Report (99) TFP172 Page 2 of 4 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector, can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON if 6* _.- .•1/7-10M`rt;�:\ irirrir,�—% 5 /c! 7/16" : i 11 4 I MAKE-IN L !__ (50,8'mm) I�� _'■i I, lowi t a r 2" 1-3/8" 0 �. t (50,8 mm) (34,9 mm) �_' 3 • - -- ------. WRENCH FLATS _ o� OA..rn 1/2" NPT** DEFLECTOR* -- 2-7/8"(73,0 mm)DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE Installation Step 2. With pipe-thread sealant e, applied to the pipe threads, hand- The TYCO Series TY-FRB,5.6 K-factor, tighten the sprinkler into the sprinkler WRENCH RECESS Upright (TY313) and Pendent (TY323) fitting. (USE ONLY Sprinklers must be installed in accor- Step 3. Tighten the sprinkler into the END"A") dance with this section. sprinkler fitting using only the W-Type ter General Instructions 6 Sprinkler Wrench(Figure 2).With ref- FIGURE 2 Do not install any bulb-type sprinkler erence to Figure 1,apply the W-Type 6 W-TYPE 6 if the bulb is cracked or there is a loss Sprinkler Wrench to the wrench flats. SPRINKLER WRENCH of liquid from the bulb. With the sprin- Torque sprinklers 7 to 14 ft.-lbs.(9,5 to kier held horizontally,a small air bubble 19,0 Nm). should be present.The diameter of the Recessed Pendent Sprinklers WRENCH air bubble is approximately 1/16 inch The Series TY-FRB Recessed Pendent RECESS (1,6 mm)for the 135°F(57°C)and 3/32 Sprinklers must be installed in accor- inch(2,4 mm)for the 286°F(141°C)tern- dance with the following instructions. �� perature ratings. �1 Step A. After installing the Style 15 0A leak-tight 1/2 inch NPT sprinkler or Style 20 Mounting Plate over the joint should be obtained by applying a sprinkler threads,and with pipe-thread I_ minimum to maximum torque of 7 to 14 sealant applied to the pipe threads, ft. lbs. (9,5 to 19,0 Nm). Higher levels hand-tighten the sprinkler into the of torque can distort the sprinkler Inlet sprinkler fitting. p with consequent leakage or impairment PUSH WRENCH of the sprinkler. Step B. Tighten the sprinkler into the IN TO ENSURE Do not attempt to compensate for sprinkler fitting using only the W-Type ENGAGEMENT p p 7 Recessed Sprinkler Wrench (Figure WITH SPRINKLERGMENinsufficient adjustment in the Escutch- 3).With reference to Figure 1,apply the WRENCHINGTAREA eon Plate by under-or over-tightening W-Type 7 Recessed Sprinkler Wrench the sprinkler. Re-adjust the position of to the sprinkler wrench flats. Torque FIGURE 3 the sprinkler fitting to suit. sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 W--TYPE 7 RECESSED Upright and Pendent Sprinklers Nm). SPRINKLER WRENCH The Series TY-FRB Upright and Step C. After ceiling installation and Pendent Sprinklers must be installed finishing, slide on the Style 15 or Style in accordance with the following 20 Closure over the Series TY-FRB instructions. Sprinkler and push the Closure over the Step 1.Install Pendent sprinklers in the Mounting Plate until its flange comes in pendent position. Install upright sprin- contact with the ceiling. klers in the upright position. TFP172 Page 3 of 4 Care and _ 2-7/8"DIA. (73,0 mm) Maintenance 2-1/4"DIA. _ — The TYCO Series TY-FRB,5.6 K-factor, FACE OF (57,2 mm) Upright (TY313) and Pendent (TY323) SPRINKLER Sprinklers must be maintained and ser- FITTING 5/8"(15,9 mm) viced in accordance with this section. + \ _ u FLUSH Before closing a fire protection system 3/8±5/16" —� I main control valve for maintenance (9,5±7,9 mm) 11 Lit '/ / + ' work on the fire protection system } / ��-��--- that it controls, obtain permission to MOUNTING 1141/8" shut down the affected fire protection (3,2 mm) systems from the proper authorities SURFACE and notify all personnel who may be CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) affected by this action. TY-FRB PLATE 3/4"(19,1 mm) Absence of the outer piece of an FIGURE 4 escutcheon,eawhichc isn usedesprinklerto cover SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) a clearance hole, can delay operation in a fire situation. WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 RECESSED ESCUTCHEON The owner must assure that the sprin- klers are not used for hanging any objects and that the sprinklers are only 2-7/8"DIA. cleaned by means of gently dusting (73,0 mm) with a feather duster; otherwise, non- FACE OF operation in the event