Specifications (51) ` ®0EPLIPSE
ECLIPSE - ENGINEERING .ENGINEERING N G
Structural Calculations
Steel Storage Shelving
By Mobile Media Storage Solutions
PO #189000SC
Lucky Brand Jeans
Washington Square Mall
9712 SW Washington Square Rd - Space #F03
Tigard, OR 97223 MAR 0 7 2018
•<<-ODPRO%
w 76024P f--
,•
at/ '--
OREGON
"Pa
O Q 13, �20 2
Expires IN 80 2018
Prepared For:
Mobile Media Storage Solutions
PO Box 177
Pine Bush, NY 12566
Please note: The calculations contained within justify the seismic resistance of the shelving for both
vertical and lateral forces as required by: the 2014 OSSC,ASCE 7-10, and ANSI/RMI-MH16.1
(2012). These storage shelves are not accessible to the general public
MISSOULA COLUMi7d ,".; � ONE BEND PORTLAND
113 West Man Seek&> oula-MT69802 729 Nucleus Ave. � ,i1 .&Me621Spolone,WA 99291 3785W 6110Me.SAe 8,Bend,OR 97702 111 SW Columbia Sheet Sole 1999 Poland,OR 97201
Phase:(409)721-6733•Few(408)6524788 Phone:(498)892 -. ( '-4 Phone(609)9217731•Fax(409)6524788 Phone:(641)380-9659•Fax(408)652-4788 Phone:(603)105-1225•Fax(408)652.4788
% EC LI PSE
ENGINEERING
MOBILE MEDIA STORAGE SOLUTIONS
STEEL STORAGE SHELVING-LIGHT RETAIL
CODES: Current Editions of the: IBC&CBC&ASCE 7& RMI
Design Inputs: Steel Storage Shelving: Typical 60"x30" Hang Unit
Shelving Geometry-
Height of Shelving Unit= 10.0 ft Steel Yield Stress= 33 ksi
Width of Shelving Unit= 5.0 ft Modulus of Elast. = 29000 ksi
Depth of Shelving Unit= 2.5 ft
Number of Shelves/Unit= 4 Eff. Length Factor= 1.7
Vertical Shelf Spacing= 39.0 in Unbraced Length,x= 39.0 in
Back to Back Units? NO Unbraced Length,y= 39.0 in
Are There Mobile Units? YES Type of Post? 14ga Upright Posts
Type of Beam? Double Rivet Beam
Shelving Loading-
Live Load per Shelf= 8 psf Display On Plaque Near Shelving Units
Maximum Weight per Shelf= 100 lbs Per 2.5ft Wide Shelf
Dead Load per Shelf= 2.5 psf Particle Board Shelf Material
Weight of Each Post= 7.5 lbs
Weight of Mobile Carriage= 50 lbs
Floor Load Calculations:
Total Load on Each Post= 139 lbs
Total Load On Each Unit= 605 lbs
Floor Area Load = 12.5 ft2
Allowable Floor Loading= 100 psf For Main Floor Slab on Grade
Floor Load Under Shelf= 48 psf OK FOR 100psf RETAIL FLOOR LOADING
- Seismic Information-
Importance Factor- 1.0 Not Open to the Public SDC: D
Site Class- D Worst Case Assumed
Mapped Accel. Parameters:
S5= 0.977 Fa= 1.110 Sms= 1.084 Sds= 0.723
S1= 0.425 F„= 1.574 Sm1= 0.669 5d1= 0.446
Structural System -ASCE 7 Section 15.5.3
Steel Storage Shelving: R= 4 a = 2.5 1p= 1.0
Average Roof Height= 20 ft 0'-0" For Ground Floor Location
Height of Base Attachment= 0 ft Ground Floor
Shear Coeff Boundaries= Vmin= 0.032
Vmax= 0.181
Design Base Shear Coeff= Vt= 0.126 Adjusted For ASD
1
EC LI PSE
ENGINEERING
Lateral Force Distribution: per ASCE 7 Section 15.5.3.3
Total Dead Load per Shelf= 38.7 lbs
Total Live Load per Shelf= 100 lbs
Lateral DL Force per Shelf= 4.9 lbs
Lateral LL Force per Shelf= 12.6 lbs
67%of LL Force per Shelf= 8.5 lbs
Total DL Base Shear= 19.6 lbs
Total LL Base Shear= 50.6 lbs
LC1: Each Shelf is Loaded to 67%of its Live Weight Cumulative Moment: 26011 in-lbs
Total Base Shear= 53.5 lbs Controlling Load Case By Inspection
Height: Load: % Per Shelf: Lateral Force/Shelf:
h1= 3 in 100 lbs 1.2% Fl = 0.7 lbs
h2= 42 in 100 lbs 17.1% F2 = 9.1 lbs
h3= 81 in 100 lbs 32.9% F3 = 17.6 lbs
h4= 120 in 100 lbs 48.8% F4= 26.1 lbs
h5= 0 in 0 lbs 0.0% F5 = 0.0 lbs
h6= 0 in 0 lbs 0.0% F6= 0.0 lbs
h7= 0 in 0 lbs 0.0% F7= 0.0 lbs
h8= 0 in 0 lbs 0.0% F8= 0.0 lbs
h9= 0 in 0 lbs 0.0% F9= 0.0 lbs
h10= 0 in 0 lbs 0.0% F10= 0.0 lbs
h11 = 0 in 0 lbs 0.0% F11= 0.0 lbs
h12= 0 in 0 lbs 0.0% F12= 0.0 lbs
h13 = 0 in 0 lbs 0.0% F13 = 0.0 lbs
h14= 0 in 0 lbs 0.0% F14= 0.0 lbs
h15 = 0 in 0 lbs 0.0% F15 = 0.0 lbs
Sum = 100% Total = 53.5 lbs
LC 2:Top Shelf Only is Loaded to 100%of its Live Weight
Total Base Shear= 32.2 lbs Does Not Control
By inspection,the force distribution for intermediate shelves without live load (case 2) is negligible.
Calculate the moment for each column based on the total seismic base shear for each shelf being loaded
to 67%of it's allowable live weight. The column at the center of the shelving system is the worst case
for this condition.
