Plans (9) BU ' 2016 - 00159 - - - , _ 01 00 00 GENERAL DATA d. PAINT CONTINUOUS BRIGHT CHROME"J"METAL,5/16"X 3/8" (HEIGHT OF EXPOSED FACE)WITH CONCEALED LEG TONS SHALL HAVE SPECIAL WRITTEN APPROVAL FROM PACTRUST. SCREWED TO THE WALL TO CARRY THE WEIGHT OF MIRROR. _ GENERAL REQUIREMENTS e. TILE,MARBLE,GRANITE,STONE,GROUT AND SCHLUTER TRIMS 7. HVAC UNITS EQUAL TO OR GREATER THAN 5-TONS TO HAVE DUCT SMOKE DETECTORS AND BE CONNECTED •.) 10.GRAB BAR SATIN FINISH BOBRICK B-6806 SERIES TO A MONITORING STATION WITHIN THE BUILDING. c.:_. #3082 _ 1. ALL CONSTRUCTION WORK SHALL BE DONE IN COMPLIANCE WITH THE LATEST EDITION OF THE OREGON f. TOILET PARTITIONS 10 28 13 BREAK COUNTER 8. ROOF TOP UNITS SHALL BE PLACED 24'MINIMUM FROM ROOF EDGE TO CENTER OF UNIT. MULTIPLE UNITS • STRUCTURAL SPECIALTY CODE AND ALL OTHER STATE OR LOCAL CODE REQUIREMENTS THAT APPLY. g. HARDWARE SHALL BE PLACED SYMMETRICALLY IN A LINE BASED ON LOAD CALCULATIONS BY STRUCTURAL ENGINEER. MARTIN W. HANSON t' 1. PAPER TOWEL DISPENSERS,SURFACE MOUNTED(KITCHEN/BREAK ROOM)BOBRICK B-262 a 2. VERIFY ALL DIMENSIONS AND CONDITIONS SHOWN ON DRAVVINGS AND AT THE EXISTING BUILDING AND 3. FINISH FLOORING TO EXTEND UNDER ALL NEW CASEWORK. 9 CURBS: 14"HIGH CURBS. ASSEMBLED AND LEVELED TO ROOF,ANCHORED TO STRUCTURAL MEMBERS / NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO STARTING THE WORK. 2. CUP DISPENSER-BOBRICK B-235 ' 4. PROVIDE A TRANSITION STRIP WHERE EVER TWO DIFFERENT FLOOR MATERIALS MEET BELOW ROOFING. • • 3. CONTRACTOR AND ALL SUBCONTRACTORS SHALL PERFORM DUE DILIGENCE INSPECTION OF ALL EXISTING 10 44 16 FIRE EXTINGUISHERS ti) C 'CKAvIAS, OREGON,„ , CONDITIONS PRIOR TO SUBMITTAL OF A PROPOSAL.SUBMITTAL OF A PROPOSAL SHALL BE CONSIDERED 5. PROVIDE SCHLUTER METAL TRIM AT ALL EXPOSED EDGES OF TILE(EXCEPT AT BULLNOSED EDGE)OF TILE a. PROFESSIONALLY ROOF IN ALL CURBS AND PENETRATIONS BY PACTRUST APPROVED ROOF ,e''' C•:1 1. FIRE EXTINGUISHER 2A10 BC (VVALL MOUNTED OR IN SEMI RECESSED CABINET AS INDICATED ON PLAN) CONTRACTOR. SEE DIVISION 1 GENERAL NOTES THIS PAGE. CONFIRMATION THAT SUCH INSPECTION HAS BEEN MADE,AND NO FURTHER COMPENSATION SHALL BE DUE (CERAMIC,QUARRY OR PORCELAIN) 1 THE CONTRACTOR FOR CLAIMS ARISING AS A RESULT OF FAILURE TO PERFORM SUCH INSPECTION. 09 21 00 GYPSUM BOARD 2. FIRE EXTINGUISHER CABINET: JL INDUSTRIES ACADEMY SERIES MODEL#C1027V10. b. UNIT MUST BE LEVEL,SEALED WITH NO AIR LEAKS AND COUNTER FLASHED. 4. BY SUBMITTING A PROPOSAL,CONTRACTOR AND ALL SUBCONTRACTORS CERTIFY THAT THEY HAVE GENERAL 11 00 00 EQUIPMENT c. CONDENSATE MUST BE TRAPPED AT UNIT. .1'4) OF 00 5 EXAMINED THE SITE AND INCLUDED IN THEIR PROPOSAL ALL WORK NECESSARY TO COMPLETE THE WORK DESCRIBED OR REASONABLY IMPLIED IN THESE DOCUMENTS. THIS INCLUDES BUT MAY NOT BE LIMITED TO 4. ALL GYPSUM BOARD WALLS: ONE LAYER 5/8"TYPE X GYPSUM WALLBOARD,EITHER AT RIGHT ANGLES OR 1. DISHWASHER: GE GLDT690JSS STAINLESS STEAL-ENERGY STAR RATED. • 7 SEISMICALLY ATTACH UNIT TO CURB IN CODE-APPROVED METHOD. ALL MATERIALS AND INSTALLATION,DISPOSAL OF EXCESS MATERIALS(USEABLE FINISH MATERIALS SHALL BE PARALLEL TO FRAMING ON EACH SIDE OF METAL STUDS SPACED AT 24"O.C. FASTEN WITH 1"TYPE S 2, GARBAGE DISPOSAL: INsINKERATOR BADGER‘,/1/2 Hp 8. ALL GAS PIPING SHALL BE STANDARD BLACK STEEL PIPE W/SUPPORTS PER CODE. PIPING SHALL BE RUN PROJECT #16220 LEFT IN THE TENANT SPACE AS DIRECTED BY PACTRUST),CLEANING AND ALL PREPARATION OF SUBSTRATE DRYWALL SCREWS 8"O.C.TO VERTICAL EDGES AND 12"O.C.TO TOP AND BOTTOM RUNNERS AND INSIDE OF BUILDING W/LEAD FLASHINGS AT ROOF PENETRATIONS. LEAD ROOF JACKS TO BE SEALED AND SURFACES PRIOR TO INSTALLATION,AS WELL AS FINAL CLEAN UP. INTERMEDIATE STUDS. STAGGER ALL VERTICAL AND HORIZONTAL JOINTS 24"O.C.(OR ONE STUD SPACING), 12 00 00 FURNISHINGS CLAMPED(STAINLESS STEEL WORM GEAR). EACH SIDE AND OPPOSITE SIDES.. 5. IT IS THE INTENT OF THESE CONTRACT DOCUMENTS TO MATCH AND MAINTAIN EXISTING BUILDING 1. CLEAN/REFURBISH EXISTING BUILDING STANDARD BLINDS AT ALL EXTERIOR GLASS. 9. ALL EXISTING AND NEW GAS PIPING EXPOSED TO THE EXTERIOR TO BE PROTECTED FROM RUST AND STANDARDS FOR ALL EXISTING PRODUCTS AND SYSTEMS. UPON DISCOVERY OF A DISCREPANCY TO THIS 5. ALL OFFICE GYPSUM BOARD TO RECEIVE ONE TAPE COAT AND TWO FINISH COATS WITH SANDING BETWEEN 2. INSTALL BUILDING STANDARD ADDRESS AND/OR SUITE NUMBER LABELS TO ALL EXTERIOR DOORS. CORROSION WITH OIL BASED PAINT(COLOR GREY). INTENTION,THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IMMEDIATELY. FINISH COATS. APPLY USG SHEETROCK BRAND FIRST COAT. PAINT AS INDICATED. 12 23 16 CABINET SPECIFICATIONS 10.LOW VOLTAGE IN SEALTITE CONDUIT FROM BELOW ROOF LINE DIRECT TO UNIT. DO NOT EXCEED BEND 0 6. FURNISH ALL NEW MATERIALS EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE. 6. ALL OTHER GYPSUM BOARD TO RECEIVE ONE TAPE COAT AND ONE FINISH COAT WITH SANDING AFTER FINISH RADIUS OF MANUFACTURER'S GUIDELINE. LIU COAT. PAINT AS INDICATED. 