI for their use, l @2016 by Honeywell International Inc. All rights reserved www.gamewell-fci.com 9021-60928 Rev.A page 1 of 4 L-Series Specifications (Continued) Physical Specifications Architect/Engineer Specifications (Continued) General(Continued) Standard Operating Ceiling strobes and horn strobes shall have the following Temperature: 32°F to 120°F(0°C to 49°C) field-selectable candela settings including: Humidity Range: 10 to 93%non condensing • 15 30 75 Strobe Flash Rate: 1 flash per second • 95 • 115 • 150 Nominal Voltage: Regulated 12 VDC or • 177 regulated 24 DC/FWR1 Operating Voltage Rangel: 8 to 17.5 V(12 V nominal)or Strobe 16 to 33 V(24 V nominal) The strobe shall be an L-Series Model listed to Operating Voltage Range UL Standard 1971 and shall be approved for fire protective (MDL3): 8.5 to 17.5V(12 V nominal)or service. The strobe shall be wired as a primary-signaling 16.5 to 33 V(24V nominal) notification appliance and comply with the Americans with Input Terminal Wire Gauge: 12 to 18 AWG Disabilities Act requirements for visible signaling appli- Ceiling-Mount Dimensions ances, flashing at 1 Hz over the strobe's entire operating (including lens): 6.8"diameter x 2.5"high voltage range. The strobe light shall consist of a xenon (173 mm diameter x 64 mm high) flash tube and associated lens/reflector system. Ceiling-Mount Surface Mount Back Box Skirt Dimensions Horn Strobe Combination (SBBCR,SBBCW): 6.9"diameter x 3.4"high The horn strobe shall be an L-Series Model listed (175 mm diameter x 86 mm high) to UL Standard 1971 and UL Standard 464 and shall be Notes: approved for fire protective service. The horn strobe shall 1. Full Wave Rectified(FWR)voltage is a non-regulated, be wired as a primary-signaling notification appliance and time-varying power source that is used on some comply with the Americans with Disabilities Act require- power supply and panel outputs. ments for visible signaling appliances,flashing at 1 Hz over 2. P, S, PC, and SC products will operate at 12 V the strobe's entire operating voltage range. The strobe nominal only for 15 and 30 cd. light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility UL Current Draw options and an option to switch between a temporal three Table 1 lists the UL maximum strobe current draw. pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on 8-17.5 Volts 16-33 Volts horn strobe models shall operate on a coded or non-coded Candela DC DC FWR power supply. 15 87 41 60 Synchronization Module 30 153 63 86 The module shall be a Sync•Circuit model MDL3 listed to 75 N/A 111 142 UL Standard 464 and shall be approved for fire protective 95 N/A 134 164 service. The module shall synchronize the L-Series 115 N/A 158 191 strobes at 1 Hz and synchronize horns at temporal three. 150 N/A 189 228 Also, while operating the strobes, the module shall silence 177 N/A 226 264 the horns on horn strobe models over a single-pair of wires. Table 1: UL Maximum Strobe Current Draw (mA RMS) The module shall mount to a 4 11/6 x 4 11/16 x 2 1/8-inch backbox. The module shall also control two Style Y(Class B) circuits or one Style Z (Class A) circuit. The module shall synchronize multiple zones. Daisy-chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 page 2 of 4 www.gamewell-fci.com 9021-60928 Rev.A J • UL Current Draw Data Table 2 lists the maximum UL Current Draw(mA RMS)allowed for 2-Wire Horn Strobes. 8 VDC 16 VDC Candela 15 30 15 30 75 95 115 150 177 EM Temp Hi 103 167 71 90 143 165 187 217 254 EM Temp Low 96 165 54 71 137 161 185 211 249 EM Cont Hi 106 173 71 90 141 165 187 230 273 EM Cont Low 95 166 54 71 124 161 170 216 258 3.1K Temp Hi 111 164 69 94 147 163 184 229 257 3.1K Temp Low 103 163 54 88 143 155 185 212 252 3.1K Cont Hi 111 172 69 94 144 164 202 220 271 3.1K Cont Low 103 169 54 88 131 155 187 217 259 16V FWR Candela 15 30 75 95 115 150 177 EM Temp Hi 107 135 179 198 223 254 286 EM Temp Low 78 101 151 172 199 229 262 EM Cont Hi 107 135 179 198 223 254 286 EM Cont Low 78 101 151 172 199 229 262 3.1K Temp Hi 108 _ 135 179 200 225 255 289 3.1K Temp Low 79 101 150 171 196 229 260 3.1K Cont Hi 