Report (2) Northwest Fire Suppression, Inc. RECEIVED EQUIPMENT SUBMITTAL APR 13 2015 CITY OF TIGARD FOR BUILDING DIVISION Cypress Semiconductor Clean Agent Suppression System 3 Lincoln, Suite 417 Tigard, Oregon 3/6/2015 JOB# 15-018 SYSTEM Fike FM-200 (HFC-227ea) Clean Agent Suppression System with SHP-Pro Suppression Control Panel CONTENTS Manufacturers Data Sheets FM-200 Flow Calculations 1800 NW 169th Place, Suite C600 • Beaverton, Oregon 97006 • 503-644-7720 • Fax 503-644-8289 www.nwfire.com CCB#088629 Licensed • Bonded • Insured .. lik• e® DATA SHEET SHP PRO° DESCRIPTION '' "'" The Fike SHP PRO,(P/N 10-063)is a Conventional Control system designed to provide a sophisticated, reliable conventional detection system for use with clean agent extinguishing,sprinkler pre-action/deluge, Y ' � watermist,waterflow alarm and fire alarm systems.It is a microprocessor based system which can be easily iiii configured for a wide range of suppression applications. The SHP PRO is designed for use with Fike Clean Agent Fire Suppressant,CO2,or sprinkler(pre-action/ deluge)suppression systems.The main controller contains all electronics required for a complete detection and control system suitable for most applications.Optional modules,which plug into the main circuit board, are available to add increased functionality to the system. The SHP PRO provides 10 Status LEDs(AC Normal,Alarm,PreDischarge,Release,Supervisory,Trouble,Panel - Silenced,Abort,Release Disabled,Ground Fault)for instant feedback.A diagnostic LED display is provided to help troubleshoot any potential field problems,provide current status and retain stored events.A Reset and Silence switch is provided to allow control of the system outputs and operation. The SHP PRO can be configured for either one or two conventional detection circuits.The detection circuits APPROVALS: can be configured for sequential detection,cross zone or single detector release. • UL Listed-S2203 Depending on the configuration selected,the SHP PRO also provides up to three initiating circuits to monitor • FM Approved-3017159 contact devices(Abort,Manual Release,Waterflow or Supervisory switches).Four different abort types are • CSFM 7165-0900:135 available including a special NYC option.All five initiating circuits can be converted to Class A operation via • City of New York- the SHP PRO Class A Input Module,P/N 10-2450.All SHP PRO initiating circuits are inherently power limited. 461-04-E A twelve position dip switch is used to set all options. • State of CA Seismic- OSP-0077-10 Three notification appliance circuits,rated for 2 amps @ 24 VDC are available.Depending on the • Hong Kong 206/0877 VII configuration,each circuit will provide distinct signaling for Alarm,PreDischarge,or Release conditions. Separate Agent Release and Solenoid circuits are provided to operate the suppression system.A dedicated Disable switch is provided for release and audible outputs.All output circuits,including solenoid and agent release circuits,are power limited. The SHP PRO provides dedicated alarm,trouble and supervisory SPDT contacts for annunciation and control. If additional outputs are required,up to two CRM4 Relay Modules can be added.(P/N 10-2204) APPROVED The SHP PRO is available in multiple hardware configurations,depending on the input power source(120 or 240 VAC),enclosure color(Gray or Red),and mode of operation(Clean Agent,Clean Agent/Sprinkler, al'i Sprinkler,Watermist,Solenoid Releasing).The system comes equipped with a 4.0 amp @ 24 VDC power� source.The system has been designed to comply with the following standards: � • NFPA 12 Carbon Dioxide • NFPA 12A Halon 1301 Extinguishing Systems • NFPA 13 Installation of Sprinkler Systems • NFPA 15 Water Spray Fixed Systems • NFPA 16 Foam-water Sprinkler and Foam-Water Spray Systems • NFPA 70 National Electric Code a4 • NFPA 72 National Fire Alarm and Signaling Code • NFPA 2001 Clean Agent Fire Extinguishing Systems . Cyt1,, u44_ li 41 iii 4 Eid fi i on � Ill 1) n n it ilii �4 �r �' i''I''1'I'>>" HIiiii gyp,'` . / Form No. D.1.07.01-7 ii �i'ilk / l'�l''CI 704 SW 10th Street • P.O.Box 610 • Blue Springs,Missouri 64013-0610 U.S.A. ,` _% Phone:816.229.3405 • www.fike.com wr t M ~ FEATURES • Suitable for multiple types of Suppression:Clean Agent,Carbon Dioxide,Pre-Action Sprinkler/Deluge,and Watermist Systems • Microprocessor based with hardware and software integration designed to guarantee reliability " • Five Class B,Style B initiating circuits • Cross zone or sequential detection,manual release,abort,water flow,and supervisory initiating circuits • Three Class B,Style Y notification appliance circuits rated for 2.0 amps @ 24VDC • Dedicated release circuits compatible with agent release or solenoid actuation • Optional Class A modules for notification appliances/releasing circuits and initiating circuits • Alpha-numeric LED display for status and troubleshooting • Programmable pre-discharge and discharge timers • Resettable and continuous auxiliary output power • Integral 4.0 amp power supply • Small surface or flush mount enclosure with removable door • Approved for releasing device service and sprinkler supervisory • Built-in Gentex and System Sensor synch protocol • Steel enclosure 21"x 14.35"x 4" • Enclosure equipped with.50"wide lip for flush mounting SHP PRO WIRING DIAGRAM COMPONENTS • 10-063-X-X-X — • 10-063-X-X-X ABC ' ,° A: 1-Clean Agent/All Modes 2-Sprinkler only Nsy1 B: Ii R-Red .....—..— G-Gray C: 1-120 VAC "" 2-240 VAC • 10-2452-1 PCB Assy,SHP PRO, CI"I� Clean Agent,All Modes © 10 d ®Ib®®I®oI®®®I®b�b® © • 10-2452-2 PCB Assy,SHP PRO, 0-51; ° " , --.t:: . ., : �— Sprinkler Only odule ^ — — i 8� 1 ,".=° pCI L— • 10-2448 Class A Output�Module , , I © • 10-2204 CRM4 Relay Module ®%s- j®,_. (Z),.. I i .1.® o • 10-2190-2 Battery Assembly ®-� ®P o= „'� ® � \ AA,A. • (Qty.2),18AH,w/wiring assembly 0 41 Cr—g GLEA LES »EEE,ERVSSOLL : K » •w --�4PPR44 HIPI 'I =_.® I Do oa O000ggo. —___Q Oo 6,,I1 0 ^ oL 4,-,6066.4t5. o , ; o w..u.O 0 w.. Copyright© Fike Corporation All Rights Reserved. 2 of 2 Form No. D.1.07.01-7,June 2011.Specifications are subject to change without notice. Fikeo DATA SHEET DOUBLE COMBINATION CONTROL ACCESSORIES APPROVALS: • UL Listed • ULC Listed DESCRIPTION • FM Approved • The Manual Release Switch is a dual actuation device which provides a means of manually discharging the CSFM Approved automatic fire extinguishing system when used in conjunction with the Fike control panel. • BSA-610-79-SA The System Abort Switch is designed to be used in conjunction with other system equipment.It provides a temporary manual means by which the agent actuation circuit may be interrupted before automatic actuation occurs. The"Main"to"Reserve"switch is used with systems that incorporate main and reserve(back-up)agent 4> 14)) storage.The switch may utilize 1 or 2 Form"C"contact blocks which will provide an electrical path to either APPROVED the"Main"or"Reserve"release device(s). The Keyed Remote Reset Switch provides a method for resetting the Control Panel from a remote location. T"c These combination controls mount on a standard 4 gang masonry electrical box measuring 7-3/8" I'' ;' (187.3mm)wide x 3-3/4"(95.3mm)high x 2-3/8"(60.3mm)deep.(Fike P/N 02-2123) LISTED o- III OM *17, ., 24': , . a 10-1643 10-1644 10-1645 v,' Manual Release/System Abort Manual Release/Main Reserve Manual Release/Remote Reset 41110 • ,Y1.. avl 10-1646 10-1647 10-1648 System Abort/Main Reserve System Abort/Remote Reset Main Reserve/Remote Reset Fir y, j ' , ar I illi Form No.P.1.73.01-1 704 SW 10th Street • P.O.Box 610 • Blue Springs, Missouri 64013-0610 U.S.A. <=s r Phone:816.229.3405 • www.fike.com I I 1 • (This page is left blank intentionally) Copyright© Fike Corporation All Rights Reserved. 2 of 2 Form No. P.1.73.01-1,March 2006.Specifications are subject to change without notice. 4_, like® DATA SHEET PHOTOELECTRIC/HEAT SMOKE DETECTOR DESCRIPTION The Photoelectric/Heat Smoke Detector(P/N 63-1025)can be used in all areas where Photoelectric Smoke 4Pt. ` Detectors are required.The wide range smoke chamber makes the photoelectric/heat smoke detector well suited for fires ranging from smoldering to flaming fires.Various styles of bases may be used with the photoelectric/heat smoke detector.Current interchangeable/compatible devices are ionization detector p� (P/N 67-1033),photoelectric detector(P/N 63-1024)and the heat detectors(P/N's 60-1029/60-1030 _ ] [135°/190°]). All conventional devices are mechanically compatible with Fike bases which may have been used in previous installations.Please check individual panel listings for compatible bases. APPROVALS: STANDARD FEATURES • UL-51383 • Low profile,2.2"high(with base) • FM-3006185 • 2 or 4 wire base compatibility,relay bases available • CSFM-7272-0410107 • 135°F Fixed Temperature heat sensor(Latching) • Heat sensor protected by a built-in guard • Highly stable operation,RF/Transient protection • Low standby current,441A at 24VDC • Two built-in power/sensitivity supervision/alarm LED's • Non-directional smoke chamber • Vandal resistant security locking feature 41> • Removable smoke labyrinth for cleaning or replacement APPROVED • Automatic Sensitivity window verification function meets outlined requirements in NFPA 72,Chapter 2&7,Inspection,Testing and Maintenance SPECIFICATIONS I; Light Source: GaAIAs Infrared Emitting Diode Heat Sensor: 135°F Rated Voltage: 17.7-30.0 VDC Working Voltage: 15.0-33.0 VDC Maximum Voltage: 42 VDC Supervisory Current: 45µA @ 24 VDC Surge Current: 160µA max. @ 24 VDC Alarm Current: 150mA max.@ 24 VDC Ambient Temperature: 32°F to 120°F(0°C to 49°C) Color&Case Material: Bone PC/ABS Blend Sensitivity Test Feature: Automatic Sensitivity window verification test ° OPERATION The photoelectric/heat smoke detector utilizes two bicolored LED's for indication of status.In a normal standby condition the LED's flash Green every 3 seconds.When the detector senses that its sensitivity has drifted outside the UL listed sensitivity window the LED's will flash Red every 3 seconds.When the detector senses smoke and goes into alarm the status LED's will latch on Red. The detector utilizes an infrared LED light source and silicon photo diode receiving element in the smoke chamber.In a normal standby condition,the receiving element receives no light from the pulsing LED light source. In the event of a fire,smoke enters the detector smoke chamber and light is reflected from the smoke particles to the receiving element.The light received is converted into an electronic signal. Signals are processed and compared to a reference level,and when two consecutive signals exceeding the + reference level are received within a specified period of time,the time delay circuit triggers the SCR switch 11i ' =� to activate the alarm signal.The status LED's light continuously during the alarm period. 