1. ALL CABINETRY TO BE INSTALLED OVER FINISH FLOOR AT ALL RESILIENT FLOORING LOCATIONS. • 7. COORDINATE THE WORK OF ALL TRADES. PROVIDE CARPET'WALK-OFF MATS"TO PROTECT EXISTING 11.ECONOMIZER TO MEET CODE AND AS FOLLOWS: F- CARPETS. 7. IN FINISHED SPACES FURR-OUT BUILDING COLUMNS AND EXTERIOR WALLS WITH 5/8"GYPSUM BOARD OVER 2. AVVI CUSTOM GRADE STANDARDS FOR CASEWORK AND COUNTER TOPS U.N.O a. 6 TONS AND ABOVE MUST HAVE ECONOMIZER. METAL STUDS. 8. ALL ROOF PENETRATIONS FROM ABANDONED EQUIPMENT TO BE REMOVED. PATCH AND REPAIR ROOF AND 3. HIGH PRESSURE LAMINATE(P-LAM HPL)ALL EXTERIOR SURFACES,INCLUDING 4"TOE KICK. EDGE BANDING I b. BAROMETRIC RELIEF ON 5-7 1/2 TON UNITS. ROOF MEMBRANE TO MATCH THE EXISTING ROOF. 8. PROVIDE ACOUSTIC GASKETS WHERE WALL INTERSECTS STOREFRONT, QUIETJOINT SHH WHERE WALL (MATCHING PVC ACCEPTABLE),FIN ENDS,DOORS,AND LIGHT VALENCE ETC. UPPER CABINET BOTTOMS 0 MEETS MULLION AND QUIETJOINT SHG WHERE WALL MEETS GLAZING.COLOR SELECTED BY ARCHITECT. OPTIONAL HPL FINISH,STANDARD MELAMINE FINISH. OPEN CABINETS OPTIONAL HPL FINISH,STANDARD c. 8 TONS AND ABOVE MUST HAVE POWER EXHAUST. 9. ALL ROOF WORK TO BE PERFORMED BY PACTRUST APPROVED ROOFING COMPANIES. APPROVED MELAMINE FINISH. CC COMPANIES INCLUDE: 9. AT ALL EXISTING WALLS,REMOVE ALL NAILS,SCREWS,FASTENERS,ETC.LEFT BY PREVIOUS TENANT AND d. 1 1/2 THRU 4-TON OSA INTAKE WITH DAMPER. PATCH HOLES READY FOR PAINT. 4. TOE KICK PLD 4"H WITH P-LAM COVER a. ARROW ROOFING, ALFONSO PEREZ (503)460-2767 PLYWOOD 12.ALL UNITS TO MEET OR EXCEED CURRENT ENERGY EFFICIENCY CODE REQUIREMENTS. < 10 REPAIR GYPSUM BOARD AT REMOVED ELECTRICAL RECEPTACLES OR DATA BOXES AND FINISH READY FOR 5. DOORS AND DRAWER FRONTS PLASTIC LAMINATE OVER 11/16"PARTICLE BOARD WITH MATCHING P-LAM OR b. PACIFIC ROOFING, GUY BELT (503)640-3163 'PAINT PVC EDGES. 13.DROP CANS TO BE SAME SIZE AS CURB OPENING AND TO EXTENDED TO WITHIN 2'OF SUSPENDED CEIILING. - MINIMUM 26 GAUGE FOR SUPPLY AIR. SEAL EDGES OF SUPPLY AIR. 0 c. GRIFFITH ROOFING, GREG STONE (503)643-1596 Z CD 11.UPON REMOVAL OF WALL BASE,REMOVE RESIDUAL ADHESIVE AND PREP WALL TO PAINT READY CONDITION. 6. MELAMINE(LOW PRESSURE LAMINATE/LPL)ALL INTERIOR AREAS,DRAWER PARTS,SHELVING ETC. 14.DISTRIBUTION DUCTWORK: 10.KEEP THE AREA OF WORK FREE OF GARBAGE AND DEBRIS ON A DAILY BASIS INCLUDING DOCK ACCESS WALL CONSTRUCTION MATERIALS 7. FLUSH OVERLAY/FRAMELESS STYLE CONSTRUCTION. 0 CI) AREAS AND COMMON AREA. FLOORS TO BE SWEPT OR VACUUMED DAILY. a. SPIRAL DUCT PERMITTED ONLY IF EXPOSED. 1 PROVIDE STUDS,TRACKS,BRACING,FASTENING AND OTHER ACCESSORIES NECESSARY FOR COMPLETE 8. HINGES-BLUM#75M3580,110 DEG.SELF CLOSING CLIP ON(OR EQUAL). 11.PROVIDE ADEQUATE PROTECTION TO ALL EXISTING IMPROVEMENTS INCLUDING BUT NOT LIMITED TO ' b. 26 GAUGE OR TO SMACNA STANDARDS WHERE DUCT IS CONCEALED ABOVE A CEILING. CO INSTALLATION. COMMON CORRIDORS AND STAIRS,BUILDING ENTRANCES,SUITE ENTRANCES,ETC. THE CONTRACTOR WILL 9. DRAWER SLIDES-BLUM #230M SERIES EXTENSION(OR EQUAL)75 LBS.MIN.FOR STANDARD DRAWERS. Z c. WRAP CONCEALED SUPPLY DUCTWORK IN NON-CONDITIONED AND SEMI-CONDITIONED SPACE WITH BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGES TO EXISTING IMPROVEMENTS DUE TO CONSTRUCTION 2. FRAMING MEMBERS SHALL HAVE THE STRUCTURAL PROPERTIES INDICATED WHERE PHYSICAL STRUCTURAL ACCURIDE#4032(OR EQUAL)HD/FULL EXT 150 LBS.MIN.FOR HD AND FILE DRAWERS. ACTIVITIES. PROPERTIES ARE NOT INDICATED,THEY SHALL BE AS NECESSARY TO WITHSTAND ALL IMPOSED LIVE LOADS. MINIMUM R4.2 INSULATION WITH FSK BARRIER. ..e. a...4- 10.PULLS-96 MM C-TO-C WIRE PULLS. FINISH TO MATCH DOOR HARDWARE. DESIGN FRAMING IN ACCORDANCE WITH AISI SG-673. d. HANGERS 12 GAUGE WIRE OR 18-GAUGE 1"WIDE STRAP. EXPOSED DUCT MUST HAVE ALL THREAD 12.PROVIDE TEMPORARY SANITARY FACILITIES. CONSTRUCTION WORKERS SHALL NOT USE BUILDING RAI <C\1 11 GENERAL CONTRACTOR TO PROVIDE CABINET MAKER WITH SINK TEMPLATE(SPEC SHEETS)FOR EACH SINK HANGERS AND FULL DIETER STRAP UP TO 18"0. LARGER THAN 18"MUST HAVE SADDLE TYPE CLAMP. RESTROOM FACILITIES. 3. COLD-FORMED FRAMING SHALL BE GALVANIZED METAL CONFORMING TO ASTM A446/A 446 M GRADE A(33000 ' • SINK CUTOUT SHALL BE DONE IN SHOP WHEN FEASIBLE AND BEFORE BACK SPLASH IS INSTALLED IN ALL . AMN- • (3) 13.STORAGE AND STAGING OF CONSTRUCTION MATERIALS SHALL BE LIMITED TO AREAS AS DESIGNATED AT PSI)G60. CASES TO ALLOW CUT OUT TO BE POSITIONED PROPERLY. ALL RAW EDGES OF CUT OUT AND BACK SPLASH e' BRANCH DUCTS SHALL BE PLUMB AND SQUARE(NO OCTOPUS). TEES SHALL BE MAXIMUM OF 45 0 0 LI) OIL) DEGREES. > D PRE-CONSTRUCTION MEETING. UNDER NO CIRCUMSTANCES SHALL BUILDING UTILITY AREAS OR ANY OTHER 4. PROVIDE THE LISTED GYPSUM BOARD PRODUCTS BY U.S.GYPSUM,GEORGIA PACIFIC,NATIONAL GYPSUM OR TO BE SEALED. MINIMIZE COUNTERTOP BUILD UPS AT FRONT AND BACK OF SINK CUT OUT TO rig CC ,Ct)N. COMMON BUILDING AREA BE USED FOR STORAGE. AN APPROVED EQUAL. ACCOMMODATE PLUMBERS SINK CLAMPS CLEARANCE. f. EACH BRANCH DUCT TO HAVE BALANCE DAMPER IN Y BRANCH. ,... " •-1 r-1 kw N- W I 1 14.KEEP THE ROOF FREE OF DEBRIS(I.E.NAILS,SCREVVS,BOTTLES,ETC.)AT ALL TIMES. 