Description Compact Analog Addressable
The Gamewell-FCI, 7100 Series fire alarm control panel is Fire Alarm Control Panel
a multi processor-based, analog addressable system. The
control panel is a compact, yet expandable, platform.
Intended for commercial, industrial and institutional instal-
lations, the 7100 Series is ideal for life safety and property
protection fire alarm applications.
The basic 7100 Series control panel provides one analogWaro
addressable Signaling Line Circuit (SLC), whether sups
ports up to 99 analog addressable sensors, as well as sup-
porting up to 98 addressable monitor modules and/or
control points, totaling 197 addresses. The 7100 uses an
advanced protocol that ensures an almost instant
response to events while at the same time suppressing
nuisance alarms.
The system may be programmed with the CAMWorksTm 7100 Series
programming utility tool or configured through a compre- Features
hensive set of intuitive, secure password-protected, front- • Listed under ANSI/UL®Standard 864 9th Edition.
panel programming options. This important feature allows • IBC Seismic Certified.
the system to quickly adapt to any future requirements due • 120 or 240 VAC (optional)input line voltage.
to changes in occupancies, building remodels, or other • Front panel programming with day/night sensitivity
contingencies. adjustments.
• 80-character alpha-numeric display.
The sophisticated circuitry and powerful analog software • One Style 4(Class"B")signaling line circuit. Style 6
enables the 7100 Series fire alarm control panel to read (Class"A")with optional CAOM Module.
the specific sensitivity level of each sensor and compen- • Two Style Y(Class"B")regulated notification appliance
sate for changes due to age, dust accumulation or other circuits rated for 1.5 amp each. Style Z(Class"A")with
environmental factors. The 7100 incorporates the option®I CAOM Module.
•
Gamewell-FCI Listed Integrated Sensitivity Testing (LIST)
FM/UL®Listed for Pre-action/Deluge with optional
which meets NFPA 72 sensitivity testing and maintenance MCOM Module.
• Periodic trouble reminder.
requirements. The LIST testing allows substantial savings • Individual sensor drift compensation.
in both maintenance and service while eliminating nui- • Dual-stage maintenance alerts("dirty"and"very dirty").
sance alarms. • Multilevel sensor sensitivity adjustments(front panel
programmable).
The Model 7100-1D features an integral Digital Alarm • Alarm verification per individual sensor.
Communicator Transmitter (DACT) with all popular trans- • Positive alarm sequence for sensors or monitor
mission formats and a 16-digit telephone number field. It is modules.
8-digit Carrier Information Code (CIC) compliant and also continued on the next page
prevents "dialer-runaway" in the event of intermittent sys-
tem faults. The 7100-1D is UL Listed for Remote Station,
Proprietary, and Central Station fire alarm systems. It SIGNALING '- -'
1410E-' A
allows ample space for wiring and room for batteries up to L
12 NH capacity.
MEA
LISTED APPROVED Approved 'ffi m . E VM=
CAMWorksTM is a trademark of Honeywell International,Inc. S1869 3003549 FDNY 6911-1703:0116(Non-High Rise)Reference Certificate
Microsoft®Word®is a registered trademark of Microsoft®Corporation. COA its 307-99-E 6911-1703:0118(High Rise) of Compliance
UL®is a registered trademark of Underwriter's Laboratories Inc. 307-99-E Vol.II 7300-1103:0106(LCD-7100) VMA-45894-02C
(Revision 1)
ISO 9001 GAMEWELL-FCI
am`"°T`"` 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118
Specifications are for information only,are not intended for installation purposes,and are subject to change without notice.No responsibility is assumed by Gamewell-FCI for their use.
2015 by Honeywell International Inc. All rights reserved. www.gam@Well-fct.com 9020-0466 Rev.N page 1 of 3
Optional Accessories Features (Continued)
LCD-7100 • Four levels of system access using six digit passwords
The LCD-7100 remote serial display offers an 80-character with up to five user passwords per Level.
alphanumeric readout for the remote display of all system • Duplicate and extra address indications.
events. It duplicates all the information on the 7100 Series • March time(60 or 120 BPM)/temporal pattern/coded
panel display and provides key switch protected functions fours/California Code/user-defined zone coding.
such as System Reset, Alarm Acknowledge, Trouble • Cross zoning.
Acknowledge, Signal Silence, and Drill Test. • System configuration programming and 280 event log
LEDs on the LCD 7100 indicate Alarm, Supervisory, Sys- stored in non-volatile memory.
tem Trouble, Power Fault, Systems Silenced, NAC#1, and • Upload/downloadFarestart withsequential ofpanelrestartfigdelay.
• of configuration between panel
NAC#2 Silenced conditions. and CAMWorks program (password protected feature).
The LCD-7100 can be surface or semi-flush mounted on a • Up to 64, 7100 panels in the E3 Broadband network
standard four-gang electrical box. It can be installed up to with an optional INI-7100 Module.
3,000 feet(914.4 m)from the main control panel.The 7100
Series fire alarm control panel supports up to five remote
LCD-7100 annunciators using one pair of twisted, non
shielded 18 AWG min. wire or serial communication and Specifications
uses another pair of 16 AWG min.for operating voltage.
