Loading...
Specifications (38) C'kk,e Tol-Brace Seismic Calculations DELTA FIRE Project Address: BURNHAM ASH APTS 14795 SW 72ND AVE PORTLAND OR 97224 eilt ttlIDLCO 12850&12790 SW Ash AVE 503 620 4020 Tgard OR 97223 Job*15-5481 Calculations based on 2013 NFPA Pamphlet#13 Brace Information Tolco Brace Components Maximum Spacing 77'0"(23A7 m) Tolco Component Fig.Number Adjusted Load Maximum Brace Length 0"(2•13 m) FfgAL Clamp 1425 lbs(646 kg) Bracing Material r Sch.40 Fig,980 Universal Swivel 1955 lbs(887 kg) *Calculation Eased on CONCENTRIC Loading Angle from Vertical 45*Min.__ - *Please Note,These calculators are for Toren components only.Use of any other components nods these calculators and the listing of the assembly. Least Rad.of Gyration 0.42"(11 mm) Assembly Detail UR Value 200 TOLco 9: — Max Horizontal Load 1310 lbs(594 kg) UNIVERSAL SWAY BRACE ATTACHMENT eller —A Force Factor(Cp) 0.5 SiEkt.PIPE /4F LATERAL BRACE Fastener Information Fastener Orientation NEPA Type B TOLCO FIG.4C PIPE CLAMP FOR'N___ SWAY BRACING I S Maximum Load 525 lbs(238 kg) o ) Diameter Length 5-1/2in„ _ Type 1„N-Screw Brace Identification on Plans Longitudinal steel Orientation of Brace Longitudinal Braced Pipe:4"Sch.10 Steel Pipe Load Information Size and Type of Pipe Total Length Total Calculated Load SCril 0 Steel Pipe(101.6 mm) pilo, 77ft(23,5 m) 454 lbs(206 kg) ai &MOPE 010143014 V.).110164, EVINter 6/14 Percentage added for Fittings and SpnnIders 15% 68 lbs(30.84 kg) Total Adjusted Load of all pipe within Zone of Influence 522 lbs(237 kg) fTol-Brace Version 71 Tol-Brace Seismic Calculations DELTA FIRE Project Address: BURNHAM ASH APTS 14795 SW 72ND AVE 12850&127x0 SW Ash AVE PORTLAND OR 97224 U-Lh* eTOLCD 503 620 4020 TigardOR 97223_ Job 8 15-54$1 Calculations based on 2013 NFPA Pamphlet 013 Brace Information Tolco Brace Components Maximum Spacing 20'0"(6,1 m) Tolco Component Fig.Number Adjusted Load Maximum Brace Length 7 p" 2.13 m) _..._ Fig.4 Clamp 377=bs(171 kg) Bracing Material 1"Sch.40 Fig,980 Universal Swivel 2395 lbs(1036 kg) Angle from Vertical 60°Min, *Calculation Based on CONCENTRIC Loading __...�®__.. *Please Note:These calculations are for To co components only.Use of any �r42.� other components viceds these calculations and the tilting of the assembly. Least Rad.of Gyration (11 mm) UR Value 200 Assembly Detail _ TOLCO FIG,98 Max Horizontal Load 1604 lbs(7260 UJNIVFRSAL.SWAY BRACE ATTACHMENT TYE. Force Factor(Cp) 0.5 STEEL PIPE • LATERAL BRACE Fastener Information Fastener Orientation NFPA C TOLCO FIG,4A 9/0 PIPE CLAMP FOR —4, Maximum Load4i SWAY BRACING 380 lbs(172 kg) Diameter y 10 Length 4-1/tin. Type LaterScrew Brace Identification on Plans LATERAL CPVC Orientation of Brace Lateral Braced Pipe;3"CPVC Load Information Size and Type of Pipe Total Length Total Calculated Load 3"CPVC(76.2 mm) 20ft(6.1 m) 48 lbs(22 kg) 1.25"CPVC(31.75 mm) 250ft(76.2 m) 135 lbs(61 kg) 1"CPVC(25.4 mm) ° A4. 