5. STANDARD GYPSUM BOARD SHALL BE'TYPE'X',5/8"THICK WITH TAPERED EDGES CONFORMING TO ASTM 12.KITCHEN/BREAK ROOM CABINETS-BASE CABINET WITH P-LAM TOP ON PLYWOOD DECKING AND 4"BACK g. ALL DISTRIBUTION DUCT WORK TO BE INSTALLED MIN.24"ABOVE FINISH CEILING. ZU) - " C-36 SPLASH. ALL CABINETS TO HAVE DOORS AND DRAWERS,U.N.O. UPPERS 12"DX 36"H-ATTACH TO WALL 0 CV CV 15.ALL DIMENSIONS ARE TO FACE OF GYPSUM BOARD UNLESS OTHERWISE NOTED. ' 15.FLEX DUCT WILL BE NO LONGER THAN 6'FROM RIGID DUCT DOWN TO DIFFUSER. WITH FRENCH CLEAT,COUNTER AND COUNTERTOPS 26"DEEP. P-LAM AT TOE/BASE. ALL SHELVES 1= Z ow 6 WATER RESISTANT GYPSUM BOARD SHALL BE 5/8"THICK WITH TAPERED EDGES. CONFORMING TO ASTM • . , . . 16.CONFIRM SIZES OF ALL OPENINGS REQUIRED FOR THE INSTALLATION OF STRUCTURAL,MECHANICAL, ' C-630' ADJUSTABLEPROVIDE HOLES AND POSTS(1 AT BASE2 AT UPPERS) 16DIFFUSERS: 1- co 5 .-........., ELECTRICAL AND PLUMBING WORK PRIOR TO FRAMING OR CUTTING FOR INSTALLATION. CO co 13 WORK/COPY/STORAGE CABINETS-BASE CABINETS WITH P-LAM TOP ON PARTICLE BOARD DECKING. SCRIBE a. SUSPENDED CEILING SYSTEM(T-BAR)-PERFORATED FACE ADJUSTABLE CURVED BLADES-DESIGN CC OF_ 0 0 7 AT TOILET ROOMS USE 5/8"USG FIBERROCK BRAND AQUATOUGH INTERIOR PANEL FROM FLOOR TO 48"A.F.F. ' 17.LEAVE THE PROJECT CLEAN AND READY FOR OCCUPANCY. • COUNTERTOPS TO WALLS. ALL CABINETS OPEN MELAMINE STANDARD INTERIORS VVITH DRAVVERS,U.N.O. TITUS PCS SUPPLY AND TITUS PAR RETURN OR APPROVED EQUAL. < 10 re. LO LO ON WALLS BEHIND OR ADJACENT TO PLUMBING FIXTURES. NO SUBSTITUTES.(EXCEPTION:EXCEPTION AT UPPERS AT 151)X 30"H -ATTACH UPPERS TO WALL WITH FRENCH CLEAT BASES AT 24"D X 36"H P LAM AT _.,,,u_ ................. 18.CLEAN ADJACENT EXTERIOR AREA,I.E.WALKS,EXTERIOR GLASS,ETC. LOCATIONS TO RECIEVE PLASTIC LAMINATE OR TILE WAINSCOT.) ' H. P-LAM GYPSUM BOARD CEILINGSUPPLY CURVED B . ; - LADE W/OBD DESIGN TITUS 250; - TYPE- TOE/BASE. ALL SHELVES ADJ.HOLES AND POST(1 AT BASE,1 AT UPPERS). RETURN BAR to 0 1 X DESIGN TITUS 350;EXHAUST-METAL OR ALUMINUM-1/2"x 1/2"EGG CRATE DESIGN TITUS 50F. 19.FILL ALL PAPER AND SOAP DISPENSERS IN RESTROOMS AND BREAK AREAS. 8. AT TILE WAINSCOT LOCATIONS INSTALL CEMENT BACKER BOARDY."THICK WITH SQUARE,REINFORCED, ,G. 1.-CL CL LL SMOOTH EDGES. PROVIDE DUROCK BRAND CEMENT BOARD OR APPROVED EQUAL. 21 00 00 FIRE SUPPRESSION : DESIGN I BUILD C. ALL SUPPLY REGISTERS TO HAVE MANUAL VOLUME DAMPERS LOCATED IN DUCT AT OR NEAR CLOSEST 20.CLEAN ALL SUPPLY AND RETURN DIFFUSERS AT PROJECT COMPLETION. 9. INSTALL WATER-RESISTANT GYPSUM BOARD BEHIND WAINSCOT OF FRP,PLASTIC LAMINATE,ETC. 1. PROVIDE SPRINKLERS THROUGHOUT SPACE AS REQUIRED BY CODE. SPRINKLER HEADS SHALL BE WYE BRANCH. 21.PROVIDE"AS-BUILT"DRAWINGS OF THE WORK AT THE CONCLUSION OF CONSTRUCTION."AS-BUILT' CENTERED IN 2 X 2 CEILING TILE.LAYOUT OF SPRINKLERS BY CONTRACTOR. SPRINKLER LAYOUT IN ALL HARD 17. THERMOSTAT: ALL EXISTING MERCURY TYPE THERMOSTATS TO BE REPLACED. NEW THERMOSTATS TO DRAWINGS MAY BE IN THE FORM OF TWO COPIES OF CONSTRUCTION DOCUMENTS MARKED-UP WITH RED 10.TRIM ACCESSORIES SHALL COMPLY WITH ASTM C-1047. CEILING AREAS(GYPSUM BOARD/PLASTER)TO BE REVIEWED AND APPROVED BY ARCHITECT PRIOR TO BEHONEYWELL COMMERCIAL GRADE VISIONPRO 8000 TOUCH SCREEN MODEL TB8220U1003 WHERE POSSIBLE. PEN.DELIVER RECORD DRAWINGS TO THE ARCHITECT. COMPLETE OPERATION AND MAINTENANCE MANUALS 11.USE GEORGIA PACIFIC DENSGLAS GOLD ON EXTERIOR FACE OF EXTERIOR WALLS AND COAT WITH STO FINISH INSTALLATION. APPROVED SUBSTITUTE: TOTAL-UNE SIGNATURE COMMERCIAL THERMOSTAT MODEL NO.P374-2800 -7 DAY SHALL BE PROVIDED FOR ALL MECHANICAL,ELECTRICAL AND PLUMBING EQUIPMENT.PACTRUST MAY HOLD PROGRAMMABLE WITH LOCKOUT FUNCTION-AUTO CHANGEOVER ONLY. MOUNT AT ADA HEIGHT(MAY REQUIRE >II SYSTEM. 2. IN NEW CEILING GRID SYSTEMS OVER 144 SF PROVIDE FLEXIBLE HEADS FOR MINIMUM SEISMIC MOVEMENT. • CONTRACTOR'S FINAL PAYMENT UNTIL"AS-BUILT"DRAWINGS AND 0&M MANUALS HAVE BEEN RECEIVED AND APPROVED. WALL CONSTRUCTION EXECUTION NO'OOPS RINGS ALLOWED". CHANGING HEIGHT AT"REPLACEMENT"LOCATIONS). CONTRACTOR SHALL PROGRAM THERMOSTATS AND 1.11 BALANCE SYSTEM. 22.IT IS THE INTENT OF THE CONTRACT DOCUMENTS THAT THE CONTRACTOR PROVIDE A COMPLETE, 1. FASTEN FRAMING MEMBERS TOGETHER BY WELDING OR BY USING SELF-DRILLING OR SELF-TAPPING 3. PROVIDE AUTOMATIC FIRE SPRINKLER FLOW INDICATOR SIEMENS CU-MHU-MCS-W OR EQUAL.SEE PLAN FOR a FUNCTIONING PROJECT INCLUDING ALL GENERAL,MECHANICAL AND ELECTRICAL CONSTRUCTION REQUIRED SCREWS. WELDING SHALL CONFORM TO AWS D13 WELDING PROCEDURE. ELECTRODES AND SCREW LOCATIONS. 