'max Form No.P.1.170.01 704 SW 10th Street • P.O.Box 610 • Blue Springs,Missouri 64013-0610 U.S.A. Phone:816.229.3405 • www.fike.com ENGINEERING SPECIFICATIONS The contractor shall furnish and install where indicated on the plans,Fike photoelectric/heat smoke detectors(P/N 63-1025).The combination detector head and twist-lock base shall be UL listed compatible with a UL listed fire alarm panel. The base shall permit direct interchange with Fike's photoelectric detector(P/N 63-1024),ionization type smoke detector(P/N 67-1033) and/or fixed temperature/rate-of-rise heat detectors(P/N 60-1029/60-1030).The base shall be appropriate twistlock base. The smoke detector shall have two flashing status LED's for visual supervision.When the detector is in standby condition the LED's will flash Green.When the detector is outside the UL listed sensitivity window the LED's will flash Red.When the detector is actuated,the flashing LED's will latch on Red.The detector may be reset by actuating the control panel reset switch. The sensitivity of the detector shall be capable of being measured.It shall be possible to perform a functional test of the detector without the need of generating smoke.The sensitivity of the detector shall be monitored automatically and continuously to verify that it is operating within the listed sensitivity range. To facilitate installation,the detector shall be non-polarized.Voltage and RF transient suppression techniques shall be employed to minimize false alarm potential.Auxiliary SPDT relays shall be installed where indicated. The vandal-resistant,security locking feature shall be used in those areas as indicated on the drawing.The locking feature shall be field removable when not required. ORDERING INFORMATION Fike P/N Mfg.P/N Description 63-1025 SLR-24H Photoelectric/Heat Smoke Detector 67-1034 NS6-224 430 C2,6 Base 67-1036 NS4-224 430 0,4"Base 67-1035 NS6-220 220 0,6"Base(SDR or Cross-Zone Only) 67-1037 NS6-220 220 0,4"Base(SDR or Cross-Zone Only) 63-1012 HSC-224R 430 0,6"Base(Sequential or Cross-Zone Only) SENSITIVITY TEST FEATURE The 63-1025 Photoelectric/heat Smoke Detector has a built-in automatic sensitivity test feature. 1.In normal condition,both LED's flash green. 2.When the sensitivity drifts outside of its sensitivity limits,both LED's flash red. 3.In the alarm state both LED's are red continuously. 4.When the sensitivity drifts outside of its sensitivity limits and both LED's flash red,the device needs to be cleaned or returned to the factory for cleaning. WIRING DIAGRAM 2-WIRE OPERATION UL LISTED (+) ■1 LISTED CONTROL .� PANEL .9 � o END OF LINE (-) i.;i "� DEVICE PANEL Rens POWER only Not annunciators unciators \e / (-) NOTE:-WIRING TERMINALS FOR 67-1036/67-1037 NEGATIVE m AND 67-1034/67-1035 ARE IDENTICAL 67-1036/67-1037 67-1034/67-1035 -BASES WITH THE„W„SUFFIX Annunciation device must be current limited to 20 mA @ ARE WHITE IN COLOR 24VDC Maximum.Not limiting current could result in damage to the detector or cause a no alarm condition. 2-wire relay wiring diagram is also available Copyright© Fike Corporation All Rights Reserved. 2 of 2 Form No. P.1.170.01,July 2013.Specifications are subject to change without notice. 40 Lir 0 0 0 ,00 SELECTABLE OUTPUT HORNS, STROBES, AND HORN/STROBES DESCRIPTION The Spectrrllert Advance series of notification appliances is designed to simplify installations,with features such as plug in designs,instant feedback messages to ensure correct installation of individual devices,and 11 field-selectable candela settings P� for wall and ceiling strobes and horn/strobes. When installing Advance products,first attach a universal .40 mounting plate to a four-inch square,four-inch octagon or a double-gang junction box.The two-wire mounting plate attaches to a single-gang junction box. Next,connect the notification appliance circuit wiring to the SEMS terminals on the mounting plate. Finally,attach the horn,strobe or horn/strobe tot he mounting plate by inserting the product's tabs in the mounting plate's grooves.The device will rotate into position,locking the APPROVALS product's pins into the mounting plate's terminals.The device • UL Listed will temporarily hold in place with a catch until it is secured • FM with a captured mounting screw • MEA • CSFM The SpectrAlert Advance series includes outdoor notification appliances. Outdoor strobes and horn/strobes (two wire and four wire)are available for wall or ceiling. Outdoor horns are available for wall only.All System Sensor outdoor products are rated between minus 40 degree Fahrenheit and 151 degrees Fahrenheit in wet or dry applications. FEATURES • Electrically compatible with existing SpectrAlert products • Automatic selection of 12-or 24-volt operation at 15 and 15/75 candela • Plug-in design • Field selectable candela settings on wall and ceiling units: 15,15/75,30,75,95,110,115, 135, 150, 177, 185 • Same mounting plate for wall-and ceiling-mount units • Shorting spring on mounting plate for continuity check before installation • Tamper resistant construction • Outdoor wall and ceiling products rated from-40°F to 151°F • Design allows minimal intrusion into the back box • Horn rated at 88+ dbA at 16 volts • Rotary switch for horn tone and three volume selections • Outdoor products UL listed to UL 1638 (strobe)and UL 464 (horn) outdoor requirements • Outdoor products rainproof per UL 50 (NEMA 3R) • Compatible with MDL sync module Form No. P.1.102.01 704 S.10th Street • P.O.Box 610 • Blue Springs,Missouri 64013-0610 U.S.A. • (816)229-3405 • (816)229-4615 • www.fike.com ARCHITECTURAL/ENGINEERING SPECIFICATIONS SpectrAlert Advance horns,strobes and horn/strobes shall mount to a standard 4 x 4 x 1 1/2 inch back box,4-inch octagon back box or double-gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 1 7/8 inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,SpectrAlert Advance products,when used with the Sync CircuitTM Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync Circuit module,12-volt rated notification appliances circuit outputs shall operate between nine and 17.5 volts;24-volt rated notification appliance circuit outputs shall operate between 17 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC,or full-wave rectified,unfiltered power supply.Strobes and horn/strobes shall have field-selectable candela settings,including 15, 15/75,30,75,95, 110, 115, 135, 150, 177, 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective services.The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobes entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn/Strobe Combination The horn/strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn/strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and option to switch between a temporal three- pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.On four-wire products,the strobe shall be powered independently on the sounder.The horn on horn/strobe models shall operate on a coded or non-coded power supply. Outdoor Products SpectrAlert Advance outdoor horns,strobes and horn/strobes shall be listed for outdoor use by Ul and shall operate between minus 40 degrees and 151 degrees Fahrenheit.The products shall be listed for use with a System Sensor outdoor/weatherproof back box with half inch and three-fourths inch conduit entries. Synchronization Module The module shall be a System Sensor Sync Circuit model MDL listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns on horn/strobe models over a single pair of wires.The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch back box.The model shall also control two Style Y(class B) circuits or one Style Z (class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply SPECIFICATIONS Standard Operating Temperature 32°F to 120°F (0°C to 49°C) K Series Operating Temperature -40°F to 151°F(-40°C to 66°C) Humidity Range 10 to 93%non-condensing(indoor products) Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12DC/FWR or regulated 24DC/FWR1 Operating Voltage Range'- 8 to 17.5V(12V nominal) or 16 to 33V(24 nominal) Input Terminal Wire Gauge 12 to 18 AWG Ceiling Mount Dimensions (including lens) 6.8"diameter x 2.5"high(173 mm diameter x 64 mm high) Wall Mount Dimensions (including lens) 5.6"L x 4.7"W x 2.5"D (142 mm L x 119 mm W x 64 mm D) Horn Dimensions 5.6"L x 4.7"W x 1.3"D (142 mm L x 119 mm W x 33 mm D) Wall Mount Back Box Skirt Dimensions 5.9"L x 5.0"W x 2.2"D (151 mm L x 128 mm W x 56 mm D) Ceiling Mount Back Box Skirt Dimensions 7.1"diameter x 2.25"high (180 mm diameter x 57 mm high) Wall Mount Weatherproof Back Box Dimensions 5.7"L x 5.1"W x 2.0"D (145 mm L x 130 mm W x 51 mm D) Ceiling Mount Weatherproof Back Box Dimensions 7.1"diameter x 2.0"high(180 mm diameter x 51 mm high) Notes: 1. Full Wave Rectified(FWR)voltage is a non-regulated,time varying power source that is used on some power supply and panel outputs. 2. P,S,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd. UL CURRENT DRAW DATA UL Max.Strobe Current Draw(mA RMS) UL Max.Horn Current Draw(mA RMS) 8-17.5 Volts 16-33 Volts j 8-17.5 Volts 16-33 Volts Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR 15* 123 128 66 71 Temporal High 57 55 69 75 15/75* 142 148 77 81 Standard 30* NA NA 94 96 Temporal Medium 44 49 58 69 Candela 75* NA NA 158 153 Temporal Low 38 44 44 48 Range 95* NA NA 181 176 Non-temporal High 57 56 69 75 110 NA NA 202 195 Non-temporal Medium 42 50 60 69 115 NA NA 210 205 Non-temporal Low 41 44 50 50 135 NA NA 228 207 Coded High 57 55 69 75 High 150 NA NA 246 220 Candela 177 NA NA 281 251 Coded Medium 44 51 56 69 Ranges 185 NA NA 286 258 Coded Low 40 46 52 50 UL Max.Current Draw(mA RMS),2-wire Horn/Strobe,Standard Candela Range(15-115 cd) 8-17.5 Volts 16-33 Volts DC Input 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 13 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-temporal High 141 152 91 100 116 176 201 221 229 Non-temporal Medium 133 145 75 85 102 163 187 207 216 Non-temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 _ Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Temporal High 142 161 103 112 126 181 203 221 229 Temporal Medium 134 155 85 95 110 166 189 208 216 Temporal Low 132 154 80 90 105 161 184 202 211 UL Max.Current Draw(mA RMS),2-wire Horn/Strobe,High Candela Range(135-185 cd) 16-33 Volts 16-33 Volts DC InputFWR Input 135 150 177 185 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 48 256 Temporal High 255 270 303 309 Temporal High 233 248 275 281 Temporal Medium 242 259 293 299 Temporal Medium 219 232 262 267 Temporal Low 238 254 291 295 Temporal Low 214 229 256 262 CANDELA DERATING HORN TONES AND SOUND OUTPUT DATA For K series products used at low temperatures, *Settings 7,8,and 9 are not available on 2-wire horn/strobe listed candela ratings must be reduced in accordance with this table Horn and Horn/Strobe Output(dBA) Strobe cd Output Switch 24 Volt Nominal p ( ) Sound 8-17.5 Volts 16-33 Volts Listed Candela Candela rating at-40°F Positio Pattern dB Reverberant Anechoic 15 n DC FWR DC FWR DC FWR DC FWR 15/75 Do not use below 32°F 1 temporal High 78 78 84 84 88 88 99 98 30 ..._ 2 temporal Medium 74 74 80 80 86 86 96 96 75 44 3 Temporal Low 71 73 76 76 83 80 94 89 95 70 4 Non-temporal High 82 82 88 88 93 92 100 100 110 110 5 Non-temporal Medium 78 78 85 85 90 90 98 98 115 115 - 135 135 6 Non-temporal Low 75 75 81 81 88 84 96 92 150 150 7* Coded High 82 82 88 88 93 92 101 