Loading...
Plans (4) M EC2017 - 00628 ° P °1N ; "A ��17.e/'E• , $-f7-fl GENERAL NOTES OREGON t� AUG 21 �Asztcb`� 19 9 0 1. THE AS-BUILT DRAWINGS USED TO CREATE THESE DRAWINGS MAY 21717 NOT REFLECT EXACT ROUTING OR SIZES OF EXISTING DUCTWORK. CiTY OF TIGARD 6 -30 EXPIRES.: q U MECHANICAL CONTRACTOR SHALL VERIFY ALL CONNECTION BUILDING pi�/IS(ON NEW DUCTLESS SPLIT SYSTEM SCHEDULEREQUIREMENTS IN FIELD PRIOR TO START OF WORK AND MAKE ,\ ADJUSTMENTS TO DESIGN AS REQUIRED. ALL WORK SHALL BE DONE PER STATE & LOCAL JURISDICTIONAL REQUIREMENTS. \ , RATED ELECTRICAL OUTDOOR KROGER GO SERVES TYPE � INDOOR OUTDOOR NOMINAL CFM COOLING SEER HSPF UNIT MANUFACTURER & MODEL REMARKS \ �� On UNIT TAG UNiT TAG TONS ePRO K-# CAPC[TY V/HZ/PH MCA MOCP WEIGHT I� I i _._ - _ `\ C, KEY NOTES HIGH EFFICIENCY, .i F_ \ mt DEC DCU MITSUBISHI; HEAT PUMP SYSTEM KIT. \ - N CUCKUST COLING-MOUNT INDOOR 2.0 640 24,000 BTUH 208/60/1 18/1 30 14 N/A 163 lbs. K-0052787 (i)(2) 1 1 IXISIING MECHANICAL EQUIPMENT AND DUCTWORK TO REMAIN. I 0 0 COOLING ONLY MODEL PLA-MUYA24NHA6-KR. ` T I I \ O _ - �. 7 0 ' N� \ O RELOCATE EXISTING RETURN GRILLE AS SHOWN. MODIFY DUCTWORK AS REQUIRED FOR NEW r .. O DEC DCU HIGH EFFICIENCY, MITSUBISHI; HEAT PUMP SYSTEM KIT. U LOCATION. 4 0) CUCKUST CEIUNG-MOUNT INDOOR 2.0 640 24,000 BTUH 208/60/1 18/1 30 14 N/A 163 lbs. MODEL PLA-MUYA24NHA6-KR. K-0052787 (1)(2) "xF.,,, >, a) W © COOLING ONLY , �_ _� l/0 ,� \~IF O EMS CONTROLS CONTRACTOR SHALL PROVIDE NEW ADD(RONAL TEMPERATURE SENSOR AS • fl 0 V 7 �/ SHOWN. THE NEW AND EXISTING TEMPERATURE SENSORS SHALL CONTROL RTF-1 IN A • c O, e 1) KIT SHALL BE OWNER-PROVIDED AND INCLUDE INDOOR AND OUTDOOR UNITS, WIRELESS THERMOSTAT, CONDENSATE PUMP, REMOTE LOCKDOWN BRACKET AND - Jit y .��-_,j_ 1/ _ I TEMPERATURE AVERAGING FASHION. , Ct C •cp S REFRIGERANT UNE SET. MECHANICAL CONTRACTOR SHALL PROVIDE ALL ADDITIONAL EQUIPMENT AND ACCESSORIES REQUIRED FOR INSTALLATION PER DETAIL HSD-110 F �, \ N cu ON THIS SHEET. ALL EQUIPMENT SHALL BE INSTALLED BY MECHANICAL CONTRACTOR. PROVIDE SYSTEM WiT1 R-410A REFRIGERANT. RED-VERIFY REQUIREMENTS EXISTING NEWT�.�1 - \ NEW I 0r O BALANCE SUPPLY AIR FOR RTF-1 AFTER DUCTWORK MODIFICATIONS HAVE BEEN COMPLETE. ' Ir-I�/ p PRIOR TO BID. I 11 RTF DFC \ ,' DCU \ /h. AIR BALANCE REPORT SHALL BE PROVIDED BY GC. PROVIDE AIR BALANCE REPORT TO • I I D_ O m 2) THERMOSTAT: PROVIDE WiTH WALL MOUNTED, WIRELESS 7-DAY PROGRAMMABLE, NIGHT SET-BACK CONTROLLER MHK1. LOCATE CONTROLLER AS SHOWN ON PLAN AT Oldp ^ 0 < \ ., 0 \/F,% D ARCHITECT FOR REVIEW BY MECHANICAL ENGINEER. PROVIDE 190 CFM OA r In 4, _ �. 48" A.F.F. I 1000 CFM ® ' I © \ �� / I O5 REFRIGERATION PIPING, SIZED PER MANUFACTURER'S REQUIREMENTS, UP TO DCU ON ROOF. ) c �illllllllll� .: SEE DETAIL HSD-11 ON THIS SHEET. - u x Cl) o II I / I ( \ \ O LOCATE WIRELESS T-STAT CONTROLLER FOR DFC 1, AND OFC-2 AT 4°-O" A.F.F. of __ \\ O NEW 10"X10" OUTDOOR AIR (OA) INTAKE HOOD WITH ADJUSTABLE BACKDRAFT DAMPER AND = •Z limil ( - N'! i \ //D. BUG SCREEN. ADJUST DAMPER TO PROVIDE 190 CFM OF O.A. WHILE UNIT IS IN OPERATION.7 �! L( j -ver J_ V i / ` DAMPER SHALL CLOSE WHEN UNIT IS IDLE. • T I • \ 2. Cooling equipment economizers:The total capacity of all cooling equipment without economizers must be less than 240 kBtu/h.This \ �Ly / < ® project lists 48 kBtu/h capacity without economizers.That portion of the equipment serving dwelling units and guest rooms is not -1 9" N. 01 D��CFT�1" t -� 1 Q01] 4FM8 CDO 1- Included in determining the total capacity of units without economizers. ,-_ _ 4�u COMcheck Software Version 4.0.6.2 m ( .