Report (99) TFP172
Page 2 of 4
Components: *Temperature rating is ** Pipe thread connections per ISO 7-1
1 - Frame 4 - Bulb indicated on Deflector, can be provided on special request.
2 - Button 5 - Compression STYLE 15 or 20
3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED
Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON
if
6* _.-
.•1/7-10M`rt;�:\ irirrir,�—%
5 /c! 7/16" : i
11
4 I MAKE-IN L !__ (50,8'mm) I�� _'■i I,
lowi
t a r 2" 1-3/8" 0
�. t (50,8 mm) (34,9 mm) �_'
3 • - -- ------. WRENCH
FLATS
_ o� OA..rn
1/2" NPT** DEFLECTOR* -- 2-7/8"(73,0 mm)DIA.
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
Installation Step 2. With pipe-thread sealant
e, applied to the pipe threads, hand-
The TYCO Series TY-FRB,5.6 K-factor, tighten the sprinkler into the sprinkler
WRENCH RECESS Upright (TY313) and Pendent (TY323) fitting.
(USE ONLY Sprinklers must be installed in accor- Step 3. Tighten the sprinkler into the
END"A") dance with this section. sprinkler fitting using only the W-Type
ter General Instructions 6 Sprinkler Wrench(Figure 2).With ref-
FIGURE 2 Do not install any bulb-type sprinkler erence to Figure 1,apply the W-Type 6
W-TYPE 6 if the bulb is cracked or there is a loss Sprinkler Wrench to the wrench flats.
SPRINKLER WRENCH of liquid from the bulb. With the sprin- Torque sprinklers 7 to 14 ft.-lbs.(9,5 to
kier held horizontally,a small air bubble 19,0 Nm).
should be present.The diameter of the Recessed Pendent Sprinklers
WRENCH air bubble is approximately 1/16 inch The Series TY-FRB Recessed Pendent
RECESS (1,6 mm)for the 135°F(57°C)and 3/32 Sprinklers must be installed in accor-
inch(2,4 mm)for the 286°F(141°C)tern- dance with the following instructions.
��
perature ratings.
�1 Step A. After installing the Style 15
0A leak-tight 1/2 inch NPT sprinkler or Style 20 Mounting Plate over the
joint should be obtained by applying a sprinkler threads,and with pipe-thread
I_ minimum to maximum torque of 7 to 14 sealant applied to the pipe threads,
ft. lbs. (9,5 to 19,0 Nm). Higher levels hand-tighten the sprinkler into the
of torque can distort the sprinkler Inlet sprinkler fitting. p
with consequent leakage or impairment
PUSH WRENCH of the sprinkler. Step B. Tighten the sprinkler into the
IN TO ENSURE Do not attempt to compensate for sprinkler fitting using only the W-Type
ENGAGEMENT p p 7 Recessed Sprinkler Wrench (Figure
WITH SPRINKLERGMENinsufficient adjustment in the Escutch- 3).With reference to Figure 1,apply the
WRENCHINGTAREA eon Plate by under-or over-tightening W-Type 7 Recessed Sprinkler Wrench
the sprinkler. Re-adjust the position of to the sprinkler wrench flats. Torque
FIGURE 3 the sprinkler fitting to suit. sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0
W--TYPE 7 RECESSED Upright and Pendent Sprinklers Nm).
SPRINKLER WRENCH The Series TY-FRB Upright and
Step C. After ceiling installation and
Pendent Sprinklers must be installed finishing, slide on the Style 15 or Style
in accordance with the following 20 Closure over the Series TY-FRB
instructions. Sprinkler and push the Closure over the
Step 1.Install Pendent sprinklers in the Mounting Plate until its flange comes in
pendent position. Install upright sprin- contact with the ceiling.
klers in the upright position.
TFP172
Page 3 of 4
Care and _ 2-7/8"DIA.
(73,0 mm)
Maintenance 2-1/4"DIA. _
—
The TYCO Series TY-FRB,5.6 K-factor, FACE OF (57,2 mm)
Upright (TY313) and Pendent (TY323) SPRINKLER
Sprinklers must be maintained and ser- FITTING 5/8"(15,9 mm)
viced in accordance with this section. + \ _ u FLUSH
Before closing a fire protection system 3/8±5/16" —� I
main control valve for maintenance (9,5±7,9 mm) 11 Lit '/ / + '
work on the fire protection system } / ��-��---
that it controls, obtain permission to MOUNTING 1141/8"
shut down the affected fire protection (3,2 mm)
systems from the proper authorities SURFACE
and notify all personnel who may be CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm)
affected by this action. TY-FRB PLATE 3/4"(19,1 mm)
Absence of the outer piece of an FIGURE 4
escutcheon,eawhichc isn usedesprinklerto cover SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323)
a clearance hole, can delay
operation in a fire situation. WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only 2-7/8"DIA.