2
L4=7%"EC Ll PS E
ENGINEERING
Column Calculations - Combined Bending and Axial
Post Type: Double Rivet"L" or"T" Post
Width = 1.5 in rx= 0.470 in
Depth = 1.5 in Sx= 0.040 in3
Thickness= 0.075 in lx= 0.060 in4
Ap= 0.220 in2
Column Bending Calculations-
Max Column Moment= 21.5 ft-lbs
Allowable Bending Stress= 19.8 ksi
Bending Stress on Column = 6.4 ksi Bending Stress OK
Column Deflection Calculations-
Max Deflection = 0.348 in At Top of Unit
Deflection Ratio = 344 L/A
Allowable Deflection = 6 in Max Deflection = 5%of Height
Deflection OK
Shelf Rivet Connection-
Diameter of Rivet= 0.25 in
Shear on Each Rivet= 171.7 lbs
Brg Capacity of Rivet= 519.8 lbs Brg Stress OK
Allowable Shear Stress= 13.5 ksi
Shear Stress on Rivet= 3.5 ksi Shear Stress OK
Column Axial Calculations- Per"L" Post
DL+ PL= 139 lbs RMI Load Combination#1
DL+ PL+ EQ= 274 lbs RMI Load Combination#6
Column Capacity Calculations-
Controlling Buckling Stress= 6.3 ksi
Allowable Comp. Stress= 6.3 ksi
Factor of Safety for Comp. = 1.80
Nominal Column Capacity= 1365 lbs
Allowable Column Capacity= 758 lbs
Static Axial Load on Column = 139 lbs Axial Load OK
Combined Bending And Axial Forces-
Critical Buckling Load = 3907 lbs
Axial Stress Unity= 0.361 Magnification Factor= 0.936
Bending Stress Unity= 0.295 Cm= 0.85
Combined Stress Unity= 0.657 Column is Adequate
3
EC LI PS E
ENGINEERING
Overturning and Anti-Tip Calculations
Overturning Forces-
Total Weight= 423 lbs Load Case 1: Dead Load+67% Live Load
Total Lateral Force = 53 lbs
Overturning Force= 412 ft*lbs Controlling Overturning Force
Total Weight= 255 lbs Load Case 2: Dead Load+ 100%Top Shelf
Total Lateral Force = 32 lbs
Overturning Force= 288 ft*lbs Does Not Control
Tension Force per Anchor= 59 lbs Per Side of Unit
Shear Force per Anchor= 27 lbs
valent)POST INSTALLED ANCHOR BOLTS •
Allowable Tension Force= 736 lbs For 2500 psi Concrete
Allowable Shear Force = 792 lbs 3/8" Diameter x 2.5" Embedment
Vertical Seismic Force= 21.4 lbs
Overstrength Factor= 2 For Anchoring to Concrete
Combined Loading= 0.161 Floor Anchors are Adequate
Anti-Tip Track Design-
Type of Anti-Tip Device= Arm and Track
Tension per Side= 59 lbs
Capacity of Screws to Carriage= 349 lbs (2)#12 Screws Are Adequate
Anti-Tip Yield Stress= 16 ksi 6063-T5
Thickness Anti-Tip = 0.12 in
Width of Anti-Tip = 0.43 in
Section Modulus of Leg= 0.0092 in3
Allowable Stress on Leg= 16 ksi
Bending Stress on Leg= 2.07 ksi
Anti-Tip Stress Unity= 0.129 Bending Stress OK
Section Modulus of Track= 0.090 in3
Spacing of Track A.B's= 24 in
Allowable Alumn. Stress= 16 ksi 6063-T5
Bending Stress on Track= 1.98 ksi
Track Stress Unity= 0.124 Bending Stress OK
4
ECLIPSE
ENGINEERING
Shelf Beam Calculations
Type of Shelf Beam: Double Rivet Beam
Steel Yield Stress= 33 ksi Shelf DL= 2.5 psf
Modulus of Elast. = 29000 ksi Shelf LL= 8.00 psf
Area of Beam = 0.277 in2
Section Modulus of Beam = 0.219 in3
Moment of Inertia of Beam = 0.22 in4
Allowable Load per Shelf= 100 lbs
Shelf Distributed Load= 13.1 plf Distributed Load
Allowable Bending Stress= 19.8 ksi
Allowable Shear Stress= 13.2 ksi
Maximum Beam Moment= 41.0 ft-lbs Simple Span
Maximum Design Moment= 41.0 ft-lbs
Maximum Design Shear= 32.8 lbs
Beam Bending Stress= 2.2 ksi
Beam Shear Stress= 0.12 ksi
Bending Stress Unity= 0.114 Bending Stress OK
Shear Stress Unity= 0.009 Shear Stress OK
Max Allowable Deflection = 0.333 in L/180
Maximum Beam Deflection = 0.017 in Deflection OK
Shelf Beam Rivet Check:
Diameter of Rivet= 0.25 in
Post Moment Shear on Rivet= 171.7 lbs
Beam Shear on Rivet= 32.8 lbs
Resultant Shear= 174.8 lbs
Brg Capacity of Rivet= 519.8 lbs Brg Stress OK
Allowable Shear Stress= 9.6 ksi
Shear Stress on Rivet= 3.6 ksi Shear Stress OK
5
'1 EC LI PS E
ENGINEERING
Wall Supported Unit Calculations
Seismic Force at Top of Units-
Average Roof Height= 20.0 ft
Height of Attachment= 10.0 ft
Shear Coeff Boundaries= Vm;n= 0.217
Vmax= 1.156
Design Base Shear Coeff= Vt= 0.258 Adjusted For ASD
Total Weight per Unit= 372 lbs
Lateral Force at Top/Bottom = 48 lbs
Standard Stud Spacing= 16 in
Wall Connections per Unit= 3
Tek Screw Capacity= 84 lbs Tension Cap.for#10 Screw in 20ga Stud
Force Per Connection = 16 lbs Screw Capacity OK
Seismic Uplift Force on Each Shelf
Seismic Uplift on Shelves-
Vertical Seismic Component= 19.0 lbs
Vertical Dead Load per Shelf= 131.3 lbs
Connection Points per Shelf= 4.0 Each Corner
Net Uplift Load per Shelf= -59.8 lbs
Uplift Forcer per Connection = -14.9 lbs Rivet Connection OK
6
EC LI PS E
ENGINEERING•
Light Gage Steel Stud Wall Framing
Stud Design Data-
Height of Wall Studs= 16.0 ft Int. Non-Brg-Worst Case Ht Assumed
Location of Point Load = 10.0 ft
Design Lateral Load 16.0 lbs From Shelving Unit
Additional Lateral Load = 5.0 psf Interior Seismic Force
Design Axial Load = 85.3 lbs Dead Load of Wall Framing
Spacing of Studs= 16.0 in
Studs @ 16" o.c. (Worst Case Assumed)
Width = 3.625 in rx= 1.450 in
Depth = 1.625 in ry= 0.616 in
Thickness= 0.035 in Sx= 0.268 in3
Fy= 33 ksi lx= 0.551 in4
E = 29000 ksi Ap= 0.262 in2
K= 1.0 Unbraced Length X= 16 ft
Unbraced Length Y= 4 ft
Stud Capacity-
Buckling Stress, X= 16.32 ksi
Buckling Stress, Y= 47.14 ksi
Allowable Buckling Stress= 16.32 ksi
Nominal Axial Strength = 4277 lbs
Factor of Safety= 1.92
Allowable Axial Load = 2228 lbs
Maximum Design Moment= 273.3 ft-lbs
Maximum Design Shear= 63.3 lbs
Allowable Bending Stress= 21.78 ksi
Actual Bending Stress= 12.24 ksi Bending Stress OK
Allowable Shear Stress= 13.20 ksi
Actual Shear Stress= 0.24 ksi Shear Stress OK
Allowable Axial Stress= 8.50 ksi
Actual Axial Stress= 0.33 ksi Axial Stress OK
Combined Stress Unity= 0.60 Combined Stress OK
7
: ECLIPSE
ENGINEERING •
Slab Bearing & Uplift Calculations
Slab Design Properties-
Minimum Concrete Strength = 2500 psi Assumed
Thickness of Concrete Slab= 4 in Assumed
Weight of Concrete Slab= 50 psf
Allowable Bearing Pressure= 500 psf Assumed
Bearing Loads On Post= 70 lbs Dead Load
200 lbs Live Load
165 lbs EQ Load
Uplift Loads on Post= 59 lbs Resultant Uplift
Slab Bearing Capacity-
Depth of Post on Slab= 1.5 in
Factored Bearing Load = 639 lbs