- of ) - �-� El L Plans reference page/section: " CV ( � ® f)I�Tf`-�1 '-- Mechanical Co m p llance Certificate o 3. Equipment and system sizing.Heating and cooling equipment and systems capacity do not exceed the loads calculated in accordance (E 22"i0 Mill- ` RE 8 with Section 503.2.E ( I t Exception(s): t ✓' - NEW ! UC UST ANEW 1 ❑ Required standby equipment and systems provided with controls and devices that allow such systems or equipment to operate DTIC 1� DCU automatically only when the primary equipment Is not operating. _ PHARMACY 11E.--- It -- +I © -I I - laid , Section 1: Project Information ❑ Multiple units of the same equipment type with combined capacities exceeding the design bad and provided with controls that Q p = have the capability to sequence the operation of each unit based on load. - J jam'�!E'e�'• Energy Code:2014 Oregon Energy Efficiency Specialty Code - _ Project Title:FM 375 Tigard Clicklist Plans reference page/section: _ • i�_!\ I = i I Project Type:New Construction 1 a ❑ 4. HVAC Equipment Performance Requirements.Reported efficiencies have been tested and rated in accordance with the applicable test - �, (E)2 0 ® (E)20"0 IDISq � 114"0 ® I Construction Site: Owner/Agent: Designer/Contractor. procedure.The efficiency has been verged through certification under an approved certification program or,if no certification program 0 -!I=!-I-4_..-J _J__I.1_1_� _l �i r�j'M Q _2 (;,� 11565 SW Pacific Hwy Fred Meyer Engineering Consultants,Inc. exists,the equipment efficiency ratings are supported by data fumished by the manufacturer. _______,J )1 ,_i. 1 --,'>��� --- r I ti ` J LIJ �.. Tigard,OR 97223 303 S Federal Way 0 5. Thermostatic Controls.The supply of heating and cooling energy to each zone is controlled by individual thermostatic controls that T li 1111 H ^ 3oise,ID 83705 respond to temperature within the zone. 750 CFMF10"CDl�1J. IJ Q 208-376-9820 750 ■ i 0 CoPlans reference page/section: Ml . 1 [ WP OF 4) vJ O 2 Section 2: General Information ❑ 6. Heat pump supplementary heat.Heat pumps having supplementary electric resistance heat have controls that,except during defrost, ❑ 0 ` --'s yrnil rc �I `IIN 5 f n co prevent supplementary heat operation when the heat pump can meet the heating load. ,1\ ` V_ Building Location(for weather data): Tigard,Oregon '-� NMY = N Plans reference page/section: �( 1( (rte W Climate Zone: 4c CO } 1 1 Et N. O 7. Set point overlap restriction.Where used to control both heating and cooling.zone thermostatic controls provide a temperature range L� --- ^ 0LL. _0 a) Section 3: Mechanical Systems List or deadband of at least 5°F(2.8°C)within which the supply of heating and cooling energy to the zone is capable of being shut off or =1Q reduced to a minimum. �/ O Exception(s): t , Quantity System Type&Descriptionl.J LI Thermostats requiring manual change over between heating and cooling modes. V f-,, O 0 Q Q 2 DFC/DCU-1,2(Single Zone): /n a Q Cooling:2 each-Split System,Capacity=24 ketu/h,Air-Cooled Condenser,Unknown Economizer Plans reference page/section: M1 1 `.J Proposed Efficiency=14.00 SEER,Required Efficiency: 13.00 SEER r:Fan System: Unspecified o 8. Optimum Start Controls.Each HVAC system has controls that vary the start-up time of the system to just meet the temperature set �l (' point at time of occupancy. O 1^ >r ) I- Section 4: Requirements Checklist Plans reference page/section: Ml . 1 /*) rte. (I I ii Ul� � o 9. Off-hour controls.Each zone is provided with thermostatic setback controls that are controlled by either an automatic time clock or - '-✓ -� CO CO In the following requirements,blank checkboxes identify requirements that the applicant has not acknowledged as being met.Checkmarks programmable control system. km saa LO identify requirements that the applicant acknowledges am met or excepted from compliance. 