101 177 177 8* Coded Medium 78 78 85 85 90 90 97 98 185 185 9* Coded Low 75 75 81 81 88 85 96 92 ORDERING INFORMATION Flke P/N Mfg.P/N Description Flke P/N Mfg.P/N Description Wall Horn/Strobes Ceiling Horn/Strobes(continued) 20-1345 P2R 2-wire Horn/Strobe,Standard cd Red 20-1306 PC2R-P 2-wire Horn/Strobe,Standard cd,Red 20-1269 P2RH 2-wire Horn/Strobe,High cd,Red 20-1308 PC2W 2-wire Horn/Strobe,Standard cd,White 20-1271 P2RHK 2-wire Horn/Strobe,High cd,Red,Outdoor 20-1309 PC2WH 2-wire Horn/Strobe,High cd,White 20-1349 P2RHK-P 2-wire Horn/Strobe,High cd Red,Outdoor,No Lettering 20-1311 PC2WH-P 2-wire Horn/Strobe,High cd,White,No Lettering 20-1273 P2RH-P 2-wire Horn/Strobe,High cd,Red,No Lettering 20-1313 PC2WH-SP 2-wire Horn/Strobe,High cd,White,Spanish 20-1275 P2RH-SP 2-wire Horn/Strobe,High cd,Red,Spanish 20-1310 PC2W-P 2-wire Horn/Strobe,Standard cd,White,No Lettering 20-1270 P2RK 2-wire Horn/Strobe,Standard cd,Red,Outdoor 20-1312 PC2W-SP 2-wire Horn/Strobe,Standard cd,White,Spanish 20-1348 P2RK-P 2-wire Horn/Strobe,Standard cd,Red,Outdoor,No Lettering 20-1314 PC4R 4-wire Horn/Strobe,Standard cd,Red 20-1272 P2R-P 2-wire Horn/Strobe,Standard cd,Red No Lettering 20-1315 PC4RH 4-wire Horn/Strobe,High cd,Red 20-1274 P2R-SP 2-wire Horn/Strobe,Standard cd,Red,Spanish 20-1317 PC4RHK 4-wire Horn/Strobe,High cd,Red,Outdoor 20-1276 P2W 2-wire Horn/Strobe,Standard cd,White 20-1316 PC4RK 4-wire Horn/Strobe,Standard cd,Red,Outdoor 20-1277 P2WH 2-wire Horn/Strobe,High cd,White 20-1318 PC4W 4-wire Horn/Strobe,Standard cd,White 20-1279 P2WH-P 2-wire Horn/Strobe,High cd,White,No Lettering 20-1319 PC4WH 4-wire Horn/Strobe,High cd,White 20-1278 P2W-P 2-wire Horn/Strobe,Standard cd,White,No Lettering Ceiling Strobes 20-1280 P4R 4-wire Horn/Strobe,Standard cd,Red 20-1320 SCR Strobe,Standard cd,Red 20-1281 P4RH 4-wire Horn/Strobe,High cd,Red 20-1321 SCRH Strobe,High cd,Red 20-1283 P4RHK 4-wire Horn/Strobe,High cd,Red,Outdoor 20-1323 SCRHK Strobe,High cd,Red,Outdoor 20-1351 P4RHK-P 4-wire Horn/Strobe,High cd,Red,Outdoor No Lettering 20-1325 SCRHK-P Strobe,Standard cd,Red,Outdoor,No Lettering 20-1285 P4RH-P 4-wire Horn/Strobe,High cd,Red,No Lettering 20-1322 SCRK Strobe,Standard cd,Red,Outdoor 20-1282 P4RK 4-wire Horn/Strobe,Standard cd,Red,Outdoor 20-1324 SCR-P Strobe,High cd,Red,No Lettering 20-1350 P4RK-P 4-wire Horn/Strobe,Standard cd,Red,Outdoor No Lettering 20-1326 SCW Strobe,Standard cd,White 20-1284 P4R-P 4-wire Horn/Strobe,Standard cd,Red,No Lettering 20-1327 SCWH Strobe,High cd,White 20-1286 P4W 4-wire Horn/Strobe,Standard cd,White 20-1329 SCWH-P Strobe,High cd,White,No Lettering 20-1287 P4WH 4-wire Horn/Strobe,High cd,White 20-1331 SCWH-SP Strobe,High cd,White,Spanish Wall Strobes 20-1328 SCW-P Strobe,Standard cd,White,No Lettering 20-1290 SR Strobe,Standard cd,Red 20-1330 SCW-SP Strobe,Standard cd,White,Spanish 20-1291 SRH Strobe,High cd,Red Horns 20-1293 SRHK Strobe,High cd,Red,Outdoor 20-1334 HR Horn,Red 20-1295 SRH-P Strobe,High cd,Red,No Lettering 20-1335 HRK Horn,Red,Outdoor 20-1297 SRH-SP Strobe,High cd,Red,Spanish 20-1336 HW Horn,White 20-1292 SRK Strobe,Standard cd,Red,Outdoor Accessories 20-1294 SR-P Strobe,Standard cd,Red,No Lettering 20-1339 BBS-2 Back Box Skirt,Wall,Red 20-1296 SR-SP Strobe,Standard cd,Red,Spanish 20-1341 BBSC-2 Back Box Skirt,Ceiling,Red 20-1298 SW* Strobe,Standard cd,White 20-1342 BBSCW-2 Back Box Skirt,Ceiling,White 20-1299 SWH* Strobe,High cd,White 20-1340 BBSW-2 Back Box Skirt,Wall,White Ceiling Horn/Strobes Electronic Chime/Sounder 20-1302 PC2R 2-wire Horn/Strobe,Standard cd,Red 20-1337 CHR Chime,Red 20-1303 PC2RH 2-wire Horn/Strobe,High cd,Red 20-1338 CHW Chime,White 20-1305 PC2RHK 2-wire Horn/Strobe,High cd,Red,Outdoor Chime/Strobe 20-1307 PC2RH-P 2-wire Horn/Strobe,High cd,Red,No Lettering 20-1332 CHSR 2-wire Chime/Strobe,Standard cd,Red 20-1304 PC2RK 2-wire Horn/Strobe,Standard cd,Red,Outdoor 20-1333 CHSW 2-wire Chime/Strobe,Standard cd,White 'koCopyright© Fike Corporation All Rights Reserved. Form No. P.1.102.01 July,2007 Specifications are subject to change without notice. n ike CORPORATION FIRE ALARM BELL APPLICATIONS .--1.-41111111111: Fike's Fire Alarm Bells,manufactured by Gentex Corporation,provide durable 4 417- and dependable operation required for life safety alarm systems. Alarm bells are low current,high decibel notification appliances for use in fire and burglary systems or other important signaling applications. The Fire Alarm Bells are available in 24VDC or 120VAC,6"or 10" housing and are can be used for indoor or outdoor applications.When used outdoors,Fike's ,:''''''!, : Back Box(P/N 20-123-125)is also required. Fike Fire Alarm Bell STANDARD FEATURES/SPECIFICATIONS APPROVALS • Four Wire 24VDC or 120VAC Operation • Americans with Disabilities Act • High dBA Output (ADA 4.28.3) • Available in 6" or 10"Housing • BFP (City of Chicago) • Mounts to a Standard 4"Square Electrical Box • BS+A/MEA#285-91-E ~ • Listed for outdoor use when used with the 20-123-125 Back Box • CSFM • 18 AWG Wire Leads • NFPA 72 • Available in Red Metal Finish • UL 464 • Meets UL 464 Requirements AVAILABLE MODELS Fike P/N Manf. P/N Voltage Housing Current Draw dBA @ 10Ft. 20-123-116 904-1278-2 24 VDC 6" 100mA- 95 20-123-117 904-1279-2 24 VDC 10" 100mA 96 20-123-118 904-1280-2 120 VAC 6" 25mA 95 20-123-119 904-1281-2 120 VAC 10" 25mA 98 Form No. P.1.58.01-1 704 S.10th Street • P.O.Box 610 • Blue Springs,Missouri 64013-0610 U.S.A. • (816)229-3405 • (816)229-4615 • www.fike.com Dimensions Mounting 10" OW GONG.' 4. 4"SQUARE OUTLET SOX *, / '+. 8" DIA, GONG-iffy.-"--. _ .t ' S t ( `- 'R', ' I I ' k 1 J )I i t �y x s _ t r .t a 1 1 ` , - .- OR PLATE ' STRIKER (2740 1) qr I I �15 HEX-iOLT GONG . iiij j y� ',taw OF BASE il C a s 3 1 1 J 152 Wiring Diagrams - D.C.BEDS (OBSERVE POLARITY) A.C. BELLS RED . RED ea' ='' N +, RECO • FROM MINX men_ To'err EB.. FppY MOM MEL '-971, 6 Be J. LillI�6S�Ie PRESTO Ell 1 ,,iiil BLACK F BL.ACK • BLACK BLACK DLIT) ARCHITECT AND ENGINEERING SPECIFICATIONS The audible signal shall be a Gentex Fire Alarm Bell or approved equal and shall be listed by Underwriters Laboratories Inc. per UL 464.The notification appliance shall also be listed with the California State Fire Marshall(CSFM) and the Bureau of Standards and Appeals (NYC). The notification appliance shall produce a peak sound output of 95dBA or greater as measured in an anechoic chamber. The appliance shall be polarized to allow for electrical supervision of the system wiring.The unit will mount to a double gang box or double workbox without the use of an adapter plate.The Fire Alarm Bell must be used with the Outdoor Box for outdoor applications to meet UL listing requirements. F• Ik0 m Copyright© Fike Corporation All Rights Reserved. CORPORATION Form No. P.1.58.01-1 August,2005 Specifications are subject to change without notice. .. .. Fike° DATA SHEET DISCHARGE PRESSURE SWITCH , 1,----:--_=, Discharge Pressure Switch DESCRIPTION --c Discharge Pressure Switch(DPS)is used to provide a positive pneumatic confirmation to the control system .i i'in that the Eike Fire Suppression system has been discharged. When a system is discharged manually(by Impulse Valve Operator(IVO)with Strike Button),the discharge !t , °° pressure switch is required to provide the input to the control system needed to activate various audio/ ' visual warning devices and auxiliary relays. The switch is operated pneumatically using the agent pressure in the discharge piping network. SPECIFICATIONS IIS�wl�� Part Number: 02-12534 Temperature Limits: 32 to 130°F(0 to 54.4°C) Enclosure Classification: NEMA 4 Contact Rating: Single pole,double throw; Containerw!Impulse 5 amps resistive, Valve �l�I��pa 3 amps inductive @ 30VDC (I,'P (can be wired for normally open or normally closed operation) Body Material: Aluminum with irridite finish Weight: 6.5 ounces APPROVALS: Pressure Connection: 1/4"NPT(6 mm) DPS Length(approx): 41/8"(105 mm)Long(including both connectors) • UL Listed �` • ULC Listed q 5 �I Electrical Connection: 1/2"NPT(15 mm) Wire Leads: (3)18 gauge x 20"(508 mm)long Violet(Common),Blue(N.O.),Black(N.C.) • FM Approved Pressure Setting: 40 psig(3 bar)(Increasing) INSTALLATION Discharge Pressure Switch is installed in the 1/4"NPT(female threads)port machined into the Adapter Nipple as shown in the illustration below.(see Figure 1) Step 1: Remove rubber cap and apply Teflon Tape to the male threads of the Discharge Pressure Switch. Step 2: Remove%"pipe plug from Adapter Nipple. LISTED Step 3: Thread Discharge Pressure Switch into 1/4"NPT port on Adaptor Nipple(Wrench tight). 41> Discharge APPROVED Pressure Switch Adapter Nipple le, a w!114"female threads l ;;:I. ., .3 EI 1 ,1 Grooved Coupling pp‘ f �Illllllr Discharge Outlet -lie j ` h1 FIGURE 1 c i � F F, f Form No.IV.1.12.01-1 704 SW 10th Street • P.O.Box 610 • Blue Springs,Missouri 64013-0610 U.S.A. ,' Phone:816.229.3405 • www.fike.com WIRING DIAGRAM Following is a typical wiring diagram showing how the discharge pressure switch is wired to the manual release input of the Fike SHP PRO® control panel.(see Figure 2)For control panel wiring details,refer to the SHP PRO manual P/N 06-297 Blue Wire • End of Line Manual Release Input _ 111 Resistor Violet Wire • FIGURE 2 Discharge Pressure Switch Normally Open Contacts (closes when pressure applied) When the Cheetah®Xi or Xi 50 is used,the switch can connect to a monitor module(MM)programmed for latching manual release.For control panel wiring details,refer to the Cheetah Xi manual P/N 06-356 or Cheetah Xi 50 manual P/N 06-369. Copyright© Fike Corporation All Rights Reserved. 2 of 2 Form No. IV.1.12.01-1,August 2012.Specifications are subject to change without notice. like ° DATA SHEET LOW PRESSURE SWITCH Low Pressure Switch DESCRIPTION Fike offers an optional Low Pressure Switch(LPS)for the purpose of continuously 4 Pitt?. �` monitoring the container pressure for a low-pressure condition. If the pressure inside the container drops below 288 psig(1986 kPa),the switch contacts FIJI P00 will transfer and invoke a"supervisory"indication on the control panel. The LPS is an optional item for Impulse Valve containers.It may be ordered along with a configured Impulse Valve container or as a separate item. FIGURE 1 The design of the Impulse Valve allows a LPS to be installed on a fully pressurized container without loss of agent or pressure. SPECIFICATIONS APPROVALS: Part Number: 02-12533 • UL LiLted Temperature Limits: 32 to 130°F(0 to 54.4°C) • ULC Listed • FM Approved Enclosure Classification: NEMA 4 a�9M� Contact Rating: Single pole,double throw;5 amps resistive, 3 amps inductive @ 30VDC (can be wired for normally open or normally closed operation) 6 iN III; Body Material: Aluminum with irridite finish Weight: 6.5 ounces Pressure Connection: M10 x 1-6G Electrical Connection: 1/2"NPT(15 mm) (DI (05 LPS Length(approx): 4 3/8"(111 mm)long(including both connectors) LISTED Wire Leads: (3)18 gauge x4.0 ft.