18.THERMOSTAT LOCATIONS TO BE REVIEWED BY ARCHITECT PRIOR TO INSTALLATION. 19.WAREHOUSE HEAT: LII TO FULFILL THAT INTENT. ALL ITEMS REQUIRED SHALL BE FURNISHED AND INSTALLED,REGARDLESS OF CONNECTIONS SHALL BE AS REQUIRED AND INDICATED IN THE DESIGN CALCULATIONS. DO NOT FIELD WELD 22 00 00 PLUMBING : DESIGN/BUILD WHETHER OR NOT SHOWN ON THE DRAWINGS. MATERIALS LIGHTER THAN 18 GA. a. GAS FIRED UNIT HEATERS USED IN NON-CONDITIONED EAS SHALL COMPLY WITH CURRENT STATE GENERAL REQUIREMENTS AR11, 23.ITEMS OR WORK NOT TO BE FURNISHED OR ACCOMPLISHED BY CONTRACTOR ARE NOTED"N.I.C.". 2. PROVIDE ACCURATELY ALIGNED RUNNERS AT TOP AND BOTTOM OF PARTITIONS. ANCHOR TRACKS AS ENERGY CODE REQUIREMENTS. PROVIDE ADJUSTABLE T-STAT FOR EACH UNIT. INDICATED IN THE DESIGN CALCULATIONS. BUTT WELD JOINTS IN TRACKS OR SPLICE WITH STUD INSERTS. 1. CONTRACTOR TO SUBMIT LAYOUT ON ELEVATIONS AND PLANS PROVIDED FOR ALL SHUT OFF VALVES,CLEAN 0 20.EXHAUST FANS: 24."ALIGN"AS USED IN THESE DOCUMENTS,MEANS TO ALIGN THE FINISHED FACES OF ELEMENTS IN THE SAME FASTENERS SHALL BE AT LEAST 3 INCHES FROM THE EDGE OF CONCRETE SLABS. OUTS,ACCESS DOORS,AND FLOOR DRAINS TO THE ARCHITECT FOR APPROVAL PRIOR TO INSTALLATION. .i...3 ... PLANE,EITHER IMMEDIATELY ADJACENT TO ONE ANOTHER OR ACROSS AN OPENING. a. CEILING MOUNTED EXHAUST FANS SHALL HAVE A MINIMUM PERFORMANCE TO MEET THE CURRENT 3 CUT STUDS SQUARE AND SET VVITH FIRM BEARING AGAINST WEBS OF TOP AND BOTTOM TRACKS. pOSMoN 2. PLUMBING CONTRACTOR TO PROVIDE AND INSTALL(1)MASTER SHUT OFF VALVE FOR EACH SET OF 0) a 25.D0 NOT DISASSEMBLE SETS OF CONSTRUCTION DRAWINGS.DRAWINGS ARE INTERRELATED. ' CODE REQUIREMENTS 1NCWDING INTEGRAL BACKDRAFT DAMPER AND VENTING TO THE EXTERIOR. STUDS VERTICALLY IN TRACKS AND SPACE AS INDICATED IN DESIGN. DO NOT SPLICE STUDS. PROVIDE AT RESTROOMS. LOCATE VALVE BEHIND HANDICAP WATER CLOSET IN MEN'S TOILET ROOM. COOK GEMINI SERIES 100 OR EQUAL;80 CFM WITH A SONE RATING OF 1.6 OR LESS,100 CFM WITH A 0 a 26.SUBMIT SAMPLES OR DRAW DOVVNS FOR ALL FINISHES REQUESTED TO THE ARCHITECT OF RECORD WITHIN LEAST TWO FULL HEIGHT KING STUDS AT DOORS AND OTHER OPENINGS 2 FEET WIDE OR LARGER. PROVIDE 3. ALL DOMESTIC WATER PIPING TO BE'TYPE L COPPER-NO EXCEPTIONS. ALL EXPOSED PIPING TO BE SONE RATING OF.9 OR LESS,200 CFM VVITH A SONE RATING OF 1.6 OR LESS. TWO WEEKS OF PROJECT AWARD.PRODUCTS INSTALLED WITHOUT APPROVED SAMPLES ARE SUBJECT TO JACK STUDS OVER OPENINGS,AS NECESSARY,TO MAINTAIN INDICATED STUD SPACING. PROVIDE TRIPLE INSULATED. - I REPLACEMENT AT CONTRACTOR COST.AN APPROVED SUBMITTAL DOES NOT CHANGE THE CONTRACTUAL STUDS AT CORNERS,POSITIONED TO RECEIVE INTERIOR AND EXTERIOR FINISHES. FASTEN STUDS AT TOP b. SINGLE FIXTURE RESTROOMS,JANITOR'S CLOSETS OR SINGLE SHOWER ROOMS TO HAVE CEILING REQUIREMENT TO PROVIDE THE SPECIFIED ITEMS UNLESS SPECIFICALLY NOTED AS A SUBSTITUTION BY THE AND BOTTOM TRACKS BY VVELD1NG OR SCREWING BOTH FLANGES TO THE TRACKS.PROVIDE LONG LEG 4. WATER HEATER(ELECTRIC)30 GAL AND LARGER 277V LESS THAN 30 GAL 120V. PROVIDE HUB DRAIN AT MOUNTED EXHAUST FANS,WIRED PER DIVISION 16 AND SVVITCHED VVITH THE LIGHTS. ..g. CONTRACTOR AND SPECIFICALLY APPROVED BY THE ARCHITECT AS SUCH.REPLACE SUCH PRODUCTS AS TRACK AT TOP OF WALL TO ALLOW FOR DEFLECTION WHERE WALL MEETS STRUCTURE ABOVE. LOCATION FOR BLOW OFF. c. MULTIPLE FIXTURE RESTROOMS,COMBINATION RESTROOM&SHOWER,AND LOCKER ROOMS TO HAVE 0 in DIRECTED AT CONTRACTOR'S COST. 4. INSTALL ALL INTERIOR AND EXTERIOR GYPSUM BOARD PRODUCTS AND ACCESSORIES AS REQUIRED FOR 5. POINT OF DEMAND WATER HEATER-BOSCH POWER STREAM PRO-MODEL RP2P 277V/30A. ADJUST WATER ROOFTOP MOUNTED EXHAUST FAN,FACTORY CURB AND BACKDRAFT DAMPER,WIRED PER DIVISION 16, o 3 27.SUBMIT COMPLETE SHOP DRAWINGS FOR MILLWORK,SPECIAL SYSTEMS,MECHANICAL,ELECTRICAL AND THE PROJECT. FLOW SETTING TO PROVIDE A HEATING RANGE OF 105 TO 120 DEGREES. CONTACT MESHER SUPPLY FOR CONTROLS AS REQUIRED BY DESIGN.COOK ACE-D SERIES OR EQUAL • PLUMBING SYSTEMS(INCWDING FIRE PROTECTION SYSTEMS). SUBMIT A MINIMUM OF TWO COPIES OF ALL AVAILABILITY,(503)236-4148. z rr 5 AT TOILET ROOMS TO RECEIVE SHEET VINYL FLOORING,INSTALL THE GYPSUM BOARD(OR AUQATOUGH) d. SPECIALTY ROOMS REQUIRING EXHAUST SHALL MEET THE ABOVE MINIMUM REQUIREMENTS- 0 PA SHOP DRAWINGS FOR REVIEW AND APPROVAL TO THE ARCHITECT OF RECORD.ARCHITECT WILL RETAIN ONE ' WITH 1/4"GAP BETWEEN THE BOARD AND THE FLOOR TO PREVENT WICKING. 6. FLOOR DRAINS SHALL BE INSTALLED IN TOILET ROOMS CONTAINING'TWO(2)OR MORE WATER CLOSETS OR 2 INDIVIDUAL ROOMS WITH AN EXHAUST REQUIREMENT GREATER THAN 250 CFM,SHALL HAVE A COPY AND ONE COPY WILL BE RETURNED TO THE CONTRACTOR. OR MORE WATER CLOSETS AND URINALS IN COMBINATION. THE FLOOR SHALL SLOPE TOWARD THE FLOOR ROOFTOP MOUNTED FAN. -I l' 6 COMPLY WITH USG GYPSUM CONSTRUCTION HANDBOOK AND MANUFACTURER'S RECOMMENDATIONS. 