'Plans reference pagelsection'identifies where In Exception(s): the p/ens/specs the requirement can be verified as being satisfied. ❑ Zones that will be operated continuously. 116 , Requirements Specific To: DFC/DCU -1,2 : ❑ Zones with a full HVAC load demand not exceeding 6,800 Btu/h(2 kW)and having a readily accessible manual shutoff switch. IL 2( 1. Equipment meets minimum efficiency: Split System: 13.00 SEER Ml . 1 .\-,..... l o 2. Energy recovery ventilation systems.Individual fan systems that have both a design supply air capacity of 5,000 cfm or greater and a Plans reference page/section: I minimum outside air supply of 70 percent or greater of the design supply air quantity have an energy recovery system. [a 10.Shutoff damper controls.Both outdoor air supply and exhaust are equipped with not less than Class I motorized dampers. (�I{I tl Exception(s): Exception(s): I I r I �lU.ly ❑ Where energy recovery systems are prohibited by the International Mechanical Code. ® Gravity dampers shall be permitted for outside air intake or exhaust airflows of 300 cfm or less. ❑ Systems serving spaces that are not cooled and are heated to less than 60°F. ' � ❑ Where more than 60 percent of the outdoor heating energy is provided from site-recovered or site solar energy. Plans reference page/sect on: Ml . 1 MECHANICAL PLAN I-_\ N ❑ Type 1 kitchen exhaust hoods. ❑ 11.Freeze Protection and Snow melt system controls.Freeze protection systems,such as heat tracing of outdoor piping and heat ❑ Cooling systems in climates with a 1-percent cooling design wet-bulb temperature less than 64°F(18°C). exchangers,including self-regulating heat tracing,include automatic controls capable of shutting off the systems when outdoor air ,__, Systems requiring dehumidification that employ series-style energyrecoverycols wrapped around the coolingcoil when the temperatures meet code criteria. SCALE: 1/8"=1'_." ``_J ❑ Y q 9 P Y ty PPe - -evaporative coil is located upstream of the exhaust air stream. Plans reference page/section: ❑ Systems exhausting toxic,flammable,paint exhaust,corrosive fumes,or dust. v, N el ❑ 12.Separate air distribution systems.Zones with special process temperature requirements and/or humidity requirements are served by o ry ❑ Laboratory fume hood systems that include qualifying features. separate air distribution systems from those serving zones requiring only comfort conditions;or shall include supplementary control } m O provisions so that the primary systems may be specifically controlled for comfort purposes only. r a 't. B o .6 Plans refen erence page/section: Exception(s): e• U [503.2.4.8+I Zones requiring only comfort heating or comfort cooling that are served by a system primarily used for process4(. y " G 8 Generic Requirements: Must be met by all systems to which the requirement is applicable: temperature and humidity control. e a 1. Calculation of heating and cooling loads.Design loads are determined in accordance with the procedures described in the c m K v ASHRAE/ACCA Standard 183.Alternatively,design loads have been determined by an approved equivalent computation procedure. Plans reference page/section: I p .;i 3 9 -, e o ii o rn ` U m1 P 3 � 33 Project Title: FM 375 Tigard Clicklist Report date: 08/17/17 Project Title: FM 375 Tigard Clicklist Report date:08117117 4 N Data filename:P:\98T10-FM#375 Tigard,OR-Clicklist\Docs\Energy Codes\98T10#375 Tigard Mechanical ComCheck.cck Page 1 of 5 Data filename:P:\98T10-FM#375 Tigard,OR-Clicklist\DocslEnergy Codes\98T10#375 Tigard Mechanical ComCheck.cck Page 2 of 5Nee w $ 12 M O enae ❑ 13.Humidity control.Where a humidity control device exists it is set to prevent the use of fossil fuel or