Required Bearing Area = 125.21 in2 11.19 inches per side
Critical Section = 2.84 in For Bending
Soil Pressure on Crit. Section = 735.3 plf Along Critical Length
Section Modulus= 32.0 in3 Plain Concrete per Foot
Shear Area = 22 in
Conc. Shear Stress= 7.3 psi
Allowable Shear Stress= 73.2 psi Shear Stress OK
Conc. Bending Stress= 7.7 psi
Allowable Bending Stress= 137.5 psi Bending Stress OK
Slab Uplift Capacity-
Required Area to Resist Uplift= 1.98 ft2
Length of Slab Req'd = 0.40 ft Assume Full Shelf Width x Req'd Length
Worst Case Length of Slab= 5.00 ft Maximum of Width or Length Req'd
Distance to Anchor Bolt= 2.50 ft
Shear Force on 1ft Strip= 175.0 lbs
Allowable Shear Force= 1760.0 lbs Shear OK
Bending Moment on 1ft Strip= 218.8 ft-lbs
Allowable Bending Moment= 366.7 ft-lbs Bending OK
8
'1 EC LI PS E
ENGINEERING
MOBILE MEDIA STORAGE SOLUTIONS
STEEL STORAGE SHELVING-LIGHT RETAIL
CODES: Current Editions of the: IBC&CBC&ASCE 7 & RMI
Design Inputs: Steel Storage Shelving: Typical 60"x30" Fold Unit
Shelving Geometry-
Height of Shelving Unit= 10.0 ft Steel Yield Stress= 33 ksi
Width of Shelving Unit= 5.0 ft Modulus of Elast. = 29000 ksi
Depth of Shelving Unit= 2.5 ft
Number of Shelves/Unit= 9 Eff. Length Factor= 1.7
Vertical Shelf Spacing= 14.6 in Unbraced Length,x= 14.6 in
Back to Back Units? NO Unbraced Length,y= 14.6 in
Are There Mobile Units? YES Type of Post? 14ga Upright Posts
Type of Beam? Double Rivet Beam
Shelving Loading-
Live Load per Shelf= 5 psf Display On Plaque Near Shelving Units
Maximum Weight per Shelf= 63 lbs Per 2.5ft Wide Shelf
Dead Load per Shelf= 2.5 psf Particle Board Shelf Material
Weight of Each Post= 7.5 lbs
Weight of Mobile Carriage= 50 lbs
Floor Load Calculations:
Total Load on Each Post= 218 lbs
Total Load On Each Unit= 924 lbs
Floor Area Load = 12.5 ft2
Allowable Floor Loading= 100 psf For Main Floor Slab on Grade
Floor Load Under Shelf= 74 psf OK FOR 100psf RETAIL FLOOR LOADING
• Seismic Information-
Importance Factor- 1.0 Not Open to the Public SDC: D
Site Class- D Worst Case Assumed
Mapped Accel. Parameters:
S5= 0.977 Fa= 1.110 Sms= 1.084 Sds= 0.723
S1= 0.425 F„= 1.574 Sm1= 0.669 5d1= 0.446
Structural System -ASCE 7 Section 15.5.3
Steel Storage Shelving: R= 4 ap= 2.5 IP= 1.0
Average Roof Height= 20 ft 0'-0" For Ground Floor Location
Height of Base Attachment= 0 ft Ground Floor
Shear Coeff Boundaries= Vm;"= 0.032
Vmax= 0.181
Design Base Shear Coeff= Vt= 0.126 Adjusted For ASD
9
EC LI PS E
ENGINEERING
Lateral Force Distribution: per ASCE 7 Section 15.5.3.3
Total Dead Load per Shelf= 34.6 lbs
Total Live Load per Shelf= 62.5 lbs
Lateral DL Force per Shelf= 4.4 lbs
Lateral LL Force per Shelf= 7.9 lbs
67%of LL Force per Shelf= 5.3 lbs
Total DL Base Shear= 39.4 lbs
Total LL Base Shear= 71.1 lbs
LC1: Each Shelf is Loaded to 67%of its Live Weight Cumulative Moment: 42316 in-lbs
Total Base Shear= 87.0 lbs Controlling Load Case By Inspection
Height: Load: % Per Shelf: Lateral Force/Shelf:
111 = 3 in 63 lbs 0.5% F1= 0.5 lbs
h2= 18 in 63 lbs 3.2% F2= 2.8 lbs
h3 = 32 in 63 lbs 5.8% F3= 5.1 lbs
h4= 47 in 63 lbs 8.5% F4= 7.4 lbs
h5= 62 in 63 lbs 11.1% F5= 9.7 lbs
h6= 76 in 63 lbs 13.8% F6= 12.0 lbs
h7= 91 in 63 lbs 16.4% F7= 14.3 lbs
h8= 105 in 63 lbs 19.0% F8= 16.6 lbs
h9= 120 in 63 lbs 21.7% F9= 18.9 lbs
h10= 0 in 0 lbs 0.0% F10= 0.0 lbs
h11 = 0 in 0 lbs 0.0% F11= 0.0 lbs
h12= 0 in 0 lbs 0.0% F12= 0.0 lbs
h13 = 0 in 0 lbs 0.0% F13 = 0.0 lbs
h14= 0 in 0 lbs 0.0% F14= 0.0 lbs
h15= 0 in 0 lbs 0.0% F15= 0.0 lbs
Sum = 100% Total = 87.0 lbs
LC 2:Top Shelf Only is Loaded to 100%of its Live Weight
Total Base Shear= 47.3 lbs Does Not Control
By inspection,the force distribution for intermediate shelves without live load (case 2) is negligible.
Calculate the moment for each column based on the total seismic base shear for each shelf being loaded
to 67%of it's allowable live weight. The column at the center of the shelving system is the worst case
for this condition.
10
EC LC PSE
ENGINEERING
Column Calculations - Combined Bending and Axial
Post Type: Double Rivet"L" or"T" Post
Width = 1.5 in rx= 0.470 in
Depth = 1.5 in Sx= 0.040 in3
Thickness= 0.075 in Ix= 0.060 in4
Ap= 0.220 in2
Column Bending Calculations-
Max Column Moment= 13.2 ft-lbs
Allowable Bending Stress= 19.8 ksi
Bending Stress on Column = 4.0 ksi Bending Stress OK
Column Deflection Calculations
Max Deflection = 0.073 in At Top of Unit
Deflection Ratio= 1648 L/A
Allowable Deflection = 6 in Max Deflection =5%of Height
Deflection OK
Shelf Rivet Connection-
Diameter of Rivet= 0.25 in
Shear on Each Rivet= 105.5 lbs
Brg Capacity of Rivet= 519.8 lbs Brg Stress OK
Allowable Shear Stress= 13.5 ksi
Shear Stress on Rivet= 2.1 ksi Shear Stress OK
Column Axial Calculations- Per"L" Post
DL+ PL= 218 lbs RMI Load Combination#1
DL+ PL+ EQ= 425 lbs RMI Load Combination#6
Column Capacity Calculations-
Controlling Buckling Stress = 21.2 ksi
Allowable Comp. Stress= 20.1 ksi
Factor of Safety for Comp. = 1.80
Nominal Column Capacity= 3909 lbs
Allowable Column Capacity= 2172 lbs
Static Axial Load on Column = 218 lbs Axial Load OK
Combined Bending And Axial Forces-
Critical Buckling Load = 27782 lbs
Axial Stress Unity= 0.196 Magnification Factor= 0.986
Bending Stress Unity= 0.172 Cm= 0.85
Combined Stress Unity= 0.368 Column is Adequate
11
EC LI PSE
ENGINEERING
Overturning and Anti-Tip Calculations
Overturning Forces-
Total Weight= 688 lbs Load Case 1: Dead Load +67% Live Load
Total Lateral Force= 87 lbs
Overturning Force= 614 ft*lbs Controlling Overturning Force
Total Weight= 374 lbs Load Case 2: Dead Load+ 100%Top Shelf
Total Lateral Force= 47 lbs •
Overturning Force= 324 ft*lbs Does Not Control
Tension Force per Anchor= 74 lbs Per Side of Unit
Shear Force per Anchor= 44 lbs
valent) POST INSTALLED ANCHOR BOLTS
Allowable Tension Force= 736 lbs For 2500 psi Concrete
Allowable Shear Force= 792 lbs 3/8" Diameter x 2.5" Embedment
Vertical Seismic Force= 34.8 lbs
Overstrength Factor= 2 For Anchoring to Concrete
Combined Loading= 0.201 Floor Anchors are Adequate
Anti-Tip Track Design-
Type of Anti-Tip Device= Arm and Track