(1.2m)long Violet(common),Blue(N.O.),Black(N.C.) Pressure Setting: 288 psig(20 bar)(decreasing) INSTALLATION 4t;* = The LPS is an optional item and must be ordered separately.This device can be installed in the Fill Port on a APPROVED container that is charged by using the following steps: Step 1: Prior to Assembly;lubricate the LPS 0-Ring with Molycoat 55 or equal. Use care not to get lubricant into pressure port. Notes: DO NOT apply Teflon Tape to LPS threads. DO NOT cross thread the LPS during installation. Step 2: Remove and retain Plug from Fill Port.(see Figure 1) III" Step 3: Remove rubber cap and screw in the LPS(Hand Tight)until the switch bottoms out.Screwing the switch in to this point will open an internal check valve and applies pressure the switch. Note:"NO TOOLS"are required to install LPS. Step 4: Leak check around the pressure gauge port using Snoop leak test fluid or equivalent. If a leak is detected;remove the LPS from the fill port and remove the lubricant and contaminants from the 0-Ring,threads and valve port using isopropyl alcohol and a soft clean cloth. Lubricate the 0-Ring with Molycoat 55 or equal and reinstall. Leak test around the fill port. If a leak is detected;remove the LPS from the fill port,remove the 0-Ring,install a new 0-Ring, lubricate the 0-ring with Molycoat 55 or equal,install the LPS in the fill port,and leak test around the fill port. Note:When installing conduct connector to LPS secure"Hand Tight". Over tightening may cause est damage to the LPS or to the Impulse valve fill port threads. { e 0 .14E0•A pf iii { ih i f Form No.IV.1.13.01-1 704 SW 10th Street • P.O.Box 610 • Blue Springs,Missouri 64013-0610 U.S.A. �f Phone:816.229.3405 • www.fike.com t N WIRING DIAGRAM—LOW PRESSURE SWITCH The LPS should be wired into a supervised circuit in the control panel used to provide a supervisory signal if the container pressure drops below 288 psig(1986 kPa). The switch is wired as a normally closed contact(open under pressure).(see Figure 2) Note:Refer to the Installation,Operation&Maintenance for the control panel being used for specific wiring criteria. Black Wire • • • Supervisory _ _ _ • End of Line Circuit Resistor Violet Wire • • • Low Pressure Switch Normally Closed Contacts (open under pressure) 'Typical 3( FIGURE 2 Copyright© Fike Corporation All Rights Reserved. 2 of 2 Form No. IV.1.13.01-1,August 2012.Specifications are subject to change without notice. Fike DATA SHEET IMPULSE VALVE OPERATOR (IVO) KIT 1 44(111(7 DESCRIPTION The Impulse Valve Operator(IVO)provides means to electrically or manually activate the Fike Impulse Valve clean agent container by providing the force required to extend a piston that will f „� ^: open the rupture disc,allowing the agent to be released from the container. t y The IVO can be activated electrically via a signal from Fike control panel or manually by depressing red strike buttom. Fike Clean Agent Containers with Impulse Valve must use an Impulse Releasing Module(IRM) to supervise the agent release circuit wiring(for open and ground fault conditions)from the container to the control panel. SPECIFICATIONS APPROVALS: Normal Supply Voltage: 24VDC • UL Listed Current Consumption: 0 Amps(for Battery Calculation) • ULC Listed Electrical Connection: DIN connector w/Cable&%"NPT for conduit connection • FM Approved IVO Material: Stainless Steel(Body)/Brass(End Cap) Temperature Range: 32 to 130°F(0 to 54.4°C) Environment: Indoor Use Only ORDERING INFORMATION (IVIDI (111i1 Item No. Fike P/N Description 70-279 IVO Kit(includes all items listed below) LISTED a 1 02-12728 IVO 2 70-286 Reset Tool 4> 4,4 3 02-12755 Wire Lead(3'long)with connector APPROVED 10-2748 IRM Item No.2 Item No.1 Item No.4 l s -1 � hi 1,1 ..,':' 1110). _ ,vialiii:::::.___, ,... .., , , .., , .,a Item No.3 1. I t III p - I . 111 3 Form No.IV.1.09.01-1. , fi,9�ti,1,Yrl r�i �1i)1��� 704 SW 10th Street • P.O.Box 6.10 • Blue Springs,Missouri 64013-0610 U.S.A. I�0j1i�llj5 �i>i�n�a�� ��i �� �9�,1 �� 11, X014 Phone:816.229.3405 • www.fike.com r ' ✓i INSTALLATION After the electrical/control system has been checked out and no trouble/ground faults are present;proceed with the Actuation System installation. Note:This should be the last items completed before the system is placed into operation. Important Note:Check to ensure IVO is armed(Firing Pin retracted)and Safety Pin is place before installing to the Impulse Valve on the container. 1j7,4_ IVO V '_ o el ; No Pin Exposed 'co n ow NCI- (Armed Position) tv °' �y Safety Pin in Install the wire lead w/connector(Item no.3)to the IVO(Item no.1)connector and secure with set screw. Install IVO;remove Retaining Clip and Plastic Plug from Impulse Valve Actuation Port. Insert IVO into Impulse Valve Actuation Port and re-insert Retaining Clip. ........................ ii Is 1 r ' Actuation Port Retaining Clip / . _ . IVO { d k`M'I .r The container is"NOW ARMED". 2of6 ELECTRIC ACTUATION—SINGLE CONTAINER SYSTEM W/IVO For wiring installation details between Fike Control Panel,IRM and the IVO,reference the Impulse Release Module Product Manual (P/N 06-552). At this point the IVO can be installed to the Clean Agent Container Impulse Valve. The Discharge Pressure Switch (P/N 02-12534)is required and is wired to the manual release contact in SHP PRO®or to a monitor module in Cheetah®Xi or Xi 50. Warning:Do not attempt to install the IVO with the firing pin in the extended position. iii 4(i4�i I C 4— IRM Assembly(p/n 10-2748) �611���i��iiNiIPIIlIIOh ! Discharge Pressure Switch (p/n 02-12534) - - > — , A IVO WI Manual Strike Button ELECTRIC ACTUATION—MULTI-CONTAINER SYSTEM WI IVO Fike Control Panel Maximum of 6 IBMs can be wired to a single Fike Control Panel) I I 1 1 I I 1 1 WI U I ©OO inn IRM Assembly (p/ii 10-2748) I . , '. . V ? v W IVO w/Plastic Cap/Manual Strike Button removed(Typical for containers) Important Note:When utilizing electric actuation(IRM)with multiple containers with IVO,the manual strike button on each IVO must be removed and plastic cap installed. The Discharge Pressure Switch is NOT used. This is to prevent a single container from being discharged in a multiple container system. For wiring installation details between Fike Control Panel,IRM and the IVO,reference the Impulse Release Module(IRM)Product Manual(P/N 06-552). At this point the IVO can be installed to the Clean Agent Container Impulse Valve. Reference detailed installation instructions on page 2 of this data sheet ELECTRIC&PNEUMATIC ACTUATION—TWO CONTAINER SYSTEM WI IVO&IVPO Item No. Fike P/N Description 1 02-4530 '4"NPTx'/<"JIC Adaptor(must be ordered separately) 2 02-4977 '4"JIC x 3.0'Ig.Actuation Hose(supplied w/IVPO kit)(see note) 3 02-4543 1/8"NPT x""JIC Adaptor(supplied w/IVPO kit) 4 02-12926 '4"JIC Male Adaptor(must be ordered separately) Note:This actuation method requires 2—WPC 3.0'Ig.Actuation Hoses,1 hose supplied w/IVPO kit,the 2nd Actuation Hose must be ordered separately. 3 of 6 Fike Control Panel i NOTE: Install Discharge f— IRM Assembly(p/n 10-2748) Pressure Switch on Container w/IVP° Adaptor r ��.. e'f Nipple w/ — 1 2(see note) 4 2 2¢ 3 ''/"Plug �— IVPO / Discharge s . TIF Pressure Switch thiti w",a IVO w/Manual Strike F�._._. (p/n 02-12534) Button First remove the'/"NPT Plug from Adaptor Nipple,then install Actuation System as shown above. Secure Actuation tubing to a solid surface. Anchoring into plaster,sheetrock wall or any other facing material is NOT acceptable. For additional information regarding the installation and resetting of the IVPO,refer to the IVPO Data Sheet IV.1.10.01 The Discharge Pressure Switch(P/N 02-12534)is required and is wired to the manual release contact in SHP PRO or to a monitor module in Cheetah Xi or Xi 50. ELECTRIC&PNEUMATIC ACTUATION—MULTI CONTAINER SYSTEM W/IVO&IVPO Item No. Fike P/N Description 1 02-4530 %"NPT x'A"JIC Adaptor(must be ordered separately) 2 02-4977 '4"JIC x 3.0'Ig.Actuation Hose(supplied w/IVPO kit)(see note) 3 02-4543 1/8"NPT x'''4"JIC Adaptor(supplied w/IVPO kit) 4 CO2-1359 '4"Tube Tee(must be ordered separately) 5 CO2-1356 '4"Male JIC x'''4"Male Tube Adaptor(must be ordered separately) 6 02-12695 '''4"Tube x'A"JIC Adaptor(must be ordered separately) 7 02-12696 '''4"Tube Elbow-90°(must be ordered separately) 8 02-12697 ''A"Tube Coupler(not shown)(must be ordered separately) Note:The Actuation Hose required to connect the 1st container w/IVO to the Actuation Tubing must be ordered separately. 4of6 • Fike Control Panel Distance will vary depending I 1"x 0.035 wall on container Stainless Steel size;cut%" bib IRM Assembly Tubing tubing to fit. (pIn 10-2748) 12(see note) 6 4 1 7 >e, �■ T 7 • 5 ; 5 Adaptor Nipple w/ j Discharge NPT j Pressure Switch Plug I 2 (p/n 02-12534) 2 0 - IVPO IVPO W 3 m3 ►� rea IVO The illustration above shows the items required to make the proper connection between the Container equipped w/an IVO and the Container(s)equipped w/an IVPO. The maximum length of pneumatic actuation line(including Hoses)can not exceed 50 ft.(15.2 m)and up to 6 containers equipped w/an IVPO. First remove the%"NPT Plug from Adaptor Nipple,then install Actuation System as shown above. Secure Actuation tubing to a solid surface. Anchoring into plaster,sheetrock wall or any other facing material is NOT acceptable. The Discharge Pressure Switch(p/n 02-12534)is required and is wired to the manual release contact in SHP PRO or to a monitor module in Cheetah Xi or Xi 50. For additional information regarding the installation and resetting of the IVPO,refer to the IVPO Data Sheet IV.1.10.01 5 of 6 4 RESET INSTRUCTIONS Remove IVO from Impulse Valve by removing Retaining Clip. Remove Safety Pin and pull the Manual Strike Button knob until it resets(clicks into place). IVO 711I— m _ Pin Extended N 'di --� Pull Knob (IVO–Fired Position) " Insert IVO into Reset Tool and secure with Retaining Clip. 1 't4 Safety Pin Reset Tool 1 ro Ilm 4 -- it lI Retaining Clip E Push Reset Tool button(firmly)against a hard surface until IVO Pin resets(clicks into place). Reset Tool @ Hard Surface qr� h6� I III Retaining Clip .,iiii- Safety Pin Insert and secure the Safety Pin,remove Retaining Clip,IVO is reset and ready to be installed on Impulse Valve. Important Note:Check IVO to ensure device is armed before inserting on Impulse Valve. IVO a 3 No Pin Exposed IA !! w! : (IVO—Armed Position) N � �^ Safety Pin > Copyright© Fike Corporation All Rights Reserved. 6 of 6 Form No. W.1.09.01-1,August 2012.Specifications are subject to change without notice. ,, like® DATA SHEET IMPULSE VALVE DESCRIPTION The 1"and 3"Impulse Valves are a rupture disc(metal diaphragm),pressure operated device that allows the � i agent to be released from the container and into the protected enclosure via the associated piping network and discharge nozzle(s). Fike Impulse Valves are equipped with four ports: • Agent Discharge Port allows agent release from container and also fulfills the pressure relief valve requirements in accordance with DOT regulations. • Agent Fill Port used to fill(refill)and pressurize the container and also used for the Low Pressure Switch. • Actuator Port used to connect an Impulse Valve Operator(IVO)with Manual Strike Button for electric and manual actuation of the container or an Impulse Valve Pneumatic Operator(IVPO)for pneumatic operation. • Pressure Gauge Port is used to connect a Pressure Gauge that will monitor internal container pressure,also equipped with an orifice plug that allows the pressure gauge to be removed safely when the container is pressurized. APPROVALS: 11140,..1,110,0 • UL Listed All i 111 11011511,, SPECIFICATIONS • ULC Listed Valve Body: Brass • FM Approved Rupture Disc Assembly: Hastelloy®C276/316 SST .i Discharge Port ► il 4112!1 ilillill i���u�il�o� a LISTED 4�'„�ii'(' d'�1'� Pressure Gauge Port 1>V' Fill Port p1 1':iiRupture Disc Assemhi>,r >`'' APPROVED 1”ImpUise Valve 1.i,e ° 1 Discharge Port f Pressure Gauge 14"�:s ''sw-� Fill Port • a° Pressure Gauge Port �` ; 3"Impulse Valve Actuator Port , a ilii p,,,, r F;Lc, , Form No. IV.1.14.01-1. 