100ft(30 5 m) 34 lbs(15 kg) SWOPE OREGON 144 Y1E C. bikes; 614 Percentage added for Fittings and Sprinklers 15% 33 lbs(14.97 kg) Total Adjusted Load of all pipe within Zone of Influence )249 lbs(113 kg) Mil-Brace Version 71 Tol-Brace Seismic Calculations DELTA FIRE Project Address: BURNHAM ASH APTS 14795 SW 72ND AVE PORTLAND OR 97224 1 1 . -. ' 13-Line ItTOLCO 12850&12790 SW Ash AVE 503 620 4020 Tigard OR 97223 Job*15-5481 Calculations based on 2013 NFPA Pamphlet#13 Brace Information Tolco Brace Components Maximum Spacing 40'0"(12.19 m) Tolco Component Fig.Number Adjusted Load Maximum Brace Length 7 0"(2.13 m) cig,1001 Clamp 1425 lbs(646 kg) Bracing Material r Sch.40 Fig,9S0 Universal Swivel 1955 lbs(887 kg) *Calculation Based on CONCENTRIC Loading Angle from Vertical 45'Min, "Please Note.These calculations are for Toco components on y.Ilse of any 0.42"(11 m m) other components no ds these calculations and the listing of the assembly. Least Rad.of Gyration Assembly Detail LIR Value 200 TOLCO FIG.984 Max Horizontal Load 1310 tbs(594 1:9) UNIVERSAL SWAY BRACE ATTACHMENT 464 force Factor(Cp) 05 STEEL PIPE LATERAL BRACE Fastener Information Fastener Orientation NFPA Type E t Maximum Load 550 lbs(249 Ic9) Diameter 51TOLCO FIG. 1001 *, 8in, FAST CLAMP 4IM. Length 5-1/2in. Type Lag-Screw _I Brace Identification on Plans Lateral Steel Pipe Orientation of Brace Lateral Braced Pipe:4"Sch.10 Steel Pipe Load Information t Size and lype of Pipe Total Length Total Calculated Load 4"Sch.10 Steel Pipe(101.6 mm) 408(12.2 m) 236 lbs(10714 2"Sch.40 Steel Pipe(50.8 mm) 1811(5.5 m) 46 lbs(21 kg) 1,5"SchA0 Steel Pipe(38.1 ram) ....to Pnote,s,t 5011(152 m) 90 lbs(41 kg) r " - 1.25"Sch.4D Steel Pipe(31_75 mm) r 54113OPE tr 3011(91 m) 44 lbs(20 kg) 1"Sch 40 Steel Pipe(25.4 mm) re.....4" 5011(152 m) 51 lbs(23 kg) OREGON 144,47.1101:1 C. EaNbar Percentage added for Fittings and Sprinklers 15% 70 lbs(31.75 kg) Total Adjusted Load of all pipe within Zone of Influence 537 lbs(244 kg) (Tel-Brace Version 71 ..., . Tol-Brace Seismic Calculations DELTA FIRE Project Address: BURNHAM ASH APTS 14795 SW 72ND AVE PORTLAND OR 97224 NA B-Line 4)TOLCO 12850&12790 SW Ash AVE 503 620 4020 Tigard OR 97223 Job*15-S4K Calculations based on 2013 NEPA Pamphlet#13 Brace Information Tolco Brace Components Maximum Spacing 40'0'.(12.19 m) Tolco Component Fig.Number Adjusted Load Maximum Brace Length? 0"(2.13 ro) .'19.4 Clamp 197 bs(89 kg) Bracing Material 1"Sch.40 Fig.98.0 Universal Swivel 1382 lbs(627 kg) *Calculation Baseo on CONCENTRIC Loading Angle from Vertical 30°Min. *Please Note These calculators are for TitIcti components on Use of any other components voids these calculations and the listing of the assembly. Least Rad.of Gyration 0.42"(11 mm) Assembly Detail UR Value 200 10LCO FIG.9 a Max Horizontal Load 926 lbs(42041) UNIVERSAL SWAY BRACE MIAOW ENT TYP. 4015O,t1 Force Factor(Cp) 05 SIM PIPE-. . LATERAL BRACE Fastener Information Fastener Orientation NEPA Type 0 TOLCO FIG.4A-... PIPL CLAMP tOR ..,...A., SWAY BRACING 'Illr'r Maximum Load 315 lbs(143 kg) Diameter inin, ,t4 Length 471/2in. Type 49-Screw 1 Brace Identification on Plans LATERAL-2 CPVC Orientation of Brace Lateral Braced Pipe:2.5"CPVC Load Information [ Size and Type of Pipe Total Length Total Calculated Load 2.5CPVC(63.5 mm) 4081(12.2 m) 65 lbs(29 kg) T CPVC(50.8 mm) 2581(7.6 m) 28 lbs(13 kg) 1.5'CPVC(38.1 mm) ftft0%,_ 5081(15.2 iri) 35 lbs(16 kg) 1 eit414-46 1.25"CPVC(34 75 mm) ad &MOPE 40ft(12.2 m) 22 lbs(10.kg) 17-4—r 1"CPVC(25.4 mm i 2081(6.1 m) 7 lbs(3 kg) orainopi Vork13;i1 C. VEllipkosi_141_,,..6 Percentage added for Fittings and Sprinklers 15% 23 lbs(1043 kg) Total Adjusted Load of all pipe within Zone of Influence 180 lbs(82 kg) EIWI-Brace Version 71