Tension per Side= 74 lbs
Capacity of Screws to Carriage= 349 lbs (2)#12 Screws Are Adequate
Anti-Tip Yield Stress= 16 ksi 6063-T5
Thickness Anti-Tip= 0.12 in
Width of Anti-Tip= 0.43 in
Section Modulus of Leg= 0.0092 in3
Allowable Stress on Leg= 16 ksi
Bending Stress on Leg= 2.58 ksi
Anti-Tip Stress Unity= 0.161 Bending Stress OK
Section Modulus of Track= 0.090 in3
Spacing of Track A.B's= 24 in
Allowable Alumn.Stress= 16 ksi 6063-T5
Bending Stress on Track= 2.47 ksi
Track Stress Unity= 0.154 Bending Stress OK
12
EC LI PS E
ENGINEERING
Shelf Beam Calculations
Type of Shelf Beam: Double Rivet Beam
Steel Yield Stress= 33 ksi Shelf DL= 2.5 psf
Modulus of Elast. = 29000 ksi Shelf LL= 5.00 psf
Area of Beam = 0.1681 int
Section Modulus of Beam = 0.0197 in3
Moment of Inertia of Beam = 0.0139 in4
Allowable Load per Shelf= 63 lbs
Shelf Distributed Load = 9.4 plf Distributed Load
Allowable Bending Stress= 19.8 ksi
Allowable Shear Stress= 13.2 ksi
Maximum Beam Moment= 29.3 ft-lbs Simple Span
Maximum Design Moment= 29.3 ft-lbs
Maximum Design Shear= 23.4 lbs
Beam Bending Stress = 17.85 ksi
Beam Shear Stress= 0.14 ksi
Bending Stress Unity= 0.901 Bending Stress OK
Shear Stress Unity= 0.011 Shear Stress OK
Max Allowable Deflection = 0.333 in L/180
Maximum Beam Deflection = 0.327 in Deflection OK
Shelf Beam Rivet Check:
Diameter of Rivet= 0.25 in
Post Moment Shear on Rivet= 105.5 lbs
Beam Shear on Rivet= 23.4 lbs
Resultant Shear= 108.1 lbs
Brg Capacity of Rivet= 519.8 lbs Brg Stress OK
Allowable Shear Stress= 9.6 ksi
Shear Stress on Rivet= 2.2 ksi Shear Stress OK
13
EC LI PSE
ENGINEERING •
Wall Supported Unit Calculations
Seismic Force at Top of Units-
Average Roof Height= 20.0 ft
Height of Attachment= 10.0 ft
Shear Coeff Boundaries= Vmin= 0.217
Vmax= 1.156
Design Base Shear Coeff= Vt= 0.258 Adjusted For ASD
Total Weight per Unit= 585 lbs
Lateral Force at Top/Bottom = 76 lbs
Standard Stud Spacing= 16 in
Wall Connections per Unit= 3
Tek Screw Capacity= 84 lbs Tension Cap.for#10 Screw in 20ga Stud
Force Per Connection = 25 lbs Screw Capacity OK
Seismic Uplift Force on Each Shelf
Seismic Uplift on Shelves-
Vertical Seismic Component= 13.6 lbs
Vertical Dead Load per Shelf= 93.8 lbs
Connection Points per Shelf= 4.0 Each Corner
Net Uplift Load per Shelf= -42.7 lbs
IUplift Forcer per Connection = -10.7 lbs Rivet Connection OK
14
`: ECLIPSE
ENGINEERING
Light Gage Steel Stud Wall Framing
Stud Design Data-
Height of Wall Studs= 16.0 ft Int. Non-Brg-Worst Case Ht Assumed
Location of Point Load = 10.0 ft
Design Lateral Load = 25.2 lbs From Shelving Unit
Additional Lateral Load = 5.0 psf Interior Seismic Force
Design Axial Load = 85.3 lbs Dead Load of Wall Framing
Spacing of Studs= 16.0 in
Studs @ 16" o.c. (Worst Case Assumed)
Width = 3.625 in rx= 1.450 in
Depth= 1.625 in ry= 0.616 in
Thickness= 0.035 in Sx= 0.268 in3
Fy= 33 ksi Ix= 0.551 in4
E = 29000 ksi Ap= 0.262 in2
K= 1.0 Unbraced Length X= 16 ft
Unbraced Length Y= 4 ft
Stud Capacity-
Buckling Stress,X= 16.32 ksi
Buckling Stress,Y= 47.14 ksi
Allowable Buckling Stress= 16.32 ksi
Nominal Axial Strength = 4277 lbs
Factor of Safety= 1.92
•
Allowable Axial Load = 2228 lbs
Maximum Design Moment= 307.8 ft-lbs
Maximum Design Shear= 69.1 lbs
Allowable Bending Stress= 21.78 ksi
Actual Bending Stress= 13.78 ksi Bending Stress OK
Allowable Shear Stress= 13.20 ksi
Actual Shear Stress= 0.26 ksi Shear Stress OK
Allowable Axial Stress= 8.50 ksi
Actual Axial Stress= 0.33 ksi Axial Stress OK
Combined Stress Unity= 0.67 Combined Stress OK
15
EC Ll PS E
ENGINEERING
Slab Bearing & Uplift Calculations
Slab Design Properties-
Minimum Concrete Strength = 2500 psi Assumed
Thickness of Concrete Slab= 4 in Assumed
Weight of Concrete Slab= 50 psf
Allowable Bearing Pressure= 500 psf Assumed
Bearing Loads On Post= 148 lbs Dead Load
281 lbs Live Load
123 lbs EQ Load
•
Uplift Loads on Post= 74 lbs Resultant Uplift
Slab Bearing Capacity-
Depth of Post on Slab= 1.5 in
Factored Bearing Load = 803 lbs
Required Bearing Area = 159.03 in2 12.61 inches per side
Critical Section = 3.56 in For Bending
Soil Pressure on Crit. Section = 727.3 plf Along Critical Length
Section Modulus= 32.0 in3 Plain Concrete per Foot
Shear Area= 22 in
Conc.Shear Stress= 9.1 psi
Allowable Shear Stress= 73.2 psi Shear Stress OK
Conc. Bending Stress= 12.0 psi
Allowable Bending Stress= 137.5 psi Bending Stress OK
Slab Uplift Capacity-
Required Area to Resist Uplift= 2.47 ft2
Length of Slab Req'd = 0.49 ft Assume Full Shelf Width x Req'd Length
Worst Case Length of Slab= 5.00 ft Maximum of Width or Length Req'd
Distance to Anchor Bolt= 2.50 ft
Shear Force on 1ft Strip= 175.0 lbs
Allowable Shear Force= 1760.0 lbs Shear OK
Bending Moment on 1ft Strip= 218.8 ft-lbs
Allowable Bending Moment= 366.7 ft-lbs Bending OK
16
i EC LI PS E Lucky Brand Jeans 3/6/2018
ENGINEERING Tigard, OR 97223 RVC
MOBILE MEDIA STORAGE SOLUTIONS
STEEL STORAGE SHELVING-LIGHT RETAIL
CODES: Current Editions of the: IBC&CBC&ASCE 7 & RMI
Design Inputs: Steel Storage Shelving: Typical 48"x30" Hang Unit
Shelving Geometry-
Height of Shelving Unit= 10.0 ft Steel Yield Stress= 33 ksi
Width of Shelving Unit= 4.0 ft Modulus of Elast. = 29000 ksi
Depth of Shelving Unit= 2.5 ft
Number of Shelves/Unit= 4 Eff. Length Factor= 1.7
Vertical Shelf Spacing= 39.0 in Unbraced Length,x= 39.0 in
Back to Back Units? NO Unbraced Length,y= 39.0 in
Are There Mobile Units? YES Type of Post? 14ga Upright Posts
Type of Beam? Double Rivet Beam
Shelving Loading-
Live Load per Shelf= 8 psf Display On Plaque Near Shelving Units
Maximum Weight per Shelf= 80 lbs Per 2.5ft Wide Shelf
Dead Load per Shelf= 2.5 psf Particle Board Shelf Material
Weight of Each Post= 7.5 lbs
Weight of Mobile Carriage= 50 lbs
Floor Load Calculations:
Total Load on Each Post= 112 lbs
Total Load On Each Unit= 500 lbs
Floor Area Load = 10.0 ft2
Allowable Floor Loading= 100 psf For Main Floor Slab on Grade
Floor Load Under Shelf= 50 psf 10K FOR 100psf RETAIL FLOOR LOADING
Seismic Information-
Importance Factor- 1.0 Not Open to the Public SDC: D
Site Class- D Worst Case Assumed
Mapped Accel. Parameters:
Ss= 0.977 Fa= 1.110 Sms= 1.084 Sds= 0.723
S1= 0.425 F„= 1.574 Sm1= 0.669 Sdl= 0.446
Structural System-ASCE 7 Section 15.5.3
Steel Storage Shelving: R= 4 aP= 2.5 Ip= 1.0
Average Roof Height= 20 ft 0'-0" For Ground Floor Location
Height of Base Attachment= 0 ft Ground Floor
Shear Coeff Boundaries= Vm;n= 0.032
Vmax= 0.181
Design Base Shear Coeff= Vt= 0.126 'Adjusted For ASD
17
E=./i Lucky Brand Jeans 3/6/2018
E N G I NEER
EC Tigard, OR 97223 RVC
E R IN G E
Lateral Force Distribution: per ASCE 7 Section 15.5.3.3
Total Dead Load per Shelf= 32.5 lbs
Total Live Load per Shelf= 80 lbs
Lateral DL Force per Shelf= 4.1 lbs
Lateral LL Force per Shelf= 10.1 lbs
67%of LL Force per Shelf= 6.8 lbs
Total DL Base Shear= 16.4 lbs
Total LL Base Shear= 40.5 lbs
LC1: Each Shelf is Loaded to 67%of its Live Weight Cumulative Moment: 21177 in-lbs
I Total Base Shear= 43.5 lbs 'Controlling Load Case By Inspection
Height: Load: %Per Shelf: Lateral Force/Shelf:
h1= 3 in 80 lbs 1.2% Fl= 0.5 lbs
h2= 42 in 80 lbs 17.1% F2 = 7.4 lbs
h3 = 81 in 80 lbs 32.9% F3= 14.3 lbs
h4= 120 in 80 lbs 48.8% F4= 21.2 lbs
h5= 0 in 0 lbs 0.0% F5 = 0.0 lbs
h6= 0 in 0 lbs 0.0% F6= 0.0 lbs
h7= 0 in 0 lbs 0.0% F7 = 0.0 lbs
h8= 0 in 0 lbs 0.0% F8= 0.0 lbs
h9= 0 in 0 lbs 0.0% F9= 0.0 lbs
h10= 0 in 0 lbs 0.0% F10= 0.0 lbs
h11 = 0 in 0 lbs 0.0% F11= 0.0 lbs
h12= 0 in 0 lbs 0.0% F12= 0.0 lbs
h13= 0 in 0 lbs 0.0% F13 = 0.0 lbs
h14= 0 in 0 lbs 0.0% F14= 0.0 lbs
h15= 0 in 0 lbs 0.0% F15 = 0.0 lbs
Sum = 100% Total = 43.5 lbs
LC 2:Top Shelf Only is Loaded to 100%of its Live Weight
Total Base Shear= 26.6 lbs Does Not Control
By inspection,the force distribution for intermediate shelves without live load (case 2) is negligible.
Calculate the moment for each column based on the total seismic base shear for each shelf being loaded
to 67%of it's allowable live weight. The column at the center of the shelving system is the worst case
for this condition.
18
, ;5 EC LI PS E Lucky Brand Jeans 3/6/2018
ENGINEERING Tigard, OR 97223 RVC
Column Calculations - Combined Bending and Axial
Post Type: Double Rivet"L" or"T" Post
Width = 1.5 in rX= 0.470 in
Depth = 1.5 in SX= 0.040 in3
Thickness= 0.075 in lx= 0.060 in4
Ap= 0.220 in2
Column Bending Calculations-
Max Column Moment= 17.5 ft-lbs
Allowable Bending Stress= 19.8 ksi
Bending Stress on Column = 5.2 ksi Bending Stress OK
Column Deflection Calculations-
Max Deflection = 0.284 in At Top of Unit
Deflection Ratio= 423 L/A
Allowable Deflection = 6 in Max Deflection =5%of Height
Deflection OK
Shelf Rivet Connection-
Diameter of Rivet= 0.25 in
Shear on Each Rivet= 139.8 lbs
Brg Capacity of Rivet= 519.8 lbs Brg Stress OK
Allowable Shear Stress= 13.5 ksi
Shear Stress on Rivet= 2.8 ksi Shear Stress OK
Column Axial Calculations- Per"L" Post
DL+ PL= 112 lbs RMI Load Combination#1
DL+ PL+ EQ= 223 lbs RMI Load Combination#6
Column Capacity Calculations-
Controlling Buckling Stress= 6.3 ksi
Allowable Comp. Stress= 6.3 ksi
Factor of Safety for Comp. = 1.80
Nominal Column Capacity= 1365 lbs
Allowable Column Capacity= 758 lbs
Static Axial Load on Column = 112 lbs Axial Load OK
Combined Bending And Axial Forces-
Critical Buckling Load = 3907 lbs
Axial Stress Unity= 0.294 Magnification Factor= 0.948
Bending Stress Unity= 0.237 Cm= 0.85
Combined Stress Unity= 0.532 Column is Adequate
19
Lucky Brand Jeans 3/6/2018
EC Li PS E
ENGINEERING Tigard, OR 97223 RVC
Overturning and Anti-Tip Calculations
Overturning Forces-
Total Weight= 344 lbs Load Case 1: Dead Load+67%Live Load
Total Lateral Force = 44 lbs
Overturning Force= 335 ft*lbs Controlling Overturning Force
Total Weight= 210 lbs Load Case 2: Dead Load + 100%Top Shelf
Total Lateral Force= 27 lbs
Overturning Force= 237 ft*lbs (Does Not Control
Tension Force per Anchor= 48 lbs Per Side of Unit
Shear Force per Anchor= 22 lbs
valent) POST INSTALLED ANCHOR BOLTS •
Allowable Tension Force= 736 lbs For 2500 psi Concrete
Allowable Shear Force= 792 lbs 3/8" Diameter x 2.5" Embedment
Vertical Seismic Force= 17.4 lbs
Overstrength Factor= 2 For Anchoring to Concrete
Combined Loading= 0.131 I Floor Anchors are Adequate
Anti-Tip Track Design-
Type of Anti-Tip Device= Arm and Track
Tension per Side = 48 lbs
Capacity of Screws to Carriage= 349 lbs (2)#12 Screws Are Adequate
Anti-Tip Yield Stress= 16 ksi 6063-T5
Thickness Anti-Tip = 0.12 in
Width of Anti-Tip= 0.43 in
Section Modulus of Leg= 0.0092 in3
Allowable Stress on Leg= 16 ksi
Bending Stress on Leg= 1.68 ksi
Anti-Tip Stress Unity= 0.105 I Bending Stress OK
Section Modulus of Track= 0.090 in3
Spacing of Track A.B's= 24 in
Allowable Alumn. Stress= 16 ksi 6063-T5
Bending Stress on Track= 1.61 ksi
Track Stress Unity= 0.101 ( Bending Stress OK
20
1 EC LI PS E Lucky Brand Jeans 3/6/2018
ENGINEERING Tigard, OR 97223 RVC
Shelf Beam Calculations
Type of Shelf Beam: Double Rivet Beam
Steel Yield Stress= 33 ksi Shelf DL= 2.5 psf
Modulus of Elast. = 29000 ksi Shelf LL= 8.00 psf
Area of Beam = 0.1681 in2
Section Modulus of Beam = 0.0197 in3
Moment of Inertia of Beam = 0.0139 in4
Allowable Load per Shelf= 80 lbs
Shelf Distributed Load = 13.1 plf Distributed Load
Allowable Bending Stress= 19.8 ksi
Allowable Shear Stress= 13.2 ksi
Maximum Beam Moment= 26.3 ft-lbs Simple Span
Maximum Design Moment= 26.3 ft-lbs
Maximum Design Shear= 26.3 lbs
Beam Bending Stress= 16.0 ksi
Beam Shear Stress= 0.16 ksi
Bending Stress Unity= 0.808 Bending Stress OK
Shear Stress Unity= 0.012 Shear Stress OK
Max Allowable Deflection = 0.267 in L/180
Maximum Beam Deflection = 0.188 in Deflection OK
Shelf Beam Rivet Check:
Diameter of Rivet= 0.25 in
Post Moment Shear on Rivet= 139.8 lbs
Beam Shear on Rivet= 26.3 lbs
Resultant Shear= 142.2 lbs
Brg Capacity of Rivet= 519.8 lbs Brg Stress OK
Allowable Shear Stress= 9.6 ksi
Shear Stress on Rivet= 2.9 ksi Shear Stress OK
21
't.5. EC LI PS E Lucky Brand Jeans 3/6/2018
ENGINEERING Tigard, OR 97223 RVC
Wall Supported Unit Calculations
Seismic Force at Top of Units-
Average Roof Height= 20.0 ft
Height of Attachment= 10.0 ft
Shear Coeff Boundaries= Vm;n= 0.217
Vmax= 1.156
Design Base Shear Coeff= Vt= 0.258 Adjusted For ASD