704 SW 10th Street • P.O.Box 610 • Blue Springs,Missouri 64013-0610 U.S.A. Phone:816.229.3405 • www.fike.com • e ..� Plug—Fill Port ► ._ " r., Rupture Disc Assembly Valve Core—Fill Port i, Actuator Pin f- '74141 g Internal View—t"Impulse Valve � Rupture Disc Assembly Plug—FillPort ►al t Actuator Pin ValveCore—FillPortI. il 14 0 n Internal View—3"Impulse Valve Copyright© Fike Corporation All Rights Reserved. 2 of 2 Form No. IV.1.14.01-1,August 2012.Specifications are subject to change without notice. . Fikeo DATA SHEET IMPULSE RELEASE MODULE DESCRIPTION 71‘'''''''';:iNk'Nk'N'''''N''..;:1— * The Impulse Releasing Module(P/N 10-2748)provides the primary interface between the supervised releasing circuit(s)of a Fike fire suppression system and the Impulse Valve Operator(IVO);which is used to release the fire suppressant agent from an impulse valve container.The IRM is equipped with three �' capacitors that receive a constant charging current from the releasing circuit of the control panel.When fully 4_/� charged,the module is capable of firing a single IVO.Upon circuit activation,the output circuit reverses its output voltage polarity,causing the energy in the capacitors to be released to the Impulse Valve Operator. Each IRM is equipped with a red LED to provide positive indication that the module is in the active(release) m >. state. ®-,;, 11i® Note:The IRM is provided as part of the IVO Kit(P/N 70-279)and does not need be ordered separately if ordering the kit. SPECIFICATIONS Current Consumption: +24V Supervisory: APPROVALS 20.0 ma(during capacitor charging) 3.0 ma(after capacitor is charged) • UL Listed-S3217 -24V Activated: • FM Approved -37.0 ma(LED active) • Cheetah®Xi Temperature: 32 to 130°F(0 to 54.4°C),93%maximum humidity • Cheetah®Xi 50 Module Wiring: Control panel to IRM connections are supervised and power-limited • SHP PRO® Impulse Valve Operator(IVO)connection is non-supervised and • CSFM-pendingpower-limited • MEA-pending Compatible Actuation Devices: 02-12728,Impulse Valve Operator(IVO) Compatible Releasing Panels: SHP PRO®,Cheetah®Xi,Cheetah®Xi 50 (Note:A maximum of six IRM's,wired in parallel,can be connected to each panel's releasing circuit.) INSTALLATION 41:* (]), Each Clean Agent container shall be provided with a Fike P/N 10-2748 Impulse Release Module(IRM).The APPROVED IRM shall be located at each container and shall be securely mounted in a standard 4"square x 2-1/8"deep UL Listed electrical box. Install conduit and releasing circuit wiring in accordance with the project drawings and appropriate wiring diagrams. All wiring must conform to the requirements of NFPA 70-National Electric r,, Code,NFPA 72-National Fire Alarm Code,NFPA 2001-Standard on Clean Agent Fire Extinguishing Systems, and the requirements of the Local Authority Having Jurisdiction. C 1 Form No. IV.1.15.01-1 Iii I�iMl��y1,1 hi 704 SW 10th Street • P.O.Box 610 • Blue Springs,Missouri 64013-0610 U.S.A. Phone:816.229.3405 • www.fike.com WIRING DIAGRAMS (-) FROM RELEASING �(� +) (+) RELEASING PANEL OR MODULE ►— IVO IVO CIRCUIT EOL emeeweP1 emeeweP1 = = = = = = 000000 + - IVO - + + - IVO - + IRM TERMINAL IRM TERMINAL BLOCK BLOCK CLASS B(STYLE Y)WIRING TO RELEASING ► PANEL OR MODULE ► (-) -) FROM RELEASING (� -) ( PANEL OR MODULE `�+� IVO (+ IVO eweemeP1 eweemeP1 = = = = = = 000000 + - IVO - + + - IVO - + IRM TERMINAL IRM TERMINAL BLOCK BLOCK CLASS A(STYLE Z)WIRING Copyright© Fike Corporation All Rights Reserved. 2 of 2 Form No. IV.1.15.01-1,December 2010.Specifications are subject to change without notice. Fike© DATA SHEET MOUNTING STRAPS AND BRACKETS 1 DESCRIPTION Mounting Straps/Brackets are used to secure containers to a wall or other suitable mounting surface. i These devices are supplied with each container purchased in accordance with the information shown below. Mounting hardware is supplied by system installer. Caution:Anchoring into plaster,sheetrock wall or any other facing material is NOT acceptable. SPECIFICATIONS Material: Carbon Steel Bracket Color: White(standard)/Red(see note below) Container Bracket P/N Size lb.(L) 5(2) 70-2135-X 10(4) 70-2135-X APPROVALS: y' 20(8.5) 70-1372-X • UL Listed 35(15) 70-1372-X • ULC Listed Approved 60(27) 701070-X 100(44) 70-1345-X 150(61) 70-2141-X 150i(61) 70-2142-X 141rb 1:1111)) iifigt215(88) 70-1310-X 375(153) 70-1310-X LISTED 650(267) 70-1384-X 1000(423) 70-1384-X 4t;* (,SIU F Note:Container brackets have 2 paint options(White or Red). When ordering a container bracket the paint option must be pppgoVEo I specified. For a bracket painted white enter part number—W and for bracket painted red enter part number—R. �j 9i j Example:20 lb.container bracket painted white,the part number is 70-1372-W. r ,1111..!>-'� „,51,''"' �I11iq'I!,I1ri , i,,,...,.-„,z-44. ( 1, 9 ,, ',,:'—., ,,,,e'-,-,,,//,'/,,,,,, ic, lib!, t i ext I i" ; I 1 ,,spr i ' Form No.IV.1.18.0 1111,, 704 SW 10th Street • P.O.Box 610 • Blue Springs,Missouri 64013-0610 U.S.A. Phone:816.229.3405 • www.fike.com , MOUNTING DETAILS-5,10,20&35 LB.(2L,4L,8.5L&15L)CONTAINERS Container Size Dimension 5 lb(21) 10 lb.(4L) 20 lb.(8.5L) 35 lb.(15L) IN(mm) IN(mm) IN(mm) IN(mm) A 12.3(313) 12.3(313) 16.3(414) 16.3(414) B 4.2(102) 4.2(102) 7.0(178) 7.0(178) C 5.7(145) 5.7(145) 8.2(209) 8.2(209) D 3.0(76) 3.0(76) 5.0(127) 5.0(127) E 2.5(63.5) 2.5(63.5) 3.0(76) 3.0(76) F 8.0(203) 8.0(203) 9.7(246) 9.7(246) G 1.8(46) 1.8(46) 3.6(91) 3.6(91) Mounting Position Upright(Valve Up) Upright(Valve Up) Upright-Horizontal Upright-Horizontal Notes: 1.)All dimensions are approximate 2.)When mounting the 20&35 Ib.(8.5L to 15L)containers in the horizontal position(wall mount or sub floor mount),the container valve"Pressure Gage" MUST point up.Failure to comply with this requirement will result in an incomplete discharge. Pressure Gauge Ir � I., * � i` C 4,14 + \ 1 ISI; A 0.375(9.53 mm) (Typ. 8 Places) 4k r' B t D 2 of 6 MOUNTING DETAILS—60 LB.(27L)CONTAINERS Dimension IN(mm) - Pressure Gaulle A 20.00(508) B 10.75(273) C 13.19(335) ,.. D 9.00(229) E 1.50(38) F 0.75(19) "E J. P, «.a �X G 3.50(89) -- H 4.88(124) Mounting Position Upright-Horizontal Notes: 1.)All dimensions ore approximate 2.)When mounting the 60 lb.(27L)container in the horizontal position(wall mount or sub-floor mount),the container valve"Pressure Gage"MUST point up.Failure to comply with this requirement will result in an incomplete discharge. ' * ` r 1 F C ► E 41— D 1 A 21,g-,,,,,,,,,:::,,,,-,i,,,,,,,,_,,,,- IIIII „ ' ''' IIII II t A II III I III ----f- 1 H ilk B F G 4 ►I 0.625 (16 mm) 3of6 i MOUNTING DETAILS—150 LB.(61L)CONTAINERS Dimension IN(mm) 17.125(435) A B 20.00(508) C 13.20(335) D 11.20(284) E 1.00(25) F 1.07(27) Mounting Position Upright Notes: 1.)All dimensions are approximate 2.)The 1i501b.container is equipped with a siphon tube and MUST be mounted in the upright(valve up)position.Failure to comply with this requirement will result in an incomplete discharge. t:P.&1, '',-,'.7.'t rot A . , -,....- ---.z.:,--- illi ..:1 :=1,_ spm I 0 1 A -. 4 C ► 4 B ► E 0 4 D ► . _mr F 0.625 (16 mm) 4of6 MOUNTING DETAILS—150i LB.(61L)CONTAINERS Dimension IN(mm) A 19.42(493) B 17.75(451) C 9.75(248) D 1.75(44) E 21.62(549) F 18.81(478) G 14.81(376) H 6.81(173) I 2.81(71) J 21.50(546) K 22.27(566) Mounting Position Inverted(Valve Down) Notes: 1.)All dimensions are approximate 2.)The 150i lb.container is NOT equipped with a siphon tube and MUST be mounted in the inverted(valve down)position.Failure to comply with this requirement will result in an incomplete discharge. X34 r. ( y, E G a _ H I e -� -0- -+- C 0.625(16 mm) (Typ 12 Places) B A 1 -®- A ,3-4,,,i J 45. A � K 5 of 6 MOUNTING DETAILS-100,215,375,650&1000 LB.(44,88,153,267,42311 CONTAINERS Dimension P/N Container Size Mounting Position A IN(mm) BIN(mm) 70-266 100 lb(44L) 20.00(508) 12.25(311) Upright(Valve Up) 70-268 215 lb(88L) 11.00(279) 21.75(552) Upright(Valve Up) 70-269 375 lb(153L) 24.00(610) 21.75(552) Upright(Valve Up) 70-270 650 lb(267L) 28.00(711) 26.00(661) Upright(Valve Up) 70-271 1000 lb(423L) 40.00(1016) 26.00(661) Upright(Valve Up) Notes: 1.)All dimensions are approximate 2.)Mounting Strap can be fastened to the Unistrut Channel with a Unistrut Spring Nut and Bolt. — _._._._._-_._._........,,.._,..... __..__. � i I NIS A I I A 0.625 (16 mm) Container I Mounting Strap v Floor P1000 Unistrut Channel B (by Others) 41 AMPE 'NEM - Wall .111 Unistrut Nut,Bolt&Washer (by Others) Copyright© Fike Corporation All Rights Reserved. 6 of 6 Form No. IV.1.18.01,August 2012.Specifications are subject to change without notice. like ° DATA SHEET AGENT STORAGE CONTAINERS WITH ECARO-25® ECARO-25 is also known by its ASHRAE designation HFC-125 n`•c' DESCRIPTION Fike Clean Agent Containers are used in fire extinguishing systems to store the Clean Agent until a fire develops t" and the agent must be released.The Clean Agent is retained in the container by a Impulse Valve assembly , ) which contains a fast-acting rupture disc.The disc will be ruptured,and the Clean Agent released,through the operation of an actuator by an electric signal that is automatically,manually or pneumatically controlled. Fike Clean Agent Containers have passed extensive testing by Factory Mutual and Underwriters Laboratory and are used in installations where 4 to 836 pounds(2.0 to 379.5 kg)of HFC-125 agent is required.Clean Agent ul containers can be filled in 1 pound(0.5 kg)increments to their maximum capacity. ;; SPECIFICATIONS Fill Range: 25 to 56 lbs/ft3 (400 to 897 kg/m3) Fill Increments: 1.0 lbs(0.5 kg) Container Super-Pressurization Level: 360 psig at 70°F(24.8 bar at 21°C)after filling with dry nitrogen APPROVALS: Container Storage Temperature Limitation: 32°F(0°C)-minimum,120°F(48.9°C)-maximum • UL Listed • ULC Listed Note:If container temperatures exceeding 120°F(48.0°C),valve will open automatically,this also fulfills the pressure relief • FM Approved valve requirements in accordance with DOT regulations. Container Construction: Carbon Steel Alloys Paint Options: Baked enamel finish white(default)or red Container Ratings: DOT 4BW500 TC 4BWM5341:0 4 Actuation Methods: Electric/Pneumatic/Manual o LISTED APPROVED 9 a ? til 77 i� t � i � f 4p h r ✓ � '-(1,//1/77 r + a s 3 1. Form No.IVf1.05.O1 3> .. f 704 SW 10th Street • P.O.Box 610 • Blue Springs,Missouri 64013-0610 U.S.A. Phone:816-229-340S • www.fike.com 1 CONTAINER DATA/SPECIFICATIONS Container Fill range Dimensions Valve Size Tare Weight (approximate) Mounting Size Minimum Maximum Diameter Height Position P/N Lb.