108 135 179 200 225 255 289 3.1K Cont Low 79 101 150 171 196 229 260 Table 2 UL Max. Current Draw(mA RMS), 2-Wire Horn Strobe Horn Strobe Tones and Sound Output Data Table 3 lists the horn strobe tones and sound output date. 8-17.5 16-33 Switch Volts Volts Position Sound Pattern dB DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 Table 3: Horn Strobe Tones and Sound Output Data K GAMEWELL-FCI � 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 K, www.gamewell-fci.com 9021-60928 Rev.A page 3 of 4 SL Series Dimensions SL Series Dimensions Figure 1 illustrates the dimensions for the ceiling-mount Figure 2 illustrates the dimensions for the ceiling backbox horn strobes. surface mount backbox. 2.47 _ 6.92 1,37 6.83 1 f t rilii(I, /' c . ---.... I ! '' w \ v,,0,,,,,,',,,,,N-4,, ---' / Figure 2 Ceiling Backbox Surface-Mount Figure 1 Ceiling-Mount Horn Strobes Backbox L-Series Ordering Information Ceiling Horn Strobes Part Number Description PC2RL 2-Wire, Standard Horn Strobe, Red PC2WL 2-Wire, Standard Horn Strobe, White Ceiling Strobes _ SCRL Standard Strobe, Red SCWL Standard Strobe,White SCWL-CLR-ALERT Standard Strobe,White,ALERT Accessories TR-2 Universal Wall Trim Ring Red TR-2W Universal Wall Trim Ring White SBBCRL Ceiling Surface Mount Back Box, Red SBBCWL Ceiling Surface Mount Back Box, White GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 page 4 of 4 www.gamewell-fci.com 9021-60928 Rev.A , . , F LSeriesGamma l ow FIRE Indoor Horns, Strobes by Honeywell and Horn Strobes Description Indoor Selectable-Output Horns, Strobes, and Horn Strobes for The L-Series audible visible notification products offer the Wall Applications most versatile and easy-to-use line of horns, strobes, andpp horn strobes in the industry. In addition, this product includes lower current draws and a modern aesthetic design which reduce installation times and maximize prof- its. The following devices offer a variety of design options, so that the L-Series can be used for any application , , requirement. • White and red plastic housings. "� • Standard and small footprint devices. • Plain, FIRE, and FUEGO-printed devices. Similar to the entire L-Series product line, the wall-mount horns, strobes, and horn strobes include a variety of fea- l tures that increase their application versatility while simpli- fying the installation. All devices offer a plug-in design so w that there is minimal intrusion into the backbox.These fea- tures make installations fast and foolproof while eliminating ,.. costly and time-consuming ground faults. To further simplify the installation and protect devices from Wall Horns/Horn Strobes construction damage, the L-Series uses a mounting plate Features for all standard and compact models that include an on- board shorting spring. This feature allows Installers to test • Listed for wall mounting only. wiring continuity before the device is installed. Installers can also easily adapt devices to suit a wide • Offers small profile devices for horns and horn strobes. range of application requirements using the following fea- • Provides an automatic selection of 12-or 24-volt tures: operation at 15 and 30 candela. • Field-selectable candela settings. • Supports a rotary switch for horn tone and two volume • Automatic selection of 12-or 24-volt operation. selections. • Rotary switch for horn tones with two volume selections. • Produces horn rated at 88+dBA at 16 volts. L-Series Specifications • Uses field-selectable candela settings on wall units: Architect/Engineer Specifications -15 -30 -75 -95 General - 110 - 135 - 185 The L-Series standard horns,strobes,and horn strobes • Includes a mounting plate for all standard and all com- shall mount to any of the following enclosures: pact wall units. • standard 2 x 4 x 1 7/8-inch backbox • Contains a mounting plate with a shorting spring that • standard 4 x 4 x 1 1/2-inch backbox checks the wiring continuity before device installation. • 4-inch octagon backbox • Features a plug-in design with minimal intrusion into the • double-gang backbox backbox. The L-Series compact products shall mount to a