Smoke Detectors with
Sounder and Relay Option .,„„„
System Sensor i3"sounder and relay smoke detectors
apply the guiding principles of installation ease, 3
intelligence,and instant inspection in a series of
specialty conventional devices.
Features Installation ease.Throughout the i3 series,installation is simple
85 d6 sounder with its installer-friendly base and plug-in design.The base
• accommodates a broad range of back box and direct mounting
•Form C relay options and provides ample space for pre-wiring the device.To
Isolated thermal sensor complete the installation,the P detector plugs into its base with a
• simple Stop-Drop'N Lock action.
•Plug-in design(base included)
Intelligence.To reduce the likelihood of nuisance alarms,all
•In-line terminals P detectors are equipped with both drift compensation and
•Flexible mounting options smoothing algorithms.These capabilities minimize both short-and
Stop-Drop'N Lock"attachment to the base long-term causes of nuisance alarms,such as RF interference and
• dust accumulation.When connected to the 2W-MOD2 loop test/
•Removable cover and chamber maintenance module or an P Ready"panel,2-wire i3 detectors can
Remote maintenance signaling generate a remote maintenance signal when in a maintenance or
• freeze trouble condition.To measure the sensitivity of any i3 detector,
•Drift compensation and smoothing algorithms the SENS-RDR displays the reading,in terms of percent-per-foot
•Simplified sensitivity measurement obscuration,within seconds.
•Dual-color LEDs Instant inspection.i3 has red and green LEDs to simplify local
status indication during power-up,standby,alarm,maintenance,
and freeze trouble conditions.When in alarm,i3 sounder models
generate an 85 dB temporal tone.If connected to the RRS-MOD
reversing relay/synchronization module,all i3 sounders on the loop
will activate when one detector is in alarm.The RRS-MOD also
synchronizes i3 sounder output to ensure a clear audible signal.
Agency Listings
Should the application call for differentiating between a local and
(2110
a general alarm,the i3 line offers an isolated thermal model,which
initiates a local alarm when smoke is detected,and a general alarm
® MEA IVISFM c� us when the thermal sensor is activated.
LISTED APPROVED 11 approved approved
��ll 3015195 7272-1653:164 372-02-E 2133 3180932
r
(u Smoke Detector Specifications
Electrical Specifications LED Modes
Operating Voltage Nominal:12/24Vnon-polarized LED Mode Green LED Red LED Condition Duration
2-wire:8.5 V to 35 V Power up Blink every Blink every 10 Initial LED 80 seconds
4-wire:l 0 V to 35 V 10 seconds seconds status
Maximum Ripple Voltage 30%of applied voltage(peak to peak) indication
Standby Current 2-wire:50 pA maximum average Normal Blink every 5 off
4-wire:50 pA maximum average (standby) seconds
Peak Standby Current 2-wire:100 pA Out of off Blink every 5
4-wire:n/a sensitivity seconds
Maximum Alarm Current 2-wire:2WTR-B:130 mA limited by control Freeze off Blink every 10
panel trouble seconds
2WTA-B:130 mA** Alarm off Solid
4-wire:4WTA-B,4WTR-B:35 mA Power-Up Sequence for LED Indication
4WTAR-B,4WITAR-B:50 mA
**Direct Power(Non-Reverse Polarity):130 Condition Duration
mA limited by panel.Reverse Polarity Power: Initial LED 80 seconds
30 mA for the 2WTA-B in alarm;12 mA for all status
other 2WTA-B units on the loop.Add 25 mA indication
for the RRS-MOD reversing relay alarm current. Architect/Engineer Specifications
Alarm Contact Ratings 2-wire:n/a Smoke detector shall be a System Sensor P Series model number ,
4-wire:05 A @ 30V AC/DC listed to Underwriters Laboratories UL 268 for Fire Protection Signaling
Form C Contact Ratings 2 A @ 30 V AC/DC Systems.The detector shall be a combination photoelectric/thermal
Physical Specifications equipped with a sounder(model 2WTA-B,4WTA-B),a Form C relay(model
2WTR-B),a combination sounder/relay(model 4WTAR-B),or an isolated
Operating Temperature 32°F to 100°F(0°C to 37.8°C) thermal/sounder/relay(model 4WITAR-B).The detector shall include a
Range mounting base for mounting to 31-inch and 4-inch octagonal,single-gang,
Operating Humidity 0 to 95%RH non-condensing and 4-inch square back boxes with a plaster ring,or direct mount to the
Range ceiling using drywall anchors.Wiring connections shall be made by means
Thermal Sensor 135°F(572°C)fixed of SEMS screws.The detector shall allow pre-wiring of the base and the
Freeze Trouble 41°F(5°C) head shall be a plug-in type.The detector shall have a nominal sensitivity
Sensitivity 2.5%/ft.nominal of 25 percent per foot as measured in the UL smoke box.The detector
shall be capable of automatically adjusting its sensitivity by means of drift
Input Terminals 14-22 AWG compensation and smoothing algorithms.The detector shall provide dual-
Dimensions(including 5.3 inches(134 mm)diameter,2.0 inches color LED indication that blinks to indicate power-up,normal standby,out of
base) (51 mm)height sensitivity,alarm,and freeze trouble conditions.When used in conjunction
Approximate Weight 7.1 oz(200 g) with the 2W-MOD2 module,2-wire models shall include a maintenance
Sound Pressure Output 85 dBA(models 2WTA-B,4WTA-B,4WTAR-B, signal to indicate the need for maintenance at the alarm control panel and
and 4WITAR-B only) shall provide a loop testing capability to verify the circuit without testing each
Mounting 3'/z inch octagonal back box,4-inch octagonal detector individually.When used in conjunction with the RRS-MOD module,
back box,single gang back box,4-inch square all i3 sounder models on a loop shall sound when one sounder alarms,all shall
back box with a plaster ring,direct mount to be synchronized,and all sounders may be silenced from the panel.
ceiling
Ordering Information
Model Thermal Wiring Alarm Current Model Description
2WTA-B Yes 2-wire 130 mA max.limited by RRS-MOD Reversing relay/synchronization module
control panel 2W-MOD2 2-wire loop test/maintenance module
2WTR-B Yes 2-wire 130 mA max.limited by SENS-RDR Sensitivity reader
control panel RT Removal/replacement tool
4WTA-B Yes 4-wire 35 mA A77-AB2 Retrofit adapter bracket
4WTR-B Yes 4-wire 35 mA
4WTAR-B Yes 4-wire 50 mA
4WITAR-B Yes 4-wire 50 mA
(�\`� SYSTEM E/ l02009 System Sensor
`` ` 3825 Ohio Avenue St.Charles,IL60174 Pro uct pec�f tions�ubjecttochangewimoutnonce.wsasyste<nsens«.comfot
�.V SENSOR' Phone:800-SENSOR2•Fax:630-377-6495 current product n(onnanon,48-044.5/09latest version ofthndata sheet
A05-0348-004.6/09 42170