Report (119) Walter L.Cook PE • Fire Protection Engineering Since 1991 ��Ep PROFFS April 10, 2015 ��,� �G t ni k- S�� ;; ;; Mr.Mike Schaenzer • . Northwest Fire Suppression, Inc. � /7r 15385 SW Beaverton Creek CT Beaverton,OR 97006 OR GOI� 7y FC. 15,1 O- RE: Engineering Review Approval-Fire Suppression System -9zTFR L. GO Cypress Semi-Conductor—Clean Agent System FE—25/Ecaro EXPIRES: 12/31 /2015 Tigard,Oregon Dear Mike, Enclosed under cover of this letter are the following document sets; • Clean Agent System Flow Calculations on Sheet FS-2 • Shop Drawing Sheets FS1—FS-2 • Manufacturers Data Submittals I find that this design package,prepared by Northwest Fire Suppression, Inc., is in general conformance with the intended project design. The submittal has been reviewed only for the limited purpose of checking for general conformance with the design concept as expressed in the Contract Documents,subject to the requirements of the Contract Documents. The finding is inclusive of equipment and installation in conformance with applicable codes including in part NFPA 2001 for Clean Agent, NFPA 13, NEC,Oregon Electrical Specialty Code,2010 Oregon Fire Code,and 2010 Oregon Structural Specialty Code and specific requirements of Tigard OR;with the following notations; • Seismic bracing is not included in the scope of this engineering review. • Interface connection with and interactive testing of the building;power,fire&HVAC systems is outside the scope of this review and the responsibility of others. • Agent concentration for fire suppression is based on NFPA 2001 as 9.0%minimum. I have placed my Oregon PE seal on this letter,indicating review approval for the documents referenced above,subject to the conditions stated herein and approval by the owner's representative and Tigard,OR. Sincerely Walter L.Cook PE 14795 SW 72nd Ave. WER-Inc. PHONE (503)333-3470 Portland,OR 97224 E-MAIL Walt.L.Cook@gmail.com