electricity to produce relative o 23.Manuals.The construction documents require that an operating and maintenance manual be provided to the building owner by the ❑ HVAC record drawings of the actual Installation,system capacities,calibration information,and performance data for each equipment humidity in excess of 30 percent.Where a humidity control device is used for dehumidification,it Is set to prevent the use of fossil fuel mechanical contractor.See long description for specifications. provided to the owner. spur SYSTEM OUTDOOR UNr. REUSE OF DOCUMENTS or electricity to reduce relative humidity below 60 percent. HVAC OSM documents for all mechanical equipment and system provided to the owner by the mechanical contractor. WEATHERPROOF DISCONNECT SWITCH Exception(s): Plans reference page/section: Al , 1 ❑ Written HVAC balancing and operations report provided to the owner. ❑ Hospitals,process needs,archives,museums,critical equipment,and other non-comfort situations with specific humidity 24.Air System Design and Control.Each HVAC system havinga total fan system motor nameplate hpexceeding5 hpmeets theprovisions ❑ DCU This document, and the ideas uY 9 Y Y P �1 requirements outside this range. of Sections 503.2.10.1 through 503.2.10.2. The above post construction requirements have been completed. 12:2! SELLTNaIT ELECTRICAL OUI FEED OUT 0 j �`` OF oscANNEcr%riot um and designs incorporated, as Plans reference page/section: Plans reference page/section: IIII/ri��it 11�� CONNECTED 1D OUFD00R UNIT. an instrument of professional j 14.Humidity control.Where a humidity control device exists it is set to maintain a deadband of at least 10%relative humidity where no ❑ 25.Allowable fan floor horsepower.Each HVAC system at fan system design conditions does not exceed the allowable fan system motor Principal Mechanical Designer-Name Signature Date ``,�`�Oy��Ill T ifrAC service is the property of active humidification or dehumidification takes place. nameplate hp(Option 1)or fan system bhp(Option 2)as shown and calulated in requirement details. �� e SYSTFL Western Construction Exception(s): Exception(s): `� UNESEIS OUT r Services, Inc. a Corp. of WA SEALDCHT Heating for dehumidification Is provided with heat recovery or heat pumping and the mechanical cooling system efficiency is 10 ELAND CON F® OF ON RATFORM�- ° ~' ❑ 9 P ry P P 9 9 Y cY ❑ Hospital and laboratory systems that utilize Dow control devices on exhaust and/or return to maintain space pressure relationships AND rptlNECIED Tp p pNREpR S+NppH ) CCURB ONNECTED and is not to be used, In percent higher than required In section 503.2.3.HVAC equipment performance requirements. necessary for occupant health and safety or environmental control shall be permitted to use variable volume fan power limitation. nn f1 0 < OUTDOOR UM'. whole or in part,for any Plans reference page/section: ❑ Individual exhaust fans with motor nameplate horsepower of 1 hp or less. I 1 SFALTIGM ELECTRICAL reason without the written Plans reference page/section: ( I Roy-FEED FROM N °UTDOOR IRU authorization of Western • 15.Ventilation.Ventilation,either natural or mechanical,h provided In accordance with Chapter 4 of the International Mechanical Code. P 9 r. A v v UNIT DOWN 11iR11 Where mechanical ventilation is provided,the system has the capability to reduce the outdoor air supplyto the minimum required by INDOOR AND Construction Services, Inc. a y P ty ❑ 26.Motor nameplate horsepower.For each fan,the selected fan motor is no larger than the first available motor size greater than the brake ROOF DECO ( TO UNIT,THRu Chapter 4 of the International Mechanical Code. PLATFORM CURB, DISCONNECTS ITCH. Corp of WA. horsepower(bhp). SEE ASO-89 LEGAL AIR GAP Plans reference page/section: Ml . 