Report 0C0c)k. sv3 RED ROCK CENTER SUITE 101 TENANT IMPROVEMENT OREGON REPRODUCTIVE MEDICINE 12115 SW 70th AVENUE TIGARD OREGON 97223 EGF JUL 2 3 2013 CITY OF TIGARD BUILDING DIVISIfN< �O`G� GOp� 0 FIRE DETECTION & ALARM SYSTEM SUITE 101 TENANT IMPROVEMENT battery&voltage-drop calculations, data sheets,&drawing sheet DTS DTS SYSTEMS INC. 7905 SW NIMBUS AVENUE BEAVERTON OREGON 97008 503-643-3127 CCB 134056 Battery Calculations ( RPS) Device: Model Qty standby total standby i alarm total alarm remote power supply 5495 1 0.075000 0.0750001 0.205000 0.205000 standby summary 0.075000 alarm sum 0.205000 standby time hours 24 panel total standby(AH) 1.8000 sileNo !?; Appliance Circuit: N1 N2 N3 N4 current 1 device NAC Device Model Qty Qty Qty Qty draw count Hom/Strobe at 15cd PC2L 2 3 2 2 _ 0.071 , 9 Hom/Strobe at 30cd PC2L 0 0 1 _ 1 0.090_ 2 Hom/Strobe at 75cd PC2L 0 0 0 0 0.143 0 hom/strobe at 95cd PC2L 0 0 0 0 0.165 0 hom/strobe at 110cd P2 0 0 0 0 0.162 0 hom.strobe at 150cd PC2L 0 0 0 0 0.217 0 Strobe at 15cd .SRL 6 4 8 7 0.043 25 Strobe at 30cd SRL 0 1 0 0 0.063 1 Strobe at 15cd SCL 0 0 0 0 0.041 0 Strobe at 30cd SCL 0 0 0 0 0.063 0 Strobe at 75cd SCL 0 0 0 0 0.111 0 Strobe at 95cd SCL 0 0 0 0 0.134 0 i weather-proof hom/strobe P2RK 0 0 0 0 0.176 0 0.4000 0.4480 0.5760 0.5330 1.9570 Alarm 2.1620 alarm multiplied for five minutes alarm 0.0830 Total NAG Panel&Device Alarm(AH) 0.1794 Safety Factor Total System AH Batteries Total Standby Total Alarm Required AH 1 Multiply by 1.2 Required Used € 1.8000 0.1794 i 1.9794 I Times 1.2 2.3753 8ah 'CerVoltage;DrOp Calculations(start voltage is 20.4 VDC, device operation range: 16-33 VDC total current draw 0.4 total current draw 0.448 NII I 14 awg wire length in feet 150 A'2 14 awg wire length in feet 170 voltage-drop 0.3684 'V voltage-drop 0.4676 voltage at last device 20.032 voltage at last device 19.932 total current draw 0.576 I total current draw 0.533 A t 14 awg wire length in feet 285 N 14 awg wire length in feet 265 I voltage-drop 1.0079 voltage-drop 0.8672 voltage at last device 19.392 voltage at last device 19.533 Suite 101 notification appliance circuits : N3 & N4 FIRE SYSTEM ACCESSORY Model 5495 0 SILENT KNIGHT Distributed Power Moduli in an emergency by Honeywer you need maximum power The 5495 Distributed Power Module by Silent Knight is the most powerful and cost-effective power supply available today. It delivers 6 amps of notification appliance circuit power and built-in synchronization for appliances from System Sensora,Gentexo,AMSECO®, Wheelock and Faraday—what you need to drive power- hungry components like ADA notification appliances. The 5495's advanced microprocessor design is years ahead of the competition. Its switch mode power supply design is up to 50% more efficient than competitive linear mode power supplies.And,ADA retrofits are easier and less expensive with the 5495 because it integrates into current systems without the costly investment in new components. For the mast sophisticated and cost-effective notification power supply available, you need the 5495. Call Silent Knight today for more information at 1-800-328-0103. Model 5495 to non-essential high-current Distributed Power Module accessories like magnetic door holders The 5495 is a 6 amp notification power . Built-in synchronization for expander that provides its own AC appliances