(L) lbs.(kg) lbs.(kg) IN(mm) lbs.(kg) IN(mm) IN(mm) 5 70-272 4 4 1 11 4.2 16.2 Upright (2) (2.0) (2.0) (25) (5.0) (102) (411.5) (Valve Up) 10 70-273 4 8 1 15 4.2 27.24 Upright (4) (2.0) (3.5) (25) (6.8) (102) (691.9) (Valve Up) 20 70-263 8 16 1 22 7.0 22.50 Upright- (8.5) (3.5) (7.5) (25) (10.0) (178) (571.5) Horizontal 35 14 30 1 32.5 7.0 33.75 Upright- (15) 70-264 (6.5) (13.5) (25) (14.7) (178) (857.3) Horizontal 60 70-265 25 54 1 52.5 10.75 28.13 Upright- (27) (11.5) (24.5) (25) (23.8) (273) (714.4) Horizontal 100 70-266 39 87 1 77 10.75 39.63 Upright (44) (18.0) (39.0) (25) (34.9) (273) (1006.5) (Valve Up) 150/150i 70 267 54 120 3 118/114 20.0 24.25 Upright/Inverted (61) (24.5) (54.5) (80) (53.5/51.7) (508) (616.0) 215 70-268 78 173 3 146 20.0 30.13 Upright (88) (35.5) (78.5) (80) (66.2) (508) (765.2) (Valve Up) 375 70-269 136 302 3 213 20.0 43.38 Upright (153) (61.5) (137.0) (80) (96.6) (508) (1101.7) (Valve Up) 650 70-270 236 528 3 373 24.0 50.50 Upright (267) (107.0) (239.5) (80) (169.2) (610) (1282.7) (Valve Up) 1000 70-271 374 836 3 535 24.0 71.88 Upright (423) (169.5) (379.5) (80) (242.7) (610) (1825.6) (Valve Up) 2 of 7 ITEMS SUPPLIED WITH CONTAINER ASSEMBLY Item Number Description Data Sheet 1 Victaulic Coupling&Nipple IV.1.19.01 Item'I ► �a a 2 Impulse Valve IV.1.14.01 Item 2 ► � 3 Pressure Gauge Iv.1.13.01 Item 3 M,_ Item 4 4 Liquid Level Indicator(LLi) C.1.40.01 Item 5 5 LLi Boss(see note 1) n/a 6 Nameplate(see note 2) n/a 7 Siphone Tube(see note 3) n/a 8 Mounting Straps&Brackets IV.1.18.01 Item 6 ► Notes: 1)100 thru 1000 lb.(44 thru 423 L)containers are equipped with a LLi Boss. 2)Fike nameplate provides the information that is specific to each container:Assembly and serial number of the container,weight information:tare,gross and agent and Item 7 Item 4 installation,operation and safety information.All containers filled either by the factory or by an Approved Initial Fill Station are provided with a name plate bearing the UL& FM markings. 1i 3)Fike Clean Agent containers[except the 150i(Inverted)]are equipped with a siphon _ tube. The 20,35&60 lb.containers have bent siphon tubes and the 5,10 and 100— 1000 lb.containers have straight siphon tubes. All containers with siphon tubes can be mounted upright. The 20,35&60 lb containers can also be mounted horizontally.The wt 150 container can only be mounted upright and the 150i can only be mounted inverted. 4, P tor" 44.Pe-sfp 1`4447 Item 8 C grfo 3 of 7 OPTIONAL ITEMS FOR CONTAINER The following container accessory items must be ordered separately. ACTUATION COMPONENTS • Electric/Manual Actuation—Impulse Valve Operator(IVO)(For detailed information,refer to the IVO Data Sheet IV.1.09.01) Impulse Valve Operator 2 (IVO) fit_ _ wmo Container w/Impulse Valve m • Pneumatic Actuation—Impulse Valve Pneumatic Operator(IVPO)(For detailed information,refer to the IVPO Data Sheet IV.1.10.01) 11 I kri Container w/Impulse Valve Impulse Valve Pneumatic Operator(IVPO) ACTUATION METHODS Clean Agent containers with an Impulse Valve can be actuated by the following methods: • Method 1—Electric Actuation—Single Container System w/IVO&IRM • Method 2—Electric Actuation—Multi-Containers System w/IVO&IRM • Method 3—Electric&Pneumatic Actuation:Two Container System w/IVO&IVPO • Method 4—Electric&Pneumatic Actuation—Multi Container System w/IVO&IVPO For detailed information on actuation methods,refer to the Impulse Valve Operator(IVO)data sheet IV.1.09.01. These devices provide the force required to extend a pin that will open the rupture disc,allowing the agent to be released from the container. 4 of 7 LOW PRESSURE SWITCH The Low Pressure Switch provides a means to continuously monitoring the container pressure for a low-pressure condition. If the pressure inside the container drops below 288 psig(1986 kPa),the switch contacts will transfer and invoke a"trouble"indication on the control panel. The Low Pressure Switch(P/N 02-12533)has a single pole,double-throw switch that can be wired for normally open or normally closed. For detailed information,refer to the Low Pressure Switch Data Sheet IV.1.13.01. INSTALLATION The system installation must comply with the requirements of this manual;NFPA 2001,latest edition;all applicable local codes, regulations,and standards and the authority having jurisdiction(AHJ). Warning:DO NOT start system installation until the final design of the total system has been verified using Fike's Engineered Flow Calculation. Warning:The Actuator shall always be the last component installed on a Fike Clean Agent Fire Suppression system to avoid accidental discharge. Factors to Consider-Container Location Mounting Surface: Container brackets must be mounted securely to solid load-bearing surfaces that will support the container load.Some installations may require additional mounting support not supplied by Fike. Environmental Effects: Container(s)should be located in clean,dry,and relatively vibration-free areas. Avoid aisle ways and other high traffic areas where physical damage or tampering is more likely.Container(s)should never be mounted where the container could potentially be splashed with,or submerged in any liquid.Do not locate containers where they would be subject to physical damage,exposure to corrosive chemicals,or harsh weather conditions. Temperature Range: Container locations must be between 32 to 120°F(0 to 48.9°C).Temperatures outside of this range may result in the system not supplying the desired quantity of agent or accidental discharge. Serviceability: In general,the larger the container,the more difficult it will be to remove it from the system for maintenance and service.However,smaller containers that are located in a sub-floor space,under a computer bank,or above the ceiling over the same computer bank can be difficult as well. Floor Space: Consideration should be given to the space available to install the container(s).For example,a 900 lb. (408 kg)system could be stored in(2)650 lb.(267 L)containers located on the floor. However,if floor space is a problem,the system could be designed to utilize(6)150i lb.(61 L)Inverted Containers mounted on the wall(s). Floor Loading: Floor loading must be considered when selecting a container location.The floor must be able to support the total weight of the Fike container(s)as they are moved into position. Consult raised floor manufacturer for floor loading limitation.The following guidelines are recommended: •Raised floor loading is a function of the manufacturer's load specification and the positioning of the container(s)on the raised floor grid. Note: Fike cannot assume responsibility for determining the suitability of a particular raised floor system;the following does provide information to help determine installation requirements. •When clean agent containers are located on a raised floor,floor integrity must be considered to determine if the type of tile and vertical floor support can handle the increased load. If necessary additional floor supports can be added. Option:To help distribute the container weight over a greater area,a''%"steel plate can be placed under the container(s),sized to span multiple floor supports. If container spans multiple floor tiles,add additional floor supports(Minimum of 4 floor supports,1 per corner,must be used). Excessive floor loading may require relocating the container(s)to a more suitable location.For floor loading information refer to the table on page 6 or to Fike's ECARO-25 Flow Calculation program for container size and actual fill weight being supplied. 5 of 7 Container Floor Area Total Container w/Plate Container w/Plate Container Floor Container Size Weight Container Floor Area Loading 1/4:x 2'x 2'plate Floor Loading lb.(L) lbs.(kg) ft'(m2) (6.4mm x 0.6m x lbs/ft'(kg/m2) 2 see note 1 lbs ft (kg/m') 0.6m plate) see note 2 ft'(m2) 1000(423) 1386(628) 3.14(0.29) 441(2166) 4.0(0.36) 352(1773) 650(267) 913(41) 3.14(0.29) 291(1431) 4.0(0.36) 234(1181) 375(153) 527(239) 2.18(0.20) 242(1195) 4.0(0.36) 137(692) 215(88) 328(148) 2.18(0.20) 150(740) 4.0(0.36) 88(439) 150(61) 283(128) 2.18(0.20) 130(640) 4.0(0.36) 76(384) 100(44) 164(74) 0.63(0.06) 260(1233) 4.0(0.36) 47(234) 60(27) 106(48) 0.63(0.06) 168(800) 4.0(0.36) 32(162) 35(15) 51(23) 0:27(0.03) 189(927) 4.0(0.36) 18(92) 20(8.5) 37(17) 0.27(0.03) 137(685) 4.0(0.36) 15(76) 10(4) 23(11) 0.10(0.009) 230(1222) 4.0(0.36) 11(59) 5(2) 15(7) 0.10(0.009) 150(778) 4.0(0.36) 9(48) Notes: 1)Total container weight is based on container tare weight+maximum fill weight 2)Total container weight+22.5 lbs(10.2 kg)added for 1/4"x 2'x 2'(6.4mm x 0.6m x 0.6m)plate used to calculate container with plate floor loading 6 of 7 RECHARGE ITEMS-1 IN(25)&3 IN(80)VALVE(Must Order Separate) After a system has been discharged,the following items must be replaced before a container can be recharged. For a detailed procedure . on recharging a Fike container with an Impulse Valve refer to Fike's Recharge Manual(p/n 06-290). 1 IN(25mm)Recharge Kit 3 IN(80mm)Recharge Kit (P/N 85-047)includes the (P/N 85-048 includes the Item Description following: following: Part Number Part Number 1 Friction Ring 70-2060 70-2063 2 Disc Assembly 70-247 70-248 3 0-Ring 02-11987 02-11989 4 Valve Core-Fill Port(not shown) 02-4161 02-4161 5 Reconditioning Instructions(not shown) 06-567 Note: 1 IN Recharge Kit is used on 5,10,20,35,60&100/b.(2,4,8,15,27&44 L)containers 3 IN Recharge Kit is used on 150,150i,215,375,650&1000/b.(61,61i,88,153,267&423 L)containers -iii, " ---5 Cz:zzlz000ei Item 1-Friction Ring ::.:,...,,___ 41 Item 2—Disc Assembly44131* CD1 Item 3—0-Ring °CD 4 (//„.•14-':ilW is i r 1 trifr'''''N,74:47,i4ittet...0 iiit4,fillv-7-....,41440:: € , y, Copyright© Fike Corporation All Rights Reserved. 7 of 7 Form No. IV.1.05.01-3,February 2012.Specifications are subject to change without notice. 