Loading...
Report Page 2 of 6 TFP176 SPRINKLER FINISH(See Note 11) K TYPE TEMP. BULB NATURAL CHROME WHITE*** LEAD LIQUID BRASS PLATED POLYESTER COATED 135°F/57°C Orange HORIZ. 155T/68°C Red SIDEWALL 1,2,3,4,9, 10 1,2,3,9 1,2,3,9 (TY3331) 175°F/79°C Yellow 200°F/93°C Green 5.6 286°F/141°C Blue 1/2" , .,,.---- NPT RECESSED 135°F/57°C Orange HORIZ. 155°F/68°C Red SIDEWALL 1,2,4,9, 10 1,2,9 N/A (TY3331)* 175°F/79°C Yellow Figure 3 200T/93°C Green RECESSED 135°F/57°C Orange " HORIZ. 155°F/68°C Red SIDEWALL 1,2,3,4,9 N/A (TY3331)** 175°F/79°C Yellow Figure 4 200°F/93°C Green VERTICAL 135°F/57°C Orange SIDEWALL 155°F/68°C Red 5.6 (TY3431) 5,6,7,8,9 5,6,7,9 1/2" Installed 175T/79°C Yellow NPT Pendent 200T/93°C Green • or Upright 286°F/141°C Blue NOTES: 1.Listed by Underwriters Laboratories, Inc. (UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector to ceiling distance. 2.Listed by Underwriters Laboratories Inc.for use in Canada(C-UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector to ceiling distance. 3.Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers for use in Light Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector to ceiling distance. 4.Approved by the Loss Prevention Certification Board(LPCB Ref. No.007a/04)at a 4 to 6 inch (100 to 150 mm)top of deflector to ceiling distance.The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 5.Listed by Underwriters Laboratories, Inc.as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. 6.Listed by Underwriters Laboratories for use in Canada(C-UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. 7.Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers for use in Light Hazard Occupancies. 8.Approved by the Loss Prevention Certification Board(LPCB Ref. No. 094a/06&007a104)as Quick Response Sprinklers. 9.Approved by the City of New York under MEA 354-01-E. 10.Approved by the Loss Prevention Certification Board(LPCB Ref. No. 094a/06)at a 4 to 6 inch(100 to 150 mm)top of deflector to ceiling distance.The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 11.Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers.Where Lead Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as Corrosion Resistant Sprinklers. * Installed with Style 10(1/2"NPT)3/4"Total Adjustment Recessed Escutcheon. **Installed with Style 20(1/2"NPT) 1/2"Total Adjustment Recessed Escutcheon. ***Frame and deflector only. Listings and approvals apply to color(Special Order). TABLE A LABORATORY LISTINGS AND APPROVALS Physical Characteristics CES Frame Bronze 0 p e ratio n Button Brass/Copper Sealing Assembly The glass Bulb contains a fluid which Beryllium Nickel w/Teflont expands when exposed to heat.When Bulb Glass the rated temperature is reached, the Compression Screw Bronze fluid expands sufficiently to shatter the HSW Deflector Bronze glass Bulb, allowing the sprinkler to o= VSW Deflector Copper activate and water to flow. o Patents a U.S.A. 5,810,263 0 TFP176 Page 3 of 6 SPRINKLER FINISH K TYPE NATURAL CHROME WHITE LEAD BRASS PLATED POLYESTER COATED HORIZONTAL SIDEWALL 250 PSI(17,2 BAR) (TY3331) OR 175 PSI (12,1 BAR) 175 PSI(12,1 BAR) 5.6 RECESSED HORIZ. 1/2" SIDEWALL(TY3331) (SEE NOTE 1) N/A NPT VERTICAL SIDEWALL (TY3431) 175 PSI(12,1 BAR) NOTES: 1.The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories, Inc. (UL);the Listing by Underwriters Laboratories, Inc.for use in Canada(C-UL);and,the Approval by the City of New York. TABLE B, MAXIMUM WORKING PRESSURE D es ig n * Temperature rating is DEFLECTOR indicated on deflector or HAT 5 Crite ria adjacent to orifice seat ( Pe�.