from System power connection, battery charging Sensor®,Gentex®,AMSECO®, circuit, and backup battery for use with Wheelock and Faraday fire and security controls such as the Silent Knight Model 5208 Fire Cerro' • Stand alone operation /Communicator. The 5495 is the cost- • Lightweight design adds to ease of effective solution for powering installation and reduces shipping notification appliances required by the costs Americans with Disabilities Act(ADA). • Operates with most polarized, UL The 5495 has built-in ANSI cadence Listed notification devices pattern,which can upgrade older control panels that lack cadence • ANSI Cadence pattern output capability. capability built-in Features Connection to Local Fire Control • UL Listed for 6 amps of notification The 5495 may be connected to a local fire control iiieh utilizes Class A or power Model 5495 Class B type =ftification circuits Distributed Power Module - Power supply's advanced switch operating bet:veen 9 and 32 VDC. The mode design reduces damaging control panel's notification circuit is Approvals heat and manages power up to 50% connected to one of the inputs on the • UL Listed more efficiently than other systems 5495. The control panel's notification • MFA 479-92-F Vnl XII • Dip switches allow for easy circuit end-of-line resistor is also • CSFM 7300-0559:123 reconfiguration connected across two terminals on the • • 24 VDC filtered output voltage 5495, which provides supervision NFPA 72 Four power-limited notification between the 5495 and the fire control - OSHPD(CA)OSP-0065-10 outputs; 2 Class A or 4 Class B, or 1 panel. Polarized audible andfor visual (see accessories) Class A and 2 Class B notification devices are then connected • Additional continuous auxiliary to the 5495 signal circuits using the output 4.7kt-1 end-of-line resistors provided. Since the 5495 draws very little power - 3 amps per output circuit from the control, it is possible to • 2 inputs; 2 Class B or 2 Class A connect one 5495 to each notification • Ground fault detector/indicator circuit on the control panel and still • Independent trouble relay provide full supervision of the - AC loss delay option shuts off power notification circuits ail the way back to the control panel. FIRE SYSTEM ACCESSORY 4-Model 5495 Distributed Power - Mot: Model 549 5 B 1 o c tc Diagram Signal Circuit Output Signal q Signal 1 Input Distributed Signal2 Signal Circuit Output Signal 2 Power IInput Module 5495 Signal 3 (Optional) Signal 4 120 VAC Aux. Power Trouble Output Local Fire Control (Alternative to notification circuit trouble.) Supervision Current: 1 Input The 5495 supervises a variety of r------- Standby 75 mA1,-,s;-), voltage range: 9 -32 VDC functions including: Alarm 205 mA I ;' Battery charging • Low AC power Auxiliary capacity: 35.0 AH • Low battery condition power circuit: 1 Ambient temp.: 32° to 120° F • Earth ground fault Notification (0° to 49° C) • Auxiliary output power limit circuits: 4 Mechanical condition Output Dimensions: 12.25"W x 16" H x • EOL supervision trouble or configuration: 2 Class A(Style Z) 3" D (30.88 cm W power limited condition at an 4 Class B (Style Y) x 40.64 cm H x output When a trouble condition occurs, (1 Class A& 7.62 D cm) 2 Class B) Indicator Lights the 5495 creates a trouble condition on the host control signal Amps per AC paver on : Green circuits