Total Weight per Unit= 301 lbs
Lateral Force at Top/Bottom = 39 lbs
Standard Stud Spacing= 16 in
Wall Connections per Unit= 3
Tek Screw Capacity= 84 lbs Tension Cap.for#10 Screw in 20ga Stud
Force Per Connection = 13 lbs Screw Capacity OK
Seismic Uplift Force on Each Shelf
Seismic Uplift on Shelves-
Vertical Seismic Component= 15.2 lbs
Vertical Dead Load per Shelf= 105.0 lbs
Connection Points per Shelf= 4.0 Each Corner
Net Uplift Load per Shelf= -47.8 lbs
Uplift Forcer per Connection = -12.0 lbs Rivet Connection OK
22
i EC LI PS E Lucky Brand Jeans 3/6/2018
ENGINEERING Tigard, OR 97223 RVC
Light Gage Steel Stud Wall Framing
Stud Design Data-
Height of Wall Studs= 16.0 ft Int. Non-Brg-Worst Case Ht Assumed
Location of Point Load = 10.0 ft
Design Lateral Load= 13.0 lbs From Shelving Unit
Additional Lateral Load = 5.0 psf Interior Seismic Force
Design Axial Load = 85.3 lbs Dead Load of Wall Framing
Spacing of Studs= 16.0 in
Studs @ 16" o.c. (Worst Case Assumed)
Width = 3.625 in rx= 1.450 in
Depth = 1.625 in ry= 0.616 in
Thickness= 0.035 in Sx= 0.268 in3
Fy= 33 ksi lx= 0.551 in4
E= 29000 ksi Ap = 0.262 in2
K= 1.0 Unbraced Length X= 16 ft
Unbraced Length Y= 4 ft
Stud Capacity-
Buckling Stress,X= 16.32 ksi
Buckling Stress,Y= 47.14 ksi
Allowable Buckling Stress= 16.32 ksi
Nominal Axial Strength = 4277 lbs
Factor of Safety= 1.92
Allowable Axial Load = 2228 lbs
Maximum Design Moment= 262.0 ft-lbs
Maximum Design Shear= 61.4 lbs
Allowable Bending Stress= 21.78 ksi
Actual Bending Stress = 11.73 ksi Bending Stress OK
Allowable Shear Stress= 13.20 ksi
Actual Shear Stress= 0.23 ksi Shear Stress OK
Allowable Axial Stress= 8.50 ksi
Actual Axial Stress= 0.33 ksi Axial Stress OK
Combined Stress Unity= 0.58 Combined Stress OK
23
"i EC Ll PS E Lucky Brand Jeans 3/6/2018
ENGINEERING Tigard, OR 97223 RVC
Slab Bearing & Uplift Calculations
Slab Design Properties-
Minimum Concrete Strength = 2500 psi Assumed
Thickness of Concrete Slab= 4 in Assumed
Weight of Concrete Slab= 50 psf
Allowable Bearing Pressure= 500 psf Assumed
Bearing Loads On Post= 57 lbs Dead Load
160 lbs Live Load
134 lbs EQ Load
Uplift Loads on Post= 48 lbs Resultant Uplift
Slab Bearing Capacity-
Depth of Post on Slab= 1.5 in
Factored Bearing Load = 517 lbs
Required Bearing Area = 101.27 in2 10.06 inches per side
Critical Section = 2.28 in For Bending
Soil Pressure on Crit. Section = 734.6 plf Along Critical Length
Section Modulus= 32.0 in3 Plain Concrete per Foot.
Shear Area = 22 in
Conc. Shear Stress= 5.9 psi
Allowable Shear Stress= 73.2 psi Shear Stress OK
Conc. Bending Stress= 5.0 psi
Allowable Bending Stress= 137.5 psi Bending Stress OK
Slab Uplift Capacity-
Required Area to Resist Uplift= 1.61 ft2
Length of Slab Req'd = 0.40 ft Assume Full Shelf Width x Req'd Length
Worst Case Length of Slab= 4.00 ft Maximum of Width or Length Req'd
Distance to Anchor Bolt= 2.00 ft
Shear Force on 1ft Strip= 140.0 lbs
Allowable Shear Force= 1760.0 lbs Shear OK
Bending Moment on 1ft Strip= 140.0 ft-lbs
Allowable Bending Moment= 366.7 ft-lbs Bending OK
24
1 EC LI PSE Lucky Brand Jeans 3/6/2018
ENGINEERING Tigard, OR 97223 RVC
MOBILE MEDIA STORAGE SOLUTIONS
STEEL STORAGE SHELVING-LIGHT RETAIL
CODES: Current Editions of the: IBC&CBC&ASCE 7& RMI
Design Inputs: Steel Storage Shelving: Typical 48"x30" Fold Unit
Shelving Geometry-
Height of Shelving Unit= 10.0 ft Steel Yield Stress= 33 ksi
Width of Shelving Unit= 4.0 ft Modulus of Elast. = 29000 ksi
Depth of Shelving Unit= 2.5 ft
Number of Shelves/Unit= 9 Eff. Length Factor= 1.7
Vertical Shelf Spacing= 14.6 in Unbraced Length,x= 14.6 in
Back to Back Units? NO Unbraced Length,y= 14.6 in
Are There Mobile Units? YES Type of Post? 14ga Upright Posts
Type of Beam? Double Rivet Beam
Shelving Loading-
Live Load per Shelf= 8 psf Display On Plaque Near Shelving Units
Maximum Weight per Shelf= 80 lbs Per 2.5ft Wide Shelf
Dead Load per Shelf= 2.5 psf Particle Board Shelf Material
Weight of Each Post= 7.5 lbs
Weight of Mobile Carriage= 50 lbs
Floor Load Calculations:
Total Load on Each Post= 244 lbs
Total Load On Each Unit= 1025 lbs
Floor Area Load = 10.0 ft2
Allowable Floor Loading= 100 psf For Main Floor Slab on Grade
Floor Load Under Shelf= 102 psf OK FOR 100psf RETAIL FLOOR LOADING
Seismic Information-
Importance Factor- 1.0 Not Open to the Public SDC: D
Site Class- D Worst Case Assumed
Mapped Accel. Parameters:
Ss= 0.977 Fa= 1.110 Sms= 1.084 Sds= 0.723
51= 0.425 F„= 1.574 Sm1= 0.669 Sd1 = 0.446
Structural System -ASCE 7 Section 15.5.3
Steel Storage Shelving: R= 4 ap= 2.5 1,= 1.0
Average Roof Height= 20 ft 0'-0" For Ground Floor Location
Height of Base Attachment= 0 ft Ground Floor
Shear Coeff Boundaries= Vm;"= 0.032
Vmax= 0.181
Design Base Shear Coeff= Vt= 0.126 Adjusted For ASD
25
!'4% Lucky Brand Jeans 3/6/2018
EC LI PS E
ENGINEERING Tigard, OR 97223 RVC
Lateral Force Distribution: per ASCE 7 Section 15.5.3.3
Total Dead Load per Shelf= 28.3 lbs
Total Live Load per Shelf= 80 lbs
Lateral DL Force per Shelf= 3.6 lbs
Lateral LL Force per Shelf= 10.1 lbs
67%of LL Force per Shelf= 6.8 lbs
Total DL Base Shear= 32.2 lbs
Total LL Base Shear= 91.1 lbs
LC1: Each Shelf is Loaded to 67%of its Live Weight Cumulative Moment: 45347 in-lbs
Total Base Shear= 93.2 lbs Controlling Load Case By Inspection
Height: Load: % Per Shelf: Lateral Force/Shelf:
h1= 3 in 80 lbs 0.5% Fl = 0.5 lbs
h2 = 18 in 80 lbs 3.2% F2 = 3.0 lbs
h3 = 32 in 80 lbs 5.8% F3 = 5.4 lbs
h4= 47 in 80 lbs 8.5% F4= 7.9 lbs
h5 = 62 in 80 lbs 11.1% F5 = 10.4 lbs
h6= 76 in 80 lbs 13.8% F6= 12.8 lbs
h7= 91 in 80 lbs 16.4% F7= 15.3 lbs
h8= 105 in 80 lbs 19.0% F8= 17.8 lbs
h9= 120 in 80 lbs 21.7% F9= 20.2 lbs
h10= 0 in 0 lbs 0.0% F10= 0.0 lbs
h11 = 0 in 0 lbs 0.0% F11 = 0.0 lbs
h12 = 0 in 0 lbs 0.0% F12= 0.0 lbs
h13 = 0 in 0 lbs 0.0% F13= 0.0 lbs
h14= 0 in 0 lbs 0.0% F14= 0.0 lbs
h15 = 0 in 0 lbs 0.0% F15 = 0.0 lbs
Sum = 100% Total = 93.2 lbs
LC 2:Top Shelf Only is Loaded to 100%of its Live Weight
Total Base Shear= 42.4 lbs Does Not Control
By inspection,the force distribution for intermediate shelves without live load (case 2) is negligible.