��, on frame. The Series TY FRB Horizontal and **Pipe thread 41, 11 Vertical Sidewall Sprinklers are in- connections per ISO 7/1 / Q'R�`�� tended for fire protection systems de- can be provided on signed in accordance with the stand- special request. and installation rules recognized by the 6* 4 2 3 1 applicable Listing or Approval agency (e.g., UL Listing is based on the re- 9/16" WRENCH 1/2"** quirements of NFPA 13, and FM Ap- (14,3 mm) FLATS NPT proval is based on the requirements of FM's Loss Prevention Data Sheets). —4111---•••011 Only the Style 10 or 20 Recessed Es- ` / i1E1r li IIIIII�I�IIIIIIV on, as applicable, is to be used for recessed ,nII�I�IIIIIIIIIIII for horizontal installations. • 1-13/16" 7/16" (46,0 mm) (11,1 mm) _ CENTERLINE NOMINAL OF SPRINKLER MAKE-IN WATERWAY 1-1/2" i (38,1 mm) 2-3/16" (55,6 mm) 1 -Frame STYLE ESCUTCHEON 2-Button — PLATE SEATING 3-Sealing i 10 or 20 — I Assembly RECESSED SURFACE 4-Bulb ESCUTCHEON 5-Compression Screw 6-Deflector 2(7-73/,80"mDmIA). II:-11I,�IIIIIIIIIIII 116111 FIGURE 1 5.6 K-FACTOR QUICK RESPONSE SERIES TY-FRB HORIZONTAL SIDEWALL(TY3331)SPRINKLERS Page 4 of 6 TFP176 Installation ARROW MUST POINT AWAY The Series TY-FRB Sprinklers must 7/16' FROM AND BE \ O be installed in accordance with the fol- ESCUTCHEON (11,1 mm) PERPENDICULAR / lowing instructions: PLATE SEATING ** NOMINAL TO THE BACK 1/2" SURFACE NPT MAKE-IN WALL SURFACE1 NOTES 1 Do not install any bulb type sprinkler if _ 1 *6 the bulb is cracked or there is a loss of 171 liquid from the bulb. With the sprinkler ��_ 5 held horizontally, a small air bubble 2-3/16" � — } 2-3/166 should be present. The diameter of the (55,6 mm) dIL�U► ilk (55,6 mm) 4 air bubble is approximately 1/16 inch 1UIJh1 ,, (1,6 mm) for the 135°F/57°C to 3/32 itii4M:fi:;: inch (2,4 mm) for the 286°F/141°C i 1/2 WRENCH '!»� 2 (36,1 mm) FLATS temperature ratings. __ 7 3 A leak tight 1/2 inch NPT sprinkler joint A^ - Ii should be obtained with a torque of 7 1 to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- SHOWN SHOWN CROSS mum of 21 ft. lbs. (28,5 Nm)of torque PENDENT UPRIGHT SECTION may be used to install sprinklers with 1/2 NPT connections. Higher levels of torque may distort the sprinkler and 1 -Frame 3-Sealing 4-Bulb 6-Deflector cause leakage or impairment of the 2-Button Assembly 5-Compression 7-Ejection Spring sprinkler. Screw Do not attempt to make-up for insuffi- cient adjustment in the escutcheon * Temperature rating is indicated on deflector or adjacent to orifice seat on frame. plate by under- or over-tightening the **Pipe thread connections per ISO 7/1 can be provided on special request. sprinkler. Readjust the position of the sprinkler fitting to suit. FIGURE 2 The Series TY-FRB Horizontal and 5.6 K-FACTOR QUICK RESPONSE Vertical Sidewall Sprinklers must be SERIES TY-FRB VERTICAL SIDEWALL(TY3431)SPRINKLERS installed in accordance with the follow- ing instructions. Step 1. Horizontal sidewall sprinklers are to be installed in the horizontal position with their centerline of water- Step B.After installing the Style 10 or Care a n d way perpendicular to the back wall and 20 Mounting Plate over the sprinkler parallel to the ceiling.The word"TOP" threads,hand tighten the sprinkler into on the Deflector is to face towards the the sprinkler fitting. Maintenance ceiling. Step C. Tighten the sprinkler into the The Series TY-BFR Sprinklers must Vertical sidewall sprinklers are to be sprinkler fitting using only the W-Type be maintained and serviced in accord- installed in the pendent or upright po- 7 Recessed Sprinkler Wrench (Ref. ance with the following instructions: sition with the arrow on the Deflector Figure 6). With reference to Figure 1, pointing away from the wall. the W-Type 7 Recessed Sprinkler NOTES Step 2. With pipe thread sealant ap- Wrench is to be applied to the sprinkler Before closing a fire protection system plied to the pipe threads, hand tighten wrench flats. main control valve for maintenance the sprinkler into the sprinkler fitting. Step D. After the ceiling has been in- work on the fire protection system that Step 3. Tighten the