28.THE DESIGN OF FIRE PROTECTION SYSTEMS IS THE RESPONSIBILITY OF THE FIRE PROTECTION SYSTEMS ' DRAIN. 21.HVAC TESTING. 5 0 CONTRACTOR.ALL FIRE PROTECTION SYSTEMS SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER 7. FINISH QUALITY: 7. FLOOR DRAINS TO BE INSTALLED WITH PRIMER VALVE WITH ISOLATION VALVE. NO ATMOSPHERIC PRIMERS. 03 4 LICENSED BY THE APPROPRIATE JURISDICTION FOR THE DESIGN OF THIS TYPE OF SYSTEM. COORDINATE a. CONTROL SYSTEMS SHALL BE TESTED TO ENSURE THAT CONTROL DEVICES,COMPONENTS, TRADE NOMENCLATURE AREA PROCESS DRAINS TO BE PRIMED FROM TOILET FIXTURES UNLESS OTHERWISE APPROVED BY PACTRUST. PROVIDE A EQUIPMENT AND SYSTEMS ARE CALIBRATED,ADJUSTED AND OPERATE IN ACCORDANCE WITH INTERFACE WITH EXISTING BUILDING SYSTEMS AND WITH ARCHITECT. ALL SPRINKLER HEADS SHALL BE MIN.12'x 12"ACCESS DOOR. - CENTERED IN CEILING TILE(OR 2 x 2 MODULE OF A SECOND LOOK II TYPE OF CEILING TILE WHERE WAREHOUSE TAPE/FINISH COAT* TIGHT DOUBLE APPROVED PLANS AND SPECIFICATIONS. EL APPLICABLE). LOCATION OF THOSE IN GYPSUM BOARD CEILINGS SHALL BE PRE-APPROVED IN WRITING BY OFFICE/OTHER AREAS TAPE/2 FINISH COATS*/ SMOOTH FINISH TAPED PLUMBING-REST ROOM FIXTURES b. SEQUENCES OF OPERATION SHALL BE FUNCTIONALLY TESTED TO ENSURE THEY OPERATE IN THE ARCHITECT PRIOR TO INSTALLATION. 1 REUSE EXISTING FIXTURES WHERE POSSIBLE. ACCORDANCE WITH APPROVED PLANS AND SPECIFICATIONS. r USG"FIRST Com* *SAND AFTER TAPE/FINISH COAT(S) . 4 29.COORDINATE ALL CONSTRUCTION SEQUENCING WITH PACTRUST AND SCHEDULE ALL SERVICE 2. WALL HUNG LAVATORY TOTO LT307.4 c. A COMPLETE COMMISSIONING REPORT OF TEST PROCEDURES AND RESULTS SHALL BE PREPARED AND _ INTERRUPTIONS OUTSIDE NORMAL BUSINESS HOURS TO MINIMIZE INCONVENIENCE TO CURRENT TENANTS. 8. FINISH EXPOSED INTERIOR GYPSUM BOARD WALLS AND CEILINGS SMOOTH STRAIGHT READY FOR FINISH AS FILED WITH PACTRUST. SHOWN ON PLANS. 3. LAVATORY FAUCET-DELTA 501 DST GENERAL 22 PROJECT CLOSE OUT DOCUMENTS REQUIRED: 09 63 00 SUSPENDED ACOUSTICAL CEILING 4. TOILET W/FLUSHOMETER-AMERICAN STANDARD AS 2234.015 AT NON ACCESSIBLE STALLS AND 2305.100 AT • 1. REMOVE ALL EXISTING VCT,SHEET VINYL,ETC.IN AREAS WHERE NEW FLOOR COVERING IS SPECIFIED PRIOR ACCESSIBLE LOCATIONS. FLUSHOMETER SLOAN FLUSH VALVE 111 OR TANK TYPE TOTO CST744SL AS a. AutoCAD FILE SHOWING AS-BUILT INFORMATION. TO INSTALLATION OF NEW FLOORING. 1. COMPLY WITH CURRENT SEISMIC REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE, INDICATED ON PLAN. b. ELECTRONIC PDF FILE OF THE AutoCAD FILE ABOVE. 2. ALL ROOF PENETRATIONS FOR ELECTRICAL,LOW VOLTAGE,GAS PIPING,ETC.SHALL BE SLEEVED THROUGH 2. FOLLOW MANUFACTURERS PRINTED INSTRUCTIONS FOR THE DELIVERY AND INSTALLATION OF CEILING 5. TOILET SEAT: BEMIS 1955SSC OR OLSONITE 10SSCT A LEAD ROOF JACK,CLAMPED WITH A STAINLESS STEEL CLAMP AND SEALED WITH VULKEM 921 SYSTEM,INCLUDING GRID,PANELS,AND HANGARS AND ACCESSORIES. C. HARD COPY OF AutoCAD FILE ABOVE. POLYURETHANE SEALANT. SILICONE SEALANT NOT PERMITTED. 3. USE ALL PRODUCTS FROM ARMSTRONG WORLD INDUSTRIES,INC. 6. AT BACK TO BACK TANK TYPE TOILET INSTALLATIONS US 3"VENT THROUGH ROOF d. OPERATIONS MANUALS FOR ALL EQUIPMENT,INCLUDING T-STATS. 01 73 29 CUTTING AND PATCHING 4. CO-ORDINATE CEILING WORK WITH INSTALLERS OF RELATED WORK INCLUDING BUT NOT LIMITED TO 7. URINAL-TOTO UT447,AMERICAN STANDARD WASHBROOK 6501.010,OR KOHLER K-5016-ET W/FLUSH VALVE SLOAN 186-1 e. COLORED ZONE MAP WITH THERMOSTAT LOCATIONS INDICATED. 1. PERFORM CUTTING AND PATCHING WITH SKILLED CRAFTSMEN EXPERIENCED WITH THE TYPE OF WORK INSULATION,GYPSUM BOARD,LIGHT FIXTURES,MECHANICAL SYSTEMS,ELECTRICAL SYSTEMS AND FIRE 26 00 00 ELECTRICAL :DESIGN I BUILD BEING UNDERTAKEN. SPRINKLERS 8. SHOWER STALL-FIBERFAB ASSISTED LIVING MODEL#38-H1-LP WITH ROUGH OPENING OF 38"WIDE BY 42" DEEP. GENERAL 2. PROTECT EXISTING CONSTRUCTION TO PREVENT DAMAGE. 5. PRODUCTS: 9. SHOWER STALL FAUCET-DELTA 57021 CHROME OR EQUAL. I. ALL ELECTRICAL FEEDS TO OUTLETS,SWITCHES,ETC.MUST BE VERTICAL DROPS FROM ABOVE EXCEPT FOR 3. PERFORM CUTTING USING METHODS LEAST LIKELY TO DAMAGE ELEMENTS TO BE RETAINED. a. GRID-PRELUDE 24 XL 15/16*EXPOSED TEE(HEAVY DUTY) 10.PROVIDE ONE FLOOR DRAIN IN EACH RESTROOM LOCATED UNDER TOILET PARTITION. HORIZONTAL RUNS UNDER WINDOWS AND RECEPTACLES ON THE SAME STUD. 4. PATCH,USING MATERIALS IDENTICAL TO EXISTING MATERIALS THAT VISUALLY MATCH EXISTING ADJACENT b. TILES-ARMSTRONG FISSURED ITEM#705,24 x 24 x 5/8"W/ANGLED TEGULAR EDGE II.SEALANT AT PLUMBING FIXTURES: 2. ALL ELECTRICAL FEEDS TO OUTLETS AND DATA BELOW WINDOW SILLS TO BE ROUTED THROUGH BUILDING SURFACES TO THE FULLEST EXTENT POSSIBLE c. ACCESSORIES-MANUFACTURERS'STANDARD SHELL WALLS. DO NOT FEED FROM PERPENDICULAR INTERIOR PARTITIONS. 