to which it is connected_the output circuit: 3.0 (6.0 amps total) Battery trouble: Yellow 5495 still maintains the ability to be Notification Ground fault: Yellow activated by the host control. In circuit output: 20.4 to 27.3 VDC addition, the 5495 provides a Form @ 3.0 amps each, Aux trouble: Yellow C trouble relay output as an 4.7 kS2 EOL Output troubles (1-4): Yellow alternative to using the notification resistor required Ordering information circuit trouble. on each Class B 5495 Distributed Power Module circuit Electrical Specification Accessories: No. of inputs 2 AC input: 120 VAC at 2 amps SK-SCK Seismic Compliance Kit Input Output: 24 VDC at 6 amps configuration: 2 Class B or 2 Class A `'9 ` IL NT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA , keep our product information up-to-date and accurate.We cannot cover all KNIGHT specific applications or anticipate all requirements.All specifications are FORM#350395 Rev F subject to change without notice. For more information, contact Silent Knight 2013 Honeywell International Inc. —oney.°ell 12 Clintonville Road,Northford,CT 06472-7161 Phone:(800)328-0103, Fax:(203)484-7118.For Technical Support,please call 800-446-6444. www.si ientknight.com DURACELL ---_ W - ,,ti „.� General Purpose ULTRA 3 ' kitt4 Z' - DURA12-8F . a moi,_ Specification L :. Cells Per Unit 6 }{ Voltage Per Unit 12 % . Capacity 8.0Ah@20hr-rate to 1.75V per cell @25°C Weight Approx.2.26 Kg(Tolerance+4%) m HI:Tom Max.Discharge Current 80A(5 sec) ",- (.: Internal Resistance Approx.25 m 0 Operating Temperature Range Discharge:-20'C-60°C Charge:0°C-50°C , Storage:-20°C-'60°C Normal Operating Temperature Range 25°C+5`C Float charging Voltage 13.7 to 13.9 VDC/unit Average at 25°C Recommended Maximum Charging 2.4A Current Limit Equalization and Cycle Service 14.6 to 14.8 VDClunitAverage at 25°C Self Discharge Duracell%Ultra Valve Regulated Lead Acid(VRLA)batteries can be stored for more than 6 months at 25'C.Self-discharge ratio less than 3%per month at25'C Please charge batteries before using Terminal Faston Tab 187(F1)/Faston tab 250(F2) Constainer Material A.B.S.UL94-HB,UL94-V0 Optional. Dimensions Unit.mm Dimension:151(L)x 65(W)X 100(H) S7 iiml F2 65 r • r i 1 G P E. Constant Curr a 9 Characteristics:A(25C) F.VITiine 5MIN 10Mi"! 15.t ,° 30MIN 1HR 2HR 311R 4HR 5HR 8HR 10HR 201-IR 9.60V 31 55 20.69 15 8.202 5.199 3179 2.095 1.706 1.402 0.924 0.800 0.428 10.0V 30.41 2017 1411 8.097 5.130 3.115 2.056 1.682 1.390 0.920 0.792 0.424 10.2V 28.63 19.17 14.50 7.973 5.081 3.082 2.038 1.665 1.381 4.912 0.779 0.413 10.5V 25.73 17.93 13.68 7.753 5=019 3.042 2.020 1.641 1.369 0.904 0.776 0.404 10.8V 23.06 16.72 12.90 7.497 4.949 3.017 1.996 1.585 1.362 0.900 0.763 0.388 11.1V 20.17 15.33 11.90 7.212 4.832 2.896 1157 1.562 1.357 0.893 0.751 0.381 Constant Power Discharge Characteristics W(25'C) F.VITime 5MIN 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR 9.60V 342.2 2268 1770.0 93.9 62.16 37.47 25.05 20.43 16.30 11.06 9.580 5.136 10.0V 333.3 222.1 167.6 92.9 61.24 36.97 24.64 : 20.14 1665 11.02 9.490 5.095 102V 317.0 213.3 165.4 92.1 60.79 36.65 24.43 19.95 16.55 10.94 9.368 4.964 10.5V 289.4 204.5 1565 90.2 59.97 36.25 24.25 19.68 16.42 10.84 9502 4.380 10.8V 2611 191.3 148.1 83.1 59.19 36.00 23.97 19.02 34 10.80 9.161 4.634 11.1V 2302 178.1 139.5 85.67 57.89 34.74 23.30 18.74 28 10.72 9.025 4.610 All mentioned values are average values(Tolerance+2%). URACELLGertral p -_ 2 0 Effect of to.o,..torttre,..