1 Exception(s): I� ❑ For fans less than 6 bhp,where the first available motor larger than the brake horsepower has a nameplate rating within 50 ❑ 16.Demand controlled ventilation(DCV).DCV is required for spaces larger than 500 ft2 for simple systems and spaces larger than 150 ft2 percent of the bhp,selection of the next larger nameplate motor size is allowed. 1 /- \ n /� /� 1-1 f A / 1 ! l f A / ° % n !1 !� / DATE ISSUE for multiple zone systems. ❑ For fans 6 bhp and larger,where the first available motor larger than the bhp has a nameplate rating within 30 percent of the bhp, •\ % 0817.17 submittal Exception(s): selection of the next larger nameplate motor size is allowed. ' �, ❑ Systems with energy recovery complying with Section 503.2.6 ❑ Spaces less than 750 ft2(69.7 m2)where an occupancy sensor turns the fan of,closes the ventilation damper,or closes the Plans reference page/section: v'•- zone damper when the space is unoccupied. \\./ ROOF ❑ 27.Large Volume Fan Systems.Fan systems over 8,000(7 m3/s)cfm without direct expansion cooling coils that serve single zones reduce JOIST .'•• Plans reference page/section: airflow based on space thermostat heating and cooling demand.A two-speed motor or variable frequency drive reduces airflow to a maximum 60 percent of peak airflow or minimum ventilation air requirement as required by Chapter 4 of the International Mechanical ❑ 17.Kitchen hoods.Kitchen makeup is provided as required by the Oregon Mechanical Specialty Code. Code,whichever is greater. 1/2°CONDENSATE UNE UP • Exception(s): Exception(s): SEALOGHT ELECTRIC./FEED FROM ELECTRIC SOUCRE UP THRU THROUGHR CURB. DISCHARGE . . ❑ Where hoods are used to exhaust ventilation air that would otherwise be exhausted by other fan systems. ❑ Systems where the function of the supply air is for purposes other than temperature control,such as maintaining specific humidity ROOF DEED PLATFORM CURB,OUT CURB NO CONFECT TO sumac ELECTRICAL FEED FROM 0, ONTO ROOF. CITY OF TIGARD ❑ Kitchen exhaust systems that include exhaust air energy recovery complying with section 503.2.6. levels or supplying an exhaust system. DISCONNECT SWITCH PER CODE ANDOUTDOOR U EDDO iHRU CURB TO r Plans referencepage/section: / 'N CONDENSATE PUMP. HVAC SPLIT SYSTEM UNFSETS REVIEWED FOR CODF�'OMPTSANCE Plans reference page/section: UP THRU ROOF INTO PLATFORM PRINCE CONDENSATE NIP ❑ 18.Enclosed parking garage ventilation controls.In Group S-2,enclosed parking garages used for storing or handling automobiles employs ❑ 28.AII air-conditioning equipment and air-handling units with direct expansion cooling and a cooling capacity at ARI conditions greater than CONDENSATE AND ASSOCIATED CONTEMNS CURB. Approved; I 1 automatic carbon monoxide sensing devices. or equal to 110,000 Btu/h that serve single zones have their supply fan operation controlled according to code specific requirements. MOSE7 AS REaDRED OTC: (t1 C.\O&_U \1 11•S It CA- Exception(s): T Exception(s): Plans reference page/section: ❑ Systems where the function of the supply air is for purposes other than temperature control,such as maintaining specific humidity I Permit#: �Si t411P. -sir 19.Duct and plenum insulation and sealing.All supply and return air ducts andplenums are insulated with the specified insulation.When levels or supplying an exhaust system. CONDENSATE PUMP - ppYPecl CONDENSATE PUMP WHEN REQUIRED DFC DISCONNECT SWITCH�� Address. ' r��` located within a building envelope assembly,the duct or plenum is separated from the building exterior or unconditioned or exempt SENSOR COMMUNICATION Plans reference page/section: UNE CONDENSATE HOSE I Suite#: - spaces by a