0 DATA SHEET HFC-125 CLEAN AGENT APPROVALS: • UL Listed • ULC Listed DESCRIPTION • FM Approved HFC-125 fire suppression agent is an environmentally acceptable replacement for Halon 1301.HFC-125 has a zero ozone depleting potential,a low global warming potential,and a short atmospheric lifetime. It is particularly useful where an environmentally acceptable agent is essential,where clean-up of other media presents a problem,where weight versus suppression potential is a factor,where an electrically non- conductive medium is needed,and where people compatibility is an overriding factor.HFC-125 can be used to protect a wide range of applications from sensitive electrical equipment to industrial applications.Consult the1111) current NFPA Standard 2001 and/or ISO 14520 for specific applications.HFC-125 fire suppression agent is used with Fike's total flooding systems. LISTED FEATURES AND BENEFITS • Colorless,odorless,compressed gas • Stored as a liquid 4X:* • Electrically non-conductive APPROVED • Discharges as a gaseous vapor(due to its relatively low boiling point) • Zero ozone depleting potential• Low global warming potential • Leaves no residue • Included on the U.S.EPA Significant New Alternative Policy(SNAP)rules l i�iih6�h hM�i EXTINGUISHING METHOD-HFC-125 HFC-125 extinguishes a fire primarily through Heat Absorption that occurs as the agent changes from a liquid to a vapor during discharge. In addition,HFC-125 also disrupts the combustion reaction which aids in the extinguishment of a fire. It is important to note,HFC-125 does not use the depletion of oxygen to extinguish a fire. USE AND LIMITATIONS—HFC-125 HFC-125 system shall be used on the following Class of Hazards: Class A&C: Electrical and Electronic Hazards Telecommunications Facilities High value assets,where the associated down-time would be costly Class B: Flammable liquids and gases HFC-125 systems shall"NOT"be used on fires involving the following materials: Chemicals or mixtures of chemicals that are capable of rapid oxidation in the absence of air. (Examples include:Cellulose Nitrate and Gunpowder Reactive metals such as Lithium,Sodium,Potassium,Magnesium,Titanium, Zirconium,Uranium,and Plutonium) Metal hydrides such as Sodium Hydride and Lithium Aluminum Hydride Chemicals capable of undergoing auto-thermal decomposition. (Examples:Organic Peroxides and Hydrazine) EXPOSURE LIMITATIONS Maximum Human Expose �i � Hazard Type Design Concentration Time �1 Normally Occupied Space 8.0%to 11.5% 5 minutes Normally Un-Occupied Space 12.0%to 13.5% 30 seconds hl Note:Fike does not recommend HFC-125 systems to be used in any normally occupied spaces where the design concentration 11, �� � e ° required is above 11.5% r b Warning:The discharge of clean agent systems to extinguish a fire can result in potential hazard to personnel from the 1' i 11) natural form of the clean agent or from the products of combustion that result from exposure of the agent to the fire or [,li hot surfaces.Unnecessary exposure of personnel either to the natural agent or to the products of decomposition shall be avoided. Form No. IV.1.06.01-1 704 SW 10th Street • P.O.Box 610 • Blue Springs,Missouri 64013-0610 U.S.A. Phone:816.229.3405 • www.fike.com PHYSICAL PROPERTIES Chemical Name/Formula Pentafluoroethane/CHF2CF, ASHRAE Designation HFC-125 Trade Name: FE-25r"(DuPont") CAS Number 354-33-6 Molecular Weight 120.02 Vapor Density @ 25°C(77°F)and atm,kg/m'(Ib/ft') 4.982 m=(0.3111) Vapor Pressure,Saturated @ 25°C(77°F),bar(psia) 13 bar(200.4) Boiling Point,1 atm,°C(°F) -48.14(-54.7) Freezing Point,°C(°F) -103(-153) Solubility in Water in FE-25 @ 25°C(77°F),ppm 700 Critical Temperature,°C(°F) 66.25(151.25) Critical Pressure,bar(psia) 36(526.6) Critical Volume,cc/mole 210 Critical Density,kg/m'(Ib/ft') 571.9(35.70) Specific Heat,Liquid(CP)@ 25°C(77°F),KJ/Kg-°C(Btu/Ib°F) 1.37(0.327) Specific Heat,Vapor(CP)@ 25°C(77°F)KJ/Kg-°C(Btu/Ib°F)and 1 atm 0.809(0.193) Heat of Vaporization @ Boiling Point KJ/Kg(Btu/lb) 164.4(70.7) Thermal Conductivity,Liquid @ 25°C(77°F),W/m-°C(Btu/hr-ft°F) 0.0652(0.0377) Thermal Conductivity,Vapor @ 25°C(77°F),W/m-°C(Btu/hr-ft°F) 0.0166(0.0096) Viscosity,Liquid @ 25°C(77°F),cP(Ib/ft-hr) 0.137 Viscosity,Vapor @ 25°C(77°F),cP(lb/ft-hr) 0.013 Ozone Depletion Potential 0 Global Warming Potential(based on a 100-yr horizon relative to CO2) 2800 Inhalation Exposure Limit(AEL-8 and 12hr.TWA),ppm 1000 Copyright© Fike Corporation All Rights Reserved. 2 of 2 Form No. IV.1.06.01-1,August 2012.Specifications are subject to change without notice. Fike ° DATA SHEET HFC-125 INSTRUCTIONAL SIGNS APPROVALS: • UL Listed • ULC Listed • FM Approved DESCRIPTION Instructional signs are used to provide the necessary information to personnel in the area and to comply with NFPA 2001 requirements.The caution lettering and backgrounds meet the requirements of ANSI Z535.The sign are made from flame retardant,Lexan'"" CIO 030 polycarbonate material.Each sign has an adhesive backing mounting purposes.These signs are an optional item and must be ordered separately. LISTED APPROVED CAUTION-AREA PROTECTED BY HFC-125(P/N 02-10314) Provided to alert personnel that the room is protected with an ECARO-25®system and A C A U T I O N that they should not enter the area during or after discharge. THIS AREA IS PROTECTED BY A The sign also indicates the requirement that all doors serving the protected area must be HFC-125 EXTINGUISHING SYSTEM kept closed at all times. DO NOT ENTER AREA DURING The sign is 13.0 IN(330 mm)x 10.0 IN(254 mm),with black lettering on a yellow OR AFTER DISCHARGE background for Caution and black lettering on a white background for Sign text. KEEP DOOR CLOSED AT ALL TIMES CAUTION-IF ACTIVE,DO NOT ENTER(P/N 02-10313) Provided to alert personnel that the room is protected with an ECARO-25 system and to A C A U T I O N evacuate the area when the alarms sound. This sign is provided to alert personnel that the room is protected with an ECARO-25 HFC-125 EXTINGUISHING system and that they should not enter the area when the alarm sounds. SYSTEM DISCHARGE ALARM The sign is 9.0 IN(229 mm)x 6.0 IN(154 mm),with black lettering on a yellow background IF ACTIVE for Caution and black lettering on a white background for Sign text. DO NOT ENTER AREA CAUTION-IF ACTIVE,EXIT AREA(P/N P02-10309) •'� provided to explain the presence of notification devices that are located inside the ACAUTION protected space. This sign explains that the ECARO-25 system will soon be discharged if the strobe light HFC-125 EXTINGUISHING is flashing,and appropriate actions should be taken. This sign should be placed at each SYSTEM ALARM strobe light location. IF ACTIVE The sign is 9.0 IN(229 mm)x 6.0 IN(154 mm),with black lettering on a yellow background EXIT AREA IMMEDIATELY for Caution and black lettering on a white background for Sign text. Form No. IV.1.08.01-1- 704 SW 10th Street • P.O.Box 610 • Blue Springs,Missouri 64013-0610 U.S.A. Phone:816.229.3405 • www.fike.com SYSTEM RELEASE(P/N 02-10312) Provided to identify each system release station associated with the ECARO-25 system. HFC-125 This reduces the risk of a manual discharge station being mistaken for a fire alarm pull station. EXTINGUISHING This sign should be placed at each manual release station location for positive identification. SYSTEM RELEASE This sign is 4.0 IN(102 mm)x 2.25 IN(57 mm),with black lettering on a white background. 02-10312-N/C MAIN/RESERVE(P/N 02-10311) 1 Provided to identify each system main/reserve station associated with the ECARO-25 system. HFC-125 This sign clearly identifies the purpose of the switch. EXTINGUISHING This sign should be placed at each main/reserve station location for positive identification. SYSTEM MAIN/RESERVE This sign is 4.0 IN(102 mm)x 2.25 IN(57 mm),with black lettering on a white background. 02-10311-MC SYSTEM ABORT(P/N 02-10310) Provided to identify each system abort station associated with the ECARO-25 system. HFC-125 This reduces the risk of an abort station being mistaken for a manual release or fire alarm pull EXTINGUISHING station. SYSTEM ABORT This sign should be placed at each abort station location for positive identification. PUSH AND HOLD The sign is 4.0 IN(102 mm)x 2.25 IN(57 mm). 02-10310-N/C Copyright© Fike Corporation All Rights Reserved. 2 of 2 Form No. IV.1.08.01-1,August 2012.Specifications are subject to change without notice. Material Safety Data Sheet au PONT a DuPontT'" FE-259 fire extinguishing agent Version 2.0 Revision Date 10/22/2010 Ref. 130000000363 This SDS adheres to the standards and regulatory requirements of the United States and may not meet the regulatory requirements in other countries. SECTION 1. PRODUCT AND COMPANY IDENTIFICATION Product name : DuPont— FE-25®fire extinguishing agent MSDS Number : 130000000363 Product Use : Fire extinguishing agent Manufacturer : DuPont 1007 Market Street Wilmington, DE 19898 Product Information : 1-302-774-1000 Medical Emergency : 1-800-441-3637 (outside the U.S. 1-302-774-1139) Transport Emergency : CHEMTREC: 1-800-424-9300 (outside the U.S. 1-703-527-3887) SECTION 2. HAZARDS IDENTIFICATION Emergency Overview Rapid evaporation of the liquid may cause frostbite. Potential Health Effects Skin Pentafluoroethane : Contact with liquid or refrigerated gas can cause cold burns and frostbite. Eyes Pentafluoroethane : Contact with liquid or refrigerated gas can cause cold burns and frostbite. Inhalation Pentafluoroethane : May cause: Central nervous system depression, Anaesthetic effects, dizziness, confusion, incoordination, drowsiness, or unconsciousness, irregular heartbeat with a strange sensation in the chest, heart thumping, apprehension, feeling of fainting, dizziness or weakness. Vapours are heavier than air and can cause suffocation by reducing oxygen available for breathing. Carcinogenicity 1 /7 Material Safety Data Sheet ali P NT, DuPontTM FE-2e fire extinguishing agent Version 2.0 Revision Date 10/22/2010 Ref. 130000000363 None of the components present in this material at concentrations equal to or greater than 0.1%are listed by IARC, NTP, or OSHA, as a carcinogen. SECTION 3. COMPOSITION/INFORMATION ON INGREDIENTS Component CAS-No. Concentration Pentafluoroethane 354-33-6 100% SECTION 4. FIRST AID MEASURES Skin contact : Take off all contaminated clothing immediately. Flush area with lukewarm water. Do not use hot water. If frostbite has occurred, call a physician. Eye contact : In case of eye contact Hold eyelids apart and flush eyes with plenty of water for at least 15 minutes. Get medical attention. Inhalation : Remove from exposure, lie down. Move to fresh air. Keep patient warm and at rest. Artificial respiration and/or oxygen may be necessary. Consult a physician. Ingestion : Is not considered a potential route of exposure. General advice : Never give anything by mouth to an unconscious person. When symptoms persist or in all cases of doubt seek medical advice. Notes to physician : Because of possible disturbances of cardiac rhythm, catecholamine drugs, such as epinephrine, that may be used in situations of emergency life support should be used with special caution. 