-, term float life... Storage characteristic . 10 s 100 F _ I I , - (Carr nta Y h 5 quired 6 ----4=77Z-1-7 ,== e use 1C Lary barge ._ = l 80 1oa f r bit Ee a --r;'' r > 4 �. " 6D I before l Esta Y h g:' w'. > - r-> tj '.'-h.,, �- I • 1- film supplementary charge hl hep m ` .._.200 . d Sa IY P sbk. .s " 447 40.0 300 2 — S pP Mry hag ayoite:: ' 1 t r ran .tre an k. j-i 20 Th b t.,should by ell t d u41i Ve' �re� 0 2 4 8 8 10 12 14 16 18 20 22 24 a 0 10 20 30 44 50 Battery Temperature tc, Storage Time(months) .0ti.,5V00 v u r ,.2i0 f_...1I 1 at t,,.i,'b%1R,ze. - -. DiEriltrir rF 1 T , 5. ili Et 15,7.5 55 ■■.■■■■ ■ x120 0.24 13, 6.51 4-3_0_1_1_ ._ ( i.. t ti 1: :: : UIIL : h1::::, - lIl 7 _ f ) 1t-_ - �� _.> 12- 6.Cr4D -13 60- 4.0 012 > 11- 55- 37 _ 1 ,,,r005CAX2hh) ° 2. 50%20052AX19h) '.I_JSi, (0 Charge > a .€ - - i. 1 l L`hcrge Voltage2275V/C i, , ` m 11-5.5- 3 7 ■ Charge CurleMO.i CA ■ 40 0.09 `0 �' 10- 5.D- 3-3 U .I ®�.Q Temperature 25°C' U U I j '. 10-50_ 33 � ■.■■.■ 20 004 9 I 4.01 3.0 I 0 I i T i lI ®11111H1111=EZIMI i J 1 I I 1 I I 1 1 5 4.51 30-I .■■® D.5 12 3 6 12 30 ■- 0 1 o 1 2 5 1D 20 24 0 2 4 5 9 10 12 14 14 18 20 24 28 min Hr Charge Tune 157 I Discharge Time Capacity Factors With Different Temperature BATTERY TYPE -20°C -10°C 0°C 5°C 10°C 20°C 25°C 30°C 40°C 45°C AGM Battery 12V 46% 66% 76% 83% 90% 98% 100% 103% 107% 109% 1 g g Discharge Current VS.Discharge Voltage - Final DISCharg. 1,75V 1.70V 1 60V Voltage Vlcell Discharge -�02 0-20< (A) .C1 00 (A) >_31.0C Crrent_ t(A) Charge the batteries at least once every six months, if they are stored at 25°C. Charging Method: Constant Voltage 0.2Cx2h 2-4-2.45Vfcellx24h Max-Current 0 30 Constant C Current 0.2Cx2h+0.1C,12h Fast 0.2Cx2h C SCx4h I www.batteriesplus.com b 2014 DURACELL,a division of the Gillette Company,Bethel,CT 05 -CELL is a registered t 1 ,. .of the Gillette Company,used under Iicense.All rights reserved The information contained on this specification is generally descrlptn e trill and is not intended to make ar imply any representation guarantee or warranty moth respect to any c.li_and battenes.battenCeli and battery design) specification are subject to modification without nonce. • Ga ewell L-Series INSTRUMENTS ffi Flu Hems, Strokes, by Honeywell ate--3771 Sniebes _ _ _ --- Description indoor Selectable-Output Strobes, and Horn SPotuEtp for The L-Series audible visible notification products offer the most versatile and easy-to-use line of horns, strobes, and = horn strobes in the industry. In addition, this product includes lower current draws and a modern aesthetic design which reduce installation times and maximize prof- its. The following devices offer a variety of design options, so that the L-Series can be used for any application requirement. • White and red plastic housings. • Standard and small footprint devices. • Plain, FIRE,and FUEGO-printed devices. Similar to the entire L-Series product line, the wall-mount horns, strobes, and horn strobes include a variety of fea- tures that increase their application versatility while simpli- fying ° ' the installation. All devices offer a plug-in design so that there is minimal intrusion into the backbox. These fea- tures make installations fast and foolproof while