5. ALL SEALANT SHALL MATCH GROUT COLOR AT TILE SURFACES. 6. PATCH WITH DURABLE,INVISIBLE SEAMS THAT ELIMINATE EVIDENCE OF PATCHING AND REFINISHING. 6. ALL TILE CUTS SHALL BE DONE WITH RAZOR SHARP KNIVES. CUT/TRIM TILE EDGE TO CREATE TEGULAR EDGE a. * 3. PROVIDE LABELS AT EACH ELECTRICAL RECEPTACLE IDENTIFYING CORRESPONDING PANEL AND BREAKER. 6. AT CONCRETE SLAB REPAIRS(POUR BACKS),PROVIDE#3 x 12"LONG REBAR DOWELS AT 24"O.C. MIN.WITH CONDITION SO THAT CEILING TILES LAY FLAT. • b SUBMIT SEALANT COLOR PRIOR TO INSTALLATION FOR ARCHITECT APPROVAL FOR ALL OTHER ai APPLICATIONS. 3. PROVIDE TYPEWRITTEN UPDATED SCHEDULE AT PANEL TO IDENTIFY CIRCUIT BREAKERS. 0 MIN.6"PENETRATION INTO EXISTING CONCRETE AND MIN.OF 6"EXPOSURE INTO POUR BACK.CENTER 7. AT CEILINGS OVER 144 SF PROVIDE HORIZONTAL RESTRAINT WIRE OR RIGID BRACING. CC DOWEL IN SLAB DEPTH. PLUMBING-BREAK ROOM FIXTURES 4. VERIFY ELECTRICAL METER AND TAG METER WITH THE TENANTS ADDRESS OR SUITE NUMBER. METER 8. INSTALL CEILING GRID WITH TWO EDGES ATTACHED TO ADJACENT WALLS. THE OTHER TWO EDGES SHALL BE IDENTIFICATION NUMBER AND TENANT ADDRESS INFORMATION SHALL BE GIVEN TO PACTRUST PRIOR TO 7. REMOVE PATCHES THAT ARE VISUALLY UNSATISFACTORY IN THE ARCHITECTS OPINION AND REPLACE AT NO ATTACHED TO WALL MOLD USING BERC2 CLIPS ALLOWING THOSE TWO SIDES TO FLOAT. 1. REUSE EXISTING FIXTURES WHERE POSSIBLE. TENANTS MOVE-IN. ADDITIONAL COST. 9. PROVIDE CEILING SEISMIC JOINTS AT LOCATIONS AS SHOWN TO LIMIT CONTIGUOUS CEILING GRID AREAS TO 2. BREAK ROOM SINK ELKAY GECR2521 5. ELECTRICAL CONTRACTOR TO PROVIDE EMERGENCY LIGHTING IN EXIT PATH SHOWN ON PLAN EQUAL TO 07 00 00 THERMAL&MOISTURE PROTECTION NO MORE THAN 2500 S.F.THE STATIONARY SIDE OF THE JOINT SHALL PERMIT THE INSTALLATION OF A LIGHT31-FOOT CANDLE. co 1. REPLACE ALL MISSING AND DAMAGED ROOF AND WALL INSULATION ABOVE THE CEILING GRID. FIXTURE IMMEDIATELY ADJACENT TO THE JOINT. . KITCHEN FAUCET DELTA 100-DST 6. EXIT LIGHTS:RUUD LIGHTING'PLASTIC LED EXIT SIGN"MODEL EXPBURVVH RED LETTERS,VVHITE HOUSING, 0 • 4. INSTANT HOT WATER DISPENSER IN-SINK-ERATOR MODEL#H770-SS 1..... r-- 2. PROVIDE NEW ROOF INSULATION TO MATCH EXISTING AT ABANDONED MECHANICAL UNITS. 10.PROVIDE RIGID STRUTS TWELVE FEET ON CENTER EACH WAY BEGINNING WITHIN SIX FEET OF PERIMETER WITH BATTERY BACKUP. a) - EDGE. INSTALL SWAY BRACING EACH STRUT ALONG FIXED EDGE IN ALL FOUR DIRECTIONS 5. 1/4°COPPER WATER LINE W/SHUT OFF VALVE FOR COFFEE MAKER AND REFRIGERATOR,SEPARATE LINES IF +a 0 3. AT ALL UN-USED EXISTING ROOF PENETRATIONS,REMOVE EQUIPMENT AND REPAIR ROOF SYSTEM. REQUIRED. 7. WHERE NEEDED,CONTRACTOR TO FURNISH AND INSTALL NEW DRY TYPE TRANSFORMERS TO PROVIDE 11.IN EXISTING SPACES REPLACE WATER STAINED OR DAMAGED TILES. 208V/120V POWER FROM THE 480V/277V SYSTEM. SIZE TO BE BIDDER DESIGN. 0 CO c\I 08 10 00 DOORS AND WINDOWS PROJECT CLOSE OUT DOCUMENTS REQUIRED: 12.TUNE UP GRID SYSTEM TO WITHIN PLUS OR MINUS 0.5 INCHES OF LEVEL. a. TRANSFORMERS TO BE ENERGY STAR LABELED. 0 1. RE-USE EXISTING DOORS AND FRAMES WHERE POSSIBLE 13.BENT OR DAMAGED T-BARS TO BE REPLACED. 1, PROVIDE AS-BUILT INFORMATION TO ARCHITECT AT PROJECT COMPLETION.INCLUDE THE FOLLOWING: b. CASE TO BE TOTALLY ENCLOSED WITH LOUVERS TO PREVENT FOREIGN OBJECTS INTO THE INTERIOR. w 0 N. o 2. APPROVED DOOR,FRAME,AND HARDWARE SUPPLIERS INCLUDE: a. DIMENSIONS (HORIZONTAL AND VERTICAL)OF BUIRED PLUMBING LINES INSTALLED OR DISCOVERED By u) cl 14.REPAIR HOLES IN GRID FROM REMOVED WALLS. USE OF ARMSTRONG"BP ES-4"EXPANSION SLEEVE THIS CONSTRUCTION. C. ENCLOSED AND VENTILATED,AIR COOLED TYPE,CLASS H INSULATION,DESIGNED FOR 115 DEGREES C0 " AN a. BAXTER D FLAMING. (503)225-0486 ACCEPTABLE. TEMPERATURE RISE ABOVE 40 DEGREES C AMBIENT TEMPERATURE AT FULL LOAD CONTINUOUS ii .0 D cc LOCATION OF SHUT OFF VALVES OPERATION.b. EQUIP WITH 2-1/2 PERCENT ANFC TAPS AND FOUR 2-1/2 PERCENT BNFC TAPS. MAXIMUM • b. D&D DOOR (503)205-5533 09 91 23 PAINTING0 SI 0 23 00 00 HVAC :DESIGN/BUILD SOUND LEVEL SHALL BE NEMA STANDARD WITH ISOLATION DAMPERS BETWEEN THE CORE AND COIL LL c. BENSON INDUSTRIES (503)907-2200 INTERIOR: ASSEMBLY AND CASE. 00- co w 15 GAS METER W el% C d. GRANT SUPPLY (360)887-0647 1. WALLS: 9. FOR FLOOR POWER AND DATA ACCESS IN BUILDINGS WITH ACCESS BELOW FLOOR,USE WIREMOLD RC7 o u) 0 0 I. eJ 1 CONTRACTOR TO VERIFY GAS METER AND TAG METER WITH THE TENANTS ADDRESS OR SUITE NUMBER. FLUSH POKE-THRU SERIES OR EQUAL FOR SLAB ON GRADE INSTALLATIONS USE RACO#5511,2 AT EACH 11.:4 f%•• 3. DOOR AND RELITE FRAMES SHALL BE ALPHA ALUMINUM PRODUCTS,INC.