(For additional information, refer to the LCD-7100 data Primary Input Power 120 VAC, 50/60 Hz @ 2.0 amps.
sheet, Part Number:9020-0486).
or 240 VAC,50/60 Hz @ 1.0 amp
Output Power 3.335 amps. @ 24 VDC(total)
RAN-7100 Non-resettable Power: 1.0 amp max.
The RAN-7100 maintains the same character display as Resettable Power: 1.0 amp max.
the 7100 Series. The RAN-7100 is mounted in a RAN2-BB 1.0 amp max. from both power
backbox for surface or flush mounting retrofits. circuits
(For additional information, refer to the Gamewell Retrofit Two Notification
Kits Data Sheet, P/N: 9020-60678). Appliance Circuits: 1.5 amp each @ 24 VDC
Current: Supervisory Alarm
CAOM
The Class"A"Optional Module(CAOM)allows Style Y and 7100-1D(One SLC) 0.065 amp 0.085 amp
Z(Class"B"and"A")operation for both Notification Appli- (One SLC w/DACT) 0.075 amp 0.095 amp
ance Circuits and allows Style 4 and 6(Class"B"and"A") LCD-7100 0.050 amp 0.075 amp
for the Signaling Line Circuit. It also provides a disconnect INI-7100-UTP,-FO 0.040 amp 0.040 amp
switch for the signaling line circuit and a common discon- Operating
nect switch for both notification appliance circuits. Temperature: 32°- 120° F(0°-49°C)
MCOM Relative Humidity: 93%(non-condensing)
The Municipal Connection Option Module(MCOM)pro- Battery Charger
vides three choices of outputs. It can be configured as a Capacity: 31 A/H (Cabinet accommodates
Municipal Circuit(City Box)output. It may also be set to 12 A/H size batteries)
Alarmserve as a Reverse Polarity output with a nominal voltage Relay ont Trouble
Relay Contacts: Form "C", 2 amps. @ 24 VDC
output of 24 VDC at 0.012 amp maximum alarm and (resistive)
supervisory current. The MCOM's third option provides a
releasing solenoid output rated at:
• 24 VDC nominal voltage.
• 0.005 amp supervisory current.
• 0.710 amp maximum alarm current.
• 2 ohms maximum line resistance.
PTRM
The Printer Transient Module(PTRM)provides RS-232
Isolator/Transient protection for the 7100's RS-232 port
(BSM connector J2). It is used in conjunction with a serial
printer applied to the RS-232 port for permanent record
keeping.
INI-7100
The Intelligent Network Interface Module allows the 7100
Series fire alarm control panel to become the platform of a
peer-to-peer,token ring, self-regenerative network corn-
prised of up to 64, 7100 panels.
GAMEWELL-FCI
12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118
9020-0466 Rev.N page 2 of 3 www.gamewell-fci.com
4
Ordering Information Ordering Information (Continued)
Systems Replacement Parts
Part Number Description Part Number Description
7100-1-PNL 7100 Addressable FACP, 1 SLC mounted BSM-7100-1 Replacement board for 7100-1
in the 7100-CAB enclosure, red BSM-7100-1D Replacement board for 7100-1D
7100-1 D-PNL 7100 Addressable FACP w/DACT, One BSM-7100-2 Replacement board for 7100-2
SLC mounted in 7100 CAB enclosure, BSM-7100-2D Replacement board for 7100-2D
red Seismic Battery Bracket Kits
Basic Kits 90516 7100-Slim 7 A/H Seismic Battery
1100-1313 Basic System Kit, 2 SLC, 240 VAC Bracket kit
Optional Modules E3 B-Slim 7 A/H Seismic Battery
LCD-7100 Remote Serial Annunciator, LCD Display Bracket Kit
90517 7100-Slim 12 A/H Seismic Battery
(80 character).
Dimensions: 4.25" H x 8.25"W x 1.90" Bracket Kit E3 B-Slim 12 A/H Seismic
(43 H x 37 W x 7.7 D cm) Battery Bracket Kit
90518 NetSOLO 7100 7 A/H Seismic Battery
RAN-7100 Remote Series Annunciator, LCD Display
Bracket Kit
(80 character).
Dimensions: 10"W x 5 1/4" H x 2 7/16" D For additional information on the Seismic Battery Brackets,
refer to the following documents:
(25 1/4 W x 13113 H x 6 9/10 D cm)
CAOM Class A Option Combination Module with •
Seismic Battery Bracket Installation Guide, P/N: 53839
disconnect switches for both signaling • E3 Series Cabinets Data Sheet, P/N: 9020-0649
line circuits and notification appliance
circuits.
MCOM Municipal Connection Option Module for
local energy city box reverse polarity sig-
. naling, or releasing solenoid.
PTRM Printer Transient Module.
INI-7100-FO Intelligent Network Interface Module,
Fiber-Optic.
INI-7100-UTP Intelligent Network Interface Module,
Unshielded, Twisted-Pair.
GAMEWELL-FCI
12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118
www.gamewell-fci.com 9020-0466 Rev.N page 3 of 3