eliminating and costly a d trine-consumin99 ground faults. _. To further simplify the installation and protect devices from rn Strobes construction damage, the L-Series uses a mounting plate Features for all standard and compact models that include an on- board shorting spring. This feature allows Installers to test • Listed for wall mounting only. wiring continuity before the device is installed. Installers can also easily adapt devices to suit a wide • Offers small profile devices for horns and horn strobes. range of application requirements using the following fea- • Provides an automatic selection of 12-or 24-volt tures: operation at 15 and 30 candela. • Field-selectable candela settings. • Supports a rotary switch for horn tone and two volume • Automatic selection of 12-or 24-volt operation. selections. • Rotary switch for horn tones with two volume selections. • Produces horn rated at 88+ dBA at 16 volts. L-Series Specifications • Uses field-selectable candela settings on wall units: Architect/Engineer Specifications - 15 -30 -75 -95 General - 110 - 135 - 185 The L-Series standard horns, strobes, and horn strobes • Includes a mounting plate for all standard and all corn- shall mount to any of the foll_-:,ino enclosures: pact wall units. • standard 2 x 4 x 1 7/8-inch backbox • Contains a mounting plate with a shorting spring that • standard 4 x 4 x 1 112-inch backbox checks the wiring continuity before device installation. • 4-inch octagon backbox • Features a plug-in design with minimal intrusion into the • double-gang backbox backbox. The L-Series compact products shall mount to a single- • Designed with a tamper-resistant construction. gang 2 x 4 x 1 7/8-inch backbox. A universal mounting • Built with an updated modern design. plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting • Supports electrical compatibility with the existing plate shall be used for mounting wall compact models. SpectrAlert and the SpectrAlert Advance products. • The notification appliance circuit wiring shall terminate at Compatible with System Sensor synchronization the universal mounting plate. Also, the L-Series products, protocol. when used with the Sync•Circuit, Module accessory, shall SIGNALING `NA•IN be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. 4110* LISTEDP PENDING ISO GAM EW EL L-F CI DIENtiat MUTT SYSTEM 12 Clintonville Road, Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 Specifications are for information only,are not intended for installation purposes,and are subject to change without notice.No responsibility is assumed by Gamewell-FCI fortheir use. c72016 by Honeywell International Inc All nghts reserved vwr wgamewell-fci.com 9021-60929 Rev.A page 1 of 4 L-Series Specifications (Continued) Physical/Electrical Specifications Architect/Engineer Specifications (Continued) General(Continued) Standard Operating When it is used with the Sync•Circuit Module,the following Temperature: 32°F to 120°F(0°C to 49°C) occur: Humidity Range: 10 to 93%non-condensing • 12-volt-rated notification appliance circuit outputs shall Strobe Flash Rate: 1 flash per second operate between 8.5 and 17.5 volts. Nominal Voltage: Regulated 12 DC or • 24-volt-rated notification appliance circuit outputs shall regulated 24 DC/FWR1 operate between 16.5 and 33 volts. Operating Voltage Rangel: 8 to 17.5 V(12 V nominal)or