single- • Designed with a tamper-resistant construction. gang 2 x 4 x 1 7/8-inch backbox. A universal mounting • Built with an updated modern design. plate shall be used for mounting ceiling and wall products • Supports electrical compatibility with the existing for all standard models and a separate universal mounting SpectrAlert and the SpectrAlert Advance products. plate shall be used for mounting wall compact models. • The notification appliance circuit wiring shall terminate at Compatible with System Sensor synchronization the universal mounting plate. Also, the L-Series products, protocol. when used with the Sync•Circuit, Module accessory, shall SIGNALING be powered from a non-coded notification appliance circuit OL output and shall operate on a nominal 12 or 24 volts. 41* ti ,` LISTED APPROVED 1. J-, PENDING ISO 9001 GAMEWELL-FCI MIM S&IIAMICIlWa QUALITY SYSTEMS 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 Specifications are for information only,are not intended for installation purposes,and are subject to change without notice.No responsibility is assumed by Gamewell-FCI for their use. 82016 by Honeywell International Inc. All rights reserved www.gamewell-fci.com 9021-60929 Rev.A page 1 of 4 L-Series Specifications (Continued) Physical/Electrical Specifications Architect/Engineer Specifications (Continued) General (Continued) Standard Operating When it is used with the Sync•Circuit Module,the following Temperature: 32°F to 120°F(0°C to 49°C) occur: Humidity Range: 10 to 93%non-condensing • 12-volt-rated notification appliance circuit outputs shall Strobe Flash Rate: 1 flash per second operate between 8.5 and 17.5 volts. Nominal Voltage: Regulated 12 DC or • 24-volt-rated notification appliance circuit outputs shall regulated 24 DC/FWR1 operate between 16.5 and 33 volts. Operating Voltage Rangel: 8 to 17.5 V(12 V nominal)or The Indoor L-Series products shall operate between 32 16 to 33 V(24 V nominal) and 120 degrees Fahrenheit from a regulated DC or full- Operating Voltage Range wave rectified unfiltered power supply. Strobes and horn (MDL3)Sync Module: 8.5 to 17 V(12 V nominal)or strobes shall have the following field-selectable candela 16.5 to 33 V settings: • 15 • 30 • 75 • 95 (24 V nominal) • 110 • 135 • 185 Input Terminal Wire Gauge: 12 to 18 AWG Strobe Wall-Mount Dimensions The strobe shall be an L-Series Model listed to (including lens): 5.6 L x 4.7 W x 1.25 D(143 UL Standard 1971 and shall be approved for fire protective mm Lx119 mm W x 32 mm D) service. The strobe shall be wired as a primary-signaling Compact Wall-Mount Dimensions: 5.26" L x 3.46"W x 1.93" D notification appliance and comply with the Americans with (including lens) (133 mm L x 88 mm W x 49 mm D) Disabilities Act requirements for visible signaling appli- Horn Dimensions: 5.6 L x 4.7 W x 1.25 D(143 ances, flashing at 1 Hz over the strobe's entire operating mm Lx119 mm W x 32 mm D) voltage range. The strobe light shall consist of a xenon Compact Horn flash tube and associated lens/reflector system. Dimensions: 5.25" L x 3.45"W x 1.25" D (133mm L x 88mm W x 32mm D) Horn Strobe Combination Notes: The horn strobe shall be an L-Series Model listed 1. Full Wave Rectified(FWR)voltage is a non-regulated, to UL Standard 1971 and UL Standard 464 and shall be time-varying power source that is used on some approved for fire protective service. The horn strobe shall power supply and panel outputs. be wired as a primary-signaling notification appliance and 2. P, S, PC, and SC products will operate at 12 V comply with the Americans with Disabilities Act requirenominal only for 15 cd and 30 cd. ments for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audible options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a Sync•Circuit model MDL3 listed to UL Standard 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also,while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires.The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch backbox. The module shall also control two Style Y (Class B) circuits or one Style Z(Class A)circuit.The module shall synchronize