minimum of R-8 insulation.All ducts,air handlers and filter boxes are sealed.Joints and seams comply with Section 603.9 J v 2E of the International Mechanical Code. ❑ 29.Series fan-powered terminal unit fan motors.Fan motors for series fan-powered terminal units are electronically-commutated motors - SPLIT SYSTEM INOCOR UNIT By: mammatillir Date: Exception(s): and have a minimum motor efficiency of 70 percent when rated in accordance with NEMA Standard MG 1-2006 at full load rating ❑ When located within equipment. conditions. ❑ When the design temperature difference between the Interior and exterior of the duct or plenum does not exceed 15°F(8°C). Plans reference page/section: PM- ❑ 20.Low-pressure duct systems.All longitudinal and transversejoints,seams and connections of low-pressure supply and retum ducts are 30.Hot Gas Bypass Limitation.For coolingsystems a 240 kBtu/h,maximum hotgas bypass capacity is no more than 50%total coolingD ) `\ OFFICE COPY P Y 9 PP Y ❑ YP Ys YP P cdY `CONDENSATE PAN securely fastened and sealed with welds,gaskets,mastics(adhesives),mastic-plus-embedded-fabric systems or tapes installed in capacity. CONOFNS TE DAME LINE N--r accordance with the manufacturers Installation instructions. ACCOROWCE MDI NDENSATE SENSOR ASSEMBLY Exception(s): Plans reference page/section: ...._ - MWIF/CNRER' / (FIELD INSTALL) INSTRUCTIONS ❑ Continuously welded and locking-type longitudinal joints and seams on ducts operating at static pressures less than 2 inches w.g. FMONAL CONOEN6ATE DRAIN pressure classification. Section 5: Compliance Statement NOTES: ROUTING TO NEAREST RECEPTACLE. Plans reference page/section: Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,specifications 1. PLATFORM ARB, SPLIT SYSTEM UNITS & UNESETS ARE DIRECT BUY ITEMS, KROGER SUPPLIED AND CONTRACTOR INSTALLED. ca21.Medium-pressure duct systems.All ducts and plenums designed to operate medium-pressure are insulated and sealed in accordance REFER TO AS13-89 FOR PLATFORM CURB INSTALLATION AND ADDITIONAL INFORMATION. DRAWN BY: TRB with Section 503.2.7.Pressure classifications specific to the duct system are clearly indicated on the construction documents. and other calculations submitted with this permit application.The proposed mechanical systems have been designed to meet the 2014 CHECKED BY: CLM Oregon Energy Efficiency Specialty Code requirements in COMcheck Version 4.0.6.2 and to comply with the mandatory requirements In the 2. INFORMATION.SYSTEM'S MANUFACTURERS AND MODELS VARY, REFERENCE MANUFACTURER'S INSTALLATION GUIDE FOR ADDITIONAL Plans reference page/section: Requirements Checklist. ❑ 22.High-pressure dud systems.Ducts designed to operate at high-pressure are Insulated and sealed In accordance with Section 503.2.7. Tim Jas z kowia k, P.E. S-f i HVAC SPLIT SYSTEM SCALE:DATE: 4/15/11 In addition,ducts and plenums are leak-tested In accordance with the SMACNA HVAC Air Duct Leakage Test Manual. JOB # : 17-EMI-1006-11 Name-Title Signatu Date DRAWN: JO Plans reference page/section: DIAGRAM Section 6: Post Construction Compliance Statement KROGER GO MASTER SPECIFICATION DETAJL HSD- 11 SCALE: AS NOTED SHEET NUMBER Project Title: FM 375 Tigard Clicklist Report date:08/17/17 Project Title: FM 375 Tigard Clicktist Report date: 08/17/17 Project Title: FM 375 Tigard Clicklist Report date:08/17/17 Data filename:P:198T1 O-FM#375 Tigard,OR-CDcklist1Docs1Energy Codes\98T10#375 TEga•d Mechanical ComCheck.cck Page 3 of 5 Data filename:P:198T1 O-FM#375 Tigard,OR-ClickllstlDocslEnergy Codes\98T10#375 Tigard Mechanical ComCheck.cck Page 4 of 5 Data filename:P:\98T10-FM#375 Tigard,OR-ClicklisODocslEnergy Codes\98T10#375 Tigard Mechanical ComCheck.cck Page 5 of 5 M 1 ■ 1