The Indoor L-Series products shall operate between 32 16 to 33 V(24 V nominal) and 120 degrees Fahrenheit from a regulated DC or full Operating Voltage Range wave rectified unfiltered power supply. Strobes and horn (MDL3)Sync Module: 8.5 to 17 V(12 V nominal)or strobes shall have the following field-selectable candela 16.5 to 33 V settings: • 15 • 30 • 75 • 95 (24 V nominal) • 110 • 135 • 185 input Terminal Wire Gauge: 12 to 18 AWG Wall-Mount Dimensions Strobe (including lens): 5.6 L x 4.7 W x 1.25 D(143 .` The strobe shall be an L-Series Model _ listed to mm LX119 mm W X 32mm D) UL Standard 1971 and shall be approved for fire protective Compact Wall-Mount service. The strobe shall be wired as a primary-signaling Dimensions: 5.26"L x 3.46"W x 1.93" D notification appliance and comply with the Americans with (including lens) (133 mm L x 88mm W x 49 mm D) Disabilities Act requirements for visible signaling appli Horn Dimensions: 5.6 L x 4.7 W x 1.25 D(143 ances, flashing at 1 Hz over the strobe's entire operating mm Lx119 mm W x 32mm D) voltage range. The strobe light shall consist of a xenon Compact Horn flash tube and associated lens/reflector system. Dimensions: 5.25"L x 3.45"W x 1.25" D (133mm L x 88mm W x 32mm D) Horn Strobe Combination Notes: The horn strobe shall be an L-Series Model_ listed 1. Full Wave Rectified(FWR)voltage is a non-regulated, to UL Standard 1971 and UL Standard 464 and shall be time-varying power source that is used on some approved for fire protective service. The horn strobe shall power supply and panel outputs. be wired as a primary-signaling notification appliance and 2. P, S, PC, and SC products will operate at 12 V comply with the Americans with Disabilities Act require nominal only for 15 cd and 30 cd. ments for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audible options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a Sync•Circuit model MDL3 listed to UL Standard 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. ,Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch backbox. The module shall also control two Style Y (Class B) circuits or one Style Z(Class A)circuit.The module shall synchronize multiple zones. Daisy-chaining two or more synchroniza- tion modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. • GAMEWELL-FCI 12 Clintonville Road. Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 page 2 of 4 www.gamewell-fci.com 9021-60929 Rev.A UL Current Draw Table 2 lists the UL maximum Horn current draw. Table 1 lists the UL maximum Strobe current draw. � 8-17.5 8-17.5 Volts 16-33 Volts I Sound Volts 16-33 Volts Candela DC 1 DC lq<<<'`f FWR ' Pattern dB DC DC FWR Candela 15 88 43 r 60 Temporal High 39 44 54 Range i 30 143 1 F 63 -t 83 Temporal Low 28 32 54 75 N/A F 107136 Non-Temporal High 43 47 54 95 N/A ; 121 ! 155 Non-Temporal Low 29 32 54 110 N/A 148 1 179 3.1 KHz Temporal High 39 41 54 135 N/A 172 209 13.1 KHz Temporal Low 29 32 54 185 N/A 72 257 3.1 KHz Non-Temporal High 42 43 54 Table 1: UL Maximum Strobe Current Draw(mA 3.1 KHz Non Temporal Low 28 29 54 Coded High 43 47 54 RMS) 3.1 KHz Coded High 42 43 54 Table 2: UL Max. Horn Current Draw(mA RMS) UL Current Draw Data Table 3 lists the maximum UL Current Draw(mA RMS)allowed for 2-Wire Horn Strobes,candala range (15-115cd). 