multiple zones. Daisy-chaining two or more synchroniza- tion modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 page 2 of 4 www.gamewell-fci.com 9021-60929 Rev.A UL Current Draw Table 2 lists the UL maximum Horn current draw. Table 1 lists the UL maximum Strobe current draw. 8-17.5 8-17.5 Volts 16-33 Volts Sound Volts 16-33 Volts Candela DC DC FWR Pattern dB DC DC FWR Candela 15 88 43 60 Temporal High 39 44 54 Range 30 143 63 83 Temporal Low 28 32 54 75 N/A 107 136 Non-Temporal High 43 47 54 95 N/A 121 155 Non-Temporal Low 29 32 54 110 N/A 148 1793.1 KHz Temporal High 39 41 54 135 N/A 172 209 3.1 KHz Temporal Low 29 32 54 185 N/A 222 257 3.1 KHz Non-Temporal High 42 43 54 Table 1: UL Maximum Strobe Current Draw(mA 3.1 KHz Non-Temporal Low 28 29 54 RMS) Coded High 43 47 54 3.1 KHz Coded High 42 43 54 Table 2: UL Max. Horn Current Draw(mA RMS) UL Current Draw Data Table 3 lists the maximum UL Current Draw(mA RMS)allowed for 2-Wire Horn Strobes, candala range(15-115cd). 1 8-17.5 Volts 16-33 Volts DC Input , 15cd 30cd 15cd 30cd 75cd 95cd 110cd 135cd 185cd EM Temp Hi 98 158 54 74 121 142 162 196 245 EM Temp Low 93 154 44 65 111 133 157 184 235 EM Cont Hi 106 166 73 94 139 160 182 211 262 EM Cont Low 93 156 51 71 119 139 162 190 239 3.1K Temp Hi 93 156 53 73 119 140 164 190 242 3.1K Temp Low 91 154 45 66 112 133 160 185 235 3.1K Cont Hi 99 162 69 90 135 _157 175 208 261 3.1k Cont Low 93 156 52 72 119 138 162 192 242 16V FWR FWR Input 15cd 30cd 75cd 95cd 110cd 135cd 185cd EM Temp Hi 83 107 156 177 198 234 287 EM Temp Low 68 91 145 165 185 _ 223 271 EM Cont Hi 111 135 185 207 230 264 316 EM Cont Low 79 104 157 175 197 235 283 3.1K Temp Hi 81 105 155 177 196 234 284 3.1K Temp Low 68 90 145 166 186 222 276 3.1K Cont Hi 104 131 177 204 230 264 326 3.1k Cont Low 77 102 156 177 199 234 291 Table 3: UL Max. Current Draw(mA RMS), 2-Wire Horn Strobe, Candela Range(15-115 cd) Horn Strobe Tones and Sound Output Data Table 4 lists the horn strobe tones and sound output data. 8-17.5 16-33 Switch Volts Volts Position Sound Pattern dB DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 9 Coded High 85 90 90 10 3.1 KHz Coded High 84 89 89 Table 4: Horn Strobe Tones and Sound Output Data GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 K_ www.gamewell-fci.com 9021-60929 Rev.A page 3 of 4 L Series Dimensions L Series Dimensions -3,45 —= --, a.6 1.25 T,_.. 1.25 / �;,,, r1 41740ilia 11 , ,asawa , ,ULe ..'...0...1, 14g�R 7.2 i"9 5.27 i �t ,,- .. !tag s.. Ekitft Figure 1 Compact Combo Figure 2 Compact Horn L Series Dimensions L Series Dimensions - 4.70 - _ 4.70 1.91 191 a 1.25 125 f , ,,,,- "','-",.....--. ":' -,,,,,, dp}xb i 7yt. .1R. 5.67 5,67 —L3-+ it Figure 3 Standard Combo Figure 4 Standard Horn L-Series Ordering Information L-Series Ordering Information Wall Horn Strobes Horns Part Number Description Part Number Description P2RL 2-Wire, Standard Horn Strobe, Red HRL Standard Horn, Red P2WL 2-Wire, Standard Horn Strobe,White HWL Standard Horn,White P2GRL 2-Wire, Compact Horn Strobe, Red HGRL Compact Horn, Red P2GWL 2-Wire, Compact Horn Strobe,White HGWL Compact Horn,White P2RL-P 2-Wire, Standard Horn Strobe,Red, Plain Accessories P2WL-P 2-Wire,Standard Horn Strobe,White,Plain TR-2 Universal Wall Trim Ring Red P2RL-SP 2-Wire,Standard Horn Strobe,Red, TR 2W Universal Wall Trim Ring White FUEGO SBBRL Standard Wall Surface Mount Backbox, P2WL-SP 2-Wire, Standard Horn Strobe,White, Red FUEGO SBBWL Standard Wall Surface Mount Backbox, Wall Strobes White SRL Standard Strobe, Red SBBGRL Compact Wall Surface Mount Backbox, Red SWL Standard Strobe,White SBBGWL Compact Wall Surface Mount Backbox, SGRL Compact Strobe, Red White SGWL Compact Strobe, White Notes: SRL-P Standard Strobe, Red, Plain All-P models have a plain housing SWL-P Standard Strobe,White, Plain (no"FIRE"marking on cover). SRL-SP Standard Strobe, Red, FUEGO All-SP models have"FUEGO"marking on cover. SWL-CLR-ALERT Standard Strobe,White,ALERT All-ALERT models have"ALERT"marking on cover. 1 GAMEWELL-FCI 1 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 page 4 of 4 www.gamewell-fci.com 9021-60929 Rev.A