Loading...
Report OP?, St) & 1. sLsGj° MORTIER ANG Asr�de-or�1s3 ENGINEERSSTRUCTURAL ( CIVIL 1355 OAK STREET,STE#200 FIRE PROTECTION EUGENE,OREGON 97401 i PHONE:(541)484-9080 June 15,2018 Terra Firma—Emily Singleton 7910 SW Hunziker St. Tigard,OR 97223 RE: 13220 SW Genesis Lp.,Tigard,OR 97223 - WO 21816 As requested,special inspection of the installation of Terra Firma push piers was conducted on June 14,2018.The repair involved placement of 7 push piers,as shown on the plans from this office dated 5/16/2018.The push piers were installed beyond the minimum installation pressure of 1350 psi(4'A"RAM)and the minimum depth of 8 feet.Each pier installation is acceptable regarding project requirements.It is noted that the EOR approved the change of location of the piers. TABLE 1—PUSH PIER DRIVE LOG DETAILS Plan Pier Number Installation Depth(feet) Installation Pressure(psi) 1 40 1400 2 43 1400 3 43 1400 4 61 1700 5 43 1800 6 61 1900 7 70 2200 The provided special inspection has been performed to meet the requirements of current building code and does not establish a guarantee of the contractor's work.It is the responsibility of the contractor to perform the work in accordance with the provided structural drawings and the specifications of Foundation Supportworks. Thank you for the opportunity to be of service.If you have any questions or concerns regarding this report,feel free to let us know. Sincerely, 4.0 PRO, 7.12.18 ����c'1NF d>0. 6 t{ royal@mortiereng.com 11/ or Ge '1{'E - Royal Mortier, PE 2018.07.12 16:04:56-07'00' •RE ON ; DIGITAL SIGNATURE FOR VERIFICATION OF ELECTRONICALLY 4 7.C•>1`<_ / TRANSIMITTED DOCUMENTS ONLY. SIGNATURE WILL AUTOMATICALLY MO VOID IF DOCUMENT IS MANIPULATED ELECTRONICALLY. EXPIE _S; 2f3ii1 N Royal Mortier,P.E. Royal Mortier,P.E. RM/ja