Calculate the moment for each column based on the total seismic base shear for each shelf being loaded
to 67%of it's allowable live weight. The column at the center of the shelving system is the worst case
for this condition.
26
' i EC LI PS E Lucky Brand Jeans 3/6/2018
ENGINEERING Tigard, OR 97223 RVC
Column Calculations - Combined Bending and Axial
Post Type: Double Rivet"L" or"T" Post
Width = 1.5 in rx= 0.470 in
Depth = 1.5 in Sx= 0.040 in3
Thickness= 0.075 in lx= 0.060 in4
Ap= 0.220 in2
Column Bending Calculations-
Max Column Moment= 14.1 ft-lbs
Allowable Bending Stress= 19.8 ksi
Bending Stress on Column = 4.2 ksi Bending Stress OK
Column Deflection Calculations-
Max Deflection = 0.078 in At Top of Unit
Deflection Ratio= 1538 L/A
Allowable Deflection = 6 in Max Deflection =5%of Height
Deflection OK
Shelf Rivet Connection-
Diameter of Rivet= 0.25 in
Shear on Each Rivet= 113.0 lbs
Brg Capacity of Rivet= 519.8 lbs Brg Stress OK
Allowable Shear Stress= 13.5 ksi
Shear Stress on Rivet= 2.3 ksi Shear Stress OK
Column Axial Calculations- Per"L" Post
DL+ PL= 244 lbs RMI Load Combination#1
DL+ PL+ EQ= 453 lbs RMI Load Combination#6
Column Capacity Calculations-
Controlling Buckling Stress = 21.2 ksi
Allowable Comp. Stress= 20.1 ksi
Factor of Safety for Comp. = 1.80
Nominal Column Capacity= 3909 lbs
Allowable Column Capacity= 2172 lbs
Static Axial Load on Column = 244 lbs Axial Load OK
Combined Bending And Axial Forces-
Critical Buckling Load = 27782 lbs
Axial Stress Unity= 0.209 Magnification Factor= 0.984
Bending Stress Unity= 0.185 Cm= 0.85
Combined Stress Unity= 0.394 Column is Adequate
27
EC LI PS E Lucky Brand Jeans 3/6/2018
ENGINEERING Tigard, OR 97223 RVC
Overturning and Anti-Tip Calculations
Overturning Forces-
Total Weight= 737 lbs Load Case 1: Dead Load+67% Live Load
Total Lateral Force = 93 lbs
Overturning Force= 658 ft*lbs Controlling Overturning Force
Total Weight= 335 lbs Load Case 2: Dead Load + 100%Top Shelf
Total Lateral Force = 42 lbs
Overturning Force= 302 ft*lbs (Does Not Control
Tension Force per Anchor= 79 lbs Per Side of Unit
Shear Force per Anchor= 47 lbs
valent) POST INSTALLED ANCHOR BOLTS
Allowable Tension Force= 736 lbs For 2500 psi Concrete
Allowable Shear Force= 792 lbs 3/8" Diameter x 2.5" Embedment
Vertical Seismic Force= 37.3 lbs
Overstrength Factor= 2 For Anchoring to Concrete
Combined Loading= 0.216 I Floor Anchors are Adequate
Anti-Tip Track Design-
Type of Anti-Tip Device = Arm and Track
Tension per Side= 79 lbs
Capacity of Screws to Carriage= 349 lbs (2)#12 Screws Are Adequate
Anti-Tip Yield Stress= 16 ksi 6063-T5
Thickness Anti-Tip= 0.12 in
Width of Anti-Tip = 0.43 in
Section Modulus of Leg= 0.0092 in3
Allowable Stress on Leg= 16 ksi
Bending Stress on Leg= 2.77 ksi
Anti-Tip Stress Unity= 0.173 I Bending Stress OK
Section Modulus of Track= 0.090 in3
Spacing of Track A.B's= 24 in
Allowable Alumn. Stress= 16 ksi 6063-T5
Bending Stress on Track= 2.64 ksi
Track Stress Unity= 0.165 I Bending Stress OK
28
EC LI PS E Lucky Brand Jeans 3/6/2018
ENGINEERING Tigard, OR 97223 RVC
Shelf Beam Calculations
Type of Shelf Beam: Double Rivet Beam
Steel Yield Stress= 33 ksi Shelf DL= 2.5 psf
Modulus of Elast. = 29000 ksi Shelf LL= 8.00 psf
Area of Beam = 0.1681 in2
Section Modulus of Beam 0.0197 in3
Moment of Inertia of Beam = 0.0139 in4
Allowable Load per Shelf= 80 lbs
Shelf Distributed Load = 13.1 plf Distributed Load
Allowable Bending Stress= 19.8 ksi
Allowable Shear Stress= 13.2 ksi
Maximum Beam Moment= 26.3 ft-lbs Simple Span
Maximum Design Moment= 26.3 ft-lbs
Maximum Design Shear= 26.3 lbs
Beam Bending Stress= 15.99 ksi
Beam Shear Stress= 0.16 ksi
Bending Stress Unity= 0.808 Bending Stress OK
Shear Stress Unity= 0.012 Shear Stress OK
Max Allowable Deflection = 0.267 in L/180
Maximum Beam Deflection = 0.188 in Deflection OK
Shelf Beam Rivet Check:
Diameter of Rivet= 0.25 in
Post Moment Shear on Rivet= 113.0 lbs
Beam Shear on Rivet= 26.3 lbs
Resultant Shear= 116.0 lbs
Brg Capacity of Rivet= 519.8 lbs Brg Stress OK
Allowable Shear Stress= 9.6 ksi
Shear Stress on Rivet= 2.4 ksi Shear Stress OK
29
Lucky Brand Jeans 3/6/2018
E N G I NEER
EC LI E Tigard, OR 97223 RVC
E R IN G g
Wall Supported Unit Calculations
Seismic Force at Top of Units-
Average Roof Height= 20.0 ft
Height of Attachment= 10.0 ft
Shear Coeff Boundaries= Vm;,,= 0.217
Vmax= 1.156
Design Base Shear Coeff= Vt= 0.258 Adjusted For ASD
Total Weight per Unit= 653 lbs
Lateral Force at Top/Bottom = 84 lbs
Standard Stud Spacing= 16 in
Wall Connections per Unit= 3
Tek Screw Capacity= 84 lbs Tension Cap.for#10 Screw in 20ga Stud
Force Per Connection = 28 lbs Screw Capacity OK
Seismic Uplift Force on Each Shelf
Seismic Uplift on Shelves-
Vertical Seismic Component= 15.2 lbs
Vertical Dead Load per Shelf= 105.0 lbs
Connection Points per Shelf= 4.0 Each Corner
Net Uplift Load per Shelf= -47.8 lbs
Uplift Forcer per Connection = -12.0 lbs Rivet Connection OK
30
EP LI PS E Lucky Brand Jeans 3/6/2018
ENGINEERING Tigard, OR 97223 RVC
Light Gage Steel Stud Wall Framing
Stud Design Data-
Height of Wall Studs= 16.0 ft Int. Non-Brg-Worst Case Ht Assumed
Location of Point Load = 10.0 ft
Design Lateral Load= 28.1 lbs From Shelving Unit
Additional Lateral Load = 5.0 psf Interior Seismic Force
Design Axial Load = 85.3 lbs Dead Load of Wall Framing
Spacing of Studs= 16.0 in
I Studs @ 16" o.c. (Worst Case Assumed)
Width = 3.625 in rx= 1.450 in
• Depth = 1.625 in ry= 0.616 in
Thickness= 0.035 in Sx= 0.268 in3