of a fire or inad- SPRINKLER 2-1/4"DIA. vertent operation may result. FITTING (57,2 mm) Sprinklers which are found to be 5/16±1/4" 1/2"(12,7 mm) leaking or exhibiting visible signs of (7,9±6,4 mm) corrosion must be replaced. + _ FLUSH Automatic sprinklers must never be T —1 painted, plated, coated, or other- � _a% wise altered after leaving the factory. f / �j� " a Modified sprinklers must be replaced. MOUNTING (3,21/81.: 3,2 1/8mm)_I I Sprinklers that have been exposed to SURFACE corrosive products of combustion, but have not operated,should be replaced J if they cannot be completely cleaned CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) by wiping the sprinkler with a cloth or TY-FRB PLATE 7/8"(22,2 mm) by brushing it with a soft bristle brush. FIGURE 5 Care must be exercised to avoid SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) damage to the sprinklers before, WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 during, and after installation. Sprin- RECESSED ESCUTCHEON kiers damaged by dropping, striking, wrench twist/slippage,or the like,mustRecessed Escutcheon be replaced. Also, replace any sprin- Limited Specify: Style 15 Recessed Escutch- kler that has a cracked bulb or that has yarrant eon with(specify*")finish,P/N(specify*) lost liquid from its bulb. (Ref. Installa- y Specify: Style 20 Recessed Escutch- tion Section.) For warranty terms and conditions,visit eon with(specify*)finish,P/N(specify*) The owner is responsible for the www.tyco-fire.com. *Refer to Technical Data Sheet TFP770 inspection,testing,and maintenance of their fire protection system and devices Sprinkler Wrench in compliance with this document, as Ordering Specify: W-Type 6 Sprinkler Wrench, well as with the applicable standards Procedure P/N 56-000-6-387 of the National Fire Protection Asso- Specify: W-Type 7 Sprinkler Wrench, ciation (e.g., NFPA 25), in addition to Contact your local distributor for avail- P/N 56-850-4-001 the standards of any other authorities ability.When placing an order, indicate having jurisdiction.Contact the install- the full product name and Part Number ing contractor or product manufacturer (p/N). with any questions. Automatic sprinkler systems are rec- Sprinkler Assemblies with NPT ommended to be inspected, tested, Specify:SConnectionsTY-FRB or and maintained by a qualified Inspec- ndSeriesspy) Upright N tion Service in accordance with local Pendent (specify) Sprinkler, SIN (specify), K=5.6, Quick Response, requirements and/or national codes. (specify) temperature rating, (specify) finish, P/N(specify,refer to Table A). • TFPi72 Page 4 of 4 SPRINKLER FINISH(See Note 7) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME POLYESTERb FACTOR COLOR BRASS PLATED 135°F(57°C) Orange UPRIGHT 155°F(68°C) Red (TY313) and 175°F(79°C) Yellow 1,2,3,4,5,6 PENDENT 200°F(93°C) Green 5.6 (TY323) 1/2"NPT 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT 1,2,3,4 (TY313) 175°F(79°C) Yellow Figures 4a and 5b 200°F(93°C) Green Notes: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. VdS Approved(For details,contact TYCO Fire Protective Products,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-54-428-3377.) 6. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers. 7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. a. Installed with Style 15(1/2"NPT)5/8"Total Adjustment Recessed Escutcheon,as applicable. b. Installed with Style 20(1/2"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable. c.Frame and Deflector only.Listings and approvals apply to color(Special Order). TABLE A LABORATORY LISTINGS AND APPROVALS FOR 5.6 K-FACTOR SPRINKLERS P/N* 77 - XXX - X - XXX SIN SPRINKLER TEMPERATURE FINISH RATINGS 370 5.6K UPRIGHT(1/2-NPT) TY313 1 NATURAL BRASS 135 135°F(57°C) 371 5.6K PENDENT(1/2"NPT) TY323 3 PURE WHITE(RAL9010)** 155 155°F(68°C) POLYESTER *Use suffix 1"for ISO 7-1 connection; 4 175 175°FSIGNAL WHITE(RAL9003) for example,77-370-4-175-I POLYESTER (79°C) 5 JET BLACK(RAL9005) 200 200°F(93°C) POLYESTER 9 CHROME PLATED 286 286°F(141°C) **Eastern Hemisphere sales only TABLE B SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION GLOBAL HEADQUARTERS 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright®2017 Tyco Fire Products,LP. All rights reserved. VICO TEFLON is a registered trademark of DuPont "f Fire Protection Products