sprinkler into the stalled or the finish coat has been ap- it controls, permission to shut down sprinkler fitting using only the W-Type plied, slide on the Style 10 or 20 Clo- the affected fire protection system 6 Sprinkler Wrench (Ref. Figure 5), sure over the Series TY-FRB Sprinkler must be obtained from the proper With reference to Figure 1 or 2, the and push the Closure over the Mount- authorities and all personnel who may W-Type 6 Sprinkler Wrench is to be ing Plate until its flange comes in con- be affected by this action must be no- applied to the wrench flats. tact with the ceiling tified. The Series TY-FRB Recessed Hori- The owner must assure that the sprin- zontal Sidewall Sprinklers must be oare not used for hanging of any installed in accordance with the follow- obbjeects; otherwise, non-operation in the event of a fire or inadvertent opera- ing instructions. tion may result. Step A. Recessed horizontal sidewall Absence of an escutcheon, which is sprinklers are to be installed in the used to cover a clearance hole, may horizontal position with their centerline delay the time to sprinkler operation in of waterway perpendicular to the back wall and parallel to the ceiling. The a fire situation. word "TOP"on the Deflector is to face Sprinklers that are found to be leaking towards the ceiling. or exhibiting visible signs of corrosion TFP176 Page 5 of 6 y 5/8±1/4" ev (15,9±6,4 mm) FACE OF WRENCH RECESS MOUNTING SPRINKLER (END"A"USED FOR SURFACE ------ FITTING 1/2"NPT MODELS) ,� A FIGURE 5 CLOSURE W-TYPE 6 SPRINKLER WRENCH -411--- (73,0 2-7/8"DIA. �� (73,0 mm) WRENCH SERIES I■• RECESS TY-FRB I ft,lIII 2-1/4"DIA. �,. (57,2 mm) MOUNTING �`• 4,41 PLATE IrA411 1/8" PUSH WRENCH (3,2 mm) INTO ENSURE ENGAGEMENT 1-1/4"(31,8 mm) 3/4"(19,1 mm) WITH SPRINKLER WRENCHING AREA 3/4"(19,1 mm) 1/4"(6,4 mm) FIGURE 3 FIGURE 6 SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER W-TYPE 7 RECESSED WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT SPRINKLER WRENCH STYLE 10 RECESSED ESCUTCHEON I 1/2±1/8" must be replaced. (12,7±3,2 mm) Automatic sprinklers must never be FACE OF painted, plated, coated or otherwise MOUNTING altered after leaving the factory. Modi- SURFACE SPRINKLER fied sprinklers must be replaced. FITTING Sprinklers that have been exposed to corrosive products of combustion, but have not operated,should be replaced CLOSURE J if they cannot be completely cleaned by wiping the sprinkler with a cloth or �� 2 7/8"DIA. by brushing it with a soft bristle brush. �� (73,0 mm) Care must be exercised to avoid dam- SERIESage to the sprinklers - before, during, TY-FRB I ,MW� 2-1/4"DIA. and after installation. Sprinklers dam- aged by dropping, striking, wrench twist/slippage, or the like, must be re- fil placed. Also, replace any sprinkler MOUNTING that has a cracked bulb or that has lost PLATE I%� liquid from its bulb. (Ref. Installation ' % Section). Frequent visual inspections are rec- 1/8" ommended to be initially performed for (3,2 mm) corrosion resistant coated sprinklers, after the installation has been corn- 1-1/4"(31,8 mm) 1/2"(12,7 mm) pleted,to verify the integrity of the cor- rosion resistant coating. Thereafter, 1"(25,4 mm) 1/4"(6,4 mm) annual inspections per NFPA 25 should suffice; however, instead of in- FIGURE 4 specting from the floor level,a random SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER sampling of close-up visual inspec- WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT tions should be made, so as to better STYLE 20 RECESSED ESCUTCHEON determine the exact sprinkler condi- tion and the long term integrity of the Page 6 of 6 TFP176 P/N 57 - XXX - X - XXX I I SPRINKLER TEMPERATURE MODEUSIN RATING 378 HORIZONTAL SIDEWALL TY3331 1 NATURAL BRASS 135 135°F/57°C 375 VERTICAL SIDEWALL TY3431 4 WHITE POLYESTER 155 155°F/68°C 3 WHITE RAL9010)" 175 175°F/79°C 