2/7 111, , Material Safety Data Sheet GU NT, DuPontTM FE-25° fire extinguishing agent Version 2.0 Revision Date 10/22/2010 Ref. 130000000363 SECTION 5. FIRE-FIGHTING MEASURES Flammable Properties Flash point : does not flash Lower explosion limit : Method : None per ASTM E681 Upper explosion limit : Method : None per ASTM E681 Fire and Explosion Hazard : pressure build-up Hazardous thermal decomposition products: Carbon oxides Hydrogen fluoride Carbonyl fluoride Fluorocarbons - Firefighting Instructions : In the event of fire, wear self-contained breathing apparatus. Wear neoprene gloves during cleaning up work after a fire. Use extinguishing measures that are appropriate to local circumstances and the surrounding environment. Cool containers/tanks with water spray. SECTION 6. ACCIDENTAL RELEASE MEASURES NOTE: Review FIRE FIGHTING MEASURES and HANDLING (PERSONNEL) sections before proceeding with clean- up. Use appropriate PERSONAL PROTECTIVE EQUIPMENT during clean-up. Safeguards (Personnel) : Evacuate personnel to safe areas. Ventilate the area. Refer to protective measures listed in sections 7 and 8. Spill Cleanup : Evaporates. Accidental Release Measures : Should not be released into the environment. SECTION 7. HANDLING AND STORAGE Handling (Personnel) : Avoid breathing vapours or mist. Avoid contact with skin, eyes and clothing. Provide sufficient air exchange and/or exhaust in work rooms. For personal 3/7 Material Safety Data Sheet DuPontTM FE-25`x'fire extinguishing agent Version 2.0 Revision Date 10/22/2010 Ref. 130000000363 protection see section 8. Handle in accordance with good industrial hygiene and safety practice. Handling (Physical Aspects) : No special protective measures against fire required. Storage : Valve protection caps and valve cutlet threaded plugs must remain in place unless container is secured with valve outlet piped to use point. Do not drag, slide or roll cylinders. Never attempt to lift cylinder by its cap. Use a check valve or trap in the discharge line to prevent hazardous back flow into the cylinder. Cylinders should be stored upright and firmly secured to prevent falling or being knocked over. Separate full containers from empty containers. Keep at temperature not exceeding 52°C. Do not store near combustible materials. Keep container tightly closed in a dry and well-ventilated place. Store in original container. Protect from contamination. Storage temperature : <52 °C (< 126 °F) SECTION 8. EXPOSURE CONTROLS/PERSONAL PROTECTION Engineering controls : Ensure adequate ventilation, especially in confined areas. Local exhaust should be used when large amounts are released. Personal protective equipment Respiratory protection : For rescue and maintenance work in storage tanks use self-contained breathing apparatus. Vapours are heavier than air and can cause suffocation by reducing oxygen available for breathing. Hand protection : Additional protection: Impervious gloves Eye protection : Safety glasses with side-shields Additionally wear a face shield where the possibility exists for face contact due to splashing, spraying or airborne contact with this material. Wear safety glasses or coverall chemical splash goggles. Protective measures : Self-contained breathing apparatus (SCBA) is required if a large release occurs. Exposure Guidelines Exposure Limit Values Pentafluoroethane AEL* (DUPONT) 1,000 ppm 8& 12 hr. TWA 4/7 Material Safety Data Sheet PNT DuPonte" FE-256 fire extinguishing agent Version 2.0 Revision Date 10/22/2010 Ref. 130000000363 AEL is DuPont's Acceptable Exposure Limit. Where governmentally imposed occupational exposure limits which are lower than the AEL are in effect, such limits shall take precedence. SECTION 9. PHYSICAL AND CHEMICAL PROPERTIES Form : Liquefied gas Color : colourless Odor : ether-like Boiling point : -48.1 °C (-54.6 °F) at 1,013 hPa %Volatile : 100% Vapour Pressure : 13,779 hPa at 25 °C (77 °F) Density : 1.22 g/cm3 at 20 °C (68 °F) (as liquid) Water solubility : 0.9 g/I at 25 °C (77 °F) at 1,013 hPa Vapour density : 4.2 (Air= 1.0) SECTION 10. STABILITY AND REACTIVITY Stability : Stable under recommended storage conditions. Conditions to avoid : The product is not flammable in air under ambient conditions of temperature and pressure.When pressurised with air or oxygen, the mixture may become flammable. Certain mixtures of HCFCs or HFCs with chlorine may become flammable or reactive under certain conditions. Incompatibility : Alkali metals Alkaline earth metals, Powdered metals, Powdered metal salts Hazardous decomposition : Hazardous thermal decomposition products: Carbon oxides, Hydrogen products fluoride, Carbonyl fluoride, Fluorocarbons SECTION 11.TOXICOLOGICAL INFORMATION DuPontFE-25®fire extinguishing agent Carcinogenicity : Animal testing did not show any carcinogenic effects. Reproductive toxicity : Did not show mutagenic or teratogenic effects in animal experiments. 5/7 Material Safety Data Sheet a IJ DuPont'M FE-25®fire extinguishing agent Version 2.0 Revision Date 10/22/2010 Ref. 130000000363 Further information : Cardiac sensitisation threshold limit : >245400 mg/m3 Anaesthetic effects threshold limit : 490800 mg/m3 Rapid evaporation of the liquid may cause frostbite. Pentafluoroethane Inhalation 4 h LC50 : 800000 ppm , rat Cardiac sensitization Repeated dose toxicity : Inhalation rat No toxicologically significant effects were found. Mutagenicity : Did not cause genetic damage in animals. Did not cause genetic damage in cultured mammalian cells. Did not cause genetic damage in cultured bacterial cells. Teratogenicity : Animal testing showed no developmental toxicity. • SECTION 12. ECOLOGICAL INFORMATION SECTION 13. DISPOSAL CONSIDERATIONS Waste Disposal : Recover by distillation or remove to a permitted waste disposal facility. Comply with applicable Federal, State/Provincial and Local Regulations. Environmental Hazards : Empty pressure vessels should be returned to the supplier. SECTION 14. TRANSPORT INFORMATION DOT UN number : 3220 Proper shipping name : Pentafluoroethane Class : 2.2 Labelling No. : 2.2 IATA_C UN number : 3220 6`/7 ' Material Safety Data Sheet T DuPontTM FE-259 fire extinguishing agent Version 2.0 Revision Date 10/22/2010 Ref. 130000000363 Proper shipping name : Pentafluoroethane Class : 2.2 Labelling No. : 2.2 IMDG UN number : 3220 Proper shipping name : Pentafluoroethane Class : 2.2 Labelling No. : 2.2 SECTION 15. REGULATORY INFORMATION California Prop. 65 : Chemicals known to the State of California to cause cancer, birth defects or any other harm: none known SECTION 16. OTHER INFORMATION Before use read DuPont's safety information. For further information contact the local DuPont office or DuPont's nominated distributors. ®DuPont's registered trademark The information provided in this Safety Data Sheet is correct to the best of our knowledge, information and belief at the date of its publication. The information given is designed only as a guidance for safe handling, use, processing, storage,transportation, disposal and release and is not to be considered a warranty or quality specification. The information relates only to the specific material designated and may not be valid for such material used in combination with any other materials or in any process, unless specified in the text. Significant change from previous version is denoted with a double bar. 7/7 • r ECARO-25 Flow Calculation Software Fike Corporation Flic ® ECARD 25 ECARO-25 Flow Calculation Software Version 4.16.0000 Copyright© 2002-2014 Fike Corporation UL Ex4623, FM 3034180 Licensed to schnzrm, NW Fire Suppression Results Printed on 4/2/2015 PROJECT INFORMATION Project Name: Cypress Expansion #417 Server Room 402 Project Designer: M. Schaenzer Project Location: Project Account: 15018 Project Description: Project Filename: 0:\2015\15018 Cypress Semiconductor\NWFS Design\ECARO Calcs\Cypress Semiconducter Server Rm 402 (2 Nozzles).125 CUSTOMER INFORMATION Company Name: Cypress Semiconductor Company Address: 3 Lincoln 10220 SW Greenburg Rd. Tigard, Oregon Company Phone: Company Fax: Contact Information: • Cypress Semiconducter Server Rm 402 (2 Nozzles).125 Page 1 ECARO-25 Flow Calculation Software Fike Corporation Agent Requirements- Enclosure 0001 (Server Room 402) Enclosure Area Enclosure Volume Added Volume Protected Volume Height Subtracted 22.00 ft L X 16.67 ft W 8.50 ft None None 3117.29 ft3 Design Maximum Minimum Maximum Elevation Agent Required Concentration Concentration Temperature Temperature 9.30% 9.31%at70°F 70°F 70°F Oft 101.0 lbs Nozzle Information - Pipe Network 0001 (Pipe Network 0001) Nozzle Number Type Enclosure Name Requested Agent 0101 180° Server Room 402 50.5 lbs 0102 180° Server Room 402 50.5 lbs Total Agent Distributed Through Pipe Network: 101.0 lbs Cylinder Information - Pipe Network 0001 (Pipe Network 0001) Cylinder Type Agent Per Manifold Type Cylinder Valve to Cylinder to Cylinder Spacing Manifold Exit 70-267 150 lb Upright 1 X 101 lbs No Manifold - - - Fill Density Empty Weight Floor Area Floor Loading 46.9 lbs/ft3 118 lbs 2.18 ft2 100 lbs/ft2 Cypress Semiconducter Server Rm 402 (2 Nozzles).125 Page 2 ECARO-25 Flow Calculation Software Fike Corporation Pipe Network Isometric 4W 101 102 4111 9 3 , • rll."19 1 150 lb Upright (101.0 lbs) Cypress Semiconducter Server Rm 402 (2 Nozzles).125 Page 3 ECARO-25 Flow Calculation Software Fike Corporation Flow Calculation Input Data - Pipe Network 0001 (Pipe Network 0001) Start End Length Elevation Select Select y0" Thru Side Union Equ C,i Nozz Select Select Pipe Dia Plpe Sch Length Type Agent Orifice 1 2 2.02 ft 2.02 ft 3 in SCH 40 T 28.88 ft 1 2 3 1.00 ft 1.00 ft 3/4 in SCH 40 T 3 4 4.75 ft 4.00 ft 3/4 in SCH 40 T 2 4 101 3.25 ft 1.25 ft 3/4 in SCH 40 T 2 1 180 50.5 lbs 0.2340 in 4 102 3.25 ft 1.25 ft 3/4 in SCH 40 T 2 1 180 50.5 lbs 0.2340 in Cypress Semiconducter Server Rm 402 (2 Nozzles).125 Page 4 ECARO-25 Flow Calculation Software Fike Corporation Flow Calculation Output Data - Pipe Network 0001 (Pipe Network 0001) Start End Pipe Type Equ Length Start Pressure End Pressure Flow Rate Agent Discharged Orifice Diameter 1 2 3 -SCH 40 30.90 ft 268 psia 267 psia 10.1 lbs/s 2 3 3/4-SCH 40 1.00 ft 267 psia 251 psia 10.1 lbs/s 3 4 3/4-SCH 40 8.87 ft 251 psia 197 psia 10.1 lbs/s 4 101 3/4-SCH 40 11.49 ft 197 psia 182 psia 5.0 lbs/s 50.5 lbs 0.2340 in 4 102 3/4-SCH 40 11.49 ft 197 psia 182 psia 5.0 lbs/s 50.5 lbs 0.2340 in Flow Calculation Messages ECARO-25 Flow Calculation Software Version 4.16.0000 Calculation based on fixed nozzle codes and pipe sizes. System calculated within limits of Fikes UL listing and FM approval Calculation performed on 4/2/2015 7:50:57 AM Cypress Semiconducter Server Rm 402 (2 Nozzles).125 Page 5 ECARO-25 Flow Calculation Software Fike Corporation Bill of Materials- Pipe Network 0001 (Pipe Network 0001) Cylinder List Qty Part Number Cylinder Description Agent Fill Amount 1 70-267 150 lb Upright 101 lbs Nozzle List Num Part Number Nozzle Size Nozzle Type Drill Diameter 101 80-086-2340 3/4-SCH 40 180° 0.2340 in 102 80-086-2340 3/4-SCH 40 180° 0.2340 in Pipe List Qty Pipe Description 5 1.00 ft, 3/4-SCH 40 1 4.00 ft, 3/4-SCH 40 1 0.75 ft, 3/4-SCH 40 2 1.25 ft, 3/4-SCH 40 t Fitting List Qty Fitting Description 6 90°Elbow, 3/4-SCH 40 1 Bullhead Tee, 3/4-SCH 40 Cypress Semiconducter Server Rm 402(2 Nozzles).125 Page 6 ti • ECARO-25 Flow Calculation Software Fike Corporation System Acceptance Report Pipe Network Discharge Time Pipe Network Discharge %Agent in Pipe Pipe Time Network Temperature 0001 -Pipe Network 0001 9.52 s 9.30% 70°F Enclosure 0001 (Server Room 402) - Nozzle Performance Nozzle Number Orifice Diameter Agent Requested Agent Predicted Nozzle Pressure 101 0.2340 in 50.5 lbs 50.5 lbs 182 psia 102 0.2340 in 50.5 lbs 50.5 lbs 182 psia Minimum Required Minimum Predicted Maximum Predicted Concentration Design Concentration Concentration Concentration 9.30% 9.30% 9.31%at 70°F 9.31%at 70°F t r Cypress Semiconducter Server Rm 402 (2 Nozzles).125 Page 7 ECARO-25 Flow Calculation Software Fike Corporation Leakage Area vs. Enclosure Pressure Legend Agent Conc. =9.31% A Positive Pressure -- Time, Discharge =9.52 secs uNegative Pressure 170- 160 150 140 130 120 110 100 - U) < 90 U) U) 80 co 70 GO 50 40 30 20 10 1 2 3 4 5 6 7 8 9 10 Enclosure Pressure (psf) a Cypress Semiconducter Server Rm 402 (2 Nozzles).125 Page 8