cleaned by means of gently dusting (73,0 mm)
with a feather duster; otherwise, non- FACE OF
operation in the event of a fire or inad- SPRINKLER 2-1/4"DIA.
vertent operation may result. FITTING (57,2 mm)
Sprinklers which are found to be 5/16±1/4" 1/2"(12,7 mm)
leaking or exhibiting visible signs of (7,9±6,4 mm)
corrosion must be replaced. + _ FLUSH
Automatic sprinklers must never be T —1
painted, plated, coated, or other- � _a%
wise altered after leaving the factory. f / �j� "
a
Modified sprinklers must be replaced. MOUNTING (3,21/81.:
3,2 1/8mm)_I I
Sprinklers that have been exposed to SURFACE
corrosive products of combustion, but
have not operated,should be replaced J
if they cannot be completely cleaned CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm)
by wiping the sprinkler with a cloth or TY-FRB PLATE 7/8"(22,2 mm)
by brushing it with a soft bristle brush. FIGURE 5
Care must be exercised to avoid SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323)
damage to the sprinklers before, WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
during, and after installation. Sprin- RECESSED ESCUTCHEON
kiers damaged by dropping, striking,
wrench twist/slippage,or the like,mustRecessed Escutcheon
be replaced. Also, replace any sprin- Limited Specify: Style 15 Recessed Escutch-
kler that has a cracked bulb or that has yarrant eon with(specify*")finish,P/N(specify*)
lost liquid from its bulb. (Ref. Installa- y Specify: Style 20 Recessed Escutch-
tion Section.) For warranty terms and conditions,visit eon with(specify*)finish,P/N(specify*)
The owner is responsible for the www.tyco-fire.com. *Refer to Technical Data Sheet TFP770
inspection,testing,and maintenance of
their fire protection system and devices Sprinkler Wrench
in compliance with this document, as Ordering Specify: W-Type 6 Sprinkler Wrench,
well as with the applicable standards Procedure P/N 56-000-6-387
of the National Fire Protection Asso- Specify: W-Type 7 Sprinkler Wrench,
ciation (e.g., NFPA 25), in addition to Contact your local distributor for avail- P/N 56-850-4-001
the standards of any other authorities ability.When placing an order, indicate
having jurisdiction.Contact the install- the full product name and Part Number
ing contractor or product manufacturer (p/N).
with any questions.
Automatic sprinkler systems are rec- Sprinkler Assemblies with NPT
ommended to be inspected, tested, Specify:SConnectionsTY-FRB
or
and maintained by a qualified Inspec- ndSeriesspy) Upright N
tion Service in accordance with local Pendent (specify) Sprinkler, SIN
(specify), K=5.6, Quick Response,
requirements and/or national codes. (specify) temperature rating, (specify)
finish, P/N(specify,refer to Table A).
•
TFPi72
Page 4 of 4
SPRINKLER FINISH(See Note 7)
K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME POLYESTERb
FACTOR COLOR BRASS PLATED
135°F(57°C) Orange
UPRIGHT 155°F(68°C) Red
(TY313)
and 175°F(79°C) Yellow 1,2,3,4,5,6
PENDENT 200°F(93°C) Green
5.6 (TY323)
1/2"NPT 286°F(141°C) Blue
135°F(57°C) Orange
RECESSED 155°F(68°C) Red
PENDENT 1,2,3,4
(TY313) 175°F(79°C) Yellow
Figures 4a and 5b
200°F(93°C) Green
Notes:
1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers.
4. Approved by the City of New York under MEA 354-01-E.
5. VdS Approved(For details,contact TYCO Fire Protective Products,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-54-428-3377.)
6. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.
a. Installed with Style 15(1/2"NPT)5/8"Total Adjustment Recessed Escutcheon,as applicable.
b. Installed with Style 20(1/2"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable.
c.Frame and Deflector only.Listings and approvals apply to color(Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
5.6 K-FACTOR SPRINKLERS
P/N* 77 - XXX - X - XXX
SIN SPRINKLER TEMPERATURE
FINISH RATINGS
370 5.6K UPRIGHT(1/2-NPT) TY313 1 NATURAL BRASS 135 135°F(57°C)
371 5.6K PENDENT(1/2"NPT) TY323 3 PURE WHITE(RAL9010)** 155 155°F(68°C)
POLYESTER
*Use suffix 1"for ISO 7-1 connection; 4 175 175°FSIGNAL WHITE(RAL9003)
for example,77-370-4-175-I POLYESTER (79°C)
5 JET BLACK(RAL9005) 200 200°F(93°C)
POLYESTER
9 CHROME PLATED 286 286°F(141°C)
**Eastern Hemisphere sales only
TABLE B
SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
GLOBAL HEADQUARTERS 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700
Copyright®2017 Tyco Fire Products,LP. All rights reserved. VICO
TEFLON is a registered trademark of DuPont "f
Fire Protection Products