(AAP) OR APPROVED. SUBMITTAL a. PRIME NEW DRYWALL WITH MILLER'S HIGH-BUILD"SUPER SEAL"PRIMER. METER IDENTIFICATION NUMBER AND TENANT ADDRESS INFORMATION SHALL BE GIVEN TO PACTRUST PRIOR LOCATION TO SEPARATE POWER AND DATA WITH 1"CONDUIT FOR POVVER AND 2"CONDUIT FOR DATA. REQUIRED PRIOR TO ORDERING MATERIAL.NEW FRAMES TO BE FACTORY FINISH CUSTOM COLOR. b. NEW AND EXISTING DRYWALL TO BE FINISHED TO ACHIEVE UNIFORM COVERAGE WITH MILLER'S 6200 OR TO TENANTS MOVE-IN. a- 1"...) as co o 10.LOW VOLTAGE SYSTEMS(TELECOMMUNICATION AND DATA)BY FUTURE TENANT. U) or (1. 1-- Q. 4. EXTERIOR DOORS AND FRAMES TO BE HOLLOW METAL FRAMES OF ONE-PIECE WELDED CONSTRUCTION, 4480 WITH A TIGHT ROLLER STIPPLE FINISH. RESTROOM FINISHES TO BE MILLER'S S/G LATEX ENAMEL. HVAC-BID PROCEDURE 14-GA.GALV.SHEET STEEL. DOORS,SDI-100,GRADE II,SEAMLESS EDGES,16 GA.GALV.SHEET STEEL. 11.LIGHTING ENERGY MANAGEMENT IS REQUIRED IN ALL BUILDINGS. , FABRICATE DOORS AND FRAMES WITH HARDWARE REINFORCING WELDED IN PLACE. 2. DOORS AND FRAMES: I. FOR BIDDING PURPOSES,THE HVAC CONTRACTOR WILL ASSUME THAT EXISTING HVAC EQUIPMENT IS IN 12.0CCUPANCY CONTROL DEVICES SHALL BE LEVITON OR WATT STOP. ' a NEW HOLLOW METAL-PRIME,SAND,AND FINISH WITH TWO COATS OF SEMI-GLOSS OIL. PROPER WORKING ORDER. REVISION 5. FIELD VERIFY EXISTING DOOR,FRAME AND HARDWARE FINISH PRIOR TO ORDERING. ALL NEW DOORS, ' . 13 TEST ALL LIGHTING CONTROL SYSTEMS TO ENSURE THAT CONTROL DEVICES,COMPONENTS,EQUIPMENT FRAMES AND HARDVVARE TO MATCH EXISTING BUILDING STANDARDS. b. EXISTING HOLLOW METAL-SAND,FILL IMPERFECTIONS VVITH BONDO,SAND AND PRIME PATCHES VVITH 2. IWENTORY EXISTING H.V.A.C.ROOFTOP UNITS AND SUBMIT TO ARCHITECT A CONDITIONS REPORT OF EACH AND SYSTEMS ARE CALIBRATED,ADJUSTED AND OPERATE IN ACCORDANCE VVITH APPROVED PLANS AND ALKYD PRIMER,AND FINISH WITH SEMI-GLOSS OIL ENAMEL. UNIT 6. ALL INTERIOR DOORS SHALL BE SOLID CORE WOOD UNLESS NOTED OTHERWISE. SPECIFICATIONS. SEQUENCES OF OPERATION SHALL BE FUNCTIONALLY TESTED TO ENSURE THEY OPERATE 3' CEILINGS: 3. LIST TONNAGE OF EACH UNIT. IN ACCORDANCE WITH APPROVED PLANS AND SPECIFICATIONS. 1 . 7. DOOR HARDWARE SHALL BE SCHLAGE AL SATURN OR D RHODES SERIES U.N.O. a' EXISTING GYP BOARD/PLASTER-SAND,SPACKLE ALL IMPERFECTIONS,SPOT PRIME AND FINISH TO HVAC-DESIGN PROCEDURE 14.REQUIRED IN DIVISION 15,PROVIDE MONITORING OF HVAC EQUIPMENT PER CODE. 2. 8. ALL DOOR HARDWARE SHALL BE INSTALLEDWITH A 5-BACKSET. ACHIEVE UNIFORM COVERAGE WITH MILLER'S 6200 OR 4480. USE EXISTING AND/OR NEW EQUIPMENT TO DESIGN MECHANICAL H.V.A.C.SYSTEM PER DESIGN STANDARDS 15.REMOVE ALL UNUSED DATA AND POWER BOXES AND INFILL WITH GYP BOARD. EXCEPTION-UNUSED DATA 9. DOOR FINISH SUBMITTAL:CONTRACTOR TO PROVIDE SHOP DRAWINGS FOR DOOR FRAMES,DOOR b. NEW GYP BOARD!PLASTER -PRIME WITH SUPER SEAL AND FINISH TO ACHIEVE UNIFORM COVERAGE LISTED BELOW. BOXES UNDER WINDOW SILLS TO REMAIN. ALL BLANK COVER PLATES TO BE BUILDING STANDARD FINISH. 3, HARDWARE AND DOORS AS WELL AS A CONTROL SAMPLE OF THE FINISHED DOOR SKIN W/STAIN AND FINISH WITH MILLER'S 6200 OR 4480. APPLIED(IF NEW DOORS ARE BEING PROVIDED). BEFORE FINISHING OF DOORS IS COMMENCED ARCHITECT PRIOR TO AWARD OF CONSTRUCTION CONTRACT,H.V.A.C.CONTRACTOR SHALL SUBMIT TO ARCHITECT FOR 16.REMOVE ALL UNUSED LOW VOLTAGE VVIRING(TELEPHONE AND DATA)FROM THE RECEPTACLE TO THE SHALL APPROVE CONTROL SAMPLE. FINISHED PRODUCT IS SUBJECT TO REJECTION BY ARCHITECT IF THIS 4. GENERAL NOTES: REVIEW AND APPROVAL A FULL DESIGN SCHEMATIC FOR THE TENANT SPACE INCLUDING BOTH DISTRIBUTION BOARD.LEAVE PULL STRINGS FROM THE BOX TO THE SPACE ABOVE THE CEILING. A SECTION 4. PROCESS IS NOT FULLY ADHERED TO AND FIELD PRODUCT DOES NOT MATCH THE APPROVED CONTROL a. KEEP ALL HARDWARE,HINGES,AND DOOR KNOBS CLEAN OF ALL PAINT SPLATTERS,DRIPS,OR ROLLER NEW/RENOVATED WORK AND SYSTEMS UNTOUCHED BY THE TENANT IMPROVEMENT AS APPLICABLE. • OF THE EXISITNG LOW VOLTAGE WIRE MAY BE LEFT IN LIEU OF A PULL STRING SAMPLE. INCLUDE THE FOLLOWING: SPRAY. OFFICE LIGHTING 5. 10.ALL INTERIOR GLAZING SHALL BE TEMPERED, a b. ALL SURFACES TO BE SANDED BETWEEN COATS,PRIOR TO INSTALLATION OF NEXT COAT. ' DUCTING AND SIZES 1. GROUP RE-LAMP EXISTING FLUORESCENT LIGHTS THROUGHOUT U.N.O. 6. ii.DEAD BOLT LOCKS AT NEW EXTERIOR DOORS TO BE INSTALLED WITH A SCHLAGE MORTISE DOUBLE c. DURING PROGRESS OF WORK,KEEP JOB SITE CLEAN OF ALL PAINT MATERIALS,RUBBISH,CANS,AND b. SUPPLY AND RETURN LOCATIONS AND CFM AT EACH GRILL OR DIFUSER 2. OFFICE LIGHT FIXTURES-LITHONIA 2PM3N G B 332 18LD MVOLT ADVANCE OR EQUAL.