8-17.5 Volts 116-33 Volts , 4r,. DC Input 15cd 30cd 1 15cd I 30cd 75cd I 95cd 110cd 1 135cd l 185cd EM Temp Hi 98 158 1 54 741 121 142 1162 1196 1245 EM Temp Low 93 154 A III-= ._ -- _ . 7 1-842u5 EM Cont Hi 106 166 73 94 139 160 182 211 262 EM Cont Low 93 156 51 71 119 139 162 190 239 3.1K Temp Hi 93 156 53 73 119 140 164 190 242 3.1K Temp Low +91 154 45 66 112 133 160 185 235 3.1K Cont Hi 99 162 69 90 135 157 175 208 261 3.1k Cont Low 93 156 52 72 119 1138 162 192 . 242 16V FWR FWR Input 15cd 30cd 75cd 95cd 110cd 135cd 185cd EM Temp Hi 83 107 156 177 198 234 287 EM Temp Low 68 91 145 165 185 223 271 EM Cont Hi 111 135 i 185 207 230 264 316 EM Cont Low 79 104 157 175 197 235 283 3.1K Temp Hi 81 105 155 177 196 234 284 3.1K Temp Low 68 90 145 166 186 222 276 3.1K Cont Hi 104 131 177 204 230 264 326 3.1k Cont Low 77 102 156 177 199 234 291 Table 3: UL Max. Current Draw(mA RMS), 2-Wire Horn Strobe, Candela Range (15-115 cd) Horn Strobe Tones and Sound Output Data Table 4 lists the horn strobe tones and sound output data. 8-17.5 16-33 I Switch Volts Volts Position Sound Pattern dB DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High ' 85 90 90 4 Non-Temp=oral Low 76 84 84 5 3.1 KHz Temporal Hiah 1 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 9 Coded High 85 90 90 10 3.1 KHz Coded High 84 89 89 Table 4: Horn Strobe Tones and Sound Output Data r GAMEWELL-FCI 12 Clintonville Road.Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 wwwgamewell-fci.corn 9021-60929 Rev.A page 3 of 4 L Series Dimensions L Series Dimensions z y Ti �.SCR Iii !!!!!,,,te:',,,,,,F7.,1,51,,,sy tF4C�YS§4%�y � � .,,.!,!,.:4.,3. S'i _ S'2.,. ; 4i 4'l is ;.� c 3� s�� a 1t,: F- i 5gags3FxY �r`S 5 F��FSF Figure 1 Compact Combo Figure 2 Compact Horn L Series Dimensions i L Series Dimensions r.,,,, , ,,,, ,:,,4 ,, ,1 „ „,..„, ,, , 44 d �Fi e f i i �,; s :ti i 1 `s 1 nttotts:A: ii t•� . i ' § • , r1 41 i t i ti i 4 t� Figure 3 Standard Combo , Figure 4 Standard Horn L-Series Ordering Information L-Series Ordering information Wall Horn Strobes Horns Part Number Description Part Number Description c ''FP2RL 2-Wire,Standard Horn Strobe, Red HRL Standard Horn, Red P2WL 2-Wire,Standard Horn Strobe,White HWL Standard Horn,White P2GRL 2-Wire,Compact Horn Strobe, Red HGRL Compact Horn, Red P2GWL 2-Wire, Compact Horn Strobe,White HGW cce Compact Horn,White P2RL-P 2-Wire,Standard Horn Strobe,Red, Plain Accessories P2WL-P 2-Wire,Standard Horn Strobe,White,Plain TR-2 Universal Wall Taira Ring Red P2RL-SP 2-Wire,Standard Horn Strobe,Red, TR-2W Universal Wall Trim Ring White FUEGO SBBRL Standard Wall Surface Mount Backbox, P2WL-SP 2-Wire,Standard Horn Strobe,Wnite, Red FUEGO SBBWL Standard Wall Surface Mount Backbox, —Wall Strobes White -,.vim SBBGRL Compact Wall Surface Mount Backbox, 3 ;. SRL Standard Strobe, Red i Red SWL Standard Strobe,White SBBGWL Compact Wall Surface Mount Backbox, SGRL Compact Strobe, Red White SGWL Compact Strobe, White Notes: SRL-P Standard Strobe, Red, Plain All-P models have a plain housing SWL-P Standard Strobe,White, Plain (no"FIRE”marking on cover). SRL-SP Standard Strobe, Red, FUEGO All-SP models have"FUEGO'marking on cover. SWL-CLR-ALERT Standard Strobe,White,ALERT All-ALERT models have"ALERT"marking on cover. GAM EWELL-FCI 12 Clintonville Road, Northford,CT 06472-1610 USA•Tel:(203)484-7161 • Fax:(203)484-7118 1 page 4 of 4 WNW.gamewell-fci.com 9021-60929 Rev.A I