9 CHROME PLATED 200 200°F/93°C 7 LEAD COATED 286 286°F/141°C TABLE C *Eastern Hemisphere sales only. PART NUMBER SELECTION SERIES TY-FRB HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS corrosion resistant coating, as it may standards of any other Authorities 0 rd a ring be affected by the corrosive conditions Having Jurisdiction. Materials found present. by TFBP to be defective shall be either procedure repaired or replaced, at TFBP's sole The owner is responsible for the in- option. TFBP neither assumes, nor spection, testing, and maintenance of authorizes any person to assume for it, When placing an order, indicate the their fire protection system and de- any other obligation in connection with full product name. Refer to the Price vices in compliance with this docu- the sale of products or parts of prod- List for complete listing of Part Num- ment, as well as with the applicable ucts.TFBP shall not be responsible for bers. standards of the National Fire Protec- sprinkler system design errors or inac- Contact your local distributor for avail- tion Association (e.g., NFPA 25), in curate or incomplete information sup- ability. addition to the standards of any other plied by Buyer or Buyer's repre- authorities having jurisdiction. The in- sentatives. Sprinkler Assemblies with NPT stalling contractor or sprinkler manu- In no event shall TFBP be liable, in Thread Connections: facturer should be contacted relative contract, tort, strict liability or under Specify: (Specify Model/SIN), Quick to any questions. any other legal theory, for incidental, Response, (specify K-factor), (specify It is recommended that automatic indirect,special or consequential dam- temperature rating), Series TY-FRB sprinkler systems be inspected, ages, including but not limited to labor (specify Horizontal Sidewall or Vertical tested, and maintained by a qualified charges, regardless of whether TFBP Sidewall) Sprinkler with (specify type Inspection Service in accordance with was informed about the possibility of of finish or coating), P/N (specify from local requirements and/or national such damages, and in no event shall Table C). codes. TFBP's liability exceed an amount equal to the sales price. Recessed Escutcheon: L im ►ted The foregoing warranty is made in lieu Specify: Style (10 or 20) RecessedEscutcheon with (specify*) finish, P/N of any and all other warranties. ex- (specify*). Warranty press or implied. including warranties of merchantability and fitness for a par- *Refer to Technical Data Sheet TFP770. Products manufactured by Tyco Fire& ticular purpose. Building Products (TFBP) are war- This limited warranty sets forth the ex- Sprinkler Wrench: ranted solely to the original Buyer for clusive remedy for claims based on Specify: W-Type 6 Sprinkler Wrench, ten(10)years against defects in mate- failure of or defect in products, materi- P/N 56-000-6-387. rial and workmanship when paid for als or components, whether the claim Specify: W-Type 7 Sprinkler Wrench, and properly installed and maintained is made in contract, tort, strict liability P/N 56-850-4-001. under normal use and service. This or any other legal theory. warranty will expire ten (10) years from date of shipment by TFBP. No This warranty will apply to the full ex- warranty is given for products or corn- tent permitted by law.The invalidity, in ponents manufactured by companies whole or part, of any portion of this not affiliated by ownership with TFBP warranty will not affect the remainder. or for products and components which have been subject to misuse,improper installation, corrosion, or which have not been installed, maintained, modi- fied or repaired in accordance with ap- plicable Standards of the National Fire Protection Association, and/or the TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue, Lansdale,Pennsylvania 19446