Fy= 33 ksi lx= 0.551 in4
E= 29000 ksi Ap= 0.262 in2
K= 1.0 Unbraced Length X= 16 ft
Unbraced Length Y= 4 ft
Stud Capacity-
Buckling Stress,X= 16.32 ksi
Buckling Stress,Y= 47.14 ksi
Allowable Buckling Stress= 16.32 ksi
Nominal Axial Strength = 4277 lbs
Factor of Safety= 1.92
- Allowable Axial Load = 2228 lbs
Maximum Design Moment= 318.7 ft-lbs
Maximum Design Shear= 70.9 lbs
Allowable Bending Stress= 21.78 ksi
Actual Bending Stress= 14.27 ksi Bending Stress OK
Allowable Shear Stress= 13.20 ksi
Actual Shear Stress= 0.27 ksi Shear Stress OK
Allowable Axial Stress= 8.50 ksi
Actual Axial Stress= 0.33 ksi Axial Stress OK
Combined Stress Unity= 0.69 Combined Stress OK
31
Lucky Brand Jeans 3/6/2018
i EC1 E E Tigard, OR 97223 RVC
E N G I N E E E R R I N G g
Slab Bearing & Uplift Calculations
Slab Design Properties-
Minimum Concrete Strength = 2500 psi Assumed
Thickness of Concrete Slab= 4 in Assumed
Weight of Concrete Slab= 50 psf
Allowable Bearing Pressure= 500 psf Assumed
Bearing Loads On Post= 120 lbs Dead Load
360 lbs Live Load
165 lbs EQ Load
Uplift Loads on Post= 79 lbs Resultant Uplift
Slab Bearing Capacity-
Depth of Post on Slab= 1.5 in
Factored Bearing Load = 955 lbs
Required Bearing Area = 185.62 in2 13.62 inches per side
Critical Section = 4.06 in For Bending
Soil Pressure on Crit.Section = 740.9 plf Along Critical Length
Section Modulus= 32.0 in3 Plain Concrete per Foot
Shear Area = 22 in
Conc.Shear Stress= 10.9 psi
Allowable Shear Stress= 73.2 psi Shear Stress OK
Conc. Bending Stress= 15.9 psi
Allowable Bending Stress= 137.5 psi Bending Stress OK
Slab Uplift Capacity-
Required Area to Resist Uplift= 2.64 ft2
Length of Slab Req'd = 0.66 ft Assume Full Shelf Width x Req'd Length
Worst Case Length of Slab= 4.00 ft Maximum of Width or Length Req'd
Distance to Anchor Bolt= 2.00 ft
Shear Force on 1ft Strip= 140.0 lbs
Allowable Shear Force= 1760.0 lbs Shear OK
Bending Moment on 1ft Strip= 140.0 ft-lbs
Allowable Bending Moment= 366.7 ft-lbs Bending OK
32
Dal I 141111111111111
www.bitti.us Profis Anchor 2.7.3
Company: Eclipse Engineering, Inc Page: 1
Specifier: Robert VanCamp Project:
Address; Sub-Project I Pos.No,:
Phone I Fax: I Date: 5/31/2017
E-Mail:
Specifiers comments:
Input data
Anchor type and diameter: KWIK HUS-EZ(KH-EZ)3/8(2 1/2) p** A,tor
Effective embedment depth: be,a.,= 1.860 in.,hrj 2.500 in.
Material; Carbon Steel
• Evaluation Service Report: ESR-3027
Issued I Valid: 2/1/2016 11211/2017
Proof: Design method ACI 318-14/Mech.
• Stand-off installation: -(Recommended plate thickness:not calculated)
Profile: no profile
Base material: cracked concrete,2500, -=2500 psi;h 4.000 iri.
Installation: hammer drilled hole,Installation condition:Dry
Reinforcement: tension:condition B, shear:condition B;no supplemental splitting reinforcement present
edge reinforcement:none or c No.4 bar
Seismic loads(cat.C,D,E,or F) Tension load:yes(17.2.3.4.3(b))
Shear load:yes(17.2.3.5.3(a))
Geometry Dn.]&Loading[lb,in.113]
Z
NOTE: SHEAR AND TENSION FORCES
ARE PROVIDED TO CALCULATE
ANCHOR CAPACITY
-REFERENCE THE CALCULATIONS
FOR ACTUAL V & T AND UNITY CHECK
St'ut
100
' zt'
Ns?
116,
Input data and results must he checked for agreement with the existmg conditions and for plausibility,
PROM Anchor(c)21303-2939 Kiln AG,FL-9494 Scheari kfitti is a registered Trademark of Kin AG,Schoen
4
I .
EZEM3E1
www.tiiicus Profis Anchor 2.7.3
Company: Eclipse Engineering, Inc Page: 2
Specifier: Robert VanCamp Project:
Address: Sub-Project I Pos.No.:
Phone I Fax: I Date: 5/31/2017
E-Mail:
2 Proof I Utilization (Governing Cases)
Design values(Pb] Utilization
Loading Proof Load Capacity riN!!iv 1%1 Status
Tension Concrete Breakout Strength 300 1051 29/- OK
Shear Pryout Strength 100 7t5o9 -/7 OK
Loading PN Pv ç Utilization ISNN(%) Status
Combined tension and shear loads 0,285 0.066 5/3 14 OK
Convert to ASD =
3 Warnings Multiply by 0.7
• Please consider all details and hints/warnings given in the detailed report!
Fastening meets the design criteria!
4 Remarks; Your Cooperation Duties
• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles,formulas and
security regulations in accordance with Hi'Ws technical directions and operating,mounting and assembly instructions,etc,,that must be strictly
complied with by the user. All figures contained therein are average figures,and therefore use-specific tests are to be conducted prior to using
the relevant HiIli product, The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore,you bear the sole responsibility for the absence of errors,the completeness and the relevance of the data to be put in by you.
Moreover,you bear sole responsibility for having the results of the calculation checked and cleared by an expert,particularly with regard to
compliance with applicable norms and permits,prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors,the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular,you must arrange for the
regular backup of programs and data and,if applicable,carry out the updates of the Software offered by Hilti on a regular basis.II you do not use
the AutoUpdate function of the Software,you must ensure that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the HiIti Website. Hilt,will not be liable for consequences,such as the recovery of lost or damaged data or
programs,arising from a culpable breach of duty by you.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor I c)2003-2009 Hai AG,FL--9454 Scheer, KW rs a registered Trademark of Heti AG.Schaan
i