(NO SYLVANIA CYLINDER 20-013C "C'KEYWAY;SOLID BRASS;VVITH ADAMS-RITE CAM AND COMPRESSION RING 1 1/8"LENGTH RAGS AT THE END OF EACH DAY. c. ROOF EQUIPMENT,SIZES AND LOCATIONS BALLASTS)-MATCH EXISTING 7. WITH HARDENED CYLINDER GUARD RING KEEDEX K-24. FINISH TO MATCH BUILDING STANDARD. d. UPON COMPLETION OF WORK,CLEAN ANY PAINT SPLATTER BY USING PROPER METHODS OF WASHING d. UNITS REQUIRING DUCTED SMOKE DETECTION 3. REST ROOM-WALL MOUNTED LIGHT FIXTURE - LITHONIA WC 232 MVOLT GEB10IS OR EQUAL(RELOCATE) 12.PATCH AND REPAIR ALL HOLES OR DAMAGE TO EXISTING STORE FRONT WINDOWS AND DOORS.TOUCH UP • AND SCRAPING,USING CARE NOT TO SCRATCH OR DAMAGE FINISHED SURFACES. • 8. • FINISH FOR AS NEW LOOK. e. THERMOSTAT LOCATIONS AND ZONE/UNIT ASSOCIATED THEREWITH 4. RECESSED LED DOWN LIGHT: LITHONIA LDN6 35/10 LOB AR LD 277 TRW e PROTECT WORK OF OTHER TRADES. 13.TOUCH UP ALL EXISTING INTERIOR DOORS AND FRAMES FOR AS NEW LOOK. ' f. ANY SUPPLEMENTAL EXHAUST FANS OR SPECIAL SYSTEMS 5. PENDANT LIGHT FIXTURES AT BREAK BAR-TO BE SELECTED BY TENANT. f PROVIDE"WET PAINT"SIGNS AS REQUIRED TO PROTECT NEWLY PAINTED FINISHES. 14.GLAZED OVERHEAD DOORS;WAYNE DALTON K-AL,CLASS I DARK BROWN ANODIZED ALUMINUM 6063-16(TO ' g. ZONE DIAGRAM 6. SCONCE LIGHTING-RELOCATE EXISTING. MATCH EXISTING STOREFRONT);HIGH-LIFTOPERATING STYLE(MATCH EXISTING)WITH TRACK AND 10 00 00 SPECIALTIES HVAC DESIGN STANDARDS WAREHOUSE LIGHTING(EXISTING TO REMAIN) DRAWN BY: HARDWARE OF HOT-DIP GALVANIZED STEEL.OPERATION;CHAIN HOIST. mwh 10 28 13 REST ROOM ACCESSORIES(MULTI OCCUPANCY) THE FOLLOWING ARE MINIMUM DESIGN STANDARDS: 1. LITHONIA FOUR LAMP,IB-454L MVOLT ADVANCE,54W,T5H0 FLUORESCENT 277V.LIGHT LEVEL 10 TO 15 FC AT 15.TUNE UP EXISTING OVERHEAD DOORS FOR SMOOTH OPERATION. WORK INCLUDES: 30"A.F.F. (EMERGENCY BATTERY PACK OPTION EL14) 1. REUSE EXISTING ACCESSORIES WHERE POSSIBLE. 1. 350 SQUARE FOOT PER TON(UNLESS OTHERWISE APPROVED IN WRITING BY PACTRUST). a. ADJUST OVERHEAD SPRING TENSION TO MEET MANUFACTURER'S SPECIFICATIONS. EXTERIOR LIGHTING DATE: 05/11/16 2. PAPER TOWEL DISPENSER AND WASTE SEMI RECESSED(ONE PER REST ROOM)BOBRICK B-3944 2. ADDRESS LOADS BY SPECIFIC LOCATION AND USE,AS WELL AS CRITERIA PROVIDED TO PACTRUST BY b. REPLACE TOP AND BOTTOM DOOR SEALS AS NEEDED. TENANT PRIOR TO CONSTRUCTION: 1. ENTRY LIGHTING AT RECESSED OPENINGS: LITHONIA LF6N,26DTT LAMP,F6OSA RELFECTOR.(EMERGENCY 3. TOILET PARTITIONS:POVVDER COATED STEEL,FLOOR ANCHORED VVITH CONTINUOUS BRACKETS,FULL PERMIT/BID SET C. REPLACE BENT TRACKS AND PANEL SECTIONS. CANTILEVER ONLY. NO CEILING ATTACHMENT OR HEAD RAIL OVER DOORS.ACCURATE OR APPROVED. a. EXTERIOR EXPOSURE AREAS BATTERY PACK OPTION EL) d. REPLACE ROLLERS AND HINGES AS NEEDED. INSTALL USING FACTORY PROVIDE SCREWS ONLY. PROVIDE BACKING IN WALL TO SUPPORT WALL 2. LITHONIA LIGHTING WST LED 1 10A700/40K SR4 MVOLT ELCW DDBXD.EXTERIOR EGRESS LIGHTING. BRACKETS. b. INTERIOR AREAS,SIZE AND USE e. REPLACE ROPES AS NEEDED. 32 00 00 EXTERIOR IMPROVEMENTS 4. LAVATORY MOUNTED SOAP DISPENSER 34 FL OZ.,6"SPOUT LENGTH BOBRICK 6-8226(ONE AT EACH SINK) c. CONFERENCE/TRAINING ROOMS f. LUBRICATE ROLLERS. PRIOR TO ANY EXTERIOR EXCAVATION OR BORING,GENERAL CONTRACTOR SHALL OBTAIN AN UNDERGROUND 5. TOILET SEAT COVER DISPENSER,SANITARY NAPKIN DISPOSAL AND TOILET TISSUE DISPENSER BOBRICK B-357 d. COMPUTER/SERVER AND TELEPHONE ROOMS TO HAVE PROVISION FOR LOW AMBIENT OPERATION LOCATE. 09 00 00 FINISHES WOMEN'S (MOUNTS IN PARTITION) • AND 24-HOUR USE.VERIFY NEED FOR A SEPARATE SPLIT SYSTEM TO MAINTAIN TEMPERATURE. UTILITY 32 01 11 RUBBER AND PAINT REMOVAL FROM PAVING GENERAL 6. TOILET SEAT COVER DISPENSER,SANITARY NAPKIN DISPOSAL AND TOILET TISSUE DISPENSER BOBRICK 3. SYSTEM DESIGN CRITERIA-SIZE ZONES FOR 3-5 TON UNITS BASED ON USE&EXPOSURE CRITERIA. . 1. CLEAN,SEAL AND WAX ALL RESILIENT FLOORS PER MANUFACTURERS SPECIFICATIONS. B-3574 VVOMEN'S (MOUNTS SIDE WALL OF SINGLE COMPARTMENT) PACKAGED OR SPLIT SYSTEM EQUIPMENT GREATER THAN 5 TONS SHALL BE SPLIT INTO MULTIPLE ZONES. 1. USE SAND BLASTING TO REMOVE UNWANTED PAINTED LINES AND STENCILS FROM PAVING AS INDICATED ON A2 VAV OR WATER SOURCE HEAT PUMP SYSTEMS GREATER THAN 3 TONS SHALL BE SPLIT INTO MULTIPLE THE SITE PLAN. BLACK PAINT OVER EXISTING PAINT IS STRICTLY PROHIBITED. 2. SUBMIT SAMPLES OR DRAW DOWNS FOR THE FOLLOWING: 7. TOILET SEAT COVER DISPENSER AND TOILET TISSUE DISPENSER BOBRICK B-347 MEN'S (MOUNTS IN ZONES,PARTITION) 32 17 23 PAVEMENT MARKINGS a. FLOOR COVERINGS,BASE AND TRANSITION STRIPS 4* ALL ENCLOSED ROOMS OR OFFICES TO HAVE DUCTED SUPPLY&RETURN GRILLES. 8. TOILET SEAT COVER DISPENSER AND TOILET TISSUE DISPENSER BOBRICK B-3474 MEN'S (MOUNTS SIDE • 1. PAINTED HANDICAP STALL SIGN:CONTRACTOR TO USE LANDLORD SUPPLIED STANDARD HANDICAPPED : b. PLASTIC LAMINATES WALL OF SINGLE COMPARTMENT) 5. VACANT SPACE SHALL HAVE DEDICATED GAS SERVICE FOR FUTURE BUILD-OUT OR FREEZE PROTECTION. • STENCIL.DO NOT APPLY OPTIONAL ADA BLUE BACKGROUND. c. ALL NATURAL WOOD(INCLUDING DOORS AND CASEWORK) 9. MIRROR STANDARD SIZES 1/4"PLATE MIRROR WITH EDGES"FLAT GROUND*BOTTOM EDGE SUPPORTED BY A 6. UNITS: LENNOX,TRANE,YORK OR CARRIER-7 1/2-TON MAXIMUM UNIT SIZE. ANY UNIT IN EXCESS OF 7 1/2 Ammorxen‘ Aummumm. . _ _ _ _